Section 6
Molded Case Circuit Breakers
Contents
6/2
Pressure and Compression Connectors
Catalog Numbering System
6/4
Breaker Modifications
6/73
Applicable Standards
6/4
Internal Accessories - Feature Combinations
6/74
External Accessories
6/75
What’s New in Circuit Breakers
Reference Guides
Panelboard Mtg Circuit Breakers BL, GFCI, AFCI
6/5
6/13
6/70
General Technical
BQ 125A Frame, Switching Neutral, DIN Rail
6/17
Enclosed Circuit Breakers
6/81
QJ 225A Frame
6/19
Series Rated Combination Guide
6/89
CQD 100A Frame and NGG 125A Frame
6/20
Unusual Operating Conditions
Sentron Thermal Mag and Electronic Circuit Breakers
ED 125A Frame and Internal Accessories
6/23
FD 250A Frame and Internal Accessories
6/26
JD/SJD 400A Frame and Internal Accessories
6/29
LD/SLD 600A Frame and Internal Accessories
6/33
LMD 800A Frame and Internal Accessories
6/37
MD/SMD 800A Frame and Internal Accessories
6/40
ND/SND 1200A Frame and Internal Accessories
6/44
PD/SPD 1600A Frame and Internal Accessories
6/48
RD 2000A Frame and Internal Accessories
6/51
STD 3200A Frame and Internal Accessories
6/53
Magnetic Trip Only—ETI Motor Circuit Protector
6/55
Adjustable Instantaneous Magnetic Trip Settings
6/58
Molded Case Switch—Circuit Disconnect
6/61
Sensitrip III Digital Solid State Sentron Series
6/62
SB Encased System Breakers
6/64
Electronic and Communications Accessories
6/68
6/99
Typical Specifications
6/101
Superseded Circuit Breakers
6/102
6
Molded Case Circuit Breakers
INTRODUCTION
What’s New?
With this Speedfax, Siemens Canada
Limited is proud to announce several new
products. These new concepts serve the
OEM and power distribution markets.
CE Marking
A wide range of Sentron® thermal
magnetic circuit breakers has been fully
tested for compliance with the European
community’s Low Voltage Directive,
and carry the CE mark, indicating their
compliance with that directive. These are
noted in the Speedfax with the stylized
CE in watermark behind the catalog
numbers. Declarations of conformity
are available for these products. A point
of misunderstanding lies in the area of
handle operators. A handle operator
alone, such as that for the Max-flex,
since there is no applicable European
Directive, may not carry the CE mark. The
mark is affixed to the finished equipment
that incorporates the handle, but not to
this component device.
Sensitrip Ammeter Display Unit
Volts or lower. These very reliable low
level switches overcome that limitation.
Standard switch contacts should, of
course, continue to be used in standard
current and voltage applications
DIN Rail mounted 120/240 V Breaker
The Siemens BQ breakers are now
available in 1- and 2-pole construction,
from 15 to 60 Amps in lug in – lug out
DIN rail mounted configuration. These
breakers, rated 120/240 Volts, are ideal
for applications in control panels and
HVAC, and with their available finger safe
terminal shields can qualify as service
disconnects.
QJ Walking Beam Interlock
Potter & Brumfield Discontinued
With SE&A’s divestiture of Siemens
Electromechanical Components, we have
ceased offering the Potter & Brumfield
line of supplementary Protectors.
NGG Type 125A Frame Circuit Breaker
The new NGG Circuit Breaker is a
compact, industrial design with true
value-added features such as Global
Ratings (UL/CSA/IEC/CE/NOM), flexible
DIN or base mounting without the need
for adapters and UL Listed for field
installable accessories. This NGG125 has
a 25KAIC interrupting rating at 480VAC
and features a Quick Make/Quick Break
Trip-free Mechanism. All this in a 3.0W x
4.8H x 2.8D package. Please consult your
sales office for availability.
Enhanced SB ICCB
6
CIRCUIT
BREAKERS
The Ammeter display for the Sensitrip®
electronic trip family of breakers brings
a new level of diagnostic capability even
to non-interconnected breakers. Having
an internal clock calendar, it can record
the date and time of each trip event that
occurs. Other products rely on being
connected in a full network to time stamp
events. This exclusive patented Siemens
device provides current metering and
breaker-trip diagnostic information
without expensive networks.
PLC Level Auxiliary Switches
A new family of gold flashed auxiliary
switches for the FD through ND breakers
allows sensing at very low voltage
and currents for interface directly to
programmable logic controllers and
other electronic devices. Standard
contacts, built to switch 120 Volts and
higher currents can be unreliable when
the sensing current is in the milliamp
range, and the sensing voltage is 12
6/2
Answering the growing need for 120/240
and 240 Volt standby power systems,
Siemens introduces the walking beam
interlock for the QJ family of 240 Volt
circuit breakers. Useful in the cell tower
and other commercial applications, the
QJ walking beam allows interlocking two
2 pole beakers mounted using only 4 pole
widths, or two 3 pole breakers using 6
pole widths.
There have been several functional
enhancements to the SB Systems
Breaker since the last issue of the
Speedfax. These include:
■ Improved reliability, including regular
monthly breaker endurance testing
to 8,000 operations, a new Electronic
Motor Operator tested to 12,000
operations, and improved secondary
disconnects
■ Extended 2 Year Standard Warranty
Molded Case Circuit Breakers
INTRODUCTION
Ordering
In the FD through RD frames, you may
order molded case circuit breakers three
basic ways:
■ As separately ordered frames, trip units
and lugs
■ As frame, trip unit and lugs ordered
as one catalog number and shipped
unassembled or assembled
Components Ordered Separately
To get the components for a 3 pole,
400 Amp standard interrupting circuit
breaker, you would order the frame
(JD63F400), the trip unit (JD63T400)
and six lugs (TA2J6500). This option is
normally useful only if you stock and
use large volumes of product and wish
to reduce your inventory cost. You may
stock, for example, a smaller number of
frames (JD63F400) and a variety of trip
units (JD63T300, JD63T350, etc.) and
assemble breakers as you need them.
Frame, Trip Unit and Lugs Ordered
Together
If you order the catalog number
JD63B400, you will receive a frame, a
trip unit and 6 lugs in separate packages.
By suffixing this number with “L” (e.g.
JD63B400L), you will receive frame, trip
unit and lugs assembled in one container.
Pursuant to UL 489, a product ordered
thus will have the markings “LINE” and
“LOAD”, and may not be “reverse fed”
(with power flowing from the “OFF” end
of the breaker toward the “ON” end).
Connecting Breakers for DC
Application
Most Siemens thermal magnetic trip
MCCBs are applicable on direct current
(dc) systems. Generally, for 250 V dc
systems a two pole breaker is used, with
one pole on each leg of the supply circuit.
For three pole breakers applied on 500
V dc systems, it is important to connect
the power supply “zig-zag” through the
breaker as shown in the figure below.
This assures that the Voltage between
phases on the breaker terminals is
uniformly distributed.
500V DC Wiring Configuration
6
As Frame and Trip Unit shipped
assembled and with the trip unit made
non-removable, in compliance with UL
489 requirements that to be reverse fed
the circuit breaker must not have an
interchangeable trip unit.
These two options are described in the
following
■
Non-Interchangeable Trip Breakers
If you place an “X” after the frame size
designator (e.g. JXD63B400), you will
receive a frame and trip unit assembled,
with the trip unit made non-removable. If
you suffix an “L” to this catalog number
(e.g. JXD63B400L), you will recieve the
breaker, non-removable trip unit and
lugs assembled. Unless you anticipate
a specific need to change the breaker’s
ampere rating in the future, this is
the preferred ordering method, as the
products are assembled to Siemens’
specifications in our factories. These
breakers are suitable for use reverse fed
according to UL 489, since the trip unit is
not removable.
The smaller frames (QJ, ED and below)
do not have removable trip units, and
consequently are shipped only as
assembled products. To add lugs, see the
ordering instructions on each product’s
catalog page.
CIRCUIT
BREAKERS
New OEM Accessories, including a Bell
Alarm and Alarm Relay Combination
Module (SBBADMRxx), providing an
alarm-only relay contact for alarms such
as Ground Fault Warning and a latching
alarm relay contact for trip indication.
■ Local Bell Alarm Reset (SBLBAR),
providing a reset button on the breaker’s
escutcheon for locally resetting the
latching bell-alarm relay contact.
■ New external power supply (SPEPS24)
for the EC Trip Unit, allowing operation
with 24 or 48 VDC control power.
■ Price competitive, high-tech EC Trip Unit
now provides phase-loss, Type-1 and
Type-2 protection for switchboards.
The enhanced SB Breaker, backed by a
two year warranty and spearheaded by
the EC Trip Unit, is continuing to improve
its strong position in circuit protection
and power quality applications
LDU – Local Display Unit
Expanding the metering capabilities of
Siemens circuit breakers, the new LDU
provides a central display for SB Insulated
Case Circuit Breakers (both TL and EC
Trip Units), Sensitrip III Molded Case
Circuit Breakers, and 4300 Power Meters
(now provided with or without individual
displays). Capabilities include:
■ Panel-mounting for switchboard and
OEM applications
■ A competitive solution when power
metering is required for multiple
breakers
■ Saves panel space by utilizing a
centralized display to enable several
4300 Power Meters without displays
to be mounted in a single section or
wire gutter to monitor several branch
breakers
■ Economical method of communicating
power metering data of up to 32 devices
■ Compatible with WinPM 5.0 and DTU
Protocol Converters
■
6/3
Molded Case Circuit Breakers
REFERENCE
Catalog Numbering System
If used on 250A frame and above means non-interchangeable trip
breaker with factory assembled frame and trip. Solid state trip and
current limiting (S or C in first character) are non-interchangeable
only, and the “X” is omitted.
X D
Trip Unit Type
— Omitted – Thermal-Magnetic
S — Sensitrip® Electronic Trip
Sentron Series Type/Interrupting Range
— Omitted – Standard Rating
H — High IC Rating
HH — Extra High IC Rating
C — Highest IC Rating and Current Limiting
Frame Identifier
E — Type ED
F — Type FD
J — Type JD
L — Type LD
LM — Type LMD
M
N
P
R
T
— Type MD
— Type ND
— Type PD
— Type RD
— Type TD
Maximum Voltage
2 — 240 Vac
4 — 480 Vac
6 — 600 Vac
Number of Poles
1
2
3
9 used to indicate the max. functions for an electronic trip circuit breaker (always 3 poles)
(Specific Application Type)
B — Standard 40°C Breaker
M — Calibrated for 50°C Application
F — Frame Only
T — 40°C Trip Unit Only
W — 50°C Trip Unit Only
S — Molded Case Switch
L — Low Instantaneous Range ETI Breaker
A — Standard Range ETI Breaker
H — High Instantaneous Range ETI Breaker
6
CIRCUIT
BREAKERS
Maximum Continuous Current Rating
ED Frame — 015, 020, 025, 030, 035, 040, 045, 050, 060, 070, 080, 090, 100, 110, 125
FD Frame — 070, 080, 090, 100, 110, 125, 150, 175, 200, 225, 250
JD Frame — 200, 225, 250, 300, 350, 400
LD Frame — 250, 300, 350, 400, 450, 500, 600
LMD Frame — 500, 600, 700, 800
MD Frame — 500, 600, 700, 800
ND Frame — 900, 100 (1000A), 120 (1200A)
PD Frame — 120 (1200A), 140 (1400A), 160 (1600A)
RD Frame — 160 (1600A), 180 (1800A), 200 (2000A)
TD Frame — 2000, 2500, 3200
Suffix
L — where applicable indicates a breaker shipped with line/loads lugs installed
A — used with a switch to show automatic self protection
Y — 400 Hertz
H — 100% rated
NOTE:
— Position omitted if not used.
Applicable Standards
UL489 — Molded Case Circuit Breakers
and Circuit Breaker Enclosures.
UL486A — Wire Connectors and
Solderless Lugs for use with copper wire
UL486B — Wire Connectors and
Solderless Lugs for use with
aluminum wire
UL943 — Ground Fault Interrupters (for
personnel protectors)
UL1087 — Molded Case Switches
UL50 — Cabinets and Boxes
Note:
(A) Molded case circuit breakers are designed and tested
in accordance to applicable portions of UL489 and CSAC22.2
No 5 and meet application requirements of the National
Electric Code. Unless marked otherwise, circuit breakers are
80% duty rated.
(B) Molded case circuit breakers are to be connected with 60 or
75°C wire for circuit breakers having a rated ampacity of
125 amperes or less. Circuit breakers having a rated ampacity
greater than 125 amperes shall only be cabled with 75°C
cable unless otherwise indicated on the circuit breaker
label. Exceptions to this rule are outlined in the article
110-14 C(1)(2) of the 2002 National Electric Code and Canadian
Electrical Code.
6/4
UL869 — Service Equipment
NEMA AB-1 — Molded Case Circuit
Breakers and Molded Case Switches
CSA–C22.2 No. 5,
C22.2 No. 14
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Load Center Breakers
QT Page
1-22, 1-27
1-22, 1-27 1-22, 1-27 1-27
1, 2, 3
1, 2, 3
Amperes, Continuous
15–50
15–125 15–125 15–125 100–200
Ratings
CSA/UL Interrupting Rating —
Symmetrical RMS Amperes
2-Pole
120/240
BLH
HBL
BQD,
BQD6
2
1-27
6-13
6-13
6-13
6-16
2,3
1, 2, 3,
1, 2, 3
1, 2, 3 1, 2, 3
120/240
120/240
150–200 15–125 15–125 15–100 15–100
120/240 120/240 120/240 120/240
277
3-Pole
—
240
240
240
240
240
240
240
240
480/277
120V
10,000
10,000
22,000
65,000
—
—
10,000
22,000
65,000
65,000
240V
10,000
10,000
22,000
65,000
100,000
10,000
10,000
22,000
65,000
65,000
277V
—
—
—
—
—
—
—
—
—
10,000
347V
—
—
—
—
—
—
—
—
—
14,000
480/277V
—
—
—
—
—
—
—
—
—
10,000 14,000
600/347V
—
—
—
—
—
—
—
—
—
Volts — 2-Pole
—
—
—
—
—
—
—
—
—
250
Interrupting Rating — DC Amperes
—
—
—
—
—
—
—
—
—
14,000
4.50
Height
Dimensions in
inches
Width
Depth
15–50A
—
2.87
2.87
—
—
7.00
3.56
3.56
—
15–30A
—
—
—
—
—
—
—
3.75
—
—
15–60A
3.12
—
—
—
—
—
—
—
—
—
55–125A
—
3.12
3.12
3.12
3.12
3.00 3.75
—
3.75
4.50
1-Pole
1.00
1.00
1.00
1.00
—
—
1.00
1.00
1.00
1.00
2-Pole
2.00 2.00 2.00 2.00
4.00 2.00
2.00
2.00
2.00
3-Pole
2.00 3.00
3.00
3.00
—
3.00 3.00
3.00
3.00
3.00
2.23
2.06
2.37
2.37
2.37
2.37
2.34
2.37
2.37
2.69
Thermal and Fixed Magnetic Trip
Molded Case Switch
—
—
—
—
—
—
—
—
—
Undervoltage Trip
—
—
—
—
—
—
—
—
—
Shunt Trip
—
—
Auxiliary Switch
—
—
—
—
—
Alarm Switch
—
—
—
—
—
—
—
—
—
Type 1 — Indoor Surface
—
—
—
—
—
Type 1 — Indoor, Flush
—
—
—
—
—
—
Type 3R — Outdoor-Rainproof
—
—
—
—
—
—
CIRCUIT
BREAKERS
Individual
Enclosures
120/240 120/240
1, 2, 3 BL
HQPPH QPJ 1-23
AC
Accessories &
Modifications
HQP,
HQPP 1, 2
1-Pole
Overcurrent
Devices
Panelboard Breakers
QPH,
QPPH Poles
Volts (60 Hertz)
DC
QP,
QPP 6
Thermal-Magnetic Trip Breakers
QP, QPH, HQP
For inches / millimeters conversion, see Application Data
section.
BQD6 CSA cerified 10,000A @ 600Y/347V 15–70A only.
Types QPP, QPPH, HQPP and HQPPH are special 2-pole
configurations for load center mains. Amperage range =
125–225A, width = 4 in.
BL, BLH, HBL
Single pole breakers available in ratings 15–70A only.
125A, 2-pole 120/240V AC only.
14,000A IR at 277/480V AC only.
Not applicable to types QPP and QPPH.
Single pole circuit breakers available in ratings 15-70A only,
125A available as a 2-pole only.
Not applicable to type HQPP.
BQD, BQD6
Fits only Siemens EQIII load centers. Breaker is 2 or 3
poles wide.
6/5
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Thermal-Magnetic Trip Breakers
General Purpose Breakers
Page
Poles
Amperes, Continuous
Ratings
CSA/UL Interrupting Rating —
Symmetrical RMS Amperes
DC
QJ2-H
HQJ2-H
CQD
NGG
6-19
6-19
6-20
6-21
1, 2, 3
1, 2, 3
2, 3
2, 3
2, 3
3
1, 2, 3
1, 2, 3
15–70
15–70
15–50
—
—
—
—
15–100
15–100
2-Pole
15–125
15–100
15–70
15–100
60–225
15–125
15–100
60–225
15–100
15–100
60–225
—
3-Pole
100–225
15–100
15-125
—
—
—
—
277
347
480/277
600/347
120/240
120/240
120/240
3-Pole
240
240
240
120V
10,000
22,000
65,000
—
—
—
—
65,000
65,000
240V
10,000
22,000
65,000
10,000
22,000
42,000
100,000
65,000
65,000
240
240
—
240
240
—
—
—
—
—
—
—
14,000
25,000
—
—
—
—
—
—
—
10,000
18,000
Volts — 2-Pole
—
—
—
—
—
—
—
250
250
Interrupting Rating — DC Amperes
—
—
—
—
—
—
—
14,000
14,000
15–50A
3.75
3.75
4.00
—
—
—
—
4.50
—
55–125A
4.00
4.00
4.00
—
—
—
—
4.50
—
60–225A
—
—
—
7.00
7.00
7.00
7.00
—
—
1-Pole
1.00
1.00
1.00
—
—
—
—
1.00
1.00
2-Pole
2.00
2.00
2.00
3.00
3.00
3.00
—
2.00
2.00
3-Pole
3.00
3.00
3.00
4.50
4.50
4.50
4.50
3.00
3.00
2.37
2.37
2.37
2.34
2.34
2.53
2.53
2.87
2.90
Thermal and Fixed Magnetic Trip
Molded Case Switch
—
—
—
—
—
—
—
Width
Depth
6
Individual
Enclosures
QJH2
6-19
480/277V
Dimensions in
inches
Accessories &
Modifications
QJ2
6-19
600/347V
Height
Overcurrent
Devices
HBQ
6-17
1, 2, 3
2-Pole
AC
BQH
6-17
1-Pole
1-Pole
Volts (60 Hertz)
BQ
6-17
Undervoltage Trip
—
—
—
—
—
—
—
—
Shunt Trip
Auxiliary Switch
Alarm Switch
—
—
—
—
—
Mechanical Interlock
—
—
—
—
—
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface
—
Type 1 — Indoor, Flush
—
Type 3R — Outdoor-Rainproof
—
CIRCUIT
BREAKERS
BQ, BQH, HBQ
QJ2, QJH2, QJ2-H
For inches / millimeters conversion, see Application Data section.
3-pole breakers only (factory installed only).
Type CQD6—CSA only.
6/6
6
CQD
NGG
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Poles
Amperes, Continuous
Volts 50/60HZ
AC
Ratings
CSA / UL
Interrupt Rating
Symmetrical RMS
Amperes
220/240V
IEC 947-2
380/415V
50/60HZ
500V
DC
Dimensions in
inches
Overcurrent
Devices
Accessories &
Modifications
Individual
Enclosures
2-Pole, 250V DC Interrupting Ratings
3-Pole, 500V DC Interrupting Ratings
Height
Width
Depth
Thermal and Fixed Magnetic Trip
Thermal and Adjustable Magnetic Trip
Adjustable Magnetic Trip Only
Motor Circuit Protector
Molded Case Switch
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
Type 12K — Semi-Dusttight
ED2
6-23
1, 2, 3
15–100
1-Pole
120
2-Pole
240
3-Pole
120V
10,000
240V
10,000
277V
—
347V
—
480V
—
600V
—
Icu
—
Ics
—
Icu
—
Ics
—
Icu
—
Ics
—
5,000
—
6.34
1-Pole 1.00
2-Pole 2.00
3-Pole 3.00
4.00
—
ED4
6-23
1, 2, 3
15–125
277
ED6
6-23
1, 2, 3
15–125
347
HED4
6-24
1, 2, 3
15–125
277
480
600
480
FD6A,
CED6
FXD6A
6-24
6-26
2, 3
2, 3
15–125
70–250
—
—
600
—
—
—
—
65,000 65,000 100,000 200,000
22,000
—
165,000
—
—
30,000
—
—
18,000 25,000 142,000 1200,000
—
18,000
—
1100,000
65,000
—
200,000 —
17,000
—
—
35,000
—
200,000 —
19,000
—
—
—
18,000
—
—
15,000
—
—
—
30,000 30,000 30,000
30,000
—
18,000
—
50,000
6.34
6.34
6.34
9.26
1.00
1.00
1.00
—
2.00
2.00
2.00
2.00
3.00
3.00
3.00
3.00
4.00
4.00
4.00
4.00
—
—
—
—
HFD6,
HFXD6
6-27
2, 3
70–250
—
HHFD6,
HHFXD6
6-27
2, 3
70–250
—
CFD6
6-27
2, 3
70–250
—
600
600
600
600
—
65,000
—
—
35,000
18,000
65,000
33,000
35,000
18,000
20,000
10,000
30,000
18,000
9.50
—
4.50
4.50
4.00
—
—
100,000
—
—
165,000
125,000
100,000
150,000
165,000
133,000
142,000
121,000
30,000
25,000
9.50
—
4.50
4.50
4.00
—
—
—
200,000 200,000
—
—
—
—
100,000 200,000
125,000 100,000
200,000
—
100,000
—
100,000
—
150,000
—
165,000
—
133,000
—
30,000
—
—
50,000
11.00
14.12
—
—
4.50
4.50
4.50
4.50
4.00
4.00
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6
Page
General Purpose Breakers
—
For inches / millimeters conversion, see Application Data section.
1-pole only.
40–100A: 25,000 AIR at 277V AC.
For DC UPS system application.
Single pole ED6 (15–30A) 30kA, (35–100A) 18 kA. CSA Only.
6/7
CIRCUIT
BREAKERS
Thermal-Magnetic Trip Breakers
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Thermal-Magnetic Trip Breakers
General Purpose Breakers
JD6-A,
HJD6-A,
JXD2-A JXD6-A HJXD6-A
6-29
6-29
6-30
2, 3
2, 3
2, 3
200-400 200-400 200-400
Page
Poles
Amperes, Continuous
Volts 50/60HZ
CSA / UL
AC
Interrupt Rating
Symmetrical RMS
Amperes
Ratings
220/240V
IEC 947-2
380/415V
50/60HZ
500V
DC
Dimensions in
inches
Overcurrent
Devices
Accessories &
Modifications
6
Individual
Enclosures
2-Pole 250V DC Interrupting Ratings
3-Pole, 500V DC Interrupting Ratings
Height
Width
Depth
Thermal and Adjustable Magnetic Trip
Adjustable Magnetic Trip Only
Motor Circuit Protector
Molded Case Switch
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
LD6,
LXD6
6-33
2, 3
450-600
HLD6,
HLXD6
6-33
2, 3
250-600
HHLD6,
HHLXD6
6-34
2, 3
250-600
CLD6
6-34
2, 3
450-600
240
600
600
600
600
600
600
600
600
65,000
—
—
—
—
—
—
—
—
30,000
—
11.00
65,000
35,000
25,000
65,000
33,000
40,000
20,000
30,000
15,000
30,000
25,000
11.00
100,000
065,000
035,000
100,000
050,000
065,000
033,000
042,000
021,000
030,000
035,000
11.00
200,000
100,000
150,000
200,000
100,000
100,000
150,000
165,000
133,000
—
—
11.00
200,000
150,000
100,000
—
—
—
—
—
—
30,000
50,000
17.86
65,000
35,000
25,000
65,000
33,000
40,000
20,000
30,000
15,000
30,000
25,000
11.00
100,000
165,000
135,000
100,000
150,000
165,000
133,000
142,000
121,000
130,000
135,000
11.00
200,000
100,000
150,000
200,000
100,000
100,000
150,000
165,000
133,000
—
—
11.00
200,000
150,000
100,000
—
—
—
—
—
—
130,000
150,000
17.86
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
7.50
1
14.00
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
CIRCUIT
BREAKERS
Type 12K — Semi-Dusttight
—
—
—
For DC UPS application.
6/8
2-Pole
3-Pole
CJD6
6-30
2, 3
200-400
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
For inches / millimeters conversion, see Application Data section.
2-Pole
3-Pole
240V
480V
600V
Icu
Ics
Icu
Ics
Icu
Ics
HHJD6-A,
HHJXD6-A
6-30
2, 3
200-400
Molded Case Circuit Breakers
SELECTION / APPLICATION
General Purpose Breakers
LMD6,
HLMD6,
MD6,
LMXD6
HLMXD6
MXD6
6-37
6-37
6-40
2, 3
2, 3
2, 3
500-800
500-800
500-800
Page
Poles
Amperes, Continuous
Volts 50/60 HZ
CSA / UL
AC
Interrupt Rating
Symmetrical RMS
Amperes
Ratings
220/240V
IEC 947-2
380/415V
50/60HZ
500V
DC
Dimensions in
inches
Overcurrent
Devices
Accessories &
Modifications
Individual
Enclosures
2-Pole 250V DC Interrupting Ratings
3-Pole, 500V DC Interrupting Ratings
Height
Width
Depth
Thermal and Fixed Magnetic Trip
Thermal and Adjustable Magnetic Trip
Adjustable Magnetic Trip Only
Motor Circuit Protector
Molded Case Switch
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 6/73)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
Type 12K — Semi-Dusttight
For
2-Pole
3-Pole
240V
480V
600V
Icu
Ics
Icu
Ics
Icu
Ics
2-Pole
3-Pole
HMD6,
HMXD6
6-41
2, 3
500-800
CMD6
6-41
3
400-800
ND6,
NXD6
6-44
2, 3
800-1200
HND6,
HNXD6
6-45
2, 3
800-1200
CND6
6-45
3
800-1200
600
600
600
600
600
600
600
600
65,000
50,000
25,000
65,000
33,000
40,000
20,000
30,000
15,000
30,000
25,000
16.00
100,000
165,000
125,000
100,000
150,000
165,000
133,000
142,000
121,000
130,000
150,000
16.00
65,000
50,000
25,000
65,000
33,000
40,000
20,000
30,000
15,000
30,000
25,000
16.00
100,000
165,000
150,000
100,000
150,000
165,000
133,000
142,000
121,000
130,000
150,000
16.00
65,000
50,000
25,000
65,000
33,000
40,000
20,000
30,000
15,000
30,000
25,000
16.00
100,000
165,000
150,000
100,000
150,000
165,000
133,000
142,000
121,000
130,000
150,000
16.00
7.50
7.50
9.00
9.00
9.00
9.00
4.59
—
4.59
—
6.19
—
6.19
—
200,000
100,000
165,000
200,000
100,000
100,000
150,000
165,000
133,000
130,000
150,000
16.00
—
9.00
6.19
—
6.19
—
6.19
—
200,000
100,000
165,000
200,000
100,000
100,000
150,000
165,000
133,000
130,000
150,000
16.00
—
9.00
6.19
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
DC UPS application.
For inches / millimeters conversion, see Application Data section.
6/9
CIRCUIT
BREAKERS
Thermal-Magnetic Trip Breakers
6
Reference Guide
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Thermal-Magnetic Trip Breakers
Page
Poles
Amperes, Continuous
Volts 50/60 HZ
CSA / UL
Ratings
AC
Interrupt Rating
Symmetrical RMS
Amperes
220/240V
IEC 947-2
380/415V
50/60HZ
500V
3-Pole
240V
480V
600V
Icu
Ics
Icu
Ics
Icu
Ics
2-Pole 250V DC Interrupting Ratings
DC
3-Pole, 500V DC Interrupting Ratings
Dimensions in
inches
Overcurrent
Devices
Accessories &
Modifications
Individual
Enclosures
Circuit breakers require Connect-all
mounting block. Dimensions shown
are for circuit breaker only.
Height
Width
Depth
6
Thermal and Adjustable Magnetic Trip
Molded Case Switch
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Electric Motor Operator
Fungus Proofing (ref. page 106)
Mounting Block (required)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
General Purpose Breakers
HPD6,
PD6 ,
HPXD6
PXD6 6-48
6-48
3
3
1200-1600
1200-1600
11,600
111,600
65,000
100,000
165,000
50,000
150,000
25,000
65,000
100,000
150,000
33,000
40,000
165,000
117,000
10,000
142,000
30,000
18,000
121,000
130,000
30,000
25,000
150,000
16.00
16.00
19.00
19.00
16.19
16.19
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
CIRCUIT
BREAKERS
6/10
HRD6,
HRXD6
6-51
3
1600-2000
111,600
100,000
165,000
150,000
100,000
150,000
165,000
117,000
142,000
121,000
130,000
150,000
16.00
19.00
16.19
—
—
—
—
— —
Type 12K — Semi-Dusttight
DC UPS application.
Connect-all mounting assembly. Dimensions shown are for circuit breaker only.
Requires
RD6 ,
RXD6 6-51
3
1600-2000
11,600
65,000
50,000
25,000
65,000
33,000
40,000
10,000
30,000
18,000
30,000
25,000
16.00
19.00
16.19
—
—
—
—
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
For inches / millimeters conversion, see Application Data section.
For
CPD6
6-48
3
1200-1600
111,600
200,000
100,000
165,000
200,000
100,000
100,000
125,000
165,000
117,000
130,000
150,000
16.00
19.00
16.19
—
—
—
—
—
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Electronic Trip Breakers
Solid State Trip Cicuit Breakers
Page
Ratings
AC
Poles
Amperes, Continuous
Volts 50/60 HZ
Interrupt Rating
Symmetrical RMS CSA / UL
Amperes
3-Pole
240V
480V
600V
SJD6
SHJD6
SCJD6
SLD6
SHLD6
SCLD6
SMD6
SHMD6
SCMD6
6-31
3
200-400
600
65,000
35,000
25,000
11.00
17.50
14.00
6-31
3
200-400
600
100,000
165,000
135,000
11.00
17.50
14.00
6-31
3
200-400
600
200,000
150,000
100,000
17.86
17.50
14.00
6-35
3
300-600
600
65,000
35,000
25,000
11.0
17.50
14.00
6-35
3
300-600
600
100,000
165,000
135,000
11.00
17.50
14.00
6-35
3
300-600
600
200,000
150,000
100,000
17.86
17.50
14.00
6-42
3
600-800
600
65,000
50,000
25,000
10.00
19.00
16.19
6-42
3
600-800
600
100,000
165,000
150,000
16.00
19.00
16.19
6-42
3
600-800
600
200,000
100,000
165,000
16.00
19.00
16.19
Dimensions in
inches
Height
Width
Depth
Overcurrent
Devices
Solid State Trip
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Accessories &
Modifications
—
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
Type 12K — Semi-Dusttight
—
—
—
CIRCUIT
BREAKERS
6
Individual
Enclosures
3-Pole
For inches / millimeters conversion, see Application Data section.
6/11
Molded Case Circuit Breakers
SELECTION / APPLICATION
Reference Guide
Electronic Trip Breakers
Insulated Case
Circuit Breakers
Solid State Trip Circuit Breakers
Page
Poles
Amperes, Continuous
Volts 50/60HZ
Ratings
CSA / UL
AC
Interrupt Rating
Symmetrical RMS
Amperes
380/415V
EC 947-2
50/60HZ
690V
Dimensions in
inches
Overcurrent
Devices
Accessories &
Modifications
Individual
Enclosures
3-Pole
240V
480V
600V
Icu
Ics
Icu
Ics
Height
Width
Depth
SND6
SHND6
SCND6
SPD6 SHPD6 STD6 SHTD6 SHHTD6 SBA
SBS
6-46
3
800-1200
600
65,000
50,000
25,000
—
—
—
—
16.00
19.00
16.19
6-46
3
800-1200
600
100,000
165,000
150,000
—
—
—
—
16.00
19.00
16.19
6-46
3
800-1200
600
200,000
100,000
165,000
—
—
—
—
16.00
19.00
16.19
6-49
3
1200-1600
600
65,000
50,000
25,000
—
—
—
—
16.00
19.00
16.19
6-49
3
1200-1600
600
100,000
165,000
150,000
—
—
—
—
16.00
19.00
16.19
6-53
3
2000-3200
600
65,000
35,000
25,000
—
—
—
—
27.5
14.12
11.38
6-53
3
2000-3200
600
100,000
165,000
135,000
—
—
—
—
27.5
14.12
11.38
6-53
3
2000-3200
600
200,000
150,000
100,000
—
—
—
—
27.5
14.12
11.38
6-64
3
400-2000
600
65,000
65,000
50,000
—
—
—
—
—
—
—
6-64
6-64
3
3
400-500 2000-5000
600
600
150,000 200,000
100,000 150,000
85,000 100,000
100
—
100
—
165
—
165
—
—
—
—
—
—
—
SBH
6
Solid State Trip
Undervoltage Trip
Shunt Trip
Auxiliary Switch
Alarm Switch
Mechanical Interlock
Rear Connection Studs
Electric Motor Operator
Plug-In Mounting Assembly
Stored Energy Mechanism
Drawout Construction
Fungus Proofing (ref. page 106)
Type 1 — Indoor Surface
Type 1 — Indoor, Flush
Type 3R — Outdoor-Rainproof
Type 7 — Flammable Gas Atmosphere
Type 9 — Combustion Dusttight
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— —
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Type 5, 12 — Lint, Fine Dust, Oils, Coolants
—
—
—
—
—
—
—
—
Type 12K — Semi-Dusttight
—
—
—
—
—
—
—
—
—
—
CIRCUIT
BREAKERS
For inches / millimeters conversion, see Application
Data section.
6/12
Requires
connect-all mounting block assembly. Dimensions
shown are for circuit breaker.
Breaker
has rating plugs which can be changed within each
frame rating.
Molded Case Circuit Breakers
SELECTION / APPLICATION
Panelboard Mounting Circuit Breakers
Type BL–Low Tab Bolt-on (10,000A IR) Non-Interchangeable Trip
Continuous
Current Rating
@ 40° C
1-Pole
2-Pole
2-Pole
3-Pole
120/240V AC
120/240V AC
Common Trip
240V AC
Common Trip
240V AC
Common Trip
Catalog
Number
Catalog
Number
Catalog
Number
015
020
025
030
035
040
045
050
060
B115 B120 B125 B130 B135 B140 B145 ■
B150 B160 30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
B215 B220 B225 B230 B235
B240 B245 B250 B260 070
B170 65.00
B270 133.00
68.00
68.00
68.00
68.00
68.00
68.00
68.00
68.00
68.00
Catalog
Number
181.00
181.00
181.00
181.00
181.00
181.00
181.00
181.00
181.00
B315 227.00
B320 227.00
B325 227.00
B330 227.00
B335 227.00
B340 227.00
B345 227.00
B350 227.00
B360 227.00
B270R ■ 240.00
B370 278.00
B280R ■ 273.00
B290R ■ 273.00
B2100R ■ 273.00
B380 314.00
B390 314.00
B3100 314.00
B215R ■
B220R ■
B225R ■
B230R ■
B235R ■
B240R ■
B245R ■
B250R ■
B260R ■
080
090
100
—
—
—
B280 181.00
B290 181.00
B2100 181.00
110
125
—
—
B2110 ■ 364.00
B2125 385.00
—
—
—
—
Type BLH – Low Tab Bolt-on (22,000A IR)
015
020
B115H 59.00
B120H 59.00
B215H 133.00
B220H 133.00
—
—
B315H 341.00
B320H 341.00
025
030
040
050
060
B125H 66.00
B130H 66.00
B140H 66.00
B150H ■ 66.00
B160H ■ 66.00
B225H 133.00
B230H 133.00
B240H 133.00
B250H 133.00
B260H 133.00
—
—
—
—
—
B325H 341.00
B330H 341.00
B340H 341.00
B350H 341.00
B360H 341.00
070
B170H ■ 83.00
B270H 205.00
—
B370H 414.00
B280H 291.00
B290H 291.00
B2100H291.00
—
—
—
B380H 486.00
B390H 486.00
B3100H486.00
080
090
100
—
—
—
—
—
—
B115HH
B120HH
B130HH
101.00
101.00
101.00
B215HH247.00
B220HH247.00
B230HH247.00
—
—
—
B315 HH429.00
B320HH429.00
B330HH429.00
040
050
060
B140HH
B150HH ■
——
118.00
118.00
B240HH302.00
B250HH302.00
B260HH302.00
—
—
—
B340HH522.00
B350HH522.00
B360HH522.00
070
——--
B270HH ■ 494.00
—
B370HH558.00
080
090
100
——-——-——--
B280HH ■ 558.00
B290HH ■ 558.00
B2100HH558.00
—
—
—
B380HH656.00
B390HH656.00
B3100HH656.00
Types BL/BLH/HBL
Internal Accessories (Factory installed only; require one additonal pole width)
Auxiliary Switches
Control Voltage
Shunt Trip
1A and 1B
AC
DC
Suffix
Suffix
120V
—
...00S01 ■
...01 ■
24V
—
...00S07 ■
...01 ■
■ Built to order. Allow 3–4 weeks for delivery.
CSA Certified / UL Listed for frequent switching
applications (SWD). 120V AC fluorescent lighting.
For 400 cycle CSA Certified/ UL Listed devices, add “Y”
suffix to catalog number. Add 25% to list price. 5000A
interrupting rating — Built To Order.
CSA
Certified / UL Listed for 3 phase 240V grounded B
at 10,000 AIR.
rated.
HACR
Modifications - page 6/73
Accessories - page 6/75 to 6/80
6/13
CIRCUIT
BREAKERS
015
020
030
6
Type HBL – Low Tab Bolt-on (65,000A IR)
Molded Case Circuit Breakers
SELECTION
Panelboard Mounting Circuit Breakers
Ordering Instructions
All BL circuit breakers are supplied with load side connectors.
All standard circuit breakers are calibrated for 40° C maximum ambient application.
Shipping Weights - BL, BLH, HBL
Number of
Poles
Number Per
Carton /Master
Shipping
Weight (lbs.)
Master
1
2 (15–50A)
2 (60–70A)
2 (80–125A)
3 (15–100A)
12/48
6/24
6/24
6/24
4/16
15.3
15.3
19.4
24.9
20.1
Lugs (Load Side)
Type
Circuit Breaker
Ampere Rating
15–40
25-35
40-50
BL, BLH, HBL
55-70
80-100
110-125
Cables Per
Lug
Wire Range
Cu/Al
1
#14–#10 AWG Cu
1
#12-#10 AWG AI
1
#14–#6 AWG Cu
1
#12-#6 AWG AI
1
#8–#6 AWG Cu
1
#8-#4 AWG AI
1
#8–#4 AWG Cu
1
#8-#2 AWG AI
1
#4–#1/0 AWG Cu
1
#2-#1/0 AWG AI
1
#2–#1/0 AWG Cu
1
#1/0-#2/0 AWG AI
Catalog Number
Fixed in Breaker
BL/BLH/HBL
6
CIRCUIT
BREAKERS
For inches / millimeters conversion, see Application Data section.
6/14
Dimensions (inches)
Breaker
Type
Amperes
L
D1
D2
BL, BLH
BL, BLH
HBL
15–50
55–125
15–125
39⁄16
33⁄4
33⁄4
23⁄8
23⁄8
23⁄8
3
3
3
Accessories page 6/75 to 6/ 80.
Molded Case Circuit Breakers
SELECTION
Special Application Panelboard Mounting Breakers
GFCI Personnel Protection (Class A) (5MA) Complete Breaker UL
Unenclosed
1-Pole
BLF
2-Pole
BLHF
1-Pole
BLHF
2-Pole
Ampere
Rating
Catalog
Number
120
120/240
240
15
20
25
30
BF115
BF120
BF125 ■
BF130
293.00
293.00
293.00
293.00
10
10
10
10
—
—
—
—
—
—
—
—
15
20
30
40
50
60
BF215
BF220
BF230
BF240 ■
BF250 ■
BF260 ■
349.00
349.00
349.00
349.00
349.00
349.00
—
—
—
—
—
—
10
10
10
10
10
10
—
—
—
—
—
—
15
20
30
BF115H 581.00
BF120H 581.00
BF130H ■ 581.00
22
22
22
—
—
—
—
—
—
15
20
30
40
50
60
BF215H ■ 633.00
BF220H ■ 633.00
BF230H ■ 633.00
BF240H ■ 633.00
BF250H ■ 633.00
BF260H ■ 633.00
—
—
—
—
—
—
22
22
22
22
22
22
—
—
—
—
—
—
10
10
10
—
—
—
—
—
—
468.00
468.00
468.00
468.00
468.00
468.00
—
—
—
—
—
—
10
10
10
10
10
10
—
—
—
—
—
—
20
30
BE120H ■ 581.00
BE130H ■ 581.00
22
22
—
—
—
—
15
20
30
40
50
60
BE215H ■ 848.00
BE220H ■ 848.00
BE230H ■ 848.00
BE240H ■ 848.00
BE250H ■ 848.00
BE260H ■ 848.00
—
—
—
—
—
—
22
22
22
22
22
22
—
—
—
—
—
—
279.00
279.00
10
10
—
—
—
—
15
20
B115AFH 553.00
B120AFH 553.00
22
22
—
—
—
—
15
20
30
B115HID ■ 38.00
B120HID 38.00
B130HID ■ 38.00
10
10
10
—
—
—
—
—
—
15
20
30
B215HID ■ 81.00
B220HID 81.00
B230HID ■ 81.00
—
—
—
10
10
10
—
—
—
EQF Equipment Protection (30MA)
15
BE115 ■ 356.00
BLE
BE120 356.00
20
1-Pole
120V AC
BLE
2-Pole
120/240V AC
BLEH
1-Pole
BLEH
2-Pole
30
15
20
30
40
50
60
BE130 356.00
BE215 ■
BE220
BE230
BE240 ■
BE250 ■
BE260 ■
AFCI Arc Fault Circuit Interrupter 15
B115AF
BAF
B120AF
20
1-Pole
BAFH
1-Pole
HID Lighting BL
1-Pole
BL
2-Pole
Switching Neutrals 15
BG
2 Wire
Common Trip
20
30
BG215 ■ 105.00
BG220 ■ 105.00
BG230 ■ 105.00
10
10
10
—
—
—
—
—
—
BG
15
20
30
BG315 ■ 158.00
BG320 ■ 158.00
BG330 ■ 158.00
—
—
—
10
10
10
—
—
—
3 Wire
Common Trip
1 Pole
2˝
2 Pole
6
BLF
1˝
Volts AC
B115AF
BG
■ Built to order. Allow 2–3 weeks for delivery.
HACR rated.
Meets 2002 NEC Section 210-12.
CSA Certified / UL Listed for frequent switching applications (SWD). 120V AC fluorescent lighting.
6/15
CIRCUIT
BREAKERS
Breaker
Type
Interrupting Ratings (KA)
(RMS Symmetrical Amperes)
Molded Case Circuit Breakers
SELECTION
BQD 100A Frame Panelboard Mounting Circuit Breakers
BQD
2-Pole
480Y/277V AC–
125/250V DC
1-Pole
277V AC–125V DC
Continuous
Current Rating
@ 40°C
15
20
25
30
35
40
45
50
60
70
80
90
100
Catalog
Number
3-Pole
480Y/277V AC
Catalog
Number
BQD115
BQD120 BQD125 BQD130 BQD135
BQD140
BQD145■
BQD150
BQD160
BQD170■
BQD180■
BQD190
BQD1100■
105.00
105.00
105.00
105.00
105.00
105.00
105.00
105.00
105.00
221.00
221.00
221.00
221.00
BQD215
BQD220
BQD225
BQD230
BQD235
BQD240
BQD245
BQD250
BQD260
BQD270
BQD280
BQD290
BQD2100
Catalog
Number
258.00
258.00
258.00
258.00
258.00
258.00
258.00
258.00
258.00
526.00
526.00
526.00
526.00
BQD315
BQD320
BQD325
BQD330
BQD335
BQD340
BQD345
BQD350
BQD360
BQD370
BQD380
BQD390
BQD3100
459.00
459.00
459.00
459.00
459.00
459.00
459.00
459.00
459.00
625.00
625.00
625.00
625.00
BQD, BQD6
BQD6 CSA Certified
2-Pole
600/347V AC
1-Pole
347V AC
Continuous
Current Rating
@ 40°C
15
20
25
30
35
40
45
50
60
70
Catalog
Number
BQD6115
BQD6120
BQD6125■
BQD6130
BQD6135■
BQD6140
BQD6145■
BQD6150
BQD6160
BQD6170
3-Pole
600/347V AC
Catalog
Number
105.00
105.00
105.00
105.00
105.00
105.00
105.00
105.00
105.00
221.00
Catalog
Number
BQD6215 258.00
BQD6220 258.00
BQD6225■258.00
BQD6230 258.00
BQD6235■258.00
BQD6240 258.00
BQD6245■258.00
BQD6250 258.00
BQD6260 258.00
BQD6270 526.00
BQD6315
BQD6320
BQD6325■
BQD6330
BQD6335■
BQD6340
BQD6345■
BQD6350
BQD6360
BQD6370
459.00
459.00
459.00
459.00
459.00
459.00
459.00
459.00
459.00
625.00
BQD, BQD6
Shipping Weights
Number of
Poles
Number per
Carton
Shipping
Weight (lbs.) (ea.)
1
2
3
1/12/48
1/6/24
1/4/16
1.6
1.2
2.0
Interrupting Ratings
6
Breaker
Type
BQD
(UL&CSA)
BQD6
(CSA)
Number
of
Poles
RMS Symmetrical Amperes (KA)
Volts AC
480/
120
240
277
277
1
2
3
1
2
3
65
—
—
65
—
—
—
65
65
—
65
65
14
—
—
10
—
—
—
14
14
—
10
10
Lugs For 60/70°C Wire
Volts DC
BQD – Load End Only
347
600/
347
125
250
—
—
—
10
—
—
—
—
—
—
10
10
14
—
—
14
—
—
—
14
—
—
14
—
15–40
#14–#6 AWG Cu
#12–#6 AWG Al
45–100
#8–#1 AWG Cu
#6–#1/0 AWG Al
CIRCUIT
BREAKERS
BQD Internal Accessories
Control Voltage
V AC
120
240
277
480
600
—
—
—
—
V DC
—
—
—
—
—
12
24
48
125
Maximum Voltage
Shunt Trip
Catalog
Number
BQDST120
BQDST240▲
BQDST277▲
BQDST480▲
BQDST600▲
BQDST12▲
BQDST24▲
BQDST48▲
BQDST125▲
569.00
569.00
569.00
569.00
569.00
569.00
569.00
569.00
569.00
AC
DC
Auxiliary Switch
Catalog
Number
240
240
125
125
BQDA1▲
BQDA2▲
Alarm Switch
Catalog
Number
Alarm and Auxiliary Switch Combination
Catalog
Number
42.00BQDBA▲
83.00—
For inches / millimeters conversion,
see Application Data section.
■ Built to order. Allow 2–3 weeks for delivery.
▲ Built to order. Allow 6–8 weeks for delivery.
6/16
Shunt Trip and Auxiliary Switch Combinations
Catalog
Number
BQDST120AAS▲
802.00
BQDST240AAS▲
802.00
BQDST277AAS▲
802.00
BQDST480AAS▲
802.00
BQDST600AAS▲
802.00
BQDST12DAS▲
802.00
BQDST24DAS▲
802.00
BQDST48DAS▲
802.00
BQDST125DAS▲
802.00
BQDA1BA
SWD
HID
rated for switching 277V AC fluorescent lighting.
rated at 277V AC.
Not suitable for 3 phase delta 480V and 600Y
applications.
HACR
483.00
rated.
Accessories pages 6/75 to 6/80
Molded Case Circuit Breakers
SELECTION
BQ 125A Frame
Ordering Instructions
All BQ circuit breakers are supplied with load side lugs. If line side lugs are required, add suffix ‘L’ to catalog number. Lugs
will be supplied at no charge if ordered with circuit breakers. All standard circuit breakers are calibrated for 40°C maximum
ambient application.
BQ 125A Frame — BQ (10,000A IR)
Non-Interchangeable Trip
Continuous
Current Rating
@ 40° C
1-Pole
2-Pole
2-Pole
3-Pole
120/240V AC
120/240V AC
Common Trip
240V AC
Common Trip 240V AC
Common Trip
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
015
020
025
030
035
040
045
050
055
060
BQ1B015 BQ1B020 BQ1B025 BQ1B030 BQ1B035 ■
BQ1B040 BQ1B045 ■
BQ1B050 BQ1B055 ■
BQ1B060 30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
BQ2B015 68.00
BQ2B020 68.00
BQ2B025 68.00
BQ2B030 68.00
BQ2B035 68.00
BQ2B040 68.00
BQ2B045 ■68.00
BQ2B050 68.00
—
–
BQ2B060 68.00
BQ2H015 181.00
BQ2H020 ■ 181.00
—
–
BQ2H030 ■ 181.00
—
BQ2H040 ■ 181.00
—
–
BQ2H050 ■ 181.00
—
–
BQ2H060 ■ 181.00
BQ3B015 227.00
BQ3B020227.00
BQ3B025 227.00
BQ3B030227.00
BQ3B035 227.00
BQ3B040227.00
BQ3B045 227.00
BQ3B050227.00
—
–
BQ3B060227.00
070
BQ1B070
30.00
BQ2B070133.00
BQ2H070 ■ 240.00
BQ3B070278.00
—
–
BQ2H090 ■ 273.00
BQ2H100 ■ 273.00
BQ3B080314.00
BQ3B090314.00
BQ3B100314.00
080
090
100
—
—
—
BQ2B080 181.00
BQ2B090181.00
BQ2B100181.00
110
—
BQ2B110 364.00
—
—
125
—
BQ2B125 385.00
—
—
015
020
BQ1B015H 59.00
BQ1B020H 59.00
BQ2B015H 133.00
BQ2B020H 133.00
—
—
BQ3B015 H 341.00
BQ3B020H 341.00
030
040
050
055
060
BQ1B030H 66.00
BQ1B040H■ 66.00
BQ1B050H■ 66.00
BQ1B055H■ 66.00
BQ1B060H■ 66.00
BQ1B070H■ 83.00
BQ2B030H
BQ2B040H
BQ2B050H
—
BQ2B060H
133.00
133.00
133.00
–133.00
—
—
—
—
—
BQ3B030H 341.00
BQ3B040H 341.00
BQ3B050H 341.00
—
BQ3B060H 341.00
BQ2B070H 200.00
—
BQ3B070H ■ 414.00
BQ2B080H 291.00
BQ2B090H 291.00
BQ2B100H 291.00
BQ2B125H ■ 291.00
—
—
—
—
BQ3B080H ■ 485.00
BQ3B090H ■ 485.00
BQ3B100H 485.00
—
–-
070
080
090
100
125
—
—
—
—
6
BQH (22,000A IR)
015
020
030
HB1B015 101.00
HB1B020 101.00
HB1B030■101.00
HB2B015■247.00
HB2B020■247.00
HB2B030■247.00
—
—
—
HB3B015■429.00
HB3B020■429.00
HB3B030■429.00
040
050
060
HB1B040■118.00
HB1B050■118.00
—
-
HB2B040■302.00
HB2B050■302.00
HB2B060■302.00
—
—
—
HB3B040■522.00
HB3B050■522.00
HB3B060■522.00
HB2B070■494.00
—
HB2B090■558.00
HB2B100■558.00
—
HB3B070■558.00
—
—
—
HB3B080■656.00
HB3B090■656.00
HB3B100 656.00
070
—
--
080
090
100
—
—
—
----
BQ/BQH/HBQ
Internal Accessories (Factory installed only)
Auxiliary Switches
Control Voltage
Shunt Trip
AC
Suffix
Suffix
...00S01n
...A01■
120V
DC
1A and 1B
■ Built to order. Allow 3–4 weeks for delivery.
CSA
Certified / UL Listed for frequent switching
applications (SWD). 120V AC fluorescent lighting.
HCAR rated.
For
400 cycle CSA Certified / UL Listed devices, add “Y”
suffix to catalog number. Add 25% to list price. 5000A
interrupting rating.■
UL Listed for use on 3 phase grounded “B” systems–
5000A IR for this application.
Interrupting Ratings page 6/6
Accessories pages 6/75 to 6/80
Modifications page 6/75
6/17
CIRCUIT
BREAKERS
HBQ (65,000A IR)
Molded Case Circuit Breakers
SELECTION
DIN Rail Mounted Circuit Breakers
Type BQXD — BQ Breaker with DIN Rail Mounting - UL Listed only
Continuous
Current
Rating
15
20
25
30
35
40
45
50
60
1-Pole
2-Pole
Catalog
Number
Catalog
Number
BQ1B015QLD
BQ1B020QLD
BQ1B025QLD
BQ1B030QLD
BQ1B035QLD
BQ1B040QLD
BQ1B045QLD
BQ1B050QLD
BQ1B060QLD
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
Interrupting Ratings (KA)
(RMS Symmetrical Amperes)
Volts AC
120/240
BQ2B015QLD
BQ2B020QLD
BQ2B025QLD
BQ2B030QLD
BQ2B035QLD
BQ2B040QLD
BQ2B045QLD
BQ2B050QLD
BQ2B060QLD
68.00
68.00
68.00
68.00
68.00
68.00
68.00
68.00
68.00
10
2-Pole DIN Rail mtd
(UL listed only)
Finger Safe Terminal Shield
Protects against accidental contact with lugs–1 per lug. Fits line and load end.
Catalog Number
Qty
BQFS2
2
BQFS1K
1000
Shipping Weights
Number of
Poles
Number Per
Carton /Master
Shipping
Weight (lbs.)
Master
BQ
1 (15–50A)
1 (55–70A)
1 (15–70A, 22 and 65K A IR)
2 (15–50A)
2 (60–125A)
2 (15–100A, 22 and 65K A IR)
2 (15–100A, 240V)
3 (15–100A)
6/72
6/66
6/66
3/36
3/33
3/33
3/33
2/22
23
23
23
24
23
24
23
23
6/66
3/33
2/22
23
24
24
BQH and HBQ
1
2
3
Dimensions (inches)
Breaker
Type
Amperes
L
D1
D2
BQ, BQH
BQ, BQH
HBQ
BQXD
15–50
55–125
15–125
15–60
33⁄4
4
4
41⁄2
23⁄8
23⁄8
23⁄8
23⁄8
3
3
3
3
6
Lugs-For Use with BQ, BQH, HBQ
Enclosures
Type
Catalog Number
1
EB3100S Circuit
Breaker
Amp. Rtg.
3R
WB31006.00
Line Side
CIRCUIT
BREAKERS
Cables
Per
Lug
Lug
Wire Range
AWG
15–40
1
1
#14–#6 Cu
#12–#6 Al
TC1Q1 13.90
50–100
1
1
#8–#1 Cu
#6–#1/0 Al
TA1Q1
12.20
15–20
1
1
#14–#10 Cu
#14–#10 Al
25–35
1
1
#14–#6 Cu
#14–#6 Al
40–50
1
1
#8–#6 Cu
#8–#4 Al
55–70
1
1
#8–#4 Cu
#8–#2 Al
80–100
1
1
#4–#1/0 Cu
#2–#1/0 Al
110–125
1
1
#2–#1/0 Cu
#1/0–#2/0 Cu
Catalog
Number
Load Side
For inches / millimeters conversion,
see Application Data section.
Surface
mounted indoor. If flush mounting is required,
replace suffix “S” in catalog number with suffix “F”.
Schedule B.
Does not include circuit breaker. Order circuit breaker
separately.
Neutral included in enclosure.
Enclosure will not accept circuit breakers with shunt trips
or auxiliary switches installed.
Discount
■ Built to order. Allow 3–4 weeks for delivery.
Terminals
are CSA Certified / UL Listed for 60°/75°C
conductors.
Connector
has steel construction.
6/18
Connectors are
Supplied with
Circuit Breaker
Package of 6 connectors.
BQXD uses TA1Q1 or TC1Q1 lugs on both line and load
ends.
Accessories pages 6/75 to 6/80
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
QJ 225A Frame
Type QJ2
Ordering Information
2-Pole
3-Pole
Continuous
Current Rating
@ 40°C
240V AC
240V AC
Catalog
Number
Catalog
Number
060
070
080
090
100
110
125
150
175
200
225
QJ22B060■374.00
QJ22B070■377.00
QJ22B080■377.00
QJ22B090■377.00
QJ22B100377.00
QJ22B110■377.00
QJ22B125377.00
QJ22B150377.00
QJ22B175377.00
QJ22B200377.00
QJ22B225377.00
QJ23B060
QJ23B070
QJ23B080
QJ23B090
QJ23B100
QJ23B110
QJ23B125
QJ23B150
QJ23B175
QJ23B200
QJ23B225
QJH22B060■
QJH22B070■
QJH22B080■
QJH22B090■
QJH22B100■
QJH22B110■
QJH22B125
QJH22B150
QJH22B175■
QJH22B200
QJH22B225
QJH23B060■
QJH23B070■
QJH23B080■
QJH23B090■
QJH23B100
QJH23B110
QJH23B125
QJH23B150
QJH23B175
QJH23B200
QJH23B225
Load side TA1Q300 lugs are mounted and
included when circuit breaker is ordered.
For line and load lugs (TA1Q300) installed at
no additional charge, add suffix “L” to catalog
number.
989.00
989.00
989.00
989.00
989.00
989.00
989.00
989.00
989.00
989.00
989.00
Type QJH2
060
070
080
090
100
110
125
150
175
200
225
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
1384.00
Type QJ2H
QJ22B060H■
QJ23B060H■ 1756.00
QJ22B070H■
QJ23B070H■ 1756.00
QJ22B080H■
QJ23B080H■ 1756.00
QJ22B090H■
QJ23B090H■ 1756.00
QJ22B100H■
QJ23B100H 1756.00
QJ22B110H■
QJ23B110H■ 1756.00
QJ22B125H1122.00QJ23B125H 1756.00
QJ22B150H1122.00QJ23B150H 1756.00
QJ22B175H■
QJ23B175H 1756.00
QJ22B200H1122.00QJ23B200H 1756.00
QJ22B225H1122.00QJ23B225H 1756.00
060
070
080
090
100
110
125
150
175
200
225
50°C Calibration - See page 6-74.
400HZ. - See page 6-74.
Shipping Weights
QJ2, QJH2, QJ2H, HQJ2H
Number of
Poles
Number per
Carton
Shipping
Weight (lbs.)
2
3
10
10
30
41
Lugs For 75°C Wire Catalog
Number
Lug
Body
Lug
Wire Range
TA1Q300
Al
(1) #6—300 kcmil Cu
(1) #4—300 kcmil Al
TC1Q250
Cu
(1) #6—250 kcmil Cu
Enclosures (Neutral Included)
Type
Catalog
Number
1
3R (2-pole)
3R (3-pole)
EB3225(S)(F)
WB2225
WB3225
296.00
323.00
UL 489 Interrupting Ratings
Breaker
Type
AIR @ 240V AC
QJ2
QJH2
QJ2H
HQJ2H
010,000
022,000
042,000
100,000
HQJ23B100H
HQJ23B110H
HQJ23B125H
HQJ23B150H
HQJ23B175H
HQJ23B200H
HQJ23B225H
—
—
—
—
—
—
—
998.00
1998.00
998.00
1998.00
998.00
1998.00
998.00
QJ2
CIRCUIT
BREAKERS
100
110
125
150
175
200
225
6
Type HQJ2H
Internal Accessories (Factory installed only) 3-pole only .
Add suffix to catalog number.
Control Voltage
Shunt Trip
Auxiliary Switches
Shunt Trip and
1A and 1B
1A and 1B Auxiliary Switch
2A and 2B
AC
DC
Suffix
Suffix
Suffix
Suffix
120/240
—
00S01■
A01■
A02■
01S01■
—
24
00S07■
A01■
A02■
01S07■
—
25
00S11■
A01■
A02■
01S11■
■ Built to order. Allow 3–4 weeks for delivery.
HACR
▲ Built to order. Allow 7–9 weeks for delivery.
Internal
See
Note: A page 6-70.
rated.
accessories are not available on 2-pole QJ
breakers.
Accessories pages 6/75 to 6/80
6/19
Molded Case Circuit Breakers
SELECTION
CQD 100A Frame
Type CQD (Cable In - Cable Out) DIN Rail Mount
Continuous
Current Rating
@ 40°C
Shipping Weights
1-Pole
2-Pole
3-Pole
277V AC
125V DC
480Y/277V AC
125/250V DC
Number of
Poles
Number per
Carton
Shipping
Weight lbs. (kg)
480Y/277V AC
Catalog
Number
Catalog
Number
Catalog
Number
1
2
3
1
1
1
0.5 (0)
1.0 (0)
1.5 (1)
115
120
125
130
CQD115 114.00
CQD120 114.00
CQD125 114.00
CQD130 114.00
135
140
145
150
160
CQD135■114.00
CQD140■114.00
CQD145■114.00
CQD150■114.00
CQD160■114.00
CQD170■229.00
CQD180■229.00
CQD190■229.00
CQD1100■229.00
170
180
190
100
CQD215
CQD220
CQD225
CQD230
272.00
272.00
272.00
272.00
CQD315485.00
CQD320485.00
CQD325485.00
CQD330485.00
CQD235■272.00
CQD240 272.00
CQD245■272.00
CQD250 272.00
CQD260 272.00
CQD335485.00
CQD340485.00
CQD345■485.00
CQD350485.00
CQD360485.00
CQD270 542.00
CQD280 542.00
CQD290■542.00
CQD2100 542.00
CQD370657.00
CQD380657.00
CQD390657.00
CQD3100657.00
Lugs For 60/75°C Wire
Amps
Wire Size
15–40
#14–#6 AWG Cu
#12–#6 AWG Al
45–100
#8–#1 AWG Cu
#6–#1/0 AWG Al
Type CQD6 (Cable In - Cable Out) CSA Certified (not UL)
Continuous
Current Rating
@ 40°C
1-Pole
2-Pole
347V AC
125V DC
600Y/347V AC
125/250V DC
Catalog
Number
115
120
125
130
135
140
145
150
160
—
CQD6120 ■
CQD6125 ■
CQD6130 ■
CQD6135■
CQD6140■
CQD6145■
CQD6150■
CQD6160■
CQD6170■
170
3-Pole
600Y/347V AC
Catalog
Number
114.00
114.00
114.00
114.00
114.00
114.00
114.00
114.00
229.00
CQD6215■
CQD6220■
CQD6225■
CQD6230■
CQD6235■
CQD6240■
CQD6245■
CQD6250■
CQD6260■
CQD6270■
Catalog
Number
272.00
272.00
272.00
272.00
272.00
272.00
272.00
272.00
272.00
542.00
CQD6315■
CQD6320■
CQD6325■
CQD6330■
CQD6335■
CQD6340■
CQD6345■
CQD6350■
CQD6360■
—
485.00
485.00
485.00
485.00
485.00
485.00
485.00
485.00
485.00
CQD, CQD6
5.4
Interrupting Ratings
6
RMS Symmetrical Amperes (KA)
Breaker
Type
Number
of Poles
Volts AC (50/60 Hz)
CQD, CQD6
Volts DC
120
240
480/277
600/347
125
250
CIRCUIT
BREAKERS
CQD
(UL)
1
2
3
65
—
—
—
65
65
14
14
14
—
—
—
14
—
—
—
14
—
CQD6
(CSA)
1
2
3
65
—
—
—
65
65
—
—
—
14
14
14
14
—
—
—
14
—
For inches / millimeters conversion, see Application Data section.
■ Built to order. Allow 3–4 weeks for delivery.
SWD
rated.
HID
rated.
HACR rated.
6/20
Accessories pages 6/23 and 6/76 to 6/81
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
NGG 125A Frame
Type NGG (Cable In - Cable Out)
1-Pole
2-Pole
Continuous
Ampere Rating
@ 40°C
3-Pole
Catalog
Number
Catalog
Number
Catalog
Number
15
20
25
30
NGG1B015L 177.00
NGG1B020L 177.00
NGG1B025L177.00
NGG1B030L177.00
NGG2B015L473.00
NGG2B020L473.00
NGG2B025L473.00
NGG2B030L473.00
NGG3B015L591.00
NGG3B020L591.00
NGG3B025L591.00
NGG3B030L591.00
35
40
50
60
NGG1B035L177.00
NGG1B040L177.00
NGG1B050L177.00
NGG1B060L177.00
NGG2B035L473.00
NGG2B040L473.00
NGG2B050L473.00
NGG2B060L473.00
NGG3B035L591.00
NGG3B040L591.00
NGG3B050L591.00
NGG3B060L591.00
70
80
90
100
NGG1B070L209.00
NGG1B080L209.00
NGG1B090L209.00
NGG1B100L209.00
NGG2B070L557.00
NGG2B080L557.00
NGG2B090L557.00
NGG2B100L557.00
NGG3B070L695.00
NGG3B080L695.00
NGG3B090L695.00
NGG3B100L695.00
NGG2B110L1023.00
NGG2B125L1023.00
NGG3B110L1279.00
NGG3B125L1279.00
110
125
—
—
NGG
2.9
5.4
Line and load lugs are included as standard. If only load side lugs are needed, change “L” suffix to “B”.
HACR rated.
Suitable for screws or DIN rail mounting.
Shipping Weights
Number of
Poles
Number per
Carton
Shipping
Weight lbs. (kg)
1
2
3
1
1
1
.75 (0.34)
1.3 (0.59)
2.0 (0.98)
NGG
Lugs For 60/75°C Wire
NGG
Wire Size
Catalog Number
15–40A
#14–#6 AWG Cu
#12–#6 AWG Al
1TC1Q1 (qty. 1)
3TC1Q1 (qty. 3)
50–100A
#8–#1 AWG Cu
#6–#1/0 AWG Al
1TA1Q1 (qty. 1)
3TA1Q1 (qty. 3)
110–125A
#6–#1/0 AWG Cu
#4–#2/0 AWG Al
3TA1GG20 (qty. 3)
15–125A
Nut Keeper plate w/screw
(for crimp terminals)
THKG3 (qty. 3)
6
Ampere Rating
Breaker
Type
NGG
Number
of
Poles
01
2, 3
CSA / UL 489 AIR
RMS Symmetrical Amperes (KA)
Volts AC(50/60Hz)
120
240
277
347
65
—
25
18
0—
65
—
—
480
—
25
600/347
0—
TBD
Volts DC
125
250
14
—
0—
14
IEC 947-2
Volts AC (50/60Hz)
220/240
380/415
lcu
lcs
lcu
25
12.5
—
25
12.5
25
lcs
—
12.5
Volts DC
250
—
10
For inches / millimeters conversion, see Application Data section.
SWD
HID
rated.
Accessories pages 6/22 and 6/75 to 6/80
rated at 277 VAC.
6/21
CIRCUIT
BREAKERS
Interrupting Ratings
Molded Case Circuit Breakers
SELECTION
Internal Accessories for CQD 100A Frame and NGG 125A Frame
Shunt Trip
Control Voltage
V AC
V DC
CQD, CQD6, NGG
Catalog Number
120
240
277
480
600
—
—
—
—
—
CQDST120569.00
CQDST240▲
CQDST277▲0
CQDST480▲00
CQDST600
—
—
—
—
012
024
048
125
CQDST12
CQDST24
CQDST48
CQDST125
Auxiliary Switch
Maximum
Voltage
Number
AC
DC
Contacts
ofCQD, CQD6, NGG
Catalog Number
240
240
125
125
1A–1B
2A–2B
CQDA1
CQDA2
Alarm Switch
Maximum
Voltage
AC
DC
CQD, CQD6, NGG
Catalog Number
240
125
CQDBA
Shunt Trip and Auxiliary Switch
Shunt Trip Voltage
AC
DC
CQD, CQD6, NGG
Catalog Number
6
120
—
CQDST120AAS▲
240
—
CQDST240AAS▲
277
—
CQDST277AAS▲
480
—
CQDST480AAS▲
600
—
CQDST600AAS▲
—
012
CQDST12DAS▲
—
024
CQDST24DAS▲
—
048
CQDST48DAS▲
—
125
CQDST125DAS▲
Alarm and Auxillary Switch Combinations
CIRCUIT
BREAKERS
For Breaker
Catalog #
CQD, CQD6, NGG
CQDA1BA▲
▲ Built to order. Allow 7–9 weeks for delivery.
6/22
Molded Case Circuit Breakers
SELECTION
ED 125A Frame Sentron Series
Ordering Instructions
All ED Frame Sentron circuit breakers are supplied with load side lugs. If line side lugs are required, add “L” suffix to catalog number, and
breaker will be supplied with line lugs installed at no charge.
50°C Calibration, 400HZ - see page 6-73. All ED frame circuit breakers may be reverse connected.
Blue Label
Continuous
Current Rating
@ 40° C
015
020
25
030
35
040
45
050
060
070
80
90
100
2-Pole
120V AC
3-Pole
Catalog
Number
ED21B015■
ED21B020■
ED21B025■
ED21B030■
ED21B035■
ED21B040■
ED21B045■
ED21B050■
ED21B060■
ED21B070■
ED21B080■
ED21B090■
ED21B100■
112.00
112.00
112.00
112.00
112.00
112.00
112.00
112.00
112.00
ED22B015
ED22B020
ED22B025■
ED22B030
ED22B035■
ED22B040
ED22B045■
ED22B050
ED22B060
257.00
257.00
257.00
257.00
257.00
257.00
257.00
257.00
257.00
ED23B015383.00
ED23B020383.00
ED23B025■383.00
ED23B030383.00
ED23B035■383.00
ED23B040383.00
ED23B045■383.00
ED23B050383.00
ED23B060383.00
206.00
206.00
206.00
206.00
ED22B070
ED22B080■
ED22B090■
ED22B100
421.00
421.00
421.00
421.00
ED23B070 548.0
ED23B080 548.0
ED23B090 548.0
ED23B100548.00
Blue Label
1-Pole
2-Pole
120V AC
277V AC
125V DC
3-Pole
480V AC
Catalog
Number
250V DC 480V AC
Catalog
Number
Catalog
Number
015
020
025
030
035
040
045
050
060
ED41B015
ED41B020
ED41B025
ED41B030
ED41B035■
ED41B040
ED41B045■
ED41B050
ED41B060
138.00
138.00
138.00
138.00
138.00
138.00
138.00
138.00
138.00
ED42B015
ED42B020
ED42B025
ED42B030
ED42B035■
ED42B040
ED42B045■
ED42B050
ED42B060
466.00
466.00
466.00
466.00
466.00
466.00
466.00
466.00
466.00
ED43B015611.00
ED43B020611.00
ED43B025611.00
ED43B030611.00
ED43B035611.00
ED43B040611.00
ED43B045611.00
ED43B050611.00
ED43B060611.00
070
080
090
100
ED41B070
ED41B080■
ED41B090■
ED41B100
258.00
258.00
258.00
258.00
ED42B070
ED42B080■
ED42B090■
ED42B100
613.00
613.00
613.00
613.00
ED43B070719.00
ED43B080719.00
ED43B090719.00
ED43B100719.00
110
125
—
—
ED42B110■ 1239.00
ED42B125
1239.00
Type ED6
Continuous
Current Rating
@ 40° C
2-Pole
347V AC
312.00
312.00
312.00
312.00
312.00
312.00
312.00
312.00
312.00
070
080
090
100
ED61B070■
ED61B080
ED61B090
ED61B100■
—
—
429.00
429.00
429.00
429.00
■ Built to order. Allow 2–3 weeks for delivery.
250V DC
600V AC
Catalog
Number
ED61B015
ED61B020
ED61B025
ED61B030
ED61B035
ED61B040
ED61B045■
ED61B050
ED61B060
Note: ED frame circuit breakers qualified to UL 489
Supplement SB “Naval”— See page 6-74 for
additional information
3-Pole
600V AC
Catalog
Number
015
020
025
030
035
040
045
050
060
110
125
ED43B1101425.
ED43B125
Blue Label
1-Pole
ED62B015
ED62B020
ED62B025■
ED62B030
ED62B035■
ED62B040■
ED62B045■
ED62B050■
ED62B060■
ED62B070■
ED62B080■
ED62B090■
ED62B100■
—
—
Number per
Carton
Shipping
Weight (lbs.)
ED2, ED4, ED6, HED4
Catalog
Number
Type ED4
Continuous
Current Rating
@ 40° C
Number of
Poles
125V DC
250V DC 240V AC
125V DC 240V AC
Catalog
Number
Shipping Weights
500V DC
Catalog
Number
548.00
548.00
548.00
548.00
548.00
548.00
548.00
548.00
548.00
ED63B015
ED63B020
ED63B025
ED63B030
ED63B035
ED63B040
ED63B045
ED63B050
ED63B060
696
691.00
691.00
691.00
691.00
ED63B070
ED63B080
ED63B090
ED63B100
=0
ED63B110
ED63B125
16
1
2
3
30
10
10
38
25
38
2
3
5
5
20
30
CED6
Lugs
Ampere
Rating
No. of
Poles
Catalog
Number
Wire
Range
Aluminum Body Lugs
All 15–25A
1, 2, 3
All 30–100A
1, 2, 3
ED2, 4, CED6
30–60A
ED2, 4, CED6
70–100A
ED2, 4, 6,
HED4
30–100A
All 110, 125A
1
1
Line/Load
SA1E025
Line Side
LN1E100
Load Side
LD1E060
Load Side
LD1E100
#14–#10 Cu
#12–#10 Al
#10–1/0 Cu/Al
#10–#4 Cu/Al
#6–#1/0 Cu/Al
2, 3
Load Side
LN1E100
#10–1/0 Cu/Al
2, 3
Line/Load
TA1E6125
#3–3/0 Cu
#1–2/0 Al
Line/Load
TC1ED6150 #10–1/0 Cu only
CCE125
2/0
Copper Body Lugs
All 30–125A
1, 2, 3
Compression Lugs
All ED, CED
6
1-Pole
Enclosures (Neutral Included)
Type
1 (Surface)
1 (Flush)
3R
4–4X
7–9
7–9
12
1 (Surface)
1 (Flush)
3R
12
Catalog Number
E2N1S(15–100A)
E2N1F (15–100A)
E2N3R (15–100A)
ED6SS4(15–100A)
EA(15–60A)
EB(70–100A)
E2N12 (15–100A)
CED6N1S CED6N1F CED6N3R CED6N12 133.00
133.00
366.00
2541.00
1565.00
1565.00
227.00
242.00
242.00
648.00
402.00
Modifications page 6-73
Accessories pages 6-25 and 6-75 to 6-86
CSA
Certified only (Not UL)
CED types and all 110–125 ampere ED frames.
See Note: A, page 6-70.
SWD rated.
HACR rated.
For
6/23
CIRCUIT
BREAKERS
Type ED2
Molded Case Circuit Breakers
SELECTION
ED 125A Frame Sentron Series
Type HED4
Black Label
Catalog
Number
402.00
402.00
402.00
402.00
HED42B015
HED42B020
HED42B025■
HED42B030
HED42B035■
HED42B040
HED42B045■
HED42B050
HED42B060■
HED42B070■
HED42B080■
HED42B090■
HED42B100■
HED42B110■
HED42B125■
D
831.00
831.00
831.00
831.00
831.00
831.00
831.00
831.00
831.00
HED43B015
HED43B020
HED43B025
HED43B030
HED43B035
HED43B040
HED43B045
HED43B050
HED43B060
1020.00
1020.00
1020.00
1020.00
1020.00
1020.00
1020.00
1020.00
1020.00
957.00
957.00
957.00
957.00
HED43B070
HED43B080
HED43B090
HED43B100
1098.00
1098.00
1098.00
1098.00
1946.00
1946.00
HED43B110
HED43B125
2244.00
2244.00
D1
H
W1
W3
W2
1 POLE
2 POLE
3 POLE
FIGURE 2 - CED (3 Pole shown)
355.00
355.00
355.00
355.00
355.00
355.00
355.00
355.00
355.00
110
125
480V AC
070
080
090
100
250V DC
D
HED41B015
HED41B020
HED41B025
HED41B030
HED41B035■
HED41B040
HED41B045■
HED41B050■
HED41B060■
HED41B070■
HED41B080■
HED41B090■
HED41B100■
—
—
015
020
025
030
035
040
045
050
060
480V AC
Catalog
Number
125V DC
277V AC
Catalog
Number
FIGURE1 - ED, HED
3-Pole
Continuous
Current Rating
@ 40° C
2-Pole
1-Pole
D1
Fuseless Current Limiting
Type CED6
6
2-Pole
600V AC, 250V DC
Catalog
Number
CED62B015
CED62B020■
—
CED62B030■
—
CED62B040■
—
CED62B050■
CED62B060■
CED62B070■
CED62B080■
CED62B090■
CED62B100■
—
CED62B125■
3-Pole
600V AC, 500V DC Catalog
Number
2465.00 CED63B015
2465.00 CED63B020
—
—
2465.00 CED63B030
—
—
2465.00 CED63B040
—
—
—
2465.00 CED63B050
2465.00 CED63B060
2465.00 CED63B070
2465.00 CED63B080
2465.00 CED63B090
2465.00 CED63B100
CED63B110■
3698.00 CED63B125
Continuous
Current
Rating
@ 40°C
015
020
025
030
035
040
045
050
060
070
080
090
100
110
125
H
Red Label
2862.00
2862.00
W2, W3
2862.00
2862.00
Dimensions (in inches)
2862.00
2862.00
2862.00
2862.00
2862.00
2862.00
4368.00
4368.00
Breaker Type
W1
W2
W3
H
D
D1
Figure 1
ED2, ED4, ED6, HED4,
ED6 ETI
1
2
3
6.35
3.92
4.56
Figure 2
CED6, CED6 ETI
—
2
3
9.58
3.92
4.56
Interrupting Ratings
CIRCUIT
BREAKERS
Breaker
Type
ED2 (1-P)
ED2 (2, 3-P)
ED4 (1-P)
ED4 (2, 3-P)
ED6 (1P)
ED6 (2, 3-P)
HED4 (1-P)
(15–30A)
HED4 (1-P)
(35–100A)
HED4 (2, 3-P) CED6 (2, 3-P)
CSA C22.2 / UL 489 AIR (File #E10848)
RMS Symmetrical Amperes (KA)
Volts AC
120
240
277
347
480
010
—
—
—
—
—
010
—
—
—
065
—
22
—
—
—
065
—
—
018
—
—
—
—
30 —
065
—
—
025
500
lcu
—
—
—
—
—
18
lcs
—
—
—
—
—
5
—
65
—
—
—
30
—
—
—
—
—
—
—
—
—
100
200
25
—
—
—
—
—
—
042
200
—
30
—
—
—
30 (2-P)
30 (2-P)
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems.
6/24
500 —
—
—
—
—
18 (3-P)
100
rated.
When
Volts DC
125
250
05
—
—
05 (2-P)
30
—
—
30 (2-P)
—
—
—
30 (2-P)
100
—
—
■ Built to order. Allow 2–3 weeks for delivery.
SWD
600
—
—
—
—
—
018
IEC 947-2
Volts AC (50/60Hz)
220/240
380/415
lcu
lcs
lcu
lcs
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
65
17
35
9
100
50 (3-P)
HED4
Single
ED6-ETI,
HACR
type circuit breakers meet the CSA / UL criteria for
“current limiting” at 240V AC.
CED6-ETI, see page 6-56 for ordering
information.
Pole 15-30A 30KA @ 347V
35-100A 18KA @ 347V
rated.
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Combinations
Available only when ordered together.
Only one module can be added to a
breaker. Additional accessories, which
always attach to the left pole, cannot be
added to the combination later.
Equipment
Ground Sensing
A field addable kit containing 30mA or
5 mA ground fault accessory module,
current transformer with 24 inch leads,
and current transformer mounting
equipment. Current transformer to
mount in gutter of lighting panel or any
control panel. Accessory module
operates from separate 120V control
power source.
Both 30MA and 5MA devices are
equipment protection devices only. Do
not use for personnel protection.
Control
Voltage
1 Shunt Trip
1 Shunt Trip
1 Shunt Trip and
1 Auxiliary Switch
1 Auxiliary Switch and 1 Alarm Switch
1 Shunt Trip and
1 Alarm Switch
1 Shunt Trip and 2
Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
024
048
120
208
240
277
480
—
—
—
—
—
—
—
S17ED60
S18ED60
S01ED60
—
S03ED60
S15ED60▲
S04ED60
—
—
S01ED62A
S02ED62A▲
S03ED62A
S15ED64A▲
S04ED64A▲
—
—
S01ED62AB
S02ED62AB▲
S03ED62AB
S15ED64AB▲
S04ED64AB▲
—
—
S01ED62B
S02ED62B▲
S03ED62B▲
S15ED64B▲
S04ED64B▲
—
—
S01ED62AA
S02ED62AA▲
S03ED62AA▲
—
—
—
—
—
—
—
012
024
048
125
250
S16ED60▲
S07ED60
S09ED60▲
S11ED60▲
S13ED60▲
S16ED62A▲
S07ED62A
S09ED62A▲
S11ED62A▲
S13ED62A▲
—
S07ED62AB▲
S09ED62AB▲
S11ED62AB▲
S13ED62AB▲
—
S07ED62B▲
S09ED62B▲
S11ED62B▲
S13ED62B▲
—
S07ED62AA▲
S09ED62AA▲
S11ED62AA▲
S13ED62AA▲
Undervoltage Trip Combinations
Control
Voltage
1 Undervoltage
Trip
1 Undervoltage Trip
1 Undervoltage
and 1 Auxiliary
1 Undervoltage
Trip and
Switch and
Trip and
1 Auxiliary Switch 1 Alarm Switch
1 Alarm Switch
1 Undervoltage
Trip and 2
Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
Catalog Number
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01ED60
U02ED60▲
U03ED60
U16ED60▲
U06ED60▲
U08ED60▲
U01ED62A
U02ED62A▲
U03ED62A▲
U16ED64A▲
U06ED64A▲
—
U01ED62AB▲
U02ED62AB▲
U03ED62AB▲
U16ED64AB▲
U06ED64AB▲
—
U01ED62B▲
U02ED62B▲
U03ED62B▲
U16ED64B▲
U06ED64B▲
—
U01ED62AA▲
U02ED62AA▲
U03ED62AA▲
—
—
—
—
—
—
—
024
048
125
250
U13ED60
U14ED60▲
U10ED60▲
U12ED60▲
U13ED62A▲
U14ED62A▲
U10ED62A▲
U12ED62A▲
U13ED62AB▲
U14ED62AB▲
U10ED62AB▲
—
U13ED62B▲
U14ED62B▲
U10ED62B▲
—
U13ED62AA▲
U14ED62AA▲
U10ED62AA▲
U12ED62AA▲
Auxiliary and Alarm Switch Combinations
Maximum
Voltage
1 Auxiliary
Switch*
1 Alarm Switch
Alarm Switch and 2 Auxiliary
1 Auxiliary Switch Switches
1 Alarm Switch and
2 Auxiliary Switches
AC
DC
Catalog Number Catalog Number
240
250
A01ED62
B00ED62
Catalog Number
Catalog Number
Catalog Number
A01ED62B
A02ED62
480
—
A01ED64
A02ED62B
B00ED64
A01ED64B
—
—
12
A01EDLV*
—
306.00
Gold Plated Contacts—for PLC use
Ground Fault Sensing Relay Kit — Equipment Protection Only
For Use With
Breaker Frame
ED2, ED4, ED6,
HED4
1550.00
Number of
Poles
Description
1, 2, 3
Catalog Number
30mA
5mA
Basic Kit
GF01ED60
GF01ED651326.00
Basic Kit with Normally
Open Bell Alarm
GF01ED60B0
GF01ED65B0▲
Basic Kit with Normally
Closed Bell Alarm
GF01ED60BC
GF01ED65BC▲
1550.00
▲ Built to order. Allow 7–9 weeks for delivery.
6/25
6
ED 125A Frame
Shunt Trip Combinations
CIRCUIT
BREAKERS
Accessories for:
Molded Case Circuit Breakers
SELECTION
FD 250A Frame Sentron Series
Blue Label
Type FXD6-A Non-Interchangeable Trip (Assembled Circuit Breaker – Without Lugs)
2-Pole Catalog
Number
FXD62B070■
FXD62B080■
FXD62B090■
FXD62B100
FXD62B110■
FXD62B125
FXD62B150
FXD62B175
FXD62B200
FXD62B225
FXD62B250
Continuous
Current Rating
@ 40°C
70
80
90
100
110
125
150
175
200
225
250
3-Pole
1610.00
1610.00
1610.00
1610.00
1610.00
1610.00
1610.00
1610.00
1610.00
1610.00
2738.00
Type FD6-A
Catalog
Number
FXD63B0702036
FXD63B0802036.
FXD63B0902036.
FXD63B1002036.
FXD63B1102036.
FXD63B1252036.
FXD63B1502036.00
FXD63B175236.00
FXD63B200203
FXD63B225
.00
FXD63B250
Blue Label
Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Catalog
Number
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
2-Pole 600V AC, 250V DC FD62B070■1695.20
FD62B080■1695.20
FD62B090■1695.20
FD62B100■1695.20
FD62B110■1695.20
FD62B125■1695.20
FD62B150■1695.20
FD62B175■1695.20
FD62B200■1695.20
FD62B225■1695.20
FD62B250■2824.20
70
80
90
100
110
125
150
175
200
225
250
FD62T070■ 839.00
FD62T080■ 839.00
FD62T090■ 839.00
FD62T100■ 839.00
FD62T110■ 839.00
FD62T125■ 839.00
FD62T150■ 839.00
FD62T175■ 839.00
FD62T200■ 839.00
FD62T225■ 839.00
FD62T250■1968.00
FD62F250 777.00
3-Pole 600V AC, 500V DC 6
FD63B070■2159.80
FD63B080■2159.80
FD63B090■2159.80
FD63B100 2159.80
FD63B110■2159.80
FD63B125 2159.80
FD63B150 2159.80
FD63B175 2159.80
FD63B200 2159.80
FD63B225 2159.80
FD63B250 3320.80
70
80
90
100
110
125
150
175
200
225
250
FD63T070■1035.00
FD63T080■1035.00
FD63T090■1035.00
FD63T100 1035.00
FD63T110■1035.00
FD63T125 1035.00
FD63T150 1035.00
FD63T175 1035.00
FD63T200 1035.00
FD63T225 1035.00
FD63T250 2196.00
FD63F2501006.00
Interrupting Ratings
CIRCUIT
BREAKERS
Breaker
Type
FXD6-A, FD6-A
HFXD6 , HFD6 HHFD6 , HHFXD6 CFD6
RMS Symmetrical Amperes (KA)
CSA / UL 489 AIR (File E10848)
Volts AC (50/60Hz)
Volts DC
240
480
600
250
500 65
100
200
200
35
65
100
200
22
25
25
100
30 (2-P)
30 (2-P)
—
50 (2-P)
18 (3-P)
25 (3-P)
—
50 (3-P)
IEC 947-2
Volts AC (50/60Hz)
220/240 380/415
lcu lcs lcu lcs
65 33
35
9
100 50
65 33
200 100 100 50
—
—
—
—
500
lcu
20
42
65
—
170-90
100-110
125-150
175-200
225-250
Nominal Instantaneous Values
Low
2
3
4
600
700
800
900
1100
640
770
900
1060
1300
690
840
1000
1210
1500
Note: FD frame qualified to UL489 supplement SB “NAVAL”.
See page 6-73 for additional information.
6/26
730
920
1100
1370
1700
Complete Breaker Unassembled with
Lugs
Prices of FD6, HFD6, and HHFD6
breakers includes frame, trip and
both line and load lugs (TA1FD350).
When ordered by these catalog
numbers, the customer will receive
the frame, trip, and lugs separately
packaged. For applications requiring
different lugs, order individual items
as needed.
Complete Breaker Assembled
without Lugs
Prices of FXD6, HFXD6, HHFXD6,
and CFD6 includes frame with noninterchangeable trip unit installed
only. Order required lugs separately.
For line and load lugs (TA1FD350A)
installed, add suffix “L” to catalog
number (add 2 times list price of
lugs for each pole).
50°C Applications see page 6-73.
400 Hz Applications see page 6-73.
Lugs For 75°C Wire Catalog
Number
Wire
Range
#6—350 kcmil Cu
#4—350 kcmil Al
TC1FD350
#6—350 kcmil Cu
Compression Lug
TA1FD350A
CCF250
350 kcmil Cu/Al
19.80
31.00
45.50
Enclosures
Type
Catalog
Number
1
3R
4-4X
7-9
12
Neutral F6N1S(F)
F6N3R
FD6SS4
EC2
F6N12
N250
164.00
542.00
4221.00
4306.00
366.00
128.00
lcs
10
21
33
—
Instantaneous Adjustment Trip Range
Breaker Ampere
Rating
Ordering Information
Modifications page 6-73
Accessories pages 6-28 and 6-75 to 6-80
5
6
7
High
770
990
1200
1520
1900
810
1060
1300
1780
2100
850
1140
1400
1930
2300
900
1200
1500
2000
2500
■ Built to order. Allow 3–4 weeks for delivery.
Type
FXD6-A circuit breakers are UL Listed for reverse
fed applications.
2-pole
units are 3-pole width.
wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
Order neutral as separate item.
See Note: A, page 6-71.
HFD6 and HHFD6 type circuit breakers meet the
UL criteria for “current limiting” at 240 and 480V AC.
HACR rated.
When
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
FD 250A Frame Sentron Series
Type HFD6 , Type HFXD6 Black Label
Interchangeable Trip
Frame Only
Trip Unit Only
Catalog
Number
Catalog
Number
Catalog
Number
D1
L
2-Pole 600V AC, 250V DC (3 Pole Width)
HFD63F250 3366.00
FD63T070■
FD63T080■
FD63T090■
FD63T100
FD63T110■
FD63T125
FD63T150
FD63T175
FD63T200
FD63T225
FD63T250
1035
1035
1035
1035
1035
1035
103
103
103
1035
Type HHFD , HHFXD6 HHFD63B070■
HHFD63B080■
HHFD63B090■
HHFD63B100
HHFD63B110■
HHFD63B125
HHFD63B150
HHFD63B175
HHFD63B200
HHFD63B225
HHFD63B250
Figure 1
W
D
Figure 2
Breaker
Type
Figure 1
FXD6-A, FD6-A,
HFD6, HFXD6,
HHFD6, FD6-ETI Figure 2
CFD6,
CFD6-ETI W
L
D
D1
(to
handle)
4.50
09.50
4
5.25
4.50
14.25
4
5.25
Shipping Weights
3-Pole 600V AC, Extra High Interrupting
070
080
090
100
110
125
150
175
200
225
250
W
HHFD63F2504093.00
FD63T070■1035.0
FD63T080■1035.0
FD63T090■1035.0
FD63T100 1035.0
FD63T110■1035.0
FD63T125 1035.0
FD63T150 1035.0
FD63T175 1035.0
FD63T200 1035.0
FD63T225 1035.0
FD63T250
Type CFD6 Red Label
Fuseless Current Limiting
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
FD6-A, HFD6, HHFD6, FXD6-A
Assembled Circuit Breaker (less connectors)
08.6
2
1
3
1
10
FD6-A, HFD6, HHFD6 Frame Only
07.5
2
1
08.7
3
1
FD6 Trip Unit Only
2
1
01.1
01.3
3
1
CFD6 Assembled Circuit Breaker (less terminals)
2
1
31
3
1
34
3-Pole
Continuous
Current Rating
@ 40°C
070
080
090
100
110
125
150
175
200
225
250
■ Built to order. Allow 3–4 weeks for delivery.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems.
For non-interchangeable trip 3-pole HFD6 type circuit
600V AC/500V DC
Catalog
Number
CFD63B070■
CFD63B080■
CFD63B090■
CFD63B100■
CFD63B110■
CFD63B125■
CFD63B150
CFD63B175
CFD63B200
CFD63B225
CFD63B250
5675.00
5675.00
5675.00
5675.00
5675.00
5675.00
5675.00
5675.00
5675.00
5675.00
6306.00
breaker, change prefix identifier from HFD6 to HFXD6.
Price equals frame and trip prices combined, e.g. price
of HFXD63B250 equals price of HFD63F250 plus price of
FD63T250. Order lugs separately.
Type HFXD6, HHFXD6, CFD6 are CSA Certified / UL
Listed for reverse feed applications.
Type HFXD6, HFD6, HHFD6, HHFXD6 meet the CSA
Certified / UL criteria for “Current Limiting” at 240 VAC
and 480V AC.
FXD6, ETI, CFD6, ETI — See page 6-55 for
ordering information.
HACR rated.
6/27
6
HFD63B070■4519.80
HFD63B080■4519.80
HFD63B090■4519.80
HFD63B100 4519.80
HFD63B110■4519.80
HFD63B125 4519.80
HFD63B150 4519.80
HFD63B175 4519.80
HFD63B200 4519.80
HFD63B225 4519.80
HFD63B250 5680.80
Dimensions (in inches)
3-Pole 600V AC, 500V DC 070
080
090
100
110
125
150
175
200
225
250
L
HFD62F250 2798.00
FD62T070■839.00
FD62T080■839.00
FD62T090■839.00
FD62T100■839.00
FD62T110■839.00
FD62T125■839.00
FD62T150■839.00
FD62T175■839.00
FD62T200■839.00
FD62T225■839.00
FD62T250■
D
HFD62B070■3716.20
HFD62B080■3716.20
HFD62B090■3716.20
HFD62B100■3716.20
HFD62B110■3716.20
HFD62B125■3716.20
HFD62B150■3716.20
HFD62B175■3716.20
HFD62B200■3716.20
HFD62B225■3716.20
HFD62B250■4845.20
070
080
090
100
110
125
150
175
200
225
250
CIRCUIT
BREAKERS
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
FD 250A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip
AC
DC
Catalog Number
024
120
240
277
480
600
—
—
—
—
—
—
S17FD60
S01FD60
S03FD60
S15FD60▲
S04FD60
S06FD60▲
—
—
—
—
—
012
024
048
125
250
S16FD60▲
S07FD60
S09FD60▲
S11FD60
S13FD60▲
Undervoltage Trip Combinations
Control Voltage
1 Undervoltage Trip and
1 Auxiliary Switch 1 Undervoltage Trip
AC
DC
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01FD60
U02FD60▲
U03FD60
U16FD60▲
U06FD60▲
U08FD60▲
569.00
569.00
569.00
569.00
569.00
569.00
Catalog Number
W01FD64
W02FD64▲
W03FD64▲
W16FD64▲
W06FD64▲
W08FD64▲
802.00
802.00
802.00
802.00
802.00
802.00
—
—
—
—
024
048
125
250
U13FD60
U14FD60▲
U10FD60▲
U12FD60▲
569.00
569.00
569.00
569.00
W13FD64
W14FD64▲
W10FD64▲
W12FD64▲
802.00
802.00
802.00
802.00
Auxiliary Switch Combinations
1 Auxiliary Switch*
2 Auxiliary Switches
Voltage
AC
DC
Catalog Number
480
—
A01FD64
242.00
Catalog Number
A02FD64
—
12
A01FDLV*
306.00
Gold Plated Contacts - for PLC use
483.00
6
Alarm Switch Combinations
CIRCUIT
BREAKERS
▲ Built to order. Allow 7–9 weeks for delivery.
Auxiliary switch application is for 480V AC maximum.
Note: Old F-frame accessories cannot be used in new
Sentron line. Likewise, new FD-frame accessories
cannot be used on old F-frame circuit breakers.
6/28
Maximum
Voltage
1 Alarm Switch
1 Alarm Switch and
1 Auxiliary Switch
AC
DC
Catalog Number
Catalog Number
480
250
B00FD64
242.00C01FD64
483.00
Molded Case Circuit Breakers
SELECTION
JD 400A Frame Sentron Series
Type JXD2-A
Blue
240V AC, 250V DC
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
2-Pole (3 Pole Width)
Catalog
Number
JXD22B200■2277.00
JXD22B225■2277.00
JXD22B250■2277.00
JXD22B3002277.00
JXD22B350■2277.00
JXD22B4002277.00
Continuous
Current Rating
@ 40°C
200
225
250
300
350
400
3-Pole
Catalog
Number
JXD23B2002767.00
JXD23B2252767.00
JXD23B2502767.00
JXD23B3002767.00
JXD23B3502767.00
JXD23B4002767.00
Type JXD6-A Blue
600V AC, 500V DC Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
JXD62B200■2847.00
JXD62B225■2847.00
JXD62B250■2847.00
JXD62B3002847.00
JXD62B350■2847.00
JXD62B4002847.00
200
225
250
300
350
400
Label
Label
JXD63B2003366.00
JXD63B2253366.00
JXD63B2503366.00
JXD63B3003366.00
JXD63B3503366.00
JXD63B4003366.00
Type JD6-A
Blue Label
Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Catalog
Number
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
2-Pole 600V AC, 250V DC (3 Pole Width)
200
225
250
300
350
400
JD62B200■2958.00
JD62B225■2958.00
JD62B250■2958.00
JD62B300■2958.00
JD62B350■2958.00
JD62B400 2958.00
JD62F400 1184.00
JD62T200■1662.00
JD62T225■1662.00
JD62T250■1662.00
JD62T300■1662.00
JD62T350■1662.00
JD62T400 1662.00
JD63F400 1515.00
JD63T200
JD63T225
JD63T250
JD63T300
JD63T350
JD63T400
Ordering Information
Complete Breaker Unassembled
with Lugs
Prices of JD6, HJD6, and HHJD6
breakers include frame, trip and
both line and load lugs (TA2J6500).
When ordered by these catalog
numbers, the customer will receive
the frame, trip, and lugs separately
packaged. For applications
requiring different lugs, order
individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of JXD6, HJXD6, HHJXD6,
and CJD6 include frame with noninterchangeable trip unit installed
only. Order required lugs separately.
For line and load lugs (TA2J6500)
installed, add suffix “L” to catalog
number (add 2 times list price of
lugs for each pole).
100% Rated
Types JXD2, JXD6 and HJXD6
breakers are available with 100%
ratings. To order add suffix “H” to
catalog number, and 10% to list
price.■ 100% rated JD breakers
require the use of 90°C Cu cable
and lugs TC1J6600 or TC2J6500.
50°C Applications see page 6-73.
400Hz Applications see page 6-73.
JD63B200
JD63B225
JD63B250
JD63B300
JD63B350
JD63B400
3534.00
3534.00
3534.00
3534.00
3534.00
3534.00
1851.00
1851.00
1851.00
1851.00
1851.00
1851.00
Interrupting Ratings
Breaker
Type
JXD2-2
JXD6-2, JD6-A
HJD6-A, HJXD6-A
HHJD6-A, HHJXD6 CJD6
RMS Symmetrical Amperes (KA)
CSA / UL 489 AIR (File E10848)
Volts AC
Volts DC
(50/60Hz)
240
480
600
250
065
—
—
30 (2-P)
065
035
025
30 (2-P)
100
065
035
30 (2-P)
200
100
050
—
200
150
100
50 (2-P)
IEC 947-2
Volts AC (50/60Hz)
220/240 380/415
500 lcu lcs lcu lcs
—
—
—
—
—
25 (3-P) 065 033 040 20
35 (3-P) 100 050 065 33
—
200 100 100 50
50 (3-P) —
—
—
—
Lugs For 75°C Wire Cables
per
Lug
1, 2
2
1
TA1L6750 1
1
TC1J6600 1
TC2J6500 1, 2
Compression Lug
CCL600
1
Catalog
Number
TA2J6500
500
lcu
—
30
42
65
—
lcs
—
15
21
33
—
Wire
Range
#3/0-500 kcmil Cu
#4/0-500 kcmil Al
250-500 kcmil Al
500-750 kcmil Al
500-600 kcmil Cu
#3/0-600 kcmil Cu
#3/0-500 kcmil Cu
500 kcmil Cu/Al
28.00
68.00
69.00
68.00
134.00
Instantaneous Adjustment Trip Range
Breaker Ampere
Rating
Nominal Instantaneous Values
Low
2
3
4
5
6
7
High
200-300
1250
1430
1610
1790
1960
2140
2320
2500
350-400
2000
2290
2570
2860
3140
3430
3710
4000
■ Built to order. Allow 3-4 weeks for delivery.
Type
JXD6 circuit breakers are UL Listed for reverse
feed applications.
When
wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
See Note: A, page 6-70.
HHJD6
type circuit breakers meet the CSA / UL criteria
for “current limiting” at 240 and 480V AC.
rated.
Note: JD frame qualified to UL489 supplement B “NAVAL.”
See page 6-73 for additional information.
HACR
Modifications page 6-73
Accessories pages 6-32 and 6-75 to 6-80
6/29
CIRCUIT
BREAKERS
200
225
250
300
350
400
6
3-Pole 600V AC, 500V DC Molded Case Circuit Breakers
SELECTION
JD 400A Frame Sentron Series
Black Label
Type HJD6-A, HJXD6-A Interchangeable Trip
Complete Breaker
Unassembled with Lugs
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
D1
Catalog
Number
Continuous
Current Rating
@ 40°C
L
2-Pole 600V AC, 250V DC (3 Pole Width)
HJD63B200 5845.00
HJD63B225 5845.00
HJD63B250 5845.00
HJD63B300 5845.00
HJD63B350 5845.00
HJD63B400 5845.00
Type HHJD6, HHJXD6-A
HJD63F400 3826.00
JD63T200 1851.00
JD63T225 1851.00
JD63T250 1851.00
JD63T300 1851.00
JD63T350 1851.00
JD63T400 1851.00
Black Label
2-Pole 600V AC (3 Pole Width)
200
225
250
300
350
400
HHJD62B200■5832.00
HHJD62B225■5832.00
HHJD62B250■5832.00
HHJD62B300■5832.00
HHJD62B350■5832.00
HHJD62B400■5832.00
200
225
250
300
350
400
HHJD63B2007011.00
HHJD63B2257011.00
HHJD63B2507011.00
HHJD63B3007011.00
HHJD63B3507011.00
HHJD63B4007011.00
HHJD62F400■4058.00
HHJD63F4004992.00
JD62T200■1662.0
JD62T225■1662.0
JD62T250■1662.0
JD62T300■1662.0
JD62T350■1662.0
JD62T400
JD63T200
JD63T225
JD63T250
JD63T300
JD63T350
JD63T400
6
Type CJD6 Red
Fuseless Current Limiting
Non-Interchangeable Trip (Assembled Circuit Breakers Without Lugs)
CIRCUIT
BREAKERS
Continuous
Current Rating
@ 40°C
200
225
250
300
350
400
For inches / millimeters conversion,
see Application Data section.
■ Built to order. Allow 3-4 weeks for delivery.
2-pole units available in 3-pole construction.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
6/30
3-Pole 600V AC, 500V DC 200
225
250
300
350
400
L
1851.00
1851.00
1851.00
1851.00
1851.00
1851.00
Label
2-Pole
3-Pole
600V AC/250V DC
600V AC/500V DC
Catalog
Number
For 2-pole application
use outside poles of
3-pole circuit breaker
For
CJD63B200■7303.
CJD63B225■7303.
CJD63B250■7303.
CJD63B300■7303.
CJD63B350■7303.
CJD63B4007303.00
non-interchangeable 3-pole HJD6 or HHJD6 type
circuit breaker change the prefix identifier to HJXD6
or HHJXD6. Order lugs separately.
W
W
Figure 1
D
HJD62F400■3077.00
JD62T200■1662.0
JD62T225■1662.0
JD62T250■1662.0
JD62T300■1662.0
JD62T350■1662.0
JD62T400
HJD62B200■4851.00
HJD62B225■4851.00
HJD62B250■4851.00
HJD62B300■4851.00
HJD62B350■4851.00
HJD62B400■4851.00
D
200
225
250
300
350
400
Figure 2
Dimensions (in inches)
D
To
Handle
D1
Figure 1
JXD2-A, JXD6-A, JD6-A
HJD6-A, HJXD6-A, HHJD6, 7.5 11
HJD6, HJXD6, HHJXD6,
JXD6-ETI 4
5.44
Figure 2
CJD6, CJD6-ETI 4
5.44
Breaker
Type
W
L
7.5 17.86
Enclosures
Type
Catalog
Number
List
Price $
1
3R
12
4X
7, 9 (200-250A)
7, 9 (300-400A)
J6N1
J6N3R
J6N12
LD6SS4
EC4
EE
231.00
1246.00
648.00
6211.00
4306.00
5958.00
Neutral
W60992
348.00
Shipping Weights
Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
JXD2, JXD6, JD6, HJD6, HHJD6
Assembled Breaker (less terminals)
2
1
17.5
3
1
19.5
JD6, HJD6, HHJD6 Frame Only
2
1
14
3
1
15.5
JD6 Trip Unit Only
2
1
03.5
3
1
04
CJD6 Complete Assembled Breaker
(less terminals)
2
1
29.5
3
1
31.5
JXD6-ETI,
CJD6-ETI see page 6-56 for ordering information.
HJXD6, HHJXD6 Circuit Breakers are CSA Certified /
UL listed for reverse fed applications.
CE applies to non-interchangeable type HJXD only.
HACR rated.
Type
Molded Case Circuit Breakers
SELECTION
SJD 400A Frame Digital Solid State Sentron Sensitrip III
Current Limiting
Type SHJD6(A)
Type SJD6(A)
Blue Label
Black Label
3-Pole, 600V AC
Catalog
Number
200
300
400
4082.00
4082.00
4082.00
200
300
400
6530.00
6530.00
6530.00
200
300
400
5545.00
5545.00
5545.00
200
300
400
8195.00
8195.00
8195.00
SHJD69200■
SHJD69300■
SHJD69400■
SHJD69200G■
SHJD69300G■
SHJD69400G■
SHJD69200NT■
SHJD69300NT■
SHJD69400NT■
SHJD69200NGT■
SHJD69300NGT■
SHJD69400NGT■
200
300
400
5812.00
5812.00
5812.00
200
300
400
8195.00
8195.00
8195.00
200
300
400
7197.00
7197.00
7197.00
200
300
400
9941.00
9941.00
9941.00
SJD 400A Frame – 100% Rated
Type SJD6A-H
Blue Label
200
300
400
7734.00
7734.00
7734.00
200
300
400
10498.00
10498.00
10498.00
200
300
400
9290.00
9290.00
9290.00
200
300
400
12818.00
12818.00
12818.00
Black Label
Catalog
Number
200
300
400
4478.00
4478.00
4478.00
200
300
400
7197.00
7197.00
7197.00
200
300
400
6098.00
6098.00
6098.00
200
300
400
9006.00
9006.00
9006.00
Trip
Type
Breaker
Type
Number per
Carton
Shipping
Weight (lbs)
SJD6(A), SLD6(A)
SHJD6(A),
SHLD6(A)
SCJD6, SCLD6
1
20
No of
Cables
Catalog
per ConNumber
nector
2
TA2J6500 2
1
TA1L6750 1
TC1J6600 1
TC2J6500 2
TA2J630 2
Compression Lug
CCL600
(1 pc.)
Max
Current
Rating
SHJD69200H■
SHJD69300H■
SHJD69400H■
SHJD69200GH■
SHJD69300GH■
SHJD69400GH■
SHJD69200NTH■
SHJD69300NTH■
SHJD69400NTH■
SHJD69200NGTH■
SHJD69300NGTH■
SHJD69400NGTH■
200
300
400
6402.00
6402.00
6402.00
200
300
400
9022.00
9022.00
9022.00
200
300
400
7894.00
7894.00
7894.00
200
300
400
10944.00
10944.00
10944.00
1
20
1
33
Cont
Current
Setting
Long
Time
Delay
Instantaneous
Setting
Short
Time
Pick Up
Wire
Range
#3/0-500 kcmil Cu
#4/0-500 kcmil Cu
500–750 kcmil Cu/Al
500–600 kcmil Cu
#3/0-600 kcmil Cu
#3/0-500 kcmil Cu
#4–#3/0-Cu/Al
List
Price
$
28.00
28.00
68.00
68.00
69.00
68.00
29.00
#1/0-500 kcmil Cu/Al 134.00
Neutral Transformers
(for 3ø, 4 wire)
Ampere
Rating
Trip Unit Adjustable Functions
Suffix
Letter
Code
Shipping Weights
Lugs for 75° C Wire
3-Pole, 600V AC
Max
Current
Rating
SJD69200H■
SJD69300H■
SJD69400H■
SJD69200GH■
SJD69300GH■
SJD69400GH■
SJD69200NTH■
SJD69300NTH■
SJD69400NTH■
SJD69200NGTH■
SJD69300NGTH■
SJD69400NGTH■
SCJD69200■
SCJD69300■
SCJD69400■
SCJD69200G■
SCJD69300G■
SCJD69400G■
SCJD69200NT■
SCJD69300NT■
SCJD69400NT■
SCJD69200NGT■
SCJD69300NGT■
SCJD69400NGT■
Type SJD6(A)-H
3-Pole, 600V AC
Catalog
Number
Max
Current
Rating
Catalog
Number
Short
Time
Delay
Short
Time
l 2t
Pick Up
Ground
Fault
Pick Up
Ground
Fault
Delay
None
LI
—
—
—
—
—
G
LIG
—
—
—
NT
LSI
—
—
NGT
LSIG
Interrupting Ratings
Breaker
Type
RMS Symmetrical kA CSA / UL 489 (File E10848)
240V AC
480V AC
600V AC
SJD6 – SLD6
SHJD6 – SHLD6
SCJD6 – SCLD6
065
100
200
035
065
150
025
035
100
200
300
400
500
600
Catalog
Number
N02SJD
N03SJD
N04SJD
N05SLD
N06SLD
354.00
354.00
354.00
354.00
354.00
Enclosures
(For JD frame, excluding SCJD6)
Type
Catalog
Number
1
3R
4–4X
7, 9 (200–250A)
7, 9 (300–400A)
12
J6N1
J6N3R
LD6SS4
EC4
EE
J6N12
231.00
1246.00
6211.00
4306.00
5958.00
648.00
Neutral
W60992
348.00
Accessories pages 6/32 and 6/75 to 6/80
Note: “G” suffix in catalog number denotes circuit breaker
for 3 phase, 3 wire systems.
For 3 phase, 4 wire, order correct 4th wire (neutral)
transformer as separate and additional item.
6
SJD69200■
SJD69300■
SJD69400■
SJD69200G■
SJD69300G■
SJD69400G■
SJD69200NT■
SJD69300NT■
SJD69400NT■
SJD69200NGT■
SJD69300NGT■
SJD69400NGT■
3-Pole, 600V AC
Max
Current
Rating
Required lugs for Digital Sentron
Series SJD and SLD frames are sold
as separate items. Separate items
– lugs are suitable for 75° C wire.
SJD6, SCJD6, SLD6, SCLD6 are
acceptable for reverse connection
application.
SHJD6 and SHLD6 are not
acceptable for reverse connection
application.
■ Built to order. Allow 3-4 weeks for delivery.
For additional information, see Note: A, page 6-71.
Refer to the NEC for proper application of 100%
rated devices.
6/31
CIRCUIT
BREAKERS
Catalog
Number
Red Label
3-Pole, 600V AC
Max
Current
Rating
Ordering Information
Type SCJD6
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
JD 400A Frame
LD 600A Frame
LMD 800A Frame
SJD 400A Frame
SLD 600A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip and
1 Auxiliary Switch
1 Shunt Trip
AC
DC
024
048
120
240
277
480
—
—
—
—
—
—
Catalog Number
S17JLD6
S18JLD6▲
S01JLD6
S03JLD6
S15JLD6▲
S04JLD6
569.00
569.00
569.00
569.00
569.00
569.00
Catalog Number
—
—
S01JLD62A
S03JLD62A
S15JLD64A▲
—
802.00
802.00
802.00
-
—
—
—
—
—
012
024
048
125
250
S16JLD6▲
S07JLD6
S09JLD6▲
S11JLD6
S13JLD6▲
569.00
569.00
569.00
569.00
569.00
S16JLD62A▲
S07JLD62A
S09JLD62A
S11JLD62A▲
S13JLD62A▲
802.00
802.00
802.00
802.00
802.00
Undervoltage Trip Combinations
Control
Voltage
Sensitrip Ammeter
1 Undervoltage Trip
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
Catalog Number
U01JLD6 569.00
U02JLD6▲569.00
U03JLD6 569.00
U16JLD6▲569.00
U06JLD6 569.00
U08JLD6▲569.00
U01JLD62A802.00
U02JLD62A▲802.00
U03JLD62A▲802.00
U16JLD64A▲802.00
U06JLD64A▲802.00
—
--
U01JLD62AA1035.00
U02JLD62AA▲1035.0
U03JLD62AA▲1035.0
U16JLD62AA▲1035.0
U06JLD64AA▲1035.0
—
--
—
—
—
—
024
048
125
250
U13JLD6 569.00
U14JLD6▲569.00
U10JLD6▲569.00
U12JLD6▲569.00
U13JLD62A802.00
U14JLD62A▲802.00
U10JLD62A▲802.00
U12JLD62A▲802.00
U13JLD62AA1035.00
U14JLD62AA▲1035.0
U10JLD62AA▲1035.0
U12JLD62AA▲
Auxiliary Switch Combinations
6
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
CIRCUIT
BREAKERS
Ammeter Mounting Kit
Maximum Voltage
1 Form C*
2 Form C
AC
DC
Catalog Number
Catalog Number
480
250
A01JLD64
242.00
A02JLD64
—
12
A01JLDLV*
306.00
(Gold Plated Contacts)
Alarm Switch Combinations
Maximum
Voltage
Note: Accessory modules can only be added to right
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
No accessories can be added if mechanical interlock
is used.
6/32
1 Alarm Switch
1 Alarm Switch and
1 Auxiliary Switch
AC
DC
Catalog
Number
Catalog
Number
480
250
B01JLD64 242.00
A01JLD64B
Plug-in Ammeter Display Units
Breaker Type
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
483.00
SJD, SLD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
▲ Built to order. Allow 7-9 weeks for delivery.
1 Alarm Switch and
2 Auxiliary Switches
Catalog
Number
483.00
A02JLD64B
Molded Case Circuit Breakers
SELECTION
LD 600A Frame Sentron Series
Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
2-Pole (3 Pole Width)
3-Pole
600V AC
250V DC 600V AC
500V DC
Catalog
Catalog
Number
Number
LXD62B450■4376.00
LXD63B4505456.00
LXD62B500■4376.00
LXD63B5005456.00
LXD62B6004376.00
LXD63B6005456.00
Type LD6-A Blue Label
Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled w/Lugs
Catalog
Number
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
2-Pole 600V AC, 250V DC (3 Pole Width)
LD62B250■4488.00
LD62B300■4488.00
LD62B350■4488.00
LD62B4004488.00
LD62B450■4488.00
LD62B500■4488.00
LD62B6004488.00
250
300
350
400
450
500
600
LD62F600
JD62T250■1662.00
JD62T300■1662.00
JD62T350■1662.00
JD62T400 1662.00
LD62T450■1662.00
LD62T500■1662.00
LD62T600 1662.00
LD63F600
JD63T250 1851.00
JD63T300 1851.00
JD63T350 1851.00
JD63T400 1851.00
LD63T450 1851.00
LD63T500 1851.00
LD63T600 1851.00
3-Pole 600V AC, 500V DC 250
300
350
400
450
500
600
LD63B2505624.00
LD63B3005624.00
LD63B3505624.00
LD63B4005624.00
LD63B4505624.00
LD63B5005624.00
LD63B6005624.00
Interrupting Ratings
Breaker
Type
RMS Symmetrical Amperes (KA)
CSA / UL 489 AIR (File E10848)
Volts AC (50/60Hz)
Volts DC
240
480
600
250
500 LXD6, LD6
HLD6, HLXD6
HHLD6, HHLXD6
CLD6
065
100
200
200
035
065
100
150
025
035
050
100
IEC 947-2
Volts AC (50/60Hz)
220/240 380/415
(lcu) (lcs) (lcu) (lcs)
25 (3-P) 065 033 040 20
35 (3-P) 100 050 065 33
—
200 100 100 50
50 (3-P) —
—
—
—
30 (2-P)
30 (2-P)
—
30 (2-P)
Shipping Weights
500
(lcu)
30
42
65
—
Instantaneous Adjustment Trip Range
Breaker Ampere
Rating
250-300
350-450
500-600
Nominal Instantaneous Values
Low
2
3
1250
1430
1610
2000
2290
2570
3000
3430
3800
4
1790
2860
4290
5
1960
3140
4710
6
2140
3430
5140
7
2320
3710
5570
Complete Breaker Unassembled
with Lugs
Prices of LD6, HLD6, and HHLD6
breakers include frame, trip, and
both line and load lugs (TA2J6500).
When ordered by these catalog
numbers, the customer will receive
the frame, trip and lugs separately
packaged. For applications requiring
different lugs, order individual items
as needed.
Complete Breaker Assembled
without Lugs
Prices of LXD6, HLXD6, HHLXD6,
and CLD6 include frame with noninterchangeable trip unit installed
only. Order required lugs separately.
For line and load lugs (TA2J6500)
installed, add suffix “L” to catalog
number (add 2 times list price of
lugs for each pole).
100% Rated
Types LXD2, LXD6 and HLXD6
breakers are available with 100%
ratings. To order add suffix “H”
to catalog number, and 10% to
list price. 100% rated LD breakers
require the use of 90°C Cu cable and
lugs TC1J6600 or TC2J6500.
50°C Applications see page 6-73.
400Hz Applications see page 6-73.
High
2500
4000
6000
(lcs)
15
21
33
—
Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
LXD6, LD6, HLD6, HHLD6
Assembled Breaker (less terminals)
2
1
17.5
3
1
19.5
LD6, HLD6, HHLD6 Frame Only
2
1
14
3
1
15.5
LD6, HHLD6 Trip Unit Only
2
1
03.5
3
1
04
CLD6 Complete Assembled Breaker
(less terminals)
2
3
1
1
29.5
31.5
Lugs For 75°C Wire ■ Built to order. Allow 3-4 weeks for delivery.
Type LXD6A circuit breakers are CSA Certified / UL Listed
for reverse
fed applications.
When wired as shown on page 6-3, this circuit breaker is
UL listed and rated for use on 500V DC ungrounded UPS
systems only.
See Note: A, page 6-70.
HACR rated.
Note: LD frame qualified to UL489 supplement SB “NAVAL”.
See page 6-73 for additional information.
Modifications page 6/73
Accessories pages 6/36 and 6/75 to 6/80
Cables
Catalog
per
Number
Lug
TA2J6500
1, 2
2
1
TC2J6500
2
TA1L6750
1
1
TC1J6600
1
Compression Lug
CCL600
1
Wire
Range
#3/0 500 kcmil Cu
#4/0 500 kcmil Al
250-500 kcmil Al
#3/0-500 kcmil Cu
500-750 kcmil Al
500-600 kcmil Cu
#3/0-600 kcmil Cu
500 kcmil Cu/Al
6/33
6
Continuous
Current Rating
@ 40°C
450
500
600
Ordering Information
CIRCUIT
BREAKERS
Type LXD6-A Molded Case Circuit Breakers
SELECTION
LD 600A Frame Sentron Series
Type HLD6-A, HLXD6 Black Label
Interchangeable Trip
Complete Breaker
Unassembled w/Lugs
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
Catalog
Number
D1
Continuous
Current Rating
@ 40°C
L
2-Pole 600V AC, 250V DC (3 Pole Width)
L
HLD62F600■
JD62T250■1662.0
JD62T300■1662.0
JD62T350■1662.0
JD62T400 1662.0
LD62T450■1662.0
LD62T500■1662.0
LD62T600
3-Pole 600V AC, 500V DC 250
300
350
400
450
500
600
HLD63B250 7465.00
HLD63B300 7465.00
HLD63B350 7465.00
HLD63B400 7465.00
HLD63B450 7465.00
HLD63B500 7465.00
HLD63B600 7465.00
HLD63F600
JD63T250
JD63T300
JD63T350
JD63T400
LD63T450
LD63T500
LD63T600
Black Label
2-Pole 600V AC (3 Pole Width)
HHLD62B250■7318.00
HHLD62B300■7318.00
HHLD62B350■7318.00
HHLD62B400■7318.00
HHLD62B450■7318.00
HHLD62B500■7318.00
HHLD62B600■7318.00
1851.0
1851.
1851.0
1851.0
0
0
1851.00
HHLD62F600■
JD62T250■ 1662.0
JD62T300■ 1662.0
JD62T350■ 1662.0
JD62T400 1662.0
HHLD62T450■1662.
HHLD62T500■1662
HHLD62T600■
W
D
Figure 2
Dimensions (in inches)
To
Handle
Figure 1
LXD6-A, LD6-A
HLD6-A
HHLD6, HHLXD6,
LXD6–ETI
Figure 2
CLD6,
CLD6-ETI
W
L
D
D1
7.5
11
4
5.44
7.5
17.86
4
5.44
Enclosures
3-Pole 600V AC
6
250
300
350
400
450
500
600
Figure 1
Breaker
Type
Type HHLD6, HHLXD6
250
300
350
400
450
500
600
W
D
HLD62B250■ 5868.00
HLD62B300■ 5868.00
HLD62B350■ 5868.00
HLD62B400■ 5868.00
HLD62B450■ 5868.00
HLD62B500■ 5868.00
HLD62B600■ 5868.00
250
300
350
400
450
500
600
HHLD63B2508864.00
HHLD63B3008864.00
HHLD63B3508864.00
HHLD63B4008864.00
HHLD63B450■8864.00
HHLD63B500■8864.00
HHLD63B600■8864.00
HHLD63F600
JD63T250 1851.0
JD63T300 1851.0
JD63T350 1851.0
JD63T400 1851.0
HHLD63T450■
HHLD63T500■
HHLD63T600■
Type CLD6 Type
Catalog
Number
1
3R
12
4X
7,9
LD6N1
LD6N3R
LD6N12
LD6SS4
ED6
402.00
1447.00
875.00
6211.00
10131.00
Neutral
W60993
308.00
Red Label
Fuseless Current Limiting
Non-Interchangeable Trip (Assembled Circuit Breaker)
CIRCUIT
BREAKERS
2-Pole
3-Pole
Continuous
Current Rating
@ 40°C
600V AC/250V DC
600V AC/500V DC
450
500
600
For 2-pole application
use outside poles of
3-pole circuit breaker
For inches / millimeters conversion,
see Application Data section
■ Built to order. Allow 3-4 weeks for delivery.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
6/34
Catalog
Number
For
CLD63B450■11666
CLD63B500 11666
CLD63B600
complete assembled 3 pole HLD6 or HHLD6 type
circuit breaker change the prefix identifier HLD6 or
HHLD6 to HLXD6 or HHLXD6. Price is sum of frame and
trip units prices, e.g. price of HLXD63B400 is the price
of HLD63F600 plus the price of LD63T600. Order the
terminal connectors separately.■
Type HLXD6, HHLXD6 Circuit Breakers are CSA Certified /
UL Listed for reverse feed applications.
LXD6-ETI, CLD6-ETI see page 6-55 for ordering information.
CE Applies to non-interchangable type HLXD only.
HACR rated.
Molded Case Circuit Breakers
SELECTION
SLD 600A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting
Type SLD6(A)
Blue Label
Black Label
3-Pole, 600V AC
SLD69300■
SLD69400■
SLD69500■
SLD69600■
SLD69300G■
SLD69400G■
SLD69500G■
SLD69600G■
SLD69300NT■
SLD69400NT■
SLD69500NT■
SLD69600NT■
SLD69300NGT■
SLD69400NGT■
SLD69500NGT■
SLD69600NGT■
Red Label
3-Pole, 600V AC
Max
Current
Rating
Catalog
Number
Type SCLD6
Type SHLD6(A)
3-Pole, 600V AC
Max
Current
Rating
Catalog
Number
300
400
500
600
5576.00
5576.00
5576.00
5576.00
300
400
500
600
7912.00
7912.00
7912.00
7912.00
300
400
500
600
7006.00
7006.00
7006.00
7006.00
300
400
500
600
9738.00
9738.00
9738.00
9738.00
SHLD69300■
SHLD69400■
SHLD69500■
SHLD69600■
SHLD69300G■
SHLD69400G■
SHLD69500G■
SHLD69600G■
SHLD69300NT■
SHLD69400NT■
SHLD69500NT■
SHLD69600NT■
SHLD69300NGT■
SHLD69400NGT■
SHLD69500NGT■
SHLD69600NGT■
Max
Current
Rating
Catalog
Number
300
400
500
600
6790.00
6790.00
6790.00
6790.00
300
400
500
600
9574.00
9574.00
9574.00
9574.00
300
400
500
600
8407.00
8407.00
8407.00
8343.00
300
400
500
600
11615.00
11615.00
11615.00
11615.00
SCLD69300■
SCLD69400■
SCLD69500■
SCLD69600■
SCLD69300G■
SCLD69400G■
SCLD69500G■
SCLD69600G■
SCLD69300NT■
SCLD69400NT■
SCLD69500NT■
SCLD69600NT■
SCLD69300NGT■
SCLD69400NGT■
SCLD69500NGT■
SCLD69600NGT■
300
400
500
600
12024.00
12024.00
12024.00
12024.00
300
400
500
600
15880.00
15880.00
15880.00
15880.00
300
400
500
600
14231.00
14231.00
14231.00
14231.00
300
400
500
600
18726.00
18726.00
18726.00
18726.00
SJD6, SLD6
H
Trip Unit Adjustable Functions
None
LI
Long
Time
Delay
Instantaneous
Setting
Short
Time
Pick Up
—
Short
Time
l2t
Pick Up
Ground
Fault
Pick Up
Ground
Fault
Delay
—
—
—
—
Short
Time
Delay
G
LIG
—
—
—
NT
LSI
—
—
NGT
LSIG
SJD6, SHJD6, SLD6, SHLD6
H
SCJD6, SCLD6
Dimensions (Inches)
Breaker
Type
W
H
D
D1
SJD6(A), SHJD6(A)
SLD6(A), SHLD6(A)
SLD6, SHLD6
7.5
11
4
5.44
SCJD6
SCLD6
7.5
17.86
4
5.44
Enclosures
(For LD frame, excluding SCLD6)
Note: “G” suffix in catalog number denotes circuit breaker
for 3 phase, 3 wire circuits.
For 3 phase, 4 wire, order correct 4th wire (neutral)
transformer as separate and additional item.
For ordering information and terminal connectors, neutral
transformers and enclosures, see page 6-31.
100% Rated – Not available in SLD6 Frame.
■ Built to order. Allow 3-4 weeks for delivery.
Type
Catalog
Number
1
3R
4–4X
7, 9
12
LD6N1
LD6N3R
LD6SS4
ED6
LD6N12
Neutral
W60993
6/35
6
Trip
Type
Cont
Current
Setting
CIRCUIT
BREAKERS
Suffix
Letter
Code
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
JD 400A Frame
LD 600A Frame
LMD 800A Frame
SJD 400A Frame
SLD 600A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip and
1 Auxiliary Switch
1 Shunt Trip
AC
DC
Catalog Number
Catalog Number
024
048
120
240
277
480
—
—
—
—
—
—
S17JLD6
S18JLD6▲
S01JLD6
S03JLD6
S15JLD6▲
S04JLD6
569.00
569.00
569.00
569.00
569.00
569.00
—
—
S01JLD62A
S03JLD62A
S15JLD64A▲
—
--802.00
802.00
802.00
-
—
—
—
—
—
012
024
048
125
250
S16JLD6▲
S07JLD6
S09JLD6▲
S11JLD6
S13JLD6▲
569.00
569.00
569.00
569.00
569.00
S16JLD62A▲
S07JLD62A
S09JLD62A
S11JLD62A▲
S13JLD62A▲
802.00
802.00
802.00
802.00
802.00
Undervoltage Trip Combinations
Control
Voltage
Sensitrip Ammeter
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip
Catalog Number
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
120
208
240
277
480
600
—
—
—
—
—
—
U01JLD6 569.00
U02JLD6▲569.00
U03JLD6 569.00
U16JLD6▲569.00
U06JLD6 569.00
U08JLD6▲569.00
Catalog Number
U01JLD62A802.00
U02JLD62A▲802.00
U03JLD62A▲802.00
U16JLD64A▲802.00
U06JLD64A▲802.00
—
--
Catalog Number
U01JLD62AA1035.00
U02JLD62AA▲1035.00
U03JLD62AA▲1035.00
U16JLD62AA▲1035.00
U06JLD64AA▲1035.00
—
--
—
—
—
—
024
048
125
250
U13JLD6 569.00
U14JLD6▲569.00
U10JLD6▲569.00
U12JLD6▲569.00
U13JLD62A802.00
U14JLD62A▲802.00
U10JLD62A▲802.00
U12JLD62A▲802.00
U13JLD62AA1035.00
U14JLD62AA▲1035.00
U10JLD62AA▲1035.00
U12JLD62AA▲1035.00
Auxiliary Switch Combinations
6
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
CIRCUIT
BREAKERS
Ammeter Mounting Kit
Maximum Voltage
1 Form C*
2 Form C
AC
DC
Catalog Number
Catalog Number
480
250
A01JLD64
A02JLD64
—
12
A01JLDLV*
(Gold Plated Contacts)
Alarm Switch Combinations
Maximum
Voltage
Note: Accessory modules can only be added to right
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
No accessories can be added if mechanical interlock
is used.
6/36
1 Alarm Switch
1 Alarm Switch and
1 Auxiliary Switch
1 Alarm Switch and
2 Auxiliary Switches
Catalog
Number
Catalog
Number
A01JLD64B
A02JLD64B
AC
DC
Catalog
Number
480
250
B01JLD64
242.00
Plug-in Ammeter Display Units
Breaker Type
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
483.00
SJD, SLD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
▲ Built to order. Allow 4-9 weeks for delivery.
1588.00
306.00
Molded Case Circuit Breakers
SELECTION
LMD 800A Frame Sentron Series
Type LMXD6 Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
2-Pole (3 Pole Width)
3-Pole
Catalog
Catalog
Number
Number
—
LMXD63B500■7
LMXD62B600■ 5582.00 LMXD63B600 7067
LMXD62B700■ 5582.00 LMXD63B700 7067
LMXD62B800 5582.00 LMXD63B800
Continuous
Current Rating
@ 40°C
500
600
700
800
Blue Label
Type LMD6 Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled w/Lugs
Catalog
Number
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
2-Pole 600V AC, 250V DC (3 Pole Width)
500
600
700
800
LMD62B500■5928.00
LMD62B600■5928.00
LMD62B700■5928.00
LMD62B800■5928.00
LMD62F800■2909.00
LMD62T500■2671.0
LMD62T600■2671.0
LMD62T700■2671.0
LMD62T800■
3-Pole 600V AC, 500V DC 500
600
700
800
LMD63B500■7589.00
LMD63B600■7589.00
LMD63B700■7589.00
LMD63B8007589.00
LMD63F8003716.00
LMD63T500■3351.0
LMD63T600■3351.0
LMD63T700■3351.0
LMD63T8003351.00
Nominal Instantaneous Values
Low
2
3
4
3000
3430
3860
4290
3200
3500
3700
4200
Complete Breaker Unassembled
with Lugs
Prices of LMD6 and HLMD6 breakers
include frame, trip, and both line and
load lugs (TA3K500). These catalog
numbers include the frame, trip
and lugs separately packaged. For
applications requiring different lugs,
order individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of LMXD6 and HLMXD6
include frame with noninterchangeable trip unit installed
only. Order required lugs separately.
For line and load lugs (TA3K500)
installed, add suffix “L” to catalog
number (add 2 times list price of
lugs for each pole).
50°C Applications see page 6-73.
400Hz Applications see page 6-73.
Shipping Weights
Instantaneous Adjustment Trip Range
Ampere Rating
500-600
700-800
Ordering Information
5
4710
4700
6
5140
6400
7
5570
7300
High
6000
8000
Number of
Poles
Number per
Carton
Shipping
Weight (lbs.)
LMD6, HLMD6, LMXD6, HLMXD6
Complete Breaker (less terminals)
2
3
1
1
53
61.5
LMD6, HLMD6 Frame Only
2
3
1
1
42.25
46
2
3
1
1
6
LMD6, HLMD6 Trip Unit Only
4.5
6.5
Catalog
Number
TA2K500
TA3K500
TA2N750
■ Built to order. Allow 3-4 weeks for delivery.
LMXD6 circuit breakers are CSA Certified / UL Listed for
reverse connected applications.
Use 6 lugs for 3-pole, use 4 connectors for 2-pole.
When
wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500UDC
ungrounded UPS systems only.
See Note: A, page 6-70.
HACR rated.
Cables
per
Lug
1, 2
1-3
1, 2
Wire
Range
#1-500 kcmil Cu/Al
#1/0-500 kcmil Cu/Al
500-750 kcmil Cu/Al
64.00
87.00
90.00
Modifications page 6/73
Enclosures Section 5
Accessories pages 6/39 and 6/75 to 6/80
6/37
CIRCUIT
BREAKERS
Lugs for 75°C Wire
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
LMD 800A Frame Sentron Series
Black Label
Type HLMXD6 Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs)
2-Pole
Continuous
Current Rating
@ 40°C
500
600
700
800
600V AC
250V DC
3-Pole
For 2-Pole application use
outside poles of 3-Pole
circuit breaker.
600V AC
500V DC
Catalog
Number
HLMXD63B500■ 8553.0
HLMXD63B600■ 8553.0
HLMXD63B700■ 85
HLMXD63B800
Black Label
Type HLMD6 Continuous
Current Rating
@ 40°C
D1
D
W
Interchangeable Trip
Complete Breaker
Unassembled
Frame Only
Catalog
Number
Catalog
Number
Trip Unit Only
Catalog
Number
L
2-Pole 600V AC, 250V DC (3 Pole Width)
500
600
700
2671.00
HLMD62B500■7066.00
HLMD62B600■7066.00
HLMD62B700■7066.00
HLMD62F800■
LMD62T500■2671.0
LMD62T600■2671.0
LMD62T700■
HLMD63F800
LMD63T500 ■ 3351.0
LMD63T600 ■ 3351.0
LMD63T700 ■ 335
LMD63T800 3351.00
3-Pole 600V AC, 500V DC 500
600
700
800
HLMD63B5009077.00
HLMD63B6009077.00
HLMD63B7009077.00
HLMD63B8009077.00
6
Breaker
Type
LMD6, LMXD6
HLMD6, HLMXD6
IEC 947-2
Volts AC (50/60HZ)
220/240 380/415
(lcu) (lcs) (lcu) (lcs)
065 033 040 20
100 050 065 33
500
(lcu) (lcs)
30 15
42 21
CIRCUIT
BREAKERS
For inches / millimeters conversion,
see Application Data section.
■ Built to order. Allow 3-4 weeks for delivery.
HLMXD6 circuit breakers are UL Listed for reverse
connection applications.
6/38
Breaker
Type
LMD6,
LMXD6,
HLMD6,
HLMXD6
LMXD6-ETI Interrupting Ratings
UL 489A IR
RMS Symmetrical Amperes (KA)
Volts AC
Volts DC
240
480
600
250
500 65
50
25
30 (2-P) 25 (3-P)
100
065
050
30 (2-P) 50 (3-P)
Dimensions (in inches)
LMXD6-ETI, see page 6-55 for catalog information.
When wired as shown on page 6-3, this circuit breaker is
UL listed and rated for use on 500VDC ungrounded UPS
systems only.
HACR rated.
W
L
D
D1
7.5
16
4.5
5.93
Enclosures
Type
Catalog
Number
1
3R
12
LMD1
LMD3R
LMD12■
802.00
1969.00
2578.00
Neutral
W63623
428.00
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
JD 400A Frame
LD 600A Frame
LMD 800A Frame
SJD 400A Frame
SLD 600A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip and
1 Auxiliary Switch
1 Shunt Trip
AC
DC
Catalog Number
024
048
120
240
277
480
—
—
—
—
—
—
S17JLD6
S18JLD6▲
S01JLD6
S03JLD6
S15JLD6▲
S04JLD6
569.00—
569.00—
569.00S01JLD62A
569.00S03JLD62A
569.00S15JLD64A▲
569.00—
Catalog Number
--802.00
802.00
802.00
--
—
—
—
—
—
012
024
048
125
250
S16JLD6▲
S07JLD6
S09JLD6▲
S11JLD6
S13JLD6▲
569.00S16JLD62A▲
569.00S07JLD62A
569.00S09JLD62A
569.00S11JLD62A▲
569.00S13JLD62A▲
802.00
802.00
Undervoltage Trip Combinations
Control
Voltage
Sensitrip Ammeter
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01JLD6
U02JLD6▲
U03JLD6
U16JLD6▲
U06JLD6
U08JLD6▲
U01JLD62A
U02JLD62A▲
U03JLD62A▲
U16JLD64A▲
U06JLD64A▲
—
802.00
802.00
802.00
802.00
802.00
--
U01JLD62AA1035.00
U02JLD62AA▲1035.00
U03JLD62AA▲1035.00
U16JLD62AA▲1035.00
U06JLD64AA▲1035.00
—
--
—
—
—
024
048
125
U13JLD6
569.00
U14JLD6▲ 569.00
U10JLD6▲ 569.00
U13JLD62A 802.00
U14JLD62A▲ 802.00
U10JLD62A▲ 802.00
U13JLD62AA1035.00
U14JLD62AA▲1035.00
U10JLD62AA▲1035.00
569.00
569.00
569.00
569.00
569.00
569.00
Auxiliary Switch Combinations
Ammeter Mounting Kit
1 Form C*
2 Form C
AC
DC
Catalog Number
Catalog Number
480
250
A01JLD64
A02JLD64483.00
—
12
A01JLDLV*
(Gold Plated Contacts)
Maximum
Voltage
AC
DC
480
250
Note: Accessory modules can only be added to right
side pole of solid state SJD and SLD frame circuit
breakers. All accessories on this page are useable
on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6,
HL6 and SLL circuit breakers.
1 Alarm Switch and
1 Auxiliary Switch
1 Alarm Switch and
2 Auxiliary Switches
Catalog
Number
Catalog
Number
Catalog
Number
B01JLD64 242.00
A01JLD64B 483.00
A02JLD64B
Plug-in Ammeter Display Units
Breaker Type
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
1 Alarm Switch
SJD, SLD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
6
Alarm Switch Combinations
1588.00
306.00
▲ Built to order. Allow 7-9 weeks for delivery.
No accessories can be added if mechanical interlock
is used.
6/39
CIRCUIT
BREAKERS
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
Maximum Voltage
Molded Case Circuit Breakers
SELECTION
MD 800A Frame Sentron Series
Type MXD6 Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole Continuous
Current Rating
@ 40°C
3-Pole
Catalog
Number
Catalog
Number
MXD62B500■5582.00
MXD62B600■5582.00
MXD62B700■5582.00
MXD62B800■5582.00
500
600
700
800
MXD63B500■ 7067.00
MXD63B600 7067.00
MXD63B700 7067.00
MXD63B800 7067.00
Type MD6 Blue Label
Interchangeable Trip
Continuous
Current Setting
@ 40°C
Complete Breaker
Unassembled with Lugs
Catalog
Number
Frame Only
Trip Unit Only
Catalog
Number
Catalog
Number
2-Pole 600V AC, 250V DC MD62B500■5928.00
MD62B600■5928.00
MD62B700■5928.00
MD62B800■5928.00
500
600
700
800
MD62F800■2909.00
MD62T500■2671.0
MD62T600■2671.0
MD62T700■ 26
MD62T800■
MD63F800 3716.00
MD63T5003351.00
MD63T6003351.00
MD63T7003351.00
MD63T8003351.00
3-Pole 600V AC, 500V DC 500
600
700
800
MD63B500 7589.00
MD63B600 7589.00
MD63B700 7589.00
MD63B800 7589.00
Lugs
Catalog
Number
Cables
Per Lug
Lugs
Per Kit
Wire
Range
TA2K500
TA3K500
TC2K500
TC3K350
1-2
1-3
1-2
1-3
1
1
1
1
#1-500 kcmil Cu/Al
1/0-500 kcmil Cu/Al
#1-500 kcmil Cu
#1-350 kcmil Cu
64.00
87.00
107.00
135.00
2TA2N8750
3TA2N8750
1-2
2
3
600-750 kcmil Cu/Al
327.00
459.00
2TA3N8750
3TA3N8750
1-3
2
3
500-750 kcmil Cu/Al
517.00
744.00
2TA4N8500
3TA4N8500
1-4
2
3
250-500 kcmil Cu/Al
526.00
762.00
2TA4P8500
3TA4P8500
1-4
2
3
250-500 kcmil Cu/Al
522.00
754.00
Ordering Information
Complete Breaker Unassembled
with Lugs
Pricing information for MD6 and
HMD6 breakers includes frame,
trip, and both line and load lugs
(TA3K500). When ordered by these
catalog numbers, the customer
will receive the frame, trip and
lugs separately packaged. For
applications requiring different lugs,
order individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of MXD6, HMXD6 and
CMD6 include frame with noninterchangeable trip units installed
only. Order required lugs separately.
For line and load lugs (TA3K500)
installed, add suffix “L” to catalog
number (add 2 times list price of
lugs for each pole).
100% Rated
Types MXD6, HMXD6 and CMD6
breakers are available with 100%
ratings. To order add suffix “H” to
catalog number, and 10% to list
price. 100% rated MD breakers
require the use of 90°C Cu cable and
lugs 2TA4P8500 or 2TA2N8750 for
2-pole; 3TA4P8500 or 3TA2N8750 for
3-pole.
50°C Applications see page 6-73.
400Hz Applications see page 6-73.
Kits
6
CIRCUIT
BREAKERS
Instantaneous Adjustment Trip Range
Ampere
Rating
500–600
700–800
Nominal Instantaneous Values
Low
2
3
4
3000
3430
3860
4280
4000
4570
5140
5710
Shipping Weights
Number of
Number per
Poles
Carton
MD6, HMD6, HMXD6, CMD6
Complete Breaker Assembled
(less lugs)
2
1
3
1
Shipping
Weight (lbs.)
53
61.5
MD6, HMD6 Frame Only
5
4710
6280
6
5140
6850
7
5570
7420
High
6000
8000
2
3
1
1
42.25
46
MD6, HMD6 Trip Unit Only
2
3
1
1
4.5
6.5
Enclosures
■ Built to order. Allow 3-4 weeks for delivery.
MXD6 circuit breakers are CSA Certified / UL Listed for
reverse connection applications.
2-pole units available in 3-pole width only.
Use 6 connectors for 3-pole, use 4 connectors for 2-pole.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems.
6/40
See
Note: A, page 6-70.
rated breakers with the CE mark will also be marked
in the 100% rated version.
HACR rated.
Note: MD frame qualified to UL489 supplement B “NAVAL”.
See page 6-73 for additional information.
80%
Type
Catalog
Number
List
Price $
1
3R
12
MND61
MND63
MND612■
802.00
1969.00
2578.00
Neutral
W63623
428.00
Modifications page 6/73
Enclosures Section 5
Accessories pages 6/43 and 6/75 to 6/80
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
MD 800A Frame Sentron Series
Black Label
Type HMXD6 Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 600V AC
250V DC
Continuous
Current Rating
@ 40°C
500
600
700
800
3-Pole 600V AC
500V DC
Catalog
Number
HMXD63B500■
HMXD63B600■
HMXD63B700■
HMXD63B800
For 2-pole application use outside
poles of 3-pole circuit breaker
8555.00
8555.00
8555.00
8555.00
Black Label
Type HMD6 Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
Catalog
Number
2-Pole 600V AC, 250V DC 500
600
700
800
HMD62B500■7066.00
HMD62B600■7066.00
HMD62B700■7066.00
HMD62B800■7066.00
HMD62F800■4047.00
MD62T500■2671.0
MD62T600■2671.0
MD62T700■2671.0
MD62T800■
3-Pole 600V AC, 500V DC 500
600
700
800
HMD63B5009077.00
HMD63B6009077.00
HMD63B7009077.00
HMD63B8009077.00
HMD63F8005204.00
Type CMD6 MD63T500 3351.0
MD63T600 3351.
MD63T700 3351.0
MD63T800 3351.00
Red Label
Fuseless Current Limiting
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
Lug
When wire lug shield NDTS is used.
Catalog
Number
500
600
700
800
For 2-pole application use
outside poles of 3-pole
circuit breaker
CMD63B500■
CMD63B600■
CMD63B700■
CMD63B800■
Note: NDTS lug shields are required when oversized lugs
are used. The kits include the NDTS shield.
12599.00
12599.00
12599.00
12599.00
Breaker
Type
MD6, MXD6
Dimensions (in inches)
W
L
D
(To
Handle)
D1
MD6, MXD6, HMD6,
HMXD6, CMD6,
MXD6-ETI, CMD6-ETI
9
16
6
8.25
with lug shields
9
24
6
8.25
Breaker
Type
Interrupting Ratings
UL 489 AIR—File E10848
RMS Symmetrical Amperes (KA)
Volts AC
Volts DC
IEC 947-2 AIR
Volts AC (50/60HZ)
220/240 380/415 500
240
065
480
050
600
25
250
30 (2-P)
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs
500 25 (3-P) 065 033 040 20 30 15
HMD6, HMXD6
100
CMD6
200
065
100
50
65
30 (2-P)
30 (2-P)
50 (3-P) 100 050 065 33
50 (3-P) 200 100 100 50
For inches / millimeters conversion,
see Application Data section.
42
65
21
33
2-pole
units available in 3-pole width only.
CMD6-ETI see page 6-56 for catalog information.
wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
HACR rated.
MXD6-ETI,
When
■ Built to order. Allow 3-4 weeks for delivery.
HMXD6 circuit breakers are CSA Certified / UL listed for
reverse connection applications.
6
3-Pole
600V AC/500V DC
6/41
CIRCUIT
BREAKERS
Continuous
Current Rating
@ 40°C
2-Pole
600V AC/250V DC
Molded Case Circuit Breakers
SELECTION
SMD 800A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting
Ordering Information
Pricing information for all Digital Sentron
Series MD and ND frames is for complete
breaker only. Price requires lugs or lug
kits as separate items. Lugs are suitable
for 75°C wire or as noted. Connector
wire ranges and cavities are established
in conjunction with Table 8.1 of UL 489
standards. Choose actual connector
for circuit breakers based on customer
requirements.
Recommended Terminal Connectors
Type SMD6
Type SHMD6
Type SCMD6
Blue Label
Black Label
Red Label
3-Pole, 600V AC
3-Pole, 600V AC
Catalog
Number
Max
Current
Rating
SMD69600A■
SMD69700A■
SMD69800A■
600
700
800
SMD69600AG■
SMD69700AG■
SMD69800AG■
SMD69600ANT■
SMD69700ANT■
SMD69800ANT■
3-Pole, 600V AC
Catalog
Number
Max
Current
Rating
7686.00
7686.00
7686.00
SHMD69600A■
SHMD69700A■
SHMD69800A■
600
700
800
600
700
800
9134.00
9134.00
9134.00
SHMD69600AG■
SHMD69700AG■
SHMD69800AG■
600
700
800
7955.00
7955.00
7955.00
SHMD69600ANT■
SHMD69700ANT■
SHMD69800ANT■
10575.00
10575.00
10217.00
SHMD69600ANGT■ 600
SHMD69700ANGT■ 700
SHMD69800ANGT■ 800
SMD69600ANGT■ 600
SMD69700ANGT■ 700
SMD69800ANGT■ 800
Catalog
Number
Max
Current
Rating
9370.00
9370.00
9370.00
SCMD69600A■
SCMD69700A■
SCMD69800A■
600
700
800
13914.00
13914.00
13914.00
600
700
800
10785.00
10785.00
10785.00
SCMD69600AG■
SCMD69700AG■
SCMD69800AG■
600
700
800
16582.00
16582.00
16582.00
600
700
800
9658.00
9658.00
9658.00
SCMD69600ANT■
SCMD69700ANT■
SCMD69800ANT■
600
700
800
15056.00
15056.00
15056.00
12418.00
12418.00
12418.00
SCMD69600ANGT■ 600
SCMD69700ANGT■ 700
SCMD69800ANGT■ 800
19201.00
19201.00
19201.00
SMD 800A Frame – 100% Rated
Type SMD6-H
6
Catalog
Number
SMD69600AH■
SMD69700AH■
SMD69800AH■
600
700
800
8452.00
8452.00
8452.00
SMD69600AGH■
SMD69700AGH■
SMD69800AGH■
600
700
800
10059.00
10059.00
10059.00
SMD69600ANTH■
SMD69700ANTH■
SMD69800ANTH■
600
700
800
SMD69600ANGTH■ 600
SMD69700ANGTH■ 700
SMD69800ANGTH■ 800
Catalog
Number
SHMD69600AH■
SHMD69700AH■
SHMD69800AH■
600
700
800
SHMD69600AGH■
SHMD69700AGH■
SHMD69800AGH■
All types
1
61.5
Lugs
for 75°C Wire Max
Current
Rating
10310.00
10310.00
10310.00
SCMD69600AH■
SCMD69700AH■
SCMD69800AH■
600
700
800
15304.00
15304.00
15304.00
600
700
800
11866.00
11866.00
11866.00
SCMD69600AGH■
SCMD69700AGH■
SCMD69800AGH■
600
700
800
18250.00
18250.00
18250.00
8818.00
8818.00
8818.00
SHMD69600ANTH■ 600
SHMD69700ANTH■ 700
SHMD69800ANTH■ 800
10641.00
10641.00
10641.00
SCMD69600ANTH■
SCMD69700ANTH■
SCMD69800ANTH■
600
700
800
16549.00
16549.00
16549.00
11647.00
11647.00
11647.00
SHMD69600ANGTH■ 600
SHMD69700ANGTH■ 700
SHMD69800ANGTH■ 800
13674.00
13674.00
13674.00
SCMD69600ANGTH■ 600
SCMD69700ANGTH■ 700
SCMD69800ANGTH■ 800
21139.00
21139.00
21139.00
CIRCUIT
BREAKERS
Trip
Type
Long
Time
Delay
Cables
Catalog
per
Wire
Number
Lug
Range
TA2K500
2
#1-500 kcmil Cu/Al
64.00
TA3K500
3
#1-500 kcmil Cu/Al
87.00
TC2K500
2
#1-500 kcmil Cu
107.00
TC3K350
3
#1-350 kcmil Cu
135.0
Kits (3 lugs/kit)
3TA4N8500
4
250–500 kcmil Cu/Al 72.00
3TA4P8500
4
250–500 kcmil Cu/Al754.00
3TA2N8750
2
600–750 kcmil Cu/Al 459.0
3TA3N8750
3
600–750 kcmil Cu/Al 744.00
Each kit contains the following:
3TA4P8500—3 connectors plus 1 NDTS end barrier
3TA3N8750—3 connectors plus 1 NDTS end barrier
3TA2N8750—3 connectors plus 1 NDTS end barrier
Neutral Transformers
Instantaneous
Setting
Short
Time
Pick Up
Short
Time
Delay
Ground
Fault
Pick Up
Ground
Fault
Delay
A
LI
—
—
—
—
AG
LIG
—
—
ANT
LSI
—
—
ANGT
LSIG
Interrupting Ratings
Breaker
Type
RMS Symmetrical kA UL 489 (File E10848)
240V AC
480V AC
600V AC
SMD6 – SND6
SHMD6 – SHND6
SCMD6 – SCND6
065
100
200
050
065
100
25
50
65
Note: “G” suffix in catalog number denotes circuit breaker
for 3 phase, 3 wire circuits.
For 3 phase, 4 wire, order correct 4th wire (neutral)
transformer as separate and additional item.
■ Built to order. Allow 3-4 weeks for delivery.
6/42
Types SMD6, SHMD6, SND6, SHND6 are
acceptable for reverse connection applications.
Type SCMD6-H
Catalog
Number
Cont
Current
Setting
TA2K500
TA3K500
TA3K500
3TA4N8500
Shipping
Weight (lbs)
Trip Unit Adjustable Functions
Suffix
Letter
Code
500–600
700–800
800
900–1200 (kit)
Number per
Carton
3-Pole, 600V AC
Max
Current
Rating
MD
MD
ND
ND
Breaker
Type
Red Label
3-Pole, 600V AC
Max
Current
Rating
Connector or
Connector Kit
Current Limiting
Black Label
3-Pole, 600V AC
Ampere
Rating
Shipping Weights
Type SHMD6-H
Blue Label
Breaker
Frame
Ampere
Rating
Catalog
Number
0600
0700
0800
1000
1200
N06SMDA
N07SMDA
N08SMDA
N10SNDA
N12SNDA
378.00
378.00
378.00
378.00
378.00
Enclosures
Type
Catalog
Number
1
3R
12
MND61
MND63
MND612
802.00
1969.00
2578.00
Neutral
W63623
428.00
Use
lugs TA2N8750 or TA4P8500 only on 100% rated
breakers.
For additional information, see Note: A, page 6-70.
Enclosures Section 5
Accessories pages 6/43 and 6/75 to 6/80
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
MD/SMD 800A Frame
ND/SND 1200A Frame
PD/SPD 1600A Frame
RD 2000A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip and
1 Auxiliary Switch
1 Shunt Trip
AC
DC
120
208
240
277
480
600
—
—
—
—
—
—
Catalog Number
S01MN6 569.00
S02MN6▲ 569.00
S03MN6 569.00
S15MN6▲ 569.00
S04MN6▲ 569.00
S06MN6▲ 569.00
Catalog Number
S01MN64A 802.00
S02MN64A▲802.00
S03MN64A▲802.00
S15MN64A▲802.00
S04MN64A▲802.00
—
-
—
—
—
—
—
012
024
048
125
250
S16MN6▲ 569.00
S07MN6 569.00
S09MN6▲ 569.00
S11MN6 569.00
S13MN6▲ 569.00
S16MN64A▲802.00
S07MN64A 802.00
—
S11MN64A▲802.00
S13MN64A▲802.00
Undervoltage Trip Combinations
Control
Voltage
Accessory modules can mount in either
left hand or right hand poles of all circuit
breakers, including solid state. Exception:
when mechanical interlock is used
accessories cannot be mounted in left pole.
Sensitrip Ammeter
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip
Catalog Number
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01MN6 569.00
U02MN6▲569.00
U03MN6▲569.00
U15MN6▲569.00
U04MN6▲569.00
U06MN6▲569.00
U01MN64A802.00
U02MN64A▲802.00
U03MN64A▲802.00
U15MN64A▲802.00
U04MN64A▲802.00
—
U01MN64AA 1035.00
U02MN64AA▲1035.00
U03MN64AA▲1035.00
U15MN64AA▲1035.00
U04MN64AA▲1035.00
—
—
—
—
—
024
048
125
250
U07MN6 569.00
U09MN6▲569.00
U11MN6▲569.00
U13MN6▲569.00
U07MN64A802.00
U09MN64A▲802.00
U11MN64A▲802.00
U13MN64A▲802.00
U07MN64AA 1035.00
U09MN64AA▲1035.00
U11MN64AA▲1035.00
U13MN64AA▲1035.00
Auxiliary Switch Combinations
Maximum Voltage
1 Form C*
AC
DC
Catalog Number
2 Form C
480
250
A01MN64
242.00
A02MN64
—
12
A01MNDLV▲*
306.00
(Gold Plated Contacts)
Catalog Number
483.00
Maximum
Voltage
AC
DC
Catalog Number
480
250
B00MN64
242.00
1 Alarm Switch and
1 Auxiliary Switch
1 Alarm Switch and
2 Auxiliary Switches
Catalog Number
Catalog Number
A01MN64B
483.00
A02MN64B
483.00
Plug-in Ammeter Display Units
Breaker Type
SMD, SND, SPD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
1588.00
306.00
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
▲ Built to order. Allow 7-9 weeks for delivery.
6/43
CIRCUIT
BREAKERS
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
1 Alarm Switch
6
Alarm Switch Combinations
Molded Case Circuit Breakers
SELECTION
ND 1200A Frame Sentron Series
Type NXD6 Blue Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 600V AC
250V DC
Continuous
Current Rating
@ 40°C
3-Pole 600V AC
500V DC
Catalog
Number
Catalog
Number
NXD62B900■9388.00
NXD62B100■9388.00
NXD62B120■9388.00
0900
1000
1200
NXD63B900 11775.00
NXD63B100 11775.00
NXD63B120 11775.00
Blue Label
Type ND6
Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
Catalog
Number
2-Pole 600V AC, 250V DC ND62B800■8574.00
ND62B900■10441.00
ND62B100■10441.00
ND62B12010441.00
0800
0900
1000
1200
ND62F1204851.00
MD62T800■2671.00
ND62T900■4538.00
ND62T100■4538.00
ND62T120 4538.00
ND63F1206086.00
MD63T8003351.00
ND63T9005689.00
ND63T1005689.00
ND63T1205689.00
3-Pole 600V AC, 500V DC 0800
0900
1000
1200
ND63B80010961.00
ND63B90013299.00
ND63B10013299.00
ND63B12013299.00
Interrupting Ratings
Breaker
Type
6
ND6, NXD6
HND6, HNXD6
CND6
RMS Symmetrical Amperes (KA)
CSA / UL 489 A IR
Volts AC
Volts DC
240
480
600
250
500 65
100
200
50
65
100
25
50
65
30 (2-P)
30 (2-P)
30 (2-P)
25 (3-P)
50 (3-P)
50 (3-P)
IEC 947-2
Volts AC (50/60HZ)
220/240
380/415
(lcu) (lcs) (lcu) (lcs)
65
33
40 20
100
50
65 33
200 100 100 50
500
(lcu)
30
42
65
CIRCUIT
BREAKERS
Nominal Instantaneous Values
Low
2
3
4
4000
4570
5140
5710
5000
5715
6430
7145
5
6280
7860
6
6850
8575
7
7420
9290
Complete Breaker Unassembled
with Lugs
Prices of ND6 and HND6 breakers
include frame, trip, and both line
and load lugs (3TA4N8500). These
catalog numbers are the frame, trip
and lugs separately packaged. For
applications requiring different lugs,
order individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of NXD6, HNXD6, and
CND6 include frame with noninterchangeable trip units installed
only. Order required terminal
connectors separately.
For line and load lugs (3TA4N8500)
installed, add suffix “L” to catalog
number (add 2 times list price of
lug kit).
100% Rated
Types NXD6, HNXD6 and CND6
breakers are available with 100%
ratings. To order, suffix “H” to catalog
number, and add 10% to list price.
100% rated ND breakers require
90°C Cu cable and lug kit 3TA4P8500.
50°C Applications see page 6-73.
400Hz Applications see page 6-73.
Lugs
(lcs)
15
21
33
Instantaneous Adjustment Trip Range
Breaker Ampere
Rating
800
900-1200
Ordering Information
High
08000
10000
Catalog
Cables Wire
Number
per Lug Range
TA2K500
2
#1-500 kcmil Cu/Al
TA3K500
3
#1-500 kcmil Cu/Al
TC2K500
2
#1-500 kcmil Cu
TC3K350
3
#1-350 kcmil Cu
Kits (2 Kits required per breaker)
2TA4P8500 250-500 kcmil Cu/Al
3TA4P8500 4
2TA4N8500 4
250-500 kcmil Cu/Al
3TA4N8500 2TA2N8750 2
600-750 kcmil Cu/Al
3TA2N8750
2TA3N8750 3
500-750 kcmil Cu/Al
3TA3N8750
64.00
87.00
107.00
135.
762.00
744.00
Enclosures
Type
1
3R
12
Neutral
■ Built to order. Allow 3-4 weeks for delivery.
NXD6 circuit breakers are UL listed for reverse
connection applications.
2-pole units available in 3-pole width only.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500VDC
ungrounded UPS systems only.
Use 6 connectors for 3-pole, use 4 connectors for 2-pole.
Use 2 – 3TA4P8500 kits for 3-pole, or 2 – 2TA4P8500
kits for 2-pole. Rated for 90°C cable. Use for 100%
6/44
rated breakers.
2 – 3TA4N8500 for 3-pole or 2 – 2TA4N8500 for
2-pole. Rated for 75°C cable.
See Note: A, page 6-70.
80% rated breakers with the CE mark will also be marked
in the 100% rated version.
HACR rated.
Catalog
Number
MND61
MND63
MND612 ■
W63623
802.00
1969.00
2578.00
428.00
Use
Note: ND frame qualified to UL489 supplement B “NAVAL”.
See page 6-73 for additional information.
Modifications page 6/73
Enclosures Section 5
Accessories pages 6/47 and 6/75 to 6/80
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
ND 1200A Frame Sentron Series
Type HNXD6 Black Label
Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs)
2-Pole 600V AC
250V DC
Continuous
Current Rating
@ 40°C
3-Pole 600V AC
500V DC
Catalog
Number
0900
1000
1200
For 2-pole application use outside
poles of 3-pole circuit breaker
HNXD63B900
HNXD63B100
HNXD63B120
13229.00
13229.00
13229.00
Black Label
Type HND6 Interchangeable Trip
Continuous
Current Rating
@ 40°C
Complete Breaker
Unassembled with Lugs
Frame Only
Catalog
Number
Trip Unit Only
Catalog
Number
Catalog
Number
2-Pole 600V AC, 250V DC 0800
0900
1000
1200
For 2-pole application use outside poles of 3-pole circuit breaker
3-Pole 600V AC, 500V DC 0800
0900
1000
1200
HND63B80012414.00
HND63B90014752.00
HND63B10014752.00
HND63B12014752.00
MD63T8003351.00
ND63T900 5689.00
ND63T100 5689.00
ND63T120 5689.00
HND63F1207539.00
Type CND6 Red Label
Fuseless Current Limiting
Non-Interchangeable Trip (Assembled Circuit Breaker)
2-Pole
0900
1000
1200
For 2-pole application,
use outside poles of
3-pole circuit breaker
CND63B900■
18322.0
CND63B100
18322.0
CND63B12018322.00
Shipping Weights
■ Built to order. Allow 3-4 weeks for delivery.
HNXD6 circuit breakers are CSA Certified / UL Listed for
reverse connection applications.
When lugs shield NDTS is used.
Note: NDTS lug shields are required when oversized lugs
(kits on page 88) are used. The kits include
the NDTS shield.
Breaker
Type
W
L
D
D1
ND6, NXD6, HND6,
HNXD6, CND6
9
16
6
8.25
with NDTS
lug shield
9
29
6
8.25
2-pole
units available in 3-pole width only.
wired as shown on page 6-3, this circuit breaker is
UL listed and rated for use on 500V DC ungrounded UPS
systems only.
HACR rated.
When
6/45
CIRCUIT
BREAKERS
Dimensions (in inches)
Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
ND6, HND6, NXD6, HNXD6, CND6
Assembled Breaker (less terminals)
2
1
53
3
1
61.5
ND6, HND6 Frame Only
2
1
42.25
3
1
46
ND6, HND6 Trip Unit Only
2
1
04.5
3
1
06.5
For inches / millimeters conversion,
see Application Data section.
Lugs
3-Pole
Catalog
Number
6
Continuous
Current Rating
@ 40°C
Molded Case Circuit Breakers
SELECTION
SND 1200A Frame Digital Solid State Sentron Sensitrip III Series
Current Limiting
Type SND6
Type SHND6
Type SCND6
Black Label
Red Label
Blue Label
3-Pole, 600V AC
3-Pole, 600V AC
3-Pole, 600V AC
Catalog
Number
Max
Current
Rating
13548.00
13548.00
13548.00
SHND69800A■
SHND69100A■
SHND69120A■
800
1000
1200
800
1000
1200
14963.00
14963.00
14963.00
SHND69800AG■
SHND69100AG■
SHND69120AG■
800
1000
1200
14104.00
14104.00
14104.00
SHND69800ANT■
SHND69100ANT■
SHND69120ANT■
16757.00
Catalog
Number
Max
Current
Rating
SHND69800A■
SHND69100A■
SHND69120A■
800
1000
1200
SHND69800AG■
SHND69100AG■
SHND69120AG■
SHND69800ANT■
SHND69100ANT■
SHND69120ANT■
SHND69800ANGT■ 800
SHND69100ANGT■ 1000
SHND69120ANGT■ 1200
16757.00
16757.00
Catalog
Number
Max
Current
Rating
13548.00
13548.00
13548.00
SCND69800A■
SCND69100A■
SCND69120A■
800
1000
1200
18650.00
18650.00
18650.00
800
1000
1200
14963.00
14963.00
14963.00
SCND69800AG■
SCND69100AG■
SCND69120AG■
800
1000
1200
20540.00
20540.00
20540.00
800
1000
1200
14104.00
14104.00
14104.00
SCND69800ANT■ 800
SCND69100ANT■ 1000
SCND69120ANT■ 1200
19406.00
19406.00
19406.00
SHND69800ANGT■ 800
SHND69100ANGT■ 1000
SHND69120ANGT■ 1200
16757.00
16757.00
16757.00
SCND69800ANGT■ 800
SCND69100ANGT■ 1000
SCND69120ANGT■ 1200
23038.00
23038.00
23038.00
SND 1200A Frame – 100% Rated
Current Limiting
Type SND6-H
Blue Label
Black Label
3-Pole, 600V AC
6
Type SCND6-H
Type SHND6H
Red Label
3-Pole, 600V AC
3-Pole, 600V AC
Catalog
Number
Max
Current
Rating
13374.00
13374.00
13374.00
SHND69800AH■
SHND69100AH■
SHND69120AH■
800
1000
1200
800
1000
1200
14993.00
14993.00
14993.00
SHND69800AGH■
SHND69100AGH■
SHND69120AGH■
800
1000
1200
13976.00
13976.00
13976.00
SHND69800ANTH■
SHND69100ANTH■
SHND69120ANTH■
SND69800ANGTH■ 800
SND69100ANGTH■ 1000
SND69120ANGTH■ 1200
16835.00
16835.00
16835.00
Catalog
Number
Max
Current
Rating
SND69800AH■
SND69100AH■
SND69120AH■
800
1000
1200
SND69800AGH■
SND69100AGH■
SND69120AGH■
SND69800ANTH■
SND69100ANTH■
SND69120ANTH■
H
Catalog
Number
Max
Current
Rating
14896.00
14896.00
14896.00
SCND69800AH■
SCND69100AH■
SCND69120AH■
800
1000
1200
20512.00
21538.00
21538.00
800
1000
1200
16470.00
16470.00
16470.00
SCND69800AGH■
SCND69100AGH■
SCND69120AGH■
800
1000
1200
22613.00
23744.00
23744.00
800
1000
1200
15501.00
15501.00
15501.00
SCND69800ANTH■
SCND69100ANTH■
SCND69120ANTH■
800
1000
1200
21343.00
22410.00
22410.00
SHND69800ANGTH■ 800
SHND69100ANGTH■ 1000
SHND69120ANGTH■ 1200
18439.00
18439.00
18439.00
SCND69800ANGTH■ 800
SCND69100ANGTH■ 1000
SCND69120ANGTH■ 1200
25337.00
26604.00
26604.00
SMD6, SHMD6, SCMD6, SND6, SHND6,
SCND6
H
CIRCUIT
BREAKERS
Trip Unit Adjustable Functions
Suffix
Letter
Code
Trip
Type
Cont
Current
Setting
Long
Time
Delay
Instantaneous
Setting
Short
Time
Pick Up
Short
Time
Delay
Short
Time
l 2t
Pick Up
Ground
Fault
Pick Up
Ground
Fault
Delay
—
A
LI
—
—
—
—
AG
LIG
—
—
—
ANT
LSI
—
—
ANGT
LSIG
When wire connector shield NDTS is used.
Dimensions (in Inches)
Breaker
Type
For inches / millimeters conversion,
see Application Data section.
For ordering information and terminal connectors, neutral
transformers and enclosures, see page 6-42.
6/46
Note: “G” suffix in catalog number denotes circuit breaker
for 3 phase, 3 wire circuits.
For 3 phase, 4 wire, order correct 4th wire (neutral)
transformer as separate and additional item.
W
H
D
D1
SMD6, SHMD6, SCMD6
SND6, SHND6, SCND6
9
16
6
8.25
With NDTS shields
9
24
6
8.25
■ Built to order. Allow 3-4 weeks for delivery.
Use 2-3TA4P8500 for 3-pole. These kits are rated for
90°C wire. 90°C Cu only cable must be used, and sized
per 75°C conductors.
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
Internal Accessories
Accessories for:
MD/SMD 800A Frame
ND/SND 1200A Frame
PD/SPD 1600A Frame
RD 2000A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip and
1 Auxiliary Switch
1 Shunt Trip
AC
DC
120
208
240
277
480
600
—
—
—
—
—
—
Catalog Number
S01MN6 569.00
S02MN6▲ 569.00
S03MN6 569.00
S15MN6▲ 569.00
S04MN6▲ 569.00
S06MN6▲ 569.00
Catalog Number
S01MN64A 802.00
S02MN64A▲802.00
S03MN64A▲802.00
S15MN64A▲802.00
S04MN64A▲802.00
—-
—
—
—
—
—
012
024
048
125
250
S16MN6▲ 569.00
S07MN6 569.00
S09MN6▲ 569.00
S11MN6 569.00
S13MN6▲ 569.00
S16MN64A▲802.00
S07MN64A 802.00
—
S11MN64A▲802.00
S13MN64A▲802.00
Undervoltage Trip Combinations
Control
Voltage
Accessory modules can mount in either
left hand or right hand poles of all circuit
breakers, including solid state. Exception:
when mechanical interlock is used
accessories cannot be mounted in left pole.
Sensitrip Ammeter
1 Undervoltage Trip and
1 Undervoltage Trip and
1 Auxiliary Switch
A
2uxailiS
rywtcihes
1 Undervoltage Trip
AC
DC
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01MN6
U02MN6▲
U03MN6▲
U15MN6▲
U04MN6▲
U06MN6▲
569.00
569.00
569.00
569.00
569.00
569.00
Catalog Number
U01MN64A802.00
U02MN64A▲802.00
U03MN64A▲802.00
U15MN64A▲802.00
U04MN64A▲802.00
—
--
U01MN64AA
U02MN64AA▲
U03MN64AA▲
U15MN64AA▲
U04MN64AA▲
—
Catalog Number
1035
1035
1035
1035
1035
--
—
—
—
—
024
048
125
250
U07MN6
U09MN6▲
U11MN6▲
U13MN6▲
569.00
569.00
569.00
569.00
U07MN64A802.00
U09MN64A▲802.00
U11MN64A▲802.00
U13MN64A▲802.00
U07MN64AA
U09MN64AA▲
U11MN64AA▲
U13MN64AA▲
1035
10
1035
Auxiliary Switch Combinations
Maximum Voltage
1 Form C*
AC
DC
Catalog Number
2 Form C
480
250
A01MN64
242.00
A02MN64
—
12
A01MNDLV▲*
306.00
(Gold Plated Contacts)
Catalog Number
483.00
Maximum
Voltage
AC
DC
Catalog Number
480
250
B00MN64
242.00
1 Alarm Switch and
1 Auxiliary Switch
1 Alarm Switch and
2 Auxiliary Switches
Catalog Number
Catalog Number
A01MN64B
483.00
A02MN64B
483.00
Plug-in Ammeter Display Units
Breaker Type
SMD, SND, SPD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
1588.00
306.00
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
▲ Built to order. Allow 7-9 weeks for delivery.
6/47
CIRCUIT
BREAKERS
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
1 Alarm Switch
6
Alarm Switch Combinations
Molded Case Circuit Breakers
SELECTION
PD 1600A Frame Sentron Series
Type PXD6 Non-Interchangeable Trip Continuous
Current Rating
40˚C
1200
1400
1600
Complete Breaker Assembled
(Frame/Trip Unit Only)
Mounting
Assembly
Catalog Number
PXD63B120■ 15086.00
PXD63B140■ 15086.00
PXD63B160
15086.00
Lugs (6 required)
Catalog Number
MB9301
-orMBR9302
Catalog Number
TA5P600
Type PD6 Interchangeable Trip Blue Label
3-Pole 600V AC, 250-500V DC Continuous
Current
40°C
Complete Breaker
Unassembled
Catalog
Number
Frame Only
Mounting
Assembly
Trip Unit Only
Catalog
Number
Catalog
Number
PD63B120■
17900.00
PD63B14017900.00 PD63F160 7754.00
PD63B16017900.00
1200
1400
1600
Catalog Rating
Number
PD63T120■0
MB9301
-orPD63T140 7332.00
PD63T160 7332.00 MBR9302
TA5P600 86.00
Blue Label
3-Pole 600V AC, 250-500V DC Complete BreakerAssembled (Frame/Trip Unit Only)
Catalog Number
HPXD63B120■
17017.00
HPXD63B140■
7017.00
HPXD63B160
17017.00
1200
1400
1600
Type HPD6 Interchangeable Trip Black Label
3-Pole 600V AC, 250-500V DC Continuous
Current
40°C
1200
HPD63B140
1600
Catalog
Number
Frame Only
Trip Unit Only
Catalog
Number
HPD63B120■ 19829.00
19829.00 HPD63F160 PD63T140
HPD63B160 19829.00
Catalog
Number
Catalog Rating
Number
1400
Complete Breaker Unassembled
with Lugs
Prices of PD6, HPD6, RD6, and
HRD6 type breakers include frame,
trip, mounting base (MB9301), and
both line and load lugs (PD Frame
– TA5P600, RD Frame – TC5R600). When
ordered by these catalog numbers,
the customer will receive the frame,
trip, mounting assembly and lugs
separately packaged. For applications
requiring different mounting base or
lugs, order individual items as needed.
Complete Breaker Assembled
without Lugs
Prices of PXD6, HPXD6, RXD6, HRXD6
and CPD6 type breakers include frame
with non-interchangeable trip unit
installed only. Order required mounting
base and lugs separately.
100% Rated
Types PXD6, HPXD6 breakers are
available with 100% ratings. To order
add suffix “H” to catalog number, and
10% to list price. RD 2000A Frames not
available with 100% ratings.
50°C Applications see page 6-73.
400HZ Applications see page 6-73.
Lugs
Catalog
Number
TA5P600
TC5R600
TC4P750▲
TA6R600
Fuseless Current Limiting
3-Pole 600V AC, 250-500V DC Red Label
No of Cables
per
Connector
1-5 Pcs.
1-5 Pcs.
1-4 Pcs.
1-6 Pcs.
Wire Range
300-600 kcmil Cu/Al
300-600 kcmil Cu only
500-750 kcmil Cu/Al
300-600 kcmil Cu/Al
286.00
381.00
260.00
302.00
Complete BreakerAssembled (Frame/Trip Unit Only)
Catalog Number
CPD63B120■
19056.00
CPD63B140■
19056.00
CPD63B160■
19056.00
Mounting Bases for PD & RD
6.19
6.00
2.00
2.00
MB9301
■ Built to order. Allow 3-4 weeks for delivery.
▲ Built to order. Allow 7-9 weeks for delivery.
Use two outside poles of a 3-pole circuit breaker for
250V
6/48
MB9301
16.00
MB9301
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
PXD6, HPXD6 type circuit breakers are UL Listed for
reverse feed applications.
18.73
16.00
CIRCUIT
BREAKERS
1200
1400
1600
Lugs (6 required)
Catalog
Number
PD63T120■ 7332.00 MB9301
-orTA5P600 286.00
PD63T160 7332.00 MBR9302
Type CPD6 Non-Interchangeable Trip
Continuous Current
Rating 40°C
Mounting
Assembly
25.50
6
Complete Breaker
Unassembled
Lugs (6 required)
Catalog
Number
Type HPXD6 Non-Interchangeable Trip Continuous Current
Rating 40°C
Ordering Instructions
Blue Label
3-Pole 600V AC, 250-500V DC MBR9302
For
MBR9302
additional information See Note: A, page 6-70.
HACR rated.
Note: PD frame qualified to UL489 supplement B “NAVAL”.
See page 6-73 for additional information.
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
SPD 1600A Frame Digital Solid State Sentron Sensitrip III Series
Ordering Information
Pricing information for all Digital Sentron Series PD frame unit is for breaker
only. Price required mounting block assembly and necessary terminal connectors
as separate items.
SPD6 and SHPD6 are acceptable for reverse connection applications.
Type SPD6
Type SHPD6
Blue Label
Black Label
3-Pole, 600V AC
3-Pole, 600V AC
SPD69140■
SPD69160■
1400
1600
SPD69140G■
SPD69160G■
Catalog
Number
Max
Current
Rating
18390.00
18390.00
SHPD69140■
SHPD69160■
1400
1600
18968.00
18968.00
1400
1600
19977.00
19977.00
SHPD69140G■
SHPD69160G■
1400
1600
20752.00
20752.00
SPD69140NT■
SPD69160NT■
1400
1600
18693.00
18693.00
SHPD69140NT■
SHPD69160NT■
1400
1600
19649.00
19649.00
SPD69140NGT■
SPD69160NGT■
1400
1600
22156.00
22156.00
SHPD69140NGT■
SHPD69160NGT■
1400
1600
22991.00
22991.00
Suffix
Letter
Code
Trip
Type
None
LI
Cont
Current
Setting
Long
Time
Delay
Instantaneous
Setting
Short
Time
Pick Up
—
Short
Time
Delay
—
Lugs
No. of
Catalog Cables per Wire
Number Connector Range
TA5P600 1–5 pcs.
TC5R600 1–5 pcs.
TA6R600 1–5 pcs.
300–600 kcmil Cu/Al
286.00
300–600 kcmil Cu Only 381.00
300–600 kcmil Cu/Al
302.00
Neutral Transformers
Short
Time
l 2t
Pick Up
Ground
Fault
Pick Up
—
—
Ground
Fault
Delay
—
G
LIG
—
—
—
NT
LSI
—
—
NGT
LSIG
Interrupting Ratings
Ampere
Rating
Catalog
Number
1400
1600
N14SPD
N16SPD
378.00
378.00
Enclosure
Type
Catalog
Number
1
PRD6N1
5655.00
Mounting Block (Required)
RMS Symmetrical kA CSA / UL 489
Breaker
Type
240V AC
480V AC
600V AC
Catalog
Number
SPD6
SHPD6
065
100
050
065
025
050
MB9301
MBR9302
1098.00
1098.00
6
Catalog
Number
Max
Current
Rating
All PD, RD Frames:
6.19
6.00
CIRCUIT
BREAKERS
2.00
MB9301 (shown)
MBR9302
For inches / millimeters conversion,
see Application Data section.
■ Built to order. Allow 3-4 weeks for delivery.
MBR9301
For
MB9301
additional information, see Note: A, page 6-70.
Note: The PD frame circuit breaker requires the use of a
connect-all mounting assembly to allow for placing
into service.
Note: “G” suffix in catalog number denotes circuit breaker
18.73
16.00
25.50
16.00
2.00
MBR9302
MBR9302
for 3 phase, 3 wire circuits.
For 3 phase, 4 wire, order correct 4th wire (neutral)
transformer as separate and additional item.
6/49
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
Internal Accessories
Accessories for:
MD/SMD 800A Frame
ND/SND 1200A Frame
PD/SPD 1600A Frame
RD 2000A Frame
Shunt Trip Combinations
1 Shunt Trip and
1 Auxiliary Switch
Control Voltage
1 Shunt Trip
AC
DC
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
S01MN6
S02MN6▲
S03MN6
S15MN6▲
S04MN6▲
S06MN6▲
569.00
569.00
569.00
569.00
569.00
569.00
S01MN64A
S02MN64A▲
S03MN64A▲
S15MN64A▲
S04MN64A▲
—
802.00
802.00
802.00
802.00
802.00
—--
—
—
—
—
—
012
024
048
125
250
S16MN6▲
S07MN6
S09MN6▲
S11MN6
S13MN6▲
569.00
569.00
569.00
569.00
569.00
S16MN64A▲
S07MN64A
—
S11MN64A▲
S13MN64A▲
802.00
802.00
—802.00
802.00
Catalog Number
Undervoltage Trip Combinations
Control
Voltage
Accessory modules can mount in either
left hand or right hand poles of all circuit
breakers, including solid state. Exception:
when mechanical interlock is used
accessories cannot be mounted in left pole.
Sensitrip Ammeter
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip
Catalog Number
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
U01MN6 569.00
U02MN6▲569.00
U03MN6▲569.00
U15MN6▲569.00
U04MN6▲569.00
U06MN6▲569
U01MN64A802.00
U02MN64A▲802.00
U03MN64A▲802.00
U15MN64A▲802.00
U04MN64A▲802.00
.00 —
--
U01MN64AA1035.00
U02MN64AA▲1035.00
U03MN64AA▲1035.00
U15MN64AA▲1035.00
U04MN64AA▲1035.00
—
--
—
—
—
—
024
048
125
250
U07MN6 569.00
U09MN6▲569.00
U11MN6▲569.00
U13MN6▲569.00
U07MN64A802.00
U09MN64A▲802.00
U11MN64A▲802.00
U13MN64A▲802.00
U07MN64AA1035.00
U09MN64AA▲1035.00
U11MN64AA▲1035.00
U13MN64AA▲1035.00
Auxiliary Switch Combinations
Maximum Voltage
1 Form C*
AC
DC
Catalog Number
2 Form C
480
250
A01MN64
242.00 A02MN64
—
12
A01MNDLV▲*
306.00 (Gold Plated Contacts)
Catalog Number
483.00
Alarm Switch Combinations
6
Maximum
Voltage
CIRCUIT
BREAKERS
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
▲ Built to order. Allow 7-9 weeks for delivery.
6/50
1 Alarm Switch
AC
DC
Catalog Number
480
250
B00MN64
1 Alarm Switch and
1 Auxiliary Switch
242.00
1 Alarm Switch and
2 Auxiliary Switches
Catalog Number
Catalog Number
A01MN64B
A02MN64B
Plug-in Ammeter Display Units
Breaker Type
SMD, SND, SPD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
1588.00
306.00
Molded Case Circuit Breakers
SELECTION
RD 2000A Frame Sentron Series
Blue Label
Type RXD6 Non-Interchangeable Trip (Assembled Circuit Breaker Only Without Lugs)
3-Pole 600V AC, 250-500V DC Continuous
Current
Rating 40°C
Complete Breaker
Assembled
(Frame/Trip Unit Only)
Mounting
Assembly
Lugs (6 required)
Catalog
Number
Catalog
Number
Catalog
Number
1600
1800
2000
RXD63B160
RXD63B180
RXD63B200
16723.00
16723.00
16723.00
MB9301
-orMBR9302
1098.00
TC5R600
381.00
1098.00
Blue Label
Type RD6
Interchangeable Trip (Unassembled Circuit Breaker with Lugs)
3-Pole 600V AC, 250-500V DC Frame Only
Catalog
Number
Catalog
Number
Mounting Block
Mounting
Assembly
Trip Unit Only
Catalog
Number
Lugs (6 required)
Catalog
Number
Catalog
Number
RD63B160■ 20108.00
RD63T160■ 7983.00 MB9301 1098.00
RD63B180 20108.00 RD63F200 8741.00 RD63T180 7983.00
-orRD63B200 20108.00
RD63T200 7983.00 MBR9302 1098.00
1600
1800
2000
Black Label
Type HRXD6 Complete Breaker Assembled
(Frame/Trip Unit Only)
Continuous
Current Rating
40°C
Catalog Number
1600
1800
2000
HRXD63B160■
HRXD63B180■
HRXD63B200
18802.00
18802.00
18802.00
Black Label
Type HRD6
Continuous
Current
Rating 40°C
Complete Breaker
Unassembled
with Lugs
1600
1800
2000
TC5R600 381.00
Frame Only
Catalog
Number
Mounting
Assembly
Trip Unit Only
Catalog
Number
Catalog
Number
Lugs (6 required)
Catalog
Number
Catalog
Number
Connection
Points
MB9301
MBR9302
Front
Rear
Shipping Weights
Number of
Number per
Shipping
Poles
Carton
Weight (lbs.)
PXD6, HPXD6, RXD6, HRXD6, CPD6
Assembled Breakers
3
1
61.5
PD6, HPD6, RD6, HRD6
Frame Only
3
1
55.0
PD6, RD6
Trip Unit Only
3
1
06.5
Mounting Assembly
MB9301
1
53.0
MBR9302
1
50.9
6
Continuous
Current
Rating 40°C
Complete Breaker
Unassembled
with Lugs
Catalog
Number
HRD63B160■ 22186.00
RD63T160■ 7983.00 MB9301 1098.00
HRD63B180 22186.00 HRD63F200 10819.00 RD63T180 7983.00
-orTC5R600
HRD63B200 22186.00
RD63T200 7983.00 MBR9302 1098.00
CSA / UL 489 A IR
IEC 947-2
RMS Symmetrical KA
Breaker
Type
PD6, PXD6,
RD6, RXD6
CIRCUIT
BREAKERS
Interrupting Ratings
Volts AC
Volts AC (50/60HZ)
Volts DC 220/240
(lcu) (lcs) (lcu) (lcs) (lcu) (lcs)
240
480
600
250
500
380/415
500
65
50
25
30 (2P)
25 (3P)
65
33
40
10
30
8
HPD6, HPXD6
HRD6, HRXD6
100
65
50
30 (2P)
50 (3P)
100
50
65
17
42
11
CPD6
200
100
65
30 (2P)
50 (3P)
200
100
100
25
65
17
Instantaneous Adjustment Trip Range (PD / RD Frames)
Breaker Ampere
Rating
1200-2000
Nominal Instantaneous Values
+25%
Tolerance
Low
2
3
4
5000
5715
6430
7145
■ Built to order. Allow 3-4 weeks for delivery.
Use two outside poles of a 3-pole circuit breaker for
250V DC applications.
When wired as shown on page 6-3, this circuit breaker
is CSA Certified / UL listed and rated for use on 500V DC
ungrounded UPS systems only.
5
7860
6
8575
7
9790
+20%
Tolerance
High
10,000
RXD6
and HRXD6 type circuit breakers are CSA Certified
/ UL Listed for reverse feed applications.
rated.
Note: RD frame qualified to UL489 supplement B “NAVAL”.
See page 6-73 for additional information.
HACR
6/51
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
Internal Accessories
Accessories for:
MD/SMD 800A Frame
ND/SND 1200A Frame
PD/SPD 1600A Frame
RD 2000A Frame
Shunt Trip Combinations
Control Voltage
1 Shunt Trip
1 Shunt Trip and
1 Auxiliary Switch
AC
DC
Catalog Number
Catalog Number
120
208
240
277
480
600
—
—
—
—
—
—
S01MN6
S02MN6▲
S03MN6
S15MN6▲
S04MN6▲
S06MN6▲
S01MN64A
S02MN64A▲
S03MN64A▲
S15MN64A▲
S04MN64A▲
—
802.00
802.00
802.00
802.00
802.00
—
—
—
—
—
012
024
048
125
250
S16MN6▲
S07MN6
S09MN6▲
S11MN6
S13MN6▲
S16MN64A▲
S07MN64A
—S11MN64A▲
S13MN64A▲
802.00
802.00
802.00
802.00
Undervoltage Trip Combinations
Control
Voltage
Accessory modules can mount in either
left hand or right hand poles of all circuit
breakers, including solid state. Exception:
when mechanical interlock is used
accessories cannot be mounted in left pole.
Sensitrip Ammeter
1 Undervoltage Trip and
1 Auxiliary Switch
1 Undervoltage Trip
Catalog Number
1 Undervoltage Trip and
2 Auxiliary Switches
AC
DC
120
208
240
277
480
600
—
—
—
—
—
—
U01MN6 569.00
U02MN6▲569.00
U03MN6▲569.00
U15MN6▲569.00
U04MN6▲569.00
U06MN6▲569.00
Catalog Number
U01MN64A 802.00
U02MN64A▲ 802.00
U03MN64A▲ 802.00
U15MN64A▲ 802.00
U04MN64A▲ 802.00
—
-
Catalog Number
U01MN64AA1035.00
U02MN64AA▲1035.00
U03MN64AA▲1035.00
U15MN64AA▲1035.00
U04MN64AA▲1035.00
—
--
—
—
—
—
024
048
125
250
U07MN6 569.00
U09MN6▲569.00
U11MN6▲569.00
U13MN6▲569.00
U07MN64A 802.00
U09MN64A▲ 802.00
U11MN64A▲ 802.00
U13MN64A▲ 802.00
U07MN64AA1035.00
U09MN64AA▲1035.00
U11MN64AA▲1035.00
U13MN64AA▲1035.00
Auxiliary Switch Combinations
Maximum Voltage
1 Form C*
2 Form C
AC
DC
Catalog Number
Catalog Number
480
250
A01MN64
242.00
A02MN64
—
12
A01MNDLV▲*
306.00
(Gold Plated Contacts)
483.00
Alarm Switch Combinations
6
Maximum
Voltage
CIRCUIT
BREAKERS
The Ammeter Display Units plug into
the Sensitrip Trip Unit and displays
the phrase current flowing in the
SADU breaker. They are powered by
the breaker’s CT’s with replaceable
battery back-up for maintaining trip
and max logs.
The SADU reads currents, current
imbalance, current demand, and trip
status.
Ammeter Mounting Kit
The Ammeter may also be panel or
door mounted using the SADURMK18
remote mounting kit.
▲ Built to order. Allow 7-9 weeks for delivery.
6/52
1 Alarm Switch
AC
DC
Catalog Number
480
250
B00MN64
1 Alarm Switch and
1 Auxiliary Switch
1 Alarm Switch and
2 Auxiliary Switches
Catalog Number
242.00
A01MN64B
Catalog Number
483.00
A02MN64B
Plug-in Ammeter Display Units
Breaker Type
SMD, SND, SPD
Desc.
Catalog Number
Display Unit
SADU
Remote Mounting Kit
SADURMK18
1588.00
306.00
Molded Case Circuit Breakers
SELECTION
STD 3200A Frame Digital Solid State Sentron Sensitrip III Series
Type STD6
Type SHTD6
Blue Label
Black Label
STD63F2000■
STD63F2500■
STD63F3200■
Max
Current
Rating
2000
2500
3200
Red Label
3-Pole, 600V AC, 80% Rated
3-Pole, 600V AC, 80% Rated
Catalog
Number
Type SHHTD6
Catalog
Number
22
SHTD63F2000■
SHTD63F2500■
SHTD63F3200■
3-Pole, 600V AC, 100% Rated
Max
Current
Rating
Max
Current
Rating
STD63F2000H■
STD63F2500H■
STD63F3200H■
Catalog
Number
SHTD63F2000H■
SHTD63F2500H■
SHTD63F3200H■
2000
2500
3200
2000
2500
3200
Max
Current
Rating
Catalog
Number
SHHTD63F2000■
SHHTD63F2500■
SHHTD63F3200■
2000
2500
3200
3-Pole, 600V AC, 100% Rated
Catalog
Number
3-Pole, 600V AC, 80% Rated
Max
Current
Rating
Ordering Information
STD Breakers are ordered by
component - Frame, Trip Unit Rating
Plug & Accessories. Contact Sales
Office for instructions.
2000
2500
3200
3-Pole, 600V AC, 100% Rated
Max
Current
Rating
Catalog
Number
266
SHHTD63F2000H■
SHHTD63F2500H■
SHHTD63F3200H■
H
H1
2000
2500
3200
Trip Unit
Fits Breaker Frame with Continuous Rating
2000 Amp
2500 Amp
3200 Amp
W
D
Function
Catalog Numbers
MLI
STD20TMLI
STD25TMLI
STD32TMLI
921.00
LS
STD20TLS
STD25TLS
STD32TLS
2021.00
LI
STD20TLI
STD25TLI
STD32TLI
1440.00
Breaker Type
H
H1
W
D
LSI
STD20TLSI
STD25TLSI
STD32TLSI
2627.00
LSG
STD20TLSG
STD25TLSG
STD32TLSG
3809.00
STD
SHTD
SHHTD
27.5
20.5
15.5
12.5
LIG
STD20TLIG
STD25TLIG
STD32TLIG
2535.00
LSIG
STD20TLSIG
STD25TLSIG
STD32TLSIG
4454.00
Terminal Connectors
Catalog
Number
Rating Plug
STD32TCON
Fits Breaker Frame with Continuous Rating
2000 Amp
2500 Amp
3200 Amp
200.00
Cable Lugs
Catalog Numbers
(2000A Only)
1000
20STD1000
—
—
1200
20STD1200
—
—
1600
20STD1600
25STD1600
32STD1600
2000
20STD2000
25STD2000
32STD2000
2500
—
25STD2500
32STD2500
3000
—
—
32STD3000
3200
—
—
32STD3200
Catalog
Number
TA6R600STD
No of
Cables
per Con- Wire
nector
Range
(1–6 pcs.) 250-600
kcmil Cu/Al
6
Long Time
Amperes
Dimensions (in Inches)
289.00
T. Connector
Catalog
Number
Interrupting Ratings
Breaker
Type
STD6
SHTD6
SHHTD6
RMS Symmetrical kA UL 489 (File E 10848)
240V AC
085
150
200
CIRCUIT
BREAKERS
(For Bus Connector)
480V AC
065
100
150
600V AC
050
085
100
IEC 947-2 (Icu=Ics, Icw=50kA)
415VAC
—
100kA
—
STD32TCON
200.00
690VAC
—
65kA
—
Neutral Transformers
Ampere
Rating
Catalog
Number
2000
2500
3200
N20STD
N25STD
N32STD
411.00
411.00
411.00
Accessories pages 6/54 and 6/75 to 6/80
■ Built to order. Allow 3-4 weeks for delivery.
Dimensions for reference, not for construction.
Dimensions
for reference, not for construction.
Dimensions
for reference, not for construction.
6/53
Molded Case Circuit Breakers
SELECTION
Internal Accessories
Accessories for:
Shunt Trip / Undervoltage Release
STD 3200A Frame
STD Breakers are built to order. It is
recommended that accessories be ordered
installed in the breaker. They may also be
field added.
Control Voltage
Shunt Trip
Under Voltage Release
AC
DC
Catalog Number
Catalog Number
120
240
480
600
—
—
—
—
STDST120▲
STDST240▲
STDST480▲
STDST600▲
STDUV120▲
STDUV240▲
STDUV480▲
STDUV600▲
694.00
694.00
694.00
694.00
Ammeter Dispay Module
—
—
—
—
012
024
048
125
STDST12▲
STDST24▲
STDST48▲
STDST125▲
STDUV12▲
STDUV24▲
STDUV48▲
STDUV125▲
694.00
694.00
694.00
694.00
The STDDM plugs into the trip unit of the
STD 3200 Amp breaker. It provides readout
of currents as well as load current alarm (in
conjunction with the display module relay).
Auxiliary Switches
Control Voltage
AC
Ground Fault Monitor
The Ground Fault Monitor for the STD
3200 Amp breaker family plugs into the Trip
Unit and reads the ground current. This is
either the residual current calculated from
the measured three phases and neutral (if
present) or the directly measured ground
return current in the ground lead of the
supply transformer, depending on the
configuration of the the trip unit. In addition
to displaying the ground current, the display
module provides an alarm on ground
overcurrent, settable at three pickup levels
with three delays (in conjunction with the
display module relay).
Quantity Contacts
DC
600
300
NO
NC
Catalog Number
1
2
3
4
5
6
1
2
3
4
5
6
STDAS2▲
STDAS4▲
STDAS6▲
STDAS8▲
STDAS10▲
STDAS12▲
Auxiliary Power Module
Alarm Switch
Control Voltage
355.00
584.00
876.00
1170.00
1468.00
1739.00
AC
DC
Catalog
Number
600
300
STDAS▲
Power Source
Catalog Number
120V AC
STDAPM▲
642.00
686.00
Electronic Bell Alarm / Display Relay
Control Voltage
Bell Alarm
Display Module Relay
AC
DC
Catalog Number
Catalog Number
120
—
—
—
—
24
48
60
STDBA120▲
STDBA24▲
STDBA48▲
STDBA125▲
STDDMR120▲
STDDMR24▲
STDDMR48▲
STDDMR125▲
Ammeter-Display Module
694.00
694.00
694.00
694.00
Ground Fault Monitor
Catalog Number
Catalog Number
6
STDDM▲
STDGFM▲
2860.00
3669.00
Display Module Relay
Remote Indicator Panels
Provides switch contact output for overload or
ground fault alarm.
Provides remote cause of trip indication.
CIRCUIT
BREAKERS
Voltage
Cat No
120V AC
24V DC
48V DC
125V DC
STDDMR120▲
STDDMR24▲
STDDMR48▲
STDDMR125▲
Catalog Number
STDRIP120▲
1372.00
Mounting Bracket for
Terminal Block
For mounting Control Terminal Blocks to
breakers. One per each side as required.
Catalog Number
STDTBM▲
Secondary Terminal Blocks
87.00
The appropriate number and location of terminal blocks should be selected from the table below based on the features and accessories ordered on
each circuit breaker. Control Terminal Blocks also require separate mounting brackets for the left and right sides.
Accessory
Contact
Block
Position
Catalog
Number
Shunt
Trip
Undervoltage
Release
Neutral
Sensor
Remote
Indication
Panel
Zone
Interlock
and
ACCESS
Auxiliary Switches
Bell Alarm
or Display
Module Relay
LEFT TOP
STDTBLT▲
145.00
✔
✔
✔
—
—
LEFT BOTTOM
STDTBLB▲ 145.00
—
—
—
—
—
—
—
—
—
✔
✔
—
—
—
—
—
—
RIGHT TOP
STDTBRT▲ 145.00
RIGHT BOTTOM
STDTBRB▲ 145.00
▲ Built to order. Allow 7-9 weeks for delivery.
The STD trip unit has built in trip status indication.
Use the STDRIP120 when display of the cause of trip
6/54
is required at location remote from the trip unit in
addition to the intrinsic trip unit capability.
1A and 1B
2A and 2B
3A and 3B
4A and 4B
5A and 5B
6A and 6B
—
—
✔
—
—
—
—
✔
✔
✔
Molded Case Circuit Breakers
SELECTION
Magnetic Trip Only — ETI Motor Circuit
Instantaneous Trip Range ED6-A
600V AC
250V DC
CED6-A
600V AC
250V DC
FXD6 600V AC
250V DC
CFD6 600V AC
250V DC
JXD6(A)
600V AC
250V DC
CJD6 600V AC
250V DC
LXD6(A)
600V AC
250V DC
CLD6 600V AC
250V DC
LMXD6
600V AC
250V DC
MXD6 600V AC
250V DC
CMD6
600V AC
250V DC
001
002
003
005
010
025
030
040
050
100
125
SHIPPING:
001
002
003
005
010
025
030
040
050
100
125
SHIPPING:
150
150
150
250
SHIPPING:
150
150
150
250
SHIPPING:
400
400
SHIPPING:
400
400
SHIPPING:
600
600
SHIPPING:
600
600
SHIPPING:
800
800
SHIPPING:
800
800
800
SHIPPING:
800
800
800
002.6
007
010
016
030
055
080
115
180
315
500
Maximum
00009
00022
00035
00054
00100
00180
00270
00375
00600
01000
01250
Catalog
Number
2-Pole
—
—
—
—
—
—
—
—
—
—
—
002.6
007
010
016
030
055
080
115
180
315
500
00009
00022
00035
00054
00100
00180
00270
00375
00600
01000
01250
—
—
—
—
—
—
—
—
—
—
—
0400
0800
1100
1100
00800
01500
02500
02500
0400
0800
1100
1100
00800
01500
02500
02500
1250
2000
02500
04000
1250
2000
02500
04000
2000
3000
04000
06000
2000
3000
04000
06000
—
—
—
—
0
—
—
—
—
12 lbs. each
—
JXD62H400■
16 lbs. each
CJD62L400■
CJD62H400■
29.5 lbs. each
LXD62L600■
—
16 lbs. each
CLD62L600■
CLD62H600■
2800
3200
06000
08000
—
—
3000
4000
5000
06000
08000
10000
—
—
—
3000
4000
5000
06000
08000
10000
—
—
—
Minimum
Catalog
Number
3-Pole
ED63A001
ED63A002
ED63A003
ED63A005
ED63A010
ED63A025
ED63A030
ED63A040
ED63A050
ED63A100
ED63A125
737.00
737.00
737.00
737.00
737.00
737.00
737.00
737.00
886.00
941.00
1786.0
3.8 lbs. each
CED63A001■
CED63A002■
CED63A003■
CED63A005■
CED63A010■2514.00
CED63A025■2514.00
CED63A030■2514.00
CED63A040■2514.00
CED63A050■3005.00
CED63A100■3226.00
CED63A125■
6 lbs. each
FXD63L150■3084.00
FXD63A1503084.00
FXD63H1503084.00
FXD63A2503084.00
9 lbs. each
CFD63L150■5960.00
CFD63A150■5960.00
CFD63H150■5960.00
CFD63A250■5960.00
12 lbs. each
JXD63L4003226.00
JXD63H4003226.00
20 lbs. each
CJD63L400■6923.00
CJD63H400■6923.00
31.5 lbs. each
LXD63L600■
LXD63H600
20 lbs. each
CLD63L600■
CLD63H600■
31.5 lbs. each
LMXD63L800■
LMXD63A800
35 lbs. each
MXD63L800■
MXD63A800■
MXD63H800 6671.0
33 lbs. each
CMD63L800■126.00
CMD63A800■25.
CMD63H800■
80 lbs. each
SHIPPING:
2514.0
2514.0
2514.0
2514.0
4837.00
6
Ampere
Rating
4710
40.00
1108200
11082.0
6671
6671
6671
6671
12536.0
Important Information
ETI interrupting ratings are determined through combination tests with properly sized overload relays and contactors.
Connectors included when ordering by circuit breaker catalog number for
ED6 and CED6 ETI’s. Order ETI circuit breaker and lugs (2 per pole) separately
for the FXD6, CFD6, MXD6, CMD6, JXD6, CJD6, LXD6 and CLD6 ETI’s.
Lug Information pages 6/70 to 6/72
Accessories pages 6/75 to 6/80
Application data pages 6/56 to 6/57
■ Built to order. Allow 2–3 weeks for delivery.
2-pole available in 3-pole width only.
When applied on DC Circuits — Trip levels will increase
approximately +15 to 20%.
Tolerance -20/+30%
For 2-pole application use outside poles of 3-pole circuit
breaker.
6/55
CIRCUIT
BREAKERS
Breaker
Type
Complete Circuit Breaker Without Lugs
Molded Case Circuit Breakers
APPLICATION
Motor Circuits
General
Protection of Motor Circuits
Molded case circuit breakers are used in
motor circuits as a disconnecting means
and for short-circuit protection. They
should be used in conjunction with motorrunning, over-current-protection devices,
and should permit the motor to start
without nuisance tripping from motorinrush current. The circuit breaker should
have a continuous-current rating of
not less than 115% of the motor
full-load current.
The recommended motor circuit
protectors (Siemens ETI instantaneous
only circuit breakers) listed have
continuous-current ratings of at least
115% of motor full-load currents. The
trip-setting positions are approximately
11 times motor full-load currents. The
suggested trip settings may have to be
adjusted upward to no higher than 1300%
of full-load current for non-design E type
motors, and no greater than 1700% of
full load current for design B & E energy
efficient motors, to allow for motor startup due to inrush currents.
Breaker Mounted Immediately Ahead
of Motor Starter
Siemens ETI motor circuit protectors are
recommended for use in combination
motor starters to provide selective short-
circuit protection for the motor branch
circuit. The adjustable instantaneous-trip
feature of the Siemens ETI motor circuit
protector provides for a trip setting slightly
above the peak motor-inrush current.
With this setting, no delay is introduced
in opening the circuit when a fault occurs.
This circuit breaker has no time-delay
trip element. Therefore it must be used
in conjunction with, and immediately
ahead of, the motor-running overcurrent
protective device.
Important: The information below does
not apply to all motor applications: it
is recommended that the user refer to
the National Electrical Code (NEC) for
specific needs.
Table 1 (When Breaker is Mounted Immediately Ahead of Motor Starter)
3 Phase Induction Type Motors (Siemens ETI motor circuit protectors for branch circuit use with alternating-current combination, full voltage motor starters).
6
CIRCUIT
BREAKERS
Motor
Full Load
Amperes
.20 –
.33
.34 –
.45
.46 –
.56
.57 –
.68
.69 –
.81
.53 –
.83
.84 – 1.14
1.15 – 1.45
1.46 – 1.68
1.69 – 2.00
.76 – 1.29
1.30 – 1.75
1.76 – 2.29
2.30 – 2.68
2.69 – 3.18
1.23 – 1.99
2.00 – 2.75
2.76 – 3.52
3.53 – 4.14
4.15 – 4.90
2.30 – 3.83
3.84 – 5.37
5.38 – 6.52
6.53 – 7.68
7.69 – 9.10
4.23 – 6.91
6.92 – 9.61
9.62 – 11.91
11.92 – 13.83
13.84 – 16.40
6.15 – 10.37
10.38 – 14.22
14.23 – 18.06
18.07 – 20.75
20.76 – 24.50
8.84 – 14.22
14.23 – 19.60
19.61 – 24.99
25.00 – 28.83
28.84 – 34.00
13.84 – 23.06
23.07 – 31.52
31.53 – 39.99
40.00 – 46.14
46.15 – 54.50
24.23 – 41.52
41.53 – 56.91
56.92 – 68.45
68.46 – 76.91
76.92 – 90.90
6/56
Catalog
ED63A001
CED63A001
ED63A002
CED63A002
ED63A003
CED63A003
ED63A005
CED63A005
ED63A010
CED63A010
ED63A025
CED63A025
ED63A030
CED63A030
ED63A040
CED63A040
ED63A050
CED63A050
ED63A100
CED63A100
ETI Trip Setting
AdjustNumber mentAmperes
Low
2.6
2
4.5
3
6
4
7.5
High
9
Low
7
2
11
3
15
4
19
High
22
Low
10
2
17
3
23
4
30
High
35
Low
16
2
26
3
36
4
46
High
54
Low
30
2
50
3
70
4
85
High
100
Low
55
2
90
3
125
4
155
High
180
Low
80
2
135
3
185
4
235
High
270
Low
115
2
185
3
255
4
325
High
375
Low
180
2
300
3
410
4
520
High
600
Low
315
2
540
3
740
4
890
High
1000
Motor Full
Catalog
Load Amperes Number
38.46 – 55.37
55.38 – 70.75
70.76 – 84.60
ED63A125
84.61 – 96.14 CED63A125
96.15 – 113.60
30.76 – 35.37
35.38 – 39.99
44.51 – 49.23 FXD63L150
53.84 – 58.45 CFD63L150
58.46 – 63.06
63.07 – 74.50
61.53 – 69.22
69.23 – 76.91
84.61 – 92.29 FXD63A150
100.00 – 108.00 CFD63A150
108.00 – 115.00
115.00 – 136.00
85.00 – 100.00
100.00 – 115.00
131.00 – 146.00 FXD63A250
162.00 – 177.00 CFD63A250
177.00 – 192.00
192.00 – 227.00
95.00 – 110.00
110.00 – 124.00
138.00 – 151.00 JXD63L400
165.00 – 178.00 CJD63L400
178.00 – 192.00
192.00 – 227.00
154.00 – 176.00
176.00 – 198.00
220.00 – 242.00 JXD63H400
264.00 – 285.00 CJD63H400
285.00 – 308.00
308.00 – 326.00
155.00 – 176.00
176.00 – 198.00
220.00 – 242.00 LXD63L600
264.00 – 285.00 CLD63L600
285.00 – 308.00
308.00 – 326.00
ETI Trip Setting
Adjustment
Amperes
Low
500
2
720
3
920
4
1100
High
1250
Low
400
2
460
4
580
6
700
7
760
High
820
Low
800
2
900
4
1100
6
1300
7
1400
High
1500
Low
1100
2
1300
4
1700
6
2100
7
2300
High
2500
Low
1250
2
1430
4
1790
6
2140
7
2320
High
2500
Low
2000
2
2290
4
2860
6
3430
7
3710
High
4000
Low
2000
2
2290
4
2860
6
3430
7
3710
High
4000
Motor Full
Catalog
Load Amperes Number
231.00 – 264.00
264.00 – 292.00
330.00 – 362.00
LXD63H600
395.00 – 428.00
CLD63H600
428.99 – 462.00
462.00 – 490.00
215.00 – 238.00
238.00 – 261.00
261.00 – 284.00
308.00 – 369.00 LMXD63L800
369.00 – 423.00
423.00 – 462.00
462.00 – 490.00
246.00 – 269.00
269.00 – 284.00
284.00 – 323.00
362.00 – 492.00 LMXD63A800
492.00 – 562.00
562.00 – 616.00
616.00 – 660.00
231.00 – 264.00
264.00 – 292.00
292.00 – 330.00
362.00 – 395.00
MXD63L800
428.00 – 462.00
CMD63L800
462.00 – 490.00
308.00 – 352.00
352.00 – 442.00
442.00 – 447.00
483.00 – 527.00 MXD63A800
571.00 – 616.00 CMD63A800
616.00 – 660.00
385.00 – 440.00
495.00 – 550.00 MXD63H800
605.00 – 660.00 CMD63H800
660.00 – 695.00
ETI Trip Setting
Adjustment Amperes
Low
3000
2
3430
4
4290
6
5140
7
5570
High
6000
Low
2800
2
3100
3
3400
5
4000
6
4800
7
5500
High
6000
Low
3200
2
3500
3
3700
5
4700
6
6400
7
7300
High
8000
Low
3000
2
3430
3
3800
5
4710
7
5570
High
6000
Low
4000
2
4570
3
5740
5
6280
7
7240
High
8000
Low
5000
3
6430
5
7860
6
8575
Molded Case Circuit Breakers
APPLICATION
Motor Circuits
Breaker Mounted at a Distance From
Motor Starter
ET thermal-magnetic circuit breakers
conform to the National Electrical Code
(2002) table 430-52 requirements for
motor branch and feeder circuit protection
when properly applied in conjunction
with motor-running overcurrent protective
devices. The recommended
circuit-breaker ratings in Table 2 provide
adequate time delay for starting the
majority of three-phase induction motors.
To determine the ampere ratings of the
ET breaker to protect a motor feeder,
add the rating of the ET breaker used to
protect the largest motor branch circuit in
the group to the full-load currents of the
remaining motors in the group.
Interrupt Ratings
For normal commercial purposes, available
fault current can conveniently be obtained
in the Interrupting Selector Tables.
Table 2 (When Breaker is Mounted at a Distance From Motor Starter)
3 Phase Induction Type Motors (EQ and ET circuit breakers (thermal-magnetic trip) for branch breaker use with alternating-current combination motor starters).
100
JXD2
JXD23B400
400
200
250
LD6 or
LMD6
LD6 or
LMD6
LMD6
—
LD63B600
LMD63B600
LD63B600 or
LMD63B600
LMD63B800
—
300
—
350
—
125
150
230V Motors
240V Circuit Breaker Data Breaker Catalog
Ampere
Type
Number
Rating
BQ3B015
015
BQ3B015
015
BQ3B015
015
BQ
BQ3B015
015
BQ3B015
015
BQ3B020
020
BQ3B030
030
BQ3B050
050
BQ
BQ3B070
070
BQ3B090
090
BQ3B100
100
FXD63B125
125
FXD63B150
150
FXD6
FXD63B175
175
FXD63B200
200
460V Motors
480V Circuit Breaker Data Breaker
Catalog
Ampere
Type
Number
Rating
ED43B015
015
ED43B015
015
ED43B015
015
ED4
ED43B015
015
ED43B015
015
ED43B015
015
ED43B015
015
ED43B030
030
ED4
ED43B030
030
ED43B040
040
ED43B050
050
FXD63B090
090
FXD63B100
100
FXD6
FXD63B125
125
FXD63B150
150
575V Motors
600V Circuit Breaker Data Breaker
Catalog
Ampere
Type
Number
Rating
ED63B015
015
ED63B015
015
ED63B015
015
ED6
ED63B015
015
ED63B015
015
ED63B015
015
ED63B015
015
ED63B020
020
ED6
ED63B030
030
ED63B035
035
ED63B050
050
FXD63B060 060
FXD63B070 070
FXD6
FXD63B090 090
FDX63B100 100
—
JXD2
FXD6, FD6
FXD6, FD6
FD6 JD6 150
200
250
250
FXD6
FXD63B100
FXD6, FD6 FXD63B125
FXD6, FD6 FD63B175
175
FXD63B200
JD63B200
FXD63B225
JD63B225
JD63B300
JD63B400
200
200
225
225
300
400
400
—
JXD23B350
—
350
JXD2
JXD23B400
400
600
LD6 or
LMD6
600
LMD6
800
—
LMD6
—
LD63B500 or
LMD63B500
LD63B600 or
LMD63B600
LMD63B800
—
—
—
—
—
—
—
—
—
—
—
FXD63B150
FXD63B200
FD63B250
JD63B250
100
125
500
JD6
JD63B300
300
600
JD6 JD63B300
300
800
—
JD6 JD6 LD6 or
LMD6
JD63B350
JD63B400
LD63B600 or
LMD63B600
350
400
FXD6, FD6
OR JD6 FXD6 or
JD6 JD6 JD6 600
JD6 JD63B400
LMD6
LMD63B700
700
LD6 or
LMD6
LD6 or
LMD6
LMD6
LD63B500 or 500
LMD63B500
LD63B600 or 600
LMD63B600
LMD63B800 800
—
—
—
—
—
—
LMD6
LMD63B800
800
—
—
—
—
—
—
—
—
—
CIRCUIT
BREAKERS
400
500
6
060
075
200 and 208V Motors
240V Circuit Breaker Data Breaker
Catalog
Ampere
Type
Number
Rating
BQ3B015
015
BQ3B015
015
BQ3B015
015
BQ
BQ3B015
015
BQ3B020
020
BQ3B030
030
BQ3B040
040
BQ3B060
060
BQ
BQ3B070
070
BQ3B100
100
—
—
FXD63B125
125
FXD63B150
150
FXD6
FXD63B175
175
FXD63B200
200
FXD63B225
225
JXD2
JXD23B300
300
JXD2
JXD23B400
400
Motor
Horsepower
Rating
0001⁄2
0003⁄4
001
0011⁄2
002
003
005
0071⁄2
010
015
020
025
030
040
050
The
selection of breakers for this table is in accordance
with Article 430, 2002 National Electric Code. The Canadian
electrical code should also be referred to for rating
information. Recommended circuit breakers are for full
voltage starting, special consideration is necessary for
reduced voltage starting.
For
panelboard applications, substitute the BL breaker for the
BQ, ED2 circuit breakers may also be used.
For
non-interchangeable trip applications, substitute the FXD6
for the FD6, the JXD6 for the JD6, or the LXD6 for
the LD6.
6/57
Molded Case Circuit Breakers
APPLICATION
Adjustable Instantaneous Magnetic Trip Settings
Breaker
Type
ED6
CED6
FXD6-A
FD6-A
6
HFD6
CIRCUIT
BREAKERS
HHFD6
CFD6
Maximum
Continuous
Amperes
1
2
3
5
10
25
30
40
50
100
125
1
2
3
5
10
25
30
40
50
100
125
70
80
90
100
110
125
150
150
150
175
200
225
250
70
80
90
100
110
125
150
175
200
225
250
70
80
90
100
110
125
150
175
200
225
250
70
80
90
100
110
125
150
175
200
225
250
70
80
90
100
110
125
150
150
150
175
200
225
250
Nominal
AC Adjustable Trip Range
Low
2
3
4
2.6
4.5
6
7.5
7
11
15
19
10
17
23
30
16
26
36
46
30
50
70
85
55
90
125
155
80
135
185
235
115
185
255
325
180
300
410
520
315
540
740
890
500
720
920
1100
2.6
4.5
6
7.5
7
11
15
19
10
17
23
30
16
26
36
46
30
50
70
85
55
90
125
155
80
135
185
235
115
185
255
325
180
300
410
520
315
540
740
890
500
720
920
1100
600
640
690
730
600
640
690
730
600
640
690
730
700
770
840
920
700
770
840
920
800
900
1000
1100
400
460
520
580
800
900
1000
1100
1100
1300
1500
1700
900
1060
1210
1370
900
1060
1210
1370
1100
1300
1500
1700
1100
1300
1500
1700
600
640
690
730
600
640
690
730
600
640
690
730
700
770
840
920
700
770
840
920
800
900
1000
1100
800
900
1000
1100
900
1060
1210
1370
900
1060
1210
1370
1100
1300
1500
1700
1100
1300
1500
1700
600
640
690
730
600
640
690
730
600
640
690
730
700
770
840
920
700
770
840
920
800
900
1000
1100
800
900
1000
1100
900
1060
1210
1370
900
1060
1210
1370
1100
1300
1500
1700
1100
1300
1500
1700
600
640
690
730
600
640
690
730
600
640
690
730
700
770
840
920
700
770
840
920
800
900
1000
1100
800
900
1000
1100
900
1060
1210
1370
900
1060
1210
1370
1100
1300
1500
1700
1100
1300
1500
1700
600
640
690
730
600
640
690
730
600
640
690
730
700
770
840
920
700
770
840
920
800
900
1000
1100
400
460
520
580
800
900
1000
1100
1100
1300
1500
1700
900
1060
1210
1370
900
1060
1210
1370
1100
1300
1500
1700
1100
1300
1500
1700
Note:
Tolerances for instantaneous trip points meet UL 489 (15.3).
Nominal AC instantaneous trip points are given in the tables.
6/58
5
6
7
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
770
770
770
990
990
1200
640
1200
1900
1520
1520
1900
1900
770
770
770
990
990
1200
1200
1520
1520
1900
1900
770
770
770
990
990
1200
1200
1520
1520
1900
1900
770
770
770
990
990
1200
1200
1520
1520
1900
1900
770
770
770
990
990
1200
640
1200
1900
1520
1520
1900
1900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
810
810
810
1060
1060
1300
700
1300
2100
1780
1780
2100
2100
810
810
810
1060
1060
1300
1300
1780
1780
2100
2100
810
810
810
1060
1060
1300
1300
1780
1780
2100
2100
810
810
810
1060
1060
1300
1300
1780
1780
2100
2100
810
810
810
1060
1060
1300
700
1300
2100
1780
1780
2100
2100
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
850
850
850
1140
1140
1400
760
1400
2300
1930
1930
2300
2300
850
850
850
1140
1140
1400
1400
1930
1930
2300
2300
850
850
850
1140
1140
1400
1400
1930
1930
2300
2300
850
850
850
1140
1140
1400
1400
1930
1930
2300
2300
850
850
850
1140
1140
1400
760
1400
2300
1930
1930
2300
2300
High
9
22
35
54
100
180
270
375
600
1000
1250
9
22
35
54
100
180
270
375
600
1000
1250
900
900
900
1200
1200
1500
820
1500
2500
2000
2000
2500
2500
900
900
900
1200
1200
1500
1500
2000
2000
2500
2500
900
900
900
1200
1200
1500
1500
2000
2000
2500
2500
900
900
900
1200
1200
1500
1500
2000
2000
2500
2500
900
900
900
1200
1200
1500
820
1500
2500
2000
2000
2500
2500
ETI Motor Circuit Protector
Thermal Magnetic
Catalog Number
CatalogNumber
3-Pole
2-Pole
3-Pole
ED63A001
—
—
ED63A002
—
—
ED63A003
—
—
ED63A005
—
—
ED63A010
—
—
ED63A025
—
—
ED63A030
—
—
ED63A040
—
—
ED63A050
—
—
ED63A100
—
—
ED63A125
—
—
CED63A001
—
—
CED63A002
—
—
CED63A003
—
—
CED63A005
—
—
CED63A010
—
—
CED63A025
—
—
CED63A030
—
—
CED63A040
—
—
CED63A050
—
—
CED63A100
—
—
CED63A125
—
—
—
FXD62B070
FXD63B070
—
FXD62B080
FXD63B080
—
FXD62B090
FXD63B090
—
FXD62B100
FXD63B100
—
FXD62B110
FXD63B110
—
FXD62B125
FXD63B125
FXD63L150
—
—
FXD63A150
FXD62B150
FXD63B150
FXD63H150
—
—
—
FXD62B175
FXD63B175
—
FXD62B200
FXD63B200
—
FXD62B225
FXD63B225
FXD63A250
FXD62B250
FXD63B250
—
FD62B070
FD63B070
—
FD62B080
FD63B080
—
FD62B090
FD63B090
—
FD62B100
FD63B100
—
FD62B110
FD63B110
—
FD62B125
FD63B125
—
FD62B150
FD63B150
—
FD62B175
FD63B175
—
FD62B200
FD63B200
—
FD62B225
FD63B225
—
FD62B250
FD63B250
—
HFD62B070
HFD63B070
—
HFD62B080
HFD63B080
—
HFD62B090
HFD63B090
—
HFD62B100
HFD63B100
—
HFD62B110
HFD63B110
—
HFD62B125
HFD63B125
—
HFD62B150
HFD63B150
—
HFD62B175
HFD63B175
—
HFD62B200
HFD63B200
—
HFD62B225
HFD63B225
—
HFD62B250
HFD63B250
—
—
HHFD63B070
—
—
HHFD63B080
—
—
HHFD63B090
—
—
HHFD63B100
—
—
HHFD63B110
—
—
HHFD63B125
—
—
HHFD63B150
—
—
HHFD63B175
—
—
HHFD63B200
—
—
HHFD63B225
—
—
HHFD63B250
—
CFD62B070
CFD63B070
—
CFD62B080
CFD63B080
—
CFD62B090
CFD63B090
—
CFD62B100
CFD63B100
—
CFD62B110
CFD63B110
—
CFD62B125
CFD63B125
CFD63L150
—
—
CFD63A150
CFD62B150
CFD63B150
CFD63H150
—
—
—
CFD62B175
CFD63B175
—
CFD62B200
CFD63B200
—
CFD62B225
CFD63B225
CFD63A250
CFD62B250
CFD63B250
For DC instantaneous trip points, add 15% to nominal values.
Instantaneous trip adjustment is made through the breaker
cover on all frame breakers. To change instantaneous trip point
on circuit breaker, depress indicating knob, then rotate to
desired position.
Molded Case Circuit Breakers
APPLICATION
JXD2(A)
JXD6(A)
JD6(A)
HJD6(A)
HHJD6
CJD6
LXD6(A)
LD6(A)
HLD6(A)
HHLD6
CLD6
LMXD6
LMD6
Maximum
Continuous
Amperes
200
225
250
300
350
400
200
225
250
300
350
400
200
225
250
300
350
400
400
200
225
250
300
350
400
200
225
250
300
350
400
200
225
250
300
350
400
400
450
500
600
250
300
350
400
450
500
600
600
250
300
350
400
450
500
600
250
300
350
400
450
500
600
250
300
350
400
450
500
600
600
500
600
700
800
800
500
600
700
800
Nominal
AC Adjustable Trip Range
Low
2
3
4
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
1250
1430
1610
1790
2000
2290
2570
2860
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
1250
1450
1610
1790
2000
2290
2570
2860
3000
3430
3860
4290
3000
3430
3860
4290
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
2000
2290
2570
2860
3000
3430
3800
4290
2000
2290
2570
2860
3000
3430
3800
4290
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
2000
2290
2570
2860
3000
3430
3860
4290
3000
3430
3860
4290
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
2000
2290
2570
2860
3000
3430
3860
4290
3000
3430
3860
4290
1250
1430
1610
1790
1250
1430
1610
1790
2000
2290
2570
2860
2000
2290
2570
2860
2000
2290
2570
2860
3000
3430
3860
4290
2000
2290
2570
2860
3000
3430
3860
4290
3000
3430
3860
4290
3000
3430
3860
4290
3200
3500
3700
4200
2800
3100
3400
3700
3200
3500
3700
4200
3000
3430
3860
4290
3000
3430
3860
4290
3200
3500
3700
4200
3200
3500
3700
4200
5
1960
1960
1960
1960
3140
3140
1960
1960
1960
1960
3140
3140
1960
1960
1960
1960
3140
1960
3140
1960
1960
1960
1960
3140
3140
1960
1960
1960
1960
3140
3140
1960
1960
1960
1960
3140
3140
1960
3140
4710
4710
1960
1960
3140
3140
3140
4710
3140
4710
1960
1960
3140
3140
3140
4710
4710
1960
1960
3140
3140
3140
4710
4710
1960
1960
3140
3140
3140
4710
3140
4710
4710
4710
4700
4000
4700
4710
4710
4700
4700
6
2140
2140
2140
2140
3430
3430
2140
2140
2140
2140
3430
3430
2140
2140
2140
2140
3430
2140
3430
2140
2140
2140
2140
3430
3430
2140
2140
2140
2140
3430
3430
2140
2140
2140
2140
3430
3430
2140
3430
5140
5140
2140
2140
3430
3430
3430
5140
3430
5140
2140
2140
3430
3430
3430
5140
5140
2140
2140
3430
3430
3430
5140
5140
2140
2140
3430
3430
3430
5140
3430
5140
5140
5140
6400
4800
6400
5140
5140
6400
6400
7
2320
2320
2320
2320
3710
3710
2320
2320
2320
2320
3710
3710
2320
2320
2320
2320
3710
2320
3710
2320
2320
2320
2320
3710
3710
2320
2320
2320
2320
3710
3710
2320
2320
2320
2320
3710
3710
2320
3710
5570
5570
2320
2320
3710
3710
3710
5570
3710
5570
2320
2320
3710
3710
3710
5570
5570
2320
2320
3710
3710
3710
5570
5570
2320
2320
3710
3710
3710
5570
3710
5570
5570
5570
7300
5500
7300
5570
5570
7300
7300
High
2500
2500
2500
2500
4000
4000
2500
2500
2500
2500
4000
4000
2500
2500
2500
2500
4000
2500
4000
2500
2500
2500
2500
4000
4000
2500
2500
2500
2500
4000
4000
2500
2500
2500
2500
4000
4000
2500
4000
6000
6000
2500
2500
4000
4000
4000
6000
4000
6000
2500
2500
4000
4000
4000
6000
6000
2500
2500
4000
4000
4000
6000
6000
2500
2500
4000
4000
4000
6000
4000
6000
6000
6000
8000
6000
8000
6000
6000
8000
8000
ETI Motor Circuit Protector
Thermal Magnetic
Catalog Number
CatalogNumber
3-Pole
2-Pole
3-Pole
—
JXD22B200
JXD23B200
—
JXD22B225
JXD23B225
—
JXD22B250
JXD23B250
—
JXD22B300
JXD23B300
—
JXD22B350
JXD23B350
—
JXD22B400
JXD23B400
—
JXD62B200
JXD63B200
—
JXD62B225
JXD63B225
—
JXD62B250
JXD63B250
—
JXD62B300
JXD62B300
—
JXD62B350
JXD23B350
—
JXD62B400
JXD23B400
—
JD62B200
JD63B200
—
JD62B225
JD63B225
—
JD62B250
JD63B250
—
JD62B300
JD63B300
—
JD62B350
JD63B350
JXD63L400
—
—
JXD63H400
JD62B400
JD63B400
—
HJD62B200
HJD63B200
—
HJD62B225
HJD63B225
—
HJD62B250
HJD63H250
—
HJD62B300
HJD63B300
—
HJD62B350
HJD63B350
—
HJD62H400
HJD63B400
—
HHJD62B200 HHJD63B200
—
HHJD62B225 HHJD63B225
—
HHJD62B250 HHJD63B250
—
HHJD62B300 HHJD63B300
—
HHJD62B350 HHJD63B350
—
HHJD62B400 HHJD63B400
—
—
CJD63B200
—
—
CJD63B225
—
—
CJD63B250
—
—
CJD63B300
—
—
CJD63B350
CJD63H400
—
CHD63B400
CJD63L400
—
—
—
LXD62B450
LXD63B450
—
LXD62B500
LXD63B500
—
LXD62B600
LXD63B600
—
LD62B250
LD63B250
—
LD62B300
LD63B300
—
LD62B350
LD63B350
—
LD62B400
LD63B400
—
LD62B450
LD63B450
—
LD62B500
LD63B500
LXD63L600
—
—
LXD63H600
LD62B600
LD63B600
—
HLD62B250
HLD63B250
—
HLD62B300
HLD63B300
—
HLD62B350
HLD63B350
—
HLD62B400
HLD63B400
—
HLD62B450
HLD63B450
—
HLD62B500
HLD63B500
—
HLD62B600
HLD63B600
—
HHLD62B250 HHLD63B250
—
HHLD62B300 HHLD63B300
—
HHLD62B350 HHLD63B350
—
HHLD62B400 HHLD63B400
—
HHLD62B450 HHLD63B450
—
HHLD62B500 HHLD63B500
—
HHLD62B600 HHLD63B600
—
—
CLD63B250
—
—
CLD63B300
—
—
CLD63B359
—
—
CLD63B400
—
—
CLD63B450
—
—
CLD63B500
CLD63L600
—
—
CLD63H600
—
CLD63B600
—
—
LMXD63B500
—
LMXD62B600 LMXD63B600
—
LMXD62B700 LMXD63B700
LMXD63L800
—
—
LMXD63A800
LMXD62B800 LMXD63B800
—
LMD62B500
LMD63B500
—
LMD62B600
LMD63B600
—
LMD62B700
LMD63B700
—
LMD62B800
LMD63B800
6/59
CIRCUIT
BREAKERS
Breaker
Type
6
Adjustable Instantaneous Magnetic Trip Settings
Molded Case Circuit Breakers
APPLICATION
Adjustable Instantaneous Magnetic Trip Settings
Breaker
Type
HLMXD6
HLMD6
MD6
MXD6
HMD6
HMXD6
CMD6
ND6
NXD6
6
HND6
HNXD6
CIRCUIT
BREAKERS
CND6
PD6
PXD6
HPD6
HPXD6
CPD6
RD6
RXD6
HRD6
6/60
Maximum
Continuous
Amperes
500
600
700
800
500
600
700
800
500
600
700
800
800
800
500
600
700
800
800
800
500
600
700
800
500
600
700
800
400
500
600
700
800
800
800
800
900
1000
1200
900
1000
1200
800
900
1000
1200
900
1000
1200
800
900
1000
1200
1200
1400
1600
1200
1400
1600
1200
1400
1600
1200
1400
1600
1200
1400
1600
1800
2000
1800
2000
1800
2000
Nominal
AC Adjustable Trip Range
Low
2
3
4
3000
3430
3860
4290
3000
3430
3860
4290
3200
3500
3700
4200
3200
3500
3700
4200
3000
3430
3860
4290
3000
3430
3860
4290
3200
3500
3700
4200
3200
3500
3700
4200
3000
3430
3860
4290
3000
3430
3860
4290
4000
4570
5140
5710
3000
3430
3860
4280
4000
4570
5140
5710
5000
5715
6430
7145
3000
3430
3860
4280
3000
3430
3860
4280
4000
4570
5140
5710
3000
3430
3860
4280
4000
4570
5140
5710
5000
5715
6430
7145
3000
3430
3860
4280
3000
3430
3860
4280
4000
4570
5140
5710
4000
4570
5140
5710
3000
3430
3860
4280
3000
3430
3860
4280
4000
4570
5140
5710
4000
4570
5140
5710
3000
3430
3860
4280
3000
3430
3860
4280
3000
3430
3860
4280
4000
4570
5140
5710
3000
3430
3860
4280
4000
4570
5140
5710
5000
5715
6430
7145
4000
4570
5140
5710
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
4000
4570
5140
5710
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
4000
4570
5140
5710
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5000
5715
6430
7145
5
4710
4710
4700
4700
4710
4710
4700
4700
4710
4710
6280
4710
6280
7860
4710
4710
6280
4710
6280
7860
4710
4710
6280
6280
4710
4710
6280
6280
4710
4710
4710
6280
4710
6280
7860
6280
7860
7860
7860
7860
7860
7860
6280
7860
7860
7860
7860
7860
7860
6280
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
7860
6
5140
5140
6400
6400
5140
5140
6400
6400
5140
5140
6850
5140
6850
8575
5140
5140
6850
5140
6850
8575
5140
5140
6850
6850
5140
5140
6850
6850
5140
5140
5140
6850
5140
6850
8575
6850
8575
8575
8575
8575
8575
8575
6850
8575
8575
8575
8575
8575
8575
6850
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
8575
7
5570
5570
7300
7300
5570
5570
7300
7300
5570
5570
7420
5570
7420
9290
5570
5570
7420
5570
7420
9290
5570
5570
7420
7420
5570
5570
7420
7420
5570
5570
5570
7420
5570
7420
9290
7420
9290
9290
9290
9290
9290
9290
7420
9290
9290
9290
9290
9290
9290
7420
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
9290
High
6000
6000
8000
8000
6000
6000
8000
8000
6000
6000
8000
6000
8000
10000
6000
6000
8000
6000
8000
10000
6000
6000
8000
8000
6000
6000
8000
8000
6000
6000
6000
8000
6000
8000
10000
8000
10000
10000
10000
10000
10000
10000
8000
10000
10000
10000
10000
10000
10000
8000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
ETI Motor Circuit Protector
Thermal Magnetic
Catalog Number
Catalog Number
3-Pole
2-Pole
3-Pole
—
—
HLMXD63B500
—
—
HLMXD63B600
—
—
HLMXD63B700
—
—
HLMXD63B800
—
HLMD62B500
HLMD63B500
—
HLMD62B600
HLMD63B600
—
HLMD62B700
HLMD63B700
—
HLMD62B800
HLMD63B800
—
MD62B500
MD63B500
—
MD62B600
MD63B600
—
MD62B700
MD63B700
MXD63L800
—
—
MXD63A800
MD62B800
MD63B800
MXD63H800
—
—
—
MXD62B500
MXD63B500
—
MXD62B600
MXD63B600
—
MXD62B700
MXD63B700
MXD63L800
—
—
MXD63A800
MXD62B800
MXD63B800
MXD63H800
—
—
—
HMD62B500
HMD63B500
—
HMD62B500
HMD63B600
—
HMD62B700
HMD63B700
—
HMD62B800
HMD63B800
—
—
HMXD63B500
—
—
HMXD63B600
—
—
HMXD63B700
—
—
HMXD63B800
—
—
CMD63B400
—
—
CMD63B500
—
—
CMD63B600
—
—
CMD63B700
CMD63L800
—
—
CMD63A800
—
CMD63B800
CMD63H800
—
—
—
ND62B800
ND63B800
—
ND62B900
ND63B900
—
ND62B100
ND63B100
—
ND62B120
ND63B120
—
NXD62B900
NXD63B900
—
NXD62B100
NXD63B100
—
NXD62B120
NXD63B120
—
HND62B800
HND63B800
—
HND62B900
HND63B900
—
HND62B100
HND63B100
—
HND62B120
HND63B120
—
—
HNXD63B900
—
—
HNXD63B100
—
—
HNXD63B120
—
—
CND63B800
—
—
CND63B900
—
—
CND63B100
—
—
CND63B120
—
—
PD63B120
—
—
PD63B140
—
—
PD63B160
—
—
PXD63B120
—
—
PXD63B140
—
—
PXD63B160
—
—
HPD63B120
—
—
HPD63B140
—
—
HPD63B160
—
—
HPXD63B120
—
—
HPXD63B140
—
—
HPXD63B160
—
—
CPD63B120
—
—
CPD63B140
—
—
CPD63B160
—
—
RD63B180
—
—
RD63B200
—
—
RXD63B180
—
—
RXD63B200
—
—
HRD63B180
—
—
HRD63B200
Molded Case Circuit Breakers
SELECTION
Molded Case Switch — Circuit Disconnect
Maximum
Frame
Rating
1100A
2-Pole
3-Pole
Catalog
Number
Catalog
Number
BQ2S060 ■
BQ2S100■
68.00
181.00
BQ3S060■
BQ3S100■
Self-Protective
Instantaneous
Override±20%
314.00
314.00
11000A
11000A
1125A
ED22S100A■ 257.00
ED42S100A■ 541.00
ED42S125A■1035.00
ED62S100A■ 624.00
—
—
CED62S100A■2325.00
CED62S125A■3509.00
ED23S100A 437.00
ED43S100A 664.00
ED43S125A 1337.00
ED63S100A 800.00
ED63S125A 1527.00
CED63S100A■2907.00
CED63S125A■4172.00
11000A
11000A
11000A
11000A
11000A
11000A
11000A
1225A
QJ22S225A■ 273.00
QJ23S225A
12000A
1250
FXD62S250A 1451.00
HFXD62S250A■
—
FXD63S250A 1758.00
13200A
HFXD63S250A■3060.00 13200A
CFD63S250A■5644.00 13200A
1400
JXD22S400A■1833.00 JXD23S400A 2262.00
—
—2539.00 JXD63S400A 3087.00
—
HJXD63S400A■5208.00
CJD63S400A■6434.00
1600
—
—
LXD63S600A 4442.00
18000A
HLXD63S600A■5942.00 18000A
CLD63S600A■10450.00 18000A
—
—
LMXD63S800A■5104.00 10000A
MXD63S800A5104.00
10000A
CMD63S800A11857.00 10000A
1200
—
NXD63S120A9016.00
10000A
CND63S120A■16930.00 10000A
1600
PXD63S160A13326.00
2000
RXD63S200A■14762.00 10000A
1800
886.00
Ordering Information
Order by catalog number. Switches
include frame and self protective
(except TD) trip unit only. Order lugs
separately from pages 6-70 to 6-72.
16000A
16000A
16000A
16000A
10000A
Non Automatic Molded Case Switch
TD63S2000■19413.00
—
2500
TD63S2500■21856.00
—
3200
TD63S3200■24053.00
—
4000-5000
See “SB” Type Insulated Case Breakers
CIRCUIT
BREAKERS
6
2000
Lugs pages 6/71 to 6/72
Accessories pages 6/75 to 6/80
■ Built to order. Allow 3-4 weeks for delivery.
For 2-pole application use outside poles of 3-pole circuit
breaker.
For additional lugs see pages 6-70 to 6-72.
Molded
case switches up to R frame contain a self
protecting instantaneous element, which may open
circuit above their override set point.
6/61
Molded Case Circuit Breakers
TECHNICAL
Digital Solid State Sentron Sensitrip III Series
Functions available in Sentron Sensitrip circuit breakers.
The Sentron Sensitrip III circuit
breaker is a true RMS current sensing
Cont
Long
InstanShort
device. Digital microprocessor
Trip
Current Time
taneous Time
circuitry within the electronic trip unit Catalog Number
provides more precise control over the (Description + Suffix) Type Setting Delay Setting Pick Up
Basic Unit + (A)
LI
—
circuit breaker functions. This control
Basic Unit + (A)G
LIG
—
allows circuit coordination flexibility
Basic Unit + (A)NT
LSI
not available with thermal magnetic
Basic Unit + (A)NGT
LSIG
circuit breakers.
Short
Time
Delay
Short
Time
l2t
Pick Up
Ground
Fault
Pick Up
Ground
Fault
Delay
—
—
—
—
—
—
—
—
Letter “A” is used for MD and ND Solid State frame types only.
Typical Trip Unit Labeling and Adjustment Positions for the Sentron Sensitrip Circuit Breaker.
SMD6, SHMD6, SCMD6, SND6, SHND6, SCND6, SPD6, SHPD6
SJD6, SHJD6, SCJD6, SCD6, SHLD6, SCLD6
6
CIRCUIT
BREAKERS
ln = Maximum circuit breaker ampere rating.
lr = Current Rating — a function of continuous ampere adjustment setting expressed in % of ln .
lg = Ground Fault Pickup — a function of adjustment setting expressed in % of ln .
6/62
Molded Case Circuit Breakers
TECHNICAL
Digital Solid State Sentron Sensitrip III Series
D. Adjustable “Short Time
Pick-Up” Switch (Optional)
A. Adjustable “Continuous
Amps” Rating Switch
Sensitrip III circuit breakers
with an adjustable short
time pick-up switch allow for
selection of short time
pick-up in a range from 1.5
to 10 times the setting of the
maximum current rating.
All Sensitrip III solid
state molded case
circuit breakers have an
adjustable ampere rating
switch. Adjustments made
to this switch change the
continuous current rating of
the breaker from 20% to
100% of its maximum trip
unit rating depending on the
circuit breaker frame.
E. Adjustable “Short Time
Delay” Switch (Optional)
Sensitrip III circuit breakers
with an adjustable short time
pick-up switch also contain a
switch for adjustment in time
delay. The adjustable short
time delay switch allows for
either of two modes of short
time delays. One range of
settings enables the breaker
to be set for fixed time
delays and the other range of
settings enables the breaker
to be set for short time
delays based on l2t curves.
B. Adjustable “Long Time
Delay” Switch
All Sensitrip III circuit
breakers have an adjustable
long time delay switch to
allow for selection of long
time delays of fixed time
intervals at six times the
setting of the adjustable
“continuous amps” rating
switch.
C. Adjustable “Instantaneous
Pick-Up” Switch
Sensitrip III circuit breakers
with an adjustable
instantaneous trip switch
allow selection of a tripping
point from related to the
adjusted circuit breaker
Rating (lr).
Adjustable “Ground Fault Pick-Up”
Switch
Sensitrip III circuit breakers
containing the optional equipment
ground fault protection cover the
ground fault pick-up range of 20% to
70% of the circuit breaker frame
rating. The ground fault pick-up
settings also allow for one of three
time delays based on 12t curves.
6
For 3-phase, 4-wire systems, an
external neutral transformer is
required with an ampere rating equal
to the trip unit ampere rating.
ln = Maximum circuit breaker ampere rating.
lr = Current Rating — a function of adjustment setting expressed in % of ln.
lg = Ground Fault Pick-up — a function of adjustment setting expressed in % of ln.
Examples of Adjustment Settings
In = 800
In = 800 amperes
Results
Continuous
Current Setting
Long Time
Delay Setting
Instantaneous
Setting
30
240 amperes
lr = 30% of 800
12
12 seconds trip
at 6 x 240 amps = 1440.
8
1920 amperes
8 x lr = 8 x 240
CIRCUIT
BREAKERS
Catalog Number SMD69800A
Catalog Number SMD69800ANGT
ln
lr
Setting
Long
Time
Delay
Short Time
Pick-Up
Off
Instantaneous
Setting
Short Time
Pick-Up
On
Short Time
Delay
l 2T
Set
Ground
Fault
Pick-Up
Ground
Fault
Delay
800 amperes
Results
070
560
20
20 sec.
—
—
10 lr
5600A
8 lr
4480A
.5
.5 secs
.28
.28 sec @ 4480A
40
320A
.2
.2 sec
ln
= 800 amperes.
lr
= 560 amperes (70% of 800).
Delay
= 20 seconds at 3360 amps (6 x lr).
Breaker will trip in 20 seconds with 3360
amperes.
Short
Time Pick-Up Off — Instantaneous can be used.
Instantaneous set at 10 x lr = 10 x 560 = 5600
amperes.
l2t switch on .28 seconds @ 6 x 560 = 3360 amperes.
(Inverse time)
Short
Ground Fault Pick-Up set at 40 = 40% of ln = 320
amperes. (Definite Time)
Time Pick-Up On — Set at 8 = 8 x 560 = 4480
amperes.
Short
Note:
Time Delay = .5 seconds. (Definite Time)
&
are mutually exclusive.
Ground Fault Delay set at .2 seconds. Breaker will trip in
200 milliseconds with a 400 ampere ground fault.
6/63
SB Encased System Breakers
GENERAL
800 to 5000 Ampere Frame Rating
Description
Siemens SENTRON® SB Breakers
provide maximum flexibility, with
four principal frame size envelopes:
1200, 2000, 3200, and 5000 amperes.
Applications include mains, ties, feeders,
and emergency source breakers in
industrial plants, commercial installations,
and health care facilities. SB Breakers
combine high interrupting ability
with extended short time tripping for
successful application in fully-rated
systems, while providing complete
selectivity through the applied breaker’s
short time rating. This assures the highest
possible reliability and availability from
the power distribution system.
The circuit breaker mechanism is a true
two-step stored energy system that
allows for a maximum five cycle closing
for distribution bus paralleling.
SB Breakers Exceed UL Requirements
SB Breakers comply with worldwide
industry standards and are UL Listed
and CSA certified for enclosed operation
at 100% in both fixed and drawout
mounting configurations. The robust,
self-cooling SB Breaker design requires
no additional ventilation, even when
operated at 100% of the Frame Ampere
Rating.
6
Internal Accessories
Electric Motor Operator
Local Electric Close
Auxiliary & Alarm Switches
Undervoltage Release (UVR)
Shunt Trip
Remote Open/Close & Alarm Relay
CSA / UL / IEC Symmetrical RMS Amperes Interrupting Ratings
Standard
Measurement
Voltage
AC
SB Encased Systems Breaker
Frame Amperage Rating 400
800
1200
2000
3200
4000
5000
Type SBA–Alternate A.I.R. (KA): Blue Label
240
065
065
065
085
—
—
—
480
065
065
065
065
—
—
—
600
042
042
042
050
—
—
—
150
Type SBS–Standard A.I.R. (KA): Black Label
CSA/UL
(489)
Interrupting
240
Ratings–
Symmetrical
480
RMS Amperes
600
100
100
100
100
150
150
100
100
100
100
100
100
100
050
050
050
065
085
085
085
Type SBH–High A.I.R. (KA): Red Label
240
N/A
N/A
N/A
200
200
200
200
480
N/A
N/A
N/A
150
150
150
150
600
N/A
N/A
N/A
100
100
100
100
0
0
0
0
0
0
0
Short Time Ratings
(KA)t = .5 seconds
IEC
947-2
(For SBS
Breakers
Only)
lcu
Interrupting
415 lcs
Ratingslcw
Symmetrical
lcu
RMS Amperes
690 lcs
(50HZ)
lcw
25
25
25
35
50
65
65
100
100
100
100
100
100
100
025
025
025
035
050
065
065
0
0
0
0
0
0
0
025
025
035
050
065
065
65
65
65
025
65
65
65
65
SB Frame Sizes, Ratings, Rating Plugs & Dimensions
Frame
Sizes 1200A
2000A
3200A
5000A
Frame
Ampere
Rating Rating Plugs
(Amperes)
0400
200, 225, 250, 300, 350, 400
0800
400, 450, 500, 600, 700, 800
1200
600, 700, 800, 1000, 1200
1200
600, 700, 800, 1000, 1200
2000
1000, 1200, 1600, 2000
2500
1600, 2000, 2500
3200
1600, 2000, 2500, 3000, 3200
2500
1600, 2000, 2500
3200
1600, 2000, 2500, 3000, 3200
4000
2000, 2500, 3000, 3200, 4000
5000
2500, 3000, 3200, 4000, 5000
Fixed Mounting
(H x W x D)
Moveable
Drawout Mounting
(H x W x D)
12.0 x 15.5 x 12.5
13.75 x 20.5 x 16.0
16.75 x 15.5 x 12.5
19.8 x 20.5 x 16.0
27.5 x 15.5 x 12.5
35.0 x 21.5 x 16.0
27.5 x 23.5 x 12.5
35.0 x 29.5 x 16.0
CIRCUIT
BREAKERS
External Accessories
Ground Fault Sensing and Relaying
Key Interlock and Padlock Features
Drawout Padlock and Close Blocking
Cell Switches
Drawout Safety Shutters
Secondary Disconnect & Terminal Block
T Connectors
Neutral Sensing Transformers
Lifting Device Jacket
Auxiliary Power Supply
Dead Front Shield
Trip Unit Retrofit Kits
PC and Network Communications
Consult
Siemens Sales Office for pricing and production
schedule. SB Price and Selection Guide IPPS-2209 is also
available.
6/64
Breaker
Frame Size refers to the physical breaker
envelope size.
Frame Ampere Rating is determined by the
current sensors in the breaker.
Breaker
SB Encased System Breakers
GENERAL
Electronic Trip Units
Two types of interchangeable trip units
for the SB Encased Systems Breakers
are available. The basic type “TL” Trip
Unit features a full range of industry
standard protective settings and the highperformance Systems Breaker Energy
Communicating Trip Unit (SB-EC Trip Unit)
offers advanced metering, protective
relaying, time-stamped logs, and power
quality monitoring functions, including an
integral keypad and LCD graphical display
for menu-driven system configuration and
real-time voltage and current waveform
displays. Both units offer unique models
to provide an efficient combination of
options versus cost for every application.
Interchangeable Rating Plugs
SB Breaker trip units use field
interchangeable rating plugs allowing
the effective ampere rating of the circuit
breaker to be field-modified and provides
security against indiscriminate changes in
the breaker’s ampere rating.
Advanced True RMS Current Sensing
Both the basic type “TL” and the
premium SB-EC Trip Unit feature
advanced digital-processing techniques to
measure the true heating content of the
current waveform. This True RMS value of
current measurement virtually eliminates
nuisance tripping due to the presence of
harmonics on the distribution bus.
Communications
control, including peak demand, trend
analysis, waveform analysis, and
harmonic calculations and displays.
These functions help pinpoint energy
consumption, power quality issues,
and the energy cost of any process.
Outages and potential outages can
be quickly diagnosed and plans can
be generated for expansion and
preventative plant maintenance.
Communications is accomplished via
EIA-485 twisted pair wire or modem,
providing communications to a remote
site and allowing access to multiple
plants. WinPM™ utilizes a Windows
DDE (dynamic data exchange) server
that allows data exchange to
other Windows software such as
spreadsheets and word-processors.
Protocol Converters are available from
Siemens for connection to a variety
of open and proprietary automation
protocols, including Profibus DP,
LonWorks, the Siemens S7 PLC,
and many other third party PLCs and
associated networks. The SB-EC Trip
Unit’s EIA-232 communications
port provides additional local PC
communications for available trip unit
data displays and trip unit configuration
via Siemens SBWin™ software.
6
All SB Circuit Breaker trip units
feature two levels of communication:
Zone Selective Interlocking and
ACCESS™ System Open-protocol
communications, allowing integration
into Siemens WinPM™ V4.0
supervisory software, along with
other popular third party energy
monitoring networks and components.
WinPM™ V4.0 delivers a powerful
energy management system providing
sophisticated monitoring capability to a
host computer and other components
in the electrical distribution system
at an affordable cost. It also provides
process
Robotics
CNC
PLCs
us, . . .
CIRCUIT
BREAKERS
t, ModB
viceNe
orks, De
W
n
o
L
,
P
FIBUS D
PC
PRO
Data Transfer Link
Win PM
Power Meters
Access
MT
SB
Breaker
MCCBs
6/65
SB Encased System Breakers
GENERAL
Electronic Trip Units
Frame Rating Indication:
indicates the frrame
rating of the circuit
breaker with which the
trip unit is used
SB-EC Trip Unit
Features by Model Type
Feature
6
SBxxTP01
SBxxTP01G
SBxxTP02
SBxxTP02G
Integral Keypad & Display
Voltage/Current Waveform Displays
Protective Functions
Long Time, Short Time, Instantaneous
Metering Functions
Volts, Amps, PF, Frequency, Watts, VARs,
VA, Crest Factor, Ampand Watt Demand,
Voltage and Current Waveforms, Voltage
and Current Unbalance
Communications
PC (RS-232), ACCESS (RS-485)
Counters
Breaker Test (Trip/No Trip), Mechanical
Counter, Interruption Level Fault Counter
Security
Password Protection
Event Log
Time-stamped—10 Most Recent Events
Trip Log
Time-stamped—5 Most Recent Events
Alarms
(Alarm Only) Overcurrent, Gnd.
Overcurrent, Over Amp Demand, Over
kW Over kW Demand, Phase Sequence,
Over KVAR, Over KVA, Under/Over P.F.
Advanced Alarms
Total Harmonics
—
—
Min./Max. Logs
Volt/Amp, Power, PF, Freq., %THD
—
—
Harmonic Analysis
Up to 19th Per Phase, THD
—
—
Protective Relay Functions
(Alarm and/or Trip)
Neutral Overcurrent, Current Balance,
Under/Over Voltage, Voltage Unbalance,
Reverse Power, Under/Over Frequency,
Phase Loss
—
—
Ground Fault Protection
Residual or Ground Return
—
—
CIRCUIT
BREAKERS
Wave Form Displays
The SB-EC Trip Unit offers digital
waveform sampling as a standard feature
that allows a real-time graphical view
of a complete cycle of line and neutral
currents or phase voltages, including
voltage and current phase relationships
and harmonic distortion. On-board
harmonic analysis functions are available
on premium units, allowing harmonic
analysis up to the 19th multiple and
permitting the data to be viewed and
examined on the integral LCD graphical
panel. Sampled data can also be stored
in memory and transmitted to a PC via
the serial communications port, using
Further Information
Refer to SB Encased Systems Breaker Bulletin IPPS-2209E
for additional price and catalog information. SB-EC Trip
Unit Product Bulletins are also available (IPPS-2208B,
IPFL-2207A).
6/66
Siemens WinPM™ Version 4.0 or later
or SBWin™ Software to display the
waveforms and automatically perform
harmonic analysis using Fast Fourier
transformation techniques. Both the
resident trip unit and the PC-based
harmonic analysis functions provide
the value of Total Harmonic Distortion
(THD) of the waveforms and are useful
in locating the source and severity of
harmonics and developing corrective
strategies.
Remote Operation
Remote, automatic open and close
operation of the breaker is possible
System Status
Indicators:
Yellow LED indicates
an alarm condition,
red LED indicates a trip
condition
System Check Indicators:
Two green LEDs blink to
indicate that protective
and metering systems
are working correctly
LCD Display:
provides fast,
convenient
display of
menu options
and device
status
ESC Key:
used to exit
menus
Up and Down Arrows:
for convenient
scrolling through
choices on LCD
EIA232 Serial Port:
for direct connection
to a personal
computer
Enter Key:
for selection
of choices
or moving
between
selections
Test Connector:
easy connection to
portable TS-31 test
set for functional
testing
via the trip unit’s EIA-232 or EIA-485
communication ports or a hard-wire
input. For remote operation via a
communication port, WinPM Version 4.0
or later, Shunt Trip and Remote Open/
Close Relay accessories are required
for the remote open function, and an
Electrical Operator accessory is required
in addition for both remote open and
close operations.
For remote operation via a hard-wire
input, only a Shunt Trip accessory is
necessary for the remote open function,
and an Electrical Operator is additionally
required for both remote open and
close operations.
SB Encased System Breakers
GENERAL
Electronic Trip Units
Rating Plug
Basic Type “TL” Trip Unit
Available Type “TL” Features by Model
Trip Unit Function
Catalog Number
SB T
Adjustable Continuous Current
Adjustable Long Time Delay
Adjustable Short Time Pickup
—
—
Adjustable Short Time Delay (l2T)
—
—
Adjustable Short Time Delay (Fixed)
—
—
Adjustable Instantaneous Pickup
—
—
Adjustable Ground Fault Pickup
—
—
—
Adjustable Ground Fault Time Delay (l2T) —
—
—
Adjustable GF Time Delay (Fixed)
—
—
—
Fixed Instantaneous Override
Internal Watchdog
Integral Testing Functions
—
—
Curve
Adjustments
Local Trip Indication:
Overload
Short Time
Short Circuit
Ground Fault
Access Communications Compatibility
Catalog Number Suffix
LI
LSI
LS
LIG
LSG LSIG
Fault indicators
Built-in
Test Functions
Consult Siemens Sales Office for pricing or refer to
SB Encased Systems Breaker Bulletin IPPS-2209E
for additional price and catalog information. (SB-EC
Trip Unit Product Bulletins are also available
IPPS-2208B, IPFL-2207A).
All standard trip units feature:
Integral Testing Functions
Built-in Trip Indicators
Instantaneous “Override”
Continuous Self-Diagnostic
“Watchdog”
System LED on front cover
Available protective function
adjustments include:
Continuous Current
Long Time Delay
Short Time Pickup and Delay
Instantaneous Pickup
Ground Fault Pickup and Delay
For 3 phase, 4 wire systems, order correct 4th wire
(neutral) transformer as separate item.
Expansion Plug and Multiplexer/Translator required. See
page 6-69.
Choose the appropriate function
package and catalog number as shown
below:
Example: S B 2 0 T L S G
Breaker
Frame
Ampere
Rating
Catalog
Number
Suffix
2000 ampere breaker ampere rating
with:
Adjustable Continuous Current
Adjustable Long Time Delay
Adjustable Short Time Pickup and
Time Delay
Adjustable Ground Fault Pickup and
Time
Delay Breaker Ampere Ratings:
04=400, 08=800, 12=1200,
16=1600, 20=2000, 25,=2500,
32=3200, 40=4000
Insert
appropriate breaker frame ampere rating
desgination into catalog number. See example above.
Add appropriate catalog number suffix as required. See
example above.
6/67
CIRCUIT
BREAKERS
The interchangeable trip unit system of
the SB breaker showcases the latest
advancements in microprocessor
controlled circuit protection technology.
Using the speed and power of its
microprocessor to drive sophisticated
digital sampling techniques, the SB trip
unit measures the true heating content
of the current waveform (RMS current)
hundreds of times each second,
effectively eliminating nuisance tripping
due to the presence of harmonics and
other “noise “ on the system.
6
Plug-in
Display Module
Molded Case Circuit Breakers
SELECTION
Electronic and Communications Accessories
Electronic & Display Devices
Local Display Unit
Breaker Type
Catalog Number
SJD, SLD, SMD, SND, SPD, SB, STD
LDU-100
SADU Ammeter Display Unit
1201.00
The Local Display Unit (LDU) provides a centralized read-out of all Sensitrip III and
SB ICCB breakers. The device provides a panel mountable display for all trip unit data
including phase currents and alarms for up to 32 breakers. Also communicates with
other ACCESS™ devices.
Trip Unit Test Set
Type
Catalog Number
Portable
TS31
Spare TS-31 Test Set Interconnecting Cable
TS31CABLE
12372.00
168.00
The TS-31 test set is used to test the operation of the fault protection functions of the
circuit breaker’s trip unit, including long-time, short-time, instaneous, and ground fault
by means of secondary current injections.
Sensitrip Ammeter Display Unit
Breaker Type
Catalog Number
SJD, SLD, SMD,
SADU
SND, SPD
SADURMK18
1588.00
306.00
6
The Sensitrip Ammeter Display Unit (SADU) provides real-time metering for all SentronSensitrip III Molded Case Circuit Breakers. The unit plugs directly onto the front of the
trip unit and provides displays for individual phase currents flowing through the breaker.
Additional features include Average, Demand, Ground and Unbalance Current displays,
along with impending Trip Status. Current Metering Logs, and a unique diagnostic Trip
Log that records the date, time and type of fault for the previous five breaker trips. The
device is UL and CSA certified.
The optional panel mount accessory (SADURMK18) allows easy device mounting
external from the circuit breaker, in panelboard and switchboard spaces or gutters, with
the flexibility of interior panel exterior panel, or wall mounting capability.
The 2 x 16 alphanumeric LCD display provides easy viewing of data, such as viewing all
three phase currents simultaneously.
Plug-in Mounting
Panel Mounting
•
•
•
•
Direct plug-in or Panel Mounting*
Trip Unit Powered & Battery back-up
2 x 16 LCD Alphanumeric Display*
Ammeter Diplay Functions
—
—
—
—
—
RMS Phase Currents
Average Current*
Current Demand*
Ground Current
Current Unbalance (%)*
• Breaker Status
— Normal
— Impending Trip*
• Time Stamped Trip Log (last 5)
— Time & Date*
— Trip Cause: LT, ST, GF, SC
CIRCUIT
BREAKERS
• Max Log (with date & time)
— Max Phase Current*
— Max Average Current*
— Max Ground Current*
— Max Unbalance Current*
— Max Current Demand*
* Unique Features
6/68
Molded Case Circuit Breakers
SELECTION
Communications Accessories
Multiplexor Translator
Breaker Type
Features
Cat No
SJD, SLD
SMD, SND
SPD, STD
SBA, SBS, SBH
Zone Interlocking Only
MTZ
1740.00
Full Communications
with Zone Interlocking
MTA
3876.00
The Multiplexor Translator MTZ is an interface device required in zone
selective interlock schemes. The MTA combines the zone selective
interlocking function with interface to ACCESS® Systems.
Cables & Connectors
Ribbon Cables
Breaker Type
Length
Cat No
SJD, SLD
SMD, SND
SPD, STD
SBA, SBS, SBH
06˝
08˝
12˝
18˝
24˝
EPC06
EPC08
EPC12■
EPC18
EPC24■
53.00
53.00
70.00
85.00
111.00
Telephone Cables
■ Built to order. Allow 3–4 weeks for delivery.
▲ Built to order. Allow 7–9 weeks for delivery.
Factory wired when ACCESS communications or ZSI
is ordered for the SB breaker from the factory.
Length
Cat No
SB
STD
08˝
15˝
25˝
50˝
MTCSB08 ▲
MTCSB15 ▲
MTCSB25 ▲
MTCSB50 ▲
70.00
105.00
139.00
139.00
SJD, SLD
SMD, SND,
SPD,
SBA, SBS, SBH
8˝
15˝
25˝
50˝
MTC08
MTC15
MTC25
MTC50
70.00
105.00
139.00
139.00
The Expansion Plug EP is a required isolating device to connect the breaker
with the Multiplexor Translator. It is connected to the trip unit on the
breaker with a “Ribbon Cable”, EPC08 e.g., and the Multiplexor Translator
with the “Telephone Cable” (an RJ-11 cable) MTCSB08 e.g.
Breaker
Type
Frame
Size
Mounting
Type
Cat.
No
SB ICCB and
STD
1200A,
2000A
Fixed
EPSBFMK■
187.00
Draw out
EPSBDMK■
187.00
SB ICCB and
STD
3200A,
5000A
Fixed
EPSB4FMK ■
187.00
Drawout
EPSB4DMK■
187.00
Sensitrip
ALL
ALL
EP
187.00
6
Expansion Plug Selection Guide
Component Selection Guide Trip Units and Application
Component
Type
ZSI (only)
with
Sensitrip
MCCB’S
Access
and/or
ZSI with
Sensitrip
MCCB’s
ZSI (only)
with all
SB-EC
Trip Units
ACCESS
ACCESS
and/or
with
SB-TL
Trip
Units
ACCESS
with
SB-EC
Trip
Units
EP
✓
✓
EPSB
—
—
—
—
—
✓
✓
MTZ ✓
—
—
✓
—
—
MTA —
✓
—
✓
—
EPC Cable
✓
✓
—
—
—
MTC Cable ✓
✓
—
—
—
MTCSB Cable
—
—
✓
✓
—
When ordered with circuit breaker from the factory.
One MTA or MTZ per eight trip units when required.
Always required when multiple MT’s are used. One
additional cable per each additional MT.
6/69
CIRCUIT
BREAKERS
ACCESS™ Communications
All SB Circuit Breaker trip units feature two levels of
communication: Zone Selective Interlocking and ACCESS™
System Open-protocol communications. The SB-EC Trip Unit is
fully equipped for direct integration into ACCESS™ or compatible
communication systems.
A multiplex/Translator (MTA) and Expansion Plug area required
for the TYPE “TL” trip unit when full Access™ communications is
specified. The MTA also has Zone Selective Interlocking capability.
Refer to Bulletin IPIM-2211A and Instruction Sheet Pc. No.
411152A00 for additional information.
Siemens WinPM™ V4.0 supervisory software delivers a powerful
energy management system providing sophisticated monitoring
capability to a host computer and other components in the
electrical distribution system at an affordable cost. It also provides
process control, including peak demand, trend analysis, waveform
analysis, and harmonic calculations and displays. These functions
help pinpoint energy consumption, power quality issues, and the
energy cost of any process. Outages and potential outages can be
quickly diagnosed and plans can be generated for expansion and
preventative plant maintanence. Refer toBulletins IPIM-2211A for
additional information.
Communications is accomplished via EIA-485 twisted pair wire or
modem, providing communications to a remote site and allowing
access to multiple plants. WinPM™ V4.0 utilizes a WIndows
DDE (dynamic data exchange) server that allows data exchange
to other Windows software such as spreadsheets and wordprocessors.
Protocol Converters are available from the Siemens ACCESS group
for connection to a variety of open and proprietary automation
protocols as part of the ACCESS™ product line, including Profibus
DP, LonWorks, the Siemens S7 PLC, and many other third party
PLCs and associated networks.
The SB-EC Trip Unit’s EIA-232 communications port provides
additional PC communications for available trip unit data displays
and trip unit configuration via Siemens SBin™ software.
Breaker Type
Lug Information
SELECTION
Mechanical Lug
For Use
With Type(s)
Circuit Breaker
Ampere Rating
Cables Per
Lug
Lug Wire Range
Catalog
Number
15–40
1
1
#14–#6 AWG Cu
#12–#6 AWG Al
TC1Q1 (Pkg. of 6)
13.90
50–100
1
1
#8–#1 AWG Cu
#6–#1/0 AWG Al
TA1Q1 (Pkg. of 6)
12.20
Line Side
BQ, BQH,
Load Side
BQHF,
BQE,
15–20
1
1
#14–#10 AWG Cu
#12–#10 AWG Al
BQF,
BL, BLH,
25–35
1
1
#14–#6 AWG Cu
#12–#6 AWG Al
HBL,
HBQ
40–50
1
1
#8–#6 AWG Cu
#8–#4 AWG Al
Switching
Neutrals
55–70
1
1
#8–#4 AWG Cu
#8–#2 AWG Al
BG
BLG
80–100
1
1
#4–#1/0 AWG Cu
#2–#1/0 AWG Al
110–125
1
1
#2–#1/0 AWG Cu
#1/0–#2/0 AWG Al
Lugs are integral to
Circuit Breaker
Line Side (CQD, CQD6) & Load Side
BQD, CQD
BQD6, CQD6
NGG
1
#14–#6 AWG Cu
#12–#6 AWG Al
Integral
45–100
1
#8–#1 AWG Cu
#6–#1/0 AWG Al
Integral
15–40
1
#12–#6 AWG Al
50–100
1
110–125
1
15–40
15–125
—
#14–#6 AWG Cu
TC1Q1 (pkg. of 6)
13.90
#8–#1 AWG Cu
#6–#1/0 AWG Al
TA1Q1 (pkg. of 6)
12.20
#6–#1/0 AWG Cu
#4–#2/0 AWG Al
3TA1GG20 (pkg. of 3)
12.00
NUT KEEPER PLATE
6
CIRCUIT
BREAKERS
Note:
(A) Molded case circuit breakers having a rated ampacity
of 125 amperes or less are to be connected with 60 or
75°C wire. Circuit breakers having a rated ampacity
greater than 125 amperes shall only be cabled with
75°C cable unless otherwise indicated on the circuit
breaker label. Exceptions to this rule are outlined in the
2002 National Electrical Code and Canadian Electrical
Code.
6/70
Lug
is steel.
in package of six.
on load side only.
One nut keeper plate is required with each lug on the
NGG breaker.
Sold
Use
TNKG3 (Pkg. of 3)
16.00
Lug Information
SELECTION
Aluminum Body Lugs for Copper or Aluminum Wire
For Use
With Type(s)
Circuit Breaker
Ampere Rating
QJ2, QJH2
QJ2H, HQJ2H
60–225
1
#6 AWG–300 kcmil (Cu)
#4 AWG–300 kcmil (Al)
15–25
1
#14–#10 AWG (Cu)
#12–#10 AWG (Al)
SA1E025
30–100
1
#10–#1/0 (Cu or Al)
LN1E100
110–125
1
#3-3/0 (Cu)
#1-2/0 (Al)
TA1E6125
30–60
1
#10–4 (Cu or Al)
LD1E060
(Load Side)
3.60
70–100
1
#4–#1/0 (Cu or Al)
LD1E100
(Load Side)
3.50
FXD6-A, FD6-A,
HFD6,
CFD6
HHFD6
70–250
1
#6 AWG–350 kcmil (Cu)
#4 AWG–350 kcmil (Al)
TA1FD350A
19.80
SJD6(A),
SHJD6(A)
SCJD6
65-200
1–2
#4 AWG–310 kcmil (Cu or Al)
TA2J630
19.80
JXD2(A), JXD6(A),
JD6(A), SJD6(A),
HJD6(A),
HHJXD6, HHJD6,
SHJD6(A), CJD6,
SCJD6
200–400
1–2
3/0–500 kcmil (Cu)
4/0–500 kcmil (Al)
TA2J6500
28.00
LXD6(A), LD6(A),
SLD6(A), HLD6(A),
HHLXD6, HHLD6,
SHLD6(A), CLD6,
SCLD6
250–600
1–2
3/0–500 kcmil (Cu)
4/0–500 kcmil (Al)
TA2J6500
28.00
500–600
1–2
250–500 kcmil (Cu or Al)
TA2K500
64.00
700–800
1–3
1/0–500 kcmil (Cu or Al)
500–750 kcmil (Cu or Al)
TA3K500
TA2N750
87.00
250–500 kcmil (Cu or Al)
2TA4P8500 3TA4P8500 522.00
754.00
250–500 kcmil (Cu or Al)
2TA4N8500 3TA4N8500 526.00
762.00
LMD6, LMXD6,
HLMD6,
HLMXD6, MD6,
MXD6, SMD6,
HMD6, HMXD6,
SHMD6, CMD6,
SCMD6
Catalog
Number
TA1Q300 (pkg of 3)
12.00
3.50
3.50
10.90
6
CED6
All 1 pole
ED, HED
Lug Wire Range
ND6,
NXD6, SND6,
HND6, HNXD6,
SHND6, CND6,
SCND6
800–1200
PD6, HPD6,
CPD6
PXD6,
HPXD6,
SPD6,
SHPD6
1200–1600
1–5
300–600 kcmil (Cu or Al)
TA5P600
286.00
PD6, PXD6,
HPD6, HPXD6,
SPD6, SHPD6,
RD6, RXD6,
HRD6, HRXD6, STD
1200–2000
1–6
300–600 kcmil (Cu or Al)
TA6R600
302.00
Use
TA2K500 or TA3K500 only.
for 100% rated MD/ND frame breakers.
Used
1–4
Contains
Contains
CIRCUIT
BREAKERS
All 2, 3 pole
ED2, ED4, ED6,
ED6 ETI,
HED4,
Cables Per
Lug
2 connectors plus 1 NDTS end barrier.
3 connectors plus 1 NDTS end barrier.
6/71
Lug Information
SELECTION
Optional Mechanical Lugs
For Use
With Type
QJ2, QJH2,
QJ2H, HQJ2H
ED, HED 2&3 pole
HFD6, HHFD6,
CFD6, F(X)D6-A
J(X)D2(A), J(X)D6(A),
HJD6(A), HHJD6,
SHJD6(A), L(X)D6(A),
HHLD6, SCD6,
HLD6(A), SHLD6(A),
CJD6, CLD6, SCJD6,
SCLD6
Circuit Breaker
Ampere Rating
Cables Per
Lug
Lug
Material
Lug Wire Range
Qty per
Cat. #
Catalog
Number
60–225
1
Cu
#6 AWG–250 kcmil (Cu)
1
TC1Q250
28.50
2–3 pole 30-125
1
Cu
#10–#1/0 (Cu)
1
TC1ED6150
30.00
70–250
1
Cu
#6 AWG–350 kcmil (Cu)
1
TC1FD350
31.00
1
1–2
Cu
3/0–600 kcmil (Cu)
3/0–500 kcmil (Cu)
1
1
TC1J6600 TC2J6500 69.00
68.00
500–750 kcmil (Al)
500–600 kcmil (Cu)
1
TA1L6750
68.00
SMD6, M(X)D6,
HM(X)D6, HMD6,
CMD6, SCMD6, SND6,
N(X)D6, HN(X)D6,
SHND6, CND6, SCND6
500–600
800–1200
1–3
Al
R(X)D6, HR(X)D6
P(X)D6, HP(X)D6,
CPD6, SPD6, SHPD6
1600–2000
1–5
Cu
#1 AWG–500 kcmil (Cu)
#1 AWG–350 kcmil (Cu)
500–750 kcmil (Cu)
500–750 kcmil (Al)
500–750 kcmil (Cu)
500–750 kcmil (Al)
300–600 kcmil (Cu)
1
1
2
3
2
3
1
TC2K500
TC3K350
2TA2N8750
3TA2N8750
2TA3N8750
3TA3N8750
TC5R600
107.00
135.00
327.00
459.00
517.00
744.00
381.00
1200–1600
1–4
Al
600–750 kcmil (Cu/Al)
1
TA4P750
216.00
250–600
700–800
1
1
Al
1–2
1–3
Cu
Cu
1–2
Al
Compression Lugs
For Circuit Breaker Types
Lugs (contains indicated number of lugs and necessary hardware per kit)
ED2, ED4, ED6, HED4, CED4
Ampere
Rating
15–125
QJ2, QJH2, QJ2-H
125–225
F(X)D6-A, HF(X)D6, HHF(X)D6, CFD6
125–250
JXD2-A, J(X)D6-A, HJ(X)D6-A, HHJ(X)D6-A, CJD6, SJD6-A, SHJD6-A,
200–600
SCJD6, L(X)D6-A, HL(X)D6-A, CLD6, SLD6-A, SHLD6-A, SCLD6
Kits (contain lugs and hardware for complete line or load end of 2 or 3 pole breaker)
500–800
N(X)D6, HN(X)D6, CND6, SND6, SHND6, SCND6
900–1200
6
M(X)D6, HM(X)D6, CMD6, SMD6, SHMD6, SCMD6
CIRCUIT
BREAKERS
Used
for 100% rated JD/LD frame circuit breakers.
6/72
Poles
Lugs
Per Kit
Lug Wire
Size
Catalog
Number
1, 2, 3
1
#2/0
2, 3
2, 3
1
1
350 kcmil
350 kcmil
CCE125
CCQ225
CCF250
24.00
45.50
45.50
2, 3
1
500 kcmil
CCL600
134.00
2
3
2
3
6
9
8
12
500 kcmil
CCM800K2
CCM800K3
CCN1200K2
CCN1200K3
649.00
945.00
851.00
1246.00
Molded Case Circuit Breakers
SELECTION / GENERAL
Modifications
Modifications
50°C Ambient Calibration — Not UL listed and not available for solid state, 100% rated breakers or
400HZ calibrated breakers.
For BL Type Circuit Breakers
— Add suffix ‘M’ to catalog number (Example: B120M)
For BQ, QJ2, and ED Frame Circuit Breakers
— Replace ‘B’ in catalog number with ‘M’ (Example: BQ3M060, QJ23M200, ED63M060)
For FD, JD, LD, LMD, MD, ND, PD, and RD Frame Circuit Breakers
Non-Interchangeable Trip (3–pole only)
— Replace ‘B’ in catalog number with ‘M’ (Example: FXD63M225, JXD63M400)
Interchangeable Trip (trip unit only, 3–pole only)
— Replace ‘T’ in catalog number with ‘W’ (Example: FD63W200, JD63W400)
400 HZ Calibration
UL Listed (5KA IR)
For BQ, BL, and QJ Type Circuit Breakers (200A max.)
— Add suffix ‘Y’ to catalog number
Not UL Listed
For all other Circuit Breakers — Add suffix ‘Y’ to catalog number
Fungus Proofing — In accordance with MIL-T-152.
All BQD, CQD, NGG, ED, FD, JD, LD, LMD, MD, ND, PD, and RD, Frame Circuit Breakers are
inherently fungus resistant and do not require special treatment.
Fungus proofing in accordance with MIL-T-152
For BL, and BQ Type Circuit Breakers
— Order must be placed directly with the factory by the sales office.
For all other Circuit Breaker Types
— Order must be placed directly with the factory by the sales office.
Certificate of Compliance
Certificate of compliance testing must be performed on the actual device being shipped. The
certificate cannot be provided after initial shipment. Order for devices with COC requirement must
be placed directly with the factory by the sales office.
UL 489 Supplement SB Naval Use Breakers
Ordering Information
Breakers tested to UL 489 Supplement SB are qualified for use
on non combat and auxiliary naval vessels.
For “NAVAL” label, order must be placed directly with the
factory by Siemens Sales Office.
6
A variety of internal and external
accessories, as well as modifications,
are available to adapt Siemens circuit
breakers to special installation
requirements. UL listed internal
accessories for 100 through 2000A
circuit breakers are field-addable.
Internal accessories fine tune an
electrical distribution system,
allowing control of the circuit breakers to
meet special application requirements.
For example, emergency situations may
dictate tripping critically placed circuit
breakers quickly. Shunt trips accomplish
this conveniently and efficiently.
Or, when voltage drops are a concern,
undervoltage trips automatically open
the circuit breaker at a predetermined
voltage level.
A wide range of external operating and
mounting accessories is also available.
For example, face, shallow, and back
mounting plates are ideal for tailoring BQ
circuit breakers to OEM applications.
A complete line of operating handles
and handle-blocking devices meet
switchboard, enclosure and safety needs.
Plug-in mounting assemblies, which
simplify switchboard mounting of circuit
breakers and permit breaker removal
without disconnecting bus or cable
connections, are available.
Supplement SB testing comprises two sets of vibration tests.
The first is to find mechanical resonances in the product and
to subject the breaker to extreme testing at each resonant
frequency. The second is a swept frequency test, in which the
frequency of excitation is changed in intervals of 1Hz, and held at
each frequency for five minutes. The excitation frequencies run
from 4 to 33Hz, and the test is conducted in each of the three
orthogonal axes of the breaker.
During these tests, the breaker must not trip from the closed
position, nor may the contacts touch from the open position.
Calibration and insulation resistance are also verified during the test.
For detailed information, refer to UL 489, Supplement SB.
Types
ED2, ED4, ED6, HED4
CED6
FD6, FXD6, HFD6, HFXD6
CFD6
JXD2, JD6, JXD6, LXD6, LD6,
HJD6, HJXD6, HLD6, HLXD6
HHJD6, HHJXD6, HHLD6, HHLXD6
CJD6, CLD6
MD6, MXD6, HMD6, HMXD6, CMD6,
ND6, NXD6, HND6, HNXD6, CND6
PD6, PXD6, HPD6, HPXD6, CPD6,
RD6, RXD6, HRD6, HRXD6
SBA400, SBS400, SBA800,
SBS800, SBA1200, SBS1200,
SBA1600, SBS1600, SBA2000, SBS2000
UL File
E10848, Vol 4, Sec 11
E10848, Vol 4, Sec 13
E10848, Vol 4, Sec 17
E10848, Vol 4, Sec 18
E10848, Vol 4, Sec 8
E10848, Vol 4, Sec 20
E10848, Vol 4, Sec 14
E10848, Vol 4, Sec 15
E10848, Vol 4, Sec 19
E9896, Vol 15, Sec 1
6/73
CIRCUIT
BREAKERS
Siemens’ molded case breakers from the ED frame through the
2000 Amp SB frame can be labeled “Naval” in compliance with
Supplement SB.
Molded Case Circuit Breakers
GENERAL / SELECTION
Internal Accessories
Feature Combinations
The available feature combinations are shown in the chart below. For applications requiring combinations of features not listed in this
chart, consult the sales office for availability.
Breakers
Avail. On
ST/
Modules/ Breaker
ST/ ST/
AUX/
UVT/
Breaker Poles
ST AUX ALSW ALSW UVT AUX
UVT/
UVT/ ST/
ALSW ALSW
AUX/
ALSW
AUX
Elect.
Bell
Ground Grd fault
ALSW Alarm fault
w/Bell
QP, BQ, BL
1
1, 2, 3
1
—
—
—
—
—
1
—
—
—
—
—
BQD, CQD, NGG
1
2, 3
1
1/1
—
—
—
—
1
1/1
1
—
—
—
QJ
1
3
1
1/1
—
—
—
—
2
—
—
—
—
—
All ED, EF
1
1, 2, 3
1
1/1
1/1
1/1/1
1
1/1, 1/2
1/1
1/1/1
1, 2
1/1, 2/1
1
—
1
1
All FD, FF
2
2, 3
1
—
—
—
1
1
—
—
1, 2
1/1
1
—
—
—
All JD, LD, LMD
2
2,3
1
1
—
—
1
1/1, 1/2
—
—
1, 2
—
1, 2
—
—
—
1
3
1
1
—
—
1
1/1, 1/2
—
—
1, 2
—
1, 2
—
—
—
2
2,3
1
1/1
—
—
1
1/1, 1/2
—
—
1, 2
1/1, 2/1
1, 2
—
—
—
—
1
1
—
—
SJD6, SHJD6, SCJD6,
SLD6, SHLD6, SCLD6
All MD, ND, PD, RD
Including Electronic
trip
1 NC / 1 NO,
2 NC / 2 NO,
STD
6
3
1
—
—
—
1
—
—
—
3 NC / 3 NO,
4 NC / 4 NO,
5 NC / 5 NO
Shunt Trip (ST)
6
One or all critical circuit breakers may
be tripped from a distant control point
by use of a shunt trip device. A shunt
trip operates through an auxiliary switch
contact; when the breaker opens, current
is not maintained on the shunt trip coil.
Undervoltage Trip (UVT)
CIRCUIT
BREAKERS
When voltage drops to a value below 35%
of the nominal coil rating, the undervoltage
trip device automatically opens the breaker.
The operation is instantaneous, and the
circuit breaker cannot be reclosed until the
voltage returns to 85% of line voltage. The
undervoltage trip, which is continuously
energized, must be energized before the
circuit breaker can be closed.
Auxiliary Switch (AUX)
For applications requiring remote “on” or
“off” indication (or electrical interlocking),
auxiliary switches are available. Each
switch comprises an “A” (open when
circuit breaker is open) and a “B” (closed
when circuit breaker is open) contact with
a common connection. (Form C)
For ED Frames
Factory
assembled only
mechanical interlock is installed, no accessory module
can be installed in the right pocket.
If
6/74
For FD Frames
If
mechanical interlock is installed, no accessory module
can be installed.
If mechanical interlock is installed, no accessory module
can be installed in the left pocket.
Alarm Switch (ALSW)
The alarm switch contact is closed when
the circuit breaker is opened automatically
by an overload, short circuit, shunt trip or
undervoltage trip. The alarm switch contact
is open when the circuit breaker is reset.
For JD and LD Frames
One
module per column.
Molded Case Circuit Breakers
SELECTION
External Accessories
Handle Ties
Provide simultaneous switching of 2 adjacent handles. Do not provide common trip.
For Use With
Breaker Frame(s)
Catalog
Number
Standard
Package
Wt Lb/
Std Pkg
BQ, BQH, HBQ, B6, BLH, HBL (2 Pole)
QTH3
50
BQXD,
BQ, BQH, HBQ, BL, BLH, HBL
ECQLD3
10
1
One pole BL, BLF, BE, BAF
ECPLD1
10
1
Two-pole BL, BLF nad BE
ECPLD2
10
1
All QJ
HL9419
10
1
All BQD, CQD
BQDPLD
1
1
All ED
ED2HPL
1
1
All FD
FD6PL1
1
1
All JD, LD, LMD
JD6HPL
1
1
All MD, ND, PD, RD
MN6PLD
1
1
STD
STDPLD ■
1
1
1
⁄4
Padlocking Devices
For locking breaker in “OFF” position.
ECQTH3
⁄4
⁄4
⁄4
⁄4
⁄8
⁄4
⁄4
⁄4
⁄4
FD Padlocking
Device
FD6PLI
Filler Plates
BQ, BQH, HBQ, BL, BLH, HBL
QF3-UL
1
Padlocking
Device
ECQLD3
1
⁄4
Handle Blocking Devices
For holding breaker in “ON” or “OFF” position. Not a lockout/tagout device.
BL, BLH, HBL, BQXD,
BQ, BQH, HBQ
QL1
25
1
QJ2, QJH2, QJ2H, HQJ2H
QJHS1
25
1
All BQD, CQD, NGG
BQDHBD
1
1
All ED
E2HBL
1
1
All FD
FD6HB1
1
1
All JD, LD, LMD
JD6HBL
1
1
All MD, ND, PD, RD
MN6BL
1
1
⁄4
⁄4
Filler Plate
QF3-UL
⁄4
⁄2
⁄2
6
⁄2
Handle Extensions
All MD, ND, PD, RD
EX11
1
2
STD
EXSTD■
—
—.00
Replacement Terminal Cover
NGG
RTCG3
10
1
⁄4
FD Handle
Blocking Device
FD6HB1
Handle
Blocking Device
ECQL1
Handle
Extension
EX11
■ Built to order. Allow 2–3 weeks for delivery.
Sold only in standard package quantities.
6/75
CIRCUIT
BREAKERS
For replacement. One extension shipped with breaker.
Molded Case Circuit Breakers
SELECTION
External Accessories
Mounting Clips
For Use With
Breaker Frame(s)
Number of
Poles
Catalog
Number
BQ, BQH
1
MB120
Standard
Package
20
Wt Lb
Std Pkg
1
⁄4
MB120
Face Mounting Plates
10
10
10
BQ, BQH, BQXD
1
2
3
FP9508
FP9555
FP9556
CQD, CQD6
1
2
3
CQDFMB1
CQDFMB2■
CQDFMB3■
BQ-GFCI
1
FP9558■
NGG
1
2
3
FMPG1
FMPG2
FMPG3
1
⁄2
1
11⁄2
1
1
1
1
⁄4
⁄4
⁄4
1
1
10
Face Mounting Plates
FP9558 FP9508 FP9555 FP9556
1
1
1
1
1
⁄4
⁄4
1
⁄4
1
Shallow Mounting Brackets
BQ, BQH
SMB6
30
11⁄2
2
3
4
BR2
BR3
BR4
10
10
10
1
1
E2BMB
1
1
1–6
Back Mounting Plates
BQ, BQH, BQXD
ED2, ED4, ED6, HED4
SMB6 (6 shown)
⁄4
Mounting Screw Kits
6
CQD, CQD6
CQDSMK 1
MSE6 MSE6100 1
100
1
All ED (CED6 requires 2 kits)
NNG
MSKG2
1
1
1
1
All QJ
MSQJ
All FD (CFD6 requires 2 kits)
MSF6 MSF650 All JD, LD
11⁄4
⁄4
1
MSJ6 1
1
All LMD
MSLMD
1
1
All MD, ND,
MSMN
1
1
All PD, RD
MSPR6
1
2
⁄4
1
⁄4
⁄4
⁄4
CIRCUIT
BREAKERS
Mounting Screw Kit
MSE6
“MI” Mechanical Interlocks
For Use With
Breaker Type(s)
Panel
Mounted
Plug-in
Mounted
BQ
—
QML12
10
1
All QJ
CSO
—
1
1
All FD
MI5444
MI5444
Complete with
two breakers
—
All JD, LD
MI5413 —
1
1
All LMD
MI5406 —
1
1
All MD
MI5404 ■
—
1
3
All ND
MI5404 ■
—
1
3
All PD, RD
MI5405▲
MI5405▲
—
—
STD
STDMIF32▲
—
—
—
6/76
Back Mounting
Plate BR2
⁄4
1
1
50
■ Built to order. Allow 2–3 weeks for delivery.
▲ Built to order. Allow 6–8 weeks for delivery.
Note: CSO = Consult Sales Office
Kit consists of 4 screws and washers.
Consists of 1 screw and washers (order 100).
Consists of 1 screw and washers (order 50).
With mechanical interlock in place, no accessory can be
QML12
⁄4
1
⁄4
1
⁄4
Standard
Package
Wt Lb
Std Pkg
⁄4
installed into circuit breaker right pole.
of the mechanical interlock will prevent
accessory installation in the left pole.
Sold only in standard package quantities. Multiply List
Price Each times package quantity for full price.
Addition
Mechanical Interlock
MI5444
Each package contains 5 strips of 6 each. Each strip can
be broken at perforations for 1, 2 or 3-pole use.
Mechanical interlock is not designed for use within
Siemens panelboards.
Molded Case Circuit Breakers
SELECTION
External Accessories
Rotary Door Mounted Operating Handles
Types 1, 3, 3R , 12, 4 4X
For Use
With
Breaker
Frames
Complete Mechanism
Handle Only
Breaker Operator
Shaft Only
Catalog Number
Standard
Depth
Variable
Depth
ED
CRHOESD
CRHOEVD
FD
CRHOFSD
CRHOFVD
JD, LD
CRHOJSD
CRHOJVD
LMD
CRHOLMSD
CRHOLMVD
MD, ND
PD, RD
RHONSD
RHONVD
Catalog
Number
Catalog
Number
RHOEBO 68.00
RHOFBO117.00
CRHOH
RHOJBO
RHOLMBO
RHONBO214.00
RHOH
Length Catalog
(inches) Number
2
RHOSSD
28.00
12
RHOSVD
28.00
16
RHOSXD
28.00
3
12
24
RHONSSD▲ 86.00
RHONSVD
86.00
RHONSXD 114.00
CRHOH
RHOH
For 3 or 3R, order shaft and breaker operator as shown, and handle RHOH. For 4 & 4X, order handle RHOH4.
Rotary Door Mounted Operating Handles
Types 1 & 12
Standard Depth
Variable Depth
Catalog
Number
Catalog
Number
CQD, NGG
—
RHOCQVD
130.00
ED
D11CEU1
D11CEU2
163.00
FD
D11CFU1▲
D11CFU2
214.00
JD, LD, LMD
—
D11CJU2
303.00
For Use With
Breaker Frames
D11CEU2
Through Door Mounted Operating Handles
Types 1 & 12
Variable Depth
For Use With
Breaker Frames
Catalog
Number
Catalog
Number
CQD, NGG
FMHOS
—
QJ
OH9498 ■
VH9499
195.00
ED
E2RH1
E2RHV9
197.00
FD
F6RH1
F6RHV9
197.00
Standard
Depth
F6RH1
6
Rotary Door Mounted
Operating Handles
Standard Depth
Type
Catalog Number
Right Hand
Catalog Number
Left Hand
2 point latch
DKR2
DKL2■
302.00
3 point latch
DKR3
DKL3■
337.00
CIRCUIT
BREAKERS
Door Latch Kits
Variable Depth
F6RHV9
■ Built to order. Allow 3–4 weeks for delivery.
▲ Built to order. Allow 7–9 weeks for delivery.
For use on 3-pole ED frame only.
6/77
Molded Case Circuit Breakers
SELECTION
External Accessories
Max-Flex™, Flange Mounted Variable Depth Operators
Complete Kit
Handle Only
Breaker Operator
36˝ Cable
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
Frames
NEMA
Type
ED
1, 3(R),
12
FHOE036 563.00
FHOH 282.00
4(X)
—
FHOH4386.00
1, 3(R),
12
FHOF036 625.00
FHOH 282.00
4(X)
—
FHOH4386.00
1, 3(R),
12
FHOJ036 664.00
FHOH 282.00
4(X)
—
FHOH4386.00
1, 3(R),
12
FHOLM036
FHOH 282.00
4(X)
—
FHOH4386.00
FHON048 857.00
FHOHN 421.00
FD
JD, LD,
SJD, SLD
LMD
1, 3(R),
MD, ND,
12
PD, RD,
SMD, SND,
4(X)
SPD
FHOEBO
Cable
Handle
FHOEC036
Breaker Operator
—
FHOFBO
FHOFC036
Max Flex ™
FHOJBO
FHOJC036
FHOLMBO
FHOJC036
FHONBO
FHONC048
FHOHN4563.00
Max-Flex™ handles are available with solid black handles instead of the customary “red for on” flange handle. These are
preferred for use in IECmarkets, where red handles have specific meaning. Order componenets separately, apppending the
letter “i” to the catalog number (e.g. FHOHI).
Alternate Length Cable Only
ED
Inches
048
060
072
084
096
120
144
FD
Catalog
Number
JD/LD/LMD
Catalog
Number
FHOEC048 162.00
FHOEC060 181.00
FHOEC072 200.00
FHOEC084▲223.00
FHOEC096 246.00
FHOEC120▲336.00
FHOEC144▲373.00
MD/ND/PD/RD
Catalog
Number
FHOFC048 172.00
FHOFC060 194.00
FHOFC072 214.00
FHOFC084▲ 236.00
FHOFC096 256.00
FHOFC120 336.00
FHOFC144▲ 373.00
Catalog
Number
FHOJC048 187.00
FHOJC060 214.00
FHOJC072 246.00
FHOJC084▲ 248.00
FHOJC096 336.0
FHOJC120▲ 365.0
FHOJC144▲ 379.00
FHONC048 212.
FHONC060 46.0
FHONC072 286.
FHONC084▲
FHONC096
FHONC120▲
FHONC144▲
6
Handle Auxiliary Switch
For use with Max-Flex and Rotary Door operators (FHOH and RHOH). 1 NO and 1 NC contact.
For Use With
Catalog Number
ED, JD, LD, LMD, ND, PD, RD, SD, Max Flex
HAS1
167.00
CIRCUIT
BREAKERS
Fixed Depth Flange Mounting
Frames
ED
Minimum
Enclosure
Depth
6.44
FD
6.44
Left Hand Mount
Right Hand Mount
NEMA
Type
Catalog Number
Catalog Number
1, 3R, 12
FDFBEL▲
246.00 FDFBER▲
246.00
4, 4X
FDFBEL4▲
329.00 FDFBER4▲
329.00
1, 3R, 12
FDFBFL▲
263.00 FDFBFR▲
263.00
4, 4X
FDFBFL4▲
349.00 FDFBFR4▲
349.00
Max-Flex™ handles are available with solid black handles instead of the customary “Red for On” flange handle. These are
preferred for use in IECmarkets, where red handles have specific meaning. Order componenets separately, apppending the
letter “i” to the catalog number (e.g. FHOHI).
FDFBFR
▲ Built to order. Allow 7–9 weeks for delivery.
For 1- or 2-pole breaker order FHOED036 complete kit or
FHOEDBO breaker operator only.
6/78
48
inch cable is standard length for M through R frame
Max-Flex operators.
Molded Case Circuit Breakers
SELECTION
External Accessories
Telemand® Motor Operator
Breaker Frame
AC
Voltage
Hinged to
Open Down
List
Price $
ED except CED
120
MOE6120
3018.00
240
MOE6240 ▲
3284.00
ED motor operator opens downward.
Breaker
Frame
DC
Voltage
Hinged to
Open Right
AC
Voltage
Hinged to
Open Right
FD
24
48
125
MOF6024DC▲
MOF6048DC▲
MOF6125DC▲
120
240
3—
MOF6120
MOF6240
—296.00
3083.00
3465.00
JD, LD
24
48
125
MOJ6024DC▲
MOJ6048DC▲
MOJ6125DC▲
120
240
—
MOJ6120
MOJ6240
—
3989.00
3989.00
LMD
24
48
125
MOLMD6024DC▲
MOLMD6048DC▲
MOLMD6125DC▲
120
240
—
MOLMD6120
MOLMD6240
—
3989.00
3989.00
MD, ND,
PD, RD
—
—
—
—
120
240
MOMN6120
MOMN6240
4505.00
4505.00
To order FD through RD motor operators with Left side hinges, add “L” to catalog number (e.g. MOF6120L).
List prices are the same.▲
FD, JD, LD, LMD, MD, ND, PD, RD
Frames
Dimensions
Frame
B
C
D
E
ED
A
7.04
4.31
—
4.31
13.84
F
8.84
FD
9.50
4.55
1.60
6.84
9.70
7.58
JD, LD, LMD
11.00
7.50
0.79
8.34
9.85
7.74
MD, ND, PD, RD
16.00
9.00
—
9.83
13.13
10.13
Operating Currents
MOE6120
MOE6240
10.25
5.2
MOF6120/L
MOF6240/L
Off
Running
(Amps)
Time
(msec)
In-Rush
(Amps)
Running
(Amps)
Time
(msec)
Reset
(Amps)
2.3
1.1
550
500
10.0
5.0
2.3
1.0
400
330
2.3
1.1
10.0
4.7
5.5
2.5
200
200
10.0
4.7
5.5
2.5
175
185
5.5
2.5
MOLMD6120/L
15.2
6.0
210
15.2
6.0
185
6.0
MOJ6120/L
MOJ6240/L
15.2
5.0
6.0
2.5
210
217
15.2
5.0
6.0
2.5
185
185
6.0
2.5
MOMN6120/L
MOMN6240/L
22.7
12.6
13.9
4.6
240
260
22.7
12.6
13.9
4.6
210
230
13.9
12.6
Front View
CIRCUIT
BREAKERS
In-Rush
(Amps)
6
On
Catalog
Number
Bottom View
For inches / millimeters conversion, see Application Data section.
▲ Built to order. Allow 7–9 weeks for delivery.
6/79
Molded Case Circuit Breakers
SELECTION / DIMENSIONS
External Accessories
Plug-In Mounting Assemblies, Including Base and Tulip Assemblies
Catalog
Number
PC2658 158.00
2
PC2637▲ 98.00
PC2638▲98.00
3
PC2657 158.00
PC2658 158.00
2
PC4753▲237.00
PC4753▲237.00
3
PC4754 309.00
PC4754 309.00
2
PC4753▲237.00
PC4753▲237.00
3
PC4754 309.00
PC4754 309.00
All JD
except CJD
2
PC5777▲318.00
PC5777▲318.00
3
PC5778 527.00
PC5778 527.00
All FD
except CFD
CFD
PL2617
PL4762
PL4763
PL5796
Kit CJD, SCJD
3
PCCJD 570.00
PCCJD 570.00
All LD
except CLD
2
PC5660▲596.00
PC5660▲596.00
3
PC5661 835.00
PC5661 835.00
Kit CLD, SCLD
3
PCCLD 769.00
PCCLD 769.00
2
PC5662▲1098.00
PC5662▲1098.00
3
PC56631341.00
PC56631341.00
2
PC5664▲1516.00
PC5664▲1516.00
3
PC5666 1748.00
PC5666 1748.00
All ND
PL5696
PL5797
PL9698
PL9699
Tulip Assemblies Separately
2 Pole
3 Pole
For
Frame
Catalog
Number
Catalog
Number
ED
TCE2▲
TCE3▲
184.00
FD
TCF2▲
TCF3▲
275.00
JD
TCJ2▲
TCJ3▲
309.00
LD
TCL2▲
TCL3▲
366.00
MD
TCM2▲
TCM3▲
408.00
ND
TCN2▲
TCN3▲
428.00
RS4755
RS4756
➝
6
Rear-Connecting Studs
For Use
With
Breaker
Frames
Ampere
Rating
Description
Extension
Behind
Breaker
(inches)
Line Side
Catalog
Number
Catalog
Number
CIRCUIT
BREAKERS
2.38
2.38
4.88
4.88
RS2643▲
—
RS2641▲
—
40.50
All ED
Line Side (Short)
Load Side (Short)
Line Side (Long)
Load Side (Long)
47.50
—
40.50
RS2644▲40.50
—
47.50
RS2642▲47.50
All FD
250
250
Short
Long
3.12
7.06
RS4756▲
RS4755▲
58.00
91.00
RS4756▲58.00
RS4755▲91.00
All JD
400
400
Short
Long
5.85
11.20
RS5774▲
RS5773▲
161.00
161.00
RS5774▲161.00
RS5773▲161.00
All LD
600
600
Short
Long
5.85
11.20
RS5784▲
RS5783▲
158.00
181.00
RS5784▲192.00
RS5783▲181.00
CJD, SCJD
CLD, SCLD
Add required shield kit.
LM(X)D6,
HLM(X)D6
800
Short
Long
5.85
11.20
RS5788▲
RS5787▲
280.00
297.00
RS5788▲280.00
RS5787▲297.00
All MD,
ND
1200
1200
Short
Long
5.50
8.00
RS5786▲
RS5785▲
231.00
291.00
RS5786▲231.00
RS5785▲291.00
—
▲ Built to order. Allow 7–9 weeks for delivery.
Furnished at no extra charge when ordered with plug-in
mounting assembly.
Each piece catalog number consists of (1) mounting
block assembly and required tulip assemblies (2) for
2-pole, (3) for 3-pole
Circuit Breaker
With Rear-Connecting Studs
Load Side
100
100
100
100
6/80
Tulip
Assemblies
Switchboard
Mounting
Plate
➝
All MD
PL5797
➝
CED
PL2616
➝
➝
PC2638▲98.00
PC2657 158.00
➝
PC2637▲ 98.00
3
➝
2
➝
All ED
except CED
Catalog
Number
➝
Poles
Base
Steel Switchboard
Mounting Plate Catalog Number
➝
For Use With
Breaker Frames
Load Side
➝
Line Side
CLRSJL3 45.50
For vertical bus mounting — for horizontal, substitute
PC5665 for PC5664 and PC5667 for PC5666.
Price includes one current stud, insulating tube, stud
nuts and terminal shields, when required.
For proper electrical clearance, studs must alternate
between short and long stud lengths on circuit breaker
poles (e.g. SLSLSL or LSLSLS).
Enclosed Circuit Breakers
GENERAL
Enclosures
Type 3R
6
Type 1
ENCLOSED CIRCUIT
BREAKERS
Types 5, 12
Type 1 — A general indoor, sheet-steel
enclosure for use in normal atmospheres.
Type 3R — An outdoor, sheet-steel
enclosure providing protection against
driving rain, sleet or snow. Listed as
service entrance equipment.
Types 5, 12 — A special-industry, sheetsteel enclosure for use in atmospheres
containing particles of lint, dust, dirt,
sawdust and other foreign matter.
6/81
Enclosed Circuit Breakers
SELECTION/ DIMENSIONS
Enclosures — Type 1
Dimensions
Figure 1
Figure 3
Figure 2
Type 1
Fig. Breaker
No. Type
1
BQ, BQH,
HBQ
2
ED2, ED4, ED6,
HED4, HED6
Number Maximum
of
Current
Catalog
Poles
Rating
Number
3
2–3
0
0
0
Weight
Lb./Ship.
Package
K.O. Dimensions
Dimensions (inches)
A
100
EB3100S 0
32
171⁄8
100
E2N1S E2N1F 008
008
1623⁄32
171⁄2
CED6N1S
CED6N1F 014
014
B
C
0
0
71⁄8
D
E
0
41⁄2
6 Plcs.
2 Plcs.
F
G
H
15⁄16
—
—
7
⁄8, 11⁄8,
13⁄8,
7
⁄8, 11⁄8,
13⁄8,
43⁄4
141⁄8
071⁄2
081⁄2
051⁄16
051⁄16
1345⁄64
1345⁄64
051⁄4
051⁄4
1
1
2115⁄32
221⁄4
0719⁄32
081⁄2
057⁄64
057⁄64
181⁄4
181⁄4
051⁄4
051⁄4
1
1
13⁄4, 2
13⁄4, 2
ED4, ED6, HED4, HED6,
2–3
CED6
2
FXD6, FD6, FXD6-A,
FD6-A, HFD6, HFXD6,
HHFD6, CFD6
2–3
0250
F6N1S F6N1F 033
3813⁄32
1115⁄32
051⁄16
33
08
133⁄64
11⁄8, 13⁄8,
13⁄4, 2,
21⁄2, 3
11⁄8, 13⁄8,
13⁄4, 20,
21⁄2, 3
3
JXD2(A), JD6(A),
JXD6(A), HJD6(A),
HJXD6(A), HHJD6,
HHJXD6, SJD6(A),
SHJD6(A), SXD6H
2–3
0400
J6N1 120
4013⁄64
2227⁄64
1045⁄64
36
181⁄4
25⁄64
—
—
3
LD6(A), LXD6(A),
HLD6(A), HLXD6(A),
HHLD6, HHLXD6,
2–3
SLD6(A), SHLD6(A),
SCJD6, SCLD6, LXD6H
0600
LD6N1 (L6N1 )
101
46
2227⁄64
1045⁄64
42
181⁄4
25⁄64
—
—
3
MD6, MXD6, SMD6,
HMD6, HMXD6,
SHMD6, ND6, NXD6,
2–3
SND6, HND6, HNXD6,
SHND6, CMD6,
SCMD6, CND6, SCND6
1200
MND61 132
60
2227⁄64
10
557⁄8
181⁄4
25⁄64
—
—
—
PD6, PXD6, HPD6,
HPXD6, CPD6, RD6,
SPD6, SHPD6, RXD6,
HRD6, HRXD6
2000
PRD6N1
—
90
32
28
—
—
—
—
—
6
2
ENCLOSED CIRCUIT
BREAKERS
3
125
For inches / millimeters conversion, see page 15/6.
Neutral
Surface
Neutral
mounted, indoor. If flush mounting is required,
replace suffix “S” in catalog number with suffix “F”. Also,
if outdoor model required, use prefix “W”
instead of “E”.
Does not include circuit breaker. Order circuit
breaker separately.
6/82
not included. Order as separate item from table
on next page.
included in enclosure.
Surface mounted, indoor. If outdoor model is required,
use prefix “W” instead of “E”. Not available in flush (“F”)
model.
Use for 110-125 ampere ED4, ED6, HED4 or HED6
circuit breakers.
Will
not accept breaker with shunt trip.
Will not accept 2-pole GFCI or breaker with shunt trip.
Built to order. Consult sales office for factory lead time
and prices.
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 1
Dimensions
Figure 4
Figure
Number
Breaker
Type
4
QJ2, QJH2,
QH2-H,
QJ, QJH
Number
of
Poles
2–3
Maximum
Current
Rating
225
Catalog
Number
EB3225S
EB3225F
Weight
Lb./Ship. Dimensions (inches)
Package A B
C
D
E
15
27
27
101⁄8 27 101⁄8 51⁄4
101⁄8 281⁄8 111⁄4 51⁄4
F
G
H
213⁄16 213⁄8 23⁄8
213⁄16 213⁄8 23⁄8
J
K
L
3
3
20
20
51⁄16 23⁄4
51⁄16 23⁄4
M
N
P
23⁄4
23⁄4
41⁄2
41⁄2
Neutrals
W53045 Neutral Cable Capacity
and Wire Range
(1 pc.) #14–2 Cu/Al
Grd. Lug (1 pc.) #14–8 Cu/Al
(1 pc.) #6–350 kcmil
Grd. Lug (1 pc.) #14–2/0 Cu/Al
(1 pc.) #1/0–750 kcmil Cu/Al or
(2 pcs.) #1/0–300 kcmil Cu/Al
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
List
Price $
246.
F6N1(S)(F)
N250 (NFD)
259.
J6N1
W60992 (NJD)
LD6N1
W60993 (NLD)
(2 pcs.) #1/0–600 kcmil
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
393.
MND61
W63623 (NMND)
(8 pcs.) 250 kcmil–500 kcmil Cu/Al
Grd. Lug (1 pc.) #6–300 kcmil Cu/Al
802.
PRD6N1
N2000
(6 pcs.) #3/0–750 kcmil Cu/Al
Grd. Lug (2 pcs.) #3/0–750 Cu/Al
259.
6
E2N1(S)(F)
CED6N1(S)(F)
Neutral
Catalog
Number
ENCLOSED CIRCUIT
BREAKERS
Enclosure
Catalog
Number
1770.
For inches / millimeters conversion, see page 15/6.
Does not include circuit breaker. Order circuit
breaker separately.
included in enclosure.
Neutral
Built to order. Consult sales office for factory lead time
and prices.
6/83
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 3R
Dimensions
Figure 2
Figure 1
Figure 3
Type 3R
Figure
Breaker
Number Type
Number Maximum
of
Current
Catalog
Poles
Rating
Number
2
BQ, BQH,
HBQ
3
3
5
ED2, ED4, ED6,
HED4, HED6
2–3
Weight
Lb./Ship.
Package
0050
0100
WB3100 00
0
E2N3R 0
100
Dimensions (inches)
A
9
171⁄8
12
179⁄16
016
22 ⁄64
B
C
0
0
D
E
45⁄16
141⁄8
51⁄4
1239⁄64
07 ⁄4
05 ⁄4
0
73⁄8
71⁄4
0
0
F
41⁄2
11⁄8
51⁄4
1
17 ⁄8
05 ⁄4
0
G
0
H
311⁄16
—
3
—
1
03
—
0
6
CED6
2–3
0125
CED6N3R
1
FXD6, FD6, FXD6-A,
FD6-A, HFD6, HFXD6,
HHFD6, CFD6
2–3
0250
F6N3R 045
381⁄8
141⁄16
073⁄4
339⁄32
08
513⁄16
131⁄2
513⁄16
1
JXD2(A), JD6(A),
JXD6(A), HJD6(A),
HJXD6(A), HHJD6,
HHJXD6, SJD6(A),
SHJD6(A), SXD6H
2–3
0400
J6N3R 126
4063⁄64
263⁄4
1123⁄32
353⁄4
181⁄4
21⁄8
241⁄2
11⁄8
1
LD6(A), LXD6(A),
LXD6H, HLD6(A),
HLXD6(A), HHLD6,
HHLXD6, CJD6,
CLD6, SCJD6(A),
SLD6(A), SHLD6(A)
2–3
0
600
LD6N3R (L6N3R)
137
4563⁄64
263⁄4
1123⁄32
403⁄4
181⁄4
21⁄8
241⁄2
11⁄8
1
MD6, MXD6, SMD6,
HMD6, HMXD6,
SHMD6, ND6, NXD6,
SND6, HND6, HNXD6, 2–3
SHND6, CMD6, SCMD6,
CND6,
SCND6
1200
MND63 210
619⁄64
263⁄4
1123⁄32
5717⁄32
181⁄4
21⁄8
245⁄8
11⁄16
ENCLOSED CIRCUIT
BREAKERS
5
For inches / millimeters conversion, see page 15/6.
Neutral
Does
Neutral
not include circuit breaker.
Order circuit breaker separately.
6/84
21
not included. Order as separate item from table
on next page.
included in enclosure.
Will not accept breaker with shunt trip.
1
1
3
1
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 3R
Dimensions
Figure 4
Figure
Breaker
Number Type
Number Maximum
of
Current
Poles
Rating
QJ2, QJH2,
2
QJ2-H,
3
QJ, QJH
6
Figure 5
225
225
Figure 6
Catalog
Number
Weight
Lb./Ship.
Package
A
B
C
D
E
F
G
H
J
K
L
M
WB2225
WB3225
17
17
27
27
5
55⁄8
0711⁄16
103⁄8
21⁄4
21⁄4
2
2
27⁄8
27⁄8
20
20
41⁄8
41⁄8
35⁄8
51⁄8
23⁄4
23⁄4
23⁄4
23⁄4
—
41⁄2
Dimensions (inches)
Neutrals
Neutral Cable Capacity
and Wire Range
List
Price $
W53045 (1 pc.) #14–2 Cu/Al
Grd. Lug (1 pc.) #14–8 Cu/Al
246.
F6N3R
N250 (NFD)
(1 pc.) #6–350 kcmil
Grd. Lug (1 pc.) #14–2/0 Cu/Al
259.
JD6N3R
W60992 (NJD)
(1 pc.) #1/0–750 kcmil Cu/Al or
(2 pcs.) #1/0–300 kcmil Cu/Al
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
259.
LD6N3R
W60993 (NLD)
(2 pcs.) #1/0–600 kcmil
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
393.
MND63
W63623 (NMND)
(8 pcs.) 250 kcmil–500 kcmil Cu/Al
Grd. Lug (1 pc.) #6–300 kcmil Cu/Al
802.
E2N3R
CED6N3R 6
Neutral
Catalog
Number
ENCLOSED CIRCUIT
BREAKERS
Enclosure
Catalog
Number
Hubs — see page 6/87
For inches / millimeters conversion, see page 15/6.
Does
not include circuit breaker. Order circuit
breaker separately.
Neutral
not included. Order as separate item from table
on next page.
Neutral included in enclosure.
Use
CED enclosure for all ED-frame 110-125
ampere units.
6/85
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Type 12
Types 5, 12
Number
of
Poles
Maximum
Current
Rating
Figure
Number
Breaker
Type
2
ED2, ED4, ED6,
HED4, HED6
2–3
0100
E2N12
1
CED6
2–3
0125
CED6N12 2
FXD6, FD6, FXD6-A,
FD6-A, HFD6, CFD.6
2–3
3
JXD2(A), JD6(A), JXD6(A),
HJD6(A), HJXD6(A),
HHJD6, HHJXD6, SJD6(A),
SHJD6(A)
Weight
Lb./Ship .
Package
Catalog
Number
Dimensions (inches)
A
B
5
C
11
D
1
E
F
1
012
18 ⁄8
08 ⁄32
07 ⁄16
18
06 ⁄16
01⁄2
0811⁄32
071⁄16
22
061⁄16
05⁄8
016
225⁄8
0250
F6N12
040
19
38 ⁄32 14 ⁄64
08 ⁄8
34
13
023⁄32
2–3
0400
J6N12
104
40
2535⁄64
117⁄8
36
2435⁄64
—
3
LD6(A), LXD6(A), HLD6(A),
HLXD6(A), HHLD6,
HHLXD6, SLD6(A),
SHLD6(A), CJD6, CLD6,
SCJD6(A), SCLD6(A)
2–3
0600
LD6N12
(L6N12)
104
45
2535⁄64
117⁄8
41
2435⁄64
—
4
MD6, MXD6, SMD6,
HMD6, HMXD6, SHMD6,
ND6, NXD6, SND6, HND6,
HNXD6, SHND6,
CMD6, SCMD6,
CND6, SCND6
2–3
1200
MND612 220
60
373⁄8
10
005⁄8
03
2
29
1
Dimensions
6
Figure 2
Figure 3
ENCLOSED CIRCUIT
BREAKERS
Figure 1
Neutrals
Enclosure
Catalog
Number
E2N12
Neutral
Catalog
Number
Neutral Cable Capacity
and Wire Range
List
Price $
W53045 (1 pc.) #14–2 Cu/Al
(1 pc.) #14–2 Cu/Al
246.
F6N12
N250 (NFD)
(1 pc.) #6–350 kcmil
Grd. Lug (1 pc.) #14–2/0 Cu/Al
259.
J6N12
W60992 (NJD)
(1 pc.) #1/0–750 kcmil Cu/Al or
(2 pc.) #1/0–300 kcmil Cu/Al
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
259.
L6N12
W60993 (NLD)
(2 pcs.) #1/0–600 kcmil
Grd. Lug (1 pc.) #6–250 kcmil Cu/Al
393.
MND612
W63623 (NMND)
(8 pcs.) 250 kcmil–500 kcmil Cu/Al
Grd. Lug (1 pc.) #6–300 kcmil Cu/Al
802.
CED6N12 For inches / millimeters conversion, see page 15/6.
Neutral
not included. Order as separate item.
included in enclosure.
CED enclosure for all ED-frame 110–125
ampere units.
Neutral
Does
not include circuit breaker.
Order circuit breaker separately.
6/86
Use
Figure 4
Enclosed Circuit Breakers
SELECTION / DIMENSIONS
Enclosures — Knockout and Hub Data
Knockouts & Wire Bending Space
Types 1, 12
Type 3R
Number of Knockouts Per Panel (type 12 have no KO’s)
Breaker
Type
BQ, BQH, HBQ
70–100A
Conduit Range
Per Knockout
Outside Dimensions
(inches)
Top
Bottom
Side
Back
Bottom
Side
⁄4, 1, 1 ⁄4
1
1
2
2
8
2
2
2
2
2
2
3
1
Back
Maximum
Hub Size
(inches)
Type 3R
Maximum Cable Sizes
Recommended (Cu/Al)
for Type 1, 3R, 4, 4X,
12 & 12K Enclosures 1
3
2
3
1
1
21⁄2
2
2
1
1
2
2
4
QJ
11⁄2, 2, 21⁄2, 3
ED2, ED4, ED6,
HED4
7
⁄8, 1 ⁄8, 1 ⁄8, 1 ⁄4, 2
2
7
⁄8, 11⁄8, 13⁄8, 13⁄4, 2
—
—
—
—
2
—
—
7
⁄8, 11⁄8, 13⁄8, 13⁄4, 2, 21⁄2
2
2
2
2
—
1
1
1
1
2
2
1
1
—
1
1
—
—
1
—
—
CED6
1
3
3
(CFD6 only 300 kcmil)
FXD6, FD6, FXD6-A, FD6-A
HFD6, CFD6
11⁄8, 13⁄8, 13⁄4, 2, 21⁄2, 3
JXD2(A), JXD6(A), JD6(A),
HJD6(A), HJXD6(A), HHJD6,
HHJXD6, SJD6(A), SHJD6(A)
11⁄2, 2, 21⁄2, 3, 31⁄2, 4
1
1
2
4
—
—
—
4
(2) 500 kcmil
LXD6(A), LD6(A), HLXD6(A),
HLD6(A), HHLD6, HHLXD6,
SLD6(A), SHLD6(A)
11⁄2, 2, 21⁄2, 3, 31⁄2, 4
1
1
2
4
—
—
—
4
(2) 500 kcmil
MD6, SMD6, HMD6
ND6, SND6, HND6
—
—
—
—
—
—
—
—
4
(3) 600 kcmil or
(4) 500 kcmil
Conduit
Size
(inches)
Catalog
Number
QP, QPH, HQP,
BQ, BQH, HBQ,
ED2, ED4, ED6,
HED4, HED6,
CED6
03⁄4
1
11⁄4
11⁄2
2
HR075
HR100
HR125
HR150
HR200
QPP, QPPH, HQPP,
QJ2, QJH2, QJ2-H
11⁄4
11⁄2
2
21⁄2
HS125
HS150
HS200
HS250
FXD6-A, FD6-A, HFD6, HFXD6,
CFD6, JXD2(A), JD6(A),
JXD6(A), HJD6(A), HJXD6(A),
LD6(A), LXD6(A), HLD6(A),
HLXD6(A)
21⁄2
3
31⁄2
4
HV250
HV300
HV350
HV400
For inches / millimeters conversion, see page 15/6.
Sufficient
171⁄8"
The
high enclosure provides sufficient wire bending
space for all available CB lugs.
wire bending space is provided for all
available mechanical type CB lugs.
use of cables larger than those listed below may
violate NEC & CSA wire bending space requirements.
Note: Enclosures for 250A max breakers have a hub
provision on the rainshed. Enclosures for larger
breakers (J, L, M & N frame) have blank top
rainsheds. Drill or punch hole in the field to
accommodate hub size desired.
The
use of compression type connectors will violate NEC
and CSA wire bending space requirements.
6/87
ENCLOSED CIRCUIT
BREAKERS
Breaker
Type
6
Hubs (Type 3R)
Notes
6
ENCLOSED CIRCUIT
BREAKERS
6/88
Molded Case Circuit Breakers
GENERAL
CIRCUIT
BREAKERS
6
Series Rated Combination Guide
6/89
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
Reading the Series Rated combination tables
Identify the application voltage.
Identify the available short circuit current at the point where the breaker is to be applied.
Identify the ampere rating and number of poles for both the upstream and downstream breakers.
Example:
The application voltage is 208V, 3phase, the available short circuit current is 19,000 Amps. The Main breaker
is 200A rated and the Branch breaker is 3 Pole, 100A rated.
From the tables select the voltage greater than and closest to the application voltage. ( 240 )
From the IC column select the current rating greater than and closest to the application short circuit current
From the Main Breaker column select the type based on the required ampere rating and number of poles.
( QJH2, 200A, 3P ) The Maximum current tested for this type of breaker is 225A.
From the Branch Breaker column select the type based on the required ampere rating and number of poles.
some cases more than one option may be available. ( QP, BQ, BL )
IC/CI KA
Main Breaker / Disjoncteur
principal
Type
Branch Breaker / Disjoncteur de branchement
Ams (Poles)
Type
6
QP, BQ, BL
22
QJH2
60 - 225 (2 & 3)
QPF, BQF BLF, QE, BE, BLE
QT
# Poles
Amps
1
2
3
1
1, 2
15 - 70
15 - 125
60 - 100
15 - 30
15, 20, 40
Max Voltage
(AC/CA)
120/240
240
240
120
120/240
This information is of a general nature and is intended for reference purposes only. Although every effort to ensure correctness of the material,
Siemens Canada Limited cannot assume any responsibility for actions taken on the basis of the content herein.
CIRCUIT
BREAKERS
Diagram for the above example:
QJH2
MAIN BREAKER
AVAILABLE FAULT
CURRENT AT
208V
(10K AMPS)
Amps)
(19K
6/90
Figure 3
QP, BQ, BL
FEEDER
BREAKERS
Molded Case Circuit Breakers
GENERAL
Type
Ams (Poles)
Type
QP, BQ, BL
22
QPH, BQH, BLH
15-70 (1), 15-125 (2),
15-100 (3)
QE, BLE, QPF, BLF
QE, BLE, QPF, BQF, BLF
QT
QP, BQ, BL
22
QPPH
125 - 225 (2)
22
QJH2
60 - 225 (2 & 3)
QE, BLE, BE, QPF, BQF, BLF
QE, BLE, BE, QPF, BLF
QPP
QT
QP, BQ, BL
QPF, BQF BLF, QE, BE, BLE
QT
QP, BQ, BL
42
QJ2H
60 - 225 (2 & 3)
QPH, BQH, BLH
QE, BLE, BE, QPF, BLF
QJH2
QP, BQ, BL, QPH, BQH, BLH
65
HQP, HBQ, HBL
15-70 (1), 15-125 (2),
QPF, BQF, BLF, BE, QFHF, BQHF, BLHF, QEH,
15-100 (3)
BLEH, QE, BLE
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF
QT
QP, BQ, BL, QPH, BQH, BLH
65
HQPP
125 - 225 (2)
QPF, BQF, BLF, QPHF, BQHF, BLHF, QEH, BLEH,
QE, BLE, BE
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF
QT
QPPH, QPP
QP, BQ, BL, QPH, BQH, BLH
65
ED4, ED6
15 - 100 (1), 15 - 125 QPHF, BQHF, BLHF, QPF, BQF, BLF, QE, QEH,
(2 & 3)
BLEH, BE, BLE
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF
ED2
QT
QP, BQ, BL, QPH, BQH, BLH
65
FD6-A, FXD6-A
70 - 250 (2 & 3)
QJ2H, QJ2, QJH2
QPPH
65
JXD2-A, JD6-A, JXD6A
200 - 400 (2 & 3)
QPH, BQH, BLH
QJ2H, QJH2
65
LD6-A
200 - 600 (2 & 3)
QPH, BQH, BLH
QJ2H, QJH2
65
LXD6-A
450 - 600 (2 & 3)
# Poles
Amps
Max
Voltage
(AC/CA)
1
2
3
1
2
1, 2
1
2
1
2
2
1, 2
1
2
3
1
1, 2
1
2
3
1
2
3
2
2, 3
1
2
3
15 -70
15 -125
15-100
15 - 60
15 - 30
15, 20, 40
15 -70
15 -125
15 - 30
15 - 60
125 - 200
15, 20, 40
15 - 70
15 - 125
60 - 100
15 - 30
15, 20, 40
15 - 70
15 - 125
60 - 100
15 - 70
15 - 125
15 - 100
15 - 60
60 - 225
15 - 70
15 - 100
15 - 100
120/240
120/240
240
120/240
120
120/240
120/240
120/240
120
120/240
120/240
120/240
120/240
240
240
120
120/240
120/240
120/240
240
120/240
120/240
240
120/240
240
120/240
120/240
240
1
15 - 30
120
2
1, 2
1
2
15 - 60
15 - 40
15 - 70
15 - 125
120/240
120/240
120/240
120/240
Branch Breaker / Disjoncteur de branchement
Main Breaker / Disjoncteur principal
QPH, BQH, BLH
QJ2H, QJH2
1
15 - 30
120
2
1, 2
2
1
2
3
15 - 60
15 - 40
125 - 200
15 - 70
15 - 125
15 - 100
120/240
120
120/240
120
120/240
240
1
15 - 30
120
2
1, 2, 3
1, 2
1
2
3
2, 3
2
1
2
3
2, 3
1
2
3
2, 3
1
2
3
2, 3
15 - 60
15 - 100
15 - 40
15 - 70
15 - 125
15 - 100
60 - 225
125 - 225
15 - 70
15 - 125
15 - 100
60 - 225
15 - 70
15 - 125
15 - 100
60 - 225
15 - 70
15 - 125
15 - 100
60 - 225
120/240
120/240
120/240
120/240
120/240
240
240
120/240
120/240
120/240
240
240
120/240
120/240
240
240
120/240
120/240
240
240
CIRCUIT
BREAKERS
100
100
100
65
IC/CI KA
6
Series Rated Combination Guide
6/91
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65
IC/CI KA
Main Breaker / Disjoncteur principal
Type
65
65
100
HJD6-A, HJXD6-A,
HLD6-A, HLXD6-A,
HMD6, HMXD6, HND6,
HNXD6, HPD6,
HPXD6, HRD6, HRXD6
Ams (Poles)
200 - 2000 (2 &3)
Type
QPH
SJD6-A, SLD6-A,
SMD6, SND6, SPD6
200 - 1600 (2 &3)
QPH, BQH, BLH
MD6, MXD6, ND6,
NXD6, PD6, PXD6,
RD6, RXD6
500 - 2000 (2 & 3)
QPH, BQH, BLH
HED4
15 - 100 (1)
ED2, ED4
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL
100
HED4, HED6
15 - 125 (2 & 3)
100
HED4
15 - 100 (1)
QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF,
BLF, BQF, BLE
QEH, BLEH, QPHF, BLHF,QPF, BLF, QE, BLE
ED2
ED4
ED4, ED6
QT
ED2, ED4
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL
100
HQPPH
125 - 225 (2)
# Poles
Amps
Max
Voltage
(AC/CA)
1
15 - 70
120/240
2
15 - 125
120/240
3
15 - 100
240
1
2
3
1
2
3
1
1
2
3
15 - 70
15 - 125
15 - 100
15 - 70
15 - 125
15 - 100
15 - 100
15 - 70
15 - 125
15 - 100
120/240
120/240
240
120/240
120/240
240
120
120
120/240
240
Branch Breaker / Disjoncteur de branchement
HQPP, QPPH, QPP
QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF,
BQF, BLF, BLE
QT
1
15 -30
120
2
1, 2, 3
1
2, 3
1, 2
1
1
2
2
15 - 60
15 - 100
15 - 100
15 - 125
15 - 40
15 - 100
15 - 70
15 - 125
125 - 225
120/240
120/240
120
240
120/240
120
120/240
120/240
120/240
1
15 - 30
120
1, 2
15 - 40
15 - 25
35 - 70
15 - 25
35 - 125
15 - 100
15 - 70
15 - 125
15 - 100
120/240
120/240
120/240
120/240
120/240
240
120/240
120/240
240
1
QP, BQ, BL
6
100
HQJ2H
60 - 225 (2 & 3)
QPH, BQH, BLH, HQP, HBQ, HBL
CIRCUIT
BREAKERS
QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF,
BQF, BLF, BLE
QEH, BLEH, QPHF, BLHF,QE, BLE, QPF, BLF
QT
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL
6/92
100
HFD6, HFXD6
70 - 250 (2 & 3)
100
HJD6-A, HJXD6-A,
SHJD6-A
200 - 400 (2 & 3)
100
HLD6-A
200 - 600 (2 & 3)
QE, BE, BLE, QPHF, BQHF, BLHF, QPF, BQF, BLF,
QEH, BLEH
QPF, BLF, QE, BLE, QPHF, BLHF, QEH, BLEH
ED4
ED4, ED6
FD6-A, FXD6-A
QJ2, QJH2, QJ2H
HQPP, QPPH, QPP
QT
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
2
3
1
2
3
1
15 - 30
120
2
1
1
2
3
15 - 60
15 - 50
15 - 70
15 - 125
15 - 100
120/240
120/240
120/240
120/240
240
1
15 - 30
120
2
1
2, 3
2, 3
2, 3
2
1, 2
1
2, 3
2, 3
2, 3
1
2, 3
2, 3
2, 3
15 - 60
15 - 100
15 - 125
70 -250
60 - 225
125 - 225
15 - 30
15 - 100
15 - 125
70 - 250
200 - 400
15 - 100
15 - 125
70 - 250
200 - 400
120
120
240
240
240
120/240
120/240
120/240
120/240
120/240
120/240
120
240
240
240
Molded Case Circuit Breakers
GENERAL
Main Breaker / Disjoncteur principal
Type
Ams (Poles)
100
HLD6-A
200 - 600 (2 & 3)
100
HLXD6-A
450 - 600 (2 & 3)
100
SHLD6-A
300 - 600 (3)
100
HMD6, HMXD6
500 - 800 (2 & 3)
100
SHMD6
500 - 800 (3)
100
HND6, HNXD6
500 - 1200 (2 & 3)
100
SHND6
500 - 1200 (2 & 3)
100
HPD6, HPXD6, SHPD
1200 - 1600 (3)
100
HPD6, HPXD6, SHPD
1200 - 1600 (3)
# Poles
Amps
Max
Voltage
(AC/CA)
2, 3
2, 3
3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
2, 3
2, 3
200 - 600
450 - 600
300 - 600
15 - 100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
15 - 100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
15 - 100
15 - 125
70 - 250
200 -400
200 - 600
450 - 600
300 - 600
500 -800
15 - 100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
500 - 800
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
500 - 600
500 - 1200
15 - 100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
500 - 600
500 - 1200
15 -100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
500 - 800
500 - 1200
1200 - 1600
240
240
240
120
240
240
240
240
240
240
120
240
240
240
240
240
240
120
240
240
240
240
240
240
240
120
240
240
240
240
240
240
240
240
240
240
240
240
240
240
120
240
240
240
240
240
240
240
240
120
240
240
240
240
240
240
240
240
240
Branch Breaker / Disjoncteur de branchement
Type
LD6-A
LXD6-A
SLD6-A
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
ND6, NXD6, SND6
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
ND6, NXD6, SND6
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
ND6, NXD6, SND6
PD6, PXD6, SPD6
6/93
CIRCUIT
BREAKERS
100
100
100
65
IC/CI KA
6
Series Rated Combination Guide
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65
IC/CI KA
Main Breaker / Disjoncteur principal
Type
100
HRD6, HRXD6
Ams (Poles)
1600 - 2000 (3)
Type
ED4
ED4, ED6
FD6-A, FXD6-A
JD6-A, JXD6-A, JXD2-A, SJD6-A
LD6-A
LXD6-A
SLD6-A
MD6, MXD6, SMD6
ND6, NXD6, SND6
PD6, PXD6, SPD6
RD6, RXD6
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL
200
CED6
15 - 125 (2 & 3)
QPHF, BQHF, BLHF, QPF, BQF, BLF, QEH, QE,
BE, BLEH
QEH, BLEH, QPHF, BLHF, QPF, BLF, QE, BLE
ED4, HED4
ED4, ED6, HED4, HED6
QT
QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL
200
CFD6
70 - 250 (2 & 3)
200
HHJD6, HHJXD6,
HHLD6, HHLXD6
200 - 600 (2 & 3)
QPHF, BQHF, BLHF, QE, BE, BLE, QPF, BQF, BLF,
QEH, BLEH
QPHF, BLHF, QE, BLE, QPF, BLF, QEH, BLEH
ED2
HED4, ED4
ED4, ED6, HED4, HED6
FD6-A, FXD6-A, HFD6, HFXD6
QJ2H, QJH2, QJ2
QPPH, QPP
QT
FD6-A, FXD6-A, HFD6, HFXD6
6
QPH, BQH, BLH, HQP, HBQ, HBL
200
CJD6
200 - 400 (2 & 3)
ED4, ED6
FD6-A, FXD6-A, HFD6, HFXD6
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A
QT
QPH, BQH, BLH, HQP, HBQ, HBL
CIRCUIT
BREAKERS
6/94
200
CLD6
450 - 600 (2 & 3)
200
CMD6
500 - 800 (2 & 3)
200
SCMD6
500 - 800 (3)
200
CND6
900 - 1200 (2 & 3)
200
CND6
900 - 1200 (2 & 3)
# Poles
Amps
Max
Voltage
(AC/CA)
1
2, 3
2, 3
2, 3
2, 3
2, 3
3
2, 3
2, 3
2, 3
2, 3
1
2
3
15 -100
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
300 - 600
500 - 800
500 - 1200
1200 - 1600
1600 - 2000
15 - 70
15 - 125
15 - 100
120
240
240
240
240
240
240
240
240
240
240
120/240
120/240
240
Branch Breaker / Disjoncteur de branchement
ED4, ED6
FD6-A, FXD6-A, HFD6, HFXD6
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HJXD6-A
QT
ED4, ED6, HED4, HED6
FD6-A, FXD6-A, HFD6, HFXD6
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
MD6, MXD6, HMD6, HMXD6
MD6, MXD6, HMD6, HMXD6
ED4, ED6, HED4, HED6
FD6-A, FXD6-A, HFD6, HFXD6
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
MD6, MXD6, HMD6, HMXD6
ND6, NXD6, SND6, HND6, HNXD6
1
15 - 30
120
2
1
2, 3
1, 2
1
2
3
15 - 60
15 - 100
15 - 125
15 - 40
15 - 70
15 - 125
15 - 100
120/240
120
240
120/240
120/240
120/240
240
1
15 - 30
120
2
1, 2, 3
1
2, 3
2, 3
2, 3
2
1, 2
15 - 60
15 - 100
15 - 100
15 - 125
70 - 250
60 - 225
125 - 225
15 - 40
120/240
120/240
120
240
240
240
120/240
120/240
2, 3
70 - 250
240
2
3
2, 3
2, 3
2, 3
1, 2
2
3
2, 3
2, 3
2, 3
2, 3
2, 3
1,2
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
100 - 125
100
15 - 125
70 - 250
200 - 400
15 - 30
100 - 125
100
15 - 25
70 - 250
200 - 400
200 - 600
450 - 600
15 - 30
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
500 - 800
15 - 125
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
500 - 1200
120/240
240
240
240
240
120/240
120/240
240
120/240
240
240
240
240
120/240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
Main Breaker / Disjoncteur principal
Ams (Poles)
200
SCND6
900 - 1200 (3)
200
CPD6
1200 - 1600 (3)
65
J, R
15 - 600 (1, 2, 3)
65
65
T
L
15 - 1200 (1, 2, 3)
601 - 6000 (1, 2, 3)
Type
MD6, HMD6, HMXD6, MXD6, SHMD6, SMD6
ND6, HND6, SHND6, NXD6, HNXD6, SND6
FD6-A, FXD6-A, HFD6, HFXD6
JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
MD6, MXD6, HMD6, HMXD6
ND6, NXD6, SND6, HND6, HNXD6
QPH, BQH, BLH
QPH, BQH, BLH
QPH, BQH, BLH
QP, BQ, BL
100
T (300 V)
15-200 (1, 2, 3)
15 - 600 (1, 2, 3)
15 - 600 (2, 3)
70 - 600 (2, 3)
100
J, R
200 - 600 (2, 3)
T
240
240
240
240
240
240
240
240
1
15-70
120/240
2
15-125
120/240
3
15 - 100
240
1
15-70
120/240
2
15-125
120/240
3
15 - 100
240
1
15-70
120/240
2
15-125
120/240
3
15 - 100
240
1, 2, 3
15 - 125
120/240
HQP, HBQ, HBL, QPH, BQH, BLH
QPF, BQF, BLF, QE, BE, BLE, QEH, BLEH, BLHF,
QPHF, BQHF,
QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF
3
15 - 100
240
1
15 - 30
120
120/240
2
15 - 60
QT
1, 2
15 - 50
120/240
QPH, BQH, BLH, HQP, HBQ, HBL
1, 2
15 - 125
120/240
ED4, HED4
1
15 - 100
120
ED4, ED6, HED4, HED6
2, 3
15 - 125
240
FD6-A, FXD6-A
2, 3
70 - 250
240
JD6-A, JXD6-A, JXD2-A, SJD6-A
2, 3
200 - 400
240
LD6-A
2, 3
200 - 600
240
3
300 - 600
240
450 - 600 (2, 3)
LXD6-A
2, 3
450 - 600
240
1
15 - 100
120/240
ED4, HED4
ED4, ED6, HED4, HED6
2, 3
15 - 125
240
70 - 1200 (2, 3)
FXD6-A, FD6-A
2, 3
70 - 250
240
450 - 1200 (2, 3)
LXD6-A
2, 3
450 - 600
240
JD6-A, JXD6-A, JXD2-A, SJD6-A
2, 3
200 - 400
240
LD6-A
2, 3
200 - 600
240
3
300 - 600
240
300 - 1200 (3)
SLD6-A
ED4, HED4
L
500 - 800
500 - 1200
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
500 - 1200
SLD6-A
200 - 1200 (2, 3)
100
Amps
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
300 - 600 (3)
15 - 1200 (2, 3)
100
# Poles
601 - 6000
(2, 3)
1
15 - 100
120/240
ED4, ED6, HED4, HED6
2, 3
15 - 125
240
FD6-A, FXD6-A
2, 3
70 - 250
240
JD6-A, JXD6-A, JXD2-A, SJD6-A
2, 3
200 - 400
240
LD6-A
2, 3
200 - 600
240
LXD6-A
2, 3
450 - 600
240
SLD6-A
3
300 - 600
240
SMD6
3
500 - 800
240
SND6
3
500 - 1200
240
PD6, PXD6, SPD6
3
1200 - 1600
240
RD6, RXD6
3
1600 - 2000
240
QJH2, QJ2H, QJ2
2, 3
125 - 200
240
125 - 600 (2, 3)
QJH2, QJ2H
2, 3
125 - 225
240
125 - 400 (2, 3)
QJ2
2, 3
125 - 225
240
125 - 200 (2, 3)
6
Type
Max
Voltage
(AC/CA)
Branch Breaker / Disjoncteur de branchement
200
R
200
T, J
200
J, R
70 - 600 (2, 3)
HFD6, HFXD6
2, 3
70 - 250
240
200
T
70 - 1200 (2, 3)
HFD6, HFXD6
2, 3
70 - 250
240
CIRCUIT
BREAKERS
100
100
100
65
IC/CI KA
6/95
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65
IC/CI KA
Type
200
# Poles
Amps
Max
Voltage
(AC/CA)
HFD6, HFXD6
2, 3
70 - 250
240
MD6, MXD6, HMD6, HMXD6
2, 3
500 - 800
240
ND6, NXD6, HND6, HNXD6
BQD, CQD
ED4
ED4, ED6
2, 3
1, 2, 3
1
2, 3
500 - 1200
15 - 100
15 - 100
15 - 125
2,3
15-100
1, 2, 3
1
2, 3
15,100
15 - 100
15 - 125
240
277
277
480
277
277
277
277
480
480
2, 3
15 - 50
480
Main Breaker / Disjoncteur principal
L
Branch Breaker / Disjoncteur de branchement
Ams (Poles)
601 - 6000 (2, 3)
Type
30
HED6
15 - 125 (2 & 3)
35
JD6, JXD6
LD6
LXD6
200-400 (2 & 3)
200-600 (2 & 3)
450-600 (2 & 3)
ED4
42
HED4
15 - 125 (2 & 3)
BQD, CQD
ED4
ED4, ED6
50
HJD6-A, HJXD6-A
200-400 (2 & 3)
50
HLD6-A, HLXD6-A
200-600 (2 & 3)
50
MD6, MXD6
500-800 (2 & 3)
HED4
FD6-A, FXD6-A
2, 3
70 - 250
480
JD6-A, JXD6-A, SJD6-A
2, 3
200 - 400
480
LD6-A
2, 3
200 - 600
480
LXD6-A
2, 3
450 - 600
480
3
400 - 600
480
2, 3
2, 3
2, 3
2, 3
3
3
2, 3
2, 3
2, 3
3
3
2, 3
2, 3
2, 3
3
3
2, 3
2, 3
2, 3
3
3
2, 3
2, 3
2, 3
2, 3
3
3
2, 3
2, 3
2, 3
2, 3
3
3
1, 2, 3
1
2, 3
1
2, 3
2, 3
70 - 250
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
70 - 250
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
70 - 250
200 - 400
200 - 600
450 - 600
200 - 400
400 - 600
15 - 100
15 - 100
15 - 125
15 - 100
70 - 250
200 - 400
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
277
480
480
480
480
SLD6-A
ND6, NXD6
500-1200 (2 & 3)
50
SMD6
500 - 800 (3)
50
SND6
500 - 1200 (3)
50
SPD6
1200 - 1600 (3)
6
50
CIRCUIT
BREAKERS
1400 - 1600 (3)
6/96
50
PD6, PXD6
50
RD6, RXD6
1800 - 2000 (3)
65
HFD6, HFXD6
70 - 250 (2 & 3)
65
HJD6-A, HJXD6-A
200 - 400 (2 & 3)
1200 - 1600 (3)
FD6-A, FXD6-A
JD6-A, JXD6-A,
LD6-A
LXD6-A
SJD6-A
SLD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
SJD6-A
SLD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
SJD6-A
SLD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
SJD6-A
SLD6-A
FD6-A, FXD6-A
JD6-A, JXD6-A, SJD6-A
LD6-A
LXD6-A
SJD6-A
SLD6-A
FD6-A, FXD6-A
JD6-A, JXD6-A, SJD6-A
LD6-A
LXD6-A
SJD6-A
SLD6-A
BQD, CQD
ED4, HED4
ED4, ED6, HED4, HED6
HED4, ED4
FD6-A, FXD6-A
JD6-A, JXD6-A
Molded Case Circuit Breakers
GENERAL
Main Breaker / Disjoncteur principal
Type
Ams (Poles)
65
HLD6-A
200 - 600 (2 & 3)
65
HLXD6-A
450 - 600 (2 & 3)
65
HMD6, HMXD6
500 - 800 (2 & 3)
65
HND6, HNXD6
500 - 1200 (2 & 3)
65
HRD6, HRXD6
1800 - 2000 (3)
100
HHJXD6, HHJD6,
HHLD6, HHLXD6
200 - 600 (2 & 3)
100
CMD6
500 - 800 (3)
100
100
SCMD
SCND6
500 - 800 (3)
900 - 1200 (3)
100
CND6
1200 (3)
100
CPD6
1200 - 1600 (3)
150
CJD6
200 - 400 (2 & 3)
150
CLD6
450 - 600 (2 & 3)
200
CED6
15 - 125 (2 & 3)
Type
ED4, HED4
FD6-A, FXD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
ED4, HED4
FD6-A, FXD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
FD6-A, FXD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
FD6-A, FXD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
MD6, MXD6, SMD6
FD6-A, FXD6-A
JD6-A, JXD6-A
LD6-A
LXD6-A
ED4, ED6, HED4, HED6
FD6-A, FXD6-A, HFD6, HFXD6
FD6-A, FXD6-A, HFD6, HFXD6
JD6-A, HJD6-A, JXD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
MD6, MXD6, HMD6, HMXD6
HFXD6
HFD6, HFXD6
FD6-A, FXD6-A, HFD6, HFXD6
JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
MD6, MXD6, HMD6, HMXD6
ND6, NXD6, HND6, HNXD6
FD6-A, FXD6-A, HFD6, HFXD6
ED4
HFD6, HFXD6
JD6-A, JXD6-A, HJD6-A, HJXD6-A
ED4
HFD6, HFXD6
JD6-A, HJD6-A, JXD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
BQD, CQD
ED4, HED4
ED4, ED6, HED4, HED6
BQD, CQD
200
CFD6
50
J
100
100
100
J
T, J
J, R
70 - 250 (2 & 3)
60 - 400 (1, 2, 3)
15 - 400 (2, 3)
15 - 400 (1, 2, 3)
70 - 600 (2, 3)
70 - 600 (2, 3)
# Poles
Amps
Max
Voltage
(AC/CA)
1
2, 3
2, 3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
1
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
1
2, 3
1
2, 3
1
2, 3
2, 3
1
2, 3
2, 3
1
2, 3
1
2, 3
2, 3
15 - 100
70 - 250
200 - 400
200 - 600
450 - 600
15 - 100
70 - 250
200 - 400
200 - 600
450 - 600
70 - 250
200 - 400
200 - 600
450 - 600
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
70 - 250
200 - 400
200 - 600
450-600
15 - 100
70 - 250
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
70 - 250
70 - 250
70 - 250
200 - 400
200 - 600
450 - 600
500 - 800
500 - 1200
70 - 250
15 - 100
70 - 250
200 - 400
15 - 100
70 - 250
200 - 400
200 - 600
450 - 600
15 - 100
20 - 30
15 - 100
15 - 125
15 - 100
20 - 30
15 - 50
15 - 100
15 - 125
70 - 250
60 - 100
15 - 100
15 - 50
70 - 250
70 - 250
277
480
480
480
480
277
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
277
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
277
480
480
277
480
480
480
480
480
480
277
480
480
480
480
277
480
480
277
480
277
480
480
Branch Breaker / Disjoncteur de branchement
ED4, ED6
ED4, HED4
HED4, HED6
FD6-A, FXD6-A, HFD6, HFXD6
ED4
ED4
ED4
FD6-A, FXD6-A
HFD6, HFXD6
CIRCUIT
BREAKERS
100
100
100
65
IC/CI KA
6
Series Rated Combination Guide
6/97
Molded Case Circuit Breakers
GENERAL
Series Rated Combination Guide
100
100
100
65
IC/CI KA
Main Breaker / Disjoncteur principal
Type
# Poles
Amps
Max
Voltage
(AC/CA)
200 - 400
200 - 600
450 - 600
70 - 250
200 - 400
200 - 600
450 - 600
70 - 250
500 - 800
500 - 1200
1200 - 1600
15 - 100
20 - 30
15 - 100
20 - 30
15 - 70
15 - 70
15 - 70
15 - 70
15 - 125
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
347
347/600
347
347/600
347/600
70 - 250
347/600
Branch Breaker / Disjoncteur de branchement
Ams (Poles)
Type
100
T, J, R
100
T
450 - 600 (2, 3)
70 - 1200 (2, 3)
100
T, L
601 - 1200 (2, 3)
100
L
601 - 6000 (2, 3)
R
15 - 100 (1, 2, 3)
BQD, CQD
T, J
15 - 200 (1, 2, 3)
BQD, CQD
18
ED6, HED6
ED6, HED6
15 -125 (1, 2, 3)
15 -125 (2, 3)
25
HFD6
70 - 250 (2, 3)
BQD6,CQD6
BQD6,CQD6
BQD6, CQD6
BQD6, CQD6, ED6, HED6
ED6, HED6
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
3
1
2, 3
1
2,3
1
2, 3
1
2, 3
2, 3
35
HJD6, HJXD6
HLD6, HLXD6
200 - 400 (2, 3)
450 - 600 (2, 3)
HFD6
2, 3
50
HMD6, HMXD6
HND6
HNXD6
500 - 800 (2, 3)
500 - 1200 (2, 3)
900 - 1200 (2, 3)
65
CFD6
70 - 250 (2, 3)
65
CMD6
CND6
CPD6
500 - 800 (2, 3)
900 - 1200 (2,3)
1200 - 1600 (2,3)
200 - 600 (2, 3)
JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A, HLXD6-A
LXD6-A,
HFD6, HFXD6
JD6-A, JXD6-A, HJD6-A, HJXD6-A
LD6-A, HLD6-A
LXD6-A, HLXD6-A
HFD6, HFXD6
MD6, MXD6, HMD6, HMXD6
ND6, NXD6, HND6, HNXD6
PD6, HPD6, HPXD6
200
HFD6
6
JD6, JXD6
HJD6, HJXD6
LD6, HLD6
LXD6, HLXD6
BQD6,CQD6
ED6, HED6
HFD6
JD6, JXD6
HJD6, HJXD6
LD6, HLD6
LXD6, HLXD6
2, 3
2, 3
2, 3
HFD6
JD6, JXD6
65
CIRCUIT
BREAKERS
100
CED6
1200 - 1600 (2, 3)
15 - 125 (2, 3)
100
CFD6
70 -250 (2, 3)
100
J,R,T
200 - 600 (2, 3)
2001.10.01
6/98
HPD6, HPXD6
HJD6, HJXD6
2, 3
70
600
200 - 400
200 - 400
200 - 600
450 - 600
15 - 70
15 - 125
70
200 - 400
200 - 400
200 - 600
450 - 600
600
600
600
600
347/600
600
600
600
600
600
600
70
600
200 - 400
600
200 - 400
600
LD6, HLD6
200 - 600
600
LXD6, HLXD6
450 - 600
600
1
15 - 70
347
2
3
2, 3
1
15 - 70
15 - 70
15 - 125
15 - 70
15 - 125
70 - 250
200 - 400
347/600
347/600
600
347
600
600
600
200 - 600
600
450 - 600
600
BQD6,CQD6
ED6, HED6
BQD6,CQD6
ED6, HED6
HFD6
JD6, JXD6
HJD6, HJXD6
LD6, HLD6
LXD6, HLXD6
2, 3
2, 3
Molded Case Circuit Breakers
REFERENCE
Unusual Operating Conditions
Note: The information provided on this and the next page is intended for reference and recommendation only. Because several
variables can act on a circuit breaker’s performance at the same time, the data below is based less on controlled testing, than on
experience and engineering judgment. Contact Siemens for further information on special conditions and treatment.
Table 1 — Temperature Derating Data for Thermal-Magnetic Breakers
Ampere Rating at:
25° C
50° C
(77° F)
(122° F)
0017
0013
0022
0018
0028
0023
0033
0028
0039
0030
0044
0037
0055
0046
0066
0056
0077
0065
0099
0084
0110
0094
0137
0114
0165
0136
0192
0159
0220
0182
0247
0205
0275
0235
0330
0276
0385
0325
0440
0372
0550
0468
0660
0564
0770
0658
0880
0754
0990
0828
0900
1100
1320
1090
1540
1304
1760
1500
1980
1690
2200
1880
60° C
(140° F)
0011
0016
0021
0026
0025
0034
0042
0052
0060
0078
0087
0100
0120
0140
0160
0180
0220
0252
0301
0340
0435
0525
0613
0704
0749
0825
1000
1148
1320
1485
1650
Siemens Breaker Frames
ED
QJ
FD
JD
LD
MD
ND
PD
6
Reference
Ampere
Rating at
40° C (104° F)
0015
0020
0025
0030
0035
0040
0050
0060
0070
0090
0100
0125
0150
0175
0200
0225
0250
0300
0350
0400
0500
0600
0700
0800
0900
1000
1200
1400
1600
1800
2000
RD
13,000 (4,000)
12,000 (3,675)
CIRCUIT
BREAKERS
Altitude in Feet (Meters)
High Ambient Temperatures
Because thermal-magnetic trip breakers
are temperature sensitive and calibrated
for a specific ambient of 40° C (104° F)
(average enclosure temperature),
a higher ambient will cause the
breaker to trip at lower current than
its nameplate rating, in other words,
causing the breaker to “derate” (see
Table 1). Similarly, the current carrying
capacity of a circuit conductor is based
upon a certain ambient temperature, a
higher ambient will reduce its current
carrying capacity, causing it to “derate.”
Thus, with a fluctuating temperature,
a thermal-magnetic breaker will derate
nearly parallel with its connected circuit
conductors and maintain close circuit
protection. If the application temperature
exceeds 40° C (104° F) and is known,
either a breaker specially calibrated for
the higher ambient or one oversized
according to Table 1 may be selected. In a
case such as this, the circuit conductors
should be oversized as well.
Siemens Sensitrip® III and Type
SB Encased Systems Breakers are
insensitive to temperature changes.
However, they do include circuitry to
protect the components from abnormally
high temperatures.
Moisture — Corrosion
For atmospheres having high moisture
content and / or where fungus growth is
prevalent, a special preventive treatment
may be required.
Where the air is heavily laden with
corrosive elements, breakers made with
special corrosion-resistant finishes
may be required.
Altitude
Reduced air density at altitudes greater
than 6600 ft. (2000 meters) affects the
ability of a molded case circuit breaker
to transfer heat and interrupt faults.
Therefore, circuit breakers applied at
these altitudes should have interrupting,
insulation and continuous currents
derated as indicated in Figure 1.
11,000 (3,350)
10,000 (3,000)
9,000 (2,750)
8,000 (2,400)
7,000 (2,100)
6,000 (1,800)
1.0
.95
.90
.85
.80
.75
Rating Correction Factor
Figure 1 — Altitude Adjustment
6/99
Molded Case Circuit Breakers
REFERENCE
Unusual Operating Conditions
400 Hz Systems Siemens molded case circuit breakers
can be applied for overcurrent protection
on 400Hz systems, commonly used to
power computer installations, aircraft,
military and other specialty equipment.
Below are basic guidelines.
Circuit Breaker Derating Required
This table lists the maximum continuous
current carrying capacity for Siemens
breakers at 400Hz. Due to the increased
resistance of the copper sections
resulting from the skin effect produced
by eddy currents at these frequencies,
circuit breakers in many cases require
derating. The thermal derating on these
devices is based upon 100%, three-phase
application in open air in a maximum of
40° C (104° F) with 48 in. (1219 mm) of
the specified cable or bus at the line and
load side. Additional derating of not less
than 20% will be required if the circuit
breaker is to be utilized in an enclosure.
Further derating may be required if the
enclosure
ambient temperature exceeds 40° C
(104° F).
Cable and Bus Sizing
The cable and bus sizes to be utilized
at 400Hz are not based on standard
National Electric Codes tables for 60Hz
application. Larger cross sections
are necessary at 400Hz. All bus bars
specified are based upon mounting
the bars in the vertical plane to allow
maximum air flow. All bus bars are
spaced at a minimum of 0.25 in.
(6mm) apart. Mounting of bus bars in
the horizontal plane will necessitate
additional drafting. Edgewise orientation
of the bus may change the maximum
ratings indicated. If additional information
is required for other connections of cable
or bus, contact Siemens for information.
Application Recommendations
It is recommended that temperatures be
measured on the line and load terminals
or T-connectors of the center pole. These
are usually the hottest terminals with a
balanced load. A maximum temperature
of 75° C (35° C over a maximum ambient
of 40° C) would verify the particular
application. Temperature profiles taken
on these breakers can be correlated to
ensure that the hottest points within
the breaker are within the required
temperature limits.
Factory Configuration
When required, molded case circuit
breakers may be factory calibrated for
400Hz application. These breakers are
specially labeled for 400Hz usage and
their nameplate current rating will
include the necessary derating factory.
The highest “Maximum Continuous
Amperes” rating at 400Hz, found in the
table below approximates the highest
specially calibrated 400Hz nameplate
ampere rating available for a given frame
size. Contact Siemens for ordering
information on other breakers applied in
400Hz systems.
400Hz Breakers
Siemens
Breaker
Type
6
ED2, ED4,
ED6, HED4,
CED6
CIRCUIT
BREAKERS
FD6, FXD6,
HFD6, HFXD6,
CFD6
JXD2, JD6,
JXD6, HJD6,
HJXD6, HHJD6,
HHJXD6, CJD6
JD6, JXD6,
HJD6, HJXD6
100% Rated
The
Maximum Continuous Ampere Rating
At 40°C (104°F) 60HZ
400HZ
Enclosed
After Derating
Open Air
Open Air 015
015
012
020
020
016
025
025
020
030
030
024
035
035
028
040
040
032
045
043
034
050
048
038
060
057
046
070
067
054
080
076
061
090
086
069
095
076
100
084
110
105
095
125
119
070
063
050
080
072
058
090
080
064
090
072
100
095
075
110
084
125
105
150
125
100
175
140
112
200
160
128
225
180
144
250
200
160
200
170
136
225
190
152
250
210
168
300
240
192
350
260
208
400
300
240
200
170
170
225
190
190
250
210
210
300
240
240
350
260
260
400
300
300
information provided on this page is intended for
reference and recommendation only. Because several
variables can act on a circuit breaker’s performance at
the same time, the data above is based less on
6/100
75°C (167° F)
Copper
Cable per Pole
No of
Wire
Pieces
Size
1
#14
1
#12
1
#10
1
#10
1
#10
1
#8
1
#8
1
#8
1
#6
1
#4
1
#4
1
#3
1
#3
1
#2
1
#1
1
#4
1
#4
1
#3
1
#3
1
#2
1
#1
1
#1/0
1
#2/0
1
#3/0
1
#4/0
1
250 kcmil
1
#3/0
1
#4/0
1
250 kcmil
1
350 kcmil
1
500 kcmil
2
#3/0
2
#3/0
2
#4/0
1
250 kcmil
1
350 kcmil
1
500 kcmil
2
#3/0
Siemens
Breaker
Type
LD6, LXD6,
HLD6, HLXD6,
HHLD6,
HHLXD6,
CLD6
LD6, LXD6,
HLD6, HLXD6,
100% Rated
MD6, MXD6,
HMD6,
HMXD6, CMD6
MD6, MXD6,
HMD6,
HMXD6, CMD6
100% Rated
ND6, NXD6
HND6, HNXD6,
CND6
ND6, NXD6
HND6, HNXD6,
CND6
PD6, PXD6,
HPD6, HPXD6,
CPD6,
100% Rated
PD6, PXD6,
HPD6, HPXD6,
CPD6
RD6, RXD6,
HRD6, HRXD6
80% Rated
Maximum Continuous Ampere Rating
At 40° C (104° F) 60HZ
400/415HZ
Enclosed
After Derating
Open Air
Open Air 0250
0210
168
0300
0240
192
0350
0260
208
0400
0300
240
0450
0340
272
0500
0375
300
0600
0420
336
0250
0210
210
0300
0240
240
0350
0260
260
0400
0300
300
0450
0340
340
0500
0375
375
0600
0420
420
0500
0400
320
0600
0430
360
0700
0500
400
0800
0560
448
0500
0400
400
0600
0430
430
0700
0500
500
0800
0560
560
0800
0560
448
0900
0600
480
0650
520
1000
0780
624
1200
0900
0600
600
0650
650
1000
0780
780
1200
0780
624
1200
0850
680
1400
0960
768
1600
0780
780
1200
0850
850
1400
0960
960
1600
0960
768
1600
1800
1080
864
2000
1200
960
controlled testing, than on experience and engineering
judgment. Contact Siemens for further information on
special conditions and treatment.
Additional derating may be required if the ambient
temperature is greater than 40°C (104°F).
Calculated
75° C (167° F)
Copper
Cable per Pole
No of
Wire
Pieces
Size
1
250 kcmil
1
350 kcmil
1
500 kcmil
2
#3/0
2
#4/0
2
250 kcmil
2
350 kcmil
1
250 kcmil
1
350 kcmil
1
500 kcmil
2
#3/0
2
#4/0
2
250 kcmil
2
350 kcmil
2
250 kcmil
2
350 kcmil
3
250 kcmil
3
300 kcmil
2
250 kcmil
2
350 kcmil
3
250 kcmil
3
300 kcmil
3
300 kcmil
3
350 kcmil
3
400 kcmil
4
350 kcmil
3
350 kcmil
3
400 kcmil
4
350 kcmil
4
400 kcmil
4
500 kcmil
5
500 kcmil
4
400 kcmil
4
500 kcmil
5
500 kcmil
5
500 kcmil
5
500 kcmil
6
500 kcmil
after derating to compensate for the heating
of the copper conductor, caused by the skin effect
generated by eddy currents produced at 400/415HZ.
Molded Case Circuit Breakers
REFERENCE
Typical Specifications
General Specifications
Molded case circuit breakers shall provide circuit overcurrent protection with inverse
time and instantaneous tripping characteristics and shall be Siemens Sentron,
Sensitrip or approved equal.
All circuit breakers shall be CSA Certified and conform to applicable requirements of
NEMA Standard Publication No. AB1.
All circuit breakers shall have a quick-make, quick-break over center toggle type
mechanism and the handle mechanism shall be trip free to prevent holding contacts
closed against a short circuit or sustained overload. All circuit breaker handles shall
assume a position between “ON” and “OFF” when tripped automatically. Multipole circuit breakers shall be common-trip such that an overload or short circuit
on any one pole will result in all poles opening simultaneously. Arc extinction is to
be accomplished by magnetic arc chutes. All ratings are to be clearly visible. When
reverse feed is indicated on the drawings, in accordance with CSA, circuit breakers
with sealed trip units shall be supplied.
Solid State Sensing Specifications
As indicated on the drawings, circuit breaker frames 400
Ampere through 3200-Ampere shall have microprocessorbased RMS sensing trip units, with the capability to
measure through to the 21st harmonic. Automatic
operation of all circuit breaker frames 400A and larger shall
be obtained by means of solid state tripping elements
providing inverse time delay and (instantaneous) and/or
(short-time delay) circuit protection. Continuous current
ratings shall be adjustable from 20% to 100% of the trip
unit rating, without the need for a rating plug. Long-time
delay and instantaneous trip shall be adjustable. The
optional short-time trip function shall have adjustable
pick-up settings, three fixed times, and I2t ramp. Circuit
breaker frames 400A and larger, and where indicated on
the drawings, shall be 100% equipment rated.
Thermal Magnetic Specifications
Motor Circuit Protectors
Where indicated on the drawings and in the combination motor starter/motor
control center schedule, furnish instantaneous magnetic trip only circuit breakers for
motor short circuit protection. The magnetic trips shall be adjustable and accessible
from the front of all circuit breakers frames. The continuous current rating shall be
between 1 and 800 Amperes as indicated on the drawing.
Integral Ground
Fault Option
Main and feeder circuit breakers, as indicated on the
drawings, shall be provided with integral ground fault
protection. Ground fault pick-up shall be adjustable from
20% to 70% of the circuit breakers maximum continuous
current rating. Ground fault time delay shall be adjustable
with three 12t ramps.
Metering Option
When indicated on the drawings, solid state trip breakers
shall be furnished with a plug-in or panel mounted
metering device. This device shall simultaneously display
all three phase currents, as well as average current, ground
current, and phase unbalance. In addition it shall display
breaker status, a max log, and a trip log. The trip log will
retain and display date, time and type of trip (overload,
short circuit or ground fault) for the most recent 5 trip
events.
6
Unless otherwise noted on the drawings, all Circuit breakers 2000 Ampere
and below shall have thermal-magnetic trip units, with inverse time-current
characteristics. Automatic operation of these circuit breakers shall be obtained
by means of thermal-magnetic tripping devices located in each pole providing
inverse time delay and instantaneous circuit protection. Circuit breakers shall be
ambient compensating in that, as the ambient temperature increases over 40°C,
the circuit breaker automatically derates itself so as to better protect its associated
conductor. Thermal magnetic breakers from 250 to 2000A frames shall have thermal
interchangeable trip units, with instantaneous magnetic trip settings that are
adjustable and accessible from the front of all circuit breakers on frame sizes 250
Amperes and above. Where indicated, provide circuit breakers CSA Certified for
application at 100% of their continuous ampere rating in their intended enclosure.
The interrupting rating of the circuit breakers shall be as indicated in the
specifications, and shown on the drawing or single line diagram. The interrupting
rating of the circuit breakers shall be at least equal to the available short circuit
current at the line terminals of the circuit breaker and correspond to the CSA
Certified integrated short circuit current rating specified.
Internal Accessories
Provide shunt trips, bell alarms, and auxiliary switches as shown on the contract
drawings. Gold plated auxiliary switches shall be supplied for PLC connection. Internal
accessories for all breakers shall be CSA Certified for field installation and modification.
Where indicated on the drawings, Siemens current limiting
circuit breakers are to be furnished. Current limiting
circuit breakers shall limit the let-through I2t to a value
less than the I2t of one-half cycle wave of the symmetrical
prospective current without any fusible elements when
operating within its current range.
Series Connected Combination Specifications
Where protective devices are applied in series combination,
such that the prospective available fault current exceeds
the interrupting rating (AIR) of the downstream protective
devices, such combinations shall be CSA Certified
combinations. All electrical equipment using these CSA
Certified circuit breaker combinations shall be clearly
marked.
Connection Accessories
Unless otherwise noted, Mechanical lugs shall be provided with all Molded Case
Breakers. Where indicated on the drawings, compression lugs shall be provided
on 1200 Ampere frame and below circuit breakers. All compression lugs shall be
supplied by the Circuit Breaker Manufacturer. Where indicated on the drawings, CSA
Certified plug-in or rear connectors shall be supplied.
6/101
CIRCUIT
BREAKERS
Current Limiting Specifications
Molded Case Circuit Breakers
GENERAL
Superseded Breakers
6
CIRCUIT
BREAKERS
Sentron Series
Note
Superseded
Note
Superseded
CED62B015-CED62B125
CED62S100A
CED63A001-CED63A125
CED63B015-CED63B125
CED63S100A
-
CLE62B015-CLE62B100
CLE62S100
CLE63A001-CLE63A125
CLE63B015-CLE63B100
CLE63S100
HHED62B015-HHED62B125
HHED63B015-HHED63B125
CE2B015-CE2B100
CE2S100
CE3B015-CEB100
CE3S100
HED62B015-HED62B125
HED63B015-HED63B125
CFD62A150, CFD62L150, CFD62A250
CFD62B070-CFD62B250
CFD62S250A
CFD63A150, CFD63L150, CFD63A250
CFD63B070-CFD63B250
CFD63S250A
CJD62B200-CJD62B400
CJD62H400, CJD62L400
CJD62S400A
CJD63B200-CJD63B400
CJD63H400, CJD63L400
CJD63S400A
CPD63B120-CPD63B160
CP3B120-CP3B160
ED21B015-ED21B100
ED22B015-ED22B100
ED22S100A
ED23B015-ED23B100
ED23S100A
E21B015-E21B100
E22B015-E22B100
E22S100A
E23B015-E23B100
E23S100A
ED41B015-ED41B100
ED42B015-ED42B125
ED42S100A
ED43B015-ED43B125
ED43S100A
E41B015-E41B100
E42B015-E42B100
E42S100
E43B015-E43B100
E43S100
ED61B015-ED61B100
ED62B015-ED62B125
ED62S100A
ED63A001-ED63A125
ED63B015-ED63B125
ED63S100A
CED62B015-CED62B125
CED62B015-CED62B125
E61B015-E61B100
E62B015-E62B100
E62S100A
E63A001-E63A125
E63B015-E63B100
E63S100A
HHED62B015-HHED62B125
HHED63B015-HHED63B125
FD62B070-FD62B250
FD63B070-FD63B250
,
FXD62A150, FXD62L150, FXD62A250
FXD62B070-FXD62B250
FXD62S250A
FXD63A150, FXD63L150, FXD63A250
FXD63B070-FXD63B250
FXD63S250A
HED41B015-HED41B100
HED42B015-HED42B125
HED43B015-HED43B125
CED62B015-CED62B125
CED63B015-CED63B125
HFD62B070-HFD62B250
HFD63B070-HFD63B250
CED62B015-CED62B125
CED63B015-CED63B125
,
,
,
CLF62A150, CLF62A250
CLF62B070-CLF62B240
CLF62S250
CLF63A150, CLF63A250
CLF63B070-CLF63B250
CLF63S250
CLJ62B100-CLJ62B400
CLJ62L400, CLJ62H400
CLJ62S400
CLJ63B200-CLJ63B400
CLJ63L400, CLJ63H400
CLJ63S400
EE1B015-EE1B100
EE2B015-EE2B100
EE2S100
EE3B015-EE3B100
EE3S100
EH1B015-EH1B100
EH2B015-ED2B125
EH2S100
EH3B015-EH3B100
EH3S100
EF1B015-EF1B020
EF2B015-EF2B100
EF2S100
EF3A003, EF3J050, EF3L050-EF3A100, EF3H1
EF3B015-EF3B100
EF3S100
HED62B015-HED62B125
HED63B015-HED63B125
-
HE41B015-HE41B100
HE42B015-HE42B100
HE43B015-HE43B100
HED61B015-HED61B100
HED62B015-HED62B125
HED63B015-HED63B125
CJ2B300-CJ2B400
CJ2S400
CJ3B300-CJ3B400
CJ3S400
-
F62B070, F62B250
F63B070-F63B250
FJ62A150, FJ62L150-FJ62A250
FJ62B070-FJ62B250
FJ62S250
FJ63A150, FJ63L150-FJ63A250
FJ63B070-FJ63B250
FJ63S250
CJ2B125-CJ2B250
CJ3B125-CJ3B250
FJ2B070-FJ2B225
FJ2S225
FJ3A225
FJ3B070-FJ3B225
FJ3S225
-
HE61B015-HE61B100
HE62B015-HE62B110 or (HE2B015-HE2B100)
HE63B015-HE63B100 or (HE3B015-HE3B100)
HF62B070-HF62B250
HF63B070-HF63B250
-
HHED62B015-HHED62B125
HHED63B015-HHED63B125
HED62B015-HED62B125
HED63B015-HED63B125
HJD63B200-HJD63B400
HJ63B200-HJ63B400
HLD63B250-HLD63B600
HL63B450-HL63B600
HMD63B500-HMD63B800
HN3B500-HN3B800
-
HND63B100-HND63B120
HK3B100-HK3B120
-
HPD63B120-HPD63B160
HP3B120-HP3B160
-
HRD63B160-HRD63B200
HR3B160-HR3B200
-
1 Mechanically and electrically interchangeable.
2 Electrically interchangeable only, refer to sales office for
further details.
3 Electrically interchangeable only if the system interrupting
capacity is less than or equal to:
200 kA at 240V AC
200 kA at 480V AC
100 kA at 600V AC
6/102
4 Electrically interchangeable only if the system interrupting
capacity is less than or equal to:
200 kA at 240V AC
150 kA at 480V AC
100 kA at 600V AC
5 Refer to local sales office for replacement information.
HJ3B125-HJ3B400
HL3B450-HL3B600
6 Effective 1994 — The FD6 and FXD6 types have been
replaced by FD6-A and FXD6-A type thermal / magnetic
circuit breakers — mechanically and electrically
interchangeable with the exception that FXD6-A and FD6-A
have 22kA at 600V AC ratings versus 18kA at 600V AC for
types FXD6 and FD6.
Molded Case Circuit Breakers
GENERAL
Superseded Breakers
Sentron Series
Note
Superseded
Note
Superseded
JD62B200-JD62B400
JD63B200-JD63B400
JLB200-JL62B400
JL63B200-JL63B400
JL2B070-JL2B400
JL3B0L0-JL3B400
JXD22B200-JXD22B400
JXD22S400A
JXD23B200-JXD23B400
JXD23S400A
JD22B200-JD22B400
JD22S400
JD23B200-JD23B400
JD23S400
JXD62B200-JXD62B400
JXD62H400, JXD62L400
JXD62S400A
JXD63B200-JXD63B400
JXD63H400, JXD63L400
JXD63S400A
JJ62B200-JJ62B400
JL62L400, JL62H400
JJ62S400A
JJ63B200-JJ63B400
JL63A400, JL63H400, JL63L400
JJ63S400A
LD62B250-LD62B500
LD62B250-LD63B600
LL63B250-LL62B600
LL63B250-LL63B600
LXD62B450-LXD62B600
LXD62J600, LXD62L600
LXD62S600A
LXD63B450-LXD63B600
LXD64H600, LXD63L600
LXD63S600A
MD62B500-MD62B800
MD63B500-MD63B800
MXD62A800, MXD62H800, MXD62L800
MXD62S800A
MXD63A800, MXD63H800, MXD63L800
MXD63S800A
ND63B100-ND63B900
NXD63A120A
PD63B120-PD63B160
PXD63S160A
RD63B160-RD63B200
QJ22B060-QJ22B225
QJ22B060H-QJ22B225H
QJ22S225
QJ23B060-QJ23B225
QJ23B060H-QJ23B225H
QJH22B060-QJH22B225
QJH23B060-QJH23B225
QJH23S225
RD63B160-RD63B200
RXD63S200A
SHJD69200-SHJD69400
SHJD69200G-SHJD69400G
SHJD69200NGT-SHJD69400NGT
SHJD69200NT-SHJD69400NT
SHLD69300-SHLD69600
SHLD69300G-SHLD69600G
SHLD69300NGT-SHLD69600NG
SHLD69300NT-SHLD69600NT
SHND69100A-SHND69120A
SHND69100AG-SHND69120AG
SHPD69120-SHPD69160
SHPD69120G-SHPD69160G
LJ62B450-LJ62B600
LL2H600, LL2U600, LL2X600
LJ62S600
LJ63B450-LJ63B600
LL63H600, LL63L600
LJ63S600A
JD2B250-JD2B400
JD2S400
JD3B250-JD3B400
JD3S400
JJ2B250-JJ2B400
JL2L400-JL2H400
JJ3B200-JJ3B400
JL3H400, JL3L400, JL3A225
LL2B450-LL2B600
LL3B450-LL3B600
LL3A450, LL3H600
LL3S600
KM2B500-KM2B800
KM3B500-KM3B800
-
KM2A800, KM2H800, KM2L800
KM2S800
KM3A600, KM3H800, KM3L800
KM3S800
-
KP3B100-KP3B900
KP3S120
-
HP3B120-HP3B160
HP3S160
-
HR3B160-HR3B200
-
QJ2B125-QJ2B225
QJS225
QJ3B125-QJ3B225
-
-
QJ2H125-QJ2B225
QJ3H125-QJ3H225
QJ3S225
-
HR3B160-HR3B200
HR3S200
-
SHJ63B200-SHJ63B400G
SHJ63B200G-SHJ63B400G
SHJ63N200G-SHJ63N400G
SHJ63N200-SHJ63N400
-
SHL63B300-SHL63B600
SHL63B300G-SHL63B600G
SHL63N300G-SHL63N600G
SHL63N300-SHL63N600
-
1 Mechanically and electrically interchangeable.
2 Electrically interchangeable only, refer to sales office for
further details.
SHND69100-SHND69800
SHND69100G-SHND69800G
SHPF3B120-SHPF3B160
SHPF3B120G-SHPF3B160G
3 Electrically interchangeable only if the system
interrupting capacity is less than or equal to:
200 kA at 240V AC
200 kA at 480V AC
100 kA at 600V AC
6
CIRCUIT
BREAKERS
SHKF3B100-SHKF3B800
SHKF3B100G-SHKF3B800G
-
4 Electrically interchangeable only if the system
interrupting capacity is less than or equal to:
200 kA at 240V AC
150 kA at 480V AC
100 kA at 600V AC
5 Refer to local sales office for replacement information.
6/103
Molded Case Circuit Breakers
GENERAL
Superseded Breakers
New Sentron Series
Note
Superseded
Note
Superseded
SHND69100NGT-SHND69800NGT
SHND69100NT-SHND69800NT
SHKF3N100G-SHKF3N800G
SHKF3N100-SHKF3N800
SHK3N100G-SHK3N600G
SHK3N100-SHK3N600
SHPF3B120-SHPF3B160
SHPF3B120G-SHPF3B160G
SHPF3N120-SHPF3N160
SHPF3N120G-SHPF3N160G
SJD69200-SJ369400
SJD69200G-SJD69400G
SJD69200NGT-SJD69400NGT
SJD69200NT-SJD69400NT
SLD69300-SLD69600
SLD69300G-SLD69600G
SLD69300NGT-SLD69600NGT
SLD69300NT-SLD69600NT
SMD69600A-SMD69800A
SMD69600AG-SMD69800AG
SMD69600ANGT-SMD69800ANGT
SMD69600ANT-SMD69800ANT
SND69800A-SND69120A
SND69800AG-SND69120AG
SND69800ANGT-SND69120ANGT
SND69800ANT-SND69120ANT
SPD69120-SPD69160
SPD69120G-SPD69160G
SPD69120NGT-SPD69160NGT
SPD69120NT-SPD69160NT
—
SHP3B120-SHP3B800
SHP3B120G-SHP3B800G
SHP3N120-SHP3N800
SHP3N120G-SHP3N800G
—
—
—
—
SJL63B200-SJL63B400
SJL63B200G-SJL63B400G
SJL63N200G-SJL63N400G
SJL63N200-SJL63N400
—
—
—
—
SLL63B300-SLL63B600
SLL63B300G-SLL63B600G
SLL63N300G-SLL63N600G
SLL63N300-SLL63N600
—
—
—
—
SMD69600-SMD69800
SMD69600G-SMD69800G
SMD69600NGT-SMD69800NGT
SMD69600NT-SMD69800NT
SND69100-SND69800
SND69100G-SND69800G
SND69100NGT-SND69800NGT
SND69100NT-SND69800NT
SKMF3B600-SKMF3B800
SKMF3B600G-SKMF3B800G
SKMF3N600G-SKMF3N800G
SKMF3N600-SKMF3N800
SKPF3B100-SKPF3B600
SKPF3B100G-SKPF3B600G
SKPF3N100G-SKPF3N600G
SKPF3N100-SKPF3N600
SHPF3B120-SHPF3B160
SHPF3B120G-SHPF3B160G
SHPF3N120-SHPF3N160G
SHPF3N120G-SHPF3N160G
—
—
—
—
BQCC1B015-BQC1B030
—
—
—
—
CC1B015-CC1B030
CC2B015-CC2B030
CC3B015-CC3B030
—
—
—
—
EF2A003, EF2H050, EF2L050, EF2A100,
EF2H150, EF2L150
—
—
—
—
—
EH1B015-EH1B100
EH2B015-EH2B100
EH3B015-EH3B100
—
—
—
—
—
—
HE2A003, HE2H050, HE2L050-HE2A100
HE3A003, HE3H050, HE3L050-HE3A100
HE3B015-HE3B100
—
—
—
6
CIRCUIT
BREAKERS
1
2
3
Mechanically and electrically interchangeable.
Electrically interchangeable only, refer to sales office
for further details.
Electrically interchangeable only if the system
interrupting capacity is less than or equal to:
200 kA at 240V AC
200 kA at 480V AC
100 kA at 600V AC
6/104
4
5
Electrically interchangeable only if the system
interrupting capacity is less than or equal to:
200 kA at 240V AC
150 kA at 480V AC
100 kA at 600V AC
These units are for replacement purposes only. Consult
sales office for availability.
6
These units are no longer manufactured, and no
replacement is available.