PGFC22 60Hz POWERED BY POWERGEN TECHNICAL SPECIFICATIONS DIESEL GENERATING SET 220/127V-60Hz-3Phase Model PGFC22 Power(ESP) kVA/kw 28/22 Power(PRP) kVA/kw 25/20 Starter Voltage V 12 Rated Current A 73 r/min 1800 Rated rotation speed 0.8 Power Factor Fuel Consumption g/KWh 240 Fuel Tank Capacity L 88 ; 121 dB(A)@7m ≤ 68 Dimension ( L*W*H ) Weight Noise level WEIGHT AND DIMENSIONS GEN-Set Open Type 1320mm×700mm×1160mm 521Kg Silent Type 1856mm×826mm×1415mm 766 Kg STANDARDS: Genset: GB/T2820—2009,ISO8528 CONFIGURATION: Alternator: CEDEX, CX18 Standard: Engine, alternator, cooling system, Base frame (excluding Diesel Engine: FAWDE , 4DW91-38D fuel tank), shock absorber, air inlet system, control box (including mains Standby Power: Continues running at variable load for duration of an floating charge), plastic fan blades (when the engine and water tank do not emergency. No overload is permitted on these ratings. bring). Optional: Base frame (including fuel tank), water jacket heater, Prime Power: Continues running at variable load for unlimited periods fuel water separator, fuel heater, fuel level sensor (only supporting with 10% overload available for 1 hour in any 12 hour period. underframe tank), switch box (with switch), power switch, the water level sensor, motor anti condensation heater, automatic fueling system (only supporting base frame including fuel tank), battery frame. Accessories: Silencer, bellow, exhaust silencing system accessories (with the matching engine), regular battery, starting cord assembly, data of genset,random tool ENGINE Specification Manufacturer: FAWDE Model Engine speed Rated Cylinder /Arrangement Displacement Bore and Stroke 4DW91-38D 1800 RPM 4/ L 2.54 L 90 mm×100 mm Compression ratio 17 :1 Max. stand by power at rated RPM 31 KW Frequency regulation , steady state Governor : type Aspiration and Cooling ≤5% Mechanical / Electronic Naturally aspirated, water cool Exhaust System Exhaust gas flow Exhaust temperature Energy to exhaust 6.6m³/min 560℃ 28.6KW Fuel System Fuel consumption100% (of the Prime Power) 240g/KWh Fuel consumption75% (of the Prime Power) Fuel consumption50% (of the Prime Power) Fuel consumption25% (of the Prime Power) Oil system Total oil capacity w/filters 8L FAWDE engines with optimized design, easy maintenance, big power density, with stable performance, reliable and durable. Low fuel consumption and emission, lower noise and smooth running. Parts commonality, seriation of engine application. Compact structure, easy maintenance. Note: All data sheets are for reference only and subject to change without prior notice. ALTERNATOR Specification Manufacturer: CEDEX Type Number of phase power Factor (Cos Phi) CX18 3 0.8 Pole 4 Bearing 1 Coupling Direct Exciter type Brushless SHUNT lnsulation : class , temperature rise H/H Degree of protection IP23 Altitude ≤1000m Winding Pitch 2/3 Winding Leads 6/12 FEATURES Class H insulation system selectable winding,To meet the demand of the bad environment 12 Lead Reconnect, able for different voltage, meet the demand of different countries and regions 2/3 pitch windings restrain the content of harmonious Different Excitation Systems for different load demand Ip23 standard protection,IP44 for option Provide single bearing or double bearing STANDARDS -IEC60034,NEMA MG1-32,ISO8528,CSA C22.2-100,VDE 0530,GB755 Note: All data sheets are for reference only and subject to change without prior notice. Control Panel Model: AMF 20 AUTOMATIC MAINS FAILURE CONTROLLER InteliLite® controllers are equipped witha powerful graphic display. Icons,symbols and bar graphs for intuitiveoperation together with high functionalityset new standards in gen-set control. Special low temperature (IL-AMF 20-LTor IL-AMF 25-LT) version is alsoavailable, allowing the display to workup to -300C. KEY FEATURES Support of engines equippedwith Electronic Control Unit - Over-/under voltage (J1939interface) - Voltage asymmetry Comprehensive diagnostic messages;SPN/FMI codes; Configurable analog inputs KWP2000 support Battery voltage, engine speed(pick-up) measurement Automatic or manual start/stop of thegen-set Configurable programmable binaryinputs and outputs Push buttons for simple control, lamptest Warm-up and cooling functions Graphic back-lit LCD display128x64 pixels Generator C.B. and Mains C.B.control with feedback and 6 LED indicators Parameters adjustable via keyboardor PC Mains measurements (50/60 Hz):U1-U3, Hz Generator measurements (50/60 Hz):U1-U3, I1-I3, Hz, kW, Modem communication support(IL-AMF 25 only) kVAr, kWh Dimensions 180x120 mm (front panel) Selectable protections alarm/shutdown Sealed to IP65 3 phase Generator protections returntimer IL-AMF 20) KEY BENEFITS - Over-/under voltage RS232 interface (AT-LINK CONVcable is necessary for - Over-/under frequency Less wiring and components - Current/voltage asymmetry Integrated solution - Overcurrent/overload Less engineering and programming 3 phase AMF function Perfect price/performance ratio - Over-/under frequency