Subido por joseleerambo

A029U889 I2 201001

Anuncio
Service Manual
Generator Set
X1.3 & X2.5 Engine with PowerStart 0500 Control
C8D5
C11D5
C17D5
C17D5 (Spec E)
C22D5
C22D5 (Spec E)
C28D5
C28D5 (Spec E)
C12D6
C12D6 (Spec E)
C16D6
C16D6 (Spec E)
C20D6
C20D6 (Spec E)
English
Original Instructions
08-2017
A029U889 (Issue 3)
PowerStart 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
Table of Contents
SECTION
TITLE
PAGE
1
IMPORTANT SAFETY INSTRUCTIONS
5
2
INTRODUCTION
7
2.1
About this Manual
7
2.2
System Overview
7
2.3
Test Equipment
7
2.4
How to Obtain Service
7
CONTROL PANEL OPERATION
8
3.1
General
8
3.2
Alternator Connections
9
3.3
Control Operation
11
3.4
Control Panel
12
3.5
Mode of Operation
14
CIRCUIT BOARD
19
Control Input and Outputs
21
5
TROUBLESHOOTING
24
5.1
Safety Considerations
24
5.2
Troubleshooting Procedure
24
6
Setup and Calibration
34
7
SERVICING THE GENERATOR
39
7.1
Testing the Generator
39
7.2
Generator Baseboard Isolation Procedure
40
7.3
Excitor Stator
41
7.4
Excitor Rectifier Bridge
42
7.5
Main Stator
45
7.6
Generator Disassembly
47
8
WITHDRAWING ROTOR
49
8.1
Generator Reassembly
49
3
4
4.1
page 3
PowerStart 0500
X1.3 & X2.5 Engine
SECTION
TITLE
Publication A029U889
Issue 3 - 8-2017
PAGE
9
WIRING DIAGRAMS
53
9.1
General Information
53
9.2
Wiring Diagram
57
9.3
Battery Charger and Coolant Heater
59
9.4
Customer Connections
62
page 4
Publication A029U889
Issue 3 - 8-2017
PowerStart 0500
X1.3 & X2.5 Engine
SECTION 1 – IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual
contains important instructions that should be followed
during installation and maintenance of the generator
and batteries.
Before operating the generator set (genset), read the
Operator’s Manual and become familiar with it and the
equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the
operator, service personnel, or the equipment.
DANGER
This symbol warns of
immediate hazards which will result in
severe personal injury or death.
WARNING
This symbol refers to a
hazard or unsafe practice which can
result in severe personal injury or death.
CAUTION
This symbol refers to a
hazard or unsafe practice which can
result in personal injury or product or
property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result
from improper practices.
• DO NOT fill fuel tanks while engine is running,
unless tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a
potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use
zinc coated or copper fuel lines with diesel fuel
• Be sure all fuel supplies have a positive shutoff
valve.
• Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a
highly explosive hydrogen gas that can be ignited
by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
likely to congregate. Visually and audibly inspect
the exhaust daily for leaks per the maintenance
schedule. Make sure that exhaust manifolds are
secured and not warped. Do not use exhaust
gases to heat a compartment.
• Be sure the unit is well ventilated.
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
birth defects, and other reproductive harm.
•
MOVING PARTS CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
moving parts.
• Before starting work on the generator set,
disconnect battery charger from its AC source,
then disconnect starting batteries, negative (–)
cable first. This will prevent accidental starting.
• Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity
of moving parts, or while working on electrical
equipment. Loose clothing and jewelry can
become caught in moving parts.
• If adjustment must be made while the unit is
running, use extreme caution around hot
manifolds, moving parts, etc.
DO NOT OPERATE INFLAMMABLE AND
EXPLOSIVE ENVIRONMENTS.
Flammable vapor can cause an engine to overspeed
and become difficult to stop, resulting in possible fire,
explosion, severe personal injury and death. Do not
operate a genset where a flammable vapor
environment can be created by fuel spill, leak, etc.,
unless the genset is equipped with an automatic
safety device to block the air intake and stop the
engine. The owners and operators of the genset are
solely responsible for operating the genset safely.
Contact
your
authorized
Cummins
Inc.
distributor for more information.
page 5
Publication A029U889
Issue 3 - 8-2017
PowerStart 0500
X1.3 & X2.5 Engine
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
•
•
•
•
Remove electric power before removing
protective shields or touching electrical
equipment. Use rubber insulative mats placed
on dry wood platforms over floors that are metal
or concrete when around electrical equipment.
Do not wear damp clothing (particularly wet
shoes) or allow skin surface to be damp when
handling electrical equipment. Do not wear
jewelry. Jewelry can short out electrical contacts
and cause shock or burning.
Use extreme caution when working on electrical
components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed
by a qualified licensed electrician. Tag and lock
open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL
SYSTEM. Hazardous voltages can flow from the
generator set into the utility line. This creates a
potential for electrocution or property damage.
Connect only through an approved isolation
switch or an approved paralleling device.
GENERAL SAFETY PRECAUTIONS
•
•
Coolants sunder pressure have a higher boiling
point than water. DO NOT open a radiator or
heat ex-changer pressure cap while the engine
is running. To prevent severe scalding, let
engine cool down before removing coolant
pressure cap. Turn cap slowly, and do not open
it fully until the pressure has been relieved.
Used engine oils have been identified by some
state or federal agencies as causing cancer or
reproductive toxicity. When checking or
changing engine oil, take care not to ingest,
breathe the fumes, or con-tact used oil.
•
Keep multi-class ABC fire extinguishers
handy. Class A fires involve ordinary
combustible materials such as wood and
cloth; Class B fires, combustible and
flammable liquid fuels and gaseous fuels;
Class C fires, live electrical equipment. (ref.
NFPA No. 10).
•
Make sure that rags are not left on or near
the generator set.
•
Make sure generator set is mounted in a
manner to prevent combustible materials
from accumulating under or near the unit.
•
Remove all unnecessary grease and oil from
the unit. Accumulated grease and oil can
cause over-heating and engine damage
which present a potential fire hazard.
•
Keep the generator set and the surrounding
area clean and free from obstructions.
Remove any debris from the set and keep
the floor clean and dry.
•
Do not work on this equipment when
mentally or physically fatigued, or after
consuming any alcohol or drug that makes
the operation of equipment unsafe.
Substances in exhaust gases have been
identified by some state or federal agencies
as causing cancer or reproductive toxicity.
Take care not to breath or ingest or come
into contact with exhaust gases.
•
•
Do not store any flammable liquids, such as
fuel, cleaners, oil, etc., near the generator
set. A fire or explosion could result.
•
Wear hearing protection when going near an
operating generator set.
•
To prevent serious burns, avoid contact with
hot metal parts such as radiator system,
turbo charger system and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
page 6
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
SECTION 2 – INTRODUCTION
2.1 ABOUT THIS MANUAL
This manual provides troubleshooting and repair
information regarding the PowerCommand®
1302Control (PCC) and generators for the
generator sets (gensets) listed on the front cover.
Engine service instructions are in the applicable
engine service manual. Operating and maintenance
instructions are in the applicable Operator’s
Manual.
This manual does not have instructions for
servicing printed circuit board assemblies. After
determining that a printed circuit board assembly is
faulty, replace it, do not repair it. Attempts to repair
a printed circuit board can lead to costly damage to
the equipment.
This manual contains basic (generic) wiring
diagrams and schematics that are included to help
in troubleshooting. Service personnel must use the
actual wiring diagram and schematic shipped with
each unit. The wiring diagrams and schematics that ƒ
are maintained with the unit should be updated
when modifications are made to the unit.
Read Important Safety Instructions and carefully
observe all instructions and precautions in this
manual.
2.2 SYSTEM OVERVIEW
The PCC is a microprocessor-based control
for Cummins Inc. generator sets. All generator
set control functions are contained on one
circuit board (Base board). The Base board
provides fuel control, main alternator voltage
output regulation and complete generator set
control and monitoring.
The operating software provides control of the
generator set and its performance characteristics,
and displays performance information on a digital
display panel. It accepts menu-driven control and
set-up input from the push button switches on the
front panel.
2.3 TEST EQUIPMENT
To perform the test procedures in this manual, the
following test equipment must be available
True RMS meter for accurate measurement of
small AC and DC voltages. Fluke models 87 or
8060A are good choices.
ƒ Grounding wrist strap to prevent circuit board
damage due to electrostatic discharge (ESD).
ƒ Battery Hydrometer.
ƒ Jumper Leads.
ƒ Tachometer or Frequency Meter.
ƒ Wheatstone Bridge or Digital Ohmmeter.
ƒ Variac.
ƒ Load Test Panel.
ƒ Megger or Insulation Resistance Meter.
InPower™ Service Tool (PC based genset
service tool).
ƒ PCC1302 Interface Kit (Used with InPower
Service Tool)
2.4 HOW TO OBTAIN SERVICE
Always give the complete Model, Specification and
Serial number of the generator set as shown on the
nameplate when seeking additional service
information or replacement parts. The nameplate is
located on the front of the control panel.
WARNING
Incorrect service or
replacement of parts can result in severe
personal injury or death, and/or equipment
damage. Service personnel must be trained and
experienced
to
perform
electrical
and
mechanical service. Read and follow Important
Safety Instructions on pages iii and iv.
page 7
Publication A029U889
Issue 3 - 8-2017
PowerStart 0500
X1.3 & X2.5 Engine
SECTION 3 – OPERATOR PANEL OPERATION
FIGURE 3-1. PS0500 - CONTROLLER
3.1 GENERAL
The PS0500 is a microprocessor-based controller
that has these abilities.
•
Start and stop the genset.
•
Monitor the status of the genset.
•
Warn the operator when unsafe conditions
are occurring
•
Shut down the genset to prevent damage
•
Adjust settings that affect genset behavior.
•
Provide a way for other devices to remotely
start / Stop the genset
This is the Operator Manual for the PowerStart 0500
control. It is not the Operator Manual for the
generator set (“genset”) or any accessories.
The third digit is flashed, followed by a half-second
pause, and then the fourth digit is flashed, followed
by a two-second pause. The PowerStart 0500 is
suitable for non-paralleling generator sets
(“gensets”) in standby or
Prime power applications.
page 8
Note: Other devices that can remotely start / Stop
the genset might be as simple as a switch or a push
button or as sophisticated as other controllers or
computers. This manual introduces the ways the
Control can interact with other devices, but this
manual cannot identify all of the devices that might
be used in every application.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
3.2 ALTERNATOR CONNECTIONS
This section introduces the connections between the
PS0500 and the alternator.
Main Alternator Output
The PS0500 is connected to the main alternator
output to measure genset voltage and genset
frequency.
The PS0500 is also connected to current
transformers (CTs) which reduce the genset current
by a known ratio for measuring main alternator
output current.
See Sequences of Operation for more information
about the behavior of this output.
Genset Connections
This section introduces the connections betweent he
PS0500 and other parts of the genset. Some of
these connections are flexible and might be made to
many types of devices.
Customer Input
The PS0500 has one customer input that can be
configured to invoke a shutdown or Warning
response
Battery Charger Failed Switch
Engine Connections
This section introduces the connections between the
PS0500 and the engine.
The PS0500’s Customer Input may be connected to
a battery charger’s status output (discrete) to
monitor the battery charger operation.
Battery Connections
Emergency Stop Buttons
The battery provides power for the PS0500 and the
PS0500 monitors the battery voltage.
The PS0500 may be connected to a push button
that shuts the genset down immediately when
pressed.
Starter
The PS0500 is connected to the starter control relay
in order to control the starter.
See Sequences of Operation for more information
about the behavior of this output.
FIGURE 3-2. EMERGENCY STOP BUTTON
(EXAMPLE)
Fuel Shutoff (FSO) Relay
The PS0500 is connected to the fuel shutoff control
(FSO) in order to control the fuel shutoff solenoid in
the fuel supply line.
Customer Output
The PS0500 has one customer output that can be
configured to become active when either a shutdown
or Warning fault occurs.
page 9
Publication A029U889
Issue 3 - 8-2017
PowerStart 0500
X1.3 & X2.5 Engine
PC-based Service Tools
The PS0500 or the Operator Panel may be
connected to a PC-based service tool, such
as InPower.
Note: See the PC-based service tool documentation
for more information.
The PC-based service tool harness (Figure 3-3) is used
to connect the PS0500 to a PC-based service tool.
FIGURE 3-3. PC-BASED SERVICE TOOL HARNESS
Ready to Load
The PS0500 may notify a device when event 1465 (Ready to
Load) is active. Typically, the device is a programmable logic
controller
Remote Start
The PS0500 may be connected to a device that can
generate a remote start signal. Typically, the device is a
transfer switch.
page 10
Certifications
The PS0500 meets or exceeds the requirements of the
following codes and standards.
• UL 508
• CSA
• C282 compliant
• 22.2 compliant
• NFPA 99 compliant
• MS 202C, Method 101 compliant
• IEEE C62.41 compliant
• IEEE C37.90 compliant
• BS ISO 8528−4:2005
• BS EN 50081−1:1992
• BS EN 61000−6−2:2001
• BS EN 61000−6−3:2001
• BS EN 61000−6−4:2001CE Marking: The control
system is suitable for use on generator sets to be CE
− marked.
• BS EN 61000−6−4:2001CE Marking: The control
system is suitable for use on generator sets to be CE
− marked.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
3.3 CONTROL OPERATION
In this section, italics are used to identify a specific
parameter by name.
Safety Considerations
AC power is present when the genset is running. Do not
open the generator output box while the genset is
running.
WARNING Contacting high-voltage
components can cause electrocution, resulting in
severe personal injury or death. Do not open the
generator output box while the set is running. Read
and observe all WARNINGS and CAUTIONS in your
genset manuals.
The PS0500 cabinet must be opened only by technically
qualified personnel.
WARNING
The PS0500 cabinet must be
opened only by qualified personnel. High-level
voltages (up to 600 VAC) are present in the PS0500
cabinet. These voltages can cause electrical shock,
resulting in personal injury or death.
CAUTION
Even with the power removed,
improper handling of components can cause
electrostatic discharge and damage to circuit
components.
FIGURE 3-4. CONTROL PANEL BUTTONS
TABLE 3-1 CONTROL PANEL BUTTONS
BUTTON(S)
Manual
Auto
DESCRIPTION
Puts the control in Manual Mode to Start
the genset Manually.
You have to push the Start button in
less than ten seconds after you push
the Manual button.
Puts the control in Auto Mode. The
genset starts and stops when it
is told by other devices (such as a
transfer switch)
Stop
Stops the genset
Read Safety Precautions, and carefully observe all of the
instructions and precautions in this manual.
When the genset starts and stops, it follows a series of
steps, called a sequence of operation that is intended to
Starting and Stopping the Genset
maximize the life of the genset. The genset might not
start or stop immediately.
The buttons related to changing mode of operation are
highlighted in figure 3.4 and described in
WARNING
Table 3.1
The genset might not start or
stop immediately. Do not attempt to service the
genset if it does not appear to respond immediately.
Accidental starting of the genset during
troubleshooting can cause severe personal injury or
death.
page 11
Power Start 0500
X1.3 & X2.5 Engine
3.4 CONTROL PANEL
The control panel (Figure 3-5) is the front panel of
the PS0500 control
FIGURE 3-5. CONTROL PANEL (PS0500)
page 12
Publication A029U889
Issue 3 - 8-2017
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Conto Panel Description
Alpha-numeric LCD Display
Buttons and LED Indicators
TABLE 3-3. BUTTONS
The 2 line 16 Character, Backlit LCD display is used to
indicate various genset parameters in several frames. The
frames are normally scrolled one after the other for 3
seconds each at a time. The scrolling can be stopped and
parameters on a particular frame can be monitored for
longer time by pressing the OK button while the frame of
interest is being displayed. Pressing the OK button again
causes the frames to start scrolling again. The LCD display
is also used to present the setup menus during the setup
modes. The set up modes are described in detail in a
separate section in this manual.
LED/BUTTON
DESCRIPTION
Manual
Press this to put the PS0500 in Manual
mode from Stop mode. If you do not
press the Start button
In ten seconds, the control automatically
enters the Stop mode The green LED
above this button blinks when the
PS0500 is in Manual mode.
In Manual mode, press this to initiate a
Manual Start sequence. In other modes,
this button has no effect.
Press this to put the PS0500 in Auto
mode from Stop mode.
The green LED above this button blinks
when the PS0500 is in Auto mode.
Press this to Stop the running Genset.
The Red LED above this button blinks
when the PS0500 is in Stop mode.
Pressing this button takes the control to
STOP mode.
This button is used along with the OK
button to enter setup mode. Holding
these two buttons pressed continuously
for 5 Seconds causes the control to
enter in setup mode if the control is in
STOP mode. This button also wakes up
the control from Power Down Sleep
Mode.
This button is used mainly in “Setup
mode” to select menu items. It is also
used to Pause / Resume the scrolling of
the parameter frames.
Start
TABLE 3-2. LED INDICATORS AND BUTTONS
Auto
LED
DESCRIPTION
Genset
Running
This green LED is lit when the genset is
running at or near rated speed and voltage.
Remote Start
Shutdown
Warning
This is not lit while the genset is Stopped.
This green LED is lit when the remote start
signal is active. This signal has no effect
unless the PS0500 is in Auto mode.
This red LED is lit when there is any active
shutdown fault. Event 1541 (Common
Shutdown) is active.
This amber LED is lit when there is an
active warning fault. Event 1540 (Common
Warning) is active.
Stop
Reset
OK
page 13
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
3.5 MODES OF OPERATION
The mode of operation determines the ways the
Genset can be started and stopped. The PS0500 runs in
one of these modes at any given time.Table 2-3 explains
how to change the mode of operation.
Stop (Off) Mode
Pressing the STOP button will always put the PS0500 in
STOP mode and the RED LED above the STOP button will
start blinking.
In this mode, the PS0500 does not allow the genset to start
/ Crank.
If the genset is running (either in Manual or Auto Mode)
when the Stop button is pressed, the PS0500 stops the
genset and enters in the STOP mode.
Setup Mode
The Setup mode can be entered only from Stop mode when
the genset is not running. This is accomplished by holding
the Reset and the OK buttons pressed for 5 seconds
continuously while in stop mode. The RED Stop Led flashes
faster (double the normal rate) as long as the control is in
setup mode. While in setup mode, pressing Start or Stop
button has no effect. Exiting from setup mode will return the
control to STOP mode.
In the setup mode, a Menu driven setup process is
available for making adjustments that are allowed to be
made from the control panel. Set up process is described in
detail in a separate section later in this manual.
Auto Mode
Pressing the Auto Button while the PS0500 is in the STOP
mode will put the PS0500 in AUTO Mode. Pressing Auto
Button while the PS0500 is in Manual Mode (Running or
Not Running) has no effect.
WARNING
In Auto mode, the genset can start
at any time. NEVER service the genset in Auto mode.
Accidental starting of the genset during
troubleshooting can cause severe personal injury or
death. Disable the genset before troubleshooting.
When the remote start signal becomes active, the PS0500
initiates the start sequence to start the genset. The PS0500
continues to run as long as the signal is active. When the
Remote Start signal becomes inactive the PS0500 initiates
a normal stop sequence.
page 14
Pressing the Stop button shall always deactivate the FSO
immediately.
Remote Start Signal
This signal will start the Genset when these conditions are
met.
• The PS0500 is in Auto mode
• There are no active shutdown faults
This signal comes typically from a transfer switch or an
external toggle switch.
Manual Mode
Pressing the Manual Button while the PS0500 is in the Stop
Mode will put the PS0500 in the Manual Mode.
In this mode, the genset is controlled manually. Pressing
the Start button initiates a Manual Start sequence. Remote
start signal has no effect.
Note: If you do not press the Start button in ten seconds,
the PS0500 changes over to STOP (Off) mode.
Pressing the Stop button initiates a stop sequence.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Power-Down Mode
Sequence of Operation
The PS0500 can enter power-down or sleep mode, to
reduce load on batteries when not being used.
Sequences of operation describe the way the PS0500
starts the genset or stops the genset. This is illustrated in
Figure 3-6.
PS0500 Power-down Mode
Table 2-4 shows how much current the PS0500 control
module consumes in normal operation and in power-down
mode.
TABLE 3-4. PS0500 CURRENT CONSUMPTION
PS0500 MODE
Normal operation
Power-down
CURRENT
350 mA
< 5 mA
The PS0500 enters power-down mode when these
conditions are met.
- The genset is not running.
- The Power down Mode Time Delay has expired.
- There is no active communication on the RS-485
communication link.
- There are no active faults
- There are no active Wake Up signals present.
In power-down mode, the microprocessor in the control
stops, thereby reducing the consumption from battery.
Wake Up Signals
The PS0500 wakes up from power-down mode when any of
these wakeup signals becomes active.
− Tool wakeup input (TB15 pin 5) is grounded.
− Τhe Reset button on the Control Panel is pressed
− Remote Start Signal (Typically, to a transfer switch) is
low.
Stopped
Start Sequence
Genset Running
Stop Sequence
FIGURE 3-6. Sequence of operation
Start Sequences
The PS0500 follows different start sequences depending on
its setup and conditions.
If a start sequence is interrupted for any reason except a
shutdown fault (for example, the remote start signal
becomes inactive), the PS0500 aborts the start sequence
and initiates a Stop sequence.
Remote Start
This sequence begins when these conditions are met.
- The PS0500 is in Auto mode.
- The remote start signal is active,
- There are no active shutdown faults.
- This sequence is shown in Figure 3-7.
page 15
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Cycle Cranking
The starter turns on for Cycle Crank Engage
Time and turns off for Cycle Crank Rest
Time. The starter repeats this process up
to Crank Attempts times.
The PS0500 turns OFF the Starter Output and keeps it
OFF when,
The Genset Frequency is >= Starter Disconnect Speed /
Frequency Speed gain,
(Example: Typically the starter disconnect speed is set
to 450 RPM. In case off a four pole alternator the value
of the Frequency speed gain is set to 30. So the genset
frequency at which the starter disengagement happens
would be calculated as 450 / 30 = 15Hz)
OR
The Battery Charging Alt Voltage >= Start Disconnect
threshold
If the genset frequency does not reach the start
disconnect threshold (15 Hz in above example) before
PS0500 finishes the cranking cycle, then it generates
shutdown fault 359 (Fail To start).
FIGURE 3-7. Remote Start Sequence
In this sequence, the PS0500 follows these steps to start
the engine.
1. The PS0500 waits until Start Time Delay expires.
If the trim Glow Plug Enable is set to Enabled, the
PS0500 turns on the Glow Plug Control output. The
PS0500 turns off the Glow Plug Output when Glow Plug
Timeout Period expires.
The PS0500 does not proceed to crank until both Start
Time Delay expires and the Glow Plug Output is turned
off.
2. The PS0500 turns on the fuel shutoff (FSO) output
and the Starter Output.
page 16
The PS0500 waits for the Genset to reach the rated
frequency and voltage. If that does not happen within 10
seconds from the starter disconnect, the PS0500
generates Shutdown Fault 2335 (loss of AC Sensing).
Manual Start
This sequence begins when these conditions are
met.
• The PS0500 is in Manual mode and the Start
button is pressed.
• There are no active shutdown faults.
This sequence is shown in Figure 3-8. There are no
active shutdown faults.
.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Meter Calibration
When running in Manual Mode, the control allows meter
calibration process to be invoked, when the Genset
Running (Ready to Load) state is reached. The Meter
Calibration process is invoked by holding the Reset and
OK buttons pressed for 5 seconds continuously. The
process allows the arrow keys to be used for adjusting
the displayed alternator AC Voltage / Current values to
actual values (as measured using an independent
calibrated instrument) one by one.
The Meter Calibration Process is available when running
the genset in Manual Mode only.
Nominal Voltage and Frequency
The PS0500 does not have the control of the genset
frequency (speed) and the genset voltage.
The nominal voltage and the nominal frequency set-up
parameters are used only for calculation of the over
voltage, under voltage, over frequency and under
frequency fault thresholds and determining if the Genset
Running (Ready to Load) state has been reached as
described above.
Stop Sequences
FIGURE 3-8. Manual Start Sequence
In this sequence, the PS0500 follows these steps to start
the engine.
1. If the trim Glow Plug Enable is set to Enabled, the
PS0500 turns on the Glow Plug Control output. The
PS0500 turns off the Glow Plug Output when Glow Plug
Timeout Period expires.
The PS0500 does not proceed to crank until the Glow
Plug Output is turned off.
2. The PS0500 turns ON the fuel shutoff (FSO) output
and the Starter Output.
The cycle cranking process as explained above is
followed in Manual Mode also.
Genset Running (Ready to Load)
The PS0500 enters the Genset Running (Ready to
Load) state when the genset frequency and voltage are
both >= 90 percent of the nominal frequency and
nominal voltage respectively.
The PS0500 follows different stop sequences depending
on its setup and conditions.
Auto Mode
In Auto mode the stop sequence begins when these
conditions are met.
− The genset is running at rated speed and voltage
− The remote start signal is inactive.
The Genset will continue to run for the Stop Delay time
and then the FSO Output will be deactivated by the
PS0500.
Manual Mode
In Manual mode the stop sequence begins when these
conditions are met.
− The genset is running at rated speed and voltage
− The Stop button has been pressed.
− There are no active shutdown faults.
The FSO Output will be deactivated by the PS0500
immediately when the Stop button is pressed.
page 17
Power Start 0500
X1.3 & X2.5 Engine
Fault Shutdown
In Manual as well as Auto mode, the FSO Output will be
deactivated by the PS0500 immediately when any of the
shutdown faults becomes active.
page 18
Publication A029U889
Issue 3 - 8-2017
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
SECTION 4. CIRCUIT BOARD
TB15 – Tool Connector
Arrow at Pin 1
J12 – CT connector
Arrow at Pin 1
J12 –Pin 4
J16 – Engine connector
Arrow at Pin 1
J16 –Pin 7
J22 – Voltage connector
Arrow at Pin 1
TB2 – Customer TB
Arrow at Pin 1
page 19
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
The dot designates pin 1 on the connectors.
TB2 – Customer Terminal Block
Customer fault input, Customer output, Glow
Plug, Remote Start, Remote E-stop.
J22
Alternator Voltage
Sense inputs and
Field Output
•
•
PS0500
CONTROL BOARD
•
J16 Engine Connections
Coolant Sensor, Lube Oil
Pressure sensor, Run / OFF /
Auto Switch, FSO, Starter,
Battery, Mag Pick Up, Starter
Disconnect Feed Back,
Battery Charger D+, Chassis
GND. Governor PWM
•
•
TB15 – Tools
Interface Connector
page 20
J12 CT Connections
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
4.1 CONTROL INPUTS AND OUTPUTS
Engine Connector
The engine connector (J16) is a 12 pin connector-plug (12 MINI M-N-L). A possible supplier is
Molex; their part number is 39299123. The Cummins part number for this connector is 0323-2589. The PCB outline
drawing shows where the connector is located as above .Each signal is described as below –
Connector Pin
J16-1
J16-2
J16-3
J16-4
J16-5
J16-6
J16-7
J16-8
J16-9
J16-10
J16-11
J16-12
Signal Name
Coolant temperature sensor
Battery charging alternator (WL)
Starter Relay Driver (Low Side)
Fuel shutoff relay Driver (Low Side)
BATChassis GND
NC
NC
Oil Pressure Sensor
Starter Disconnect Input
Sensor Common
BAT +
CT Connector
The CT connector is a 6- pin MATE-N-LOCK connector. The possible manufacturer is Tyco, and the supplier part
number for the part is 643749-1. The Cummins part number for this connector is 0323-2154. Connector details are as
follows –
Connector pin
J12-1
J12-2
J12-3
J12-4
J12-5
J12-6
Signal
CT1_input
CT2_input
CT3_input
CT1_COM
CT2_COM
CT3_COM
page 21
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Voltage Connector
The voltage connection is via a 4 pin header with alternate spaces between the pins. The possible supplier is Tyco
with the supplier part number as 282828-4. The Cummins part number for the same is 0323-2225-03.
Connector pin
J22-1
J22-2
J22-3
J22-4
Signal
Gen_V1
Gen_V2
Gen_V3
Gen_N
Customer Connections TB2
The customer connection TB2 is a 6 pin terminal block. The possible supplier is Magnum:
The terminal pins details are as shown belowTerminal pins
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
Signal
Remote start Switch Input
Glow Plug Output Relay Driver
(Low Side)
Customer Output Relay Driver
(Low Side)
Customer Input
E-Stop
NC
All the inputs are active GND. And outputs are low side drivers. Remote E-Stop switch should have two independent
potential free contacts. One NC contact for cutting out the Battery supply to the Fuel Solenoid and another NC contact
to disconnect controller’s E-Stop input from GND to indicate to the control when the E-Stop is pushed in active state.
Battery Positive is not provided on the Customer terminal block (TB2). External provision needs to be made in the
harness to provide fused B+ via a 1 amp fuse for wiring up external relays. External Relays of suitable contact ratings
must be used for controlling FSO, Starter, Customer Output and Glow plug.
PC Tool Connector
The PC tool connector is a dedicated 5 pin connector header block. The possible supplier is Tyco, with the supplier
part numbers are 796643-5. The Cummins part number for the same is 0323-2191-04.
Terminal pins
TB15-1
TB15-2
TB15-3
TB15-4
TB15-5
page 22
Signal
GND
NC
RS485_DATA_A
RS485_DATA_B
TOOL_WAKEUP
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
Connector Part
Numbers
Quantity
Name
Description
Manufacturer
Manufacturer’s
part number
Cummins
part no
1
J22
Alt Voltage
Connector
TYCO
282828-4
0323-2225-03
1
J12
CT Connector
TYCO
643749-1
0323-2154
1
J16
Engine
Connector
MOLEX
39299123
0323-2589
1
TB2
Customer TB
MAGNUM
EM257506VC
0323-1677-05
1
TB15
Tool
Connector
TYCO
796643-5
0323-2191-04
1
J22
TYCO
282809-4
0323-2226-03
1
J12
1-480704-0
0323-1932
350551-1
0323-1200
1
J16
39012120
0323-2602
39000038
0323-2603
EM256506H
0323-1678-05
Alt Voltage
Connector
CT Connector
Crimp
Terminals
Engine
Connector
Crimp
terminals
TYCO
MOLEX
1
TB2
Customer TB
MAGNUM
1
TB15
Tool
Connector
TYCO
Remarks
All these
connectors
are PCB
mounted
connectors
Communication cable Kit 0541-1199 is used for
the tool interface
page 23
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
SECTION 5 - TROUBLESHOOTING
General
The PS0500 control continuously monitors engine
sensors for abnormal conditions, such as low oil
pressure and high coolant temperature. If any of these
conditions occur, the control will light a yellow warning
lamp or a red shutdown lamp and display a message on
the LCD display.
PC Based Service Tool
The PC based service tool can be used in
troubleshooting to perform tests, verify control inputs and
outputs, and test protective functions.
When used improperly, a PC based service tool can
cause symptoms like warnings and shutdowns that
appear to be a defective control. When these problems
occur, always verify that a self-test or fault simulation
(override) have not been left enabled with the tool. If you
do not have a PC based service tool, or the enabled fault
simulation(s) can not be found using the tool, disconnect
battery power to disable the test or override condition.
Make sure that parameter adjustments and time delays,
related to the fault condition, have been appropriately set
for the application. It may be necessary to write the initial
capture file to the device or update the calibration file.
Updating a calibration file requires a Pro version of many
of PC based service tools. Confirm that the installed
calibration part number matches the serial plate
information.
CAUTION
Using the wrong capture file can
result in equipment damage. Do not swap Controls
from another genset model and only use the
calibration file shown on the nameplate.
5.1 SAFETY CONSIDERATIONS
WARNING
Contacting high voltage
components can cause electrocution, resulting in
severe personal injury or death. Keep the output
box covers in place during Trouble shooting.
WARNING Ignition of explosive battery
gases can cause severe personal injury or death.
Arcing at battery terminals, light switch or other
equipment, flame, pilot lights and sparks can ignite
battery gas. Do not smoke, or switch trouble light
page 24
ON or OFF near battery. Discharge static electricity
from body before touching batteries by first
touching a grounded metal surface.
Ventilate battery area before working on or near
battery—Wear goggles—Stop genset and
disconnect charger before disconnecting battery
cables—Disconnect negative (-) cable first and
reconnect last.
CAUTION
Disconnect battery charger from
AC source before disconnecting battery cables.
Reading Fault Codes
The fault code and message can be viewed on the
display. After the fault is acknowledged and corrected,
the recorded fault will be deleted from the control panel
memory, but will remain in a data log to maintain a fault
code history. A PC based service tool is required to view
this data log.
5.2 TROUBLESHOOTING PROCEDURE
The following tables are a guide to help you evaluate
problems with the generator set. You can save time if
you read through the manual ahead of time and
understand the system.
Voltage/Continuity Testing
Voltage and continuity tests are required in the following
tables. In some cases, it is necessary to remove a plug
to complete the test. Where required, the corrective
action will mention when it is necessary to remove a plug
for testing. In other cases, the plug cannot be removed
for testing. When plug removal is not mentioned, testing
must be performed by inserting a narrow meter probe
into the back of the plug.
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
TABLE 20-1. ENGINE DOES NOT CRANK IN
MANUAL MODE
Reason: This indicates that the control has not received
or recognized a manual start signal.
Effect: Engine will not start.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. No power
Check if the control is in Manual
supplied to
mode and when the Start button is
control
pressed, and that there are no
shutdown faults present.
Poor battery cable connections. Clean
the battery cable terminals and
tighten all connections.
Check for blown fuses.
2. Control not
properly
calibrated or
corrupt
calibration.
3. The
Emergency
Stop switch or
wiring is
defective.
5. Oil Pressure
switch or wiring
is defective
6. Oil Pressure
sender, setup
on wiring is
defective.
TABLE 20-2. ENGINE DOES NOT CRANK IN
REMOTE MODE
Reason: This indicates that the PS0500 control has not
received or recognized a remote start signal.
Effect: Engine will not start in remote mode, but starts in
manual mode.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. The remote
Check if the control is in Auto mode
start switch or
and there are no shutdown faults
wiring is faulty.
present. Attempt to start, and check
for ground at TB2-1.
If ground level is not present, isolate
to the remote switch or wiring. Repair
as necessary.
If ground level is present then the
control is bad. Replace the control
Remove connector P16 and check for
B+ at P16-12 and GND at P16-5. If
B+ or ground missing, check the
harness. If B+ and ground check OK,
cycle power to control by
reconnecting P16. Press Reset
Button to wake the control up. And
retry operation.
Confirm that the installed calibration
part number matches the serial plate
information. Re-enter calibration file if
necessary.
With Emergency Stop push button not
activated (switch closed), remove
leads from TB2-5 and B- and check
for continuity between these two
leads. If circuit is open, isolate to
Emergency Stop switch and wiring. If
there is continuity, go to next step.
Remove P16 connection and check
wiring between P16-9 and P16-11 to
the switch.
Verify control is configured for the
type of sensor installed.
Verify proper operation of the switch
Remove P16 connection and check
wiring between P16-9, P16-11 to the
sender. Verify control is configured for
the type of sender. Verify operation of
the sender
page 25
Power Start 0500
X1.3 & X2.5 Engine
TABLE 20-3. WARNING AND SHUTDOWN CODES
FAULT CODE
CORRECTIVE ACTION
Indicates engine has overheated
151
(coolant temperature has risen
HIGH COOLANT
above the shutdown trip point).
TEMP
Lamp: Shutdown
Allow engine to cool down
completely before proceeding with
the following checks:
a. Check coolant level and
replenish if low. Look for
possible coolant leakage
points and repair if
necessary.
b. Check for obstructions to
cooling airflow and correct as
necessary.
c. Check fan belt and repair or
tighten if necessary.
d. Check blower fan and
circulation pumps on remote
radiator installations.
e. Reset control and restart after
locating and correcting
problem.
Indicates engine oil pressure has
415
dropped below the shutdown trip
LOW OIL
point. Check oil level, lines and
PRESSURE
Lamp: Shutdown
filters. If oil system is OK but oil
level is low, replenish. Reset
control and restart. If oil switch is
used, check switch performance.
Indicates that one or more of the
1446
phase voltages has exceeded
HIGH AC
130% of nominal for 0 second, or
VOLTAGE
Lamp: Shutdown
has exceeded high ac voltage
threshold for High AC Voltage
time delay seconds.
Indicates that one or more of the
1447
phase voltages has dropped
LOW AC
below low ac voltage threshold for
VOLTAGE
Lamp: Shutdown
low ac voltage time delay
seconds.
Indicates frequency is 10% above
1449
base frequency for approximately
OVER
10 seconds.
FREQUENCY
Lamp: Shutdown
Indicates that Frequency had
1448
dropped below 90% of nominal for
UNDER
approximately 10 seconds.
FREQUENCY
Lamp: Shutdown
Check fuel supply, intake air
supply and load.
Indicates remote Emergency
1434
Stop. To reset the remote
EMERGENCY
Emergency Stop button:
STOP
Lamp: Shutdown
1. Open (disable) remote
page 26
Publication A029U889
Issue 3 - 8-2017
emergency stop button.
Press the OFF button.
Select the desired operating
mode (manual or auto).
Indicates possible fuel system or
air induction problem. (Engine
cranks but fails to start)
a.
Check for empty fuel tank,
fuel leaks, or plugged fuel
lines and correct as
required.
b.
Check for dirty fuel filter and
replace if necessary.
c.
Check for dirty or plugged
air filter and replace if
necessary.
d.
Reset the control and
restart after correcting the
problem.
Genset continues to run after
receiving shutdown command
from the controller.
Check the FSO Relay and related
wiring.
Check that the FSO is not
mechanically stuck
A shutdown fault occurred while
the Battle Short mode was
enabled. Check fault history for
faults that may have been
bypassed.
Indicates engine is operating near
cooling system capacity. Increase
in load or higher ambient
temperature may cause High
Coolant Temp (151) shutdown.
Review code 151 correction list
for other possible causes.
Indicates engine coolant heater is
not operating or is not circulating
coolant.
Check for the following conditions:
a. Coolant heater not
connected to power supply.
Check for blown fuse or
disconnected heater cord
and correct as required.
b. Check for low coolant level
c. and replenish if required.
Look for possible coolant
leakage points and repair as
required.
Open heater element. Check
current draw of heater.
2.
359
FAIL TO START
Lamp: Shutdown
2677
FAIL TO STOP
Lamp: Shutdown
1123
SHUTDOWN
AFTER BS
Lamp: Shutdown
146
HIGH COOL
TEMP.
Lamp: Warning
1435
LOW COOLANT
TEMP
Lamp: Warning
Set is not
operating.
Warning occurs
when engine
coolant
temperature is
70F (21C) or
lower. NOTE: In
applications
where the
ambient
temperature falls
below 40F (4C),
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
Low Coolant
Temp may be
indicated even
though the
coolant heaters
are operating.
1312
CUSOMER
INPUT FAULT
Lamp: Warning Or
Shutdown
Depending on the
setup
Coolant temperature must be
below 70F (default setting) for one
minute to activate warning and be
above 70F for five minutes before
the warning can be cleared.
144
COOL SENSOR
OOR
Lamp: Warning
Indicates that the control has
sensed that the engine coolant
temperature sensor output is out
of range (high or low). Check
sender/connectors/wires. This
fault will only occur if water
temperature sensor is equipped
on the genset.
Indicates battery voltage supply to
the control is approaching a low
level at which unpredictable
operation will occur.
a. Discharged or defective
battery.Check the battery
charger fuse.Recharge or
replace the battery.
b. Poor battery cable
connections. Clean the
battery cable terminals and
tighten all connections.
c. Check battery
wiring/calibration.
Check engine DC alternator.
Replace engine DC alternator
if normal battery charging
voltage is not obtained.
e. Check battery charge voltage
float level if applicable (raise
float level).
441
LOW BATTERY
Lamp: Warning
1131
BATTLE
SHORT ACTIVE
Lamp: Warning
2678
CHARGER
FAILURE
Lamp: Warning
Indicates the Customer Input is
active.
Example inputs: Low Fuel Day
Tank, Water In Fuel, Ground
Fault, etc.
If multiple of these are connected
in parallel, check if any one of
them is active.
Indicates that the control is in Battle
Short mode - used to bypass several
fault shutdowns for genset operation
during emergencies.
Indicates the battery charging
alternator has not reached an
acceptable voltage range within the
selected period (default = 120
1416
FAIL TO
SHUTDOWN
Lamp: Warning
1442
WEAK
BATTERY
Lamp: Warning
seconds). Refer to engine service
manual if this fault occurs. If not
failed, check wiring.
Genset continues to run after
receiving shutdown command from
the controller. Battle Short feature
enabled - used to bypass several
critical fault shutdowns for genset
operation during emergencies.
Indicates that during cranking, the
battery voltage is at or below the
weak battery warning trip point for a
time greater than or equal to the
weak battery set time. See code 441
for corrective action.
CODE 151/146 - HIGH OR PRE-HIGH COOLANT
TEMPERATURE (SHUTDOWN/SHUTDOWN)
Reason: Engine coolant temperature has exceeded the
warning threshold for pre-high/high coolant temperature.
Effect: 146 – . Warning Lamp lights , Faul code pops up.
151.- Engine will shut down
1. Fault
simulation was
enabled with a
PC based
service tool.
2. Engine or
sensor circuitry
problem.
3. The sensor
could be bad.
1. With a PC based service tool,
verify that the fault simulation is not
enabled for the coolant sensor.
If you do not have a PC based
service tool, remove battery power
from the control to disable fault
simulation overrides.
Check the sensor accuracy with a
thermocouple or similar temperature
probe.
•
If the coolant temperature
reading is accurate, the engine
may be overheating. Refer to the
engine service manual.
•
If the coolant temperature
reading is not accurate, go to
next step.
Disconnect the sensor and connect a
coolant temperature sensor
simulator to the harness.
If the control responds to the
simulator, replace the sensor. If
control does not respond, go to next
step.
4. The harness
or Control could
be bad.
4. Measure the resistance of the
coolant sensor and reconnect
harness to sensor. Remove
connector P16 from Control and
check resistance between pins P161 and P16-11.
page 27
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
•
•
If resistance is not the same,
harness is bad.
If resistance is the same, Control
is bad.
CODE 143/ 415 - LOW OIL OR PRE-LOW PRESSURE
(WARNING/SHUTDOWN)
Reason: Engine oil pressure has dropped below the
warning/shutdown threshold for low/high oil pressure.
Effect: 143. – Warning Lamp lights, Engine will shut
down for code 415. – Engine shuts down
POSSIBLE
CAUSE
1. Fault
simulation was
enabled with a
PC based
service tool.
2. Low oil level.
Clogged lines
or filters.
3. Sensor or oil
pump could be
bad. Or the
generator set
may be shutting
down on
another fault.
4. Harness or
Control could
be bad.
page 28
CORRECTIVE ACTION
With a PC based service tool, verify
that the fault simulation is not enabled
for the oil pressure sensor.
If you do not have a PC based service
tool, remove battery power from the
control to disable fault simulation
overrides.
Check oil level, lines and filters. If oil
system is OK but oil level is low,
replenish.
Disconnect the oil pressure sensor
leads, and connect an oil pressure
sensor simulator to the harness.
a. If the control responds to the
simulator, reconnect the sensor,
disconnect the + signal wire at the
fuel solenoid, and crank the engine.
Check the oil pressure reading on the
digital display.
• If the display shows an acceptable
oil pressure, the problem may not
be in the oil or oil sensing system.
The genset may be shutting down
on another fault (out of fuel,
intermittent connector). Restart
the genset and monitor the
display panel for other faults.
• If the display does not show an
acceptable oil pressure, replace
the sensor. If the Control still
doesn’t display an oil pressure
while cranking, the oil pump may
be bad. Refer to the engine
service manual.
b. If the control does not respond to
the simulator, go to next step.
If the control does not respond to the
simulator, the Control or the harness
is bad.
Check the resistance in P16-9 and
5. Low Oil
Pressure fault
set points could
be incorrect.
P16-11 (Sensor COMM). If the
resistance signal (100 to 33 Ohm)
does not get to P16, isolate to the
harness. If the resistance does go to
P16, the Control is bad.
Verify set points against the normal
operating pressures of the engine.
Refer to engine manual.
CODE 1446 - HIGH AC VOLTAGE (SHUTDOWN)
Reason: One or more of the phase voltages has
exceeded 130% of nominal for 1 seconds, or has
exceeded the High AC Voltage Threshold for the High
AC Voltage Delay seconds.
Effect: Engine will shut down.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Fault simulation 1. With a PC based service tool,
was enabled with
verify that the related fault
a PC based
simulation is not enabled.
service tool.
If you do not have a PC based
service tool, remove battery power
from the control to disable fault
simulation overrides.
2. Single step
2. Clear fault and restart genset.
large block load
removal.
3. Fault threshold
3. Reset the threshold to the
is not set correctly highest allowable setting.
with
Determine the required operating
InPower.
range before adjusting the
threshold.
4. AVR or
4. Refer to Generator AVR Board
generator is bad.
Isolation Procedure in Alternator
manual to determine if the AVR
board is causing the high AC
voltage shutdown fault.
5. Voltage sense
See Section 17 for proper
connections/set
corrective actions.
up could be
incorrect.
CODE 1447 - LOW AC VOLTAGE (SHUTDOWN)
Reason: One or more of the phase voltages has
dropped below the Low AC Voltage Threshold for Low
AC Voltage Delay seconds.
Effect: Engine will shut down.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Fault simulation
1. With a PC based service tool,
was enabled with a verify that the related fault
PC based service
simulation is not enabled.
tool.
If you do not have a PC based
Power Start 0500
X1.3 & X2.5 Engine
2. Fault threshold is
not set correctly
with
a PC based service
tool.
3. Overload.
4. Improper
connections have
been made at the
generator output
terminals.
5. Voltage sense or
setup wiring
connection could
be incorrect.
6. The rotating
rectifier assembly
(diodes CR1
through CR6) is
faulty.
7. Loose connector
or Control is bad.
8. AVR or
Alternator is bad.
9. Voltage sense
connections/setup
could be incorrect
Publication A029U889
Issue 3 - 8-2017
service tool, remove battery power
from the control to disable fault
simulation overrides.
2. Reset the threshold to the
lowest allowable setting.
Determine the required operating
range before adjusting the
threshold.
3. Check the load and correct any
overload. Check operation by
disconnecting load and restarting
generator set.
4. Reconnect according to the
appropriate reconnection diagram.
See Section 17.
5. Check that Voltage senses
inputs P22-1 to 4 are connected to
the correct voltage sensing point
at alternator.
6. Check each diode. See genset
service manual
8. Repair connections (P22) or
replace the Control if necessary.
4. Refer to Alternator / AVR Board
Isolation Procedure in Alternator
manual to determine if the AVR
board is causing the Low AC
voltage shutdown fault.
See section 17 for proper
connections
CODE 1449 - OVER FREQUENCY (SHUTDOWN)
Reason: Generator AC output frequency is high.
Effect: Generator set will shut down.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Fault
2. Reset the threshold to the highest
threshold is not allowable setting. Determine the
set correctly
required operating range before
with
adjusting the threshold.
PC based
service tool.
2. Fuel or air
3. Refer to the engine service manual.
delivery
problem.
3. Loose
4. Repair connections (P22 – 1 to 4)
connector or
or replace the Control if necessary.
Control is bad.
CODE 1448 - UNDER FREQUENCY (SHUTDOWN)
Reason: Generator AC output frequency is low.
Effect: Generator set will shut down.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Fault
2. Reset the threshold to the lowest
threshold is not allowable setting. Determine the
set correctly
required operating range before
with
adjusting the threshold.
PC based
service tool.
2. Overload.
3. Check the load and correct any
overload. Check operation by
disconnecting load and restarting
generator set.
3. Fuel or air
4. Refer to the engine service manual.
delivery
problem.
4. Governor
5. Check fuel shutoff solenoid
fault.
adjustment (refer to Section 8).
5. Loose
6. Repair connections (P22 – 1 to 4)
connector or
or replace the Control if necessary.
Control is bad.
CODE 234 - OVERSPEED (SHUTDOWN)
Reason: Engine speed signal indicates an engine speed
greater than shutdown threshold.
Effect: Engine will shut down.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Cold engine
1. Overspeed can occur when starting
(no coolant
a very cold engine. Clear fault and
heaters)
restart genset.
2. Single step
large block load
removal.
3. Fault
simulation was
enabled with a
PC based
service tool.
4. Fault
threshold is not
set correctly
with
PC based
service tool.
5. Monitor the
engine rpm
using InPower.
2. Clear fault and restart genset.
3. With PC based service tool, verify
that the fault simulation is not enabled
for the coolant sensor.
If you do not have PC based service
tool, remove battery power from the
control to disable fault simulation
overrides.
4. Reset the threshold to the highest
allowable setting. Determine the
required operating range before
adjusting the threshold.
5. If the RPM is not correct, refer to
fault code 1449 for corrective action.
page 29
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
6. Governor
fault.
7. Mechanical
Fuel system
setup could be
incorrect.
6a. Check fuel shutoff solenoid
adjustment (refer to Section 8).
6b. Replace defective injection pump
unit.
Verify fuel stop settings for the
application.
CODE 359 - FAIL TO START (SHUTDOWN)
MECHANICAL GOVERNED ENGINE
Reason: This indicates that the engine failed to start
after expiration of last crank time.
Effect: Engine will not start.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Restricted fuel
1a. Add fuel if low. Prime the fuel
supply due to:
system.
a. Fuel level
1b. Open any closed shutoff valve
below
in the fuel line supplying the engine.
pickup tube
1c. Refer to engine service manual.
in tank.
1d. Bleed air from fuel system.
b. Closed
Refer to engine service manual.
shutoff valve
in supply
line.
c. Fuel
injectors
clogged.
d. Air in fuel
system.
2. Glow plugs are
not heating due to:
a. Glow plug(s) is
bad.
b. Control is bad.
c. Glow Plug
Relay is bad.
3. Fuel solenoid on
the injection pump
not energized due
to:
a. Fuse may be
open.
b. Fuel solenoid
is bad.
c. Control/K7
Fuel Relay is
bad.
The Control determines at what
temperature and duration of time
that the glow plugs will be
energized. Using sensed coolant
temperature, the glow plugs are
energized at 77F (25C) and
colder. The glow plugs are
energized for up to 15 seconds
when the coolant temperature is 5F (-20.5C) or colder. Time
duration (15-0 seconds) is linear
between -5F and 77F.
With coolant temperature colder
than 77F (25C):
2a. Each glow plug should be
warm to the touch if the engine
has just been cranking. First clean
and tighten the terminal of any
cold glow plug and then replace it
if necessary.
2b. Attempt to start and check for
if Glow plug relay energizes. TB2-
page 30
5. The engine fuel
system is worn or
2 should be at GND potential. If
the TB2-2 is at GND and K2 relay
is not working check relay coil.
• If TB2-2 is not at GND
potential replace the Control.
• If B+ is present, check for open
circuit between glow plug relay
contact and glow plugs.
Isolate to fuse, K7 relay, fuel
solenoid or Control.
3a. Remove fuse (if installed) and
check continuity. If open, replace
the fuse with one of the same
type and amp rating. If fuse
reopens, check wiring continuity
of fuel solenoid circuit/test fuel
solenoid.
Binding in the solenoid linkage
can prevent activation of the hold
coil circuitry in the solenoid. Make
sure solenoid shaft moves
completely in and out freely.
(Applies to solenoids with both
Pull and Hold coils.)
3b. Attempt to start and check for
B+ at the fuel solenoid coil.
•
If B+ is present, fuel solenoid
is bad.
•
If B+ is not present, go to
step c.
3c. Check wiring continuity/test
K7 relay or fuel pilot:
Remove lead from K7-COM (fuel
pilot). Attempt to start and check
for GND at lead COM.
•
If there is no GND, check for
open circuit between K7
COM and Base card.
•
If GND is present, reconnect
lead COM to relay. Remove
lead from N/O connection.
Attempt to start and check for
B+ at terminal N/O
connection.
•
If B+ is present, check for
open circuit between N/O
connection and fuel
solenoid(+).
•
If B+ is not present, check for
relay contacts.
4. Service according to the engine
service manual.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
malfunctioning or
has lost prime (fuel
lift pump, injection
pump, injectors,
timing).
6. The engine is
5. Service according to the engine
worn or
service manual.
malfunctioning
mechanically.
CODE 1312 - CONFIGURABLE INPUT (SHUTDOWN)
Reason: The nature of the fault is an optional
configurable selection.
Effect: Shutdown.
POSSIBLE CAUSE CORRECTIVE ACTION
If there is no actual
Disconnect the signal lead from
fault, the problem
TB2 and reset the control. Check
may be an external the following two points.
wiring problem.
• Customer Input – TB2-4
If the message drops out, the
external wiring has a short
circuit. Grounding of the input
activates fault.
CODE 146 - HIGH COOLANT TEMP (WARNING)
Reason:
Effect:
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Refer to
1. Refer to code 151.
code 151.
CODE 1435 - LOW COOLANT TEMPERATURE
(WARNING)
Reason: Engine coolant temperature has dropped
below the warning threshold for low coolant temperature.
Effect: No action is taken by the control. Engine may not
start due to slow cranking speed.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Fault
1. With PC based service tool, verify
simulation was
that the fault simulation is not enabled
enabled with
for the coolant sensor.
PC based
If you do not have a based service
service.
tool, remove battery power from the
control to disable fault simulation
overrides.
2. Fault
2. Reset the threshold to the lowest
threshold is not allowable setting. Determine the
set correctly
required operating range before
with
adjusting the threshold.
a PC based
service tool.
3. The engine
3. Coolant heater not operating due
coolant heater
to:
could be bad.
(Radiant heat
should be felt
with hand
held close to
outlet hose.)
• Coolant heater not connected to
power. Check for blown fuse, or
disconnected heater cord and
correct as required.
• Low coolant level. Look for possible
coolant leakage points and repair
as required.
• Defective heater
element/thermostat. With coolant
heater removed from engine and
power disconnected, flush with cold
tap water for two minutes to close
internal heater thermostat (opens
at 100˜ F and closes at 80˜ F).
Check resistance across input
power leads:
a. Open - replace coolant heater.
b. Closed - coolant heater OK (coil
resistance of 10 to 60 ohms)
4. The sensor
4. Inspect the sensor and engine
connections
harness connector pins. Repair or
could be bad.
replace as necessary.
5. The sensor
5. Disconnect the sensor, and plug in
could be bad.
a resistive sensor simulator to isolate
the fault.
If the control responds to the
simulator, replace the sensor. If
control does not respond, harness or
Control are bad.
6. The harness 6. Measure the resistance of the
or Control could coolant temperature sensor and
be
reconnect harness to sensor. Remove
bad.
connector P16 from Control and
check resistance between pins P16-1
and P16-11
(Sensor Common).
• If resistance is not the same,
harness is bad.
• If resistance is the same, Control
is bad.
CODE 1312 - CONFIGURABLE INPUT (WARNING)
Reason: The nature of the fault is an optional
configurable selection.
Effect: Warning.
POSSIBLE
CORRECTIVE ACTION
CAUSE
If there is no
Disconnect the signal lead from TB2
actual fault, the and reset the control. Check the
problem may
following pins .Customer Input –
be an external
TB2-4 If the message drops out, the
wiring problem. external wiring has a short circuit.
Grounding of the input activates fault.
page 31
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
CODE 144 - COOLANT SENSOR OOR (HIGH/LOW)
(WARNING)
Reason: This indicates that the coolant temperature
sensor signal is out of range - shorted high or low.
Effect: No engine protection for coolant temperature
during genset operation. Possible white smoke.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. The sensor
2. Inspect the sensor and engine
connections
harness connector pins. Repair or
could be bad.
replace as necessary.
2. The sensor
3. Disconnect the sensor, and plug in
could be bad.
a resistive sensor simulator to isolate
the fault.
If the control responds to the
simulator, replace the sensor. If
control does not respond, go to next
step.
3. The harness
4a. Remove connector P16 from
or Control could Control and disconnect sensor.
be bad.
Check pins P16-1 and P16-11
(Sensor common) for short circuit as
follows:
•
Check for a short circuit to the
engine block ground (more than
200k ohms OK).
Check for a short circuit from pin
to pin (more than 200k ohms
OK).Repair or replace as
necessary.
4b. Measure the resistance of the
coolant sensor and reconnect
harness to sensor. Remove
connector P16 from Control and
check resistance between pins P16-1
and P16-11 (Sensor Common).
•
If resistance is not the same,
harness is bad.
•
If resistance is the same, Control
is bad.
CODE 441 - LOW BATTERY (WARNING)
Reason: Low voltage has been detected for battery.
Effect: The control’s voltage supply approaching level at
which unpredictable operation may occur.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Weak or
1. Recharge or replace the battery.
discharged
Specific gravity for a fully charged
battery.
battery is approximately 1.260 at 80F
(27C).
2. Low
2. Replenish electrolyte and recharge
electrolyte level
battery.
in battery.
page 32
3. Battery
connections
loose or dirty.
4. Insufficient
battery charging
voltage.
5. Engine DC
alternator could
be bad.
3. Clean and tighten or replace the
battery cable connectors and cables
at the battery and the set.
4. Adjust charge rate of AC powered
battery charging circuit, according to
manufactures instructions.
5. Replace engine DC alternator if
normal battery charging voltage (12
to 14 VDC) is not obtained.
6. If the
batteries are
OK, the problem
may be the
harness or the
Control.
6. Remove connector P16 from
Control and check battery voltage at
P16-12 (B+) to P16-5 (GND).
•
If the voltage at P16 is not the
same as the battery voltage, the
harness is bad.
If the voltage at P16 is OK, the
Control is bad.
7. Check fault threshold against
requirement of the application.
7. Fault
threshold could
be bad.
CODE 442 - HIGH BATTERY VOLTAGE (WARNING)
Reason: High voltage has been detected for battery.
Effect: Control damage will occur.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Excessive
1. Adjust charge rate of AC powered
battery charging battery charging circuit according to
voltage.
manufacturers instructions.
2. Engine DC
2. Replace engine DC alternator if
alternator could
normal battery charging voltage
be bad.
(12 to 14 VDC) is not obtained.
3. Fault
3. Check fault threshold against
threshold could
requirement of the application.
be bad.
CODE 143 - LOW OIL PRESSURE (WARNING)
Reason:
Effect:
POSSIBLE CAUSE
CORRECTIVE ACTION
1. Refer to code 415.
1. Refer to code 415.
CODE 141 - OIL PRESSURE SENSOR OOR
(HIGH/LOW) (WARNING)
Reason: This indicates that the engine oil pressure
sensor signal is out of range - shorted high or low.
Effect: No engine protection for oil pressure during
genset operation.
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. The sensor
2. Inspect the sensor and engine
connections
harness connector pins. Repair or
could be bad.
replace as necessary.
2. The sensor
3. Disconnect the oil pressure sensor
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
could be bad.
leads, and connect an oil pressure
sensor simulator to the harness.
“OIL PRESSURE SENSOR OOR”
warning is displayed after the fault
condition is sensed for 10
seconds.
3. The harness
could be bad.
4. The Control
If the control responds to the
simulator, replace the sensor. If
control does not respond, go to next
step.
4. Remove connector P7 from Control
and connector from sensor.
Check P16-9 and P16-11 as follows:
• Check for a short circuit from pin
to pin (more than 200k ohms OK).
• Check for an open circuit (10
ohms or less OK).
Repair or replace as necessary.
5. With all connectors attached,
could be bad.
check pressure signal (.500 to .033
VDC) at P16-9 and P16-11 (Sensor
Common). If in range, replace
Control.
CODE 1442 - WEAK BATTERY (WARNING)
Reason:
Effect:
POSSIBLE
CORRECTIVE ACTION
CAUSE
1. Refer to code 1. Refer to code 441.
441
page 33
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
SECTION 6 – SETUP AND CALIBRATION
Read Safety Precautions, and carefully observe all of the instructions and precautions in this manual.
CAUTION
Only qualified technicians should adjust the parameters described in this section. Failure
to follow this may affect genset operation and may cause damage to the genset or to equipment connected to
the genset.
In this section, italics are used to identify a specific parameter by name.
Parameters
See Section 4 for more information about parameters that you can adjust in the Operator Panel.
Capture File
Use InPower to save the current settings in a capture file on a PC or network. You can use the capture file to look at
the current settings while you are away from the PS0500 or to restore settings if you have to reset the PS0500 for any
reason. See the InPower User Guide for more information.
While InPower can be used with the PS0500 for facilitating the setup, it is not essential for carrying out the basic setup
operations. The basic setup can be performed directly from the control panel of PS0500. Following paragraphs
Describe the process of carrying out basic setup from the control panel.
Entering and leaving the Setup Mode
The Setup mode can be entered only from Stop mode when the genset is not running. This is accomplished by
holding the Reset and the OK buttons pressed for 5 seconds continuously while in stop mode. The RED Stop Led
flashes faster (double the normal rate) as long as the control is in setup mode. Pressing ← button while in Main Menu
exits the setup mode. Navigation through the setup menus is described further in a separate section later.
MENU Description
Tables 6.1 to 6.18 show a summary of the menus offered on the control panel of the PS0500.
Table 6.1 Main Menu Description
Menu
Description
Alt Setup
Use this menu to select alternator setup parameters like Single / Three phase, 50 / 60 Hz
operation, Wye / Delta , Voltage etc.
Units
Use this menu to select Metric or US units for Coolant Temperature and Oil Pressure
Oil Pr Input
Use this menu to select the sensor types used with oil pressure
Use this Menu to configure the response to Customer input and to configure usage of the
customer output
Customer I/O
Flt History
Use this menu to view last five faults that are stored in the control
Load Defaults
Use this menu to set the default values.
page 34
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
Table 6.2 Alt Setup Menu
SubMenu
Phase Type
CT Ratio
Connect Type
Nom LL Voltage
Frequency
Table 6.5 Nom LL Voltage Sub Menu
Description
Select this submenu to
choose between single /
three phase operation
Select this submenu to
choose the CT Ratio
Select this submenu to
choose between Wye /
Delta connection of
alternator windings
Select this submenu to
choose the alternator
nominal voltage
Select this submenu to
choose the frequency of
operation
Menu Items
190
200
208
220
230
240
380
400
416
440
460
Table 6.3 Frequency Sub Menu
480
600
Menu Items
50 Hz
Table 6.6 Connect Type Sub Menu
60 Hz
Menu Items
Table 6.4 CT Ratio Sub Menu
Single 3 Wire
3 Phase
Single 2 wire
Menu Items
50:5
75:5
100:5
150:5
200:5
250:5
Table 6.7 Connect Type Sub Menu
Menu Items
Star Connect
Delta Connect
300:5
page 35
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Table 6.8 Units Menu
Table 6.13 Customer O/P1 menu
Menu
Item
Metric
US
Description
Select this item to choose Metric
Units for the display of Coolant
Temperature and Oil Pressure
Select this item to choose US
Units for the display of Coolant
Temperature and Oil Pressure
Table 6.9 Oil Pr Input
SubMenu Description
Sensor
Select this if using a Sender
Switch
Select this if using a Switch
Menu Items
Glow Plug
Warning
Shutdown
Table 6.14 Customer O/P2 menu
Menu Items
ShutDown
Warning
Genset Running
Table 6.15 Flt History Menu
Menu Items
Fault 1 – Fault 5
Description
View the last 5 faults
stored in the control
Table 6.10 Oil Pressure Sensor Sub Menu
Table 6.16 Load Default
MenuItems
ONAN
CIL
Menu Items
Confirmation Screen
Table 6.11 Customer I/O Menu
SubMenu
Cust I/P Flt
Customer O/P1
Customer O/P2
Description
Choose the
response to the
input when active
Choose the
function of this
output
Choose the
function of this
output
Table 6.12 Cust I/P Flt Submenu
MenuItems
ShutDown
Warning
page 36
Description
To confirm the action
press OK
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Navigation
The manual (↑), Reset (↓ //), OK (→) and Auto (←) buttons are used for navigation during the setup. As long as
setup mode is not exited these buttons will only act as arrow keys. The RED Stop lamp flashes at twice the
normal rate as long as the setup mode is not exited and the control is not returned to STOP mode.
Navigation Example
(Set the nominal LL voltage to 440)
← Main Menu
//
Alt Setup
→
The Fig above shows the basic elements of a Setup Menu.
Line 1 always bears the Menu Name and Line 2 shows items in the Menu.
The symbols ←, / /, → indicate that the buttons bearing those symbols are active and can be used as follows
←
//
→
Back Button
(↓) Scroll Down to the next item
Select the item shown on line 2
When a menu or submenu containing more choices is selected, the Name of the Menu or Submenu moves to
line 1 and the choices in the menu are displayed on line 2. / / (↓) button can then be used to scroll through the
choices available in the Menu, and → (OK) button can be used to choose the item shown on line 2. The ←
button can be used to go back one level up in the menu.
Here in the current example, pressing → will take you to the Alt Setup menu. The Name of the chosen Menu (Alt
Setup) will move into the line 1 and the first choice within that menu (phase type) will be shown on line 2.
← Alt Setup
Phase Type
//
→
You can now press / / (↓) button to scroll through the choices available in the Alt Setup Menu one by one. When
the choice that you want appears on line 2, pressing → will take you into that submenu.
Here in our example, let us say, you pressed / / (↓) until “Nom LL Voltage” submenu was displayed in line 2.
← Alt Setup
Nom LL Voltage
//
→
Pressing → will take you into the choices available for nominal line to line voltages. Pressing ← will take you to
the main menu and pressing / / (↓) will take you to the next item within Alt Setup Menu.
Let us say you pressed →. The display will now look like this.
page 37
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
← Nom LL Voltage
190
//
→
Pressing / / (↓) will show all the choices available for nominal LL voltage one by one. Let us say you pressed / /
(↓) until 440 was displayed.
← Nom LL Voltage
//
440
→
Pressing → will select that as the Nominal LL Voltage. An asterisk (*) will appear in line 2 indicating that to be
the current selection. The → at the end of line 2 will change to ← indicating that the only active buttons now are /
/ (↓) and ←.
← Nom LL Voltage
//
* 440
←
Pressing ← button will take you to one level up in the menu tree at a time. You have to press ← several times to
reach the main menu. Pressing ← button while at the main menu shall exit the setup mode. Following message
shall be displayed before leaving the setup mode.
Current Config
Saved
←
Press ← to leave setup mode and resume normal operation. The red Stop LED will resume flashing with normal
rate (1 Hz).
page 38
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
SECTION 7 - SERVICING THE GENERATOR
7.1 TESTING THE GENERATOR
These tests can be performed without removing the
generator. Before starting tests, disconnect the
negative (–) cable from the battery to make sure the
engine will not start while performing these tests.
CAUTION
Disconnect
battery
charger from AC source before disconnecting
battery cables. Otherwise, disconnecting cables
can result in voltage spikes damaging to DC
control circuits of the set.
WARNING
Ignition of explosive
battery gases can cause severe personal injury
or death. Arcing at battery terminals, light
switch or other equipment, flame, pilot lights
and sparks can ignite battery gas. Do not
smoke, or switch trouble light ON or OFF near
battery. Discharge static electricity from body
before touching batteries by first touching a
grounded metal surface. Ventilate battery area
before working on or near battery—Wear
goggles—Stop genset and disconnect charger
before
disconnecting
battery
cables—
Disconnect negative (–) cable first and
reconnect last
WARNING
Accidental starting of the
generator set can cause severe personal injury
or death. Prevent accidental starting by
disconnecting the negative (–) cable from the
battery terminal.
FIGURE 7.1 Po P1 Appropriate frame and type of connection is used to meet the application
requirements in terms of single phase three phase, 50 Hz, 60 Hz temperature rise and the KVA rating
page 39
Power Start 0500
X1.3 & X2.5 Engine
7.2 GENERATOR/BASE BOARD
ISOLATION PROCEDURE
The following procedure is used to determine if the
generator or the control Base board is causing a high
AC voltage shutdown fault.
1. Throw the line circuit breaker OFF and
shutdown the set.
CAUTION
This
test
involves
unregulated excitation of the generator. To
prevent dam-age to the generator due to
over current, make sure that all loads have
been disconnected and that all faults have
been cleared from the power output
terminals of the generator.
WARNING HAZARDOUS
VOLTAGE.
Touching Un-insulated parts inside the
control housing and power output boxes
can result in severe personal injury or
death. Measurements and adjustments
must be done with care to avoid touching
hazardous voltage parts.
Stand on a dry wooden platform or rubber
insulating mat, make sure your clothing and shoes
are dry, remove jewelry and use tools with
insulated handles.
2. Remove the side access cover of the control
housing to access the exciter stator leads (X
and XX). Disconnect the X and XX leads from
the AC harness (quick connect type
connectors).
3. Prepare to measure output voltage across the
generator terminals while the set is running.
page 40
Publication A029U889
Issue 3 - 8-2017
4. Bring two jumpers from a 12 volt battery for
connection to the exciter stator X (Field +) and
XX (Field –) leads.
Connect the jumper from the positive (+) post of the
battery to the X lead. Be prepared to connect the
jumper from the negative (–) post oft he battery to the
XX leads. If one of the 12 volt cranking batteries is
used, bring the jumpers from the battery connected on
the grounded side of the system to avoid inadvertently
imposing 24 volts on the system.
5. Check polarity again. Polarity must be
corrector this test will be inconclusive because
the induced and residual magnetic polarities in
the exciter stator will be opposed.
Genset may shut down on a fault condition
with in 5 to15 seconds due to the exciter stator
leads being disconnected from the Base
board. Clear fault and start genset to check
next phase.
6. Start the set and connect the jumper from the
battery negative (–) terminal to the XX lead.
7. The generator circuitry is probably okay if
rated output voltage or higher is obtained and
the voltages for all phases are balanced when
the exciter is powered by a 12 volt battery.
Refer to Section 4to troubleshoot the PCC
control circuitry. (Normal excitation voltage
ranges from approximately 10 VDC at no-load
to approximately 40 VDC at full–load.)
8. If the voltages are unbalanced, trouble shoot
the main stator first. If the voltages are
uniformly low, troubleshoot the exciter and
field circuits first.
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
7.3 EXCITER STATOR
Testing Winding Resistance:
Measure winding resistance with a stone bridge or
digital ohm-meter. Replace the stator if winding
resistance is not as specified by Table 7-2.
Testing Winding Insulation Resistance:
Disconnect the exciter stator leads X and XX from their
connectors in the AC harness and isolate them from
ground. Using an ohmmeter, measure resistance
between either lead and the stator laminations. Re-place
the stator if insulation resistance is less than 1megohm
(1,000,000 ohms)
Flashing the Field (Self-Excited Generators Only): If
necessary, flash the exciter field before or after
installation. Apply 110 to 220 VAC for one to two seconds
to the X and XX leads of the exciter stator.
The generator must be shut down, the Baseboard
disconnected, a diode used to establish correct
polarity and a 3 amp fuse to prevent over-excitation.
See the diagram.
Alternatively, while the set is running and disconnected
from all loads, apply a 12 VDC battery for one to two
seconds as shown in the diagram.
Polarity must be correct: + to X, – to XX.
FIGURE 7-2. TESTING AND FLASHING THE EXCITER STATOR
page 41
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
7.4 EXCITER RECTIFIER BRIDGE
(Rotating Rectifier Assembly)
The exciter rectifier bridge is mounted on the exciter
rotor, inboard, facing the main rotor. It consists of a
positive plate and a negative plate, split diametrically.
Each carries three diodes, three terminal posts for
connecting exciter rotor leads to the diode pig-tails and
a terminal for the main rotor (generator field) lead. A
surge suppresser is connected across the two plates
to prevent transient voltages that could damage the
diodes.
Testing Diodes: Disconnect the diode pigtails from the
terminal posts. Using an ohmmeter, measure electrical
resistance between each diode pigtail and the plate on
which the diode is mounted. Reverse the meter test
probes and repeat the tests. The electrical resistance
across each diode should be high in one direction and
low in the other. If the resistance is high or low in both
directions, replace the diode.
Replacing Diodes: Make sure the replacement diode
is of the correct polarity. Disconnect the pig tail from
the terminal post and unscrew the old diode. Apply
heat-sink compound under the head of the diode.
Make sure the compound does not get on the threads.
Torque the diodes to 36 to 42 in-lbs (4 to 4.8Nm) and
the pigtail terminals to 24 in-lbs (2.7 Nm) when
reassembling.
Surge Suppresser Testing and Replacement:
Remove the suppresser. Replace the suppresser if it
appears to have overheated or if ohmmeter readings
indicate less than infinite resistance (end of scale) in
both directions. Torque the terminals to 24in-lbs (2.7
Nm) when reassembling.
CAUTION
Layers of dust can cause
diodes to overheat and fail. Brush dust off
regularly.
FIGURE 7–3. TESTING THE ROTATING RECTIFIER ASSEMBLY
page 42
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
assembly if the resistance of any winding is not as
specified in Figure 7-4.
Exciter Rotor
Testing Winding Resistance:
Testing Winding Insulation Resistance:
Disconnect the six rotor winding leads from the
terminal posts on the rectifier assembly. With a
Wheatstone bridge, mea-sure electrical resistance
across each pair of rotor windings: U (CR1 or CR4)
and V (CR2 or CR5), V(CR2 or CR5) and W (CR3 or
CR6), W (CR3 orCR6) and U (CR1 or CR4). See the
winding schematic. Replace the whole rotor shaft
Using an ohmmeter, measure the resistance between
any rotor winding lead or the terminal to which it is
connected and the rotor laminations. Replace the
whole rotor shaft assembly if insulation resistance is
less than 1 megohm.
FIGURE 7–4. TESTING THE EXCITER ROTOR
page 43
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Main Rotor (Generator Field)
Testing Winding Insulation Resistance
Testing Winding Resistance:
Using an ohmmeter, measure the resistance between
either lead of the main rotor windings, or the terminal
to which it is connected, and the main rotor
laminations. Replace the rotor if insulation resistance
is less than 1 mega ohm.
Disconnect the two leads of the main rotor from the
terminals on the rotating rectifier assembly. See
Figure 7-5. Measure electrical resistance between the
two leads with a Wheatstone bridge or digital
ohmmeter. Replace the rotor if the resistance is not
as specified in Table 6-1. Connect the rotor leads and
torque the terminals to 24 in-lbs (2.7 Nm) when
reassembling.
NOTE : Incorrect resistances indicate faulty windings
and component replacement is necessary.
FIGURE 7–5. TESTING THE MAIN ROTOR
page 44
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
7.5 MAIN STATOR
Testing Winding Resistance:
Measure electrical resistance across each pair of stator
leads (U1-U2, U5-U6, VI-V2, V5-V6, W1-W2 and W5W6) with a Wheatstone bridge or ohmmeter having at
least0.001 ohm precision. Replace the stator if the
resistance of any winding is not as specified in Table6-1.
Alternatively, winding resistance can be measured lineto-line at the generator terminals (U-V, V-W,W-U)on
“star” connected generators. On a 600 volt generator,
line-to-line resistance should be twice the table value
(two winding elements in series). On a “series star”
connected generator, line-to-line resistance should be
four times the table value (four winding elements in
series).
On a “parallel star” connected generator, line-to-line
resistance should be the same as the table value (two
sets of two winding elements in series). Single phase
only windings can be measured at W-V and should be
twice the table value.
Testing Winding Insulation Resistance:
Disconnect the AVR completely, (AT THE AVR), before
carrying out this test. Disconnect any connections from
Neutral to Earth.The Stator insulation should be checked
with an Insulation tester. The test instrument should be
500 or 1000 volts for low voltage Generators (up to
690V). For low voltage machines (up to 690V), the
MINIMUM insulation value is 1.0 Meg-Ohm to Earth
(Ground).
WINDINGS MUST BE DRIED OUT IF
BELOW 1.0 MEG-OHM.
NOTE Faults on the stator winding or cables may
also cause noticeable load increase on the engine
when excitation is applied.
FIGURE 7.6 TESTING THE GENERATOR STATOR
page 45
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Main Excitation Windings:
If after establishing and correcting any fault on the rectifier assembly the output is still low when separately excited,
then the main rotor, exciter stator and exciter rotor winding resistances should be checked (see Resistance Charts),
as the fault must be in one of these windings. The exciter stator resistance is measured across leads F1 and F2.
The exciter rotor is connected to six studs, which also carry the diode lead terminals. The main rotor winding is
connected across the two rectifier plates. The respective leads must be disconnected before taking the readings.
Resistance values should be within 10% of the values given in the table below
ALTERNATOR FRAME SIZE
P044D
Main Rotor (Ohms)
0.437
Exciter stator (Ohms)
17.5
Exciter Rotor (Ohms)
0.211
P044E
0.415
17.7
0.211
P044F
P044G
P044H
P144D
P144E
P144F
P144G
P144H
P144J
P144K
0.465
0.551
0.545
0.657
0.67
0.708
0.857
0.89
0.983
0.99
18.5
18.5
18.5
18.5
19.36
20.25
22.25
22.9
22.9
22.9
0.228
0.228
0.228
0.228
0.215
0.201
0.201
0.21
0.21
0.21
Main Stator Resistance
ALTERNATOR FRAME SIZE
Main stator winding resistances (Ohms)
Windings
P044D
12 Lead Reconnect able*
P044E
1.33
P044F
0.95
P044G
0.625
P044H
0.51
P144D
P144E
0.353
1.908
0.3
*- Note :These Windings are referred by the alternator Manufacturer as “311” Winding no.
page 46
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
7.6. GENERATOR DISASSEMBLY
The generator is heavy. You will need an assistant and a
hoist of sufficient capacity to remove and service the
generator.
WARNING
Accidentally
dropping
the
generator can damage it and cause severe personal
injury and death. The hoist, straps and chains must
have sufficient capacity and be attached properly so
that the load cannot shift.
Before starting, disconnect the negative (–) cable from
the battery to make sure the set will not start while
working on it.
WARNING
Ignition of explosive battery
gases can cause severe personal injury or death. Arcing at battery terminals, light switch or other
equipment, flame, pilot lights and sparks can ignite
battery gas. Do not smoke, or switch trouble light ON
or OFF near battery. Discharge static electricity from
body before touching batteries by first touching a
grounded metal surface.
Ventilate battery area before working on or near
battery—Wear goggles—Stop genset and disconnect
charger before disconnecting battery cables—
Disconnect negative (–) cable first and reconnect last.
CAUTION
Disconnect battery charger from
AC source before disconnecting battery cables.
Otherwise, disconnecting cables can result in voltage
spikes damaging to DC control circuits of the set .
WARNING
Accidental
starting
of
the
generator set can cause severe personal injury or
death. Prevent accidental starting by disconnecting
the negative (–) cable from the battery terminal.
Removing The Generator Control Housing
1. Disconnect the line cables and conduit. For
reconnections later, make sure each cable is
clearly marked to indicate the correct terminal.
2. Disconnect the remote control wiring and conduit.
For reconnections later, make sure each wire is
clearly marked to indicate the correct terminal.
3. Disconnect all engine wiring harness connections
in the generator control and output boxes. For
reconnections later, make sure each wire is
clearly marked to indicate the correct terminal.
4. Disconnect all generator control leads (winding
taps) from connections in the output box. For
reconnections later, make sure each wire is
clearly marked to indicate the correct terminal.
5. If the set has a mounted line circuit breaker,
disconnect the cables to the circuit breaker. For
reconnections later, make sure each cable is
clearly marked to indicate the correct terminal.
6. Attach a hoist to the generator output box, loosen
the mounting bolts on the sides of the generator
and remove the box.
Withdrawing The Generator From The Set
CAUTION
Do not use fan blade to bar over
engine. That can damage blades and cause property
damage and personal injury.
1. The rotor will be carried inside the stator when
the generator is withdrawn from the engine. Bar
the engine until one of the four poles of the rotor
points straight down so that the rotor will rest on
the face of the pole when the generator is
withdrawn.
2.
CAUTION
The rotor can be damaged if it
rests on the edges of the winding slot between two
poles.
2. Attach lifting eyes and a hoist of sufficient
capacity (Figure 6-7).
3. Take up hoist slack and remove the two through
bolts securing the generator to the rubber
isolation mounts.
4. Raise the generator end approximately one inch
(12 mm) and securely block the engine under the
flywheel housing. Lower the generator slightly so
that the blocks carry most of the weight.
5. Remove the bolts securing the generator drive
discs to the flywheel.
6. Loosen all the bolts securing the generator
adapter casting to the flywheel housing. Adjust
the hoist to carry the full weight of the generator,
remove the bolts and pull the generator away.
Never withdraw the generator leaving the rotor to
hang by the drive discs. The weight of the rotor will
damage the drive discs.
page 47
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
25
CINCH STRAP AROUNDTHE
MIDDLEOF THE ROTOR
FIGURE 7-7. GENERATOR ASSEMBLY
page 48
Power Start 0500
X1.3 & X2.5 Engine
SECTION 8 – WITHDRAWING THE ROTOR
FROM THE GENERATOR
1.
Remove the generator adaptor casting on the drive
disc end and the end plate on the bearing end.
2. Using a hoist of sufficient capacity, cinch a lifting
strap on the drive end of the rotor. Lift the bearing
end of the rotor by a Eye Bolt and push it towards
the drive end of the generator until half the width of
the rotor core protrudes from the stator. Release
the weight of the rotor and recinch the lifting strap
around the middle of the rotor core. Withdraw the
rotor until it is free of the stator, guiding it by
Publication A029U889
Issue 3 - 8-2017
hand on both ends to prevent contact with the
stator windings
3. Rest the rotor in a cradle, solidly supporting it
on two pole faces—not on the drive discs,
blower or exciter.
4. Remove the retaining clip if the rotor shaft
bearing is to be removed.
8.1 Generator Reassembly
Reassembling is the reverse of disassembling. Note
the following. The Assembly Torques are specified in
the succeeding page.
page 49
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Generator Assembly Tools and Torque Values
Part Description
Earth lead to NDE bracket
EBG Str Hsg to NDE bracket
EBG Str to EBG Str Hsg
Excitor stator to NDE bracket
Stator Lead to terminal studs
Diode fitting
Small Terminal box to NDE bracket
EBG Rtr to shaft
Coupling disc to flywheel
DE Adaptor to Flywheel housing
Clamping spacer to rectifier hub
Rectifier hub to excitor rotor core
Rotor leads to Clamping spacer
EBG Housing cover to housing
Terminal block to NDE bracket
Varistor to rectifier hub
AVR cover to NDE bracket
AVR to NDE bracket
Axial air inlet cover to NDE bracket
DE Air outlet cover
Fan to fan hub 290 and 344
Radial Inlet cover to Nde bracket
Terminal box lid to terminal box
Coupling disc to shaft
Tool
Torque value Nm
10mm socket head box screw driver or 10mm
socket
6
10
10
10
6.5
11mm socket head box screw driver / Crimping
Tool
150mm long x 8mm socket or 8mm socket head
box screw driver
17mm socket
17mm socket x 60mm long( non-standard)
17mm socket x 75mm long(STD.)
8 mm socket
8mm open type spanner
8mm socket head box screw driver or 8mm socket
8mm socket with Allen key bit.
2.8/3.6
5
50
51
51
2.8/3.6
2.8/3.6
2.8/3.6
6.5
5
2.8/3.6
5
5
5
6.5
5
5
5
75
DE Adaptor to frame blocks
T' type wrench with extension rod and 13mm
socket
26
NDE bracket to Frame blocks
T' type wrench with extension rod and 13mm
socket
26
page 50
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
GENSET SPECIFICATIONS
3-Phase Ratings
50 Hz
Model
Standby
Prime
kW (kVA)
kW (kVA)
C8D5
6.6 (8.25)
6 (7.5)
C11D5
8.8 (11)
8 (10)
C17D5, C17D5 (Spec E)
13 (16.5)
12 (15)
C22D5, C22D5 (Spec E)
17 (22)
16 (20)
C28D5, C28D5 (Spec E)
22 (27.5)
20 (25)
60 Hz
Model
Standby
Prime
kW (kVA)
kW (kVA)
C12D6, C12D6 (Spec E)
12 (15)
11 (13)
C16D6, C16D6 (Spec E)
16 (20)
15 (18)
C20D6, C20D6 (Spec E)
20 (25)
18 (22)
Generator set specifications:Governor regulation class
ISO8528 Part 1 Class G2
Voltage regulation, no load to full load
±
1%
Random voltage variation
±
1%
Frequency regulation
Droop
Random frequency variation
± 0.25%
page 51
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Engine specifications
X1.3
Design
4 cycle, in-line, naturally aspirated
X2.5
4 cycle, in-line, naturally aspirated
Bore
95mm (3.74 in)
91.44mm (3.6 in)
Stroke
91mm (3.58 in.)
127mm (5 in)
Displacement
1.3 liter (78.72 in.³ )
2.5 liter ( 152.56 in.³ )
Cylinder block
Alloy Cast iron, In-line, 2 cylinder
Alloy Cast iron, In-line, 2 cylinder
Battery capacity
32 Ampere-Hour
63 Ampere-Hour
Battery charging alternator
N/A
N/A
Starting voltage
12 volt, negative ground
12 volt, negative ground
Fuel system
Direct injection: Number 2 diesel fuel
Direct injection: Number 2 diesel fuel
Fuel filter
Single element, Spin-on fuel filter cum Water
Separator, Filtration efficiency 25 micron
99%(min) ,Water Separation efficiency 90%
(min)
Single element, Spin-on fuel filter cum Water
Separator, Filtration efficiency 25 micron
99%(min) ,Water Separation efficiency 90%
(min)
Air cleaner type
Dry replaceable element
Dry replaceable element
Spin on full flow filter , Filtration efficiency 25
micron 99%(min)
122°F (50°C) ambient radiator with coolant
Recovery System
Spin on full flow filter , Filtration efficiency 25
micron 99%(min)
122°F (50°C) ambient radiator with coolant
Recovery System
Lube oil filter type(s)
Standard cooling system
Alternator specifications
Design
Brushless, 4 pole, revolving field
Stator
2/3 pitch
Rotor
Single bearing, flexible disc
Insulation system
Class H
Standard temperature rise
163 ºC standby @ 27 ºC ambient
Exciter type
Torque match (shunt) standard, EBS optional EBS(Excitation Boost System)
Phase rotation
A (U), B (V), C (W)
Alternator cooling
Telephone influence factor (TIF)
Shaft mounted centrifugal fan
THD < 1.8 % on no-load and < 5 % under non-distorting
balanced linear load
< 50
Telephone harmonic factor (THF)
< 2%
AC waveform total harmonic distortion
Available voltages
50 Hz line–neutral/line-line ( Std Voltage -)
230/400
(STD)
240/416
220/380
127/220
138/240
254/440
265/460
277/480
120/208
133/230
Generator set options and accessories
Engine
Alternator
Control panel
Generator set
0
ˆ 208/240/480 Volt coolant
heater.
Exhaust system
page 52
ˆ 105 C Temp Rise Alternator
ˆ Shunt Trip
ˆ 125°C Temp Rise Alternator
ˆ Auxiliary Contacts
ˆ 150°C Temp Rise Alternator
ˆ Earth Fault Relay
ˆ EBS (Excitation Boost System)
ˆ 120/240 V, 25 W, anticondensation heater.
ˆ Standard Residential Grade exhaust Silencer
ˆ Heavy Duty Air Cleaner
ˆ Electronic Governing
ˆ Battery Charger
ˆ 1500 /3000 hours Maintenance Kit
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
SECTION 9 - WIRING DIAGRAMS
9.1 GENERAL INFORMATION
This section consists of the schematic and connection
wiring diagrams referenced in the text. The following
drawings are included.
•
•
•
•
•
•
•
Page 54, 3 Phase Reconnect Wiring Diagram
Page 56, 1 Phase NON Reconnect Wiring
Page 57, Wiring Diagram
Page 58, Battery Charger and Coolant Heater
Connections (optional)
Page 59, 3 Phase - Mechanical Governor wiring
Page 122, Engine Harness Jumper (PC2100
to PCC1302)
Page 123, Customer Connections
NOTE: P1 Alternators for X1.3 have Winding 311 for 3
phase for 50 05/06 Winding for 50/60 Hz Single phase
respectively.
NOTE: The Wiring Drawings are representative
drawings.
For service, use drawing supplied with geneset pasted
on the backside of the door of the pedestal panel
The Drawings can be downloaded from the PGBU
Engineering Database.
page 53
Power Start 0500
X1.3 & X2.5 Engine
3 Phase Reconnectable, 12 Lead CT Secondary Connection
NOTE: Sense Lead N is Not Used. Tape End and
Tie Back .
page 54
Publication A029U889
Issue 3 - 8-2017
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
3 Phase Reconnectable, 12 Lead CT Secondary Connection (continued)
8–3
page 55
Power Start 0500
X1.3 & X2.5 Engine
1 Phase NON -Reconnectable, 4 Lead CT Secondary Con
page 56
Publication A029U889
Issue 3 - 8-2017
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
9.2 WIRING DIAGRAM
Wiring diagram for X1.3 generator set
page 57
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Wiring diagram for X2.5 generator set
page 58
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
9.3 BATTERY CHARGER AND COOLANT HEATER CONNECTIONS (optional)
page 59
Power Start 0500
X1.3 & X2.5 Engine
page 60
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
Publication A029U889
Issue 3 - 8-2017
page 61
Publication A029U889
Issue 3 - 8-2017
Power Start 0500
X1.3 & X2.5 Engine
9.4 CUSTOMER CONNECTIONS
page 62
page 63
power.cummins.com
Copyright E 2017 Cummins Inc. All rights reserved.
Cummins, the “C” logo, PowerCommand, AmpSentry, and InPower are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.
Descargar