Section 6 Molded Case Circuit Breakers Contents 6/2 Pressure and Compression Connectors Catalog Numbering System 6/4 Breaker Modifications 6/73 Applicable Standards 6/4 Internal Accessories - Feature Combinations 6/74 External Accessories 6/75 What’s New in Circuit Breakers Reference Guides Panelboard Mtg Circuit Breakers BL, GFCI, AFCI 6/5 6/13 6/70 General Technical BQ 125A Frame, Switching Neutral, DIN Rail 6/17 Enclosed Circuit Breakers 6/81 QJ 225A Frame 6/19 Series Rated Combination Guide 6/89 CQD 100A Frame and NGG 125A Frame 6/20 Unusual Operating Conditions Sentron Thermal Mag and Electronic Circuit Breakers ED 125A Frame and Internal Accessories 6/23 FD 250A Frame and Internal Accessories 6/26 JD/SJD 400A Frame and Internal Accessories 6/29 LD/SLD 600A Frame and Internal Accessories 6/33 LMD 800A Frame and Internal Accessories 6/37 MD/SMD 800A Frame and Internal Accessories 6/40 ND/SND 1200A Frame and Internal Accessories 6/44 PD/SPD 1600A Frame and Internal Accessories 6/48 RD 2000A Frame and Internal Accessories 6/51 STD 3200A Frame and Internal Accessories 6/53 Magnetic Trip Only—ETI Motor Circuit Protector 6/55 Adjustable Instantaneous Magnetic Trip Settings 6/58 Molded Case Switch—Circuit Disconnect 6/61 Sensitrip III Digital Solid State Sentron Series 6/62 SB Encased System Breakers 6/64 Electronic and Communications Accessories 6/68 6/99 Typical Specifications 6/101 Superseded Circuit Breakers 6/102 6 Molded Case Circuit Breakers INTRODUCTION What’s New? With this Speedfax, Siemens Canada Limited is proud to announce several new products. These new concepts serve the OEM and power distribution markets. CE Marking A wide range of Sentron® thermal magnetic circuit breakers has been fully tested for compliance with the European community’s Low Voltage Directive, and carry the CE mark, indicating their compliance with that directive. These are noted in the Speedfax with the stylized CE in watermark behind the catalog numbers. Declarations of conformity are available for these products. A point of misunderstanding lies in the area of handle operators. A handle operator alone, such as that for the Max-flex, since there is no applicable European Directive, may not carry the CE mark. The mark is affixed to the finished equipment that incorporates the handle, but not to this component device. Sensitrip Ammeter Display Unit Volts or lower. These very reliable low level switches overcome that limitation. Standard switch contacts should, of course, continue to be used in standard current and voltage applications DIN Rail mounted 120/240 V Breaker The Siemens BQ breakers are now available in 1- and 2-pole construction, from 15 to 60 Amps in lug in – lug out DIN rail mounted configuration. These breakers, rated 120/240 Volts, are ideal for applications in control panels and HVAC, and with their available finger safe terminal shields can qualify as service disconnects. QJ Walking Beam Interlock Potter & Brumfield Discontinued With SE&A’s divestiture of Siemens Electromechanical Components, we have ceased offering the Potter & Brumfield line of supplementary Protectors. NGG Type 125A Frame Circuit Breaker The new NGG Circuit Breaker is a compact, industrial design with true value-added features such as Global Ratings (UL/CSA/IEC/CE/NOM), flexible DIN or base mounting without the need for adapters and UL Listed for field installable accessories. This NGG125 has a 25KAIC interrupting rating at 480VAC and features a Quick Make/Quick Break Trip-free Mechanism. All this in a 3.0W x 4.8H x 2.8D package. Please consult your sales office for availability. Enhanced SB ICCB 6 CIRCUIT BREAKERS The Ammeter display for the Sensitrip® electronic trip family of breakers brings a new level of diagnostic capability even to non-interconnected breakers. Having an internal clock calendar, it can record the date and time of each trip event that occurs. Other products rely on being connected in a full network to time stamp events. This exclusive patented Siemens device provides current metering and breaker-trip diagnostic information without expensive networks. PLC Level Auxiliary Switches A new family of gold flashed auxiliary switches for the FD through ND breakers allows sensing at very low voltage and currents for interface directly to programmable logic controllers and other electronic devices. Standard contacts, built to switch 120 Volts and higher currents can be unreliable when the sensing current is in the milliamp range, and the sensing voltage is 12 6/2 Answering the growing need for 120/240 and 240 Volt standby power systems, Siemens introduces the walking beam interlock for the QJ family of 240 Volt circuit breakers. Useful in the cell tower and other commercial applications, the QJ walking beam allows interlocking two 2 pole beakers mounted using only 4 pole widths, or two 3 pole breakers using 6 pole widths. There have been several functional enhancements to the SB Systems Breaker since the last issue of the Speedfax. These include: ■ Improved reliability, including regular monthly breaker endurance testing to 8,000 operations, a new Electronic Motor Operator tested to 12,000 operations, and improved secondary disconnects ■ Extended 2 Year Standard Warranty Molded Case Circuit Breakers INTRODUCTION Ordering In the FD through RD frames, you may order molded case circuit breakers three basic ways: ■ As separately ordered frames, trip units and lugs ■ As frame, trip unit and lugs ordered as one catalog number and shipped unassembled or assembled Components Ordered Separately To get the components for a 3 pole, 400 Amp standard interrupting circuit breaker, you would order the frame (JD63F400), the trip unit (JD63T400) and six lugs (TA2J6500). This option is normally useful only if you stock and use large volumes of product and wish to reduce your inventory cost. You may stock, for example, a smaller number of frames (JD63F400) and a variety of trip units (JD63T300, JD63T350, etc.) and assemble breakers as you need them. Frame, Trip Unit and Lugs Ordered Together If you order the catalog number JD63B400, you will receive a frame, a trip unit and 6 lugs in separate packages. By suffixing this number with “L” (e.g. JD63B400L), you will receive frame, trip unit and lugs assembled in one container. Pursuant to UL 489, a product ordered thus will have the markings “LINE” and “LOAD”, and may not be “reverse fed” (with power flowing from the “OFF” end of the breaker toward the “ON” end). Connecting Breakers for DC Application Most Siemens thermal magnetic trip MCCBs are applicable on direct current (dc) systems. Generally, for 250 V dc systems a two pole breaker is used, with one pole on each leg of the supply circuit. For three pole breakers applied on 500 V dc systems, it is important to connect the power supply “zig-zag” through the breaker as shown in the figure below. This assures that the Voltage between phases on the breaker terminals is uniformly distributed. 500V DC Wiring Configuration 6 As Frame and Trip Unit shipped assembled and with the trip unit made non-removable, in compliance with UL 489 requirements that to be reverse fed the circuit breaker must not have an interchangeable trip unit. These two options are described in the following ■ Non-Interchangeable Trip Breakers If you place an “X” after the frame size designator (e.g. JXD63B400), you will receive a frame and trip unit assembled, with the trip unit made non-removable. If you suffix an “L” to this catalog number (e.g. JXD63B400L), you will recieve the breaker, non-removable trip unit and lugs assembled. Unless you anticipate a specific need to change the breaker’s ampere rating in the future, this is the preferred ordering method, as the products are assembled to Siemens’ specifications in our factories. These breakers are suitable for use reverse fed according to UL 489, since the trip unit is not removable. The smaller frames (QJ, ED and below) do not have removable trip units, and consequently are shipped only as assembled products. To add lugs, see the ordering instructions on each product’s catalog page. CIRCUIT BREAKERS New OEM Accessories, including a Bell Alarm and Alarm Relay Combination Module (SBBADMRxx), providing an alarm-only relay contact for alarms such as Ground Fault Warning and a latching alarm relay contact for trip indication. ■ Local Bell Alarm Reset (SBLBAR), providing a reset button on the breaker’s escutcheon for locally resetting the latching bell-alarm relay contact. ■ New external power supply (SPEPS24) for the EC Trip Unit, allowing operation with 24 or 48 VDC control power. ■ Price competitive, high-tech EC Trip Unit now provides phase-loss, Type-1 and Type-2 protection for switchboards. The enhanced SB Breaker, backed by a two year warranty and spearheaded by the EC Trip Unit, is continuing to improve its strong position in circuit protection and power quality applications LDU – Local Display Unit Expanding the metering capabilities of Siemens circuit breakers, the new LDU provides a central display for SB Insulated Case Circuit Breakers (both TL and EC Trip Units), Sensitrip III Molded Case Circuit Breakers, and 4300 Power Meters (now provided with or without individual displays). Capabilities include: ■ Panel-mounting for switchboard and OEM applications ■ A competitive solution when power metering is required for multiple breakers ■ Saves panel space by utilizing a centralized display to enable several 4300 Power Meters without displays to be mounted in a single section or wire gutter to monitor several branch breakers ■ Economical method of communicating power metering data of up to 32 devices ■ Compatible with WinPM 5.0 and DTU Protocol Converters ■ 6/3 Molded Case Circuit Breakers REFERENCE Catalog Numbering System If used on 250A frame and above means non-interchangeable trip breaker with factory assembled frame and trip. Solid state trip and current limiting (S or C in first character) are non-interchangeable only, and the “X” is omitted. X D Trip Unit Type — Omitted – Thermal-Magnetic S — Sensitrip® Electronic Trip Sentron Series Type/Interrupting Range — Omitted – Standard Rating H — High IC Rating HH — Extra High IC Rating C — Highest IC Rating and Current Limiting Frame Identifier E — Type ED F — Type FD J — Type JD L — Type LD LM — Type LMD M N P R T — Type MD — Type ND — Type PD — Type RD — Type TD Maximum Voltage 2 — 240 Vac 4 — 480 Vac 6 — 600 Vac Number of Poles 1 2 3 9 used to indicate the max. functions for an electronic trip circuit breaker (always 3 poles) (Specific Application Type) B — Standard 40°C Breaker M — Calibrated for 50°C Application F — Frame Only T — 40°C Trip Unit Only W — 50°C Trip Unit Only S — Molded Case Switch L — Low Instantaneous Range ETI Breaker A — Standard Range ETI Breaker H — High Instantaneous Range ETI Breaker 6 CIRCUIT BREAKERS Maximum Continuous Current Rating ED Frame — 015, 020, 025, 030, 035, 040, 045, 050, 060, 070, 080, 090, 100, 110, 125 FD Frame — 070, 080, 090, 100, 110, 125, 150, 175, 200, 225, 250 JD Frame — 200, 225, 250, 300, 350, 400 LD Frame — 250, 300, 350, 400, 450, 500, 600 LMD Frame — 500, 600, 700, 800 MD Frame — 500, 600, 700, 800 ND Frame — 900, 100 (1000A), 120 (1200A) PD Frame — 120 (1200A), 140 (1400A), 160 (1600A) RD Frame — 160 (1600A), 180 (1800A), 200 (2000A) TD Frame — 2000, 2500, 3200 Suffix L — where applicable indicates a breaker shipped with line/loads lugs installed A — used with a switch to show automatic self protection Y — 400 Hertz H — 100% rated NOTE: — Position omitted if not used. Applicable Standards UL489 — Molded Case Circuit Breakers and Circuit Breaker Enclosures. UL486A — Wire Connectors and Solderless Lugs for use with copper wire UL486B — Wire Connectors and Solderless Lugs for use with aluminum wire UL943 — Ground Fault Interrupters (for personnel protectors) UL1087 — Molded Case Switches UL50 — Cabinets and Boxes Note: (A) Molded case circuit breakers are designed and tested in accordance to applicable portions of UL489 and CSAC22.2 No 5 and meet application requirements of the National Electric Code. Unless marked otherwise, circuit breakers are 80% duty rated. (B) Molded case circuit breakers are to be connected with 60 or 75°C wire for circuit breakers having a rated ampacity of 125 amperes or less. Circuit breakers having a rated ampacity greater than 125 amperes shall only be cabled with 75°C cable unless otherwise indicated on the circuit breaker label. Exceptions to this rule are outlined in the article 110-14 C(1)(2) of the 2002 National Electric Code and Canadian Electrical Code. 6/4 UL869 — Service Equipment NEMA AB-1 — Molded Case Circuit Breakers and Molded Case Switches CSA–C22.2 No. 5, C22.2 No. 14 Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Load Center Breakers QT Page 1-22, 1-27 1-22, 1-27 1-22, 1-27 1-27 1, 2, 3 1, 2, 3 Amperes, Continuous 15–50 15–125 15–125 15–125 100–200 Ratings CSA/UL Interrupting Rating — Symmetrical RMS Amperes 2-Pole 120/240 BLH HBL BQD, BQD6 2 1-27 6-13 6-13 6-13 6-16 2,3 1, 2, 3, 1, 2, 3 1, 2, 3 1, 2, 3 120/240 120/240 150–200 15–125 15–125 15–100 15–100 120/240 120/240 120/240 120/240 277 3-Pole — 240 240 240 240 240 240 240 240 480/277 120V 10,000 10,000 22,000 65,000 — — 10,000 22,000 65,000 65,000 240V 10,000 10,000 22,000 65,000 100,000 10,000 10,000 22,000 65,000 65,000 277V — — — — — — — — — 10,000 347V — — — — — — — — — 14,000 480/277V — — — — — — — — — 10,000 14,000 600/347V — — — — — — — — — Volts — 2-Pole — — — — — — — — — 250 Interrupting Rating — DC Amperes — — — — — — — — — 14,000 4.50 Height Dimensions in inches Width Depth 15–50A — 2.87 2.87 — — 7.00 3.56 3.56 — 15–30A — — — — — — — 3.75 — — 15–60A 3.12 — — — — — — — — — 55–125A — 3.12 3.12 3.12 3.12 3.00 3.75 — 3.75 4.50 1-Pole 1.00 1.00 1.00 1.00 — — 1.00 1.00 1.00 1.00 2-Pole 2.00 2.00 2.00 2.00 4.00 2.00 2.00 2.00 2.00 3-Pole 2.00 3.00 3.00 3.00 — 3.00 3.00 3.00 3.00 3.00 2.23 2.06 2.37 2.37 2.37 2.37 2.34 2.37 2.37 2.69 Thermal and Fixed Magnetic Trip Molded Case Switch — — — — — — — — — Undervoltage Trip — — — — — — — — — Shunt Trip — — Auxiliary Switch — — — — — Alarm Switch — — — — — — — — — Type 1 — Indoor Surface — — — — — Type 1 — Indoor, Flush — — — — — — Type 3R — Outdoor-Rainproof — — — — — — CIRCUIT BREAKERS Individual Enclosures 120/240 120/240 1, 2, 3 BL HQPPH QPJ 1-23 AC Accessories & Modifications HQP, HQPP 1, 2 1-Pole Overcurrent Devices Panelboard Breakers QPH, QPPH Poles Volts (60 Hertz) DC QP, QPP 6 Thermal-Magnetic Trip Breakers QP, QPH, HQP For inches / millimeters conversion, see Application Data section. BQD6 CSA cerified 10,000A @ 600Y/347V 15–70A only. Types QPP, QPPH, HQPP and HQPPH are special 2-pole configurations for load center mains. Amperage range = 125–225A, width = 4 in. BL, BLH, HBL Single pole breakers available in ratings 15–70A only. 125A, 2-pole 120/240V AC only. 14,000A IR at 277/480V AC only. Not applicable to types QPP and QPPH. Single pole circuit breakers available in ratings 15-70A only, 125A available as a 2-pole only. Not applicable to type HQPP. BQD, BQD6 Fits only Siemens EQIII load centers. Breaker is 2 or 3 poles wide. 6/5 Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Thermal-Magnetic Trip Breakers General Purpose Breakers Page Poles Amperes, Continuous Ratings CSA/UL Interrupting Rating — Symmetrical RMS Amperes DC QJ2-H HQJ2-H CQD NGG 6-19 6-19 6-20 6-21 1, 2, 3 1, 2, 3 2, 3 2, 3 2, 3 3 1, 2, 3 1, 2, 3 15–70 15–70 15–50 — — — — 15–100 15–100 2-Pole 15–125 15–100 15–70 15–100 60–225 15–125 15–100 60–225 15–100 15–100 60–225 — 3-Pole 100–225 15–100 15-125 — — — — 277 347 480/277 600/347 120/240 120/240 120/240 3-Pole 240 240 240 120V 10,000 22,000 65,000 — — — — 65,000 65,000 240V 10,000 22,000 65,000 10,000 22,000 42,000 100,000 65,000 65,000 240 240 — 240 240 — — — — — — — 14,000 25,000 — — — — — — — 10,000 18,000 Volts — 2-Pole — — — — — — — 250 250 Interrupting Rating — DC Amperes — — — — — — — 14,000 14,000 15–50A 3.75 3.75 4.00 — — — — 4.50 — 55–125A 4.00 4.00 4.00 — — — — 4.50 — 60–225A — — — 7.00 7.00 7.00 7.00 — — 1-Pole 1.00 1.00 1.00 — — — — 1.00 1.00 2-Pole 2.00 2.00 2.00 3.00 3.00 3.00 — 2.00 2.00 3-Pole 3.00 3.00 3.00 4.50 4.50 4.50 4.50 3.00 3.00 2.37 2.37 2.37 2.34 2.34 2.53 2.53 2.87 2.90 Thermal and Fixed Magnetic Trip Molded Case Switch — — — — — — — Width Depth 6 Individual Enclosures QJH2 6-19 480/277V Dimensions in inches Accessories & Modifications QJ2 6-19 600/347V Height Overcurrent Devices HBQ 6-17 1, 2, 3 2-Pole AC BQH 6-17 1-Pole 1-Pole Volts (60 Hertz) BQ 6-17 Undervoltage Trip — — — — — — — — Shunt Trip Auxiliary Switch Alarm Switch — — — — — Mechanical Interlock — — — — — Fungus Proofing (ref. page 106) Type 1 — Indoor Surface — Type 1 — Indoor, Flush — Type 3R — Outdoor-Rainproof — CIRCUIT BREAKERS BQ, BQH, HBQ QJ2, QJH2, QJ2-H For inches / millimeters conversion, see Application Data section. 3-pole breakers only (factory installed only). Type CQD6—CSA only. 6/6 6 CQD NGG Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Poles Amperes, Continuous Volts 50/60HZ AC Ratings CSA / UL Interrupt Rating Symmetrical RMS Amperes 220/240V IEC 947-2 380/415V 50/60HZ 500V DC Dimensions in inches Overcurrent Devices Accessories & Modifications Individual Enclosures 2-Pole, 250V DC Interrupting Ratings 3-Pole, 500V DC Interrupting Ratings Height Width Depth Thermal and Fixed Magnetic Trip Thermal and Adjustable Magnetic Trip Adjustable Magnetic Trip Only Motor Circuit Protector Molded Case Switch Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Rear Connection Studs Electric Motor Operator Plug-In Mounting Assembly Fungus Proofing (ref. page 106) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight Type 5, 12 — Lint, Fine Dust, Oils, Coolants Type 12K — Semi-Dusttight ED2 6-23 1, 2, 3 15–100 1-Pole 120 2-Pole 240 3-Pole 120V 10,000 240V 10,000 277V — 347V — 480V — 600V — Icu — Ics — Icu — Ics — Icu — Ics — 5,000 — 6.34 1-Pole 1.00 2-Pole 2.00 3-Pole 3.00 4.00 — ED4 6-23 1, 2, 3 15–125 277 ED6 6-23 1, 2, 3 15–125 347 HED4 6-24 1, 2, 3 15–125 277 480 600 480 FD6A, CED6 FXD6A 6-24 6-26 2, 3 2, 3 15–125 70–250 — — 600 — — — — 65,000 65,000 100,000 200,000 22,000 — 165,000 — — 30,000 — — 18,000 25,000 142,000 1200,000 — 18,000 — 1100,000 65,000 — 200,000 — 17,000 — — 35,000 — 200,000 — 19,000 — — — 18,000 — — 15,000 — — — 30,000 30,000 30,000 30,000 — 18,000 — 50,000 6.34 6.34 6.34 9.26 1.00 1.00 1.00 — 2.00 2.00 2.00 2.00 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 — — — — HFD6, HFXD6 6-27 2, 3 70–250 — HHFD6, HHFXD6 6-27 2, 3 70–250 — CFD6 6-27 2, 3 70–250 — 600 600 600 600 — 65,000 — — 35,000 18,000 65,000 33,000 35,000 18,000 20,000 10,000 30,000 18,000 9.50 — 4.50 4.50 4.00 — — 100,000 — — 165,000 125,000 100,000 150,000 165,000 133,000 142,000 121,000 30,000 25,000 9.50 — 4.50 4.50 4.00 — — — 200,000 200,000 — — — — 100,000 200,000 125,000 100,000 200,000 — 100,000 — 100,000 — 150,000 — 165,000 — 133,000 — 30,000 — — 50,000 11.00 14.12 — — 4.50 4.50 4.50 4.50 4.00 4.00 — — — — — — — — — — — — — — — — — — — — 6 Page General Purpose Breakers — For inches / millimeters conversion, see Application Data section. 1-pole only. 40–100A: 25,000 AIR at 277V AC. For DC UPS system application. Single pole ED6 (15–30A) 30kA, (35–100A) 18 kA. CSA Only. 6/7 CIRCUIT BREAKERS Thermal-Magnetic Trip Breakers Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Thermal-Magnetic Trip Breakers General Purpose Breakers JD6-A, HJD6-A, JXD2-A JXD6-A HJXD6-A 6-29 6-29 6-30 2, 3 2, 3 2, 3 200-400 200-400 200-400 Page Poles Amperes, Continuous Volts 50/60HZ CSA / UL AC Interrupt Rating Symmetrical RMS Amperes Ratings 220/240V IEC 947-2 380/415V 50/60HZ 500V DC Dimensions in inches Overcurrent Devices Accessories & Modifications 6 Individual Enclosures 2-Pole 250V DC Interrupting Ratings 3-Pole, 500V DC Interrupting Ratings Height Width Depth Thermal and Adjustable Magnetic Trip Adjustable Magnetic Trip Only Motor Circuit Protector Molded Case Switch Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Rear Connection Studs Electric Motor Operator Plug-In Mounting Assembly Fungus Proofing (ref. page 106) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight LD6, LXD6 6-33 2, 3 450-600 HLD6, HLXD6 6-33 2, 3 250-600 HHLD6, HHLXD6 6-34 2, 3 250-600 CLD6 6-34 2, 3 450-600 240 600 600 600 600 600 600 600 600 65,000 — — — — — — — — 30,000 — 11.00 65,000 35,000 25,000 65,000 33,000 40,000 20,000 30,000 15,000 30,000 25,000 11.00 100,000 065,000 035,000 100,000 050,000 065,000 033,000 042,000 021,000 030,000 035,000 11.00 200,000 100,000 150,000 200,000 100,000 100,000 150,000 165,000 133,000 — — 11.00 200,000 150,000 100,000 — — — — — — 30,000 50,000 17.86 65,000 35,000 25,000 65,000 33,000 40,000 20,000 30,000 15,000 30,000 25,000 11.00 100,000 165,000 135,000 100,000 150,000 165,000 133,000 142,000 121,000 130,000 135,000 11.00 200,000 100,000 150,000 200,000 100,000 100,000 150,000 165,000 133,000 — — 11.00 200,000 150,000 100,000 — — — — — — 130,000 150,000 17.86 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 7.50 1 14.00 — — — — — — — — — — — — — — — — — — — — — — — — CIRCUIT BREAKERS Type 12K — Semi-Dusttight — — — For DC UPS application. 6/8 2-Pole 3-Pole CJD6 6-30 2, 3 200-400 Type 5, 12 — Lint, Fine Dust, Oils, Coolants For inches / millimeters conversion, see Application Data section. 2-Pole 3-Pole 240V 480V 600V Icu Ics Icu Ics Icu Ics HHJD6-A, HHJXD6-A 6-30 2, 3 200-400 Molded Case Circuit Breakers SELECTION / APPLICATION General Purpose Breakers LMD6, HLMD6, MD6, LMXD6 HLMXD6 MXD6 6-37 6-37 6-40 2, 3 2, 3 2, 3 500-800 500-800 500-800 Page Poles Amperes, Continuous Volts 50/60 HZ CSA / UL AC Interrupt Rating Symmetrical RMS Amperes Ratings 220/240V IEC 947-2 380/415V 50/60HZ 500V DC Dimensions in inches Overcurrent Devices Accessories & Modifications Individual Enclosures 2-Pole 250V DC Interrupting Ratings 3-Pole, 500V DC Interrupting Ratings Height Width Depth Thermal and Fixed Magnetic Trip Thermal and Adjustable Magnetic Trip Adjustable Magnetic Trip Only Motor Circuit Protector Molded Case Switch Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Rear Connection Studs Electric Motor Operator Plug-In Mounting Assembly Fungus Proofing (ref. page 6/73) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 5, 12 — Lint, Fine Dust, Oils, Coolants Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight Type 12K — Semi-Dusttight For 2-Pole 3-Pole 240V 480V 600V Icu Ics Icu Ics Icu Ics 2-Pole 3-Pole HMD6, HMXD6 6-41 2, 3 500-800 CMD6 6-41 3 400-800 ND6, NXD6 6-44 2, 3 800-1200 HND6, HNXD6 6-45 2, 3 800-1200 CND6 6-45 3 800-1200 600 600 600 600 600 600 600 600 65,000 50,000 25,000 65,000 33,000 40,000 20,000 30,000 15,000 30,000 25,000 16.00 100,000 165,000 125,000 100,000 150,000 165,000 133,000 142,000 121,000 130,000 150,000 16.00 65,000 50,000 25,000 65,000 33,000 40,000 20,000 30,000 15,000 30,000 25,000 16.00 100,000 165,000 150,000 100,000 150,000 165,000 133,000 142,000 121,000 130,000 150,000 16.00 65,000 50,000 25,000 65,000 33,000 40,000 20,000 30,000 15,000 30,000 25,000 16.00 100,000 165,000 150,000 100,000 150,000 165,000 133,000 142,000 121,000 130,000 150,000 16.00 7.50 7.50 9.00 9.00 9.00 9.00 4.59 — 4.59 — 6.19 — 6.19 — 200,000 100,000 165,000 200,000 100,000 100,000 150,000 165,000 133,000 130,000 150,000 16.00 — 9.00 6.19 — 6.19 — 6.19 — 200,000 100,000 165,000 200,000 100,000 100,000 150,000 165,000 133,000 130,000 150,000 16.00 — 9.00 6.19 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — DC UPS application. For inches / millimeters conversion, see Application Data section. 6/9 CIRCUIT BREAKERS Thermal-Magnetic Trip Breakers 6 Reference Guide Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Thermal-Magnetic Trip Breakers Page Poles Amperes, Continuous Volts 50/60 HZ CSA / UL Ratings AC Interrupt Rating Symmetrical RMS Amperes 220/240V IEC 947-2 380/415V 50/60HZ 500V 3-Pole 240V 480V 600V Icu Ics Icu Ics Icu Ics 2-Pole 250V DC Interrupting Ratings DC 3-Pole, 500V DC Interrupting Ratings Dimensions in inches Overcurrent Devices Accessories & Modifications Individual Enclosures Circuit breakers require Connect-all mounting block. Dimensions shown are for circuit breaker only. Height Width Depth 6 Thermal and Adjustable Magnetic Trip Molded Case Switch Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Electric Motor Operator Fungus Proofing (ref. page 106) Mounting Block (required) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight General Purpose Breakers HPD6, PD6 , HPXD6 PXD6 6-48 6-48 3 3 1200-1600 1200-1600 11,600 111,600 65,000 100,000 165,000 50,000 150,000 25,000 65,000 100,000 150,000 33,000 40,000 165,000 117,000 10,000 142,000 30,000 18,000 121,000 130,000 30,000 25,000 150,000 16.00 16.00 19.00 19.00 16.19 16.19 — — — — — — — — — — — — — — — — — — CIRCUIT BREAKERS 6/10 HRD6, HRXD6 6-51 3 1600-2000 111,600 100,000 165,000 150,000 100,000 150,000 165,000 117,000 142,000 121,000 130,000 150,000 16.00 19.00 16.19 — — — — — — Type 12K — Semi-Dusttight DC UPS application. Connect-all mounting assembly. Dimensions shown are for circuit breaker only. Requires RD6 , RXD6 6-51 3 1600-2000 11,600 65,000 50,000 25,000 65,000 33,000 40,000 10,000 30,000 18,000 30,000 25,000 16.00 19.00 16.19 — — — — Type 5, 12 — Lint, Fine Dust, Oils, Coolants For inches / millimeters conversion, see Application Data section. For CPD6 6-48 3 1200-1600 111,600 200,000 100,000 165,000 200,000 100,000 100,000 125,000 165,000 117,000 130,000 150,000 16.00 19.00 16.19 — — — — — Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Electronic Trip Breakers Solid State Trip Cicuit Breakers Page Ratings AC Poles Amperes, Continuous Volts 50/60 HZ Interrupt Rating Symmetrical RMS CSA / UL Amperes 3-Pole 240V 480V 600V SJD6 SHJD6 SCJD6 SLD6 SHLD6 SCLD6 SMD6 SHMD6 SCMD6 6-31 3 200-400 600 65,000 35,000 25,000 11.00 17.50 14.00 6-31 3 200-400 600 100,000 165,000 135,000 11.00 17.50 14.00 6-31 3 200-400 600 200,000 150,000 100,000 17.86 17.50 14.00 6-35 3 300-600 600 65,000 35,000 25,000 11.0 17.50 14.00 6-35 3 300-600 600 100,000 165,000 135,000 11.00 17.50 14.00 6-35 3 300-600 600 200,000 150,000 100,000 17.86 17.50 14.00 6-42 3 600-800 600 65,000 50,000 25,000 10.00 19.00 16.19 6-42 3 600-800 600 100,000 165,000 150,000 16.00 19.00 16.19 6-42 3 600-800 600 200,000 100,000 165,000 16.00 19.00 16.19 Dimensions in inches Height Width Depth Overcurrent Devices Solid State Trip Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Rear Connection Studs Electric Motor Operator Plug-In Mounting Assembly Fungus Proofing (ref. page 106) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight — — — — — — — — — — — — — — — — — — — — — — — — — — — — Accessories & Modifications — Type 5, 12 — Lint, Fine Dust, Oils, Coolants Type 12K — Semi-Dusttight — — — CIRCUIT BREAKERS 6 Individual Enclosures 3-Pole For inches / millimeters conversion, see Application Data section. 6/11 Molded Case Circuit Breakers SELECTION / APPLICATION Reference Guide Electronic Trip Breakers Insulated Case Circuit Breakers Solid State Trip Circuit Breakers Page Poles Amperes, Continuous Volts 50/60HZ Ratings CSA / UL AC Interrupt Rating Symmetrical RMS Amperes 380/415V EC 947-2 50/60HZ 690V Dimensions in inches Overcurrent Devices Accessories & Modifications Individual Enclosures 3-Pole 240V 480V 600V Icu Ics Icu Ics Height Width Depth SND6 SHND6 SCND6 SPD6 SHPD6 STD6 SHTD6 SHHTD6 SBA SBS 6-46 3 800-1200 600 65,000 50,000 25,000 — — — — 16.00 19.00 16.19 6-46 3 800-1200 600 100,000 165,000 150,000 — — — — 16.00 19.00 16.19 6-46 3 800-1200 600 200,000 100,000 165,000 — — — — 16.00 19.00 16.19 6-49 3 1200-1600 600 65,000 50,000 25,000 — — — — 16.00 19.00 16.19 6-49 3 1200-1600 600 100,000 165,000 150,000 — — — — 16.00 19.00 16.19 6-53 3 2000-3200 600 65,000 35,000 25,000 — — — — 27.5 14.12 11.38 6-53 3 2000-3200 600 100,000 165,000 135,000 — — — — 27.5 14.12 11.38 6-53 3 2000-3200 600 200,000 150,000 100,000 — — — — 27.5 14.12 11.38 6-64 3 400-2000 600 65,000 65,000 50,000 — — — — — — — 6-64 6-64 3 3 400-500 2000-5000 600 600 150,000 200,000 100,000 150,000 85,000 100,000 100 — 100 — 165 — 165 — — — — — — — SBH 6 Solid State Trip Undervoltage Trip Shunt Trip Auxiliary Switch Alarm Switch Mechanical Interlock Rear Connection Studs Electric Motor Operator Plug-In Mounting Assembly Stored Energy Mechanism Drawout Construction Fungus Proofing (ref. page 106) Type 1 — Indoor Surface Type 1 — Indoor, Flush Type 3R — Outdoor-Rainproof Type 7 — Flammable Gas Atmosphere Type 9 — Combustion Dusttight — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Type 5, 12 — Lint, Fine Dust, Oils, Coolants — — — — — — — — Type 12K — Semi-Dusttight — — — — — — — — — — CIRCUIT BREAKERS For inches / millimeters conversion, see Application Data section. 6/12 Requires connect-all mounting block assembly. Dimensions shown are for circuit breaker. Breaker has rating plugs which can be changed within each frame rating. Molded Case Circuit Breakers SELECTION / APPLICATION Panelboard Mounting Circuit Breakers Type BL–Low Tab Bolt-on (10,000A IR) Non-Interchangeable Trip Continuous Current Rating @ 40° C 1-Pole 2-Pole 2-Pole 3-Pole 120/240V AC 120/240V AC Common Trip 240V AC Common Trip 240V AC Common Trip Catalog Number Catalog Number Catalog Number 015 020 025 030 035 040 045 050 060 B115 B120 B125 B130 B135 B140 B145 ■ B150 B160 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 B215 B220 B225 B230 B235 B240 B245 B250 B260 070 B170 65.00 B270 133.00 68.00 68.00 68.00 68.00 68.00 68.00 68.00 68.00 68.00 Catalog Number 181.00 181.00 181.00 181.00 181.00 181.00 181.00 181.00 181.00 B315 227.00 B320 227.00 B325 227.00 B330 227.00 B335 227.00 B340 227.00 B345 227.00 B350 227.00 B360 227.00 B270R ■ 240.00 B370 278.00 B280R ■ 273.00 B290R ■ 273.00 B2100R ■ 273.00 B380 314.00 B390 314.00 B3100 314.00 B215R ■ B220R ■ B225R ■ B230R ■ B235R ■ B240R ■ B245R ■ B250R ■ B260R ■ 080 090 100 — — — B280 181.00 B290 181.00 B2100 181.00 110 125 — — B2110 ■ 364.00 B2125 385.00 — — — — Type BLH – Low Tab Bolt-on (22,000A IR) 015 020 B115H 59.00 B120H 59.00 B215H 133.00 B220H 133.00 — — B315H 341.00 B320H 341.00 025 030 040 050 060 B125H 66.00 B130H 66.00 B140H 66.00 B150H ■ 66.00 B160H ■ 66.00 B225H 133.00 B230H 133.00 B240H 133.00 B250H 133.00 B260H 133.00 — — — — — B325H 341.00 B330H 341.00 B340H 341.00 B350H 341.00 B360H 341.00 070 B170H ■ 83.00 B270H 205.00 — B370H 414.00 B280H 291.00 B290H 291.00 B2100H291.00 — — — B380H 486.00 B390H 486.00 B3100H486.00 080 090 100 — — — — — — B115HH B120HH B130HH 101.00 101.00 101.00 B215HH247.00 B220HH247.00 B230HH247.00 — — — B315 HH429.00 B320HH429.00 B330HH429.00 040 050 060 B140HH B150HH ■ —— 118.00 118.00 B240HH302.00 B250HH302.00 B260HH302.00 — — — B340HH522.00 B350HH522.00 B360HH522.00 070 ——-- B270HH ■ 494.00 — B370HH558.00 080 090 100 ——-——-——-- B280HH ■ 558.00 B290HH ■ 558.00 B2100HH558.00 — — — B380HH656.00 B390HH656.00 B3100HH656.00 Types BL/BLH/HBL Internal Accessories (Factory installed only; require one additonal pole width) Auxiliary Switches Control Voltage Shunt Trip 1A and 1B AC DC Suffix Suffix 120V — ...00S01 ■ ...01 ■ 24V — ...00S07 ■ ...01 ■ ■ Built to order. Allow 3–4 weeks for delivery. CSA Certified / UL Listed for frequent switching applications (SWD). 120V AC fluorescent lighting. For 400 cycle CSA Certified/ UL Listed devices, add “Y” suffix to catalog number. Add 25% to list price. 5000A interrupting rating — Built To Order. CSA Certified / UL Listed for 3 phase 240V grounded B at 10,000 AIR. rated. HACR Modifications - page 6/73 Accessories - page 6/75 to 6/80 6/13 CIRCUIT BREAKERS 015 020 030 6 Type HBL – Low Tab Bolt-on (65,000A IR) Molded Case Circuit Breakers SELECTION Panelboard Mounting Circuit Breakers Ordering Instructions All BL circuit breakers are supplied with load side connectors. All standard circuit breakers are calibrated for 40° C maximum ambient application. Shipping Weights - BL, BLH, HBL Number of Poles Number Per Carton /Master Shipping Weight (lbs.) Master 1 2 (15–50A) 2 (60–70A) 2 (80–125A) 3 (15–100A) 12/48 6/24 6/24 6/24 4/16 15.3 15.3 19.4 24.9 20.1 Lugs (Load Side) Type Circuit Breaker Ampere Rating 15–40 25-35 40-50 BL, BLH, HBL 55-70 80-100 110-125 Cables Per Lug Wire Range Cu/Al 1 #14–#10 AWG Cu 1 #12-#10 AWG AI 1 #14–#6 AWG Cu 1 #12-#6 AWG AI 1 #8–#6 AWG Cu 1 #8-#4 AWG AI 1 #8–#4 AWG Cu 1 #8-#2 AWG AI 1 #4–#1/0 AWG Cu 1 #2-#1/0 AWG AI 1 #2–#1/0 AWG Cu 1 #1/0-#2/0 AWG AI Catalog Number Fixed in Breaker BL/BLH/HBL 6 CIRCUIT BREAKERS For inches / millimeters conversion, see Application Data section. 6/14 Dimensions (inches) Breaker Type Amperes L D1 D2 BL, BLH BL, BLH HBL 15–50 55–125 15–125 39⁄16 33⁄4 33⁄4 23⁄8 23⁄8 23⁄8 3 3 3 Accessories page 6/75 to 6/ 80. Molded Case Circuit Breakers SELECTION Special Application Panelboard Mounting Breakers GFCI Personnel Protection (Class A) (5MA) Complete Breaker UL Unenclosed 1-Pole BLF 2-Pole BLHF 1-Pole BLHF 2-Pole Ampere Rating Catalog Number 120 120/240 240 15 20 25 30 BF115 BF120 BF125 ■ BF130 293.00 293.00 293.00 293.00 10 10 10 10 — — — — — — — — 15 20 30 40 50 60 BF215 BF220 BF230 BF240 ■ BF250 ■ BF260 ■ 349.00 349.00 349.00 349.00 349.00 349.00 — — — — — — 10 10 10 10 10 10 — — — — — — 15 20 30 BF115H 581.00 BF120H 581.00 BF130H ■ 581.00 22 22 22 — — — — — — 15 20 30 40 50 60 BF215H ■ 633.00 BF220H ■ 633.00 BF230H ■ 633.00 BF240H ■ 633.00 BF250H ■ 633.00 BF260H ■ 633.00 — — — — — — 22 22 22 22 22 22 — — — — — — 10 10 10 — — — — — — 468.00 468.00 468.00 468.00 468.00 468.00 — — — — — — 10 10 10 10 10 10 — — — — — — 20 30 BE120H ■ 581.00 BE130H ■ 581.00 22 22 — — — — 15 20 30 40 50 60 BE215H ■ 848.00 BE220H ■ 848.00 BE230H ■ 848.00 BE240H ■ 848.00 BE250H ■ 848.00 BE260H ■ 848.00 — — — — — — 22 22 22 22 22 22 — — — — — — 279.00 279.00 10 10 — — — — 15 20 B115AFH 553.00 B120AFH 553.00 22 22 — — — — 15 20 30 B115HID ■ 38.00 B120HID 38.00 B130HID ■ 38.00 10 10 10 — — — — — — 15 20 30 B215HID ■ 81.00 B220HID 81.00 B230HID ■ 81.00 — — — 10 10 10 — — — EQF Equipment Protection (30MA) 15 BE115 ■ 356.00 BLE BE120 356.00 20 1-Pole 120V AC BLE 2-Pole 120/240V AC BLEH 1-Pole BLEH 2-Pole 30 15 20 30 40 50 60 BE130 356.00 BE215 ■ BE220 BE230 BE240 ■ BE250 ■ BE260 ■ AFCI Arc Fault Circuit Interrupter 15 B115AF BAF B120AF 20 1-Pole BAFH 1-Pole HID Lighting BL 1-Pole BL 2-Pole Switching Neutrals 15 BG 2 Wire Common Trip 20 30 BG215 ■ 105.00 BG220 ■ 105.00 BG230 ■ 105.00 10 10 10 — — — — — — BG 15 20 30 BG315 ■ 158.00 BG320 ■ 158.00 BG330 ■ 158.00 — — — 10 10 10 — — — 3 Wire Common Trip 1 Pole 2˝ 2 Pole 6 BLF 1˝ Volts AC B115AF BG ■ Built to order. Allow 2–3 weeks for delivery. HACR rated. Meets 2002 NEC Section 210-12. CSA Certified / UL Listed for frequent switching applications (SWD). 120V AC fluorescent lighting. 6/15 CIRCUIT BREAKERS Breaker Type Interrupting Ratings (KA) (RMS Symmetrical Amperes) Molded Case Circuit Breakers SELECTION BQD 100A Frame Panelboard Mounting Circuit Breakers BQD 2-Pole 480Y/277V AC– 125/250V DC 1-Pole 277V AC–125V DC Continuous Current Rating @ 40°C 15 20 25 30 35 40 45 50 60 70 80 90 100 Catalog Number 3-Pole 480Y/277V AC Catalog Number BQD115 BQD120 BQD125 BQD130 BQD135 BQD140 BQD145■ BQD150 BQD160 BQD170■ BQD180■ BQD190 BQD1100■ 105.00 105.00 105.00 105.00 105.00 105.00 105.00 105.00 105.00 221.00 221.00 221.00 221.00 BQD215 BQD220 BQD225 BQD230 BQD235 BQD240 BQD245 BQD250 BQD260 BQD270 BQD280 BQD290 BQD2100 Catalog Number 258.00 258.00 258.00 258.00 258.00 258.00 258.00 258.00 258.00 526.00 526.00 526.00 526.00 BQD315 BQD320 BQD325 BQD330 BQD335 BQD340 BQD345 BQD350 BQD360 BQD370 BQD380 BQD390 BQD3100 459.00 459.00 459.00 459.00 459.00 459.00 459.00 459.00 459.00 625.00 625.00 625.00 625.00 BQD, BQD6 BQD6 CSA Certified 2-Pole 600/347V AC 1-Pole 347V AC Continuous Current Rating @ 40°C 15 20 25 30 35 40 45 50 60 70 Catalog Number BQD6115 BQD6120 BQD6125■ BQD6130 BQD6135■ BQD6140 BQD6145■ BQD6150 BQD6160 BQD6170 3-Pole 600/347V AC Catalog Number 105.00 105.00 105.00 105.00 105.00 105.00 105.00 105.00 105.00 221.00 Catalog Number BQD6215 258.00 BQD6220 258.00 BQD6225■258.00 BQD6230 258.00 BQD6235■258.00 BQD6240 258.00 BQD6245■258.00 BQD6250 258.00 BQD6260 258.00 BQD6270 526.00 BQD6315 BQD6320 BQD6325■ BQD6330 BQD6335■ BQD6340 BQD6345■ BQD6350 BQD6360 BQD6370 459.00 459.00 459.00 459.00 459.00 459.00 459.00 459.00 459.00 625.00 BQD, BQD6 Shipping Weights Number of Poles Number per Carton Shipping Weight (lbs.) (ea.) 1 2 3 1/12/48 1/6/24 1/4/16 1.6 1.2 2.0 Interrupting Ratings 6 Breaker Type BQD (UL&CSA) BQD6 (CSA) Number of Poles RMS Symmetrical Amperes (KA) Volts AC 480/ 120 240 277 277 1 2 3 1 2 3 65 — — 65 — — — 65 65 — 65 65 14 — — 10 — — — 14 14 — 10 10 Lugs For 60/70°C Wire Volts DC BQD – Load End Only 347 600/ 347 125 250 — — — 10 — — — — — — 10 10 14 — — 14 — — — 14 — — 14 — 15–40 #14–#6 AWG Cu #12–#6 AWG Al 45–100 #8–#1 AWG Cu #6–#1/0 AWG Al CIRCUIT BREAKERS BQD Internal Accessories Control Voltage V AC 120 240 277 480 600 — — — — V DC — — — — — 12 24 48 125 Maximum Voltage Shunt Trip Catalog Number BQDST120 BQDST240▲ BQDST277▲ BQDST480▲ BQDST600▲ BQDST12▲ BQDST24▲ BQDST48▲ BQDST125▲ 569.00 569.00 569.00 569.00 569.00 569.00 569.00 569.00 569.00 AC DC Auxiliary Switch Catalog Number 240 240 125 125 BQDA1▲ BQDA2▲ Alarm Switch Catalog Number Alarm and Auxiliary Switch Combination Catalog Number 42.00BQDBA▲ 83.00— For inches / millimeters conversion, see Application Data section. ■ Built to order. Allow 2–3 weeks for delivery. ▲ Built to order. Allow 6–8 weeks for delivery. 6/16 Shunt Trip and Auxiliary Switch Combinations Catalog Number BQDST120AAS▲ 802.00 BQDST240AAS▲ 802.00 BQDST277AAS▲ 802.00 BQDST480AAS▲ 802.00 BQDST600AAS▲ 802.00 BQDST12DAS▲ 802.00 BQDST24DAS▲ 802.00 BQDST48DAS▲ 802.00 BQDST125DAS▲ 802.00 BQDA1BA SWD HID rated for switching 277V AC fluorescent lighting. rated at 277V AC. Not suitable for 3 phase delta 480V and 600Y applications. HACR 483.00 rated. Accessories pages 6/75 to 6/80 Molded Case Circuit Breakers SELECTION BQ 125A Frame Ordering Instructions All BQ circuit breakers are supplied with load side lugs. If line side lugs are required, add suffix ‘L’ to catalog number. Lugs will be supplied at no charge if ordered with circuit breakers. All standard circuit breakers are calibrated for 40°C maximum ambient application. BQ 125A Frame — BQ (10,000A IR) Non-Interchangeable Trip Continuous Current Rating @ 40° C 1-Pole 2-Pole 2-Pole 3-Pole 120/240V AC 120/240V AC Common Trip 240V AC Common Trip 240V AC Common Trip Catalog Number Catalog Number Catalog Number Catalog Number 015 020 025 030 035 040 045 050 055 060 BQ1B015 BQ1B020 BQ1B025 BQ1B030 BQ1B035 ■ BQ1B040 BQ1B045 ■ BQ1B050 BQ1B055 ■ BQ1B060 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 BQ2B015 68.00 BQ2B020 68.00 BQ2B025 68.00 BQ2B030 68.00 BQ2B035 68.00 BQ2B040 68.00 BQ2B045 ■68.00 BQ2B050 68.00 — – BQ2B060 68.00 BQ2H015 181.00 BQ2H020 ■ 181.00 — – BQ2H030 ■ 181.00 — BQ2H040 ■ 181.00 — – BQ2H050 ■ 181.00 — – BQ2H060 ■ 181.00 BQ3B015 227.00 BQ3B020227.00 BQ3B025 227.00 BQ3B030227.00 BQ3B035 227.00 BQ3B040227.00 BQ3B045 227.00 BQ3B050227.00 — – BQ3B060227.00 070 BQ1B070 30.00 BQ2B070133.00 BQ2H070 ■ 240.00 BQ3B070278.00 — – BQ2H090 ■ 273.00 BQ2H100 ■ 273.00 BQ3B080314.00 BQ3B090314.00 BQ3B100314.00 080 090 100 — — — BQ2B080 181.00 BQ2B090181.00 BQ2B100181.00 110 — BQ2B110 364.00 — — 125 — BQ2B125 385.00 — — 015 020 BQ1B015H 59.00 BQ1B020H 59.00 BQ2B015H 133.00 BQ2B020H 133.00 — — BQ3B015 H 341.00 BQ3B020H 341.00 030 040 050 055 060 BQ1B030H 66.00 BQ1B040H■ 66.00 BQ1B050H■ 66.00 BQ1B055H■ 66.00 BQ1B060H■ 66.00 BQ1B070H■ 83.00 BQ2B030H BQ2B040H BQ2B050H — BQ2B060H 133.00 133.00 133.00 –133.00 — — — — — BQ3B030H 341.00 BQ3B040H 341.00 BQ3B050H 341.00 — BQ3B060H 341.00 BQ2B070H 200.00 — BQ3B070H ■ 414.00 BQ2B080H 291.00 BQ2B090H 291.00 BQ2B100H 291.00 BQ2B125H ■ 291.00 — — — — BQ3B080H ■ 485.00 BQ3B090H ■ 485.00 BQ3B100H 485.00 — –- 070 080 090 100 125 — — — — 6 BQH (22,000A IR) 015 020 030 HB1B015 101.00 HB1B020 101.00 HB1B030■101.00 HB2B015■247.00 HB2B020■247.00 HB2B030■247.00 — — — HB3B015■429.00 HB3B020■429.00 HB3B030■429.00 040 050 060 HB1B040■118.00 HB1B050■118.00 — - HB2B040■302.00 HB2B050■302.00 HB2B060■302.00 — — — HB3B040■522.00 HB3B050■522.00 HB3B060■522.00 HB2B070■494.00 — HB2B090■558.00 HB2B100■558.00 — HB3B070■558.00 — — — HB3B080■656.00 HB3B090■656.00 HB3B100 656.00 070 — -- 080 090 100 — — — ---- BQ/BQH/HBQ Internal Accessories (Factory installed only) Auxiliary Switches Control Voltage Shunt Trip AC Suffix Suffix ...00S01n ...A01■ 120V DC 1A and 1B ■ Built to order. Allow 3–4 weeks for delivery. CSA Certified / UL Listed for frequent switching applications (SWD). 120V AC fluorescent lighting. HCAR rated. For 400 cycle CSA Certified / UL Listed devices, add “Y” suffix to catalog number. Add 25% to list price. 5000A interrupting rating.■ UL Listed for use on 3 phase grounded “B” systems– 5000A IR for this application. Interrupting Ratings page 6/6 Accessories pages 6/75 to 6/80 Modifications page 6/75 6/17 CIRCUIT BREAKERS HBQ (65,000A IR) Molded Case Circuit Breakers SELECTION DIN Rail Mounted Circuit Breakers Type BQXD — BQ Breaker with DIN Rail Mounting - UL Listed only Continuous Current Rating 15 20 25 30 35 40 45 50 60 1-Pole 2-Pole Catalog Number Catalog Number BQ1B015QLD BQ1B020QLD BQ1B025QLD BQ1B030QLD BQ1B035QLD BQ1B040QLD BQ1B045QLD BQ1B050QLD BQ1B060QLD 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00 Interrupting Ratings (KA) (RMS Symmetrical Amperes) Volts AC 120/240 BQ2B015QLD BQ2B020QLD BQ2B025QLD BQ2B030QLD BQ2B035QLD BQ2B040QLD BQ2B045QLD BQ2B050QLD BQ2B060QLD 68.00 68.00 68.00 68.00 68.00 68.00 68.00 68.00 68.00 10 2-Pole DIN Rail mtd (UL listed only) Finger Safe Terminal Shield Protects against accidental contact with lugs–1 per lug. Fits line and load end. Catalog Number Qty BQFS2 2 BQFS1K 1000 Shipping Weights Number of Poles Number Per Carton /Master Shipping Weight (lbs.) Master BQ 1 (15–50A) 1 (55–70A) 1 (15–70A, 22 and 65K A IR) 2 (15–50A) 2 (60–125A) 2 (15–100A, 22 and 65K A IR) 2 (15–100A, 240V) 3 (15–100A) 6/72 6/66 6/66 3/36 3/33 3/33 3/33 2/22 23 23 23 24 23 24 23 23 6/66 3/33 2/22 23 24 24 BQH and HBQ 1 2 3 Dimensions (inches) Breaker Type Amperes L D1 D2 BQ, BQH BQ, BQH HBQ BQXD 15–50 55–125 15–125 15–60 33⁄4 4 4 41⁄2 23⁄8 23⁄8 23⁄8 23⁄8 3 3 3 3 6 Lugs-For Use with BQ, BQH, HBQ Enclosures Type Catalog Number 1 EB3100S Circuit Breaker Amp. Rtg. 3R WB31006.00 Line Side CIRCUIT BREAKERS Cables Per Lug Lug Wire Range AWG 15–40 1 1 #14–#6 Cu #12–#6 Al TC1Q1 13.90 50–100 1 1 #8–#1 Cu #6–#1/0 Al TA1Q1 12.20 15–20 1 1 #14–#10 Cu #14–#10 Al 25–35 1 1 #14–#6 Cu #14–#6 Al 40–50 1 1 #8–#6 Cu #8–#4 Al 55–70 1 1 #8–#4 Cu #8–#2 Al 80–100 1 1 #4–#1/0 Cu #2–#1/0 Al 110–125 1 1 #2–#1/0 Cu #1/0–#2/0 Cu Catalog Number Load Side For inches / millimeters conversion, see Application Data section. Surface mounted indoor. If flush mounting is required, replace suffix “S” in catalog number with suffix “F”. Schedule B. Does not include circuit breaker. Order circuit breaker separately. Neutral included in enclosure. Enclosure will not accept circuit breakers with shunt trips or auxiliary switches installed. Discount ■ Built to order. Allow 3–4 weeks for delivery. Terminals are CSA Certified / UL Listed for 60°/75°C conductors. Connector has steel construction. 6/18 Connectors are Supplied with Circuit Breaker Package of 6 connectors. BQXD uses TA1Q1 or TC1Q1 lugs on both line and load ends. Accessories pages 6/75 to 6/80 Molded Case Circuit Breakers SELECTION / DIMENSIONS QJ 225A Frame Type QJ2 Ordering Information 2-Pole 3-Pole Continuous Current Rating @ 40°C 240V AC 240V AC Catalog Number Catalog Number 060 070 080 090 100 110 125 150 175 200 225 QJ22B060■374.00 QJ22B070■377.00 QJ22B080■377.00 QJ22B090■377.00 QJ22B100377.00 QJ22B110■377.00 QJ22B125377.00 QJ22B150377.00 QJ22B175377.00 QJ22B200377.00 QJ22B225377.00 QJ23B060 QJ23B070 QJ23B080 QJ23B090 QJ23B100 QJ23B110 QJ23B125 QJ23B150 QJ23B175 QJ23B200 QJ23B225 QJH22B060■ QJH22B070■ QJH22B080■ QJH22B090■ QJH22B100■ QJH22B110■ QJH22B125 QJH22B150 QJH22B175■ QJH22B200 QJH22B225 QJH23B060■ QJH23B070■ QJH23B080■ QJH23B090■ QJH23B100 QJH23B110 QJH23B125 QJH23B150 QJH23B175 QJH23B200 QJH23B225 Load side TA1Q300 lugs are mounted and included when circuit breaker is ordered. For line and load lugs (TA1Q300) installed at no additional charge, add suffix “L” to catalog number. 989.00 989.00 989.00 989.00 989.00 989.00 989.00 989.00 989.00 989.00 989.00 Type QJH2 060 070 080 090 100 110 125 150 175 200 225 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 1384.00 Type QJ2H QJ22B060H■ QJ23B060H■ 1756.00 QJ22B070H■ QJ23B070H■ 1756.00 QJ22B080H■ QJ23B080H■ 1756.00 QJ22B090H■ QJ23B090H■ 1756.00 QJ22B100H■ QJ23B100H 1756.00 QJ22B110H■ QJ23B110H■ 1756.00 QJ22B125H1122.00QJ23B125H 1756.00 QJ22B150H1122.00QJ23B150H 1756.00 QJ22B175H■ QJ23B175H 1756.00 QJ22B200H1122.00QJ23B200H 1756.00 QJ22B225H1122.00QJ23B225H 1756.00 060 070 080 090 100 110 125 150 175 200 225 50°C Calibration - See page 6-74. 400HZ. - See page 6-74. Shipping Weights QJ2, QJH2, QJ2H, HQJ2H Number of Poles Number per Carton Shipping Weight (lbs.) 2 3 10 10 30 41 Lugs For 75°C Wire Catalog Number Lug Body Lug Wire Range TA1Q300 Al (1) #6—300 kcmil Cu (1) #4—300 kcmil Al TC1Q250 Cu (1) #6—250 kcmil Cu Enclosures (Neutral Included) Type Catalog Number 1 3R (2-pole) 3R (3-pole) EB3225(S)(F) WB2225 WB3225 296.00 323.00 UL 489 Interrupting Ratings Breaker Type AIR @ 240V AC QJ2 QJH2 QJ2H HQJ2H 010,000 022,000 042,000 100,000 HQJ23B100H HQJ23B110H HQJ23B125H HQJ23B150H HQJ23B175H HQJ23B200H HQJ23B225H — — — — — — — 998.00 1998.00 998.00 1998.00 998.00 1998.00 998.00 QJ2 CIRCUIT BREAKERS 100 110 125 150 175 200 225 6 Type HQJ2H Internal Accessories (Factory installed only) 3-pole only . Add suffix to catalog number. Control Voltage Shunt Trip Auxiliary Switches Shunt Trip and 1A and 1B 1A and 1B Auxiliary Switch 2A and 2B AC DC Suffix Suffix Suffix Suffix 120/240 — 00S01■ A01■ A02■ 01S01■ — 24 00S07■ A01■ A02■ 01S07■ — 25 00S11■ A01■ A02■ 01S11■ ■ Built to order. Allow 3–4 weeks for delivery. HACR ▲ Built to order. Allow 7–9 weeks for delivery. Internal See Note: A page 6-70. rated. accessories are not available on 2-pole QJ breakers. Accessories pages 6/75 to 6/80 6/19 Molded Case Circuit Breakers SELECTION CQD 100A Frame Type CQD (Cable In - Cable Out) DIN Rail Mount Continuous Current Rating @ 40°C Shipping Weights 1-Pole 2-Pole 3-Pole 277V AC 125V DC 480Y/277V AC 125/250V DC Number of Poles Number per Carton Shipping Weight lbs. (kg) 480Y/277V AC Catalog Number Catalog Number Catalog Number 1 2 3 1 1 1 0.5 (0) 1.0 (0) 1.5 (1) 115 120 125 130 CQD115 114.00 CQD120 114.00 CQD125 114.00 CQD130 114.00 135 140 145 150 160 CQD135■114.00 CQD140■114.00 CQD145■114.00 CQD150■114.00 CQD160■114.00 CQD170■229.00 CQD180■229.00 CQD190■229.00 CQD1100■229.00 170 180 190 100 CQD215 CQD220 CQD225 CQD230 272.00 272.00 272.00 272.00 CQD315485.00 CQD320485.00 CQD325485.00 CQD330485.00 CQD235■272.00 CQD240 272.00 CQD245■272.00 CQD250 272.00 CQD260 272.00 CQD335485.00 CQD340485.00 CQD345■485.00 CQD350485.00 CQD360485.00 CQD270 542.00 CQD280 542.00 CQD290■542.00 CQD2100 542.00 CQD370657.00 CQD380657.00 CQD390657.00 CQD3100657.00 Lugs For 60/75°C Wire Amps Wire Size 15–40 #14–#6 AWG Cu #12–#6 AWG Al 45–100 #8–#1 AWG Cu #6–#1/0 AWG Al Type CQD6 (Cable In - Cable Out) CSA Certified (not UL) Continuous Current Rating @ 40°C 1-Pole 2-Pole 347V AC 125V DC 600Y/347V AC 125/250V DC Catalog Number 115 120 125 130 135 140 145 150 160 — CQD6120 ■ CQD6125 ■ CQD6130 ■ CQD6135■ CQD6140■ CQD6145■ CQD6150■ CQD6160■ CQD6170■ 170 3-Pole 600Y/347V AC Catalog Number 114.00 114.00 114.00 114.00 114.00 114.00 114.00 114.00 229.00 CQD6215■ CQD6220■ CQD6225■ CQD6230■ CQD6235■ CQD6240■ CQD6245■ CQD6250■ CQD6260■ CQD6270■ Catalog Number 272.00 272.00 272.00 272.00 272.00 272.00 272.00 272.00 272.00 542.00 CQD6315■ CQD6320■ CQD6325■ CQD6330■ CQD6335■ CQD6340■ CQD6345■ CQD6350■ CQD6360■ — 485.00 485.00 485.00 485.00 485.00 485.00 485.00 485.00 485.00 CQD, CQD6 5.4 Interrupting Ratings 6 RMS Symmetrical Amperes (KA) Breaker Type Number of Poles Volts AC (50/60 Hz) CQD, CQD6 Volts DC 120 240 480/277 600/347 125 250 CIRCUIT BREAKERS CQD (UL) 1 2 3 65 — — — 65 65 14 14 14 — — — 14 — — — 14 — CQD6 (CSA) 1 2 3 65 — — — 65 65 — — — 14 14 14 14 — — — 14 — For inches / millimeters conversion, see Application Data section. ■ Built to order. Allow 3–4 weeks for delivery. SWD rated. HID rated. HACR rated. 6/20 Accessories pages 6/23 and 6/76 to 6/81 Molded Case Circuit Breakers SELECTION / DIMENSIONS NGG 125A Frame Type NGG (Cable In - Cable Out) 1-Pole 2-Pole Continuous Ampere Rating @ 40°C 3-Pole Catalog Number Catalog Number Catalog Number 15 20 25 30 NGG1B015L 177.00 NGG1B020L 177.00 NGG1B025L177.00 NGG1B030L177.00 NGG2B015L473.00 NGG2B020L473.00 NGG2B025L473.00 NGG2B030L473.00 NGG3B015L591.00 NGG3B020L591.00 NGG3B025L591.00 NGG3B030L591.00 35 40 50 60 NGG1B035L177.00 NGG1B040L177.00 NGG1B050L177.00 NGG1B060L177.00 NGG2B035L473.00 NGG2B040L473.00 NGG2B050L473.00 NGG2B060L473.00 NGG3B035L591.00 NGG3B040L591.00 NGG3B050L591.00 NGG3B060L591.00 70 80 90 100 NGG1B070L209.00 NGG1B080L209.00 NGG1B090L209.00 NGG1B100L209.00 NGG2B070L557.00 NGG2B080L557.00 NGG2B090L557.00 NGG2B100L557.00 NGG3B070L695.00 NGG3B080L695.00 NGG3B090L695.00 NGG3B100L695.00 NGG2B110L1023.00 NGG2B125L1023.00 NGG3B110L1279.00 NGG3B125L1279.00 110 125 — — NGG 2.9 5.4 Line and load lugs are included as standard. If only load side lugs are needed, change “L” suffix to “B”. HACR rated. Suitable for screws or DIN rail mounting. Shipping Weights Number of Poles Number per Carton Shipping Weight lbs. (kg) 1 2 3 1 1 1 .75 (0.34) 1.3 (0.59) 2.0 (0.98) NGG Lugs For 60/75°C Wire NGG Wire Size Catalog Number 15–40A #14–#6 AWG Cu #12–#6 AWG Al 1TC1Q1 (qty. 1) 3TC1Q1 (qty. 3) 50–100A #8–#1 AWG Cu #6–#1/0 AWG Al 1TA1Q1 (qty. 1) 3TA1Q1 (qty. 3) 110–125A #6–#1/0 AWG Cu #4–#2/0 AWG Al 3TA1GG20 (qty. 3) 15–125A Nut Keeper plate w/screw (for crimp terminals) THKG3 (qty. 3) 6 Ampere Rating Breaker Type NGG Number of Poles 01 2, 3 CSA / UL 489 AIR RMS Symmetrical Amperes (KA) Volts AC(50/60Hz) 120 240 277 347 65 — 25 18 0— 65 — — 480 — 25 600/347 0— TBD Volts DC 125 250 14 — 0— 14 IEC 947-2 Volts AC (50/60Hz) 220/240 380/415 lcu lcs lcu 25 12.5 — 25 12.5 25 lcs — 12.5 Volts DC 250 — 10 For inches / millimeters conversion, see Application Data section. SWD HID rated. Accessories pages 6/22 and 6/75 to 6/80 rated at 277 VAC. 6/21 CIRCUIT BREAKERS Interrupting Ratings Molded Case Circuit Breakers SELECTION Internal Accessories for CQD 100A Frame and NGG 125A Frame Shunt Trip Control Voltage V AC V DC CQD, CQD6, NGG Catalog Number 120 240 277 480 600 — — — — — CQDST120569.00 CQDST240▲ CQDST277▲0 CQDST480▲00 CQDST600 — — — — 012 024 048 125 CQDST12 CQDST24 CQDST48 CQDST125 Auxiliary Switch Maximum Voltage Number AC DC Contacts ofCQD, CQD6, NGG Catalog Number 240 240 125 125 1A–1B 2A–2B CQDA1 CQDA2 Alarm Switch Maximum Voltage AC DC CQD, CQD6, NGG Catalog Number 240 125 CQDBA Shunt Trip and Auxiliary Switch Shunt Trip Voltage AC DC CQD, CQD6, NGG Catalog Number 6 120 — CQDST120AAS▲ 240 — CQDST240AAS▲ 277 — CQDST277AAS▲ 480 — CQDST480AAS▲ 600 — CQDST600AAS▲ — 012 CQDST12DAS▲ — 024 CQDST24DAS▲ — 048 CQDST48DAS▲ — 125 CQDST125DAS▲ Alarm and Auxillary Switch Combinations CIRCUIT BREAKERS For Breaker Catalog # CQD, CQD6, NGG CQDA1BA▲ ▲ Built to order. Allow 7–9 weeks for delivery. 6/22 Molded Case Circuit Breakers SELECTION ED 125A Frame Sentron Series Ordering Instructions All ED Frame Sentron circuit breakers are supplied with load side lugs. If line side lugs are required, add “L” suffix to catalog number, and breaker will be supplied with line lugs installed at no charge. 50°C Calibration, 400HZ - see page 6-73. All ED frame circuit breakers may be reverse connected. Blue Label Continuous Current Rating @ 40° C 015 020 25 030 35 040 45 050 060 070 80 90 100 2-Pole 120V AC 3-Pole Catalog Number ED21B015■ ED21B020■ ED21B025■ ED21B030■ ED21B035■ ED21B040■ ED21B045■ ED21B050■ ED21B060■ ED21B070■ ED21B080■ ED21B090■ ED21B100■ 112.00 112.00 112.00 112.00 112.00 112.00 112.00 112.00 112.00 ED22B015 ED22B020 ED22B025■ ED22B030 ED22B035■ ED22B040 ED22B045■ ED22B050 ED22B060 257.00 257.00 257.00 257.00 257.00 257.00 257.00 257.00 257.00 ED23B015383.00 ED23B020383.00 ED23B025■383.00 ED23B030383.00 ED23B035■383.00 ED23B040383.00 ED23B045■383.00 ED23B050383.00 ED23B060383.00 206.00 206.00 206.00 206.00 ED22B070 ED22B080■ ED22B090■ ED22B100 421.00 421.00 421.00 421.00 ED23B070 548.0 ED23B080 548.0 ED23B090 548.0 ED23B100548.00 Blue Label 1-Pole 2-Pole 120V AC 277V AC 125V DC 3-Pole 480V AC Catalog Number 250V DC 480V AC Catalog Number Catalog Number 015 020 025 030 035 040 045 050 060 ED41B015 ED41B020 ED41B025 ED41B030 ED41B035■ ED41B040 ED41B045■ ED41B050 ED41B060 138.00 138.00 138.00 138.00 138.00 138.00 138.00 138.00 138.00 ED42B015 ED42B020 ED42B025 ED42B030 ED42B035■ ED42B040 ED42B045■ ED42B050 ED42B060 466.00 466.00 466.00 466.00 466.00 466.00 466.00 466.00 466.00 ED43B015611.00 ED43B020611.00 ED43B025611.00 ED43B030611.00 ED43B035611.00 ED43B040611.00 ED43B045611.00 ED43B050611.00 ED43B060611.00 070 080 090 100 ED41B070 ED41B080■ ED41B090■ ED41B100 258.00 258.00 258.00 258.00 ED42B070 ED42B080■ ED42B090■ ED42B100 613.00 613.00 613.00 613.00 ED43B070719.00 ED43B080719.00 ED43B090719.00 ED43B100719.00 110 125 — — ED42B110■ 1239.00 ED42B125 1239.00 Type ED6 Continuous Current Rating @ 40° C 2-Pole 347V AC 312.00 312.00 312.00 312.00 312.00 312.00 312.00 312.00 312.00 070 080 090 100 ED61B070■ ED61B080 ED61B090 ED61B100■ — — 429.00 429.00 429.00 429.00 ■ Built to order. Allow 2–3 weeks for delivery. 250V DC 600V AC Catalog Number ED61B015 ED61B020 ED61B025 ED61B030 ED61B035 ED61B040 ED61B045■ ED61B050 ED61B060 Note: ED frame circuit breakers qualified to UL 489 Supplement SB “Naval”— See page 6-74 for additional information 3-Pole 600V AC Catalog Number 015 020 025 030 035 040 045 050 060 110 125 ED43B1101425. ED43B125 Blue Label 1-Pole ED62B015 ED62B020 ED62B025■ ED62B030 ED62B035■ ED62B040■ ED62B045■ ED62B050■ ED62B060■ ED62B070■ ED62B080■ ED62B090■ ED62B100■ — — Number per Carton Shipping Weight (lbs.) ED2, ED4, ED6, HED4 Catalog Number Type ED4 Continuous Current Rating @ 40° C Number of Poles 125V DC 250V DC 240V AC 125V DC 240V AC Catalog Number Shipping Weights 500V DC Catalog Number 548.00 548.00 548.00 548.00 548.00 548.00 548.00 548.00 548.00 ED63B015 ED63B020 ED63B025 ED63B030 ED63B035 ED63B040 ED63B045 ED63B050 ED63B060 696 691.00 691.00 691.00 691.00 ED63B070 ED63B080 ED63B090 ED63B100 =0 ED63B110 ED63B125 16 1 2 3 30 10 10 38 25 38 2 3 5 5 20 30 CED6 Lugs Ampere Rating No. of Poles Catalog Number Wire Range Aluminum Body Lugs All 15–25A 1, 2, 3 All 30–100A 1, 2, 3 ED2, 4, CED6 30–60A ED2, 4, CED6 70–100A ED2, 4, 6, HED4 30–100A All 110, 125A 1 1 Line/Load SA1E025 Line Side LN1E100 Load Side LD1E060 Load Side LD1E100 #14–#10 Cu #12–#10 Al #10–1/0 Cu/Al #10–#4 Cu/Al #6–#1/0 Cu/Al 2, 3 Load Side LN1E100 #10–1/0 Cu/Al 2, 3 Line/Load TA1E6125 #3–3/0 Cu #1–2/0 Al Line/Load TC1ED6150 #10–1/0 Cu only CCE125 2/0 Copper Body Lugs All 30–125A 1, 2, 3 Compression Lugs All ED, CED 6 1-Pole Enclosures (Neutral Included) Type 1 (Surface) 1 (Flush) 3R 4–4X 7–9 7–9 12 1 (Surface) 1 (Flush) 3R 12 Catalog Number E2N1S(15–100A) E2N1F (15–100A) E2N3R (15–100A) ED6SS4(15–100A) EA(15–60A) EB(70–100A) E2N12 (15–100A) CED6N1S CED6N1F CED6N3R CED6N12 133.00 133.00 366.00 2541.00 1565.00 1565.00 227.00 242.00 242.00 648.00 402.00 Modifications page 6-73 Accessories pages 6-25 and 6-75 to 6-86 CSA Certified only (Not UL) CED types and all 110–125 ampere ED frames. See Note: A, page 6-70. SWD rated. HACR rated. For 6/23 CIRCUIT BREAKERS Type ED2 Molded Case Circuit Breakers SELECTION ED 125A Frame Sentron Series Type HED4 Black Label Catalog Number 402.00 402.00 402.00 402.00 HED42B015 HED42B020 HED42B025■ HED42B030 HED42B035■ HED42B040 HED42B045■ HED42B050 HED42B060■ HED42B070■ HED42B080■ HED42B090■ HED42B100■ HED42B110■ HED42B125■ D 831.00 831.00 831.00 831.00 831.00 831.00 831.00 831.00 831.00 HED43B015 HED43B020 HED43B025 HED43B030 HED43B035 HED43B040 HED43B045 HED43B050 HED43B060 1020.00 1020.00 1020.00 1020.00 1020.00 1020.00 1020.00 1020.00 1020.00 957.00 957.00 957.00 957.00 HED43B070 HED43B080 HED43B090 HED43B100 1098.00 1098.00 1098.00 1098.00 1946.00 1946.00 HED43B110 HED43B125 2244.00 2244.00 D1 H W1 W3 W2 1 POLE 2 POLE 3 POLE FIGURE 2 - CED (3 Pole shown) 355.00 355.00 355.00 355.00 355.00 355.00 355.00 355.00 355.00 110 125 480V AC 070 080 090 100 250V DC D HED41B015 HED41B020 HED41B025 HED41B030 HED41B035■ HED41B040 HED41B045■ HED41B050■ HED41B060■ HED41B070■ HED41B080■ HED41B090■ HED41B100■ — — 015 020 025 030 035 040 045 050 060 480V AC Catalog Number 125V DC 277V AC Catalog Number FIGURE1 - ED, HED 3-Pole Continuous Current Rating @ 40° C 2-Pole 1-Pole D1 Fuseless Current Limiting Type CED6 6 2-Pole 600V AC, 250V DC Catalog Number CED62B015 CED62B020■ — CED62B030■ — CED62B040■ — CED62B050■ CED62B060■ CED62B070■ CED62B080■ CED62B090■ CED62B100■ — CED62B125■ 3-Pole 600V AC, 500V DC Catalog Number 2465.00 CED63B015 2465.00 CED63B020 — — 2465.00 CED63B030 — — 2465.00 CED63B040 — — — 2465.00 CED63B050 2465.00 CED63B060 2465.00 CED63B070 2465.00 CED63B080 2465.00 CED63B090 2465.00 CED63B100 CED63B110■ 3698.00 CED63B125 Continuous Current Rating @ 40°C 015 020 025 030 035 040 045 050 060 070 080 090 100 110 125 H Red Label 2862.00 2862.00 W2, W3 2862.00 2862.00 Dimensions (in inches) 2862.00 2862.00 2862.00 2862.00 2862.00 2862.00 4368.00 4368.00 Breaker Type W1 W2 W3 H D D1 Figure 1 ED2, ED4, ED6, HED4, ED6 ETI 1 2 3 6.35 3.92 4.56 Figure 2 CED6, CED6 ETI — 2 3 9.58 3.92 4.56 Interrupting Ratings CIRCUIT BREAKERS Breaker Type ED2 (1-P) ED2 (2, 3-P) ED4 (1-P) ED4 (2, 3-P) ED6 (1P) ED6 (2, 3-P) HED4 (1-P) (15–30A) HED4 (1-P) (35–100A) HED4 (2, 3-P) CED6 (2, 3-P) CSA C22.2 / UL 489 AIR (File #E10848) RMS Symmetrical Amperes (KA) Volts AC 120 240 277 347 480 010 — — — — — 010 — — — 065 — 22 — — — 065 — — 018 — — — — 30 — 065 — — 025 500 lcu — — — — — 18 lcs — — — — — 5 — 65 — — — 30 — — — — — — — — — 100 200 25 — — — — — — 042 200 — 30 — — — 30 (2-P) 30 (2-P) — — — — — — — — — — — — — — — — — — — wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems. 6/24 500 — — — — — 18 (3-P) 100 rated. When Volts DC 125 250 05 — — 05 (2-P) 30 — — 30 (2-P) — — — 30 (2-P) 100 — — ■ Built to order. Allow 2–3 weeks for delivery. SWD 600 — — — — — 018 IEC 947-2 Volts AC (50/60Hz) 220/240 380/415 lcu lcs lcu lcs — — — — — — — — — — — — — — — — — — — — 65 17 35 9 100 50 (3-P) HED4 Single ED6-ETI, HACR type circuit breakers meet the CSA / UL criteria for “current limiting” at 240V AC. CED6-ETI, see page 6-56 for ordering information. Pole 15-30A 30KA @ 347V 35-100A 18KA @ 347V rated. Molded Case Circuit Breakers SELECTION Internal Accessories Combinations Available only when ordered together. Only one module can be added to a breaker. Additional accessories, which always attach to the left pole, cannot be added to the combination later. Equipment Ground Sensing A field addable kit containing 30mA or 5 mA ground fault accessory module, current transformer with 24 inch leads, and current transformer mounting equipment. Current transformer to mount in gutter of lighting panel or any control panel. Accessory module operates from separate 120V control power source. Both 30MA and 5MA devices are equipment protection devices only. Do not use for personnel protection. Control Voltage 1 Shunt Trip 1 Shunt Trip 1 Shunt Trip and 1 Auxiliary Switch 1 Auxiliary Switch and 1 Alarm Switch 1 Shunt Trip and 1 Alarm Switch 1 Shunt Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number 024 048 120 208 240 277 480 — — — — — — — S17ED60 S18ED60 S01ED60 — S03ED60 S15ED60▲ S04ED60 — — S01ED62A S02ED62A▲ S03ED62A S15ED64A▲ S04ED64A▲ — — S01ED62AB S02ED62AB▲ S03ED62AB S15ED64AB▲ S04ED64AB▲ — — S01ED62B S02ED62B▲ S03ED62B▲ S15ED64B▲ S04ED64B▲ — — S01ED62AA S02ED62AA▲ S03ED62AA▲ — — — — — — — 012 024 048 125 250 S16ED60▲ S07ED60 S09ED60▲ S11ED60▲ S13ED60▲ S16ED62A▲ S07ED62A S09ED62A▲ S11ED62A▲ S13ED62A▲ — S07ED62AB▲ S09ED62AB▲ S11ED62AB▲ S13ED62AB▲ — S07ED62B▲ S09ED62B▲ S11ED62B▲ S13ED62B▲ — S07ED62AA▲ S09ED62AA▲ S11ED62AA▲ S13ED62AA▲ Undervoltage Trip Combinations Control Voltage 1 Undervoltage Trip 1 Undervoltage Trip 1 Undervoltage and 1 Auxiliary 1 Undervoltage Trip and Switch and Trip and 1 Auxiliary Switch 1 Alarm Switch 1 Alarm Switch 1 Undervoltage Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — U01ED60 U02ED60▲ U03ED60 U16ED60▲ U06ED60▲ U08ED60▲ U01ED62A U02ED62A▲ U03ED62A▲ U16ED64A▲ U06ED64A▲ — U01ED62AB▲ U02ED62AB▲ U03ED62AB▲ U16ED64AB▲ U06ED64AB▲ — U01ED62B▲ U02ED62B▲ U03ED62B▲ U16ED64B▲ U06ED64B▲ — U01ED62AA▲ U02ED62AA▲ U03ED62AA▲ — — — — — — — 024 048 125 250 U13ED60 U14ED60▲ U10ED60▲ U12ED60▲ U13ED62A▲ U14ED62A▲ U10ED62A▲ U12ED62A▲ U13ED62AB▲ U14ED62AB▲ U10ED62AB▲ — U13ED62B▲ U14ED62B▲ U10ED62B▲ — U13ED62AA▲ U14ED62AA▲ U10ED62AA▲ U12ED62AA▲ Auxiliary and Alarm Switch Combinations Maximum Voltage 1 Auxiliary Switch* 1 Alarm Switch Alarm Switch and 2 Auxiliary 1 Auxiliary Switch Switches 1 Alarm Switch and 2 Auxiliary Switches AC DC Catalog Number Catalog Number 240 250 A01ED62 B00ED62 Catalog Number Catalog Number Catalog Number A01ED62B A02ED62 480 — A01ED64 A02ED62B B00ED64 A01ED64B — — 12 A01EDLV* — 306.00 Gold Plated Contacts—for PLC use Ground Fault Sensing Relay Kit — Equipment Protection Only For Use With Breaker Frame ED2, ED4, ED6, HED4 1550.00 Number of Poles Description 1, 2, 3 Catalog Number 30mA 5mA Basic Kit GF01ED60 GF01ED651326.00 Basic Kit with Normally Open Bell Alarm GF01ED60B0 GF01ED65B0▲ Basic Kit with Normally Closed Bell Alarm GF01ED60BC GF01ED65BC▲ 1550.00 ▲ Built to order. Allow 7–9 weeks for delivery. 6/25 6 ED 125A Frame Shunt Trip Combinations CIRCUIT BREAKERS Accessories for: Molded Case Circuit Breakers SELECTION FD 250A Frame Sentron Series Blue Label Type FXD6-A Non-Interchangeable Trip (Assembled Circuit Breaker – Without Lugs) 2-Pole Catalog Number FXD62B070■ FXD62B080■ FXD62B090■ FXD62B100 FXD62B110■ FXD62B125 FXD62B150 FXD62B175 FXD62B200 FXD62B225 FXD62B250 Continuous Current Rating @ 40°C 70 80 90 100 110 125 150 175 200 225 250 3-Pole 1610.00 1610.00 1610.00 1610.00 1610.00 1610.00 1610.00 1610.00 1610.00 1610.00 2738.00 Type FD6-A Catalog Number FXD63B0702036 FXD63B0802036. FXD63B0902036. FXD63B1002036. FXD63B1102036. FXD63B1252036. FXD63B1502036.00 FXD63B175236.00 FXD63B200203 FXD63B225 .00 FXD63B250 Blue Label Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 2-Pole 600V AC, 250V DC FD62B070■1695.20 FD62B080■1695.20 FD62B090■1695.20 FD62B100■1695.20 FD62B110■1695.20 FD62B125■1695.20 FD62B150■1695.20 FD62B175■1695.20 FD62B200■1695.20 FD62B225■1695.20 FD62B250■2824.20 70 80 90 100 110 125 150 175 200 225 250 FD62T070■ 839.00 FD62T080■ 839.00 FD62T090■ 839.00 FD62T100■ 839.00 FD62T110■ 839.00 FD62T125■ 839.00 FD62T150■ 839.00 FD62T175■ 839.00 FD62T200■ 839.00 FD62T225■ 839.00 FD62T250■1968.00 FD62F250 777.00 3-Pole 600V AC, 500V DC 6 FD63B070■2159.80 FD63B080■2159.80 FD63B090■2159.80 FD63B100 2159.80 FD63B110■2159.80 FD63B125 2159.80 FD63B150 2159.80 FD63B175 2159.80 FD63B200 2159.80 FD63B225 2159.80 FD63B250 3320.80 70 80 90 100 110 125 150 175 200 225 250 FD63T070■1035.00 FD63T080■1035.00 FD63T090■1035.00 FD63T100 1035.00 FD63T110■1035.00 FD63T125 1035.00 FD63T150 1035.00 FD63T175 1035.00 FD63T200 1035.00 FD63T225 1035.00 FD63T250 2196.00 FD63F2501006.00 Interrupting Ratings CIRCUIT BREAKERS Breaker Type FXD6-A, FD6-A HFXD6 , HFD6 HHFD6 , HHFXD6 CFD6 RMS Symmetrical Amperes (KA) CSA / UL 489 AIR (File E10848) Volts AC (50/60Hz) Volts DC 240 480 600 250 500 65 100 200 200 35 65 100 200 22 25 25 100 30 (2-P) 30 (2-P) — 50 (2-P) 18 (3-P) 25 (3-P) — 50 (3-P) IEC 947-2 Volts AC (50/60Hz) 220/240 380/415 lcu lcs lcu lcs 65 33 35 9 100 50 65 33 200 100 100 50 — — — — 500 lcu 20 42 65 — 170-90 100-110 125-150 175-200 225-250 Nominal Instantaneous Values Low 2 3 4 600 700 800 900 1100 640 770 900 1060 1300 690 840 1000 1210 1500 Note: FD frame qualified to UL489 supplement SB “NAVAL”. See page 6-73 for additional information. 6/26 730 920 1100 1370 1700 Complete Breaker Unassembled with Lugs Prices of FD6, HFD6, and HHFD6 breakers includes frame, trip and both line and load lugs (TA1FD350). When ordered by these catalog numbers, the customer will receive the frame, trip, and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of FXD6, HFXD6, HHFXD6, and CFD6 includes frame with noninterchangeable trip unit installed only. Order required lugs separately. For line and load lugs (TA1FD350A) installed, add suffix “L” to catalog number (add 2 times list price of lugs for each pole). 50°C Applications see page 6-73. 400 Hz Applications see page 6-73. Lugs For 75°C Wire Catalog Number Wire Range #6—350 kcmil Cu #4—350 kcmil Al TC1FD350 #6—350 kcmil Cu Compression Lug TA1FD350A CCF250 350 kcmil Cu/Al 19.80 31.00 45.50 Enclosures Type Catalog Number 1 3R 4-4X 7-9 12 Neutral F6N1S(F) F6N3R FD6SS4 EC2 F6N12 N250 164.00 542.00 4221.00 4306.00 366.00 128.00 lcs 10 21 33 — Instantaneous Adjustment Trip Range Breaker Ampere Rating Ordering Information Modifications page 6-73 Accessories pages 6-28 and 6-75 to 6-80 5 6 7 High 770 990 1200 1520 1900 810 1060 1300 1780 2100 850 1140 1400 1930 2300 900 1200 1500 2000 2500 ■ Built to order. Allow 3–4 weeks for delivery. Type FXD6-A circuit breakers are UL Listed for reverse fed applications. 2-pole units are 3-pole width. wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. Order neutral as separate item. See Note: A, page 6-71. HFD6 and HHFD6 type circuit breakers meet the UL criteria for “current limiting” at 240 and 480V AC. HACR rated. When Molded Case Circuit Breakers SELECTION / DIMENSIONS FD 250A Frame Sentron Series Type HFD6 , Type HFXD6 Black Label Interchangeable Trip Frame Only Trip Unit Only Catalog Number Catalog Number Catalog Number D1 L 2-Pole 600V AC, 250V DC (3 Pole Width) HFD63F250 3366.00 FD63T070■ FD63T080■ FD63T090■ FD63T100 FD63T110■ FD63T125 FD63T150 FD63T175 FD63T200 FD63T225 FD63T250 1035 1035 1035 1035 1035 1035 103 103 103 1035 Type HHFD , HHFXD6 HHFD63B070■ HHFD63B080■ HHFD63B090■ HHFD63B100 HHFD63B110■ HHFD63B125 HHFD63B150 HHFD63B175 HHFD63B200 HHFD63B225 HHFD63B250 Figure 1 W D Figure 2 Breaker Type Figure 1 FXD6-A, FD6-A, HFD6, HFXD6, HHFD6, FD6-ETI Figure 2 CFD6, CFD6-ETI W L D D1 (to handle) 4.50 09.50 4 5.25 4.50 14.25 4 5.25 Shipping Weights 3-Pole 600V AC, Extra High Interrupting 070 080 090 100 110 125 150 175 200 225 250 W HHFD63F2504093.00 FD63T070■1035.0 FD63T080■1035.0 FD63T090■1035.0 FD63T100 1035.0 FD63T110■1035.0 FD63T125 1035.0 FD63T150 1035.0 FD63T175 1035.0 FD63T200 1035.0 FD63T225 1035.0 FD63T250 Type CFD6 Red Label Fuseless Current Limiting Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) Number of Number per Shipping Poles Carton Weight (lbs.) FD6-A, HFD6, HHFD6, FXD6-A Assembled Circuit Breaker (less connectors) 08.6 2 1 3 1 10 FD6-A, HFD6, HHFD6 Frame Only 07.5 2 1 08.7 3 1 FD6 Trip Unit Only 2 1 01.1 01.3 3 1 CFD6 Assembled Circuit Breaker (less terminals) 2 1 31 3 1 34 3-Pole Continuous Current Rating @ 40°C 070 080 090 100 110 125 150 175 200 225 250 ■ Built to order. Allow 3–4 weeks for delivery. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems. For non-interchangeable trip 3-pole HFD6 type circuit 600V AC/500V DC Catalog Number CFD63B070■ CFD63B080■ CFD63B090■ CFD63B100■ CFD63B110■ CFD63B125■ CFD63B150 CFD63B175 CFD63B200 CFD63B225 CFD63B250 5675.00 5675.00 5675.00 5675.00 5675.00 5675.00 5675.00 5675.00 5675.00 5675.00 6306.00 breaker, change prefix identifier from HFD6 to HFXD6. Price equals frame and trip prices combined, e.g. price of HFXD63B250 equals price of HFD63F250 plus price of FD63T250. Order lugs separately. Type HFXD6, HHFXD6, CFD6 are CSA Certified / UL Listed for reverse feed applications. Type HFXD6, HFD6, HHFD6, HHFXD6 meet the CSA Certified / UL criteria for “Current Limiting” at 240 VAC and 480V AC. FXD6, ETI, CFD6, ETI — See page 6-55 for ordering information. HACR rated. 6/27 6 HFD63B070■4519.80 HFD63B080■4519.80 HFD63B090■4519.80 HFD63B100 4519.80 HFD63B110■4519.80 HFD63B125 4519.80 HFD63B150 4519.80 HFD63B175 4519.80 HFD63B200 4519.80 HFD63B225 4519.80 HFD63B250 5680.80 Dimensions (in inches) 3-Pole 600V AC, 500V DC 070 080 090 100 110 125 150 175 200 225 250 L HFD62F250 2798.00 FD62T070■839.00 FD62T080■839.00 FD62T090■839.00 FD62T100■839.00 FD62T110■839.00 FD62T125■839.00 FD62T150■839.00 FD62T175■839.00 FD62T200■839.00 FD62T225■839.00 FD62T250■ D HFD62B070■3716.20 HFD62B080■3716.20 HFD62B090■3716.20 HFD62B100■3716.20 HFD62B110■3716.20 HFD62B125■3716.20 HFD62B150■3716.20 HFD62B175■3716.20 HFD62B200■3716.20 HFD62B225■3716.20 HFD62B250■4845.20 070 080 090 100 110 125 150 175 200 225 250 CIRCUIT BREAKERS Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: FD 250A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip AC DC Catalog Number 024 120 240 277 480 600 — — — — — — S17FD60 S01FD60 S03FD60 S15FD60▲ S04FD60 S06FD60▲ — — — — — 012 024 048 125 250 S16FD60▲ S07FD60 S09FD60▲ S11FD60 S13FD60▲ Undervoltage Trip Combinations Control Voltage 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip AC DC Catalog Number 120 208 240 277 480 600 — — — — — — U01FD60 U02FD60▲ U03FD60 U16FD60▲ U06FD60▲ U08FD60▲ 569.00 569.00 569.00 569.00 569.00 569.00 Catalog Number W01FD64 W02FD64▲ W03FD64▲ W16FD64▲ W06FD64▲ W08FD64▲ 802.00 802.00 802.00 802.00 802.00 802.00 — — — — 024 048 125 250 U13FD60 U14FD60▲ U10FD60▲ U12FD60▲ 569.00 569.00 569.00 569.00 W13FD64 W14FD64▲ W10FD64▲ W12FD64▲ 802.00 802.00 802.00 802.00 Auxiliary Switch Combinations 1 Auxiliary Switch* 2 Auxiliary Switches Voltage AC DC Catalog Number 480 — A01FD64 242.00 Catalog Number A02FD64 — 12 A01FDLV* 306.00 Gold Plated Contacts - for PLC use 483.00 6 Alarm Switch Combinations CIRCUIT BREAKERS ▲ Built to order. Allow 7–9 weeks for delivery. Auxiliary switch application is for 480V AC maximum. Note: Old F-frame accessories cannot be used in new Sentron line. Likewise, new FD-frame accessories cannot be used on old F-frame circuit breakers. 6/28 Maximum Voltage 1 Alarm Switch 1 Alarm Switch and 1 Auxiliary Switch AC DC Catalog Number Catalog Number 480 250 B00FD64 242.00C01FD64 483.00 Molded Case Circuit Breakers SELECTION JD 400A Frame Sentron Series Type JXD2-A Blue 240V AC, 250V DC Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) 2-Pole (3 Pole Width) Catalog Number JXD22B200■2277.00 JXD22B225■2277.00 JXD22B250■2277.00 JXD22B3002277.00 JXD22B350■2277.00 JXD22B4002277.00 Continuous Current Rating @ 40°C 200 225 250 300 350 400 3-Pole Catalog Number JXD23B2002767.00 JXD23B2252767.00 JXD23B2502767.00 JXD23B3002767.00 JXD23B3502767.00 JXD23B4002767.00 Type JXD6-A Blue 600V AC, 500V DC Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) JXD62B200■2847.00 JXD62B225■2847.00 JXD62B250■2847.00 JXD62B3002847.00 JXD62B350■2847.00 JXD62B4002847.00 200 225 250 300 350 400 Label Label JXD63B2003366.00 JXD63B2253366.00 JXD63B2503366.00 JXD63B3003366.00 JXD63B3503366.00 JXD63B4003366.00 Type JD6-A Blue Label Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 2-Pole 600V AC, 250V DC (3 Pole Width) 200 225 250 300 350 400 JD62B200■2958.00 JD62B225■2958.00 JD62B250■2958.00 JD62B300■2958.00 JD62B350■2958.00 JD62B400 2958.00 JD62F400 1184.00 JD62T200■1662.00 JD62T225■1662.00 JD62T250■1662.00 JD62T300■1662.00 JD62T350■1662.00 JD62T400 1662.00 JD63F400 1515.00 JD63T200 JD63T225 JD63T250 JD63T300 JD63T350 JD63T400 Ordering Information Complete Breaker Unassembled with Lugs Prices of JD6, HJD6, and HHJD6 breakers include frame, trip and both line and load lugs (TA2J6500). When ordered by these catalog numbers, the customer will receive the frame, trip, and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of JXD6, HJXD6, HHJXD6, and CJD6 include frame with noninterchangeable trip unit installed only. Order required lugs separately. For line and load lugs (TA2J6500) installed, add suffix “L” to catalog number (add 2 times list price of lugs for each pole). 100% Rated Types JXD2, JXD6 and HJXD6 breakers are available with 100% ratings. To order add suffix “H” to catalog number, and 10% to list price.■ 100% rated JD breakers require the use of 90°C Cu cable and lugs TC1J6600 or TC2J6500. 50°C Applications see page 6-73. 400Hz Applications see page 6-73. JD63B200 JD63B225 JD63B250 JD63B300 JD63B350 JD63B400 3534.00 3534.00 3534.00 3534.00 3534.00 3534.00 1851.00 1851.00 1851.00 1851.00 1851.00 1851.00 Interrupting Ratings Breaker Type JXD2-2 JXD6-2, JD6-A HJD6-A, HJXD6-A HHJD6-A, HHJXD6 CJD6 RMS Symmetrical Amperes (KA) CSA / UL 489 AIR (File E10848) Volts AC Volts DC (50/60Hz) 240 480 600 250 065 — — 30 (2-P) 065 035 025 30 (2-P) 100 065 035 30 (2-P) 200 100 050 — 200 150 100 50 (2-P) IEC 947-2 Volts AC (50/60Hz) 220/240 380/415 500 lcu lcs lcu lcs — — — — — 25 (3-P) 065 033 040 20 35 (3-P) 100 050 065 33 — 200 100 100 50 50 (3-P) — — — — Lugs For 75°C Wire Cables per Lug 1, 2 2 1 TA1L6750 1 1 TC1J6600 1 TC2J6500 1, 2 Compression Lug CCL600 1 Catalog Number TA2J6500 500 lcu — 30 42 65 — lcs — 15 21 33 — Wire Range #3/0-500 kcmil Cu #4/0-500 kcmil Al 250-500 kcmil Al 500-750 kcmil Al 500-600 kcmil Cu #3/0-600 kcmil Cu #3/0-500 kcmil Cu 500 kcmil Cu/Al 28.00 68.00 69.00 68.00 134.00 Instantaneous Adjustment Trip Range Breaker Ampere Rating Nominal Instantaneous Values Low 2 3 4 5 6 7 High 200-300 1250 1430 1610 1790 1960 2140 2320 2500 350-400 2000 2290 2570 2860 3140 3430 3710 4000 ■ Built to order. Allow 3-4 weeks for delivery. Type JXD6 circuit breakers are UL Listed for reverse feed applications. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. See Note: A, page 6-70. HHJD6 type circuit breakers meet the CSA / UL criteria for “current limiting” at 240 and 480V AC. rated. Note: JD frame qualified to UL489 supplement B “NAVAL.” See page 6-73 for additional information. HACR Modifications page 6-73 Accessories pages 6-32 and 6-75 to 6-80 6/29 CIRCUIT BREAKERS 200 225 250 300 350 400 6 3-Pole 600V AC, 500V DC Molded Case Circuit Breakers SELECTION JD 400A Frame Sentron Series Black Label Type HJD6-A, HJXD6-A Interchangeable Trip Complete Breaker Unassembled with Lugs Frame Only Catalog Number Trip Unit Only Catalog Number D1 Catalog Number Continuous Current Rating @ 40°C L 2-Pole 600V AC, 250V DC (3 Pole Width) HJD63B200 5845.00 HJD63B225 5845.00 HJD63B250 5845.00 HJD63B300 5845.00 HJD63B350 5845.00 HJD63B400 5845.00 Type HHJD6, HHJXD6-A HJD63F400 3826.00 JD63T200 1851.00 JD63T225 1851.00 JD63T250 1851.00 JD63T300 1851.00 JD63T350 1851.00 JD63T400 1851.00 Black Label 2-Pole 600V AC (3 Pole Width) 200 225 250 300 350 400 HHJD62B200■5832.00 HHJD62B225■5832.00 HHJD62B250■5832.00 HHJD62B300■5832.00 HHJD62B350■5832.00 HHJD62B400■5832.00 200 225 250 300 350 400 HHJD63B2007011.00 HHJD63B2257011.00 HHJD63B2507011.00 HHJD63B3007011.00 HHJD63B3507011.00 HHJD63B4007011.00 HHJD62F400■4058.00 HHJD63F4004992.00 JD62T200■1662.0 JD62T225■1662.0 JD62T250■1662.0 JD62T300■1662.0 JD62T350■1662.0 JD62T400 JD63T200 JD63T225 JD63T250 JD63T300 JD63T350 JD63T400 6 Type CJD6 Red Fuseless Current Limiting Non-Interchangeable Trip (Assembled Circuit Breakers Without Lugs) CIRCUIT BREAKERS Continuous Current Rating @ 40°C 200 225 250 300 350 400 For inches / millimeters conversion, see Application Data section. ■ Built to order. Allow 3-4 weeks for delivery. 2-pole units available in 3-pole construction. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. 6/30 3-Pole 600V AC, 500V DC 200 225 250 300 350 400 L 1851.00 1851.00 1851.00 1851.00 1851.00 1851.00 Label 2-Pole 3-Pole 600V AC/250V DC 600V AC/500V DC Catalog Number For 2-pole application use outside poles of 3-pole circuit breaker For CJD63B200■7303. CJD63B225■7303. CJD63B250■7303. CJD63B300■7303. CJD63B350■7303. CJD63B4007303.00 non-interchangeable 3-pole HJD6 or HHJD6 type circuit breaker change the prefix identifier to HJXD6 or HHJXD6. Order lugs separately. W W Figure 1 D HJD62F400■3077.00 JD62T200■1662.0 JD62T225■1662.0 JD62T250■1662.0 JD62T300■1662.0 JD62T350■1662.0 JD62T400 HJD62B200■4851.00 HJD62B225■4851.00 HJD62B250■4851.00 HJD62B300■4851.00 HJD62B350■4851.00 HJD62B400■4851.00 D 200 225 250 300 350 400 Figure 2 Dimensions (in inches) D To Handle D1 Figure 1 JXD2-A, JXD6-A, JD6-A HJD6-A, HJXD6-A, HHJD6, 7.5 11 HJD6, HJXD6, HHJXD6, JXD6-ETI 4 5.44 Figure 2 CJD6, CJD6-ETI 4 5.44 Breaker Type W L 7.5 17.86 Enclosures Type Catalog Number List Price $ 1 3R 12 4X 7, 9 (200-250A) 7, 9 (300-400A) J6N1 J6N3R J6N12 LD6SS4 EC4 EE 231.00 1246.00 648.00 6211.00 4306.00 5958.00 Neutral W60992 348.00 Shipping Weights Number of Number per Shipping Poles Carton Weight (lbs.) JXD2, JXD6, JD6, HJD6, HHJD6 Assembled Breaker (less terminals) 2 1 17.5 3 1 19.5 JD6, HJD6, HHJD6 Frame Only 2 1 14 3 1 15.5 JD6 Trip Unit Only 2 1 03.5 3 1 04 CJD6 Complete Assembled Breaker (less terminals) 2 1 29.5 3 1 31.5 JXD6-ETI, CJD6-ETI see page 6-56 for ordering information. HJXD6, HHJXD6 Circuit Breakers are CSA Certified / UL listed for reverse fed applications. CE applies to non-interchangeable type HJXD only. HACR rated. Type Molded Case Circuit Breakers SELECTION SJD 400A Frame Digital Solid State Sentron Sensitrip III Current Limiting Type SHJD6(A) Type SJD6(A) Blue Label Black Label 3-Pole, 600V AC Catalog Number 200 300 400 4082.00 4082.00 4082.00 200 300 400 6530.00 6530.00 6530.00 200 300 400 5545.00 5545.00 5545.00 200 300 400 8195.00 8195.00 8195.00 SHJD69200■ SHJD69300■ SHJD69400■ SHJD69200G■ SHJD69300G■ SHJD69400G■ SHJD69200NT■ SHJD69300NT■ SHJD69400NT■ SHJD69200NGT■ SHJD69300NGT■ SHJD69400NGT■ 200 300 400 5812.00 5812.00 5812.00 200 300 400 8195.00 8195.00 8195.00 200 300 400 7197.00 7197.00 7197.00 200 300 400 9941.00 9941.00 9941.00 SJD 400A Frame – 100% Rated Type SJD6A-H Blue Label 200 300 400 7734.00 7734.00 7734.00 200 300 400 10498.00 10498.00 10498.00 200 300 400 9290.00 9290.00 9290.00 200 300 400 12818.00 12818.00 12818.00 Black Label Catalog Number 200 300 400 4478.00 4478.00 4478.00 200 300 400 7197.00 7197.00 7197.00 200 300 400 6098.00 6098.00 6098.00 200 300 400 9006.00 9006.00 9006.00 Trip Type Breaker Type Number per Carton Shipping Weight (lbs) SJD6(A), SLD6(A) SHJD6(A), SHLD6(A) SCJD6, SCLD6 1 20 No of Cables Catalog per ConNumber nector 2 TA2J6500 2 1 TA1L6750 1 TC1J6600 1 TC2J6500 2 TA2J630 2 Compression Lug CCL600 (1 pc.) Max Current Rating SHJD69200H■ SHJD69300H■ SHJD69400H■ SHJD69200GH■ SHJD69300GH■ SHJD69400GH■ SHJD69200NTH■ SHJD69300NTH■ SHJD69400NTH■ SHJD69200NGTH■ SHJD69300NGTH■ SHJD69400NGTH■ 200 300 400 6402.00 6402.00 6402.00 200 300 400 9022.00 9022.00 9022.00 200 300 400 7894.00 7894.00 7894.00 200 300 400 10944.00 10944.00 10944.00 1 20 1 33 Cont Current Setting Long Time Delay Instantaneous Setting Short Time Pick Up Wire Range #3/0-500 kcmil Cu #4/0-500 kcmil Cu 500–750 kcmil Cu/Al 500–600 kcmil Cu #3/0-600 kcmil Cu #3/0-500 kcmil Cu #4–#3/0-Cu/Al List Price $ 28.00 28.00 68.00 68.00 69.00 68.00 29.00 #1/0-500 kcmil Cu/Al 134.00 Neutral Transformers (for 3ø, 4 wire) Ampere Rating Trip Unit Adjustable Functions Suffix Letter Code Shipping Weights Lugs for 75° C Wire 3-Pole, 600V AC Max Current Rating SJD69200H■ SJD69300H■ SJD69400H■ SJD69200GH■ SJD69300GH■ SJD69400GH■ SJD69200NTH■ SJD69300NTH■ SJD69400NTH■ SJD69200NGTH■ SJD69300NGTH■ SJD69400NGTH■ SCJD69200■ SCJD69300■ SCJD69400■ SCJD69200G■ SCJD69300G■ SCJD69400G■ SCJD69200NT■ SCJD69300NT■ SCJD69400NT■ SCJD69200NGT■ SCJD69300NGT■ SCJD69400NGT■ Type SJD6(A)-H 3-Pole, 600V AC Catalog Number Max Current Rating Catalog Number Short Time Delay Short Time l 2t Pick Up Ground Fault Pick Up Ground Fault Delay None LI — — — — — G LIG — — — NT LSI — — NGT LSIG Interrupting Ratings Breaker Type RMS Symmetrical kA CSA / UL 489 (File E10848) 240V AC 480V AC 600V AC SJD6 – SLD6 SHJD6 – SHLD6 SCJD6 – SCLD6 065 100 200 035 065 150 025 035 100 200 300 400 500 600 Catalog Number N02SJD N03SJD N04SJD N05SLD N06SLD 354.00 354.00 354.00 354.00 354.00 Enclosures (For JD frame, excluding SCJD6) Type Catalog Number 1 3R 4–4X 7, 9 (200–250A) 7, 9 (300–400A) 12 J6N1 J6N3R LD6SS4 EC4 EE J6N12 231.00 1246.00 6211.00 4306.00 5958.00 648.00 Neutral W60992 348.00 Accessories pages 6/32 and 6/75 to 6/80 Note: “G” suffix in catalog number denotes circuit breaker for 3 phase, 3 wire systems. For 3 phase, 4 wire, order correct 4th wire (neutral) transformer as separate and additional item. 6 SJD69200■ SJD69300■ SJD69400■ SJD69200G■ SJD69300G■ SJD69400G■ SJD69200NT■ SJD69300NT■ SJD69400NT■ SJD69200NGT■ SJD69300NGT■ SJD69400NGT■ 3-Pole, 600V AC Max Current Rating Required lugs for Digital Sentron Series SJD and SLD frames are sold as separate items. Separate items – lugs are suitable for 75° C wire. SJD6, SCJD6, SLD6, SCLD6 are acceptable for reverse connection application. SHJD6 and SHLD6 are not acceptable for reverse connection application. ■ Built to order. Allow 3-4 weeks for delivery. For additional information, see Note: A, page 6-71. Refer to the NEC for proper application of 100% rated devices. 6/31 CIRCUIT BREAKERS Catalog Number Red Label 3-Pole, 600V AC Max Current Rating Ordering Information Type SCJD6 Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: JD 400A Frame LD 600A Frame LMD 800A Frame SJD 400A Frame SLD 600A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip AC DC 024 048 120 240 277 480 — — — — — — Catalog Number S17JLD6 S18JLD6▲ S01JLD6 S03JLD6 S15JLD6▲ S04JLD6 569.00 569.00 569.00 569.00 569.00 569.00 Catalog Number — — S01JLD62A S03JLD62A S15JLD64A▲ — 802.00 802.00 802.00 - — — — — — 012 024 048 125 250 S16JLD6▲ S07JLD6 S09JLD6▲ S11JLD6 S13JLD6▲ 569.00 569.00 569.00 569.00 569.00 S16JLD62A▲ S07JLD62A S09JLD62A S11JLD62A▲ S13JLD62A▲ 802.00 802.00 802.00 802.00 802.00 Undervoltage Trip Combinations Control Voltage Sensitrip Ammeter 1 Undervoltage Trip 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — Catalog Number U01JLD6 569.00 U02JLD6▲569.00 U03JLD6 569.00 U16JLD6▲569.00 U06JLD6 569.00 U08JLD6▲569.00 U01JLD62A802.00 U02JLD62A▲802.00 U03JLD62A▲802.00 U16JLD64A▲802.00 U06JLD64A▲802.00 — -- U01JLD62AA1035.00 U02JLD62AA▲1035.0 U03JLD62AA▲1035.0 U16JLD62AA▲1035.0 U06JLD64AA▲1035.0 — -- — — — — 024 048 125 250 U13JLD6 569.00 U14JLD6▲569.00 U10JLD6▲569.00 U12JLD6▲569.00 U13JLD62A802.00 U14JLD62A▲802.00 U10JLD62A▲802.00 U12JLD62A▲802.00 U13JLD62AA1035.00 U14JLD62AA▲1035.0 U10JLD62AA▲1035.0 U12JLD62AA▲ Auxiliary Switch Combinations 6 The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. CIRCUIT BREAKERS Ammeter Mounting Kit Maximum Voltage 1 Form C* 2 Form C AC DC Catalog Number Catalog Number 480 250 A01JLD64 242.00 A02JLD64 — 12 A01JLDLV* 306.00 (Gold Plated Contacts) Alarm Switch Combinations Maximum Voltage Note: Accessory modules can only be added to right side pole of solid state SJD and SLD frame circuit breakers. All accessories on this page are useable on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6, HL6 and SLL circuit breakers. No accessories can be added if mechanical interlock is used. 6/32 1 Alarm Switch 1 Alarm Switch and 1 Auxiliary Switch AC DC Catalog Number Catalog Number 480 250 B01JLD64 242.00 A01JLD64B Plug-in Ammeter Display Units Breaker Type The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. 483.00 SJD, SLD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 ▲ Built to order. Allow 7-9 weeks for delivery. 1 Alarm Switch and 2 Auxiliary Switches Catalog Number 483.00 A02JLD64B Molded Case Circuit Breakers SELECTION LD 600A Frame Sentron Series Blue Label Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) 2-Pole (3 Pole Width) 3-Pole 600V AC 250V DC 600V AC 500V DC Catalog Catalog Number Number LXD62B450■4376.00 LXD63B4505456.00 LXD62B500■4376.00 LXD63B5005456.00 LXD62B6004376.00 LXD63B6005456.00 Type LD6-A Blue Label Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled w/Lugs Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 2-Pole 600V AC, 250V DC (3 Pole Width) LD62B250■4488.00 LD62B300■4488.00 LD62B350■4488.00 LD62B4004488.00 LD62B450■4488.00 LD62B500■4488.00 LD62B6004488.00 250 300 350 400 450 500 600 LD62F600 JD62T250■1662.00 JD62T300■1662.00 JD62T350■1662.00 JD62T400 1662.00 LD62T450■1662.00 LD62T500■1662.00 LD62T600 1662.00 LD63F600 JD63T250 1851.00 JD63T300 1851.00 JD63T350 1851.00 JD63T400 1851.00 LD63T450 1851.00 LD63T500 1851.00 LD63T600 1851.00 3-Pole 600V AC, 500V DC 250 300 350 400 450 500 600 LD63B2505624.00 LD63B3005624.00 LD63B3505624.00 LD63B4005624.00 LD63B4505624.00 LD63B5005624.00 LD63B6005624.00 Interrupting Ratings Breaker Type RMS Symmetrical Amperes (KA) CSA / UL 489 AIR (File E10848) Volts AC (50/60Hz) Volts DC 240 480 600 250 500 LXD6, LD6 HLD6, HLXD6 HHLD6, HHLXD6 CLD6 065 100 200 200 035 065 100 150 025 035 050 100 IEC 947-2 Volts AC (50/60Hz) 220/240 380/415 (lcu) (lcs) (lcu) (lcs) 25 (3-P) 065 033 040 20 35 (3-P) 100 050 065 33 — 200 100 100 50 50 (3-P) — — — — 30 (2-P) 30 (2-P) — 30 (2-P) Shipping Weights 500 (lcu) 30 42 65 — Instantaneous Adjustment Trip Range Breaker Ampere Rating 250-300 350-450 500-600 Nominal Instantaneous Values Low 2 3 1250 1430 1610 2000 2290 2570 3000 3430 3800 4 1790 2860 4290 5 1960 3140 4710 6 2140 3430 5140 7 2320 3710 5570 Complete Breaker Unassembled with Lugs Prices of LD6, HLD6, and HHLD6 breakers include frame, trip, and both line and load lugs (TA2J6500). When ordered by these catalog numbers, the customer will receive the frame, trip and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of LXD6, HLXD6, HHLXD6, and CLD6 include frame with noninterchangeable trip unit installed only. Order required lugs separately. For line and load lugs (TA2J6500) installed, add suffix “L” to catalog number (add 2 times list price of lugs for each pole). 100% Rated Types LXD2, LXD6 and HLXD6 breakers are available with 100% ratings. To order add suffix “H” to catalog number, and 10% to list price. 100% rated LD breakers require the use of 90°C Cu cable and lugs TC1J6600 or TC2J6500. 50°C Applications see page 6-73. 400Hz Applications see page 6-73. High 2500 4000 6000 (lcs) 15 21 33 — Number of Number per Shipping Poles Carton Weight (lbs.) LXD6, LD6, HLD6, HHLD6 Assembled Breaker (less terminals) 2 1 17.5 3 1 19.5 LD6, HLD6, HHLD6 Frame Only 2 1 14 3 1 15.5 LD6, HHLD6 Trip Unit Only 2 1 03.5 3 1 04 CLD6 Complete Assembled Breaker (less terminals) 2 3 1 1 29.5 31.5 Lugs For 75°C Wire ■ Built to order. Allow 3-4 weeks for delivery. Type LXD6A circuit breakers are CSA Certified / UL Listed for reverse fed applications. When wired as shown on page 6-3, this circuit breaker is UL listed and rated for use on 500V DC ungrounded UPS systems only. See Note: A, page 6-70. HACR rated. Note: LD frame qualified to UL489 supplement SB “NAVAL”. See page 6-73 for additional information. Modifications page 6/73 Accessories pages 6/36 and 6/75 to 6/80 Cables Catalog per Number Lug TA2J6500 1, 2 2 1 TC2J6500 2 TA1L6750 1 1 TC1J6600 1 Compression Lug CCL600 1 Wire Range #3/0 500 kcmil Cu #4/0 500 kcmil Al 250-500 kcmil Al #3/0-500 kcmil Cu 500-750 kcmil Al 500-600 kcmil Cu #3/0-600 kcmil Cu 500 kcmil Cu/Al 6/33 6 Continuous Current Rating @ 40°C 450 500 600 Ordering Information CIRCUIT BREAKERS Type LXD6-A Molded Case Circuit Breakers SELECTION LD 600A Frame Sentron Series Type HLD6-A, HLXD6 Black Label Interchangeable Trip Complete Breaker Unassembled w/Lugs Frame Only Catalog Number Trip Unit Only Catalog Number Catalog Number D1 Continuous Current Rating @ 40°C L 2-Pole 600V AC, 250V DC (3 Pole Width) L HLD62F600■ JD62T250■1662.0 JD62T300■1662.0 JD62T350■1662.0 JD62T400 1662.0 LD62T450■1662.0 LD62T500■1662.0 LD62T600 3-Pole 600V AC, 500V DC 250 300 350 400 450 500 600 HLD63B250 7465.00 HLD63B300 7465.00 HLD63B350 7465.00 HLD63B400 7465.00 HLD63B450 7465.00 HLD63B500 7465.00 HLD63B600 7465.00 HLD63F600 JD63T250 JD63T300 JD63T350 JD63T400 LD63T450 LD63T500 LD63T600 Black Label 2-Pole 600V AC (3 Pole Width) HHLD62B250■7318.00 HHLD62B300■7318.00 HHLD62B350■7318.00 HHLD62B400■7318.00 HHLD62B450■7318.00 HHLD62B500■7318.00 HHLD62B600■7318.00 1851.0 1851. 1851.0 1851.0 0 0 1851.00 HHLD62F600■ JD62T250■ 1662.0 JD62T300■ 1662.0 JD62T350■ 1662.0 JD62T400 1662.0 HHLD62T450■1662. HHLD62T500■1662 HHLD62T600■ W D Figure 2 Dimensions (in inches) To Handle Figure 1 LXD6-A, LD6-A HLD6-A HHLD6, HHLXD6, LXD6–ETI Figure 2 CLD6, CLD6-ETI W L D D1 7.5 11 4 5.44 7.5 17.86 4 5.44 Enclosures 3-Pole 600V AC 6 250 300 350 400 450 500 600 Figure 1 Breaker Type Type HHLD6, HHLXD6 250 300 350 400 450 500 600 W D HLD62B250■ 5868.00 HLD62B300■ 5868.00 HLD62B350■ 5868.00 HLD62B400■ 5868.00 HLD62B450■ 5868.00 HLD62B500■ 5868.00 HLD62B600■ 5868.00 250 300 350 400 450 500 600 HHLD63B2508864.00 HHLD63B3008864.00 HHLD63B3508864.00 HHLD63B4008864.00 HHLD63B450■8864.00 HHLD63B500■8864.00 HHLD63B600■8864.00 HHLD63F600 JD63T250 1851.0 JD63T300 1851.0 JD63T350 1851.0 JD63T400 1851.0 HHLD63T450■ HHLD63T500■ HHLD63T600■ Type CLD6 Type Catalog Number 1 3R 12 4X 7,9 LD6N1 LD6N3R LD6N12 LD6SS4 ED6 402.00 1447.00 875.00 6211.00 10131.00 Neutral W60993 308.00 Red Label Fuseless Current Limiting Non-Interchangeable Trip (Assembled Circuit Breaker) CIRCUIT BREAKERS 2-Pole 3-Pole Continuous Current Rating @ 40°C 600V AC/250V DC 600V AC/500V DC 450 500 600 For 2-pole application use outside poles of 3-pole circuit breaker For inches / millimeters conversion, see Application Data section ■ Built to order. Allow 3-4 weeks for delivery. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. 6/34 Catalog Number For CLD63B450■11666 CLD63B500 11666 CLD63B600 complete assembled 3 pole HLD6 or HHLD6 type circuit breaker change the prefix identifier HLD6 or HHLD6 to HLXD6 or HHLXD6. Price is sum of frame and trip units prices, e.g. price of HLXD63B400 is the price of HLD63F600 plus the price of LD63T600. Order the terminal connectors separately.■ Type HLXD6, HHLXD6 Circuit Breakers are CSA Certified / UL Listed for reverse feed applications. LXD6-ETI, CLD6-ETI see page 6-55 for ordering information. CE Applies to non-interchangable type HLXD only. HACR rated. Molded Case Circuit Breakers SELECTION SLD 600A Frame Digital Solid State Sentron Sensitrip III Series Current Limiting Type SLD6(A) Blue Label Black Label 3-Pole, 600V AC SLD69300■ SLD69400■ SLD69500■ SLD69600■ SLD69300G■ SLD69400G■ SLD69500G■ SLD69600G■ SLD69300NT■ SLD69400NT■ SLD69500NT■ SLD69600NT■ SLD69300NGT■ SLD69400NGT■ SLD69500NGT■ SLD69600NGT■ Red Label 3-Pole, 600V AC Max Current Rating Catalog Number Type SCLD6 Type SHLD6(A) 3-Pole, 600V AC Max Current Rating Catalog Number 300 400 500 600 5576.00 5576.00 5576.00 5576.00 300 400 500 600 7912.00 7912.00 7912.00 7912.00 300 400 500 600 7006.00 7006.00 7006.00 7006.00 300 400 500 600 9738.00 9738.00 9738.00 9738.00 SHLD69300■ SHLD69400■ SHLD69500■ SHLD69600■ SHLD69300G■ SHLD69400G■ SHLD69500G■ SHLD69600G■ SHLD69300NT■ SHLD69400NT■ SHLD69500NT■ SHLD69600NT■ SHLD69300NGT■ SHLD69400NGT■ SHLD69500NGT■ SHLD69600NGT■ Max Current Rating Catalog Number 300 400 500 600 6790.00 6790.00 6790.00 6790.00 300 400 500 600 9574.00 9574.00 9574.00 9574.00 300 400 500 600 8407.00 8407.00 8407.00 8343.00 300 400 500 600 11615.00 11615.00 11615.00 11615.00 SCLD69300■ SCLD69400■ SCLD69500■ SCLD69600■ SCLD69300G■ SCLD69400G■ SCLD69500G■ SCLD69600G■ SCLD69300NT■ SCLD69400NT■ SCLD69500NT■ SCLD69600NT■ SCLD69300NGT■ SCLD69400NGT■ SCLD69500NGT■ SCLD69600NGT■ 300 400 500 600 12024.00 12024.00 12024.00 12024.00 300 400 500 600 15880.00 15880.00 15880.00 15880.00 300 400 500 600 14231.00 14231.00 14231.00 14231.00 300 400 500 600 18726.00 18726.00 18726.00 18726.00 SJD6, SLD6 H Trip Unit Adjustable Functions None LI Long Time Delay Instantaneous Setting Short Time Pick Up — Short Time l2t Pick Up Ground Fault Pick Up Ground Fault Delay — — — — Short Time Delay G LIG — — — NT LSI — — NGT LSIG SJD6, SHJD6, SLD6, SHLD6 H SCJD6, SCLD6 Dimensions (Inches) Breaker Type W H D D1 SJD6(A), SHJD6(A) SLD6(A), SHLD6(A) SLD6, SHLD6 7.5 11 4 5.44 SCJD6 SCLD6 7.5 17.86 4 5.44 Enclosures (For LD frame, excluding SCLD6) Note: “G” suffix in catalog number denotes circuit breaker for 3 phase, 3 wire circuits. For 3 phase, 4 wire, order correct 4th wire (neutral) transformer as separate and additional item. For ordering information and terminal connectors, neutral transformers and enclosures, see page 6-31. 100% Rated – Not available in SLD6 Frame. ■ Built to order. Allow 3-4 weeks for delivery. Type Catalog Number 1 3R 4–4X 7, 9 12 LD6N1 LD6N3R LD6SS4 ED6 LD6N12 Neutral W60993 6/35 6 Trip Type Cont Current Setting CIRCUIT BREAKERS Suffix Letter Code Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: JD 400A Frame LD 600A Frame LMD 800A Frame SJD 400A Frame SLD 600A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip AC DC Catalog Number Catalog Number 024 048 120 240 277 480 — — — — — — S17JLD6 S18JLD6▲ S01JLD6 S03JLD6 S15JLD6▲ S04JLD6 569.00 569.00 569.00 569.00 569.00 569.00 — — S01JLD62A S03JLD62A S15JLD64A▲ — --802.00 802.00 802.00 - — — — — — 012 024 048 125 250 S16JLD6▲ S07JLD6 S09JLD6▲ S11JLD6 S13JLD6▲ 569.00 569.00 569.00 569.00 569.00 S16JLD62A▲ S07JLD62A S09JLD62A S11JLD62A▲ S13JLD62A▲ 802.00 802.00 802.00 802.00 802.00 Undervoltage Trip Combinations Control Voltage Sensitrip Ammeter 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip Catalog Number 1 Undervoltage Trip and 2 Auxiliary Switches AC DC 120 208 240 277 480 600 — — — — — — U01JLD6 569.00 U02JLD6▲569.00 U03JLD6 569.00 U16JLD6▲569.00 U06JLD6 569.00 U08JLD6▲569.00 Catalog Number U01JLD62A802.00 U02JLD62A▲802.00 U03JLD62A▲802.00 U16JLD64A▲802.00 U06JLD64A▲802.00 — -- Catalog Number U01JLD62AA1035.00 U02JLD62AA▲1035.00 U03JLD62AA▲1035.00 U16JLD62AA▲1035.00 U06JLD64AA▲1035.00 — -- — — — — 024 048 125 250 U13JLD6 569.00 U14JLD6▲569.00 U10JLD6▲569.00 U12JLD6▲569.00 U13JLD62A802.00 U14JLD62A▲802.00 U10JLD62A▲802.00 U12JLD62A▲802.00 U13JLD62AA1035.00 U14JLD62AA▲1035.00 U10JLD62AA▲1035.00 U12JLD62AA▲1035.00 Auxiliary Switch Combinations 6 The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. CIRCUIT BREAKERS Ammeter Mounting Kit Maximum Voltage 1 Form C* 2 Form C AC DC Catalog Number Catalog Number 480 250 A01JLD64 A02JLD64 — 12 A01JLDLV* (Gold Plated Contacts) Alarm Switch Combinations Maximum Voltage Note: Accessory modules can only be added to right side pole of solid state SJD and SLD frame circuit breakers. All accessories on this page are useable on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6, HL6 and SLL circuit breakers. No accessories can be added if mechanical interlock is used. 6/36 1 Alarm Switch 1 Alarm Switch and 1 Auxiliary Switch 1 Alarm Switch and 2 Auxiliary Switches Catalog Number Catalog Number A01JLD64B A02JLD64B AC DC Catalog Number 480 250 B01JLD64 242.00 Plug-in Ammeter Display Units Breaker Type The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. 483.00 SJD, SLD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 ▲ Built to order. Allow 4-9 weeks for delivery. 1588.00 306.00 Molded Case Circuit Breakers SELECTION LMD 800A Frame Sentron Series Type LMXD6 Blue Label Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) 2-Pole (3 Pole Width) 3-Pole Catalog Catalog Number Number — LMXD63B500■7 LMXD62B600■ 5582.00 LMXD63B600 7067 LMXD62B700■ 5582.00 LMXD63B700 7067 LMXD62B800 5582.00 LMXD63B800 Continuous Current Rating @ 40°C 500 600 700 800 Blue Label Type LMD6 Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled w/Lugs Catalog Number Frame Only Catalog Number Trip Unit Only Catalog Number 2-Pole 600V AC, 250V DC (3 Pole Width) 500 600 700 800 LMD62B500■5928.00 LMD62B600■5928.00 LMD62B700■5928.00 LMD62B800■5928.00 LMD62F800■2909.00 LMD62T500■2671.0 LMD62T600■2671.0 LMD62T700■2671.0 LMD62T800■ 3-Pole 600V AC, 500V DC 500 600 700 800 LMD63B500■7589.00 LMD63B600■7589.00 LMD63B700■7589.00 LMD63B8007589.00 LMD63F8003716.00 LMD63T500■3351.0 LMD63T600■3351.0 LMD63T700■3351.0 LMD63T8003351.00 Nominal Instantaneous Values Low 2 3 4 3000 3430 3860 4290 3200 3500 3700 4200 Complete Breaker Unassembled with Lugs Prices of LMD6 and HLMD6 breakers include frame, trip, and both line and load lugs (TA3K500). These catalog numbers include the frame, trip and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of LMXD6 and HLMXD6 include frame with noninterchangeable trip unit installed only. Order required lugs separately. For line and load lugs (TA3K500) installed, add suffix “L” to catalog number (add 2 times list price of lugs for each pole). 50°C Applications see page 6-73. 400Hz Applications see page 6-73. Shipping Weights Instantaneous Adjustment Trip Range Ampere Rating 500-600 700-800 Ordering Information 5 4710 4700 6 5140 6400 7 5570 7300 High 6000 8000 Number of Poles Number per Carton Shipping Weight (lbs.) LMD6, HLMD6, LMXD6, HLMXD6 Complete Breaker (less terminals) 2 3 1 1 53 61.5 LMD6, HLMD6 Frame Only 2 3 1 1 42.25 46 2 3 1 1 6 LMD6, HLMD6 Trip Unit Only 4.5 6.5 Catalog Number TA2K500 TA3K500 TA2N750 ■ Built to order. Allow 3-4 weeks for delivery. LMXD6 circuit breakers are CSA Certified / UL Listed for reverse connected applications. Use 6 lugs for 3-pole, use 4 connectors for 2-pole. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500UDC ungrounded UPS systems only. See Note: A, page 6-70. HACR rated. Cables per Lug 1, 2 1-3 1, 2 Wire Range #1-500 kcmil Cu/Al #1/0-500 kcmil Cu/Al 500-750 kcmil Cu/Al 64.00 87.00 90.00 Modifications page 6/73 Enclosures Section 5 Accessories pages 6/39 and 6/75 to 6/80 6/37 CIRCUIT BREAKERS Lugs for 75°C Wire Molded Case Circuit Breakers SELECTION / DIMENSIONS LMD 800A Frame Sentron Series Black Label Type HLMXD6 Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) 2-Pole Continuous Current Rating @ 40°C 500 600 700 800 600V AC 250V DC 3-Pole For 2-Pole application use outside poles of 3-Pole circuit breaker. 600V AC 500V DC Catalog Number HLMXD63B500■ 8553.0 HLMXD63B600■ 8553.0 HLMXD63B700■ 85 HLMXD63B800 Black Label Type HLMD6 Continuous Current Rating @ 40°C D1 D W Interchangeable Trip Complete Breaker Unassembled Frame Only Catalog Number Catalog Number Trip Unit Only Catalog Number L 2-Pole 600V AC, 250V DC (3 Pole Width) 500 600 700 2671.00 HLMD62B500■7066.00 HLMD62B600■7066.00 HLMD62B700■7066.00 HLMD62F800■ LMD62T500■2671.0 LMD62T600■2671.0 LMD62T700■ HLMD63F800 LMD63T500 ■ 3351.0 LMD63T600 ■ 3351.0 LMD63T700 ■ 335 LMD63T800 3351.00 3-Pole 600V AC, 500V DC 500 600 700 800 HLMD63B5009077.00 HLMD63B6009077.00 HLMD63B7009077.00 HLMD63B8009077.00 6 Breaker Type LMD6, LMXD6 HLMD6, HLMXD6 IEC 947-2 Volts AC (50/60HZ) 220/240 380/415 (lcu) (lcs) (lcu) (lcs) 065 033 040 20 100 050 065 33 500 (lcu) (lcs) 30 15 42 21 CIRCUIT BREAKERS For inches / millimeters conversion, see Application Data section. ■ Built to order. Allow 3-4 weeks for delivery. HLMXD6 circuit breakers are UL Listed for reverse connection applications. 6/38 Breaker Type LMD6, LMXD6, HLMD6, HLMXD6 LMXD6-ETI Interrupting Ratings UL 489A IR RMS Symmetrical Amperes (KA) Volts AC Volts DC 240 480 600 250 500 65 50 25 30 (2-P) 25 (3-P) 100 065 050 30 (2-P) 50 (3-P) Dimensions (in inches) LMXD6-ETI, see page 6-55 for catalog information. When wired as shown on page 6-3, this circuit breaker is UL listed and rated for use on 500VDC ungrounded UPS systems only. HACR rated. W L D D1 7.5 16 4.5 5.93 Enclosures Type Catalog Number 1 3R 12 LMD1 LMD3R LMD12■ 802.00 1969.00 2578.00 Neutral W63623 428.00 Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: JD 400A Frame LD 600A Frame LMD 800A Frame SJD 400A Frame SLD 600A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip AC DC Catalog Number 024 048 120 240 277 480 — — — — — — S17JLD6 S18JLD6▲ S01JLD6 S03JLD6 S15JLD6▲ S04JLD6 569.00— 569.00— 569.00S01JLD62A 569.00S03JLD62A 569.00S15JLD64A▲ 569.00— Catalog Number --802.00 802.00 802.00 -- — — — — — 012 024 048 125 250 S16JLD6▲ S07JLD6 S09JLD6▲ S11JLD6 S13JLD6▲ 569.00S16JLD62A▲ 569.00S07JLD62A 569.00S09JLD62A 569.00S11JLD62A▲ 569.00S13JLD62A▲ 802.00 802.00 Undervoltage Trip Combinations Control Voltage Sensitrip Ammeter 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip 1 Undervoltage Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — U01JLD6 U02JLD6▲ U03JLD6 U16JLD6▲ U06JLD6 U08JLD6▲ U01JLD62A U02JLD62A▲ U03JLD62A▲ U16JLD64A▲ U06JLD64A▲ — 802.00 802.00 802.00 802.00 802.00 -- U01JLD62AA1035.00 U02JLD62AA▲1035.00 U03JLD62AA▲1035.00 U16JLD62AA▲1035.00 U06JLD64AA▲1035.00 — -- — — — 024 048 125 U13JLD6 569.00 U14JLD6▲ 569.00 U10JLD6▲ 569.00 U13JLD62A 802.00 U14JLD62A▲ 802.00 U10JLD62A▲ 802.00 U13JLD62AA1035.00 U14JLD62AA▲1035.00 U10JLD62AA▲1035.00 569.00 569.00 569.00 569.00 569.00 569.00 Auxiliary Switch Combinations Ammeter Mounting Kit 1 Form C* 2 Form C AC DC Catalog Number Catalog Number 480 250 A01JLD64 A02JLD64483.00 — 12 A01JLDLV* (Gold Plated Contacts) Maximum Voltage AC DC 480 250 Note: Accessory modules can only be added to right side pole of solid state SJD and SLD frame circuit breakers. All accessories on this page are useable on superseded JD2, JJ6, JL6, HJ6, SJL, LJ6, LL6, HL6 and SLL circuit breakers. 1 Alarm Switch and 1 Auxiliary Switch 1 Alarm Switch and 2 Auxiliary Switches Catalog Number Catalog Number Catalog Number B01JLD64 242.00 A01JLD64B 483.00 A02JLD64B Plug-in Ammeter Display Units Breaker Type The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. 1 Alarm Switch SJD, SLD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 6 Alarm Switch Combinations 1588.00 306.00 ▲ Built to order. Allow 7-9 weeks for delivery. No accessories can be added if mechanical interlock is used. 6/39 CIRCUIT BREAKERS The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. Maximum Voltage Molded Case Circuit Breakers SELECTION MD 800A Frame Sentron Series Type MXD6 Blue Label Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) 2-Pole Continuous Current Rating @ 40°C 3-Pole Catalog Number Catalog Number MXD62B500■5582.00 MXD62B600■5582.00 MXD62B700■5582.00 MXD62B800■5582.00 500 600 700 800 MXD63B500■ 7067.00 MXD63B600 7067.00 MXD63B700 7067.00 MXD63B800 7067.00 Type MD6 Blue Label Interchangeable Trip Continuous Current Setting @ 40°C Complete Breaker Unassembled with Lugs Catalog Number Frame Only Trip Unit Only Catalog Number Catalog Number 2-Pole 600V AC, 250V DC MD62B500■5928.00 MD62B600■5928.00 MD62B700■5928.00 MD62B800■5928.00 500 600 700 800 MD62F800■2909.00 MD62T500■2671.0 MD62T600■2671.0 MD62T700■ 26 MD62T800■ MD63F800 3716.00 MD63T5003351.00 MD63T6003351.00 MD63T7003351.00 MD63T8003351.00 3-Pole 600V AC, 500V DC 500 600 700 800 MD63B500 7589.00 MD63B600 7589.00 MD63B700 7589.00 MD63B800 7589.00 Lugs Catalog Number Cables Per Lug Lugs Per Kit Wire Range TA2K500 TA3K500 TC2K500 TC3K350 1-2 1-3 1-2 1-3 1 1 1 1 #1-500 kcmil Cu/Al 1/0-500 kcmil Cu/Al #1-500 kcmil Cu #1-350 kcmil Cu 64.00 87.00 107.00 135.00 2TA2N8750 3TA2N8750 1-2 2 3 600-750 kcmil Cu/Al 327.00 459.00 2TA3N8750 3TA3N8750 1-3 2 3 500-750 kcmil Cu/Al 517.00 744.00 2TA4N8500 3TA4N8500 1-4 2 3 250-500 kcmil Cu/Al 526.00 762.00 2TA4P8500 3TA4P8500 1-4 2 3 250-500 kcmil Cu/Al 522.00 754.00 Ordering Information Complete Breaker Unassembled with Lugs Pricing information for MD6 and HMD6 breakers includes frame, trip, and both line and load lugs (TA3K500). When ordered by these catalog numbers, the customer will receive the frame, trip and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of MXD6, HMXD6 and CMD6 include frame with noninterchangeable trip units installed only. Order required lugs separately. For line and load lugs (TA3K500) installed, add suffix “L” to catalog number (add 2 times list price of lugs for each pole). 100% Rated Types MXD6, HMXD6 and CMD6 breakers are available with 100% ratings. To order add suffix “H” to catalog number, and 10% to list price. 100% rated MD breakers require the use of 90°C Cu cable and lugs 2TA4P8500 or 2TA2N8750 for 2-pole; 3TA4P8500 or 3TA2N8750 for 3-pole. 50°C Applications see page 6-73. 400Hz Applications see page 6-73. Kits 6 CIRCUIT BREAKERS Instantaneous Adjustment Trip Range Ampere Rating 500–600 700–800 Nominal Instantaneous Values Low 2 3 4 3000 3430 3860 4280 4000 4570 5140 5710 Shipping Weights Number of Number per Poles Carton MD6, HMD6, HMXD6, CMD6 Complete Breaker Assembled (less lugs) 2 1 3 1 Shipping Weight (lbs.) 53 61.5 MD6, HMD6 Frame Only 5 4710 6280 6 5140 6850 7 5570 7420 High 6000 8000 2 3 1 1 42.25 46 MD6, HMD6 Trip Unit Only 2 3 1 1 4.5 6.5 Enclosures ■ Built to order. Allow 3-4 weeks for delivery. MXD6 circuit breakers are CSA Certified / UL Listed for reverse connection applications. 2-pole units available in 3-pole width only. Use 6 connectors for 3-pole, use 4 connectors for 2-pole. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems. 6/40 See Note: A, page 6-70. rated breakers with the CE mark will also be marked in the 100% rated version. HACR rated. Note: MD frame qualified to UL489 supplement B “NAVAL”. See page 6-73 for additional information. 80% Type Catalog Number List Price $ 1 3R 12 MND61 MND63 MND612■ 802.00 1969.00 2578.00 Neutral W63623 428.00 Modifications page 6/73 Enclosures Section 5 Accessories pages 6/43 and 6/75 to 6/80 Molded Case Circuit Breakers SELECTION / DIMENSIONS MD 800A Frame Sentron Series Black Label Type HMXD6 Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) 2-Pole 600V AC 250V DC Continuous Current Rating @ 40°C 500 600 700 800 3-Pole 600V AC 500V DC Catalog Number HMXD63B500■ HMXD63B600■ HMXD63B700■ HMXD63B800 For 2-pole application use outside poles of 3-pole circuit breaker 8555.00 8555.00 8555.00 8555.00 Black Label Type HMD6 Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Frame Only Catalog Number Trip Unit Only Catalog Number Catalog Number 2-Pole 600V AC, 250V DC 500 600 700 800 HMD62B500■7066.00 HMD62B600■7066.00 HMD62B700■7066.00 HMD62B800■7066.00 HMD62F800■4047.00 MD62T500■2671.0 MD62T600■2671.0 MD62T700■2671.0 MD62T800■ 3-Pole 600V AC, 500V DC 500 600 700 800 HMD63B5009077.00 HMD63B6009077.00 HMD63B7009077.00 HMD63B8009077.00 HMD63F8005204.00 Type CMD6 MD63T500 3351.0 MD63T600 3351. MD63T700 3351.0 MD63T800 3351.00 Red Label Fuseless Current Limiting Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) Lug When wire lug shield NDTS is used. Catalog Number 500 600 700 800 For 2-pole application use outside poles of 3-pole circuit breaker CMD63B500■ CMD63B600■ CMD63B700■ CMD63B800■ Note: NDTS lug shields are required when oversized lugs are used. The kits include the NDTS shield. 12599.00 12599.00 12599.00 12599.00 Breaker Type MD6, MXD6 Dimensions (in inches) W L D (To Handle) D1 MD6, MXD6, HMD6, HMXD6, CMD6, MXD6-ETI, CMD6-ETI 9 16 6 8.25 with lug shields 9 24 6 8.25 Breaker Type Interrupting Ratings UL 489 AIR—File E10848 RMS Symmetrical Amperes (KA) Volts AC Volts DC IEC 947-2 AIR Volts AC (50/60HZ) 220/240 380/415 500 240 065 480 050 600 25 250 30 (2-P) (lcu) (lcs) (lcu) (lcs) (lcu) (lcs 500 25 (3-P) 065 033 040 20 30 15 HMD6, HMXD6 100 CMD6 200 065 100 50 65 30 (2-P) 30 (2-P) 50 (3-P) 100 050 065 33 50 (3-P) 200 100 100 50 For inches / millimeters conversion, see Application Data section. 42 65 21 33 2-pole units available in 3-pole width only. CMD6-ETI see page 6-56 for catalog information. wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. HACR rated. MXD6-ETI, When ■ Built to order. Allow 3-4 weeks for delivery. HMXD6 circuit breakers are CSA Certified / UL listed for reverse connection applications. 6 3-Pole 600V AC/500V DC 6/41 CIRCUIT BREAKERS Continuous Current Rating @ 40°C 2-Pole 600V AC/250V DC Molded Case Circuit Breakers SELECTION SMD 800A Frame Digital Solid State Sentron Sensitrip III Series Current Limiting Ordering Information Pricing information for all Digital Sentron Series MD and ND frames is for complete breaker only. Price requires lugs or lug kits as separate items. Lugs are suitable for 75°C wire or as noted. Connector wire ranges and cavities are established in conjunction with Table 8.1 of UL 489 standards. Choose actual connector for circuit breakers based on customer requirements. Recommended Terminal Connectors Type SMD6 Type SHMD6 Type SCMD6 Blue Label Black Label Red Label 3-Pole, 600V AC 3-Pole, 600V AC Catalog Number Max Current Rating SMD69600A■ SMD69700A■ SMD69800A■ 600 700 800 SMD69600AG■ SMD69700AG■ SMD69800AG■ SMD69600ANT■ SMD69700ANT■ SMD69800ANT■ 3-Pole, 600V AC Catalog Number Max Current Rating 7686.00 7686.00 7686.00 SHMD69600A■ SHMD69700A■ SHMD69800A■ 600 700 800 600 700 800 9134.00 9134.00 9134.00 SHMD69600AG■ SHMD69700AG■ SHMD69800AG■ 600 700 800 7955.00 7955.00 7955.00 SHMD69600ANT■ SHMD69700ANT■ SHMD69800ANT■ 10575.00 10575.00 10217.00 SHMD69600ANGT■ 600 SHMD69700ANGT■ 700 SHMD69800ANGT■ 800 SMD69600ANGT■ 600 SMD69700ANGT■ 700 SMD69800ANGT■ 800 Catalog Number Max Current Rating 9370.00 9370.00 9370.00 SCMD69600A■ SCMD69700A■ SCMD69800A■ 600 700 800 13914.00 13914.00 13914.00 600 700 800 10785.00 10785.00 10785.00 SCMD69600AG■ SCMD69700AG■ SCMD69800AG■ 600 700 800 16582.00 16582.00 16582.00 600 700 800 9658.00 9658.00 9658.00 SCMD69600ANT■ SCMD69700ANT■ SCMD69800ANT■ 600 700 800 15056.00 15056.00 15056.00 12418.00 12418.00 12418.00 SCMD69600ANGT■ 600 SCMD69700ANGT■ 700 SCMD69800ANGT■ 800 19201.00 19201.00 19201.00 SMD 800A Frame – 100% Rated Type SMD6-H 6 Catalog Number SMD69600AH■ SMD69700AH■ SMD69800AH■ 600 700 800 8452.00 8452.00 8452.00 SMD69600AGH■ SMD69700AGH■ SMD69800AGH■ 600 700 800 10059.00 10059.00 10059.00 SMD69600ANTH■ SMD69700ANTH■ SMD69800ANTH■ 600 700 800 SMD69600ANGTH■ 600 SMD69700ANGTH■ 700 SMD69800ANGTH■ 800 Catalog Number SHMD69600AH■ SHMD69700AH■ SHMD69800AH■ 600 700 800 SHMD69600AGH■ SHMD69700AGH■ SHMD69800AGH■ All types 1 61.5 Lugs for 75°C Wire Max Current Rating 10310.00 10310.00 10310.00 SCMD69600AH■ SCMD69700AH■ SCMD69800AH■ 600 700 800 15304.00 15304.00 15304.00 600 700 800 11866.00 11866.00 11866.00 SCMD69600AGH■ SCMD69700AGH■ SCMD69800AGH■ 600 700 800 18250.00 18250.00 18250.00 8818.00 8818.00 8818.00 SHMD69600ANTH■ 600 SHMD69700ANTH■ 700 SHMD69800ANTH■ 800 10641.00 10641.00 10641.00 SCMD69600ANTH■ SCMD69700ANTH■ SCMD69800ANTH■ 600 700 800 16549.00 16549.00 16549.00 11647.00 11647.00 11647.00 SHMD69600ANGTH■ 600 SHMD69700ANGTH■ 700 SHMD69800ANGTH■ 800 13674.00 13674.00 13674.00 SCMD69600ANGTH■ 600 SCMD69700ANGTH■ 700 SCMD69800ANGTH■ 800 21139.00 21139.00 21139.00 CIRCUIT BREAKERS Trip Type Long Time Delay Cables Catalog per Wire Number Lug Range TA2K500 2 #1-500 kcmil Cu/Al 64.00 TA3K500 3 #1-500 kcmil Cu/Al 87.00 TC2K500 2 #1-500 kcmil Cu 107.00 TC3K350 3 #1-350 kcmil Cu 135.0 Kits (3 lugs/kit) 3TA4N8500 4 250–500 kcmil Cu/Al 72.00 3TA4P8500 4 250–500 kcmil Cu/Al754.00 3TA2N8750 2 600–750 kcmil Cu/Al 459.0 3TA3N8750 3 600–750 kcmil Cu/Al 744.00 Each kit contains the following: 3TA4P8500—3 connectors plus 1 NDTS end barrier 3TA3N8750—3 connectors plus 1 NDTS end barrier 3TA2N8750—3 connectors plus 1 NDTS end barrier Neutral Transformers Instantaneous Setting Short Time Pick Up Short Time Delay Ground Fault Pick Up Ground Fault Delay A LI — — — — AG LIG — — ANT LSI — — ANGT LSIG Interrupting Ratings Breaker Type RMS Symmetrical kA UL 489 (File E10848) 240V AC 480V AC 600V AC SMD6 – SND6 SHMD6 – SHND6 SCMD6 – SCND6 065 100 200 050 065 100 25 50 65 Note: “G” suffix in catalog number denotes circuit breaker for 3 phase, 3 wire circuits. For 3 phase, 4 wire, order correct 4th wire (neutral) transformer as separate and additional item. ■ Built to order. Allow 3-4 weeks for delivery. 6/42 Types SMD6, SHMD6, SND6, SHND6 are acceptable for reverse connection applications. Type SCMD6-H Catalog Number Cont Current Setting TA2K500 TA3K500 TA3K500 3TA4N8500 Shipping Weight (lbs) Trip Unit Adjustable Functions Suffix Letter Code 500–600 700–800 800 900–1200 (kit) Number per Carton 3-Pole, 600V AC Max Current Rating MD MD ND ND Breaker Type Red Label 3-Pole, 600V AC Max Current Rating Connector or Connector Kit Current Limiting Black Label 3-Pole, 600V AC Ampere Rating Shipping Weights Type SHMD6-H Blue Label Breaker Frame Ampere Rating Catalog Number 0600 0700 0800 1000 1200 N06SMDA N07SMDA N08SMDA N10SNDA N12SNDA 378.00 378.00 378.00 378.00 378.00 Enclosures Type Catalog Number 1 3R 12 MND61 MND63 MND612 802.00 1969.00 2578.00 Neutral W63623 428.00 Use lugs TA2N8750 or TA4P8500 only on 100% rated breakers. For additional information, see Note: A, page 6-70. Enclosures Section 5 Accessories pages 6/43 and 6/75 to 6/80 Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: MD/SMD 800A Frame ND/SND 1200A Frame PD/SPD 1600A Frame RD 2000A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip AC DC 120 208 240 277 480 600 — — — — — — Catalog Number S01MN6 569.00 S02MN6▲ 569.00 S03MN6 569.00 S15MN6▲ 569.00 S04MN6▲ 569.00 S06MN6▲ 569.00 Catalog Number S01MN64A 802.00 S02MN64A▲802.00 S03MN64A▲802.00 S15MN64A▲802.00 S04MN64A▲802.00 — - — — — — — 012 024 048 125 250 S16MN6▲ 569.00 S07MN6 569.00 S09MN6▲ 569.00 S11MN6 569.00 S13MN6▲ 569.00 S16MN64A▲802.00 S07MN64A 802.00 — S11MN64A▲802.00 S13MN64A▲802.00 Undervoltage Trip Combinations Control Voltage Accessory modules can mount in either left hand or right hand poles of all circuit breakers, including solid state. Exception: when mechanical interlock is used accessories cannot be mounted in left pole. Sensitrip Ammeter 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip Catalog Number 1 Undervoltage Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — U01MN6 569.00 U02MN6▲569.00 U03MN6▲569.00 U15MN6▲569.00 U04MN6▲569.00 U06MN6▲569.00 U01MN64A802.00 U02MN64A▲802.00 U03MN64A▲802.00 U15MN64A▲802.00 U04MN64A▲802.00 — U01MN64AA 1035.00 U02MN64AA▲1035.00 U03MN64AA▲1035.00 U15MN64AA▲1035.00 U04MN64AA▲1035.00 — — — — — 024 048 125 250 U07MN6 569.00 U09MN6▲569.00 U11MN6▲569.00 U13MN6▲569.00 U07MN64A802.00 U09MN64A▲802.00 U11MN64A▲802.00 U13MN64A▲802.00 U07MN64AA 1035.00 U09MN64AA▲1035.00 U11MN64AA▲1035.00 U13MN64AA▲1035.00 Auxiliary Switch Combinations Maximum Voltage 1 Form C* AC DC Catalog Number 2 Form C 480 250 A01MN64 242.00 A02MN64 — 12 A01MNDLV▲* 306.00 (Gold Plated Contacts) Catalog Number 483.00 Maximum Voltage AC DC Catalog Number 480 250 B00MN64 242.00 1 Alarm Switch and 1 Auxiliary Switch 1 Alarm Switch and 2 Auxiliary Switches Catalog Number Catalog Number A01MN64B 483.00 A02MN64B 483.00 Plug-in Ammeter Display Units Breaker Type SMD, SND, SPD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 1588.00 306.00 Ammeter Mounting Kit The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. ▲ Built to order. Allow 7-9 weeks for delivery. 6/43 CIRCUIT BREAKERS The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. 1 Alarm Switch 6 Alarm Switch Combinations Molded Case Circuit Breakers SELECTION ND 1200A Frame Sentron Series Type NXD6 Blue Label Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) 2-Pole 600V AC 250V DC Continuous Current Rating @ 40°C 3-Pole 600V AC 500V DC Catalog Number Catalog Number NXD62B900■9388.00 NXD62B100■9388.00 NXD62B120■9388.00 0900 1000 1200 NXD63B900 11775.00 NXD63B100 11775.00 NXD63B120 11775.00 Blue Label Type ND6 Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Frame Only Catalog Number Trip Unit Only Catalog Number Catalog Number 2-Pole 600V AC, 250V DC ND62B800■8574.00 ND62B900■10441.00 ND62B100■10441.00 ND62B12010441.00 0800 0900 1000 1200 ND62F1204851.00 MD62T800■2671.00 ND62T900■4538.00 ND62T100■4538.00 ND62T120 4538.00 ND63F1206086.00 MD63T8003351.00 ND63T9005689.00 ND63T1005689.00 ND63T1205689.00 3-Pole 600V AC, 500V DC 0800 0900 1000 1200 ND63B80010961.00 ND63B90013299.00 ND63B10013299.00 ND63B12013299.00 Interrupting Ratings Breaker Type 6 ND6, NXD6 HND6, HNXD6 CND6 RMS Symmetrical Amperes (KA) CSA / UL 489 A IR Volts AC Volts DC 240 480 600 250 500 65 100 200 50 65 100 25 50 65 30 (2-P) 30 (2-P) 30 (2-P) 25 (3-P) 50 (3-P) 50 (3-P) IEC 947-2 Volts AC (50/60HZ) 220/240 380/415 (lcu) (lcs) (lcu) (lcs) 65 33 40 20 100 50 65 33 200 100 100 50 500 (lcu) 30 42 65 CIRCUIT BREAKERS Nominal Instantaneous Values Low 2 3 4 4000 4570 5140 5710 5000 5715 6430 7145 5 6280 7860 6 6850 8575 7 7420 9290 Complete Breaker Unassembled with Lugs Prices of ND6 and HND6 breakers include frame, trip, and both line and load lugs (3TA4N8500). These catalog numbers are the frame, trip and lugs separately packaged. For applications requiring different lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of NXD6, HNXD6, and CND6 include frame with noninterchangeable trip units installed only. Order required terminal connectors separately. For line and load lugs (3TA4N8500) installed, add suffix “L” to catalog number (add 2 times list price of lug kit). 100% Rated Types NXD6, HNXD6 and CND6 breakers are available with 100% ratings. To order, suffix “H” to catalog number, and add 10% to list price. 100% rated ND breakers require 90°C Cu cable and lug kit 3TA4P8500. 50°C Applications see page 6-73. 400Hz Applications see page 6-73. Lugs (lcs) 15 21 33 Instantaneous Adjustment Trip Range Breaker Ampere Rating 800 900-1200 Ordering Information High 08000 10000 Catalog Cables Wire Number per Lug Range TA2K500 2 #1-500 kcmil Cu/Al TA3K500 3 #1-500 kcmil Cu/Al TC2K500 2 #1-500 kcmil Cu TC3K350 3 #1-350 kcmil Cu Kits (2 Kits required per breaker) 2TA4P8500 250-500 kcmil Cu/Al 3TA4P8500 4 2TA4N8500 4 250-500 kcmil Cu/Al 3TA4N8500 2TA2N8750 2 600-750 kcmil Cu/Al 3TA2N8750 2TA3N8750 3 500-750 kcmil Cu/Al 3TA3N8750 64.00 87.00 107.00 135. 762.00 744.00 Enclosures Type 1 3R 12 Neutral ■ Built to order. Allow 3-4 weeks for delivery. NXD6 circuit breakers are UL listed for reverse connection applications. 2-pole units available in 3-pole width only. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500VDC ungrounded UPS systems only. Use 6 connectors for 3-pole, use 4 connectors for 2-pole. Use 2 – 3TA4P8500 kits for 3-pole, or 2 – 2TA4P8500 kits for 2-pole. Rated for 90°C cable. Use for 100% 6/44 rated breakers. 2 – 3TA4N8500 for 3-pole or 2 – 2TA4N8500 for 2-pole. Rated for 75°C cable. See Note: A, page 6-70. 80% rated breakers with the CE mark will also be marked in the 100% rated version. HACR rated. Catalog Number MND61 MND63 MND612 ■ W63623 802.00 1969.00 2578.00 428.00 Use Note: ND frame qualified to UL489 supplement B “NAVAL”. See page 6-73 for additional information. Modifications page 6/73 Enclosures Section 5 Accessories pages 6/47 and 6/75 to 6/80 Molded Case Circuit Breakers SELECTION / DIMENSIONS ND 1200A Frame Sentron Series Type HNXD6 Black Label Non-Interchangeable Trip (Assembled Circuit Breaker Without Lugs) 2-Pole 600V AC 250V DC Continuous Current Rating @ 40°C 3-Pole 600V AC 500V DC Catalog Number 0900 1000 1200 For 2-pole application use outside poles of 3-pole circuit breaker HNXD63B900 HNXD63B100 HNXD63B120 13229.00 13229.00 13229.00 Black Label Type HND6 Interchangeable Trip Continuous Current Rating @ 40°C Complete Breaker Unassembled with Lugs Frame Only Catalog Number Trip Unit Only Catalog Number Catalog Number 2-Pole 600V AC, 250V DC 0800 0900 1000 1200 For 2-pole application use outside poles of 3-pole circuit breaker 3-Pole 600V AC, 500V DC 0800 0900 1000 1200 HND63B80012414.00 HND63B90014752.00 HND63B10014752.00 HND63B12014752.00 MD63T8003351.00 ND63T900 5689.00 ND63T100 5689.00 ND63T120 5689.00 HND63F1207539.00 Type CND6 Red Label Fuseless Current Limiting Non-Interchangeable Trip (Assembled Circuit Breaker) 2-Pole 0900 1000 1200 For 2-pole application, use outside poles of 3-pole circuit breaker CND63B900■ 18322.0 CND63B100 18322.0 CND63B12018322.00 Shipping Weights ■ Built to order. Allow 3-4 weeks for delivery. HNXD6 circuit breakers are CSA Certified / UL Listed for reverse connection applications. When lugs shield NDTS is used. Note: NDTS lug shields are required when oversized lugs (kits on page 88) are used. The kits include the NDTS shield. Breaker Type W L D D1 ND6, NXD6, HND6, HNXD6, CND6 9 16 6 8.25 with NDTS lug shield 9 29 6 8.25 2-pole units available in 3-pole width only. wired as shown on page 6-3, this circuit breaker is UL listed and rated for use on 500V DC ungrounded UPS systems only. HACR rated. When 6/45 CIRCUIT BREAKERS Dimensions (in inches) Number of Number per Shipping Poles Carton Weight (lbs.) ND6, HND6, NXD6, HNXD6, CND6 Assembled Breaker (less terminals) 2 1 53 3 1 61.5 ND6, HND6 Frame Only 2 1 42.25 3 1 46 ND6, HND6 Trip Unit Only 2 1 04.5 3 1 06.5 For inches / millimeters conversion, see Application Data section. Lugs 3-Pole Catalog Number 6 Continuous Current Rating @ 40°C Molded Case Circuit Breakers SELECTION SND 1200A Frame Digital Solid State Sentron Sensitrip III Series Current Limiting Type SND6 Type SHND6 Type SCND6 Black Label Red Label Blue Label 3-Pole, 600V AC 3-Pole, 600V AC 3-Pole, 600V AC Catalog Number Max Current Rating 13548.00 13548.00 13548.00 SHND69800A■ SHND69100A■ SHND69120A■ 800 1000 1200 800 1000 1200 14963.00 14963.00 14963.00 SHND69800AG■ SHND69100AG■ SHND69120AG■ 800 1000 1200 14104.00 14104.00 14104.00 SHND69800ANT■ SHND69100ANT■ SHND69120ANT■ 16757.00 Catalog Number Max Current Rating SHND69800A■ SHND69100A■ SHND69120A■ 800 1000 1200 SHND69800AG■ SHND69100AG■ SHND69120AG■ SHND69800ANT■ SHND69100ANT■ SHND69120ANT■ SHND69800ANGT■ 800 SHND69100ANGT■ 1000 SHND69120ANGT■ 1200 16757.00 16757.00 Catalog Number Max Current Rating 13548.00 13548.00 13548.00 SCND69800A■ SCND69100A■ SCND69120A■ 800 1000 1200 18650.00 18650.00 18650.00 800 1000 1200 14963.00 14963.00 14963.00 SCND69800AG■ SCND69100AG■ SCND69120AG■ 800 1000 1200 20540.00 20540.00 20540.00 800 1000 1200 14104.00 14104.00 14104.00 SCND69800ANT■ 800 SCND69100ANT■ 1000 SCND69120ANT■ 1200 19406.00 19406.00 19406.00 SHND69800ANGT■ 800 SHND69100ANGT■ 1000 SHND69120ANGT■ 1200 16757.00 16757.00 16757.00 SCND69800ANGT■ 800 SCND69100ANGT■ 1000 SCND69120ANGT■ 1200 23038.00 23038.00 23038.00 SND 1200A Frame – 100% Rated Current Limiting Type SND6-H Blue Label Black Label 3-Pole, 600V AC 6 Type SCND6-H Type SHND6H Red Label 3-Pole, 600V AC 3-Pole, 600V AC Catalog Number Max Current Rating 13374.00 13374.00 13374.00 SHND69800AH■ SHND69100AH■ SHND69120AH■ 800 1000 1200 800 1000 1200 14993.00 14993.00 14993.00 SHND69800AGH■ SHND69100AGH■ SHND69120AGH■ 800 1000 1200 13976.00 13976.00 13976.00 SHND69800ANTH■ SHND69100ANTH■ SHND69120ANTH■ SND69800ANGTH■ 800 SND69100ANGTH■ 1000 SND69120ANGTH■ 1200 16835.00 16835.00 16835.00 Catalog Number Max Current Rating SND69800AH■ SND69100AH■ SND69120AH■ 800 1000 1200 SND69800AGH■ SND69100AGH■ SND69120AGH■ SND69800ANTH■ SND69100ANTH■ SND69120ANTH■ H Catalog Number Max Current Rating 14896.00 14896.00 14896.00 SCND69800AH■ SCND69100AH■ SCND69120AH■ 800 1000 1200 20512.00 21538.00 21538.00 800 1000 1200 16470.00 16470.00 16470.00 SCND69800AGH■ SCND69100AGH■ SCND69120AGH■ 800 1000 1200 22613.00 23744.00 23744.00 800 1000 1200 15501.00 15501.00 15501.00 SCND69800ANTH■ SCND69100ANTH■ SCND69120ANTH■ 800 1000 1200 21343.00 22410.00 22410.00 SHND69800ANGTH■ 800 SHND69100ANGTH■ 1000 SHND69120ANGTH■ 1200 18439.00 18439.00 18439.00 SCND69800ANGTH■ 800 SCND69100ANGTH■ 1000 SCND69120ANGTH■ 1200 25337.00 26604.00 26604.00 SMD6, SHMD6, SCMD6, SND6, SHND6, SCND6 H CIRCUIT BREAKERS Trip Unit Adjustable Functions Suffix Letter Code Trip Type Cont Current Setting Long Time Delay Instantaneous Setting Short Time Pick Up Short Time Delay Short Time l 2t Pick Up Ground Fault Pick Up Ground Fault Delay — A LI — — — — AG LIG — — — ANT LSI — — ANGT LSIG When wire connector shield NDTS is used. Dimensions (in Inches) Breaker Type For inches / millimeters conversion, see Application Data section. For ordering information and terminal connectors, neutral transformers and enclosures, see page 6-42. 6/46 Note: “G” suffix in catalog number denotes circuit breaker for 3 phase, 3 wire circuits. For 3 phase, 4 wire, order correct 4th wire (neutral) transformer as separate and additional item. W H D D1 SMD6, SHMD6, SCMD6 SND6, SHND6, SCND6 9 16 6 8.25 With NDTS shields 9 24 6 8.25 ■ Built to order. Allow 3-4 weeks for delivery. Use 2-3TA4P8500 for 3-pole. These kits are rated for 90°C wire. 90°C Cu only cable must be used, and sized per 75°C conductors. Molded Case Circuit Breakers SELECTION / DIMENSIONS Internal Accessories Accessories for: MD/SMD 800A Frame ND/SND 1200A Frame PD/SPD 1600A Frame RD 2000A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip and 1 Auxiliary Switch 1 Shunt Trip AC DC 120 208 240 277 480 600 — — — — — — Catalog Number S01MN6 569.00 S02MN6▲ 569.00 S03MN6 569.00 S15MN6▲ 569.00 S04MN6▲ 569.00 S06MN6▲ 569.00 Catalog Number S01MN64A 802.00 S02MN64A▲802.00 S03MN64A▲802.00 S15MN64A▲802.00 S04MN64A▲802.00 —- — — — — — 012 024 048 125 250 S16MN6▲ 569.00 S07MN6 569.00 S09MN6▲ 569.00 S11MN6 569.00 S13MN6▲ 569.00 S16MN64A▲802.00 S07MN64A 802.00 — S11MN64A▲802.00 S13MN64A▲802.00 Undervoltage Trip Combinations Control Voltage Accessory modules can mount in either left hand or right hand poles of all circuit breakers, including solid state. Exception: when mechanical interlock is used accessories cannot be mounted in left pole. Sensitrip Ammeter 1 Undervoltage Trip and 1 Undervoltage Trip and 1 Auxiliary Switch A 2uxailiS rywtcihes 1 Undervoltage Trip AC DC Catalog Number 120 208 240 277 480 600 — — — — — — U01MN6 U02MN6▲ U03MN6▲ U15MN6▲ U04MN6▲ U06MN6▲ 569.00 569.00 569.00 569.00 569.00 569.00 Catalog Number U01MN64A802.00 U02MN64A▲802.00 U03MN64A▲802.00 U15MN64A▲802.00 U04MN64A▲802.00 — -- U01MN64AA U02MN64AA▲ U03MN64AA▲ U15MN64AA▲ U04MN64AA▲ — Catalog Number 1035 1035 1035 1035 1035 -- — — — — 024 048 125 250 U07MN6 U09MN6▲ U11MN6▲ U13MN6▲ 569.00 569.00 569.00 569.00 U07MN64A802.00 U09MN64A▲802.00 U11MN64A▲802.00 U13MN64A▲802.00 U07MN64AA U09MN64AA▲ U11MN64AA▲ U13MN64AA▲ 1035 10 1035 Auxiliary Switch Combinations Maximum Voltage 1 Form C* AC DC Catalog Number 2 Form C 480 250 A01MN64 242.00 A02MN64 — 12 A01MNDLV▲* 306.00 (Gold Plated Contacts) Catalog Number 483.00 Maximum Voltage AC DC Catalog Number 480 250 B00MN64 242.00 1 Alarm Switch and 1 Auxiliary Switch 1 Alarm Switch and 2 Auxiliary Switches Catalog Number Catalog Number A01MN64B 483.00 A02MN64B 483.00 Plug-in Ammeter Display Units Breaker Type SMD, SND, SPD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 1588.00 306.00 Ammeter Mounting Kit The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. ▲ Built to order. Allow 7-9 weeks for delivery. 6/47 CIRCUIT BREAKERS The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. 1 Alarm Switch 6 Alarm Switch Combinations Molded Case Circuit Breakers SELECTION PD 1600A Frame Sentron Series Type PXD6 Non-Interchangeable Trip Continuous Current Rating 40˚C 1200 1400 1600 Complete Breaker Assembled (Frame/Trip Unit Only) Mounting Assembly Catalog Number PXD63B120■ 15086.00 PXD63B140■ 15086.00 PXD63B160 15086.00 Lugs (6 required) Catalog Number MB9301 -orMBR9302 Catalog Number TA5P600 Type PD6 Interchangeable Trip Blue Label 3-Pole 600V AC, 250-500V DC Continuous Current 40°C Complete Breaker Unassembled Catalog Number Frame Only Mounting Assembly Trip Unit Only Catalog Number Catalog Number PD63B120■ 17900.00 PD63B14017900.00 PD63F160 7754.00 PD63B16017900.00 1200 1400 1600 Catalog Rating Number PD63T120■0 MB9301 -orPD63T140 7332.00 PD63T160 7332.00 MBR9302 TA5P600 86.00 Blue Label 3-Pole 600V AC, 250-500V DC Complete BreakerAssembled (Frame/Trip Unit Only) Catalog Number HPXD63B120■ 17017.00 HPXD63B140■ 7017.00 HPXD63B160 17017.00 1200 1400 1600 Type HPD6 Interchangeable Trip Black Label 3-Pole 600V AC, 250-500V DC Continuous Current 40°C 1200 HPD63B140 1600 Catalog Number Frame Only Trip Unit Only Catalog Number HPD63B120■ 19829.00 19829.00 HPD63F160 PD63T140 HPD63B160 19829.00 Catalog Number Catalog Rating Number 1400 Complete Breaker Unassembled with Lugs Prices of PD6, HPD6, RD6, and HRD6 type breakers include frame, trip, mounting base (MB9301), and both line and load lugs (PD Frame – TA5P600, RD Frame – TC5R600). When ordered by these catalog numbers, the customer will receive the frame, trip, mounting assembly and lugs separately packaged. For applications requiring different mounting base or lugs, order individual items as needed. Complete Breaker Assembled without Lugs Prices of PXD6, HPXD6, RXD6, HRXD6 and CPD6 type breakers include frame with non-interchangeable trip unit installed only. Order required mounting base and lugs separately. 100% Rated Types PXD6, HPXD6 breakers are available with 100% ratings. To order add suffix “H” to catalog number, and 10% to list price. RD 2000A Frames not available with 100% ratings. 50°C Applications see page 6-73. 400HZ Applications see page 6-73. Lugs Catalog Number TA5P600 TC5R600 TC4P750▲ TA6R600 Fuseless Current Limiting 3-Pole 600V AC, 250-500V DC Red Label No of Cables per Connector 1-5 Pcs. 1-5 Pcs. 1-4 Pcs. 1-6 Pcs. Wire Range 300-600 kcmil Cu/Al 300-600 kcmil Cu only 500-750 kcmil Cu/Al 300-600 kcmil Cu/Al 286.00 381.00 260.00 302.00 Complete BreakerAssembled (Frame/Trip Unit Only) Catalog Number CPD63B120■ 19056.00 CPD63B140■ 19056.00 CPD63B160■ 19056.00 Mounting Bases for PD & RD 6.19 6.00 2.00 2.00 MB9301 ■ Built to order. Allow 3-4 weeks for delivery. ▲ Built to order. Allow 7-9 weeks for delivery. Use two outside poles of a 3-pole circuit breaker for 250V 6/48 MB9301 16.00 MB9301 When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. PXD6, HPXD6 type circuit breakers are UL Listed for reverse feed applications. 18.73 16.00 CIRCUIT BREAKERS 1200 1400 1600 Lugs (6 required) Catalog Number PD63T120■ 7332.00 MB9301 -orTA5P600 286.00 PD63T160 7332.00 MBR9302 Type CPD6 Non-Interchangeable Trip Continuous Current Rating 40°C Mounting Assembly 25.50 6 Complete Breaker Unassembled Lugs (6 required) Catalog Number Type HPXD6 Non-Interchangeable Trip Continuous Current Rating 40°C Ordering Instructions Blue Label 3-Pole 600V AC, 250-500V DC MBR9302 For MBR9302 additional information See Note: A, page 6-70. HACR rated. Note: PD frame qualified to UL489 supplement B “NAVAL”. See page 6-73 for additional information. Molded Case Circuit Breakers SELECTION / DIMENSIONS SPD 1600A Frame Digital Solid State Sentron Sensitrip III Series Ordering Information Pricing information for all Digital Sentron Series PD frame unit is for breaker only. Price required mounting block assembly and necessary terminal connectors as separate items. SPD6 and SHPD6 are acceptable for reverse connection applications. Type SPD6 Type SHPD6 Blue Label Black Label 3-Pole, 600V AC 3-Pole, 600V AC SPD69140■ SPD69160■ 1400 1600 SPD69140G■ SPD69160G■ Catalog Number Max Current Rating 18390.00 18390.00 SHPD69140■ SHPD69160■ 1400 1600 18968.00 18968.00 1400 1600 19977.00 19977.00 SHPD69140G■ SHPD69160G■ 1400 1600 20752.00 20752.00 SPD69140NT■ SPD69160NT■ 1400 1600 18693.00 18693.00 SHPD69140NT■ SHPD69160NT■ 1400 1600 19649.00 19649.00 SPD69140NGT■ SPD69160NGT■ 1400 1600 22156.00 22156.00 SHPD69140NGT■ SHPD69160NGT■ 1400 1600 22991.00 22991.00 Suffix Letter Code Trip Type None LI Cont Current Setting Long Time Delay Instantaneous Setting Short Time Pick Up — Short Time Delay — Lugs No. of Catalog Cables per Wire Number Connector Range TA5P600 1–5 pcs. TC5R600 1–5 pcs. TA6R600 1–5 pcs. 300–600 kcmil Cu/Al 286.00 300–600 kcmil Cu Only 381.00 300–600 kcmil Cu/Al 302.00 Neutral Transformers Short Time l 2t Pick Up Ground Fault Pick Up — — Ground Fault Delay — G LIG — — — NT LSI — — NGT LSIG Interrupting Ratings Ampere Rating Catalog Number 1400 1600 N14SPD N16SPD 378.00 378.00 Enclosure Type Catalog Number 1 PRD6N1 5655.00 Mounting Block (Required) RMS Symmetrical kA CSA / UL 489 Breaker Type 240V AC 480V AC 600V AC Catalog Number SPD6 SHPD6 065 100 050 065 025 050 MB9301 MBR9302 1098.00 1098.00 6 Catalog Number Max Current Rating All PD, RD Frames: 6.19 6.00 CIRCUIT BREAKERS 2.00 MB9301 (shown) MBR9302 For inches / millimeters conversion, see Application Data section. ■ Built to order. Allow 3-4 weeks for delivery. MBR9301 For MB9301 additional information, see Note: A, page 6-70. Note: The PD frame circuit breaker requires the use of a connect-all mounting assembly to allow for placing into service. Note: “G” suffix in catalog number denotes circuit breaker 18.73 16.00 25.50 16.00 2.00 MBR9302 MBR9302 for 3 phase, 3 wire circuits. For 3 phase, 4 wire, order correct 4th wire (neutral) transformer as separate and additional item. 6/49 Molded Case Circuit Breakers SELECTION / DIMENSIONS Internal Accessories Accessories for: MD/SMD 800A Frame ND/SND 1200A Frame PD/SPD 1600A Frame RD 2000A Frame Shunt Trip Combinations 1 Shunt Trip and 1 Auxiliary Switch Control Voltage 1 Shunt Trip AC DC Catalog Number 120 208 240 277 480 600 — — — — — — S01MN6 S02MN6▲ S03MN6 S15MN6▲ S04MN6▲ S06MN6▲ 569.00 569.00 569.00 569.00 569.00 569.00 S01MN64A S02MN64A▲ S03MN64A▲ S15MN64A▲ S04MN64A▲ — 802.00 802.00 802.00 802.00 802.00 —-- — — — — — 012 024 048 125 250 S16MN6▲ S07MN6 S09MN6▲ S11MN6 S13MN6▲ 569.00 569.00 569.00 569.00 569.00 S16MN64A▲ S07MN64A — S11MN64A▲ S13MN64A▲ 802.00 802.00 —802.00 802.00 Catalog Number Undervoltage Trip Combinations Control Voltage Accessory modules can mount in either left hand or right hand poles of all circuit breakers, including solid state. Exception: when mechanical interlock is used accessories cannot be mounted in left pole. Sensitrip Ammeter 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip Catalog Number 1 Undervoltage Trip and 2 Auxiliary Switches AC DC Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — U01MN6 569.00 U02MN6▲569.00 U03MN6▲569.00 U15MN6▲569.00 U04MN6▲569.00 U06MN6▲569 U01MN64A802.00 U02MN64A▲802.00 U03MN64A▲802.00 U15MN64A▲802.00 U04MN64A▲802.00 .00 — -- U01MN64AA1035.00 U02MN64AA▲1035.00 U03MN64AA▲1035.00 U15MN64AA▲1035.00 U04MN64AA▲1035.00 — -- — — — — 024 048 125 250 U07MN6 569.00 U09MN6▲569.00 U11MN6▲569.00 U13MN6▲569.00 U07MN64A802.00 U09MN64A▲802.00 U11MN64A▲802.00 U13MN64A▲802.00 U07MN64AA1035.00 U09MN64AA▲1035.00 U11MN64AA▲1035.00 U13MN64AA▲1035.00 Auxiliary Switch Combinations Maximum Voltage 1 Form C* AC DC Catalog Number 2 Form C 480 250 A01MN64 242.00 A02MN64 — 12 A01MNDLV▲* 306.00 (Gold Plated Contacts) Catalog Number 483.00 Alarm Switch Combinations 6 Maximum Voltage CIRCUIT BREAKERS The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. Ammeter Mounting Kit The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. ▲ Built to order. Allow 7-9 weeks for delivery. 6/50 1 Alarm Switch AC DC Catalog Number 480 250 B00MN64 1 Alarm Switch and 1 Auxiliary Switch 242.00 1 Alarm Switch and 2 Auxiliary Switches Catalog Number Catalog Number A01MN64B A02MN64B Plug-in Ammeter Display Units Breaker Type SMD, SND, SPD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 1588.00 306.00 Molded Case Circuit Breakers SELECTION RD 2000A Frame Sentron Series Blue Label Type RXD6 Non-Interchangeable Trip (Assembled Circuit Breaker Only Without Lugs) 3-Pole 600V AC, 250-500V DC Continuous Current Rating 40°C Complete Breaker Assembled (Frame/Trip Unit Only) Mounting Assembly Lugs (6 required) Catalog Number Catalog Number Catalog Number 1600 1800 2000 RXD63B160 RXD63B180 RXD63B200 16723.00 16723.00 16723.00 MB9301 -orMBR9302 1098.00 TC5R600 381.00 1098.00 Blue Label Type RD6 Interchangeable Trip (Unassembled Circuit Breaker with Lugs) 3-Pole 600V AC, 250-500V DC Frame Only Catalog Number Catalog Number Mounting Block Mounting Assembly Trip Unit Only Catalog Number Lugs (6 required) Catalog Number Catalog Number RD63B160■ 20108.00 RD63T160■ 7983.00 MB9301 1098.00 RD63B180 20108.00 RD63F200 8741.00 RD63T180 7983.00 -orRD63B200 20108.00 RD63T200 7983.00 MBR9302 1098.00 1600 1800 2000 Black Label Type HRXD6 Complete Breaker Assembled (Frame/Trip Unit Only) Continuous Current Rating 40°C Catalog Number 1600 1800 2000 HRXD63B160■ HRXD63B180■ HRXD63B200 18802.00 18802.00 18802.00 Black Label Type HRD6 Continuous Current Rating 40°C Complete Breaker Unassembled with Lugs 1600 1800 2000 TC5R600 381.00 Frame Only Catalog Number Mounting Assembly Trip Unit Only Catalog Number Catalog Number Lugs (6 required) Catalog Number Catalog Number Connection Points MB9301 MBR9302 Front Rear Shipping Weights Number of Number per Shipping Poles Carton Weight (lbs.) PXD6, HPXD6, RXD6, HRXD6, CPD6 Assembled Breakers 3 1 61.5 PD6, HPD6, RD6, HRD6 Frame Only 3 1 55.0 PD6, RD6 Trip Unit Only 3 1 06.5 Mounting Assembly MB9301 1 53.0 MBR9302 1 50.9 6 Continuous Current Rating 40°C Complete Breaker Unassembled with Lugs Catalog Number HRD63B160■ 22186.00 RD63T160■ 7983.00 MB9301 1098.00 HRD63B180 22186.00 HRD63F200 10819.00 RD63T180 7983.00 -orTC5R600 HRD63B200 22186.00 RD63T200 7983.00 MBR9302 1098.00 CSA / UL 489 A IR IEC 947-2 RMS Symmetrical KA Breaker Type PD6, PXD6, RD6, RXD6 CIRCUIT BREAKERS Interrupting Ratings Volts AC Volts AC (50/60HZ) Volts DC 220/240 (lcu) (lcs) (lcu) (lcs) (lcu) (lcs) 240 480 600 250 500 380/415 500 65 50 25 30 (2P) 25 (3P) 65 33 40 10 30 8 HPD6, HPXD6 HRD6, HRXD6 100 65 50 30 (2P) 50 (3P) 100 50 65 17 42 11 CPD6 200 100 65 30 (2P) 50 (3P) 200 100 100 25 65 17 Instantaneous Adjustment Trip Range (PD / RD Frames) Breaker Ampere Rating 1200-2000 Nominal Instantaneous Values +25% Tolerance Low 2 3 4 5000 5715 6430 7145 ■ Built to order. Allow 3-4 weeks for delivery. Use two outside poles of a 3-pole circuit breaker for 250V DC applications. When wired as shown on page 6-3, this circuit breaker is CSA Certified / UL listed and rated for use on 500V DC ungrounded UPS systems only. 5 7860 6 8575 7 9790 +20% Tolerance High 10,000 RXD6 and HRXD6 type circuit breakers are CSA Certified / UL Listed for reverse feed applications. rated. Note: RD frame qualified to UL489 supplement B “NAVAL”. See page 6-73 for additional information. HACR 6/51 Molded Case Circuit Breakers SELECTION / DIMENSIONS Internal Accessories Accessories for: MD/SMD 800A Frame ND/SND 1200A Frame PD/SPD 1600A Frame RD 2000A Frame Shunt Trip Combinations Control Voltage 1 Shunt Trip 1 Shunt Trip and 1 Auxiliary Switch AC DC Catalog Number Catalog Number 120 208 240 277 480 600 — — — — — — S01MN6 S02MN6▲ S03MN6 S15MN6▲ S04MN6▲ S06MN6▲ S01MN64A S02MN64A▲ S03MN64A▲ S15MN64A▲ S04MN64A▲ — 802.00 802.00 802.00 802.00 802.00 — — — — — 012 024 048 125 250 S16MN6▲ S07MN6 S09MN6▲ S11MN6 S13MN6▲ S16MN64A▲ S07MN64A —S11MN64A▲ S13MN64A▲ 802.00 802.00 802.00 802.00 Undervoltage Trip Combinations Control Voltage Accessory modules can mount in either left hand or right hand poles of all circuit breakers, including solid state. Exception: when mechanical interlock is used accessories cannot be mounted in left pole. Sensitrip Ammeter 1 Undervoltage Trip and 1 Auxiliary Switch 1 Undervoltage Trip Catalog Number 1 Undervoltage Trip and 2 Auxiliary Switches AC DC 120 208 240 277 480 600 — — — — — — U01MN6 569.00 U02MN6▲569.00 U03MN6▲569.00 U15MN6▲569.00 U04MN6▲569.00 U06MN6▲569.00 Catalog Number U01MN64A 802.00 U02MN64A▲ 802.00 U03MN64A▲ 802.00 U15MN64A▲ 802.00 U04MN64A▲ 802.00 — - Catalog Number U01MN64AA1035.00 U02MN64AA▲1035.00 U03MN64AA▲1035.00 U15MN64AA▲1035.00 U04MN64AA▲1035.00 — -- — — — — 024 048 125 250 U07MN6 569.00 U09MN6▲569.00 U11MN6▲569.00 U13MN6▲569.00 U07MN64A 802.00 U09MN64A▲ 802.00 U11MN64A▲ 802.00 U13MN64A▲ 802.00 U07MN64AA1035.00 U09MN64AA▲1035.00 U11MN64AA▲1035.00 U13MN64AA▲1035.00 Auxiliary Switch Combinations Maximum Voltage 1 Form C* 2 Form C AC DC Catalog Number Catalog Number 480 250 A01MN64 242.00 A02MN64 — 12 A01MNDLV▲* 306.00 (Gold Plated Contacts) 483.00 Alarm Switch Combinations 6 Maximum Voltage CIRCUIT BREAKERS The Ammeter Display Units plug into the Sensitrip Trip Unit and displays the phrase current flowing in the SADU breaker. They are powered by the breaker’s CT’s with replaceable battery back-up for maintaining trip and max logs. The SADU reads currents, current imbalance, current demand, and trip status. Ammeter Mounting Kit The Ammeter may also be panel or door mounted using the SADURMK18 remote mounting kit. ▲ Built to order. Allow 7-9 weeks for delivery. 6/52 1 Alarm Switch AC DC Catalog Number 480 250 B00MN64 1 Alarm Switch and 1 Auxiliary Switch 1 Alarm Switch and 2 Auxiliary Switches Catalog Number 242.00 A01MN64B Catalog Number 483.00 A02MN64B Plug-in Ammeter Display Units Breaker Type SMD, SND, SPD Desc. Catalog Number Display Unit SADU Remote Mounting Kit SADURMK18 1588.00 306.00 Molded Case Circuit Breakers SELECTION STD 3200A Frame Digital Solid State Sentron Sensitrip III Series Type STD6 Type SHTD6 Blue Label Black Label STD63F2000■ STD63F2500■ STD63F3200■ Max Current Rating 2000 2500 3200 Red Label 3-Pole, 600V AC, 80% Rated 3-Pole, 600V AC, 80% Rated Catalog Number Type SHHTD6 Catalog Number 22 SHTD63F2000■ SHTD63F2500■ SHTD63F3200■ 3-Pole, 600V AC, 100% Rated Max Current Rating Max Current Rating STD63F2000H■ STD63F2500H■ STD63F3200H■ Catalog Number SHTD63F2000H■ SHTD63F2500H■ SHTD63F3200H■ 2000 2500 3200 2000 2500 3200 Max Current Rating Catalog Number SHHTD63F2000■ SHHTD63F2500■ SHHTD63F3200■ 2000 2500 3200 3-Pole, 600V AC, 100% Rated Catalog Number 3-Pole, 600V AC, 80% Rated Max Current Rating Ordering Information STD Breakers are ordered by component - Frame, Trip Unit Rating Plug & Accessories. Contact Sales Office for instructions. 2000 2500 3200 3-Pole, 600V AC, 100% Rated Max Current Rating Catalog Number 266 SHHTD63F2000H■ SHHTD63F2500H■ SHHTD63F3200H■ H H1 2000 2500 3200 Trip Unit Fits Breaker Frame with Continuous Rating 2000 Amp 2500 Amp 3200 Amp W D Function Catalog Numbers MLI STD20TMLI STD25TMLI STD32TMLI 921.00 LS STD20TLS STD25TLS STD32TLS 2021.00 LI STD20TLI STD25TLI STD32TLI 1440.00 Breaker Type H H1 W D LSI STD20TLSI STD25TLSI STD32TLSI 2627.00 LSG STD20TLSG STD25TLSG STD32TLSG 3809.00 STD SHTD SHHTD 27.5 20.5 15.5 12.5 LIG STD20TLIG STD25TLIG STD32TLIG 2535.00 LSIG STD20TLSIG STD25TLSIG STD32TLSIG 4454.00 Terminal Connectors Catalog Number Rating Plug STD32TCON Fits Breaker Frame with Continuous Rating 2000 Amp 2500 Amp 3200 Amp 200.00 Cable Lugs Catalog Numbers (2000A Only) 1000 20STD1000 — — 1200 20STD1200 — — 1600 20STD1600 25STD1600 32STD1600 2000 20STD2000 25STD2000 32STD2000 2500 — 25STD2500 32STD2500 3000 — — 32STD3000 3200 — — 32STD3200 Catalog Number TA6R600STD No of Cables per Con- Wire nector Range (1–6 pcs.) 250-600 kcmil Cu/Al 6 Long Time Amperes Dimensions (in Inches) 289.00 T. Connector Catalog Number Interrupting Ratings Breaker Type STD6 SHTD6 SHHTD6 RMS Symmetrical kA UL 489 (File E 10848) 240V AC 085 150 200 CIRCUIT BREAKERS (For Bus Connector) 480V AC 065 100 150 600V AC 050 085 100 IEC 947-2 (Icu=Ics, Icw=50kA) 415VAC — 100kA — STD32TCON 200.00 690VAC — 65kA — Neutral Transformers Ampere Rating Catalog Number 2000 2500 3200 N20STD N25STD N32STD 411.00 411.00 411.00 Accessories pages 6/54 and 6/75 to 6/80 ■ Built to order. Allow 3-4 weeks for delivery. Dimensions for reference, not for construction. Dimensions for reference, not for construction. Dimensions for reference, not for construction. 6/53 Molded Case Circuit Breakers SELECTION Internal Accessories Accessories for: Shunt Trip / Undervoltage Release STD 3200A Frame STD Breakers are built to order. It is recommended that accessories be ordered installed in the breaker. They may also be field added. Control Voltage Shunt Trip Under Voltage Release AC DC Catalog Number Catalog Number 120 240 480 600 — — — — STDST120▲ STDST240▲ STDST480▲ STDST600▲ STDUV120▲ STDUV240▲ STDUV480▲ STDUV600▲ 694.00 694.00 694.00 694.00 Ammeter Dispay Module — — — — 012 024 048 125 STDST12▲ STDST24▲ STDST48▲ STDST125▲ STDUV12▲ STDUV24▲ STDUV48▲ STDUV125▲ 694.00 694.00 694.00 694.00 The STDDM plugs into the trip unit of the STD 3200 Amp breaker. It provides readout of currents as well as load current alarm (in conjunction with the display module relay). Auxiliary Switches Control Voltage AC Ground Fault Monitor The Ground Fault Monitor for the STD 3200 Amp breaker family plugs into the Trip Unit and reads the ground current. This is either the residual current calculated from the measured three phases and neutral (if present) or the directly measured ground return current in the ground lead of the supply transformer, depending on the configuration of the the trip unit. In addition to displaying the ground current, the display module provides an alarm on ground overcurrent, settable at three pickup levels with three delays (in conjunction with the display module relay). Quantity Contacts DC 600 300 NO NC Catalog Number 1 2 3 4 5 6 1 2 3 4 5 6 STDAS2▲ STDAS4▲ STDAS6▲ STDAS8▲ STDAS10▲ STDAS12▲ Auxiliary Power Module Alarm Switch Control Voltage 355.00 584.00 876.00 1170.00 1468.00 1739.00 AC DC Catalog Number 600 300 STDAS▲ Power Source Catalog Number 120V AC STDAPM▲ 642.00 686.00 Electronic Bell Alarm / Display Relay Control Voltage Bell Alarm Display Module Relay AC DC Catalog Number Catalog Number 120 — — — — 24 48 60 STDBA120▲ STDBA24▲ STDBA48▲ STDBA125▲ STDDMR120▲ STDDMR24▲ STDDMR48▲ STDDMR125▲ Ammeter-Display Module 694.00 694.00 694.00 694.00 Ground Fault Monitor Catalog Number Catalog Number 6 STDDM▲ STDGFM▲ 2860.00 3669.00 Display Module Relay Remote Indicator Panels Provides switch contact output for overload or ground fault alarm. Provides remote cause of trip indication. CIRCUIT BREAKERS Voltage Cat No 120V AC 24V DC 48V DC 125V DC STDDMR120▲ STDDMR24▲ STDDMR48▲ STDDMR125▲ Catalog Number STDRIP120▲ 1372.00 Mounting Bracket for Terminal Block For mounting Control Terminal Blocks to breakers. One per each side as required. Catalog Number STDTBM▲ Secondary Terminal Blocks 87.00 The appropriate number and location of terminal blocks should be selected from the table below based on the features and accessories ordered on each circuit breaker. Control Terminal Blocks also require separate mounting brackets for the left and right sides. Accessory Contact Block Position Catalog Number Shunt Trip Undervoltage Release Neutral Sensor Remote Indication Panel Zone Interlock and ACCESS Auxiliary Switches Bell Alarm or Display Module Relay LEFT TOP STDTBLT▲ 145.00 ✔ ✔ ✔ — — LEFT BOTTOM STDTBLB▲ 145.00 — — — — — — — — — ✔ ✔ — — — — — — RIGHT TOP STDTBRT▲ 145.00 RIGHT BOTTOM STDTBRB▲ 145.00 ▲ Built to order. Allow 7-9 weeks for delivery. The STD trip unit has built in trip status indication. Use the STDRIP120 when display of the cause of trip 6/54 is required at location remote from the trip unit in addition to the intrinsic trip unit capability. 1A and 1B 2A and 2B 3A and 3B 4A and 4B 5A and 5B 6A and 6B — — ✔ — — — — ✔ ✔ ✔ Molded Case Circuit Breakers SELECTION Magnetic Trip Only — ETI Motor Circuit Instantaneous Trip Range ED6-A 600V AC 250V DC CED6-A 600V AC 250V DC FXD6 600V AC 250V DC CFD6 600V AC 250V DC JXD6(A) 600V AC 250V DC CJD6 600V AC 250V DC LXD6(A) 600V AC 250V DC CLD6 600V AC 250V DC LMXD6 600V AC 250V DC MXD6 600V AC 250V DC CMD6 600V AC 250V DC 001 002 003 005 010 025 030 040 050 100 125 SHIPPING: 001 002 003 005 010 025 030 040 050 100 125 SHIPPING: 150 150 150 250 SHIPPING: 150 150 150 250 SHIPPING: 400 400 SHIPPING: 400 400 SHIPPING: 600 600 SHIPPING: 600 600 SHIPPING: 800 800 SHIPPING: 800 800 800 SHIPPING: 800 800 800 002.6 007 010 016 030 055 080 115 180 315 500 Maximum 00009 00022 00035 00054 00100 00180 00270 00375 00600 01000 01250 Catalog Number 2-Pole — — — — — — — — — — — 002.6 007 010 016 030 055 080 115 180 315 500 00009 00022 00035 00054 00100 00180 00270 00375 00600 01000 01250 — — — — — — — — — — — 0400 0800 1100 1100 00800 01500 02500 02500 0400 0800 1100 1100 00800 01500 02500 02500 1250 2000 02500 04000 1250 2000 02500 04000 2000 3000 04000 06000 2000 3000 04000 06000 — — — — 0 — — — — 12 lbs. each — JXD62H400■ 16 lbs. each CJD62L400■ CJD62H400■ 29.5 lbs. each LXD62L600■ — 16 lbs. each CLD62L600■ CLD62H600■ 2800 3200 06000 08000 — — 3000 4000 5000 06000 08000 10000 — — — 3000 4000 5000 06000 08000 10000 — — — Minimum Catalog Number 3-Pole ED63A001 ED63A002 ED63A003 ED63A005 ED63A010 ED63A025 ED63A030 ED63A040 ED63A050 ED63A100 ED63A125 737.00 737.00 737.00 737.00 737.00 737.00 737.00 737.00 886.00 941.00 1786.0 3.8 lbs. each CED63A001■ CED63A002■ CED63A003■ CED63A005■ CED63A010■2514.00 CED63A025■2514.00 CED63A030■2514.00 CED63A040■2514.00 CED63A050■3005.00 CED63A100■3226.00 CED63A125■ 6 lbs. each FXD63L150■3084.00 FXD63A1503084.00 FXD63H1503084.00 FXD63A2503084.00 9 lbs. each CFD63L150■5960.00 CFD63A150■5960.00 CFD63H150■5960.00 CFD63A250■5960.00 12 lbs. each JXD63L4003226.00 JXD63H4003226.00 20 lbs. each CJD63L400■6923.00 CJD63H400■6923.00 31.5 lbs. each LXD63L600■ LXD63H600 20 lbs. each CLD63L600■ CLD63H600■ 31.5 lbs. each LMXD63L800■ LMXD63A800 35 lbs. each MXD63L800■ MXD63A800■ MXD63H800 6671.0 33 lbs. each CMD63L800■126.00 CMD63A800■25. CMD63H800■ 80 lbs. each SHIPPING: 2514.0 2514.0 2514.0 2514.0 4837.00 6 Ampere Rating 4710 40.00 1108200 11082.0 6671 6671 6671 6671 12536.0 Important Information ETI interrupting ratings are determined through combination tests with properly sized overload relays and contactors. Connectors included when ordering by circuit breaker catalog number for ED6 and CED6 ETI’s. Order ETI circuit breaker and lugs (2 per pole) separately for the FXD6, CFD6, MXD6, CMD6, JXD6, CJD6, LXD6 and CLD6 ETI’s. Lug Information pages 6/70 to 6/72 Accessories pages 6/75 to 6/80 Application data pages 6/56 to 6/57 ■ Built to order. Allow 2–3 weeks for delivery. 2-pole available in 3-pole width only. When applied on DC Circuits — Trip levels will increase approximately +15 to 20%. Tolerance -20/+30% For 2-pole application use outside poles of 3-pole circuit breaker. 6/55 CIRCUIT BREAKERS Breaker Type Complete Circuit Breaker Without Lugs Molded Case Circuit Breakers APPLICATION Motor Circuits General Protection of Motor Circuits Molded case circuit breakers are used in motor circuits as a disconnecting means and for short-circuit protection. They should be used in conjunction with motorrunning, over-current-protection devices, and should permit the motor to start without nuisance tripping from motorinrush current. The circuit breaker should have a continuous-current rating of not less than 115% of the motor full-load current. The recommended motor circuit protectors (Siemens ETI instantaneous only circuit breakers) listed have continuous-current ratings of at least 115% of motor full-load currents. The trip-setting positions are approximately 11 times motor full-load currents. The suggested trip settings may have to be adjusted upward to no higher than 1300% of full-load current for non-design E type motors, and no greater than 1700% of full load current for design B & E energy efficient motors, to allow for motor startup due to inrush currents. Breaker Mounted Immediately Ahead of Motor Starter Siemens ETI motor circuit protectors are recommended for use in combination motor starters to provide selective short- circuit protection for the motor branch circuit. The adjustable instantaneous-trip feature of the Siemens ETI motor circuit protector provides for a trip setting slightly above the peak motor-inrush current. With this setting, no delay is introduced in opening the circuit when a fault occurs. This circuit breaker has no time-delay trip element. Therefore it must be used in conjunction with, and immediately ahead of, the motor-running overcurrent protective device. Important: The information below does not apply to all motor applications: it is recommended that the user refer to the National Electrical Code (NEC) for specific needs. Table 1 (When Breaker is Mounted Immediately Ahead of Motor Starter) 3 Phase Induction Type Motors (Siemens ETI motor circuit protectors for branch circuit use with alternating-current combination, full voltage motor starters). 6 CIRCUIT BREAKERS Motor Full Load Amperes .20 – .33 .34 – .45 .46 – .56 .57 – .68 .69 – .81 .53 – .83 .84 – 1.14 1.15 – 1.45 1.46 – 1.68 1.69 – 2.00 .76 – 1.29 1.30 – 1.75 1.76 – 2.29 2.30 – 2.68 2.69 – 3.18 1.23 – 1.99 2.00 – 2.75 2.76 – 3.52 3.53 – 4.14 4.15 – 4.90 2.30 – 3.83 3.84 – 5.37 5.38 – 6.52 6.53 – 7.68 7.69 – 9.10 4.23 – 6.91 6.92 – 9.61 9.62 – 11.91 11.92 – 13.83 13.84 – 16.40 6.15 – 10.37 10.38 – 14.22 14.23 – 18.06 18.07 – 20.75 20.76 – 24.50 8.84 – 14.22 14.23 – 19.60 19.61 – 24.99 25.00 – 28.83 28.84 – 34.00 13.84 – 23.06 23.07 – 31.52 31.53 – 39.99 40.00 – 46.14 46.15 – 54.50 24.23 – 41.52 41.53 – 56.91 56.92 – 68.45 68.46 – 76.91 76.92 – 90.90 6/56 Catalog ED63A001 CED63A001 ED63A002 CED63A002 ED63A003 CED63A003 ED63A005 CED63A005 ED63A010 CED63A010 ED63A025 CED63A025 ED63A030 CED63A030 ED63A040 CED63A040 ED63A050 CED63A050 ED63A100 CED63A100 ETI Trip Setting AdjustNumber mentAmperes Low 2.6 2 4.5 3 6 4 7.5 High 9 Low 7 2 11 3 15 4 19 High 22 Low 10 2 17 3 23 4 30 High 35 Low 16 2 26 3 36 4 46 High 54 Low 30 2 50 3 70 4 85 High 100 Low 55 2 90 3 125 4 155 High 180 Low 80 2 135 3 185 4 235 High 270 Low 115 2 185 3 255 4 325 High 375 Low 180 2 300 3 410 4 520 High 600 Low 315 2 540 3 740 4 890 High 1000 Motor Full Catalog Load Amperes Number 38.46 – 55.37 55.38 – 70.75 70.76 – 84.60 ED63A125 84.61 – 96.14 CED63A125 96.15 – 113.60 30.76 – 35.37 35.38 – 39.99 44.51 – 49.23 FXD63L150 53.84 – 58.45 CFD63L150 58.46 – 63.06 63.07 – 74.50 61.53 – 69.22 69.23 – 76.91 84.61 – 92.29 FXD63A150 100.00 – 108.00 CFD63A150 108.00 – 115.00 115.00 – 136.00 85.00 – 100.00 100.00 – 115.00 131.00 – 146.00 FXD63A250 162.00 – 177.00 CFD63A250 177.00 – 192.00 192.00 – 227.00 95.00 – 110.00 110.00 – 124.00 138.00 – 151.00 JXD63L400 165.00 – 178.00 CJD63L400 178.00 – 192.00 192.00 – 227.00 154.00 – 176.00 176.00 – 198.00 220.00 – 242.00 JXD63H400 264.00 – 285.00 CJD63H400 285.00 – 308.00 308.00 – 326.00 155.00 – 176.00 176.00 – 198.00 220.00 – 242.00 LXD63L600 264.00 – 285.00 CLD63L600 285.00 – 308.00 308.00 – 326.00 ETI Trip Setting Adjustment Amperes Low 500 2 720 3 920 4 1100 High 1250 Low 400 2 460 4 580 6 700 7 760 High 820 Low 800 2 900 4 1100 6 1300 7 1400 High 1500 Low 1100 2 1300 4 1700 6 2100 7 2300 High 2500 Low 1250 2 1430 4 1790 6 2140 7 2320 High 2500 Low 2000 2 2290 4 2860 6 3430 7 3710 High 4000 Low 2000 2 2290 4 2860 6 3430 7 3710 High 4000 Motor Full Catalog Load Amperes Number 231.00 – 264.00 264.00 – 292.00 330.00 – 362.00 LXD63H600 395.00 – 428.00 CLD63H600 428.99 – 462.00 462.00 – 490.00 215.00 – 238.00 238.00 – 261.00 261.00 – 284.00 308.00 – 369.00 LMXD63L800 369.00 – 423.00 423.00 – 462.00 462.00 – 490.00 246.00 – 269.00 269.00 – 284.00 284.00 – 323.00 362.00 – 492.00 LMXD63A800 492.00 – 562.00 562.00 – 616.00 616.00 – 660.00 231.00 – 264.00 264.00 – 292.00 292.00 – 330.00 362.00 – 395.00 MXD63L800 428.00 – 462.00 CMD63L800 462.00 – 490.00 308.00 – 352.00 352.00 – 442.00 442.00 – 447.00 483.00 – 527.00 MXD63A800 571.00 – 616.00 CMD63A800 616.00 – 660.00 385.00 – 440.00 495.00 – 550.00 MXD63H800 605.00 – 660.00 CMD63H800 660.00 – 695.00 ETI Trip Setting Adjustment Amperes Low 3000 2 3430 4 4290 6 5140 7 5570 High 6000 Low 2800 2 3100 3 3400 5 4000 6 4800 7 5500 High 6000 Low 3200 2 3500 3 3700 5 4700 6 6400 7 7300 High 8000 Low 3000 2 3430 3 3800 5 4710 7 5570 High 6000 Low 4000 2 4570 3 5740 5 6280 7 7240 High 8000 Low 5000 3 6430 5 7860 6 8575 Molded Case Circuit Breakers APPLICATION Motor Circuits Breaker Mounted at a Distance From Motor Starter ET thermal-magnetic circuit breakers conform to the National Electrical Code (2002) table 430-52 requirements for motor branch and feeder circuit protection when properly applied in conjunction with motor-running overcurrent protective devices. The recommended circuit-breaker ratings in Table 2 provide adequate time delay for starting the majority of three-phase induction motors. To determine the ampere ratings of the ET breaker to protect a motor feeder, add the rating of the ET breaker used to protect the largest motor branch circuit in the group to the full-load currents of the remaining motors in the group. Interrupt Ratings For normal commercial purposes, available fault current can conveniently be obtained in the Interrupting Selector Tables. Table 2 (When Breaker is Mounted at a Distance From Motor Starter) 3 Phase Induction Type Motors (EQ and ET circuit breakers (thermal-magnetic trip) for branch breaker use with alternating-current combination motor starters). 100 JXD2 JXD23B400 400 200 250 LD6 or LMD6 LD6 or LMD6 LMD6 — LD63B600 LMD63B600 LD63B600 or LMD63B600 LMD63B800 — 300 — 350 — 125 150 230V Motors 240V Circuit Breaker Data Breaker Catalog Ampere Type Number Rating BQ3B015 015 BQ3B015 015 BQ3B015 015 BQ BQ3B015 015 BQ3B015 015 BQ3B020 020 BQ3B030 030 BQ3B050 050 BQ BQ3B070 070 BQ3B090 090 BQ3B100 100 FXD63B125 125 FXD63B150 150 FXD6 FXD63B175 175 FXD63B200 200 460V Motors 480V Circuit Breaker Data Breaker Catalog Ampere Type Number Rating ED43B015 015 ED43B015 015 ED43B015 015 ED4 ED43B015 015 ED43B015 015 ED43B015 015 ED43B015 015 ED43B030 030 ED4 ED43B030 030 ED43B040 040 ED43B050 050 FXD63B090 090 FXD63B100 100 FXD6 FXD63B125 125 FXD63B150 150 575V Motors 600V Circuit Breaker Data Breaker Catalog Ampere Type Number Rating ED63B015 015 ED63B015 015 ED63B015 015 ED6 ED63B015 015 ED63B015 015 ED63B015 015 ED63B015 015 ED63B020 020 ED6 ED63B030 030 ED63B035 035 ED63B050 050 FXD63B060 060 FXD63B070 070 FXD6 FXD63B090 090 FDX63B100 100 — JXD2 FXD6, FD6 FXD6, FD6 FD6 JD6 150 200 250 250 FXD6 FXD63B100 FXD6, FD6 FXD63B125 FXD6, FD6 FD63B175 175 FXD63B200 JD63B200 FXD63B225 JD63B225 JD63B300 JD63B400 200 200 225 225 300 400 400 — JXD23B350 — 350 JXD2 JXD23B400 400 600 LD6 or LMD6 600 LMD6 800 — LMD6 — LD63B500 or LMD63B500 LD63B600 or LMD63B600 LMD63B800 — — — — — — — — — — — FXD63B150 FXD63B200 FD63B250 JD63B250 100 125 500 JD6 JD63B300 300 600 JD6 JD63B300 300 800 — JD6 JD6 LD6 or LMD6 JD63B350 JD63B400 LD63B600 or LMD63B600 350 400 FXD6, FD6 OR JD6 FXD6 or JD6 JD6 JD6 600 JD6 JD63B400 LMD6 LMD63B700 700 LD6 or LMD6 LD6 or LMD6 LMD6 LD63B500 or 500 LMD63B500 LD63B600 or 600 LMD63B600 LMD63B800 800 — — — — — — LMD6 LMD63B800 800 — — — — — — — — — CIRCUIT BREAKERS 400 500 6 060 075 200 and 208V Motors 240V Circuit Breaker Data Breaker Catalog Ampere Type Number Rating BQ3B015 015 BQ3B015 015 BQ3B015 015 BQ BQ3B015 015 BQ3B020 020 BQ3B030 030 BQ3B040 040 BQ3B060 060 BQ BQ3B070 070 BQ3B100 100 — — FXD63B125 125 FXD63B150 150 FXD6 FXD63B175 175 FXD63B200 200 FXD63B225 225 JXD2 JXD23B300 300 JXD2 JXD23B400 400 Motor Horsepower Rating 0001⁄2 0003⁄4 001 0011⁄2 002 003 005 0071⁄2 010 015 020 025 030 040 050 The selection of breakers for this table is in accordance with Article 430, 2002 National Electric Code. The Canadian electrical code should also be referred to for rating information. Recommended circuit breakers are for full voltage starting, special consideration is necessary for reduced voltage starting. For panelboard applications, substitute the BL breaker for the BQ, ED2 circuit breakers may also be used. For non-interchangeable trip applications, substitute the FXD6 for the FD6, the JXD6 for the JD6, or the LXD6 for the LD6. 6/57 Molded Case Circuit Breakers APPLICATION Adjustable Instantaneous Magnetic Trip Settings Breaker Type ED6 CED6 FXD6-A FD6-A 6 HFD6 CIRCUIT BREAKERS HHFD6 CFD6 Maximum Continuous Amperes 1 2 3 5 10 25 30 40 50 100 125 1 2 3 5 10 25 30 40 50 100 125 70 80 90 100 110 125 150 150 150 175 200 225 250 70 80 90 100 110 125 150 175 200 225 250 70 80 90 100 110 125 150 175 200 225 250 70 80 90 100 110 125 150 175 200 225 250 70 80 90 100 110 125 150 150 150 175 200 225 250 Nominal AC Adjustable Trip Range Low 2 3 4 2.6 4.5 6 7.5 7 11 15 19 10 17 23 30 16 26 36 46 30 50 70 85 55 90 125 155 80 135 185 235 115 185 255 325 180 300 410 520 315 540 740 890 500 720 920 1100 2.6 4.5 6 7.5 7 11 15 19 10 17 23 30 16 26 36 46 30 50 70 85 55 90 125 155 80 135 185 235 115 185 255 325 180 300 410 520 315 540 740 890 500 720 920 1100 600 640 690 730 600 640 690 730 600 640 690 730 700 770 840 920 700 770 840 920 800 900 1000 1100 400 460 520 580 800 900 1000 1100 1100 1300 1500 1700 900 1060 1210 1370 900 1060 1210 1370 1100 1300 1500 1700 1100 1300 1500 1700 600 640 690 730 600 640 690 730 600 640 690 730 700 770 840 920 700 770 840 920 800 900 1000 1100 800 900 1000 1100 900 1060 1210 1370 900 1060 1210 1370 1100 1300 1500 1700 1100 1300 1500 1700 600 640 690 730 600 640 690 730 600 640 690 730 700 770 840 920 700 770 840 920 800 900 1000 1100 800 900 1000 1100 900 1060 1210 1370 900 1060 1210 1370 1100 1300 1500 1700 1100 1300 1500 1700 600 640 690 730 600 640 690 730 600 640 690 730 700 770 840 920 700 770 840 920 800 900 1000 1100 800 900 1000 1100 900 1060 1210 1370 900 1060 1210 1370 1100 1300 1500 1700 1100 1300 1500 1700 600 640 690 730 600 640 690 730 600 640 690 730 700 770 840 920 700 770 840 920 800 900 1000 1100 400 460 520 580 800 900 1000 1100 1100 1300 1500 1700 900 1060 1210 1370 900 1060 1210 1370 1100 1300 1500 1700 1100 1300 1500 1700 Note: Tolerances for instantaneous trip points meet UL 489 (15.3). Nominal AC instantaneous trip points are given in the tables. 6/58 5 6 7 — — — — — — — — — — — — — — — — — — — — — — 770 770 770 990 990 1200 640 1200 1900 1520 1520 1900 1900 770 770 770 990 990 1200 1200 1520 1520 1900 1900 770 770 770 990 990 1200 1200 1520 1520 1900 1900 770 770 770 990 990 1200 1200 1520 1520 1900 1900 770 770 770 990 990 1200 640 1200 1900 1520 1520 1900 1900 — — — — — — — — — — — — — — — — — — — — — — 810 810 810 1060 1060 1300 700 1300 2100 1780 1780 2100 2100 810 810 810 1060 1060 1300 1300 1780 1780 2100 2100 810 810 810 1060 1060 1300 1300 1780 1780 2100 2100 810 810 810 1060 1060 1300 1300 1780 1780 2100 2100 810 810 810 1060 1060 1300 700 1300 2100 1780 1780 2100 2100 — — — — — — — — — — — — — — — — — — — — — — 850 850 850 1140 1140 1400 760 1400 2300 1930 1930 2300 2300 850 850 850 1140 1140 1400 1400 1930 1930 2300 2300 850 850 850 1140 1140 1400 1400 1930 1930 2300 2300 850 850 850 1140 1140 1400 1400 1930 1930 2300 2300 850 850 850 1140 1140 1400 760 1400 2300 1930 1930 2300 2300 High 9 22 35 54 100 180 270 375 600 1000 1250 9 22 35 54 100 180 270 375 600 1000 1250 900 900 900 1200 1200 1500 820 1500 2500 2000 2000 2500 2500 900 900 900 1200 1200 1500 1500 2000 2000 2500 2500 900 900 900 1200 1200 1500 1500 2000 2000 2500 2500 900 900 900 1200 1200 1500 1500 2000 2000 2500 2500 900 900 900 1200 1200 1500 820 1500 2500 2000 2000 2500 2500 ETI Motor Circuit Protector Thermal Magnetic Catalog Number CatalogNumber 3-Pole 2-Pole 3-Pole ED63A001 — — ED63A002 — — ED63A003 — — ED63A005 — — ED63A010 — — ED63A025 — — ED63A030 — — ED63A040 — — ED63A050 — — ED63A100 — — ED63A125 — — CED63A001 — — CED63A002 — — CED63A003 — — CED63A005 — — CED63A010 — — CED63A025 — — CED63A030 — — CED63A040 — — CED63A050 — — CED63A100 — — CED63A125 — — — FXD62B070 FXD63B070 — FXD62B080 FXD63B080 — FXD62B090 FXD63B090 — FXD62B100 FXD63B100 — FXD62B110 FXD63B110 — FXD62B125 FXD63B125 FXD63L150 — — FXD63A150 FXD62B150 FXD63B150 FXD63H150 — — — FXD62B175 FXD63B175 — FXD62B200 FXD63B200 — FXD62B225 FXD63B225 FXD63A250 FXD62B250 FXD63B250 — FD62B070 FD63B070 — FD62B080 FD63B080 — FD62B090 FD63B090 — FD62B100 FD63B100 — FD62B110 FD63B110 — FD62B125 FD63B125 — FD62B150 FD63B150 — FD62B175 FD63B175 — FD62B200 FD63B200 — FD62B225 FD63B225 — FD62B250 FD63B250 — HFD62B070 HFD63B070 — HFD62B080 HFD63B080 — HFD62B090 HFD63B090 — HFD62B100 HFD63B100 — HFD62B110 HFD63B110 — HFD62B125 HFD63B125 — HFD62B150 HFD63B150 — HFD62B175 HFD63B175 — HFD62B200 HFD63B200 — HFD62B225 HFD63B225 — HFD62B250 HFD63B250 — — HHFD63B070 — — HHFD63B080 — — HHFD63B090 — — HHFD63B100 — — HHFD63B110 — — HHFD63B125 — — HHFD63B150 — — HHFD63B175 — — HHFD63B200 — — HHFD63B225 — — HHFD63B250 — CFD62B070 CFD63B070 — CFD62B080 CFD63B080 — CFD62B090 CFD63B090 — CFD62B100 CFD63B100 — CFD62B110 CFD63B110 — CFD62B125 CFD63B125 CFD63L150 — — CFD63A150 CFD62B150 CFD63B150 CFD63H150 — — — CFD62B175 CFD63B175 — CFD62B200 CFD63B200 — CFD62B225 CFD63B225 CFD63A250 CFD62B250 CFD63B250 For DC instantaneous trip points, add 15% to nominal values. Instantaneous trip adjustment is made through the breaker cover on all frame breakers. To change instantaneous trip point on circuit breaker, depress indicating knob, then rotate to desired position. Molded Case Circuit Breakers APPLICATION JXD2(A) JXD6(A) JD6(A) HJD6(A) HHJD6 CJD6 LXD6(A) LD6(A) HLD6(A) HHLD6 CLD6 LMXD6 LMD6 Maximum Continuous Amperes 200 225 250 300 350 400 200 225 250 300 350 400 200 225 250 300 350 400 400 200 225 250 300 350 400 200 225 250 300 350 400 200 225 250 300 350 400 400 450 500 600 250 300 350 400 450 500 600 600 250 300 350 400 450 500 600 250 300 350 400 450 500 600 250 300 350 400 450 500 600 600 500 600 700 800 800 500 600 700 800 Nominal AC Adjustable Trip Range Low 2 3 4 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 1250 1430 1610 1790 2000 2290 2570 2860 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 1250 1450 1610 1790 2000 2290 2570 2860 3000 3430 3860 4290 3000 3430 3860 4290 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 2000 2290 2570 2860 3000 3430 3800 4290 2000 2290 2570 2860 3000 3430 3800 4290 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 2000 2290 2570 2860 3000 3430 3860 4290 3000 3430 3860 4290 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 2000 2290 2570 2860 3000 3430 3860 4290 3000 3430 3860 4290 1250 1430 1610 1790 1250 1430 1610 1790 2000 2290 2570 2860 2000 2290 2570 2860 2000 2290 2570 2860 3000 3430 3860 4290 2000 2290 2570 2860 3000 3430 3860 4290 3000 3430 3860 4290 3000 3430 3860 4290 3200 3500 3700 4200 2800 3100 3400 3700 3200 3500 3700 4200 3000 3430 3860 4290 3000 3430 3860 4290 3200 3500 3700 4200 3200 3500 3700 4200 5 1960 1960 1960 1960 3140 3140 1960 1960 1960 1960 3140 3140 1960 1960 1960 1960 3140 1960 3140 1960 1960 1960 1960 3140 3140 1960 1960 1960 1960 3140 3140 1960 1960 1960 1960 3140 3140 1960 3140 4710 4710 1960 1960 3140 3140 3140 4710 3140 4710 1960 1960 3140 3140 3140 4710 4710 1960 1960 3140 3140 3140 4710 4710 1960 1960 3140 3140 3140 4710 3140 4710 4710 4710 4700 4000 4700 4710 4710 4700 4700 6 2140 2140 2140 2140 3430 3430 2140 2140 2140 2140 3430 3430 2140 2140 2140 2140 3430 2140 3430 2140 2140 2140 2140 3430 3430 2140 2140 2140 2140 3430 3430 2140 2140 2140 2140 3430 3430 2140 3430 5140 5140 2140 2140 3430 3430 3430 5140 3430 5140 2140 2140 3430 3430 3430 5140 5140 2140 2140 3430 3430 3430 5140 5140 2140 2140 3430 3430 3430 5140 3430 5140 5140 5140 6400 4800 6400 5140 5140 6400 6400 7 2320 2320 2320 2320 3710 3710 2320 2320 2320 2320 3710 3710 2320 2320 2320 2320 3710 2320 3710 2320 2320 2320 2320 3710 3710 2320 2320 2320 2320 3710 3710 2320 2320 2320 2320 3710 3710 2320 3710 5570 5570 2320 2320 3710 3710 3710 5570 3710 5570 2320 2320 3710 3710 3710 5570 5570 2320 2320 3710 3710 3710 5570 5570 2320 2320 3710 3710 3710 5570 3710 5570 5570 5570 7300 5500 7300 5570 5570 7300 7300 High 2500 2500 2500 2500 4000 4000 2500 2500 2500 2500 4000 4000 2500 2500 2500 2500 4000 2500 4000 2500 2500 2500 2500 4000 4000 2500 2500 2500 2500 4000 4000 2500 2500 2500 2500 4000 4000 2500 4000 6000 6000 2500 2500 4000 4000 4000 6000 4000 6000 2500 2500 4000 4000 4000 6000 6000 2500 2500 4000 4000 4000 6000 6000 2500 2500 4000 4000 4000 6000 4000 6000 6000 6000 8000 6000 8000 6000 6000 8000 8000 ETI Motor Circuit Protector Thermal Magnetic Catalog Number CatalogNumber 3-Pole 2-Pole 3-Pole — JXD22B200 JXD23B200 — JXD22B225 JXD23B225 — JXD22B250 JXD23B250 — JXD22B300 JXD23B300 — JXD22B350 JXD23B350 — JXD22B400 JXD23B400 — JXD62B200 JXD63B200 — JXD62B225 JXD63B225 — JXD62B250 JXD63B250 — JXD62B300 JXD62B300 — JXD62B350 JXD23B350 — JXD62B400 JXD23B400 — JD62B200 JD63B200 — JD62B225 JD63B225 — JD62B250 JD63B250 — JD62B300 JD63B300 — JD62B350 JD63B350 JXD63L400 — — JXD63H400 JD62B400 JD63B400 — HJD62B200 HJD63B200 — HJD62B225 HJD63B225 — HJD62B250 HJD63H250 — HJD62B300 HJD63B300 — HJD62B350 HJD63B350 — HJD62H400 HJD63B400 — HHJD62B200 HHJD63B200 — HHJD62B225 HHJD63B225 — HHJD62B250 HHJD63B250 — HHJD62B300 HHJD63B300 — HHJD62B350 HHJD63B350 — HHJD62B400 HHJD63B400 — — CJD63B200 — — CJD63B225 — — CJD63B250 — — CJD63B300 — — CJD63B350 CJD63H400 — CHD63B400 CJD63L400 — — — LXD62B450 LXD63B450 — LXD62B500 LXD63B500 — LXD62B600 LXD63B600 — LD62B250 LD63B250 — LD62B300 LD63B300 — LD62B350 LD63B350 — LD62B400 LD63B400 — LD62B450 LD63B450 — LD62B500 LD63B500 LXD63L600 — — LXD63H600 LD62B600 LD63B600 — HLD62B250 HLD63B250 — HLD62B300 HLD63B300 — HLD62B350 HLD63B350 — HLD62B400 HLD63B400 — HLD62B450 HLD63B450 — HLD62B500 HLD63B500 — HLD62B600 HLD63B600 — HHLD62B250 HHLD63B250 — HHLD62B300 HHLD63B300 — HHLD62B350 HHLD63B350 — HHLD62B400 HHLD63B400 — HHLD62B450 HHLD63B450 — HHLD62B500 HHLD63B500 — HHLD62B600 HHLD63B600 — — CLD63B250 — — CLD63B300 — — CLD63B359 — — CLD63B400 — — CLD63B450 — — CLD63B500 CLD63L600 — — CLD63H600 — CLD63B600 — — LMXD63B500 — LMXD62B600 LMXD63B600 — LMXD62B700 LMXD63B700 LMXD63L800 — — LMXD63A800 LMXD62B800 LMXD63B800 — LMD62B500 LMD63B500 — LMD62B600 LMD63B600 — LMD62B700 LMD63B700 — LMD62B800 LMD63B800 6/59 CIRCUIT BREAKERS Breaker Type 6 Adjustable Instantaneous Magnetic Trip Settings Molded Case Circuit Breakers APPLICATION Adjustable Instantaneous Magnetic Trip Settings Breaker Type HLMXD6 HLMD6 MD6 MXD6 HMD6 HMXD6 CMD6 ND6 NXD6 6 HND6 HNXD6 CIRCUIT BREAKERS CND6 PD6 PXD6 HPD6 HPXD6 CPD6 RD6 RXD6 HRD6 6/60 Maximum Continuous Amperes 500 600 700 800 500 600 700 800 500 600 700 800 800 800 500 600 700 800 800 800 500 600 700 800 500 600 700 800 400 500 600 700 800 800 800 800 900 1000 1200 900 1000 1200 800 900 1000 1200 900 1000 1200 800 900 1000 1200 1200 1400 1600 1200 1400 1600 1200 1400 1600 1200 1400 1600 1200 1400 1600 1800 2000 1800 2000 1800 2000 Nominal AC Adjustable Trip Range Low 2 3 4 3000 3430 3860 4290 3000 3430 3860 4290 3200 3500 3700 4200 3200 3500 3700 4200 3000 3430 3860 4290 3000 3430 3860 4290 3200 3500 3700 4200 3200 3500 3700 4200 3000 3430 3860 4290 3000 3430 3860 4290 4000 4570 5140 5710 3000 3430 3860 4280 4000 4570 5140 5710 5000 5715 6430 7145 3000 3430 3860 4280 3000 3430 3860 4280 4000 4570 5140 5710 3000 3430 3860 4280 4000 4570 5140 5710 5000 5715 6430 7145 3000 3430 3860 4280 3000 3430 3860 4280 4000 4570 5140 5710 4000 4570 5140 5710 3000 3430 3860 4280 3000 3430 3860 4280 4000 4570 5140 5710 4000 4570 5140 5710 3000 3430 3860 4280 3000 3430 3860 4280 3000 3430 3860 4280 4000 4570 5140 5710 3000 3430 3860 4280 4000 4570 5140 5710 5000 5715 6430 7145 4000 4570 5140 5710 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 4000 4570 5140 5710 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 4000 4570 5140 5710 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5000 5715 6430 7145 5 4710 4710 4700 4700 4710 4710 4700 4700 4710 4710 6280 4710 6280 7860 4710 4710 6280 4710 6280 7860 4710 4710 6280 6280 4710 4710 6280 6280 4710 4710 4710 6280 4710 6280 7860 6280 7860 7860 7860 7860 7860 7860 6280 7860 7860 7860 7860 7860 7860 6280 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 7860 6 5140 5140 6400 6400 5140 5140 6400 6400 5140 5140 6850 5140 6850 8575 5140 5140 6850 5140 6850 8575 5140 5140 6850 6850 5140 5140 6850 6850 5140 5140 5140 6850 5140 6850 8575 6850 8575 8575 8575 8575 8575 8575 6850 8575 8575 8575 8575 8575 8575 6850 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 8575 7 5570 5570 7300 7300 5570 5570 7300 7300 5570 5570 7420 5570 7420 9290 5570 5570 7420 5570 7420 9290 5570 5570 7420 7420 5570 5570 7420 7420 5570 5570 5570 7420 5570 7420 9290 7420 9290 9290 9290 9290 9290 9290 7420 9290 9290 9290 9290 9290 9290 7420 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 9290 High 6000 6000 8000 8000 6000 6000 8000 8000 6000 6000 8000 6000 8000 10000 6000 6000 8000 6000 8000 10000 6000 6000 8000 8000 6000 6000 8000 8000 6000 6000 6000 8000 6000 8000 10000 8000 10000 10000 10000 10000 10000 10000 8000 10000 10000 10000 10000 10000 10000 8000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 ETI Motor Circuit Protector Thermal Magnetic Catalog Number Catalog Number 3-Pole 2-Pole 3-Pole — — HLMXD63B500 — — HLMXD63B600 — — HLMXD63B700 — — HLMXD63B800 — HLMD62B500 HLMD63B500 — HLMD62B600 HLMD63B600 — HLMD62B700 HLMD63B700 — HLMD62B800 HLMD63B800 — MD62B500 MD63B500 — MD62B600 MD63B600 — MD62B700 MD63B700 MXD63L800 — — MXD63A800 MD62B800 MD63B800 MXD63H800 — — — MXD62B500 MXD63B500 — MXD62B600 MXD63B600 — MXD62B700 MXD63B700 MXD63L800 — — MXD63A800 MXD62B800 MXD63B800 MXD63H800 — — — HMD62B500 HMD63B500 — HMD62B500 HMD63B600 — HMD62B700 HMD63B700 — HMD62B800 HMD63B800 — — HMXD63B500 — — HMXD63B600 — — HMXD63B700 — — HMXD63B800 — — CMD63B400 — — CMD63B500 — — CMD63B600 — — CMD63B700 CMD63L800 — — CMD63A800 — CMD63B800 CMD63H800 — — — ND62B800 ND63B800 — ND62B900 ND63B900 — ND62B100 ND63B100 — ND62B120 ND63B120 — NXD62B900 NXD63B900 — NXD62B100 NXD63B100 — NXD62B120 NXD63B120 — HND62B800 HND63B800 — HND62B900 HND63B900 — HND62B100 HND63B100 — HND62B120 HND63B120 — — HNXD63B900 — — HNXD63B100 — — HNXD63B120 — — CND63B800 — — CND63B900 — — CND63B100 — — CND63B120 — — PD63B120 — — PD63B140 — — PD63B160 — — PXD63B120 — — PXD63B140 — — PXD63B160 — — HPD63B120 — — HPD63B140 — — HPD63B160 — — HPXD63B120 — — HPXD63B140 — — HPXD63B160 — — CPD63B120 — — CPD63B140 — — CPD63B160 — — RD63B180 — — RD63B200 — — RXD63B180 — — RXD63B200 — — HRD63B180 — — HRD63B200 Molded Case Circuit Breakers SELECTION Molded Case Switch — Circuit Disconnect Maximum Frame Rating 1100A 2-Pole 3-Pole Catalog Number Catalog Number BQ2S060 ■ BQ2S100■ 68.00 181.00 BQ3S060■ BQ3S100■ Self-Protective Instantaneous Override±20% 314.00 314.00 11000A 11000A 1125A ED22S100A■ 257.00 ED42S100A■ 541.00 ED42S125A■1035.00 ED62S100A■ 624.00 — — CED62S100A■2325.00 CED62S125A■3509.00 ED23S100A 437.00 ED43S100A 664.00 ED43S125A 1337.00 ED63S100A 800.00 ED63S125A 1527.00 CED63S100A■2907.00 CED63S125A■4172.00 11000A 11000A 11000A 11000A 11000A 11000A 11000A 1225A QJ22S225A■ 273.00 QJ23S225A 12000A 1250 FXD62S250A 1451.00 HFXD62S250A■ — FXD63S250A 1758.00 13200A HFXD63S250A■3060.00 13200A CFD63S250A■5644.00 13200A 1400 JXD22S400A■1833.00 JXD23S400A 2262.00 — —2539.00 JXD63S400A 3087.00 — HJXD63S400A■5208.00 CJD63S400A■6434.00 1600 — — LXD63S600A 4442.00 18000A HLXD63S600A■5942.00 18000A CLD63S600A■10450.00 18000A — — LMXD63S800A■5104.00 10000A MXD63S800A5104.00 10000A CMD63S800A11857.00 10000A 1200 — NXD63S120A9016.00 10000A CND63S120A■16930.00 10000A 1600 PXD63S160A13326.00 2000 RXD63S200A■14762.00 10000A 1800 886.00 Ordering Information Order by catalog number. Switches include frame and self protective (except TD) trip unit only. Order lugs separately from pages 6-70 to 6-72. 16000A 16000A 16000A 16000A 10000A Non Automatic Molded Case Switch TD63S2000■19413.00 — 2500 TD63S2500■21856.00 — 3200 TD63S3200■24053.00 — 4000-5000 See “SB” Type Insulated Case Breakers CIRCUIT BREAKERS 6 2000 Lugs pages 6/71 to 6/72 Accessories pages 6/75 to 6/80 ■ Built to order. Allow 3-4 weeks for delivery. For 2-pole application use outside poles of 3-pole circuit breaker. For additional lugs see pages 6-70 to 6-72. Molded case switches up to R frame contain a self protecting instantaneous element, which may open circuit above their override set point. 6/61 Molded Case Circuit Breakers TECHNICAL Digital Solid State Sentron Sensitrip III Series Functions available in Sentron Sensitrip circuit breakers. The Sentron Sensitrip III circuit breaker is a true RMS current sensing Cont Long InstanShort device. Digital microprocessor Trip Current Time taneous Time circuitry within the electronic trip unit Catalog Number provides more precise control over the (Description + Suffix) Type Setting Delay Setting Pick Up Basic Unit + (A) LI — circuit breaker functions. This control Basic Unit + (A)G LIG — allows circuit coordination flexibility Basic Unit + (A)NT LSI not available with thermal magnetic Basic Unit + (A)NGT LSIG circuit breakers. Short Time Delay Short Time l2t Pick Up Ground Fault Pick Up Ground Fault Delay — — — — — — — — Letter “A” is used for MD and ND Solid State frame types only. Typical Trip Unit Labeling and Adjustment Positions for the Sentron Sensitrip Circuit Breaker. SMD6, SHMD6, SCMD6, SND6, SHND6, SCND6, SPD6, SHPD6 SJD6, SHJD6, SCJD6, SCD6, SHLD6, SCLD6 6 CIRCUIT BREAKERS ln = Maximum circuit breaker ampere rating. lr = Current Rating — a function of continuous ampere adjustment setting expressed in % of ln . lg = Ground Fault Pickup — a function of adjustment setting expressed in % of ln . 6/62 Molded Case Circuit Breakers TECHNICAL Digital Solid State Sentron Sensitrip III Series D. Adjustable “Short Time Pick-Up” Switch (Optional) A. Adjustable “Continuous Amps” Rating Switch Sensitrip III circuit breakers with an adjustable short time pick-up switch allow for selection of short time pick-up in a range from 1.5 to 10 times the setting of the maximum current rating. All Sensitrip III solid state molded case circuit breakers have an adjustable ampere rating switch. Adjustments made to this switch change the continuous current rating of the breaker from 20% to 100% of its maximum trip unit rating depending on the circuit breaker frame. E. Adjustable “Short Time Delay” Switch (Optional) Sensitrip III circuit breakers with an adjustable short time pick-up switch also contain a switch for adjustment in time delay. The adjustable short time delay switch allows for either of two modes of short time delays. One range of settings enables the breaker to be set for fixed time delays and the other range of settings enables the breaker to be set for short time delays based on l2t curves. B. Adjustable “Long Time Delay” Switch All Sensitrip III circuit breakers have an adjustable long time delay switch to allow for selection of long time delays of fixed time intervals at six times the setting of the adjustable “continuous amps” rating switch. C. Adjustable “Instantaneous Pick-Up” Switch Sensitrip III circuit breakers with an adjustable instantaneous trip switch allow selection of a tripping point from related to the adjusted circuit breaker Rating (lr). Adjustable “Ground Fault Pick-Up” Switch Sensitrip III circuit breakers containing the optional equipment ground fault protection cover the ground fault pick-up range of 20% to 70% of the circuit breaker frame rating. The ground fault pick-up settings also allow for one of three time delays based on 12t curves. 6 For 3-phase, 4-wire systems, an external neutral transformer is required with an ampere rating equal to the trip unit ampere rating. ln = Maximum circuit breaker ampere rating. lr = Current Rating — a function of adjustment setting expressed in % of ln. lg = Ground Fault Pick-up — a function of adjustment setting expressed in % of ln. Examples of Adjustment Settings In = 800 In = 800 amperes Results Continuous Current Setting Long Time Delay Setting Instantaneous Setting 30 240 amperes lr = 30% of 800 12 12 seconds trip at 6 x 240 amps = 1440. 8 1920 amperes 8 x lr = 8 x 240 CIRCUIT BREAKERS Catalog Number SMD69800A Catalog Number SMD69800ANGT ln lr Setting Long Time Delay Short Time Pick-Up Off Instantaneous Setting Short Time Pick-Up On Short Time Delay l 2T Set Ground Fault Pick-Up Ground Fault Delay 800 amperes Results 070 560 20 20 sec. — — 10 lr 5600A 8 lr 4480A .5 .5 secs .28 .28 sec @ 4480A 40 320A .2 .2 sec ln = 800 amperes. lr = 560 amperes (70% of 800). Delay = 20 seconds at 3360 amps (6 x lr). Breaker will trip in 20 seconds with 3360 amperes. Short Time Pick-Up Off — Instantaneous can be used. Instantaneous set at 10 x lr = 10 x 560 = 5600 amperes. l2t switch on .28 seconds @ 6 x 560 = 3360 amperes. (Inverse time) Short Ground Fault Pick-Up set at 40 = 40% of ln = 320 amperes. (Definite Time) Time Pick-Up On — Set at 8 = 8 x 560 = 4480 amperes. Short Note: Time Delay = .5 seconds. (Definite Time) & are mutually exclusive. Ground Fault Delay set at .2 seconds. Breaker will trip in 200 milliseconds with a 400 ampere ground fault. 6/63 SB Encased System Breakers GENERAL 800 to 5000 Ampere Frame Rating Description Siemens SENTRON® SB Breakers provide maximum flexibility, with four principal frame size envelopes: 1200, 2000, 3200, and 5000 amperes. Applications include mains, ties, feeders, and emergency source breakers in industrial plants, commercial installations, and health care facilities. SB Breakers combine high interrupting ability with extended short time tripping for successful application in fully-rated systems, while providing complete selectivity through the applied breaker’s short time rating. This assures the highest possible reliability and availability from the power distribution system. The circuit breaker mechanism is a true two-step stored energy system that allows for a maximum five cycle closing for distribution bus paralleling. SB Breakers Exceed UL Requirements SB Breakers comply with worldwide industry standards and are UL Listed and CSA certified for enclosed operation at 100% in both fixed and drawout mounting configurations. The robust, self-cooling SB Breaker design requires no additional ventilation, even when operated at 100% of the Frame Ampere Rating. 6 Internal Accessories Electric Motor Operator Local Electric Close Auxiliary & Alarm Switches Undervoltage Release (UVR) Shunt Trip Remote Open/Close & Alarm Relay CSA / UL / IEC Symmetrical RMS Amperes Interrupting Ratings Standard Measurement Voltage AC SB Encased Systems Breaker Frame Amperage Rating 400 800 1200 2000 3200 4000 5000 Type SBA–Alternate A.I.R. (KA): Blue Label 240 065 065 065 085 — — — 480 065 065 065 065 — — — 600 042 042 042 050 — — — 150 Type SBS–Standard A.I.R. (KA): Black Label CSA/UL (489) Interrupting 240 Ratings– Symmetrical 480 RMS Amperes 600 100 100 100 100 150 150 100 100 100 100 100 100 100 050 050 050 065 085 085 085 Type SBH–High A.I.R. (KA): Red Label 240 N/A N/A N/A 200 200 200 200 480 N/A N/A N/A 150 150 150 150 600 N/A N/A N/A 100 100 100 100 0 0 0 0 0 0 0 Short Time Ratings (KA)t = .5 seconds IEC 947-2 (For SBS Breakers Only) lcu Interrupting 415 lcs Ratingslcw Symmetrical lcu RMS Amperes 690 lcs (50HZ) lcw 25 25 25 35 50 65 65 100 100 100 100 100 100 100 025 025 025 035 050 065 065 0 0 0 0 0 0 0 025 025 035 050 065 065 65 65 65 025 65 65 65 65 SB Frame Sizes, Ratings, Rating Plugs & Dimensions Frame Sizes 1200A 2000A 3200A 5000A Frame Ampere Rating Rating Plugs (Amperes) 0400 200, 225, 250, 300, 350, 400 0800 400, 450, 500, 600, 700, 800 1200 600, 700, 800, 1000, 1200 1200 600, 700, 800, 1000, 1200 2000 1000, 1200, 1600, 2000 2500 1600, 2000, 2500 3200 1600, 2000, 2500, 3000, 3200 2500 1600, 2000, 2500 3200 1600, 2000, 2500, 3000, 3200 4000 2000, 2500, 3000, 3200, 4000 5000 2500, 3000, 3200, 4000, 5000 Fixed Mounting (H x W x D) Moveable Drawout Mounting (H x W x D) 12.0 x 15.5 x 12.5 13.75 x 20.5 x 16.0 16.75 x 15.5 x 12.5 19.8 x 20.5 x 16.0 27.5 x 15.5 x 12.5 35.0 x 21.5 x 16.0 27.5 x 23.5 x 12.5 35.0 x 29.5 x 16.0 CIRCUIT BREAKERS External Accessories Ground Fault Sensing and Relaying Key Interlock and Padlock Features Drawout Padlock and Close Blocking Cell Switches Drawout Safety Shutters Secondary Disconnect & Terminal Block T Connectors Neutral Sensing Transformers Lifting Device Jacket Auxiliary Power Supply Dead Front Shield Trip Unit Retrofit Kits PC and Network Communications Consult Siemens Sales Office for pricing and production schedule. SB Price and Selection Guide IPPS-2209 is also available. 6/64 Breaker Frame Size refers to the physical breaker envelope size. Frame Ampere Rating is determined by the current sensors in the breaker. Breaker SB Encased System Breakers GENERAL Electronic Trip Units Two types of interchangeable trip units for the SB Encased Systems Breakers are available. The basic type “TL” Trip Unit features a full range of industry standard protective settings and the highperformance Systems Breaker Energy Communicating Trip Unit (SB-EC Trip Unit) offers advanced metering, protective relaying, time-stamped logs, and power quality monitoring functions, including an integral keypad and LCD graphical display for menu-driven system configuration and real-time voltage and current waveform displays. Both units offer unique models to provide an efficient combination of options versus cost for every application. Interchangeable Rating Plugs SB Breaker trip units use field interchangeable rating plugs allowing the effective ampere rating of the circuit breaker to be field-modified and provides security against indiscriminate changes in the breaker’s ampere rating. Advanced True RMS Current Sensing Both the basic type “TL” and the premium SB-EC Trip Unit feature advanced digital-processing techniques to measure the true heating content of the current waveform. This True RMS value of current measurement virtually eliminates nuisance tripping due to the presence of harmonics on the distribution bus. Communications control, including peak demand, trend analysis, waveform analysis, and harmonic calculations and displays. These functions help pinpoint energy consumption, power quality issues, and the energy cost of any process. Outages and potential outages can be quickly diagnosed and plans can be generated for expansion and preventative plant maintenance. Communications is accomplished via EIA-485 twisted pair wire or modem, providing communications to a remote site and allowing access to multiple plants. WinPM™ utilizes a Windows DDE (dynamic data exchange) server that allows data exchange to other Windows software such as spreadsheets and word-processors. Protocol Converters are available from Siemens for connection to a variety of open and proprietary automation protocols, including Profibus DP, LonWorks, the Siemens S7 PLC, and many other third party PLCs and associated networks. The SB-EC Trip Unit’s EIA-232 communications port provides additional local PC communications for available trip unit data displays and trip unit configuration via Siemens SBWin™ software. 6 All SB Circuit Breaker trip units feature two levels of communication: Zone Selective Interlocking and ACCESS™ System Open-protocol communications, allowing integration into Siemens WinPM™ V4.0 supervisory software, along with other popular third party energy monitoring networks and components. WinPM™ V4.0 delivers a powerful energy management system providing sophisticated monitoring capability to a host computer and other components in the electrical distribution system at an affordable cost. It also provides process Robotics CNC PLCs us, . . . CIRCUIT BREAKERS t, ModB viceNe orks, De W n o L , P FIBUS D PC PRO Data Transfer Link Win PM Power Meters Access MT SB Breaker MCCBs 6/65 SB Encased System Breakers GENERAL Electronic Trip Units Frame Rating Indication: indicates the frrame rating of the circuit breaker with which the trip unit is used SB-EC Trip Unit Features by Model Type Feature 6 SBxxTP01 SBxxTP01G SBxxTP02 SBxxTP02G Integral Keypad & Display Voltage/Current Waveform Displays Protective Functions Long Time, Short Time, Instantaneous Metering Functions Volts, Amps, PF, Frequency, Watts, VARs, VA, Crest Factor, Ampand Watt Demand, Voltage and Current Waveforms, Voltage and Current Unbalance Communications PC (RS-232), ACCESS (RS-485) Counters Breaker Test (Trip/No Trip), Mechanical Counter, Interruption Level Fault Counter Security Password Protection Event Log Time-stamped—10 Most Recent Events Trip Log Time-stamped—5 Most Recent Events Alarms (Alarm Only) Overcurrent, Gnd. Overcurrent, Over Amp Demand, Over kW Over kW Demand, Phase Sequence, Over KVAR, Over KVA, Under/Over P.F. Advanced Alarms Total Harmonics — — Min./Max. Logs Volt/Amp, Power, PF, Freq., %THD — — Harmonic Analysis Up to 19th Per Phase, THD — — Protective Relay Functions (Alarm and/or Trip) Neutral Overcurrent, Current Balance, Under/Over Voltage, Voltage Unbalance, Reverse Power, Under/Over Frequency, Phase Loss — — Ground Fault Protection Residual or Ground Return — — CIRCUIT BREAKERS Wave Form Displays The SB-EC Trip Unit offers digital waveform sampling as a standard feature that allows a real-time graphical view of a complete cycle of line and neutral currents or phase voltages, including voltage and current phase relationships and harmonic distortion. On-board harmonic analysis functions are available on premium units, allowing harmonic analysis up to the 19th multiple and permitting the data to be viewed and examined on the integral LCD graphical panel. Sampled data can also be stored in memory and transmitted to a PC via the serial communications port, using Further Information Refer to SB Encased Systems Breaker Bulletin IPPS-2209E for additional price and catalog information. SB-EC Trip Unit Product Bulletins are also available (IPPS-2208B, IPFL-2207A). 6/66 Siemens WinPM™ Version 4.0 or later or SBWin™ Software to display the waveforms and automatically perform harmonic analysis using Fast Fourier transformation techniques. Both the resident trip unit and the PC-based harmonic analysis functions provide the value of Total Harmonic Distortion (THD) of the waveforms and are useful in locating the source and severity of harmonics and developing corrective strategies. Remote Operation Remote, automatic open and close operation of the breaker is possible System Status Indicators: Yellow LED indicates an alarm condition, red LED indicates a trip condition System Check Indicators: Two green LEDs blink to indicate that protective and metering systems are working correctly LCD Display: provides fast, convenient display of menu options and device status ESC Key: used to exit menus Up and Down Arrows: for convenient scrolling through choices on LCD EIA232 Serial Port: for direct connection to a personal computer Enter Key: for selection of choices or moving between selections Test Connector: easy connection to portable TS-31 test set for functional testing via the trip unit’s EIA-232 or EIA-485 communication ports or a hard-wire input. For remote operation via a communication port, WinPM Version 4.0 or later, Shunt Trip and Remote Open/ Close Relay accessories are required for the remote open function, and an Electrical Operator accessory is required in addition for both remote open and close operations. For remote operation via a hard-wire input, only a Shunt Trip accessory is necessary for the remote open function, and an Electrical Operator is additionally required for both remote open and close operations. SB Encased System Breakers GENERAL Electronic Trip Units Rating Plug Basic Type “TL” Trip Unit Available Type “TL” Features by Model Trip Unit Function Catalog Number SB T Adjustable Continuous Current Adjustable Long Time Delay Adjustable Short Time Pickup — — Adjustable Short Time Delay (l2T) — — Adjustable Short Time Delay (Fixed) — — Adjustable Instantaneous Pickup — — Adjustable Ground Fault Pickup — — — Adjustable Ground Fault Time Delay (l2T) — — — Adjustable GF Time Delay (Fixed) — — — Fixed Instantaneous Override Internal Watchdog Integral Testing Functions — — Curve Adjustments Local Trip Indication: Overload Short Time Short Circuit Ground Fault Access Communications Compatibility Catalog Number Suffix LI LSI LS LIG LSG LSIG Fault indicators Built-in Test Functions Consult Siemens Sales Office for pricing or refer to SB Encased Systems Breaker Bulletin IPPS-2209E for additional price and catalog information. (SB-EC Trip Unit Product Bulletins are also available IPPS-2208B, IPFL-2207A). All standard trip units feature: Integral Testing Functions Built-in Trip Indicators Instantaneous “Override” Continuous Self-Diagnostic “Watchdog” System LED on front cover Available protective function adjustments include: Continuous Current Long Time Delay Short Time Pickup and Delay Instantaneous Pickup Ground Fault Pickup and Delay For 3 phase, 4 wire systems, order correct 4th wire (neutral) transformer as separate item. Expansion Plug and Multiplexer/Translator required. See page 6-69. Choose the appropriate function package and catalog number as shown below: Example: S B 2 0 T L S G Breaker Frame Ampere Rating Catalog Number Suffix 2000 ampere breaker ampere rating with: Adjustable Continuous Current Adjustable Long Time Delay Adjustable Short Time Pickup and Time Delay Adjustable Ground Fault Pickup and Time Delay Breaker Ampere Ratings: 04=400, 08=800, 12=1200, 16=1600, 20=2000, 25,=2500, 32=3200, 40=4000 Insert appropriate breaker frame ampere rating desgination into catalog number. See example above. Add appropriate catalog number suffix as required. See example above. 6/67 CIRCUIT BREAKERS The interchangeable trip unit system of the SB breaker showcases the latest advancements in microprocessor controlled circuit protection technology. Using the speed and power of its microprocessor to drive sophisticated digital sampling techniques, the SB trip unit measures the true heating content of the current waveform (RMS current) hundreds of times each second, effectively eliminating nuisance tripping due to the presence of harmonics and other “noise “ on the system. 6 Plug-in Display Module Molded Case Circuit Breakers SELECTION Electronic and Communications Accessories Electronic & Display Devices Local Display Unit Breaker Type Catalog Number SJD, SLD, SMD, SND, SPD, SB, STD LDU-100 SADU Ammeter Display Unit 1201.00 The Local Display Unit (LDU) provides a centralized read-out of all Sensitrip III and SB ICCB breakers. The device provides a panel mountable display for all trip unit data including phase currents and alarms for up to 32 breakers. Also communicates with other ACCESS™ devices. Trip Unit Test Set Type Catalog Number Portable TS31 Spare TS-31 Test Set Interconnecting Cable TS31CABLE 12372.00 168.00 The TS-31 test set is used to test the operation of the fault protection functions of the circuit breaker’s trip unit, including long-time, short-time, instaneous, and ground fault by means of secondary current injections. Sensitrip Ammeter Display Unit Breaker Type Catalog Number SJD, SLD, SMD, SADU SND, SPD SADURMK18 1588.00 306.00 6 The Sensitrip Ammeter Display Unit (SADU) provides real-time metering for all SentronSensitrip III Molded Case Circuit Breakers. The unit plugs directly onto the front of the trip unit and provides displays for individual phase currents flowing through the breaker. Additional features include Average, Demand, Ground and Unbalance Current displays, along with impending Trip Status. Current Metering Logs, and a unique diagnostic Trip Log that records the date, time and type of fault for the previous five breaker trips. The device is UL and CSA certified. The optional panel mount accessory (SADURMK18) allows easy device mounting external from the circuit breaker, in panelboard and switchboard spaces or gutters, with the flexibility of interior panel exterior panel, or wall mounting capability. The 2 x 16 alphanumeric LCD display provides easy viewing of data, such as viewing all three phase currents simultaneously. Plug-in Mounting Panel Mounting • • • • Direct plug-in or Panel Mounting* Trip Unit Powered & Battery back-up 2 x 16 LCD Alphanumeric Display* Ammeter Diplay Functions — — — — — RMS Phase Currents Average Current* Current Demand* Ground Current Current Unbalance (%)* • Breaker Status — Normal — Impending Trip* • Time Stamped Trip Log (last 5) — Time & Date* — Trip Cause: LT, ST, GF, SC CIRCUIT BREAKERS • Max Log (with date & time) — Max Phase Current* — Max Average Current* — Max Ground Current* — Max Unbalance Current* — Max Current Demand* * Unique Features 6/68 Molded Case Circuit Breakers SELECTION Communications Accessories Multiplexor Translator Breaker Type Features Cat No SJD, SLD SMD, SND SPD, STD SBA, SBS, SBH Zone Interlocking Only MTZ 1740.00 Full Communications with Zone Interlocking MTA 3876.00 The Multiplexor Translator MTZ is an interface device required in zone selective interlock schemes. The MTA combines the zone selective interlocking function with interface to ACCESS® Systems. Cables & Connectors Ribbon Cables Breaker Type Length Cat No SJD, SLD SMD, SND SPD, STD SBA, SBS, SBH 06˝ 08˝ 12˝ 18˝ 24˝ EPC06 EPC08 EPC12■ EPC18 EPC24■ 53.00 53.00 70.00 85.00 111.00 Telephone Cables ■ Built to order. Allow 3–4 weeks for delivery. ▲ Built to order. Allow 7–9 weeks for delivery. Factory wired when ACCESS communications or ZSI is ordered for the SB breaker from the factory. Length Cat No SB STD 08˝ 15˝ 25˝ 50˝ MTCSB08 ▲ MTCSB15 ▲ MTCSB25 ▲ MTCSB50 ▲ 70.00 105.00 139.00 139.00 SJD, SLD SMD, SND, SPD, SBA, SBS, SBH 8˝ 15˝ 25˝ 50˝ MTC08 MTC15 MTC25 MTC50 70.00 105.00 139.00 139.00 The Expansion Plug EP is a required isolating device to connect the breaker with the Multiplexor Translator. It is connected to the trip unit on the breaker with a “Ribbon Cable”, EPC08 e.g., and the Multiplexor Translator with the “Telephone Cable” (an RJ-11 cable) MTCSB08 e.g. Breaker Type Frame Size Mounting Type Cat. No SB ICCB and STD 1200A, 2000A Fixed EPSBFMK■ 187.00 Draw out EPSBDMK■ 187.00 SB ICCB and STD 3200A, 5000A Fixed EPSB4FMK ■ 187.00 Drawout EPSB4DMK■ 187.00 Sensitrip ALL ALL EP 187.00 6 Expansion Plug Selection Guide Component Selection Guide Trip Units and Application Component Type ZSI (only) with Sensitrip MCCB’S Access and/or ZSI with Sensitrip MCCB’s ZSI (only) with all SB-EC Trip Units ACCESS ACCESS and/or with SB-TL Trip Units ACCESS with SB-EC Trip Units EP ✓ ✓ EPSB — — — — — ✓ ✓ MTZ ✓ — — ✓ — — MTA — ✓ — ✓ — EPC Cable ✓ ✓ — — — MTC Cable ✓ ✓ — — — MTCSB Cable — — ✓ ✓ — When ordered with circuit breaker from the factory. One MTA or MTZ per eight trip units when required. Always required when multiple MT’s are used. One additional cable per each additional MT. 6/69 CIRCUIT BREAKERS ACCESS™ Communications All SB Circuit Breaker trip units feature two levels of communication: Zone Selective Interlocking and ACCESS™ System Open-protocol communications. The SB-EC Trip Unit is fully equipped for direct integration into ACCESS™ or compatible communication systems. A multiplex/Translator (MTA) and Expansion Plug area required for the TYPE “TL” trip unit when full Access™ communications is specified. The MTA also has Zone Selective Interlocking capability. Refer to Bulletin IPIM-2211A and Instruction Sheet Pc. No. 411152A00 for additional information. Siemens WinPM™ V4.0 supervisory software delivers a powerful energy management system providing sophisticated monitoring capability to a host computer and other components in the electrical distribution system at an affordable cost. It also provides process control, including peak demand, trend analysis, waveform analysis, and harmonic calculations and displays. These functions help pinpoint energy consumption, power quality issues, and the energy cost of any process. Outages and potential outages can be quickly diagnosed and plans can be generated for expansion and preventative plant maintanence. Refer toBulletins IPIM-2211A for additional information. Communications is accomplished via EIA-485 twisted pair wire or modem, providing communications to a remote site and allowing access to multiple plants. WinPM™ V4.0 utilizes a WIndows DDE (dynamic data exchange) server that allows data exchange to other Windows software such as spreadsheets and wordprocessors. Protocol Converters are available from the Siemens ACCESS group for connection to a variety of open and proprietary automation protocols as part of the ACCESS™ product line, including Profibus DP, LonWorks, the Siemens S7 PLC, and many other third party PLCs and associated networks. The SB-EC Trip Unit’s EIA-232 communications port provides additional PC communications for available trip unit data displays and trip unit configuration via Siemens SBin™ software. Breaker Type Lug Information SELECTION Mechanical Lug For Use With Type(s) Circuit Breaker Ampere Rating Cables Per Lug Lug Wire Range Catalog Number 15–40 1 1 #14–#6 AWG Cu #12–#6 AWG Al TC1Q1 (Pkg. of 6) 13.90 50–100 1 1 #8–#1 AWG Cu #6–#1/0 AWG Al TA1Q1 (Pkg. of 6) 12.20 Line Side BQ, BQH, Load Side BQHF, BQE, 15–20 1 1 #14–#10 AWG Cu #12–#10 AWG Al BQF, BL, BLH, 25–35 1 1 #14–#6 AWG Cu #12–#6 AWG Al HBL, HBQ 40–50 1 1 #8–#6 AWG Cu #8–#4 AWG Al Switching Neutrals 55–70 1 1 #8–#4 AWG Cu #8–#2 AWG Al BG BLG 80–100 1 1 #4–#1/0 AWG Cu #2–#1/0 AWG Al 110–125 1 1 #2–#1/0 AWG Cu #1/0–#2/0 AWG Al Lugs are integral to Circuit Breaker Line Side (CQD, CQD6) & Load Side BQD, CQD BQD6, CQD6 NGG 1 #14–#6 AWG Cu #12–#6 AWG Al Integral 45–100 1 #8–#1 AWG Cu #6–#1/0 AWG Al Integral 15–40 1 #12–#6 AWG Al 50–100 1 110–125 1 15–40 15–125 — #14–#6 AWG Cu TC1Q1 (pkg. of 6) 13.90 #8–#1 AWG Cu #6–#1/0 AWG Al TA1Q1 (pkg. of 6) 12.20 #6–#1/0 AWG Cu #4–#2/0 AWG Al 3TA1GG20 (pkg. of 3) 12.00 NUT KEEPER PLATE 6 CIRCUIT BREAKERS Note: (A) Molded case circuit breakers having a rated ampacity of 125 amperes or less are to be connected with 60 or 75°C wire. Circuit breakers having a rated ampacity greater than 125 amperes shall only be cabled with 75°C cable unless otherwise indicated on the circuit breaker label. Exceptions to this rule are outlined in the 2002 National Electrical Code and Canadian Electrical Code. 6/70 Lug is steel. in package of six. on load side only. One nut keeper plate is required with each lug on the NGG breaker. Sold Use TNKG3 (Pkg. of 3) 16.00 Lug Information SELECTION Aluminum Body Lugs for Copper or Aluminum Wire For Use With Type(s) Circuit Breaker Ampere Rating QJ2, QJH2 QJ2H, HQJ2H 60–225 1 #6 AWG–300 kcmil (Cu) #4 AWG–300 kcmil (Al) 15–25 1 #14–#10 AWG (Cu) #12–#10 AWG (Al) SA1E025 30–100 1 #10–#1/0 (Cu or Al) LN1E100 110–125 1 #3-3/0 (Cu) #1-2/0 (Al) TA1E6125 30–60 1 #10–4 (Cu or Al) LD1E060 (Load Side) 3.60 70–100 1 #4–#1/0 (Cu or Al) LD1E100 (Load Side) 3.50 FXD6-A, FD6-A, HFD6, CFD6 HHFD6 70–250 1 #6 AWG–350 kcmil (Cu) #4 AWG–350 kcmil (Al) TA1FD350A 19.80 SJD6(A), SHJD6(A) SCJD6 65-200 1–2 #4 AWG–310 kcmil (Cu or Al) TA2J630 19.80 JXD2(A), JXD6(A), JD6(A), SJD6(A), HJD6(A), HHJXD6, HHJD6, SHJD6(A), CJD6, SCJD6 200–400 1–2 3/0–500 kcmil (Cu) 4/0–500 kcmil (Al) TA2J6500 28.00 LXD6(A), LD6(A), SLD6(A), HLD6(A), HHLXD6, HHLD6, SHLD6(A), CLD6, SCLD6 250–600 1–2 3/0–500 kcmil (Cu) 4/0–500 kcmil (Al) TA2J6500 28.00 500–600 1–2 250–500 kcmil (Cu or Al) TA2K500 64.00 700–800 1–3 1/0–500 kcmil (Cu or Al) 500–750 kcmil (Cu or Al) TA3K500 TA2N750 87.00 250–500 kcmil (Cu or Al) 2TA4P8500 3TA4P8500 522.00 754.00 250–500 kcmil (Cu or Al) 2TA4N8500 3TA4N8500 526.00 762.00 LMD6, LMXD6, HLMD6, HLMXD6, MD6, MXD6, SMD6, HMD6, HMXD6, SHMD6, CMD6, SCMD6 Catalog Number TA1Q300 (pkg of 3) 12.00 3.50 3.50 10.90 6 CED6 All 1 pole ED, HED Lug Wire Range ND6, NXD6, SND6, HND6, HNXD6, SHND6, CND6, SCND6 800–1200 PD6, HPD6, CPD6 PXD6, HPXD6, SPD6, SHPD6 1200–1600 1–5 300–600 kcmil (Cu or Al) TA5P600 286.00 PD6, PXD6, HPD6, HPXD6, SPD6, SHPD6, RD6, RXD6, HRD6, HRXD6, STD 1200–2000 1–6 300–600 kcmil (Cu or Al) TA6R600 302.00 Use TA2K500 or TA3K500 only. for 100% rated MD/ND frame breakers. Used 1–4 Contains Contains CIRCUIT BREAKERS All 2, 3 pole ED2, ED4, ED6, ED6 ETI, HED4, Cables Per Lug 2 connectors plus 1 NDTS end barrier. 3 connectors plus 1 NDTS end barrier. 6/71 Lug Information SELECTION Optional Mechanical Lugs For Use With Type QJ2, QJH2, QJ2H, HQJ2H ED, HED 2&3 pole HFD6, HHFD6, CFD6, F(X)D6-A J(X)D2(A), J(X)D6(A), HJD6(A), HHJD6, SHJD6(A), L(X)D6(A), HHLD6, SCD6, HLD6(A), SHLD6(A), CJD6, CLD6, SCJD6, SCLD6 Circuit Breaker Ampere Rating Cables Per Lug Lug Material Lug Wire Range Qty per Cat. # Catalog Number 60–225 1 Cu #6 AWG–250 kcmil (Cu) 1 TC1Q250 28.50 2–3 pole 30-125 1 Cu #10–#1/0 (Cu) 1 TC1ED6150 30.00 70–250 1 Cu #6 AWG–350 kcmil (Cu) 1 TC1FD350 31.00 1 1–2 Cu 3/0–600 kcmil (Cu) 3/0–500 kcmil (Cu) 1 1 TC1J6600 TC2J6500 69.00 68.00 500–750 kcmil (Al) 500–600 kcmil (Cu) 1 TA1L6750 68.00 SMD6, M(X)D6, HM(X)D6, HMD6, CMD6, SCMD6, SND6, N(X)D6, HN(X)D6, SHND6, CND6, SCND6 500–600 800–1200 1–3 Al R(X)D6, HR(X)D6 P(X)D6, HP(X)D6, CPD6, SPD6, SHPD6 1600–2000 1–5 Cu #1 AWG–500 kcmil (Cu) #1 AWG–350 kcmil (Cu) 500–750 kcmil (Cu) 500–750 kcmil (Al) 500–750 kcmil (Cu) 500–750 kcmil (Al) 300–600 kcmil (Cu) 1 1 2 3 2 3 1 TC2K500 TC3K350 2TA2N8750 3TA2N8750 2TA3N8750 3TA3N8750 TC5R600 107.00 135.00 327.00 459.00 517.00 744.00 381.00 1200–1600 1–4 Al 600–750 kcmil (Cu/Al) 1 TA4P750 216.00 250–600 700–800 1 1 Al 1–2 1–3 Cu Cu 1–2 Al Compression Lugs For Circuit Breaker Types Lugs (contains indicated number of lugs and necessary hardware per kit) ED2, ED4, ED6, HED4, CED4 Ampere Rating 15–125 QJ2, QJH2, QJ2-H 125–225 F(X)D6-A, HF(X)D6, HHF(X)D6, CFD6 125–250 JXD2-A, J(X)D6-A, HJ(X)D6-A, HHJ(X)D6-A, CJD6, SJD6-A, SHJD6-A, 200–600 SCJD6, L(X)D6-A, HL(X)D6-A, CLD6, SLD6-A, SHLD6-A, SCLD6 Kits (contain lugs and hardware for complete line or load end of 2 or 3 pole breaker) 500–800 N(X)D6, HN(X)D6, CND6, SND6, SHND6, SCND6 900–1200 6 M(X)D6, HM(X)D6, CMD6, SMD6, SHMD6, SCMD6 CIRCUIT BREAKERS Used for 100% rated JD/LD frame circuit breakers. 6/72 Poles Lugs Per Kit Lug Wire Size Catalog Number 1, 2, 3 1 #2/0 2, 3 2, 3 1 1 350 kcmil 350 kcmil CCE125 CCQ225 CCF250 24.00 45.50 45.50 2, 3 1 500 kcmil CCL600 134.00 2 3 2 3 6 9 8 12 500 kcmil CCM800K2 CCM800K3 CCN1200K2 CCN1200K3 649.00 945.00 851.00 1246.00 Molded Case Circuit Breakers SELECTION / GENERAL Modifications Modifications 50°C Ambient Calibration — Not UL listed and not available for solid state, 100% rated breakers or 400HZ calibrated breakers. For BL Type Circuit Breakers — Add suffix ‘M’ to catalog number (Example: B120M) For BQ, QJ2, and ED Frame Circuit Breakers — Replace ‘B’ in catalog number with ‘M’ (Example: BQ3M060, QJ23M200, ED63M060) For FD, JD, LD, LMD, MD, ND, PD, and RD Frame Circuit Breakers Non-Interchangeable Trip (3–pole only) — Replace ‘B’ in catalog number with ‘M’ (Example: FXD63M225, JXD63M400) Interchangeable Trip (trip unit only, 3–pole only) — Replace ‘T’ in catalog number with ‘W’ (Example: FD63W200, JD63W400) 400 HZ Calibration UL Listed (5KA IR) For BQ, BL, and QJ Type Circuit Breakers (200A max.) — Add suffix ‘Y’ to catalog number Not UL Listed For all other Circuit Breakers — Add suffix ‘Y’ to catalog number Fungus Proofing — In accordance with MIL-T-152. All BQD, CQD, NGG, ED, FD, JD, LD, LMD, MD, ND, PD, and RD, Frame Circuit Breakers are inherently fungus resistant and do not require special treatment. Fungus proofing in accordance with MIL-T-152 For BL, and BQ Type Circuit Breakers — Order must be placed directly with the factory by the sales office. For all other Circuit Breaker Types — Order must be placed directly with the factory by the sales office. Certificate of Compliance Certificate of compliance testing must be performed on the actual device being shipped. The certificate cannot be provided after initial shipment. Order for devices with COC requirement must be placed directly with the factory by the sales office. UL 489 Supplement SB Naval Use Breakers Ordering Information Breakers tested to UL 489 Supplement SB are qualified for use on non combat and auxiliary naval vessels. For “NAVAL” label, order must be placed directly with the factory by Siemens Sales Office. 6 A variety of internal and external accessories, as well as modifications, are available to adapt Siemens circuit breakers to special installation requirements. UL listed internal accessories for 100 through 2000A circuit breakers are field-addable. Internal accessories fine tune an electrical distribution system, allowing control of the circuit breakers to meet special application requirements. For example, emergency situations may dictate tripping critically placed circuit breakers quickly. Shunt trips accomplish this conveniently and efficiently. Or, when voltage drops are a concern, undervoltage trips automatically open the circuit breaker at a predetermined voltage level. A wide range of external operating and mounting accessories is also available. For example, face, shallow, and back mounting plates are ideal for tailoring BQ circuit breakers to OEM applications. A complete line of operating handles and handle-blocking devices meet switchboard, enclosure and safety needs. Plug-in mounting assemblies, which simplify switchboard mounting of circuit breakers and permit breaker removal without disconnecting bus or cable connections, are available. Supplement SB testing comprises two sets of vibration tests. The first is to find mechanical resonances in the product and to subject the breaker to extreme testing at each resonant frequency. The second is a swept frequency test, in which the frequency of excitation is changed in intervals of 1Hz, and held at each frequency for five minutes. The excitation frequencies run from 4 to 33Hz, and the test is conducted in each of the three orthogonal axes of the breaker. During these tests, the breaker must not trip from the closed position, nor may the contacts touch from the open position. Calibration and insulation resistance are also verified during the test. For detailed information, refer to UL 489, Supplement SB. Types ED2, ED4, ED6, HED4 CED6 FD6, FXD6, HFD6, HFXD6 CFD6 JXD2, JD6, JXD6, LXD6, LD6, HJD6, HJXD6, HLD6, HLXD6 HHJD6, HHJXD6, HHLD6, HHLXD6 CJD6, CLD6 MD6, MXD6, HMD6, HMXD6, CMD6, ND6, NXD6, HND6, HNXD6, CND6 PD6, PXD6, HPD6, HPXD6, CPD6, RD6, RXD6, HRD6, HRXD6 SBA400, SBS400, SBA800, SBS800, SBA1200, SBS1200, SBA1600, SBS1600, SBA2000, SBS2000 UL File E10848, Vol 4, Sec 11 E10848, Vol 4, Sec 13 E10848, Vol 4, Sec 17 E10848, Vol 4, Sec 18 E10848, Vol 4, Sec 8 E10848, Vol 4, Sec 20 E10848, Vol 4, Sec 14 E10848, Vol 4, Sec 15 E10848, Vol 4, Sec 19 E9896, Vol 15, Sec 1 6/73 CIRCUIT BREAKERS Siemens’ molded case breakers from the ED frame through the 2000 Amp SB frame can be labeled “Naval” in compliance with Supplement SB. Molded Case Circuit Breakers GENERAL / SELECTION Internal Accessories Feature Combinations The available feature combinations are shown in the chart below. For applications requiring combinations of features not listed in this chart, consult the sales office for availability. Breakers Avail. On ST/ Modules/ Breaker ST/ ST/ AUX/ UVT/ Breaker Poles ST AUX ALSW ALSW UVT AUX UVT/ UVT/ ST/ ALSW ALSW AUX/ ALSW AUX Elect. Bell Ground Grd fault ALSW Alarm fault w/Bell QP, BQ, BL 1 1, 2, 3 1 — — — — — 1 — — — — — BQD, CQD, NGG 1 2, 3 1 1/1 — — — — 1 1/1 1 — — — QJ 1 3 1 1/1 — — — — 2 — — — — — All ED, EF 1 1, 2, 3 1 1/1 1/1 1/1/1 1 1/1, 1/2 1/1 1/1/1 1, 2 1/1, 2/1 1 — 1 1 All FD, FF 2 2, 3 1 — — — 1 1 — — 1, 2 1/1 1 — — — All JD, LD, LMD 2 2,3 1 1 — — 1 1/1, 1/2 — — 1, 2 — 1, 2 — — — 1 3 1 1 — — 1 1/1, 1/2 — — 1, 2 — 1, 2 — — — 2 2,3 1 1/1 — — 1 1/1, 1/2 — — 1, 2 1/1, 2/1 1, 2 — — — — 1 1 — — SJD6, SHJD6, SCJD6, SLD6, SHLD6, SCLD6 All MD, ND, PD, RD Including Electronic trip 1 NC / 1 NO, 2 NC / 2 NO, STD 6 3 1 — — — 1 — — — 3 NC / 3 NO, 4 NC / 4 NO, 5 NC / 5 NO Shunt Trip (ST) 6 One or all critical circuit breakers may be tripped from a distant control point by use of a shunt trip device. A shunt trip operates through an auxiliary switch contact; when the breaker opens, current is not maintained on the shunt trip coil. Undervoltage Trip (UVT) CIRCUIT BREAKERS When voltage drops to a value below 35% of the nominal coil rating, the undervoltage trip device automatically opens the breaker. The operation is instantaneous, and the circuit breaker cannot be reclosed until the voltage returns to 85% of line voltage. The undervoltage trip, which is continuously energized, must be energized before the circuit breaker can be closed. Auxiliary Switch (AUX) For applications requiring remote “on” or “off” indication (or electrical interlocking), auxiliary switches are available. Each switch comprises an “A” (open when circuit breaker is open) and a “B” (closed when circuit breaker is open) contact with a common connection. (Form C) For ED Frames Factory assembled only mechanical interlock is installed, no accessory module can be installed in the right pocket. If 6/74 For FD Frames If mechanical interlock is installed, no accessory module can be installed. If mechanical interlock is installed, no accessory module can be installed in the left pocket. Alarm Switch (ALSW) The alarm switch contact is closed when the circuit breaker is opened automatically by an overload, short circuit, shunt trip or undervoltage trip. The alarm switch contact is open when the circuit breaker is reset. For JD and LD Frames One module per column. Molded Case Circuit Breakers SELECTION External Accessories Handle Ties Provide simultaneous switching of 2 adjacent handles. Do not provide common trip. For Use With Breaker Frame(s) Catalog Number Standard Package Wt Lb/ Std Pkg BQ, BQH, HBQ, B6, BLH, HBL (2 Pole) QTH3 50 BQXD, BQ, BQH, HBQ, BL, BLH, HBL ECQLD3 10 1 One pole BL, BLF, BE, BAF ECPLD1 10 1 Two-pole BL, BLF nad BE ECPLD2 10 1 All QJ HL9419 10 1 All BQD, CQD BQDPLD 1 1 All ED ED2HPL 1 1 All FD FD6PL1 1 1 All JD, LD, LMD JD6HPL 1 1 All MD, ND, PD, RD MN6PLD 1 1 STD STDPLD ■ 1 1 1 ⁄4 Padlocking Devices For locking breaker in “OFF” position. ECQTH3 ⁄4 ⁄4 ⁄4 ⁄4 ⁄8 ⁄4 ⁄4 ⁄4 ⁄4 FD Padlocking Device FD6PLI Filler Plates BQ, BQH, HBQ, BL, BLH, HBL QF3-UL 1 Padlocking Device ECQLD3 1 ⁄4 Handle Blocking Devices For holding breaker in “ON” or “OFF” position. Not a lockout/tagout device. BL, BLH, HBL, BQXD, BQ, BQH, HBQ QL1 25 1 QJ2, QJH2, QJ2H, HQJ2H QJHS1 25 1 All BQD, CQD, NGG BQDHBD 1 1 All ED E2HBL 1 1 All FD FD6HB1 1 1 All JD, LD, LMD JD6HBL 1 1 All MD, ND, PD, RD MN6BL 1 1 ⁄4 ⁄4 Filler Plate QF3-UL ⁄4 ⁄2 ⁄2 6 ⁄2 Handle Extensions All MD, ND, PD, RD EX11 1 2 STD EXSTD■ — —.00 Replacement Terminal Cover NGG RTCG3 10 1 ⁄4 FD Handle Blocking Device FD6HB1 Handle Blocking Device ECQL1 Handle Extension EX11 ■ Built to order. Allow 2–3 weeks for delivery. Sold only in standard package quantities. 6/75 CIRCUIT BREAKERS For replacement. One extension shipped with breaker. Molded Case Circuit Breakers SELECTION External Accessories Mounting Clips For Use With Breaker Frame(s) Number of Poles Catalog Number BQ, BQH 1 MB120 Standard Package 20 Wt Lb Std Pkg 1 ⁄4 MB120 Face Mounting Plates 10 10 10 BQ, BQH, BQXD 1 2 3 FP9508 FP9555 FP9556 CQD, CQD6 1 2 3 CQDFMB1 CQDFMB2■ CQDFMB3■ BQ-GFCI 1 FP9558■ NGG 1 2 3 FMPG1 FMPG2 FMPG3 1 ⁄2 1 11⁄2 1 1 1 1 ⁄4 ⁄4 ⁄4 1 1 10 Face Mounting Plates FP9558 FP9508 FP9555 FP9556 1 1 1 1 1 ⁄4 ⁄4 1 ⁄4 1 Shallow Mounting Brackets BQ, BQH SMB6 30 11⁄2 2 3 4 BR2 BR3 BR4 10 10 10 1 1 E2BMB 1 1 1–6 Back Mounting Plates BQ, BQH, BQXD ED2, ED4, ED6, HED4 SMB6 (6 shown) ⁄4 Mounting Screw Kits 6 CQD, CQD6 CQDSMK 1 MSE6 MSE6100 1 100 1 All ED (CED6 requires 2 kits) NNG MSKG2 1 1 1 1 All QJ MSQJ All FD (CFD6 requires 2 kits) MSF6 MSF650 All JD, LD 11⁄4 ⁄4 1 MSJ6 1 1 All LMD MSLMD 1 1 All MD, ND, MSMN 1 1 All PD, RD MSPR6 1 2 ⁄4 1 ⁄4 ⁄4 ⁄4 CIRCUIT BREAKERS Mounting Screw Kit MSE6 “MI” Mechanical Interlocks For Use With Breaker Type(s) Panel Mounted Plug-in Mounted BQ — QML12 10 1 All QJ CSO — 1 1 All FD MI5444 MI5444 Complete with two breakers — All JD, LD MI5413 — 1 1 All LMD MI5406 — 1 1 All MD MI5404 ■ — 1 3 All ND MI5404 ■ — 1 3 All PD, RD MI5405▲ MI5405▲ — — STD STDMIF32▲ — — — 6/76 Back Mounting Plate BR2 ⁄4 1 1 50 ■ Built to order. Allow 2–3 weeks for delivery. ▲ Built to order. Allow 6–8 weeks for delivery. Note: CSO = Consult Sales Office Kit consists of 4 screws and washers. Consists of 1 screw and washers (order 100). Consists of 1 screw and washers (order 50). With mechanical interlock in place, no accessory can be QML12 ⁄4 1 ⁄4 1 ⁄4 Standard Package Wt Lb Std Pkg ⁄4 installed into circuit breaker right pole. of the mechanical interlock will prevent accessory installation in the left pole. Sold only in standard package quantities. Multiply List Price Each times package quantity for full price. Addition Mechanical Interlock MI5444 Each package contains 5 strips of 6 each. Each strip can be broken at perforations for 1, 2 or 3-pole use. Mechanical interlock is not designed for use within Siemens panelboards. Molded Case Circuit Breakers SELECTION External Accessories Rotary Door Mounted Operating Handles Types 1, 3, 3R , 12, 4 4X For Use With Breaker Frames Complete Mechanism Handle Only Breaker Operator Shaft Only Catalog Number Standard Depth Variable Depth ED CRHOESD CRHOEVD FD CRHOFSD CRHOFVD JD, LD CRHOJSD CRHOJVD LMD CRHOLMSD CRHOLMVD MD, ND PD, RD RHONSD RHONVD Catalog Number Catalog Number RHOEBO 68.00 RHOFBO117.00 CRHOH RHOJBO RHOLMBO RHONBO214.00 RHOH Length Catalog (inches) Number 2 RHOSSD 28.00 12 RHOSVD 28.00 16 RHOSXD 28.00 3 12 24 RHONSSD▲ 86.00 RHONSVD 86.00 RHONSXD 114.00 CRHOH RHOH For 3 or 3R, order shaft and breaker operator as shown, and handle RHOH. For 4 & 4X, order handle RHOH4. Rotary Door Mounted Operating Handles Types 1 & 12 Standard Depth Variable Depth Catalog Number Catalog Number CQD, NGG — RHOCQVD 130.00 ED D11CEU1 D11CEU2 163.00 FD D11CFU1▲ D11CFU2 214.00 JD, LD, LMD — D11CJU2 303.00 For Use With Breaker Frames D11CEU2 Through Door Mounted Operating Handles Types 1 & 12 Variable Depth For Use With Breaker Frames Catalog Number Catalog Number CQD, NGG FMHOS — QJ OH9498 ■ VH9499 195.00 ED E2RH1 E2RHV9 197.00 FD F6RH1 F6RHV9 197.00 Standard Depth F6RH1 6 Rotary Door Mounted Operating Handles Standard Depth Type Catalog Number Right Hand Catalog Number Left Hand 2 point latch DKR2 DKL2■ 302.00 3 point latch DKR3 DKL3■ 337.00 CIRCUIT BREAKERS Door Latch Kits Variable Depth F6RHV9 ■ Built to order. Allow 3–4 weeks for delivery. ▲ Built to order. Allow 7–9 weeks for delivery. For use on 3-pole ED frame only. 6/77 Molded Case Circuit Breakers SELECTION External Accessories Max-Flex™, Flange Mounted Variable Depth Operators Complete Kit Handle Only Breaker Operator 36˝ Cable Catalog Number Catalog Number Catalog Number Catalog Number Frames NEMA Type ED 1, 3(R), 12 FHOE036 563.00 FHOH 282.00 4(X) — FHOH4386.00 1, 3(R), 12 FHOF036 625.00 FHOH 282.00 4(X) — FHOH4386.00 1, 3(R), 12 FHOJ036 664.00 FHOH 282.00 4(X) — FHOH4386.00 1, 3(R), 12 FHOLM036 FHOH 282.00 4(X) — FHOH4386.00 FHON048 857.00 FHOHN 421.00 FD JD, LD, SJD, SLD LMD 1, 3(R), MD, ND, 12 PD, RD, SMD, SND, 4(X) SPD FHOEBO Cable Handle FHOEC036 Breaker Operator — FHOFBO FHOFC036 Max Flex ™ FHOJBO FHOJC036 FHOLMBO FHOJC036 FHONBO FHONC048 FHOHN4563.00 Max-Flex™ handles are available with solid black handles instead of the customary “red for on” flange handle. These are preferred for use in IECmarkets, where red handles have specific meaning. Order componenets separately, apppending the letter “i” to the catalog number (e.g. FHOHI). Alternate Length Cable Only ED Inches 048 060 072 084 096 120 144 FD Catalog Number JD/LD/LMD Catalog Number FHOEC048 162.00 FHOEC060 181.00 FHOEC072 200.00 FHOEC084▲223.00 FHOEC096 246.00 FHOEC120▲336.00 FHOEC144▲373.00 MD/ND/PD/RD Catalog Number FHOFC048 172.00 FHOFC060 194.00 FHOFC072 214.00 FHOFC084▲ 236.00 FHOFC096 256.00 FHOFC120 336.00 FHOFC144▲ 373.00 Catalog Number FHOJC048 187.00 FHOJC060 214.00 FHOJC072 246.00 FHOJC084▲ 248.00 FHOJC096 336.0 FHOJC120▲ 365.0 FHOJC144▲ 379.00 FHONC048 212. FHONC060 46.0 FHONC072 286. FHONC084▲ FHONC096 FHONC120▲ FHONC144▲ 6 Handle Auxiliary Switch For use with Max-Flex and Rotary Door operators (FHOH and RHOH). 1 NO and 1 NC contact. For Use With Catalog Number ED, JD, LD, LMD, ND, PD, RD, SD, Max Flex HAS1 167.00 CIRCUIT BREAKERS Fixed Depth Flange Mounting Frames ED Minimum Enclosure Depth 6.44 FD 6.44 Left Hand Mount Right Hand Mount NEMA Type Catalog Number Catalog Number 1, 3R, 12 FDFBEL▲ 246.00 FDFBER▲ 246.00 4, 4X FDFBEL4▲ 329.00 FDFBER4▲ 329.00 1, 3R, 12 FDFBFL▲ 263.00 FDFBFR▲ 263.00 4, 4X FDFBFL4▲ 349.00 FDFBFR4▲ 349.00 Max-Flex™ handles are available with solid black handles instead of the customary “Red for On” flange handle. These are preferred for use in IECmarkets, where red handles have specific meaning. Order componenets separately, apppending the letter “i” to the catalog number (e.g. FHOHI). FDFBFR ▲ Built to order. Allow 7–9 weeks for delivery. For 1- or 2-pole breaker order FHOED036 complete kit or FHOEDBO breaker operator only. 6/78 48 inch cable is standard length for M through R frame Max-Flex operators. Molded Case Circuit Breakers SELECTION External Accessories Telemand® Motor Operator Breaker Frame AC Voltage Hinged to Open Down List Price $ ED except CED 120 MOE6120 3018.00 240 MOE6240 ▲ 3284.00 ED motor operator opens downward. Breaker Frame DC Voltage Hinged to Open Right AC Voltage Hinged to Open Right FD 24 48 125 MOF6024DC▲ MOF6048DC▲ MOF6125DC▲ 120 240 3— MOF6120 MOF6240 —296.00 3083.00 3465.00 JD, LD 24 48 125 MOJ6024DC▲ MOJ6048DC▲ MOJ6125DC▲ 120 240 — MOJ6120 MOJ6240 — 3989.00 3989.00 LMD 24 48 125 MOLMD6024DC▲ MOLMD6048DC▲ MOLMD6125DC▲ 120 240 — MOLMD6120 MOLMD6240 — 3989.00 3989.00 MD, ND, PD, RD — — — — 120 240 MOMN6120 MOMN6240 4505.00 4505.00 To order FD through RD motor operators with Left side hinges, add “L” to catalog number (e.g. MOF6120L). List prices are the same.▲ FD, JD, LD, LMD, MD, ND, PD, RD Frames Dimensions Frame B C D E ED A 7.04 4.31 — 4.31 13.84 F 8.84 FD 9.50 4.55 1.60 6.84 9.70 7.58 JD, LD, LMD 11.00 7.50 0.79 8.34 9.85 7.74 MD, ND, PD, RD 16.00 9.00 — 9.83 13.13 10.13 Operating Currents MOE6120 MOE6240 10.25 5.2 MOF6120/L MOF6240/L Off Running (Amps) Time (msec) In-Rush (Amps) Running (Amps) Time (msec) Reset (Amps) 2.3 1.1 550 500 10.0 5.0 2.3 1.0 400 330 2.3 1.1 10.0 4.7 5.5 2.5 200 200 10.0 4.7 5.5 2.5 175 185 5.5 2.5 MOLMD6120/L 15.2 6.0 210 15.2 6.0 185 6.0 MOJ6120/L MOJ6240/L 15.2 5.0 6.0 2.5 210 217 15.2 5.0 6.0 2.5 185 185 6.0 2.5 MOMN6120/L MOMN6240/L 22.7 12.6 13.9 4.6 240 260 22.7 12.6 13.9 4.6 210 230 13.9 12.6 Front View CIRCUIT BREAKERS In-Rush (Amps) 6 On Catalog Number Bottom View For inches / millimeters conversion, see Application Data section. ▲ Built to order. Allow 7–9 weeks for delivery. 6/79 Molded Case Circuit Breakers SELECTION / DIMENSIONS External Accessories Plug-In Mounting Assemblies, Including Base and Tulip Assemblies Catalog Number PC2658 158.00 2 PC2637▲ 98.00 PC2638▲98.00 3 PC2657 158.00 PC2658 158.00 2 PC4753▲237.00 PC4753▲237.00 3 PC4754 309.00 PC4754 309.00 2 PC4753▲237.00 PC4753▲237.00 3 PC4754 309.00 PC4754 309.00 All JD except CJD 2 PC5777▲318.00 PC5777▲318.00 3 PC5778 527.00 PC5778 527.00 All FD except CFD CFD PL2617 PL4762 PL4763 PL5796 Kit CJD, SCJD 3 PCCJD 570.00 PCCJD 570.00 All LD except CLD 2 PC5660▲596.00 PC5660▲596.00 3 PC5661 835.00 PC5661 835.00 Kit CLD, SCLD 3 PCCLD 769.00 PCCLD 769.00 2 PC5662▲1098.00 PC5662▲1098.00 3 PC56631341.00 PC56631341.00 2 PC5664▲1516.00 PC5664▲1516.00 3 PC5666 1748.00 PC5666 1748.00 All ND PL5696 PL5797 PL9698 PL9699 Tulip Assemblies Separately 2 Pole 3 Pole For Frame Catalog Number Catalog Number ED TCE2▲ TCE3▲ 184.00 FD TCF2▲ TCF3▲ 275.00 JD TCJ2▲ TCJ3▲ 309.00 LD TCL2▲ TCL3▲ 366.00 MD TCM2▲ TCM3▲ 408.00 ND TCN2▲ TCN3▲ 428.00 RS4755 RS4756 ➝ 6 Rear-Connecting Studs For Use With Breaker Frames Ampere Rating Description Extension Behind Breaker (inches) Line Side Catalog Number Catalog Number CIRCUIT BREAKERS 2.38 2.38 4.88 4.88 RS2643▲ — RS2641▲ — 40.50 All ED Line Side (Short) Load Side (Short) Line Side (Long) Load Side (Long) 47.50 — 40.50 RS2644▲40.50 — 47.50 RS2642▲47.50 All FD 250 250 Short Long 3.12 7.06 RS4756▲ RS4755▲ 58.00 91.00 RS4756▲58.00 RS4755▲91.00 All JD 400 400 Short Long 5.85 11.20 RS5774▲ RS5773▲ 161.00 161.00 RS5774▲161.00 RS5773▲161.00 All LD 600 600 Short Long 5.85 11.20 RS5784▲ RS5783▲ 158.00 181.00 RS5784▲192.00 RS5783▲181.00 CJD, SCJD CLD, SCLD Add required shield kit. LM(X)D6, HLM(X)D6 800 Short Long 5.85 11.20 RS5788▲ RS5787▲ 280.00 297.00 RS5788▲280.00 RS5787▲297.00 All MD, ND 1200 1200 Short Long 5.50 8.00 RS5786▲ RS5785▲ 231.00 291.00 RS5786▲231.00 RS5785▲291.00 — ▲ Built to order. Allow 7–9 weeks for delivery. Furnished at no extra charge when ordered with plug-in mounting assembly. Each piece catalog number consists of (1) mounting block assembly and required tulip assemblies (2) for 2-pole, (3) for 3-pole Circuit Breaker With Rear-Connecting Studs Load Side 100 100 100 100 6/80 Tulip Assemblies Switchboard Mounting Plate ➝ All MD PL5797 ➝ CED PL2616 ➝ ➝ PC2638▲98.00 PC2657 158.00 ➝ PC2637▲ 98.00 3 ➝ 2 ➝ All ED except CED Catalog Number ➝ Poles Base Steel Switchboard Mounting Plate Catalog Number ➝ For Use With Breaker Frames Load Side ➝ Line Side CLRSJL3 45.50 For vertical bus mounting — for horizontal, substitute PC5665 for PC5664 and PC5667 for PC5666. Price includes one current stud, insulating tube, stud nuts and terminal shields, when required. For proper electrical clearance, studs must alternate between short and long stud lengths on circuit breaker poles (e.g. SLSLSL or LSLSLS). Enclosed Circuit Breakers GENERAL Enclosures Type 3R 6 Type 1 ENCLOSED CIRCUIT BREAKERS Types 5, 12 Type 1 — A general indoor, sheet-steel enclosure for use in normal atmospheres. Type 3R — An outdoor, sheet-steel enclosure providing protection against driving rain, sleet or snow. Listed as service entrance equipment. Types 5, 12 — A special-industry, sheetsteel enclosure for use in atmospheres containing particles of lint, dust, dirt, sawdust and other foreign matter. 6/81 Enclosed Circuit Breakers SELECTION/ DIMENSIONS Enclosures — Type 1 Dimensions Figure 1 Figure 3 Figure 2 Type 1 Fig. Breaker No. Type 1 BQ, BQH, HBQ 2 ED2, ED4, ED6, HED4, HED6 Number Maximum of Current Catalog Poles Rating Number 3 2–3 0 0 0 Weight Lb./Ship. Package K.O. Dimensions Dimensions (inches) A 100 EB3100S 0 32 171⁄8 100 E2N1S E2N1F 008 008 1623⁄32 171⁄2 CED6N1S CED6N1F 014 014 B C 0 0 71⁄8 D E 0 41⁄2 6 Plcs. 2 Plcs. F G H 15⁄16 — — 7 ⁄8, 11⁄8, 13⁄8, 7 ⁄8, 11⁄8, 13⁄8, 43⁄4 141⁄8 071⁄2 081⁄2 051⁄16 051⁄16 1345⁄64 1345⁄64 051⁄4 051⁄4 1 1 2115⁄32 221⁄4 0719⁄32 081⁄2 057⁄64 057⁄64 181⁄4 181⁄4 051⁄4 051⁄4 1 1 13⁄4, 2 13⁄4, 2 ED4, ED6, HED4, HED6, 2–3 CED6 2 FXD6, FD6, FXD6-A, FD6-A, HFD6, HFXD6, HHFD6, CFD6 2–3 0250 F6N1S F6N1F 033 3813⁄32 1115⁄32 051⁄16 33 08 133⁄64 11⁄8, 13⁄8, 13⁄4, 2, 21⁄2, 3 11⁄8, 13⁄8, 13⁄4, 20, 21⁄2, 3 3 JXD2(A), JD6(A), JXD6(A), HJD6(A), HJXD6(A), HHJD6, HHJXD6, SJD6(A), SHJD6(A), SXD6H 2–3 0400 J6N1 120 4013⁄64 2227⁄64 1045⁄64 36 181⁄4 25⁄64 — — 3 LD6(A), LXD6(A), HLD6(A), HLXD6(A), HHLD6, HHLXD6, 2–3 SLD6(A), SHLD6(A), SCJD6, SCLD6, LXD6H 0600 LD6N1 (L6N1 ) 101 46 2227⁄64 1045⁄64 42 181⁄4 25⁄64 — — 3 MD6, MXD6, SMD6, HMD6, HMXD6, SHMD6, ND6, NXD6, 2–3 SND6, HND6, HNXD6, SHND6, CMD6, SCMD6, CND6, SCND6 1200 MND61 132 60 2227⁄64 10 557⁄8 181⁄4 25⁄64 — — — PD6, PXD6, HPD6, HPXD6, CPD6, RD6, SPD6, SHPD6, RXD6, HRD6, HRXD6 2000 PRD6N1 — 90 32 28 — — — — — 6 2 ENCLOSED CIRCUIT BREAKERS 3 125 For inches / millimeters conversion, see page 15/6. Neutral Surface Neutral mounted, indoor. If flush mounting is required, replace suffix “S” in catalog number with suffix “F”. Also, if outdoor model required, use prefix “W” instead of “E”. Does not include circuit breaker. Order circuit breaker separately. 6/82 not included. Order as separate item from table on next page. included in enclosure. Surface mounted, indoor. If outdoor model is required, use prefix “W” instead of “E”. Not available in flush (“F”) model. Use for 110-125 ampere ED4, ED6, HED4 or HED6 circuit breakers. Will not accept breaker with shunt trip. Will not accept 2-pole GFCI or breaker with shunt trip. Built to order. Consult sales office for factory lead time and prices. Enclosed Circuit Breakers SELECTION / DIMENSIONS Enclosures — Type 1 Dimensions Figure 4 Figure Number Breaker Type 4 QJ2, QJH2, QH2-H, QJ, QJH Number of Poles 2–3 Maximum Current Rating 225 Catalog Number EB3225S EB3225F Weight Lb./Ship. Dimensions (inches) Package A B C D E 15 27 27 101⁄8 27 101⁄8 51⁄4 101⁄8 281⁄8 111⁄4 51⁄4 F G H 213⁄16 213⁄8 23⁄8 213⁄16 213⁄8 23⁄8 J K L 3 3 20 20 51⁄16 23⁄4 51⁄16 23⁄4 M N P 23⁄4 23⁄4 41⁄2 41⁄2 Neutrals W53045 Neutral Cable Capacity and Wire Range (1 pc.) #14–2 Cu/Al Grd. Lug (1 pc.) #14–8 Cu/Al (1 pc.) #6–350 kcmil Grd. Lug (1 pc.) #14–2/0 Cu/Al (1 pc.) #1/0–750 kcmil Cu/Al or (2 pcs.) #1/0–300 kcmil Cu/Al Grd. Lug (1 pc.) #6–250 kcmil Cu/Al List Price $ 246. F6N1(S)(F) N250 (NFD) 259. J6N1 W60992 (NJD) LD6N1 W60993 (NLD) (2 pcs.) #1/0–600 kcmil Grd. Lug (1 pc.) #6–250 kcmil Cu/Al 393. MND61 W63623 (NMND) (8 pcs.) 250 kcmil–500 kcmil Cu/Al Grd. Lug (1 pc.) #6–300 kcmil Cu/Al 802. PRD6N1 N2000 (6 pcs.) #3/0–750 kcmil Cu/Al Grd. Lug (2 pcs.) #3/0–750 Cu/Al 259. 6 E2N1(S)(F) CED6N1(S)(F) Neutral Catalog Number ENCLOSED CIRCUIT BREAKERS Enclosure Catalog Number 1770. For inches / millimeters conversion, see page 15/6. Does not include circuit breaker. Order circuit breaker separately. included in enclosure. Neutral Built to order. Consult sales office for factory lead time and prices. 6/83 Enclosed Circuit Breakers SELECTION / DIMENSIONS Enclosures — Type 3R Dimensions Figure 2 Figure 1 Figure 3 Type 3R Figure Breaker Number Type Number Maximum of Current Catalog Poles Rating Number 2 BQ, BQH, HBQ 3 3 5 ED2, ED4, ED6, HED4, HED6 2–3 Weight Lb./Ship. Package 0050 0100 WB3100 00 0 E2N3R 0 100 Dimensions (inches) A 9 171⁄8 12 179⁄16 016 22 ⁄64 B C 0 0 D E 45⁄16 141⁄8 51⁄4 1239⁄64 07 ⁄4 05 ⁄4 0 73⁄8 71⁄4 0 0 F 41⁄2 11⁄8 51⁄4 1 17 ⁄8 05 ⁄4 0 G 0 H 311⁄16 — 3 — 1 03 — 0 6 CED6 2–3 0125 CED6N3R 1 FXD6, FD6, FXD6-A, FD6-A, HFD6, HFXD6, HHFD6, CFD6 2–3 0250 F6N3R 045 381⁄8 141⁄16 073⁄4 339⁄32 08 513⁄16 131⁄2 513⁄16 1 JXD2(A), JD6(A), JXD6(A), HJD6(A), HJXD6(A), HHJD6, HHJXD6, SJD6(A), SHJD6(A), SXD6H 2–3 0400 J6N3R 126 4063⁄64 263⁄4 1123⁄32 353⁄4 181⁄4 21⁄8 241⁄2 11⁄8 1 LD6(A), LXD6(A), LXD6H, HLD6(A), HLXD6(A), HHLD6, HHLXD6, CJD6, CLD6, SCJD6(A), SLD6(A), SHLD6(A) 2–3 0 600 LD6N3R (L6N3R) 137 4563⁄64 263⁄4 1123⁄32 403⁄4 181⁄4 21⁄8 241⁄2 11⁄8 1 MD6, MXD6, SMD6, HMD6, HMXD6, SHMD6, ND6, NXD6, SND6, HND6, HNXD6, 2–3 SHND6, CMD6, SCMD6, CND6, SCND6 1200 MND63 210 619⁄64 263⁄4 1123⁄32 5717⁄32 181⁄4 21⁄8 245⁄8 11⁄16 ENCLOSED CIRCUIT BREAKERS 5 For inches / millimeters conversion, see page 15/6. Neutral Does Neutral not include circuit breaker. Order circuit breaker separately. 6/84 21 not included. Order as separate item from table on next page. included in enclosure. Will not accept breaker with shunt trip. 1 1 3 1 Enclosed Circuit Breakers SELECTION / DIMENSIONS Enclosures — Type 3R Dimensions Figure 4 Figure Breaker Number Type Number Maximum of Current Poles Rating QJ2, QJH2, 2 QJ2-H, 3 QJ, QJH 6 Figure 5 225 225 Figure 6 Catalog Number Weight Lb./Ship. Package A B C D E F G H J K L M WB2225 WB3225 17 17 27 27 5 55⁄8 0711⁄16 103⁄8 21⁄4 21⁄4 2 2 27⁄8 27⁄8 20 20 41⁄8 41⁄8 35⁄8 51⁄8 23⁄4 23⁄4 23⁄4 23⁄4 — 41⁄2 Dimensions (inches) Neutrals Neutral Cable Capacity and Wire Range List Price $ W53045 (1 pc.) #14–2 Cu/Al Grd. Lug (1 pc.) #14–8 Cu/Al 246. F6N3R N250 (NFD) (1 pc.) #6–350 kcmil Grd. Lug (1 pc.) #14–2/0 Cu/Al 259. JD6N3R W60992 (NJD) (1 pc.) #1/0–750 kcmil Cu/Al or (2 pcs.) #1/0–300 kcmil Cu/Al Grd. Lug (1 pc.) #6–250 kcmil Cu/Al 259. LD6N3R W60993 (NLD) (2 pcs.) #1/0–600 kcmil Grd. Lug (1 pc.) #6–250 kcmil Cu/Al 393. MND63 W63623 (NMND) (8 pcs.) 250 kcmil–500 kcmil Cu/Al Grd. Lug (1 pc.) #6–300 kcmil Cu/Al 802. E2N3R CED6N3R 6 Neutral Catalog Number ENCLOSED CIRCUIT BREAKERS Enclosure Catalog Number Hubs — see page 6/87 For inches / millimeters conversion, see page 15/6. Does not include circuit breaker. Order circuit breaker separately. Neutral not included. Order as separate item from table on next page. Neutral included in enclosure. Use CED enclosure for all ED-frame 110-125 ampere units. 6/85 Enclosed Circuit Breakers SELECTION / DIMENSIONS Enclosures — Type 12 Types 5, 12 Number of Poles Maximum Current Rating Figure Number Breaker Type 2 ED2, ED4, ED6, HED4, HED6 2–3 0100 E2N12 1 CED6 2–3 0125 CED6N12 2 FXD6, FD6, FXD6-A, FD6-A, HFD6, CFD.6 2–3 3 JXD2(A), JD6(A), JXD6(A), HJD6(A), HJXD6(A), HHJD6, HHJXD6, SJD6(A), SHJD6(A) Weight Lb./Ship . Package Catalog Number Dimensions (inches) A B 5 C 11 D 1 E F 1 012 18 ⁄8 08 ⁄32 07 ⁄16 18 06 ⁄16 01⁄2 0811⁄32 071⁄16 22 061⁄16 05⁄8 016 225⁄8 0250 F6N12 040 19 38 ⁄32 14 ⁄64 08 ⁄8 34 13 023⁄32 2–3 0400 J6N12 104 40 2535⁄64 117⁄8 36 2435⁄64 — 3 LD6(A), LXD6(A), HLD6(A), HLXD6(A), HHLD6, HHLXD6, SLD6(A), SHLD6(A), CJD6, CLD6, SCJD6(A), SCLD6(A) 2–3 0600 LD6N12 (L6N12) 104 45 2535⁄64 117⁄8 41 2435⁄64 — 4 MD6, MXD6, SMD6, HMD6, HMXD6, SHMD6, ND6, NXD6, SND6, HND6, HNXD6, SHND6, CMD6, SCMD6, CND6, SCND6 2–3 1200 MND612 220 60 373⁄8 10 005⁄8 03 2 29 1 Dimensions 6 Figure 2 Figure 3 ENCLOSED CIRCUIT BREAKERS Figure 1 Neutrals Enclosure Catalog Number E2N12 Neutral Catalog Number Neutral Cable Capacity and Wire Range List Price $ W53045 (1 pc.) #14–2 Cu/Al (1 pc.) #14–2 Cu/Al 246. F6N12 N250 (NFD) (1 pc.) #6–350 kcmil Grd. Lug (1 pc.) #14–2/0 Cu/Al 259. J6N12 W60992 (NJD) (1 pc.) #1/0–750 kcmil Cu/Al or (2 pc.) #1/0–300 kcmil Cu/Al Grd. Lug (1 pc.) #6–250 kcmil Cu/Al 259. L6N12 W60993 (NLD) (2 pcs.) #1/0–600 kcmil Grd. Lug (1 pc.) #6–250 kcmil Cu/Al 393. MND612 W63623 (NMND) (8 pcs.) 250 kcmil–500 kcmil Cu/Al Grd. Lug (1 pc.) #6–300 kcmil Cu/Al 802. CED6N12 For inches / millimeters conversion, see page 15/6. Neutral not included. Order as separate item. included in enclosure. CED enclosure for all ED-frame 110–125 ampere units. Neutral Does not include circuit breaker. Order circuit breaker separately. 6/86 Use Figure 4 Enclosed Circuit Breakers SELECTION / DIMENSIONS Enclosures — Knockout and Hub Data Knockouts & Wire Bending Space Types 1, 12 Type 3R Number of Knockouts Per Panel (type 12 have no KO’s) Breaker Type BQ, BQH, HBQ 70–100A Conduit Range Per Knockout Outside Dimensions (inches) Top Bottom Side Back Bottom Side ⁄4, 1, 1 ⁄4 1 1 2 2 8 2 2 2 2 2 2 3 1 Back Maximum Hub Size (inches) Type 3R Maximum Cable Sizes Recommended (Cu/Al) for Type 1, 3R, 4, 4X, 12 & 12K Enclosures 1 3 2 3 1 1 21⁄2 2 2 1 1 2 2 4 QJ 11⁄2, 2, 21⁄2, 3 ED2, ED4, ED6, HED4 7 ⁄8, 1 ⁄8, 1 ⁄8, 1 ⁄4, 2 2 7 ⁄8, 11⁄8, 13⁄8, 13⁄4, 2 — — — — 2 — — 7 ⁄8, 11⁄8, 13⁄8, 13⁄4, 2, 21⁄2 2 2 2 2 — 1 1 1 1 2 2 1 1 — 1 1 — — 1 — — CED6 1 3 3 (CFD6 only 300 kcmil) FXD6, FD6, FXD6-A, FD6-A HFD6, CFD6 11⁄8, 13⁄8, 13⁄4, 2, 21⁄2, 3 JXD2(A), JXD6(A), JD6(A), HJD6(A), HJXD6(A), HHJD6, HHJXD6, SJD6(A), SHJD6(A) 11⁄2, 2, 21⁄2, 3, 31⁄2, 4 1 1 2 4 — — — 4 (2) 500 kcmil LXD6(A), LD6(A), HLXD6(A), HLD6(A), HHLD6, HHLXD6, SLD6(A), SHLD6(A) 11⁄2, 2, 21⁄2, 3, 31⁄2, 4 1 1 2 4 — — — 4 (2) 500 kcmil MD6, SMD6, HMD6 ND6, SND6, HND6 — — — — — — — — 4 (3) 600 kcmil or (4) 500 kcmil Conduit Size (inches) Catalog Number QP, QPH, HQP, BQ, BQH, HBQ, ED2, ED4, ED6, HED4, HED6, CED6 03⁄4 1 11⁄4 11⁄2 2 HR075 HR100 HR125 HR150 HR200 QPP, QPPH, HQPP, QJ2, QJH2, QJ2-H 11⁄4 11⁄2 2 21⁄2 HS125 HS150 HS200 HS250 FXD6-A, FD6-A, HFD6, HFXD6, CFD6, JXD2(A), JD6(A), JXD6(A), HJD6(A), HJXD6(A), LD6(A), LXD6(A), HLD6(A), HLXD6(A) 21⁄2 3 31⁄2 4 HV250 HV300 HV350 HV400 For inches / millimeters conversion, see page 15/6. Sufficient 171⁄8" The high enclosure provides sufficient wire bending space for all available CB lugs. wire bending space is provided for all available mechanical type CB lugs. use of cables larger than those listed below may violate NEC & CSA wire bending space requirements. Note: Enclosures for 250A max breakers have a hub provision on the rainshed. Enclosures for larger breakers (J, L, M & N frame) have blank top rainsheds. Drill or punch hole in the field to accommodate hub size desired. The use of compression type connectors will violate NEC and CSA wire bending space requirements. 6/87 ENCLOSED CIRCUIT BREAKERS Breaker Type 6 Hubs (Type 3R) Notes 6 ENCLOSED CIRCUIT BREAKERS 6/88 Molded Case Circuit Breakers GENERAL CIRCUIT BREAKERS 6 Series Rated Combination Guide 6/89 Molded Case Circuit Breakers GENERAL Series Rated Combination Guide Reading the Series Rated combination tables Identify the application voltage. Identify the available short circuit current at the point where the breaker is to be applied. Identify the ampere rating and number of poles for both the upstream and downstream breakers. Example: The application voltage is 208V, 3phase, the available short circuit current is 19,000 Amps. The Main breaker is 200A rated and the Branch breaker is 3 Pole, 100A rated. From the tables select the voltage greater than and closest to the application voltage. ( 240 ) From the IC column select the current rating greater than and closest to the application short circuit current From the Main Breaker column select the type based on the required ampere rating and number of poles. ( QJH2, 200A, 3P ) The Maximum current tested for this type of breaker is 225A. From the Branch Breaker column select the type based on the required ampere rating and number of poles. some cases more than one option may be available. ( QP, BQ, BL ) IC/CI KA Main Breaker / Disjoncteur principal Type Branch Breaker / Disjoncteur de branchement Ams (Poles) Type 6 QP, BQ, BL 22 QJH2 60 - 225 (2 & 3) QPF, BQF BLF, QE, BE, BLE QT # Poles Amps 1 2 3 1 1, 2 15 - 70 15 - 125 60 - 100 15 - 30 15, 20, 40 Max Voltage (AC/CA) 120/240 240 240 120 120/240 This information is of a general nature and is intended for reference purposes only. Although every effort to ensure correctness of the material, Siemens Canada Limited cannot assume any responsibility for actions taken on the basis of the content herein. CIRCUIT BREAKERS Diagram for the above example: QJH2 MAIN BREAKER AVAILABLE FAULT CURRENT AT 208V (10K AMPS) Amps) (19K 6/90 Figure 3 QP, BQ, BL FEEDER BREAKERS Molded Case Circuit Breakers GENERAL Type Ams (Poles) Type QP, BQ, BL 22 QPH, BQH, BLH 15-70 (1), 15-125 (2), 15-100 (3) QE, BLE, QPF, BLF QE, BLE, QPF, BQF, BLF QT QP, BQ, BL 22 QPPH 125 - 225 (2) 22 QJH2 60 - 225 (2 & 3) QE, BLE, BE, QPF, BQF, BLF QE, BLE, BE, QPF, BLF QPP QT QP, BQ, BL QPF, BQF BLF, QE, BE, BLE QT QP, BQ, BL 42 QJ2H 60 - 225 (2 & 3) QPH, BQH, BLH QE, BLE, BE, QPF, BLF QJH2 QP, BQ, BL, QPH, BQH, BLH 65 HQP, HBQ, HBL 15-70 (1), 15-125 (2), QPF, BQF, BLF, BE, QFHF, BQHF, BLHF, QEH, 15-100 (3) BLEH, QE, BLE QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF QT QP, BQ, BL, QPH, BQH, BLH 65 HQPP 125 - 225 (2) QPF, BQF, BLF, QPHF, BQHF, BLHF, QEH, BLEH, QE, BLE, BE QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF QT QPPH, QPP QP, BQ, BL, QPH, BQH, BLH 65 ED4, ED6 15 - 100 (1), 15 - 125 QPHF, BQHF, BLHF, QPF, BQF, BLF, QE, QEH, (2 & 3) BLEH, BE, BLE QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF ED2 QT QP, BQ, BL, QPH, BQH, BLH 65 FD6-A, FXD6-A 70 - 250 (2 & 3) QJ2H, QJ2, QJH2 QPPH 65 JXD2-A, JD6-A, JXD6A 200 - 400 (2 & 3) QPH, BQH, BLH QJ2H, QJH2 65 LD6-A 200 - 600 (2 & 3) QPH, BQH, BLH QJ2H, QJH2 65 LXD6-A 450 - 600 (2 & 3) # Poles Amps Max Voltage (AC/CA) 1 2 3 1 2 1, 2 1 2 1 2 2 1, 2 1 2 3 1 1, 2 1 2 3 1 2 3 2 2, 3 1 2 3 15 -70 15 -125 15-100 15 - 60 15 - 30 15, 20, 40 15 -70 15 -125 15 - 30 15 - 60 125 - 200 15, 20, 40 15 - 70 15 - 125 60 - 100 15 - 30 15, 20, 40 15 - 70 15 - 125 60 - 100 15 - 70 15 - 125 15 - 100 15 - 60 60 - 225 15 - 70 15 - 100 15 - 100 120/240 120/240 240 120/240 120 120/240 120/240 120/240 120 120/240 120/240 120/240 120/240 240 240 120 120/240 120/240 120/240 240 120/240 120/240 240 120/240 240 120/240 120/240 240 1 15 - 30 120 2 1, 2 1 2 15 - 60 15 - 40 15 - 70 15 - 125 120/240 120/240 120/240 120/240 Branch Breaker / Disjoncteur de branchement Main Breaker / Disjoncteur principal QPH, BQH, BLH QJ2H, QJH2 1 15 - 30 120 2 1, 2 2 1 2 3 15 - 60 15 - 40 125 - 200 15 - 70 15 - 125 15 - 100 120/240 120 120/240 120 120/240 240 1 15 - 30 120 2 1, 2, 3 1, 2 1 2 3 2, 3 2 1 2 3 2, 3 1 2 3 2, 3 1 2 3 2, 3 15 - 60 15 - 100 15 - 40 15 - 70 15 - 125 15 - 100 60 - 225 125 - 225 15 - 70 15 - 125 15 - 100 60 - 225 15 - 70 15 - 125 15 - 100 60 - 225 15 - 70 15 - 125 15 - 100 60 - 225 120/240 120/240 120/240 120/240 120/240 240 240 120/240 120/240 120/240 240 240 120/240 120/240 240 240 120/240 120/240 240 240 CIRCUIT BREAKERS 100 100 100 65 IC/CI KA 6 Series Rated Combination Guide 6/91 Molded Case Circuit Breakers GENERAL Series Rated Combination Guide 100 100 100 65 IC/CI KA Main Breaker / Disjoncteur principal Type 65 65 100 HJD6-A, HJXD6-A, HLD6-A, HLXD6-A, HMD6, HMXD6, HND6, HNXD6, HPD6, HPXD6, HRD6, HRXD6 Ams (Poles) 200 - 2000 (2 &3) Type QPH SJD6-A, SLD6-A, SMD6, SND6, SPD6 200 - 1600 (2 &3) QPH, BQH, BLH MD6, MXD6, ND6, NXD6, PD6, PXD6, RD6, RXD6 500 - 2000 (2 & 3) QPH, BQH, BLH HED4 15 - 100 (1) ED2, ED4 QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 100 HED4, HED6 15 - 125 (2 & 3) 100 HED4 15 - 100 (1) QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF, BLF, BQF, BLE QEH, BLEH, QPHF, BLHF,QPF, BLF, QE, BLE ED2 ED4 ED4, ED6 QT ED2, ED4 QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 100 HQPPH 125 - 225 (2) # Poles Amps Max Voltage (AC/CA) 1 15 - 70 120/240 2 15 - 125 120/240 3 15 - 100 240 1 2 3 1 2 3 1 1 2 3 15 - 70 15 - 125 15 - 100 15 - 70 15 - 125 15 - 100 15 - 100 15 - 70 15 - 125 15 - 100 120/240 120/240 240 120/240 120/240 240 120 120 120/240 240 Branch Breaker / Disjoncteur de branchement HQPP, QPPH, QPP QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF, BQF, BLF, BLE QT 1 15 -30 120 2 1, 2, 3 1 2, 3 1, 2 1 1 2 2 15 - 60 15 - 100 15 - 100 15 - 125 15 - 40 15 - 100 15 - 70 15 - 125 125 - 225 120/240 120/240 120 240 120/240 120 120/240 120/240 120/240 1 15 - 30 120 1, 2 15 - 40 15 - 25 35 - 70 15 - 25 35 - 125 15 - 100 15 - 70 15 - 125 15 - 100 120/240 120/240 120/240 120/240 120/240 240 120/240 120/240 240 1 QP, BQ, BL 6 100 HQJ2H 60 - 225 (2 & 3) QPH, BQH, BLH, HQP, HBQ, HBL CIRCUIT BREAKERS QEH, BLEH, QE, BE, QPHF, BQHF, BLHF, QPF, BQF, BLF, BLE QEH, BLEH, QPHF, BLHF,QE, BLE, QPF, BLF QT QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 6/92 100 HFD6, HFXD6 70 - 250 (2 & 3) 100 HJD6-A, HJXD6-A, SHJD6-A 200 - 400 (2 & 3) 100 HLD6-A 200 - 600 (2 & 3) QE, BE, BLE, QPHF, BQHF, BLHF, QPF, BQF, BLF, QEH, BLEH QPF, BLF, QE, BLE, QPHF, BLHF, QEH, BLEH ED4 ED4, ED6 FD6-A, FXD6-A QJ2, QJH2, QJ2H HQPP, QPPH, QPP QT ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A 2 3 1 2 3 1 15 - 30 120 2 1 1 2 3 15 - 60 15 - 50 15 - 70 15 - 125 15 - 100 120/240 120/240 120/240 120/240 240 1 15 - 30 120 2 1 2, 3 2, 3 2, 3 2 1, 2 1 2, 3 2, 3 2, 3 1 2, 3 2, 3 2, 3 15 - 60 15 - 100 15 - 125 70 -250 60 - 225 125 - 225 15 - 30 15 - 100 15 - 125 70 - 250 200 - 400 15 - 100 15 - 125 70 - 250 200 - 400 120 120 240 240 240 120/240 120/240 120/240 120/240 120/240 120/240 120 240 240 240 Molded Case Circuit Breakers GENERAL Main Breaker / Disjoncteur principal Type Ams (Poles) 100 HLD6-A 200 - 600 (2 & 3) 100 HLXD6-A 450 - 600 (2 & 3) 100 SHLD6-A 300 - 600 (3) 100 HMD6, HMXD6 500 - 800 (2 & 3) 100 SHMD6 500 - 800 (3) 100 HND6, HNXD6 500 - 1200 (2 & 3) 100 SHND6 500 - 1200 (2 & 3) 100 HPD6, HPXD6, SHPD 1200 - 1600 (3) 100 HPD6, HPXD6, SHPD 1200 - 1600 (3) # Poles Amps Max Voltage (AC/CA) 2, 3 2, 3 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 2, 3 200 - 600 450 - 600 300 - 600 15 - 100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 15 - 100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 15 - 100 15 - 125 70 - 250 200 -400 200 - 600 450 - 600 300 - 600 500 -800 15 - 100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 500 - 800 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 500 - 600 500 - 1200 15 - 100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 500 - 600 500 - 1200 15 -100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 500 - 800 500 - 1200 1200 - 1600 240 240 240 120 240 240 240 240 240 240 120 240 240 240 240 240 240 120 240 240 240 240 240 240 240 120 240 240 240 240 240 240 240 240 240 240 240 240 240 240 120 240 240 240 240 240 240 240 240 120 240 240 240 240 240 240 240 240 240 Branch Breaker / Disjoncteur de branchement Type LD6-A LXD6-A SLD6-A ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 ND6, NXD6, SND6 ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 ND6, NXD6, SND6 ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 ND6, NXD6, SND6 PD6, PXD6, SPD6 6/93 CIRCUIT BREAKERS 100 100 100 65 IC/CI KA 6 Series Rated Combination Guide Molded Case Circuit Breakers GENERAL Series Rated Combination Guide 100 100 100 65 IC/CI KA Main Breaker / Disjoncteur principal Type 100 HRD6, HRXD6 Ams (Poles) 1600 - 2000 (3) Type ED4 ED4, ED6 FD6-A, FXD6-A JD6-A, JXD6-A, JXD2-A, SJD6-A LD6-A LXD6-A SLD6-A MD6, MXD6, SMD6 ND6, NXD6, SND6 PD6, PXD6, SPD6 RD6, RXD6 QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 200 CED6 15 - 125 (2 & 3) QPHF, BQHF, BLHF, QPF, BQF, BLF, QEH, QE, BE, BLEH QEH, BLEH, QPHF, BLHF, QPF, BLF, QE, BLE ED4, HED4 ED4, ED6, HED4, HED6 QT QP, BQ, BL, QPH, BQH, BLH, HQP, HBQ, HBL 200 CFD6 70 - 250 (2 & 3) 200 HHJD6, HHJXD6, HHLD6, HHLXD6 200 - 600 (2 & 3) QPHF, BQHF, BLHF, QE, BE, BLE, QPF, BQF, BLF, QEH, BLEH QPHF, BLHF, QE, BLE, QPF, BLF, QEH, BLEH ED2 HED4, ED4 ED4, ED6, HED4, HED6 FD6-A, FXD6-A, HFD6, HFXD6 QJ2H, QJH2, QJ2 QPPH, QPP QT FD6-A, FXD6-A, HFD6, HFXD6 6 QPH, BQH, BLH, HQP, HBQ, HBL 200 CJD6 200 - 400 (2 & 3) ED4, ED6 FD6-A, FXD6-A, HFD6, HFXD6 JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A QT QPH, BQH, BLH, HQP, HBQ, HBL CIRCUIT BREAKERS 6/94 200 CLD6 450 - 600 (2 & 3) 200 CMD6 500 - 800 (2 & 3) 200 SCMD6 500 - 800 (3) 200 CND6 900 - 1200 (2 & 3) 200 CND6 900 - 1200 (2 & 3) # Poles Amps Max Voltage (AC/CA) 1 2, 3 2, 3 2, 3 2, 3 2, 3 3 2, 3 2, 3 2, 3 2, 3 1 2 3 15 -100 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 300 - 600 500 - 800 500 - 1200 1200 - 1600 1600 - 2000 15 - 70 15 - 125 15 - 100 120 240 240 240 240 240 240 240 240 240 240 120/240 120/240 240 Branch Breaker / Disjoncteur de branchement ED4, ED6 FD6-A, FXD6-A, HFD6, HFXD6 JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HJXD6-A QT ED4, ED6, HED4, HED6 FD6-A, FXD6-A, HFD6, HFXD6 JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A MD6, MXD6, HMD6, HMXD6 MD6, MXD6, HMD6, HMXD6 ED4, ED6, HED4, HED6 FD6-A, FXD6-A, HFD6, HFXD6 JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A MD6, MXD6, HMD6, HMXD6 ND6, NXD6, SND6, HND6, HNXD6 1 15 - 30 120 2 1 2, 3 1, 2 1 2 3 15 - 60 15 - 100 15 - 125 15 - 40 15 - 70 15 - 125 15 - 100 120/240 120 240 120/240 120/240 120/240 240 1 15 - 30 120 2 1, 2, 3 1 2, 3 2, 3 2, 3 2 1, 2 15 - 60 15 - 100 15 - 100 15 - 125 70 - 250 60 - 225 125 - 225 15 - 40 120/240 120/240 120 240 240 240 120/240 120/240 2, 3 70 - 250 240 2 3 2, 3 2, 3 2, 3 1, 2 2 3 2, 3 2, 3 2, 3 2, 3 2, 3 1,2 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 100 - 125 100 15 - 125 70 - 250 200 - 400 15 - 30 100 - 125 100 15 - 25 70 - 250 200 - 400 200 - 600 450 - 600 15 - 30 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 500 - 800 15 - 125 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 500 - 1200 120/240 240 240 240 240 120/240 120/240 240 120/240 240 240 240 240 120/240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 Molded Case Circuit Breakers GENERAL Series Rated Combination Guide Main Breaker / Disjoncteur principal Ams (Poles) 200 SCND6 900 - 1200 (3) 200 CPD6 1200 - 1600 (3) 65 J, R 15 - 600 (1, 2, 3) 65 65 T L 15 - 1200 (1, 2, 3) 601 - 6000 (1, 2, 3) Type MD6, HMD6, HMXD6, MXD6, SHMD6, SMD6 ND6, HND6, SHND6, NXD6, HNXD6, SND6 FD6-A, FXD6-A, HFD6, HFXD6 JXD2-A, JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A MD6, MXD6, HMD6, HMXD6 ND6, NXD6, SND6, HND6, HNXD6 QPH, BQH, BLH QPH, BQH, BLH QPH, BQH, BLH QP, BQ, BL 100 T (300 V) 15-200 (1, 2, 3) 15 - 600 (1, 2, 3) 15 - 600 (2, 3) 70 - 600 (2, 3) 100 J, R 200 - 600 (2, 3) T 240 240 240 240 240 240 240 240 1 15-70 120/240 2 15-125 120/240 3 15 - 100 240 1 15-70 120/240 2 15-125 120/240 3 15 - 100 240 1 15-70 120/240 2 15-125 120/240 3 15 - 100 240 1, 2, 3 15 - 125 120/240 HQP, HBQ, HBL, QPH, BQH, BLH QPF, BQF, BLF, QE, BE, BLE, QEH, BLEH, BLHF, QPHF, BQHF, QEH, BLEH, QE, QPHF, BLHF, BLE, QPF, BLF 3 15 - 100 240 1 15 - 30 120 120/240 2 15 - 60 QT 1, 2 15 - 50 120/240 QPH, BQH, BLH, HQP, HBQ, HBL 1, 2 15 - 125 120/240 ED4, HED4 1 15 - 100 120 ED4, ED6, HED4, HED6 2, 3 15 - 125 240 FD6-A, FXD6-A 2, 3 70 - 250 240 JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240 LD6-A 2, 3 200 - 600 240 3 300 - 600 240 450 - 600 (2, 3) LXD6-A 2, 3 450 - 600 240 1 15 - 100 120/240 ED4, HED4 ED4, ED6, HED4, HED6 2, 3 15 - 125 240 70 - 1200 (2, 3) FXD6-A, FD6-A 2, 3 70 - 250 240 450 - 1200 (2, 3) LXD6-A 2, 3 450 - 600 240 JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240 LD6-A 2, 3 200 - 600 240 3 300 - 600 240 300 - 1200 (3) SLD6-A ED4, HED4 L 500 - 800 500 - 1200 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 500 - 1200 SLD6-A 200 - 1200 (2, 3) 100 Amps 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 300 - 600 (3) 15 - 1200 (2, 3) 100 # Poles 601 - 6000 (2, 3) 1 15 - 100 120/240 ED4, ED6, HED4, HED6 2, 3 15 - 125 240 FD6-A, FXD6-A 2, 3 70 - 250 240 JD6-A, JXD6-A, JXD2-A, SJD6-A 2, 3 200 - 400 240 LD6-A 2, 3 200 - 600 240 LXD6-A 2, 3 450 - 600 240 SLD6-A 3 300 - 600 240 SMD6 3 500 - 800 240 SND6 3 500 - 1200 240 PD6, PXD6, SPD6 3 1200 - 1600 240 RD6, RXD6 3 1600 - 2000 240 QJH2, QJ2H, QJ2 2, 3 125 - 200 240 125 - 600 (2, 3) QJH2, QJ2H 2, 3 125 - 225 240 125 - 400 (2, 3) QJ2 2, 3 125 - 225 240 125 - 200 (2, 3) 6 Type Max Voltage (AC/CA) Branch Breaker / Disjoncteur de branchement 200 R 200 T, J 200 J, R 70 - 600 (2, 3) HFD6, HFXD6 2, 3 70 - 250 240 200 T 70 - 1200 (2, 3) HFD6, HFXD6 2, 3 70 - 250 240 CIRCUIT BREAKERS 100 100 100 65 IC/CI KA 6/95 Molded Case Circuit Breakers GENERAL Series Rated Combination Guide 100 100 100 65 IC/CI KA Type 200 # Poles Amps Max Voltage (AC/CA) HFD6, HFXD6 2, 3 70 - 250 240 MD6, MXD6, HMD6, HMXD6 2, 3 500 - 800 240 ND6, NXD6, HND6, HNXD6 BQD, CQD ED4 ED4, ED6 2, 3 1, 2, 3 1 2, 3 500 - 1200 15 - 100 15 - 100 15 - 125 2,3 15-100 1, 2, 3 1 2, 3 15,100 15 - 100 15 - 125 240 277 277 480 277 277 277 277 480 480 2, 3 15 - 50 480 Main Breaker / Disjoncteur principal L Branch Breaker / Disjoncteur de branchement Ams (Poles) 601 - 6000 (2, 3) Type 30 HED6 15 - 125 (2 & 3) 35 JD6, JXD6 LD6 LXD6 200-400 (2 & 3) 200-600 (2 & 3) 450-600 (2 & 3) ED4 42 HED4 15 - 125 (2 & 3) BQD, CQD ED4 ED4, ED6 50 HJD6-A, HJXD6-A 200-400 (2 & 3) 50 HLD6-A, HLXD6-A 200-600 (2 & 3) 50 MD6, MXD6 500-800 (2 & 3) HED4 FD6-A, FXD6-A 2, 3 70 - 250 480 JD6-A, JXD6-A, SJD6-A 2, 3 200 - 400 480 LD6-A 2, 3 200 - 600 480 LXD6-A 2, 3 450 - 600 480 3 400 - 600 480 2, 3 2, 3 2, 3 2, 3 3 3 2, 3 2, 3 2, 3 3 3 2, 3 2, 3 2, 3 3 3 2, 3 2, 3 2, 3 3 3 2, 3 2, 3 2, 3 2, 3 3 3 2, 3 2, 3 2, 3 2, 3 3 3 1, 2, 3 1 2, 3 1 2, 3 2, 3 70 - 250 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 70 - 250 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 70 - 250 200 - 400 200 - 600 450 - 600 200 - 400 400 - 600 15 - 100 15 - 100 15 - 125 15 - 100 70 - 250 200 - 400 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 277 480 480 480 480 SLD6-A ND6, NXD6 500-1200 (2 & 3) 50 SMD6 500 - 800 (3) 50 SND6 500 - 1200 (3) 50 SPD6 1200 - 1600 (3) 6 50 CIRCUIT BREAKERS 1400 - 1600 (3) 6/96 50 PD6, PXD6 50 RD6, RXD6 1800 - 2000 (3) 65 HFD6, HFXD6 70 - 250 (2 & 3) 65 HJD6-A, HJXD6-A 200 - 400 (2 & 3) 1200 - 1600 (3) FD6-A, FXD6-A JD6-A, JXD6-A, LD6-A LXD6-A SJD6-A SLD6-A JD6-A, JXD6-A LD6-A LXD6-A SJD6-A SLD6-A JD6-A, JXD6-A LD6-A LXD6-A SJD6-A SLD6-A JD6-A, JXD6-A LD6-A LXD6-A SJD6-A SLD6-A FD6-A, FXD6-A JD6-A, JXD6-A, SJD6-A LD6-A LXD6-A SJD6-A SLD6-A FD6-A, FXD6-A JD6-A, JXD6-A, SJD6-A LD6-A LXD6-A SJD6-A SLD6-A BQD, CQD ED4, HED4 ED4, ED6, HED4, HED6 HED4, ED4 FD6-A, FXD6-A JD6-A, JXD6-A Molded Case Circuit Breakers GENERAL Main Breaker / Disjoncteur principal Type Ams (Poles) 65 HLD6-A 200 - 600 (2 & 3) 65 HLXD6-A 450 - 600 (2 & 3) 65 HMD6, HMXD6 500 - 800 (2 & 3) 65 HND6, HNXD6 500 - 1200 (2 & 3) 65 HRD6, HRXD6 1800 - 2000 (3) 100 HHJXD6, HHJD6, HHLD6, HHLXD6 200 - 600 (2 & 3) 100 CMD6 500 - 800 (3) 100 100 SCMD SCND6 500 - 800 (3) 900 - 1200 (3) 100 CND6 1200 (3) 100 CPD6 1200 - 1600 (3) 150 CJD6 200 - 400 (2 & 3) 150 CLD6 450 - 600 (2 & 3) 200 CED6 15 - 125 (2 & 3) Type ED4, HED4 FD6-A, FXD6-A JD6-A, JXD6-A LD6-A LXD6-A ED4, HED4 FD6-A, FXD6-A JD6-A, JXD6-A LD6-A LXD6-A FD6-A, FXD6-A JD6-A, JXD6-A LD6-A LXD6-A FD6-A, FXD6-A JD6-A, JXD6-A LD6-A LXD6-A MD6, MXD6, SMD6 FD6-A, FXD6-A JD6-A, JXD6-A LD6-A LXD6-A ED4, ED6, HED4, HED6 FD6-A, FXD6-A, HFD6, HFXD6 FD6-A, FXD6-A, HFD6, HFXD6 JD6-A, HJD6-A, JXD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A MD6, MXD6, HMD6, HMXD6 HFXD6 HFD6, HFXD6 FD6-A, FXD6-A, HFD6, HFXD6 JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A MD6, MXD6, HMD6, HMXD6 ND6, NXD6, HND6, HNXD6 FD6-A, FXD6-A, HFD6, HFXD6 ED4 HFD6, HFXD6 JD6-A, JXD6-A, HJD6-A, HJXD6-A ED4 HFD6, HFXD6 JD6-A, HJD6-A, JXD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A BQD, CQD ED4, HED4 ED4, ED6, HED4, HED6 BQD, CQD 200 CFD6 50 J 100 100 100 J T, J J, R 70 - 250 (2 & 3) 60 - 400 (1, 2, 3) 15 - 400 (2, 3) 15 - 400 (1, 2, 3) 70 - 600 (2, 3) 70 - 600 (2, 3) # Poles Amps Max Voltage (AC/CA) 1 2, 3 2, 3 2, 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 1 2, 3 2, 3 1 2, 3 2, 3 2, 3 2, 3 1 2, 3 1 2, 3 1 2, 3 2, 3 1 2, 3 2, 3 1 2, 3 1 2, 3 2, 3 15 - 100 70 - 250 200 - 400 200 - 600 450 - 600 15 - 100 70 - 250 200 - 400 200 - 600 450 - 600 70 - 250 200 - 400 200 - 600 450 - 600 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 70 - 250 200 - 400 200 - 600 450-600 15 - 100 70 - 250 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 70 - 250 70 - 250 70 - 250 200 - 400 200 - 600 450 - 600 500 - 800 500 - 1200 70 - 250 15 - 100 70 - 250 200 - 400 15 - 100 70 - 250 200 - 400 200 - 600 450 - 600 15 - 100 20 - 30 15 - 100 15 - 125 15 - 100 20 - 30 15 - 50 15 - 100 15 - 125 70 - 250 60 - 100 15 - 100 15 - 50 70 - 250 70 - 250 277 480 480 480 480 277 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 277 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 277 480 480 277 480 480 480 480 480 480 277 480 480 480 480 277 480 480 277 480 277 480 480 Branch Breaker / Disjoncteur de branchement ED4, ED6 ED4, HED4 HED4, HED6 FD6-A, FXD6-A, HFD6, HFXD6 ED4 ED4 ED4 FD6-A, FXD6-A HFD6, HFXD6 CIRCUIT BREAKERS 100 100 100 65 IC/CI KA 6 Series Rated Combination Guide 6/97 Molded Case Circuit Breakers GENERAL Series Rated Combination Guide 100 100 100 65 IC/CI KA Main Breaker / Disjoncteur principal Type # Poles Amps Max Voltage (AC/CA) 200 - 400 200 - 600 450 - 600 70 - 250 200 - 400 200 - 600 450 - 600 70 - 250 500 - 800 500 - 1200 1200 - 1600 15 - 100 20 - 30 15 - 100 20 - 30 15 - 70 15 - 70 15 - 70 15 - 70 15 - 125 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 347 347/600 347 347/600 347/600 70 - 250 347/600 Branch Breaker / Disjoncteur de branchement Ams (Poles) Type 100 T, J, R 100 T 450 - 600 (2, 3) 70 - 1200 (2, 3) 100 T, L 601 - 1200 (2, 3) 100 L 601 - 6000 (2, 3) R 15 - 100 (1, 2, 3) BQD, CQD T, J 15 - 200 (1, 2, 3) BQD, CQD 18 ED6, HED6 ED6, HED6 15 -125 (1, 2, 3) 15 -125 (2, 3) 25 HFD6 70 - 250 (2, 3) BQD6,CQD6 BQD6,CQD6 BQD6, CQD6 BQD6, CQD6, ED6, HED6 ED6, HED6 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 3 1 2, 3 1 2,3 1 2, 3 1 2, 3 2, 3 35 HJD6, HJXD6 HLD6, HLXD6 200 - 400 (2, 3) 450 - 600 (2, 3) HFD6 2, 3 50 HMD6, HMXD6 HND6 HNXD6 500 - 800 (2, 3) 500 - 1200 (2, 3) 900 - 1200 (2, 3) 65 CFD6 70 - 250 (2, 3) 65 CMD6 CND6 CPD6 500 - 800 (2, 3) 900 - 1200 (2,3) 1200 - 1600 (2,3) 200 - 600 (2, 3) JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A, HLXD6-A LXD6-A, HFD6, HFXD6 JD6-A, JXD6-A, HJD6-A, HJXD6-A LD6-A, HLD6-A LXD6-A, HLXD6-A HFD6, HFXD6 MD6, MXD6, HMD6, HMXD6 ND6, NXD6, HND6, HNXD6 PD6, HPD6, HPXD6 200 HFD6 6 JD6, JXD6 HJD6, HJXD6 LD6, HLD6 LXD6, HLXD6 BQD6,CQD6 ED6, HED6 HFD6 JD6, JXD6 HJD6, HJXD6 LD6, HLD6 LXD6, HLXD6 2, 3 2, 3 2, 3 HFD6 JD6, JXD6 65 CIRCUIT BREAKERS 100 CED6 1200 - 1600 (2, 3) 15 - 125 (2, 3) 100 CFD6 70 -250 (2, 3) 100 J,R,T 200 - 600 (2, 3) 2001.10.01 6/98 HPD6, HPXD6 HJD6, HJXD6 2, 3 70 600 200 - 400 200 - 400 200 - 600 450 - 600 15 - 70 15 - 125 70 200 - 400 200 - 400 200 - 600 450 - 600 600 600 600 600 347/600 600 600 600 600 600 600 70 600 200 - 400 600 200 - 400 600 LD6, HLD6 200 - 600 600 LXD6, HLXD6 450 - 600 600 1 15 - 70 347 2 3 2, 3 1 15 - 70 15 - 70 15 - 125 15 - 70 15 - 125 70 - 250 200 - 400 347/600 347/600 600 347 600 600 600 200 - 600 600 450 - 600 600 BQD6,CQD6 ED6, HED6 BQD6,CQD6 ED6, HED6 HFD6 JD6, JXD6 HJD6, HJXD6 LD6, HLD6 LXD6, HLXD6 2, 3 2, 3 Molded Case Circuit Breakers REFERENCE Unusual Operating Conditions Note: The information provided on this and the next page is intended for reference and recommendation only. Because several variables can act on a circuit breaker’s performance at the same time, the data below is based less on controlled testing, than on experience and engineering judgment. Contact Siemens for further information on special conditions and treatment. Table 1 — Temperature Derating Data for Thermal-Magnetic Breakers Ampere Rating at: 25° C 50° C (77° F) (122° F) 0017 0013 0022 0018 0028 0023 0033 0028 0039 0030 0044 0037 0055 0046 0066 0056 0077 0065 0099 0084 0110 0094 0137 0114 0165 0136 0192 0159 0220 0182 0247 0205 0275 0235 0330 0276 0385 0325 0440 0372 0550 0468 0660 0564 0770 0658 0880 0754 0990 0828 0900 1100 1320 1090 1540 1304 1760 1500 1980 1690 2200 1880 60° C (140° F) 0011 0016 0021 0026 0025 0034 0042 0052 0060 0078 0087 0100 0120 0140 0160 0180 0220 0252 0301 0340 0435 0525 0613 0704 0749 0825 1000 1148 1320 1485 1650 Siemens Breaker Frames ED QJ FD JD LD MD ND PD 6 Reference Ampere Rating at 40° C (104° F) 0015 0020 0025 0030 0035 0040 0050 0060 0070 0090 0100 0125 0150 0175 0200 0225 0250 0300 0350 0400 0500 0600 0700 0800 0900 1000 1200 1400 1600 1800 2000 RD 13,000 (4,000) 12,000 (3,675) CIRCUIT BREAKERS Altitude in Feet (Meters) High Ambient Temperatures Because thermal-magnetic trip breakers are temperature sensitive and calibrated for a specific ambient of 40° C (104° F) (average enclosure temperature), a higher ambient will cause the breaker to trip at lower current than its nameplate rating, in other words, causing the breaker to “derate” (see Table 1). Similarly, the current carrying capacity of a circuit conductor is based upon a certain ambient temperature, a higher ambient will reduce its current carrying capacity, causing it to “derate.” Thus, with a fluctuating temperature, a thermal-magnetic breaker will derate nearly parallel with its connected circuit conductors and maintain close circuit protection. If the application temperature exceeds 40° C (104° F) and is known, either a breaker specially calibrated for the higher ambient or one oversized according to Table 1 may be selected. In a case such as this, the circuit conductors should be oversized as well. Siemens Sensitrip® III and Type SB Encased Systems Breakers are insensitive to temperature changes. However, they do include circuitry to protect the components from abnormally high temperatures. Moisture — Corrosion For atmospheres having high moisture content and / or where fungus growth is prevalent, a special preventive treatment may be required. Where the air is heavily laden with corrosive elements, breakers made with special corrosion-resistant finishes may be required. Altitude Reduced air density at altitudes greater than 6600 ft. (2000 meters) affects the ability of a molded case circuit breaker to transfer heat and interrupt faults. Therefore, circuit breakers applied at these altitudes should have interrupting, insulation and continuous currents derated as indicated in Figure 1. 11,000 (3,350) 10,000 (3,000) 9,000 (2,750) 8,000 (2,400) 7,000 (2,100) 6,000 (1,800) 1.0 .95 .90 .85 .80 .75 Rating Correction Factor Figure 1 — Altitude Adjustment 6/99 Molded Case Circuit Breakers REFERENCE Unusual Operating Conditions 400 Hz Systems Siemens molded case circuit breakers can be applied for overcurrent protection on 400Hz systems, commonly used to power computer installations, aircraft, military and other specialty equipment. Below are basic guidelines. Circuit Breaker Derating Required This table lists the maximum continuous current carrying capacity for Siemens breakers at 400Hz. Due to the increased resistance of the copper sections resulting from the skin effect produced by eddy currents at these frequencies, circuit breakers in many cases require derating. The thermal derating on these devices is based upon 100%, three-phase application in open air in a maximum of 40° C (104° F) with 48 in. (1219 mm) of the specified cable or bus at the line and load side. Additional derating of not less than 20% will be required if the circuit breaker is to be utilized in an enclosure. Further derating may be required if the enclosure ambient temperature exceeds 40° C (104° F). Cable and Bus Sizing The cable and bus sizes to be utilized at 400Hz are not based on standard National Electric Codes tables for 60Hz application. Larger cross sections are necessary at 400Hz. All bus bars specified are based upon mounting the bars in the vertical plane to allow maximum air flow. All bus bars are spaced at a minimum of 0.25 in. (6mm) apart. Mounting of bus bars in the horizontal plane will necessitate additional drafting. Edgewise orientation of the bus may change the maximum ratings indicated. If additional information is required for other connections of cable or bus, contact Siemens for information. Application Recommendations It is recommended that temperatures be measured on the line and load terminals or T-connectors of the center pole. These are usually the hottest terminals with a balanced load. A maximum temperature of 75° C (35° C over a maximum ambient of 40° C) would verify the particular application. Temperature profiles taken on these breakers can be correlated to ensure that the hottest points within the breaker are within the required temperature limits. Factory Configuration When required, molded case circuit breakers may be factory calibrated for 400Hz application. These breakers are specially labeled for 400Hz usage and their nameplate current rating will include the necessary derating factory. The highest “Maximum Continuous Amperes” rating at 400Hz, found in the table below approximates the highest specially calibrated 400Hz nameplate ampere rating available for a given frame size. Contact Siemens for ordering information on other breakers applied in 400Hz systems. 400Hz Breakers Siemens Breaker Type 6 ED2, ED4, ED6, HED4, CED6 CIRCUIT BREAKERS FD6, FXD6, HFD6, HFXD6, CFD6 JXD2, JD6, JXD6, HJD6, HJXD6, HHJD6, HHJXD6, CJD6 JD6, JXD6, HJD6, HJXD6 100% Rated The Maximum Continuous Ampere Rating At 40°C (104°F) 60HZ 400HZ Enclosed After Derating Open Air Open Air 015 015 012 020 020 016 025 025 020 030 030 024 035 035 028 040 040 032 045 043 034 050 048 038 060 057 046 070 067 054 080 076 061 090 086 069 095 076 100 084 110 105 095 125 119 070 063 050 080 072 058 090 080 064 090 072 100 095 075 110 084 125 105 150 125 100 175 140 112 200 160 128 225 180 144 250 200 160 200 170 136 225 190 152 250 210 168 300 240 192 350 260 208 400 300 240 200 170 170 225 190 190 250 210 210 300 240 240 350 260 260 400 300 300 information provided on this page is intended for reference and recommendation only. Because several variables can act on a circuit breaker’s performance at the same time, the data above is based less on 6/100 75°C (167° F) Copper Cable per Pole No of Wire Pieces Size 1 #14 1 #12 1 #10 1 #10 1 #10 1 #8 1 #8 1 #8 1 #6 1 #4 1 #4 1 #3 1 #3 1 #2 1 #1 1 #4 1 #4 1 #3 1 #3 1 #2 1 #1 1 #1/0 1 #2/0 1 #3/0 1 #4/0 1 250 kcmil 1 #3/0 1 #4/0 1 250 kcmil 1 350 kcmil 1 500 kcmil 2 #3/0 2 #3/0 2 #4/0 1 250 kcmil 1 350 kcmil 1 500 kcmil 2 #3/0 Siemens Breaker Type LD6, LXD6, HLD6, HLXD6, HHLD6, HHLXD6, CLD6 LD6, LXD6, HLD6, HLXD6, 100% Rated MD6, MXD6, HMD6, HMXD6, CMD6 MD6, MXD6, HMD6, HMXD6, CMD6 100% Rated ND6, NXD6 HND6, HNXD6, CND6 ND6, NXD6 HND6, HNXD6, CND6 PD6, PXD6, HPD6, HPXD6, CPD6, 100% Rated PD6, PXD6, HPD6, HPXD6, CPD6 RD6, RXD6, HRD6, HRXD6 80% Rated Maximum Continuous Ampere Rating At 40° C (104° F) 60HZ 400/415HZ Enclosed After Derating Open Air Open Air 0250 0210 168 0300 0240 192 0350 0260 208 0400 0300 240 0450 0340 272 0500 0375 300 0600 0420 336 0250 0210 210 0300 0240 240 0350 0260 260 0400 0300 300 0450 0340 340 0500 0375 375 0600 0420 420 0500 0400 320 0600 0430 360 0700 0500 400 0800 0560 448 0500 0400 400 0600 0430 430 0700 0500 500 0800 0560 560 0800 0560 448 0900 0600 480 0650 520 1000 0780 624 1200 0900 0600 600 0650 650 1000 0780 780 1200 0780 624 1200 0850 680 1400 0960 768 1600 0780 780 1200 0850 850 1400 0960 960 1600 0960 768 1600 1800 1080 864 2000 1200 960 controlled testing, than on experience and engineering judgment. Contact Siemens for further information on special conditions and treatment. Additional derating may be required if the ambient temperature is greater than 40°C (104°F). Calculated 75° C (167° F) Copper Cable per Pole No of Wire Pieces Size 1 250 kcmil 1 350 kcmil 1 500 kcmil 2 #3/0 2 #4/0 2 250 kcmil 2 350 kcmil 1 250 kcmil 1 350 kcmil 1 500 kcmil 2 #3/0 2 #4/0 2 250 kcmil 2 350 kcmil 2 250 kcmil 2 350 kcmil 3 250 kcmil 3 300 kcmil 2 250 kcmil 2 350 kcmil 3 250 kcmil 3 300 kcmil 3 300 kcmil 3 350 kcmil 3 400 kcmil 4 350 kcmil 3 350 kcmil 3 400 kcmil 4 350 kcmil 4 400 kcmil 4 500 kcmil 5 500 kcmil 4 400 kcmil 4 500 kcmil 5 500 kcmil 5 500 kcmil 5 500 kcmil 6 500 kcmil after derating to compensate for the heating of the copper conductor, caused by the skin effect generated by eddy currents produced at 400/415HZ. Molded Case Circuit Breakers REFERENCE Typical Specifications General Specifications Molded case circuit breakers shall provide circuit overcurrent protection with inverse time and instantaneous tripping characteristics and shall be Siemens Sentron, Sensitrip or approved equal. All circuit breakers shall be CSA Certified and conform to applicable requirements of NEMA Standard Publication No. AB1. All circuit breakers shall have a quick-make, quick-break over center toggle type mechanism and the handle mechanism shall be trip free to prevent holding contacts closed against a short circuit or sustained overload. All circuit breaker handles shall assume a position between “ON” and “OFF” when tripped automatically. Multipole circuit breakers shall be common-trip such that an overload or short circuit on any one pole will result in all poles opening simultaneously. Arc extinction is to be accomplished by magnetic arc chutes. All ratings are to be clearly visible. When reverse feed is indicated on the drawings, in accordance with CSA, circuit breakers with sealed trip units shall be supplied. Solid State Sensing Specifications As indicated on the drawings, circuit breaker frames 400 Ampere through 3200-Ampere shall have microprocessorbased RMS sensing trip units, with the capability to measure through to the 21st harmonic. Automatic operation of all circuit breaker frames 400A and larger shall be obtained by means of solid state tripping elements providing inverse time delay and (instantaneous) and/or (short-time delay) circuit protection. Continuous current ratings shall be adjustable from 20% to 100% of the trip unit rating, without the need for a rating plug. Long-time delay and instantaneous trip shall be adjustable. The optional short-time trip function shall have adjustable pick-up settings, three fixed times, and I2t ramp. Circuit breaker frames 400A and larger, and where indicated on the drawings, shall be 100% equipment rated. Thermal Magnetic Specifications Motor Circuit Protectors Where indicated on the drawings and in the combination motor starter/motor control center schedule, furnish instantaneous magnetic trip only circuit breakers for motor short circuit protection. The magnetic trips shall be adjustable and accessible from the front of all circuit breakers frames. The continuous current rating shall be between 1 and 800 Amperes as indicated on the drawing. Integral Ground Fault Option Main and feeder circuit breakers, as indicated on the drawings, shall be provided with integral ground fault protection. Ground fault pick-up shall be adjustable from 20% to 70% of the circuit breakers maximum continuous current rating. Ground fault time delay shall be adjustable with three 12t ramps. Metering Option When indicated on the drawings, solid state trip breakers shall be furnished with a plug-in or panel mounted metering device. This device shall simultaneously display all three phase currents, as well as average current, ground current, and phase unbalance. In addition it shall display breaker status, a max log, and a trip log. The trip log will retain and display date, time and type of trip (overload, short circuit or ground fault) for the most recent 5 trip events. 6 Unless otherwise noted on the drawings, all Circuit breakers 2000 Ampere and below shall have thermal-magnetic trip units, with inverse time-current characteristics. Automatic operation of these circuit breakers shall be obtained by means of thermal-magnetic tripping devices located in each pole providing inverse time delay and instantaneous circuit protection. Circuit breakers shall be ambient compensating in that, as the ambient temperature increases over 40°C, the circuit breaker automatically derates itself so as to better protect its associated conductor. Thermal magnetic breakers from 250 to 2000A frames shall have thermal interchangeable trip units, with instantaneous magnetic trip settings that are adjustable and accessible from the front of all circuit breakers on frame sizes 250 Amperes and above. Where indicated, provide circuit breakers CSA Certified for application at 100% of their continuous ampere rating in their intended enclosure. The interrupting rating of the circuit breakers shall be as indicated in the specifications, and shown on the drawing or single line diagram. The interrupting rating of the circuit breakers shall be at least equal to the available short circuit current at the line terminals of the circuit breaker and correspond to the CSA Certified integrated short circuit current rating specified. Internal Accessories Provide shunt trips, bell alarms, and auxiliary switches as shown on the contract drawings. Gold plated auxiliary switches shall be supplied for PLC connection. Internal accessories for all breakers shall be CSA Certified for field installation and modification. Where indicated on the drawings, Siemens current limiting circuit breakers are to be furnished. Current limiting circuit breakers shall limit the let-through I2t to a value less than the I2t of one-half cycle wave of the symmetrical prospective current without any fusible elements when operating within its current range. Series Connected Combination Specifications Where protective devices are applied in series combination, such that the prospective available fault current exceeds the interrupting rating (AIR) of the downstream protective devices, such combinations shall be CSA Certified combinations. All electrical equipment using these CSA Certified circuit breaker combinations shall be clearly marked. Connection Accessories Unless otherwise noted, Mechanical lugs shall be provided with all Molded Case Breakers. Where indicated on the drawings, compression lugs shall be provided on 1200 Ampere frame and below circuit breakers. All compression lugs shall be supplied by the Circuit Breaker Manufacturer. Where indicated on the drawings, CSA Certified plug-in or rear connectors shall be supplied. 6/101 CIRCUIT BREAKERS Current Limiting Specifications Molded Case Circuit Breakers GENERAL Superseded Breakers 6 CIRCUIT BREAKERS Sentron Series Note Superseded Note Superseded CED62B015-CED62B125 CED62S100A CED63A001-CED63A125 CED63B015-CED63B125 CED63S100A - CLE62B015-CLE62B100 CLE62S100 CLE63A001-CLE63A125 CLE63B015-CLE63B100 CLE63S100 HHED62B015-HHED62B125 HHED63B015-HHED63B125 CE2B015-CE2B100 CE2S100 CE3B015-CEB100 CE3S100 HED62B015-HED62B125 HED63B015-HED63B125 CFD62A150, CFD62L150, CFD62A250 CFD62B070-CFD62B250 CFD62S250A CFD63A150, CFD63L150, CFD63A250 CFD63B070-CFD63B250 CFD63S250A CJD62B200-CJD62B400 CJD62H400, CJD62L400 CJD62S400A CJD63B200-CJD63B400 CJD63H400, CJD63L400 CJD63S400A CPD63B120-CPD63B160 CP3B120-CP3B160 ED21B015-ED21B100 ED22B015-ED22B100 ED22S100A ED23B015-ED23B100 ED23S100A E21B015-E21B100 E22B015-E22B100 E22S100A E23B015-E23B100 E23S100A ED41B015-ED41B100 ED42B015-ED42B125 ED42S100A ED43B015-ED43B125 ED43S100A E41B015-E41B100 E42B015-E42B100 E42S100 E43B015-E43B100 E43S100 ED61B015-ED61B100 ED62B015-ED62B125 ED62S100A ED63A001-ED63A125 ED63B015-ED63B125 ED63S100A CED62B015-CED62B125 CED62B015-CED62B125 E61B015-E61B100 E62B015-E62B100 E62S100A E63A001-E63A125 E63B015-E63B100 E63S100A HHED62B015-HHED62B125 HHED63B015-HHED63B125 FD62B070-FD62B250 FD63B070-FD63B250 , FXD62A150, FXD62L150, FXD62A250 FXD62B070-FXD62B250 FXD62S250A FXD63A150, FXD63L150, FXD63A250 FXD63B070-FXD63B250 FXD63S250A HED41B015-HED41B100 HED42B015-HED42B125 HED43B015-HED43B125 CED62B015-CED62B125 CED63B015-CED63B125 HFD62B070-HFD62B250 HFD63B070-HFD63B250 CED62B015-CED62B125 CED63B015-CED63B125 , , , CLF62A150, CLF62A250 CLF62B070-CLF62B240 CLF62S250 CLF63A150, CLF63A250 CLF63B070-CLF63B250 CLF63S250 CLJ62B100-CLJ62B400 CLJ62L400, CLJ62H400 CLJ62S400 CLJ63B200-CLJ63B400 CLJ63L400, CLJ63H400 CLJ63S400 EE1B015-EE1B100 EE2B015-EE2B100 EE2S100 EE3B015-EE3B100 EE3S100 EH1B015-EH1B100 EH2B015-ED2B125 EH2S100 EH3B015-EH3B100 EH3S100 EF1B015-EF1B020 EF2B015-EF2B100 EF2S100 EF3A003, EF3J050, EF3L050-EF3A100, EF3H1 EF3B015-EF3B100 EF3S100 HED62B015-HED62B125 HED63B015-HED63B125 - HE41B015-HE41B100 HE42B015-HE42B100 HE43B015-HE43B100 HED61B015-HED61B100 HED62B015-HED62B125 HED63B015-HED63B125 CJ2B300-CJ2B400 CJ2S400 CJ3B300-CJ3B400 CJ3S400 - F62B070, F62B250 F63B070-F63B250 FJ62A150, FJ62L150-FJ62A250 FJ62B070-FJ62B250 FJ62S250 FJ63A150, FJ63L150-FJ63A250 FJ63B070-FJ63B250 FJ63S250 CJ2B125-CJ2B250 CJ3B125-CJ3B250 FJ2B070-FJ2B225 FJ2S225 FJ3A225 FJ3B070-FJ3B225 FJ3S225 - HE61B015-HE61B100 HE62B015-HE62B110 or (HE2B015-HE2B100) HE63B015-HE63B100 or (HE3B015-HE3B100) HF62B070-HF62B250 HF63B070-HF63B250 - HHED62B015-HHED62B125 HHED63B015-HHED63B125 HED62B015-HED62B125 HED63B015-HED63B125 HJD63B200-HJD63B400 HJ63B200-HJ63B400 HLD63B250-HLD63B600 HL63B450-HL63B600 HMD63B500-HMD63B800 HN3B500-HN3B800 - HND63B100-HND63B120 HK3B100-HK3B120 - HPD63B120-HPD63B160 HP3B120-HP3B160 - HRD63B160-HRD63B200 HR3B160-HR3B200 - 1 Mechanically and electrically interchangeable. 2 Electrically interchangeable only, refer to sales office for further details. 3 Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 200 kA at 480V AC 100 kA at 600V AC 6/102 4 Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 150 kA at 480V AC 100 kA at 600V AC 5 Refer to local sales office for replacement information. HJ3B125-HJ3B400 HL3B450-HL3B600 6 Effective 1994 — The FD6 and FXD6 types have been replaced by FD6-A and FXD6-A type thermal / magnetic circuit breakers — mechanically and electrically interchangeable with the exception that FXD6-A and FD6-A have 22kA at 600V AC ratings versus 18kA at 600V AC for types FXD6 and FD6. Molded Case Circuit Breakers GENERAL Superseded Breakers Sentron Series Note Superseded Note Superseded JD62B200-JD62B400 JD63B200-JD63B400 JLB200-JL62B400 JL63B200-JL63B400 JL2B070-JL2B400 JL3B0L0-JL3B400 JXD22B200-JXD22B400 JXD22S400A JXD23B200-JXD23B400 JXD23S400A JD22B200-JD22B400 JD22S400 JD23B200-JD23B400 JD23S400 JXD62B200-JXD62B400 JXD62H400, JXD62L400 JXD62S400A JXD63B200-JXD63B400 JXD63H400, JXD63L400 JXD63S400A JJ62B200-JJ62B400 JL62L400, JL62H400 JJ62S400A JJ63B200-JJ63B400 JL63A400, JL63H400, JL63L400 JJ63S400A LD62B250-LD62B500 LD62B250-LD63B600 LL63B250-LL62B600 LL63B250-LL63B600 LXD62B450-LXD62B600 LXD62J600, LXD62L600 LXD62S600A LXD63B450-LXD63B600 LXD64H600, LXD63L600 LXD63S600A MD62B500-MD62B800 MD63B500-MD63B800 MXD62A800, MXD62H800, MXD62L800 MXD62S800A MXD63A800, MXD63H800, MXD63L800 MXD63S800A ND63B100-ND63B900 NXD63A120A PD63B120-PD63B160 PXD63S160A RD63B160-RD63B200 QJ22B060-QJ22B225 QJ22B060H-QJ22B225H QJ22S225 QJ23B060-QJ23B225 QJ23B060H-QJ23B225H QJH22B060-QJH22B225 QJH23B060-QJH23B225 QJH23S225 RD63B160-RD63B200 RXD63S200A SHJD69200-SHJD69400 SHJD69200G-SHJD69400G SHJD69200NGT-SHJD69400NGT SHJD69200NT-SHJD69400NT SHLD69300-SHLD69600 SHLD69300G-SHLD69600G SHLD69300NGT-SHLD69600NG SHLD69300NT-SHLD69600NT SHND69100A-SHND69120A SHND69100AG-SHND69120AG SHPD69120-SHPD69160 SHPD69120G-SHPD69160G LJ62B450-LJ62B600 LL2H600, LL2U600, LL2X600 LJ62S600 LJ63B450-LJ63B600 LL63H600, LL63L600 LJ63S600A JD2B250-JD2B400 JD2S400 JD3B250-JD3B400 JD3S400 JJ2B250-JJ2B400 JL2L400-JL2H400 JJ3B200-JJ3B400 JL3H400, JL3L400, JL3A225 LL2B450-LL2B600 LL3B450-LL3B600 LL3A450, LL3H600 LL3S600 KM2B500-KM2B800 KM3B500-KM3B800 - KM2A800, KM2H800, KM2L800 KM2S800 KM3A600, KM3H800, KM3L800 KM3S800 - KP3B100-KP3B900 KP3S120 - HP3B120-HP3B160 HP3S160 - HR3B160-HR3B200 - QJ2B125-QJ2B225 QJS225 QJ3B125-QJ3B225 - - QJ2H125-QJ2B225 QJ3H125-QJ3H225 QJ3S225 - HR3B160-HR3B200 HR3S200 - SHJ63B200-SHJ63B400G SHJ63B200G-SHJ63B400G SHJ63N200G-SHJ63N400G SHJ63N200-SHJ63N400 - SHL63B300-SHL63B600 SHL63B300G-SHL63B600G SHL63N300G-SHL63N600G SHL63N300-SHL63N600 - 1 Mechanically and electrically interchangeable. 2 Electrically interchangeable only, refer to sales office for further details. SHND69100-SHND69800 SHND69100G-SHND69800G SHPF3B120-SHPF3B160 SHPF3B120G-SHPF3B160G 3 Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 200 kA at 480V AC 100 kA at 600V AC 6 CIRCUIT BREAKERS SHKF3B100-SHKF3B800 SHKF3B100G-SHKF3B800G - 4 Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 150 kA at 480V AC 100 kA at 600V AC 5 Refer to local sales office for replacement information. 6/103 Molded Case Circuit Breakers GENERAL Superseded Breakers New Sentron Series Note Superseded Note Superseded SHND69100NGT-SHND69800NGT SHND69100NT-SHND69800NT SHKF3N100G-SHKF3N800G SHKF3N100-SHKF3N800 SHK3N100G-SHK3N600G SHK3N100-SHK3N600 SHPF3B120-SHPF3B160 SHPF3B120G-SHPF3B160G SHPF3N120-SHPF3N160 SHPF3N120G-SHPF3N160G SJD69200-SJ369400 SJD69200G-SJD69400G SJD69200NGT-SJD69400NGT SJD69200NT-SJD69400NT SLD69300-SLD69600 SLD69300G-SLD69600G SLD69300NGT-SLD69600NGT SLD69300NT-SLD69600NT SMD69600A-SMD69800A SMD69600AG-SMD69800AG SMD69600ANGT-SMD69800ANGT SMD69600ANT-SMD69800ANT SND69800A-SND69120A SND69800AG-SND69120AG SND69800ANGT-SND69120ANGT SND69800ANT-SND69120ANT SPD69120-SPD69160 SPD69120G-SPD69160G SPD69120NGT-SPD69160NGT SPD69120NT-SPD69160NT — SHP3B120-SHP3B800 SHP3B120G-SHP3B800G SHP3N120-SHP3N800 SHP3N120G-SHP3N800G — — — — SJL63B200-SJL63B400 SJL63B200G-SJL63B400G SJL63N200G-SJL63N400G SJL63N200-SJL63N400 — — — — SLL63B300-SLL63B600 SLL63B300G-SLL63B600G SLL63N300G-SLL63N600G SLL63N300-SLL63N600 — — — — SMD69600-SMD69800 SMD69600G-SMD69800G SMD69600NGT-SMD69800NGT SMD69600NT-SMD69800NT SND69100-SND69800 SND69100G-SND69800G SND69100NGT-SND69800NGT SND69100NT-SND69800NT SKMF3B600-SKMF3B800 SKMF3B600G-SKMF3B800G SKMF3N600G-SKMF3N800G SKMF3N600-SKMF3N800 SKPF3B100-SKPF3B600 SKPF3B100G-SKPF3B600G SKPF3N100G-SKPF3N600G SKPF3N100-SKPF3N600 SHPF3B120-SHPF3B160 SHPF3B120G-SHPF3B160G SHPF3N120-SHPF3N160G SHPF3N120G-SHPF3N160G — — — — BQCC1B015-BQC1B030 — — — — CC1B015-CC1B030 CC2B015-CC2B030 CC3B015-CC3B030 — — — — EF2A003, EF2H050, EF2L050, EF2A100, EF2H150, EF2L150 — — — — — EH1B015-EH1B100 EH2B015-EH2B100 EH3B015-EH3B100 — — — — — — HE2A003, HE2H050, HE2L050-HE2A100 HE3A003, HE3H050, HE3L050-HE3A100 HE3B015-HE3B100 — — — 6 CIRCUIT BREAKERS 1 2 3 Mechanically and electrically interchangeable. Electrically interchangeable only, refer to sales office for further details. Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 200 kA at 480V AC 100 kA at 600V AC 6/104 4 5 Electrically interchangeable only if the system interrupting capacity is less than or equal to: 200 kA at 240V AC 150 kA at 480V AC 100 kA at 600V AC These units are for replacement purposes only. Consult sales office for availability. 6 These units are no longer manufactured, and no replacement is available.