test report 757312-10

Anuncio
ABB Power Grids
Switzerland Ltd.
Customer
Ordernumber
Order item
page 1 / 4
ABB POWER GRIDS PERU S. A.
757312
10
Type of arrester
Pieces
Test station
POLIM-K 19-50
6
Mittelspannung 1
Test report
Factory tests on Metal-oxide Surge Arresters without gaps (MO-arresters)
Standard: IEC 60099-4, 60Hz
ABB internal test specification: HATW600359
This test report contains 4 pages
- Cover sheet
- measured values
- Legend
Date: 27. Januar 2021
Factory test carried out
A
1
All the tested arresters fulfil the electrical specifications
ABB Power Grids Switzerland Ltd.
Surge Arresters PGHV
Jurastrasse 45
CH-Wettingen
www.abb.com/arrestersonline
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization
of its contents in whole or in parts is forbidden without prior written consent of ABB Power Grids AG. Copyright © 2019 ABB Power Grids. This is an
electronically generated report hence does not require signature.
ABB Power Grids
Switzerland Ltd.
Customer
Ordernumber
Order item
page 2 / 4
ABB POWER GRIDS PERU S. A.
757312
10
Type of arrester
Pieces
Test station
POLIM-K 19-50
6
Mittelspannung 1
Arrester data
Operating voltage
AC reference current
Frequency
PD-Test
= 19.00
= 1.60
= 60.00
= 19.95
Hz
Test sequence
Required values
1. Reference voltage
2. Partial discharges
3. Leakage current
at
at
at
PD
= 23.75 .... 26.22
<= 5.0
= 0.30 .... 0.75
pC
Ambient conditions during test
Airpressure
Relative humidity
19.3 %
Ambient temperature
26.1 ° C
Measured
values
Serial number
Date
13492904
13492905
13492906
13492907
13492908
13492909
2021-01-26
2021-01-26
2021-01-26
2021-01-26
2021-01-26
2021-01-26
24.39
24.08
24.20
24.14
24.41
24.26
0.59
0.61
0.60
0.60
0.58
0.59
PD
pC
Passed
<= 5.0
<= 5.0
<= 5.0
<= 5.0
<= 5.0
<= 5.0
OK
OK
OK
OK
OK
OK
** According MO-block allocation
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization
of its contents in whole or in parts is forbidden without prior written consent of ABB Power Grids AG. Copyright © 2019 ABB Power Grids. This is an
electronically generated report hence does not require signature.
ABB Power Grids
Switzerland Ltd.
Customer
Ordernumber
Order item
page 3 / 4
ABB POWER GRIDS PERU S. A.
757312
10
Type of arrester
Pieces
Test station
POLIM-K 19-50
6
Mittelspannung 1
Principle diagram of test circuit
Principle test sequence
Typical current- / voltage curves
Note: the given current and voltage curves are for information only. Deciding for the result of the routine test is exclusively
the value in the list of measuring results.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization
of its contents in whole or in parts is forbidden without prior written consent of ABB Power Grids AG. Copyright © 2019 ABB Power Grids. This is an
electronically generated report hence does not require signature.
ABB Power Grids
Switzerland Ltd.
Customer
Ordernumber
Order item
page 4 / 4
ABB POWER GRIDS PERU S. A.
757312
10
Type of arrester
Pieces
Test station
POLIM-K 19-50
6
Mittelspannung 1
Legend
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization
of its contents in whole or in parts is forbidden without prior written consent of ABB Power Grids AG. Copyright © 2019 ABB Power Grids. This is an
electronically generated report hence does not require signature.