APPENDIX A TABLE OF CONTENTS CHANGING THE DCE POWER SUPPLY................................................................... 1 CHANGING THE GLOBAL DCE POWER SUPPLY ................................................. 6 CHANGING THE AC WELDER POWER SUPPLY ................................................. 16 PROCEDURE FOR POWER VERIFICATION .......................................................... 19 PROGRAMMING STUD LENGTH DETECTION (WELD HEADS) ....................... 20 PROGRAMMING ANGULARITY (WELD GUNS) .................................................. 22 ADJUSTING STUD STICKOUT (WELD HEAD) ..................................................... 23 ADJUSTING STUD STICKOUT (WELD GUN) ....................................................... 24 CLEAR RAM PROCEDURE....................................................................................... 25 PK560 HANDGUN SET-UP (3 STEPS) .................................................................... 27 PISTON LUBRICATION PROCEDURE .................................................................... 30 PISTON TIP AIR FLOW PROCEDURE FOR NUT WELD HEADS ........................ 36 PROPER ETF20 FEEDER SETUP PROCEDURE ..................................................... 44 CHANGING THE DCE POWER SUPPLY IMPORTANT SAFETY NOTE: HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE DCE CONTROL. TURN OFF AND LOCK OUT ALL 480VAC INPUT POWER TO DCE WELDER CONTROL CABINET BEFORE CONTINUING WITH THIS PROCEDURE VERIFY WITH VOLTMETER THAT After securing and locking out the input power to the DCE cabinet, open the 480VAC INPUT POWER HAS BEEN front door of the DCE and remove the top cover. Continue with the procedure on the next page. TURNED OFF CONTINUE TO NEXT PAGE 1 Loosen three Philips screws and remove the wires Dismount Relay K1 Flat head screw driver You may need to push the DIN bracket back in order to access the release tab on the K1 relay CONTINUED NEXT PAGE 2 Loosen the flat head screw on the terminal block and pull ground wire out Remove wire-run strip covers as necessary X-20 Remove the brown and white wires on X-20. These wires are going to the Safety Module Pcb. CONTINUED NEXT PAGE 3 Remove Fiber Optic connection Remove X-14 connector Fan +24v power su p p l y X-20 wires X-6 X-14 Remove X-6 connector SOW +15v power supply connector Remove two 13mm hex bolts CONTINUED NEXT PAGE 4 Lift power supply by the support bars and remove The K-1 relay is left inside the controller Filter END OF PROCEDURE 5 CHANGING THE GLOBAL DCE POWER SUPPLY Remove welder cover by removing these 4 bolts. Note: There is a ground cable attached to cover. It is OK to let the cover hang on this cable 6 With power turned off, open the cabinet door. Note the Plexi-glass inner door. Open Plexi-glass inner door by first removing the top screw. 7 Next, remove the bottom 2 screws Remove the ground cable under the bottom Plexi-glass door hinge. 8 Open the Plexi-glass door then remove it by removing the upper and lower door hinges. Remove the upper ground wire from the terminal strip next to the Relay K1 9 NOTE: Unless there is something wrong with Relay K1 it will be used on the new power supply Relay K1 To remove K1, push down on the top of the relay and swing the bottom out 10 Remove the three wires on the bottom of Relay K1 Lift K1 off of the mounting rail Remove the Wire Harness Cover adjacent to the PWM (Pulse Width Modulator) board. Locate small white floating terminal strip X20 inside the harness run 11 Remove the brown and white wires from the bottom of X20 Remove Wire Harness Cover that runs along the top of the power supply. 12 X14 (2-pin) X6 (3-pin) Remove connectors X14 and X6 from the PWM board. Remove Fiber-Optic cable from upper left hand side of PWM board 13 The bundle of cables disconnected from the SMPS Power Supply. Fiber optic cable X14 X6 X20 Remove the ASSIST Box cable connection from the Ethernet Board (If applicable) ZCPU board Ethernet board 14 Remove the 2 hex bolts at the bottom of the SMPS Power Supply Slide SMPS Power Supply out front of Welder Control. Reverse this procedure to re-install the new SMPS Power Supply. 15 CHANGING THE AC WELDER POWER SUPPLY 1. Remove wires from top of Power Supply Grounding wire (not shown in this picture) X5-1 Brown F10 Brown F11** White X6-1 White X3-2 Brown X3-1 White Yellow Green Always label all wires disconnected from Power Supply **Note: The schematics call this F12 and not F11. This may or may not be labeled F11 on your control; always consider this slot and Fuse as F12. A. When this fuse is bad 1. “Measurement Line Broken” all active outlets 2. “Common Measurement Line Broken” 3. No power LED’s on Head 1 Driver board and Weld Common Driver Board SEE PICTURE BELOW Weld Common Driver Bd. Head 1 Driver Bd. Head 1 Weld Power Cable Weld Common Weld Power Cable 16 2. Remove wires from Relay K1 and dismount relay from bracket Remove these three wires Remove these four wires Green Brown White Yellow 3. Remove Fiber Optic cable and indicated wire connections from PWM Board Wire Run Cover X4 Fiber Optic Cable X6 X19 17 4. Remove bolts from bracing bracket at top of Power Supply. Bolts 5. Remove mounting bolts at bottom of Power Supply Bolts 6. Remove all cabling that exit the bottom of the Control Cabinet (weld power cables, etc.) 7. Slide Power Supply out the front of the cabinet. Reverse procedure to reinstall. 18 PROCEDURE FOR POWER VERIFICATION Examine the Green LED H1 on the outside of the front door of the DCE Control. If Green LED is on, continue troubleshooting with your ORIGINAL fault. If Green LED is off, perform the following steps H1 1. Verify that there is 480VAC +/- 10%, 60 cycle, 3-phase) to the controller, and (should be 277VAC +/- 10% in reference to ground). If not, repair plant power. If power is OK continue with step 2. 2. Open the cabinet door and power up the control. On the inside of the front door near the top is the Auxiliary Power Supply Board (see the figure below). Verify that the Red LED’s (D1 through D5, and D10) on the board are lit. If any of the Red LED’s are out proceed to step 3. If not, proceed to step 2 A. F5 under cover D5 D10 CAUTION 480VAC and 230VAC are present under this cover. D4 F3 F4 F2 F1 D3 D2 D1 X9 A) B) C) If all LED’s are lit, disconnect X9 on the door power supply and carefully check for 24vdc between pins 1 & 2 on the board itself. If 24vdc is present, the green LED is defective. Continue troubleshooting your original fault. Replace the green LED at the earliest opportunity. If 24vdc is not present, continue troubleshooting your original fault and replace the Auxiliary Power Supply Board at the earliest opportunity. 3. If any of the red LED’s are out. A) Secure power to the control and remove the corresponding fuse to the LED that is out and check it (Note: The fuse for D3 is F4 and the fuse for D4 is F3; also, do not forget about the fuse under the cover). Replace defective fuse and power up control checking for green led H1 on front door of DCE Cabinet. B) Secure power to the control and remove F1 through F6 on the Fuse Bank and check fuses (See Appendix B Fig. 7). If any are defective replace fuse(s) and power up control checking for green led. If the fuses are ok, replace the door power supply. 4. Once you have the Green LED lit, reset faults if possible and proceed with troubleshooting any remaining faults. 19 PROGRAMMING STUD LENGTH DETECTION (WELD HEADS) This program will prevent welding if there are deviations of stud preload or stick-out. **You must have a part present, clamped, in a weld position, and stick-out properly adjusted (SEE “ADJUSTING STUD STICKOUT” IN APPENDIX A) to perform this setup** Activate Stud Length Detection for Single Weld Applications. 1. 2. 3. 4. 5. At the keypad and from the Main Menu scroll down to Programming and press <Enter>. With Outlet Programming Highlighted press <Enter>. Outlet _ will be flashing; Enter the outlet # and press <Enter>. Scroll down to Check Stud Length and press + to change from no to yes. Use the right arrow and move to <Teach> Press <Enter>. When the keypad shows the “Warning Entering Test Mode” press <Enter>. 6. At Teach Length - Press F6 and <Enter> at the same time. When the keypad shows “Function Complete” press <Enter>. There will now be a Value (Ref) listed. This is the measured preload and your programmed penetration can never exceed this value. 7. Scroll Down to Check Length - Press F6 and <Enter> at the same time. When the keypad shows “Function Complete” press <Enter>. This will show any measured deviation in the difference line which you will need to consider when programming a tolerance. 8. Scroll down to Tolerance – Select a tolerance from .300mm to 2.000mm by using the + or – on the keypad. 9. Scroll down to <> this will take you back to Check Stud Length, press <Enter> to save the values. 10. Test to see if program is working correctly. Activate Stud Length Detection for Multiple Welding Applications. 1. At the keypad and from the Main Menu scroll down to Programming and press <Enter>. 2. With Outlet Programming highlighted press <Enter>. 3. Outlet _ will be flashing; Enter the outlet # and press <Enter>. 4. Scroll down to Check Stud Length and press + to change from no to yes and press <Enter>. 5. Press <Esc> 6. Scroll down to Weld Programming and press <Enter>. 7. Outlet _ will be highlighted; enter the outlet # and press <Enter>. 8. Weld Program _ will be highlighted; enter the program # and press <Enter>. 9. Scroll down to Check Stud Length and press + to change from Outlet to Program. 10. Use the right arrow and move to <Teach> Press <Enter>. When the keypad shows the “Warning Entering Test Mode” press <Enter>. 11. At Teach Length - Press F6 and <Enter> at the same time. When the keypad shows “Function Complete” press <Enter>. There will now be a Value (Ref) listed. This is the measured preload and your programmed penetration can never exceed this value. 12. Scroll Down to Check Length - Press F6 and <Enter> at the same time. When the keypad shows “Function Complete” press <Enter>. This will show any measured deviation in the difference line which you will need to consider when programming a tolerance. 20 13. Scroll down to Tolerance – Select a tolerance from .300mm to 2.000mm by using the + or – on the keypad. 14. Scroll down to <> this will take you back to Weld Program Standard. Scroll up to Graphical Monitoring and press <Enter> to save the values. 15. Test to see if program is working correctly. 16. Advance the robot to the next weld point and repeat steps 7 thru 16 to the remaining points. 21 PROGRAMMING ANGULARITY (WELD GUNS) This program will prevent welding if the gun is not in proper position with regard to the programmed angularity. **You must have a part present, clamped and stick-out properly adjusted (SEE “ADJUSTING STUD STICKOUT” IN APPENDIX A) to perform this setup** 1. 2. 3. 4. 5. At the keypad and from the Main Menu scroll down to Programming and press <Enter>. With Outlet Programming Highlighted press <Enter>. Outlet _ will be flashing; Enter the outlet # and press <Enter>. Scroll down to Angularity and press + to change from no to yes. Use the right arrow and move to <Teach> Press <Enter>. When the keypad shows the “Warning Entering Test Mode” press <Enter>. 6. The Teach Position Value (Ref) will be highlighted and the green LED on the rear of the gun will be flashing. a. Press the gun on the part firmly seating the flash shield. b. Pull the trigger and release. Note: It will not weld at this point When the keypad shows “Function Complete” press <Enter>. There will now be a Value (Ref) listed. This is the measured preload and your programmed penetration can never exceed this value. 7. Scroll Down to Check Position Difference. The green LED on the rear of the gun will be flashing. a. Press the gun on the part firmly seating the flash shield. b. Pull the trigger and release. When the keypad shows “Function Complete” press <Enter>. This will show any measured deviation in the difference line which you will need to consider when programming a tolerance. 8. Scroll down to Tolerance – Select a tolerance from .050mm to 2.000mm by using the + or – on the keypad. 9. Scroll down to <> this will take you back to Angularity, press <Enter> to save the values. 10. Test to see if program is working correctly. 22 ADJUSTING STUD STICKOUT (WELD HEAD) ***Weld Head must be plugged into an ETF feeder and Air Supply should be on and at the proper pressure.*** Loosen Collar Stabilizer Loosen Adjustment Screws Stick-Out Gauge 2mm 1. 2. 3. Loosen the adjustment screws and collar screws as needed. Adjust stabilizer as needed to achieve stud stickout per drawing above. Tighten all screws and recheck with gauge. 23 ADJUSTING STUD STICKOUT (WELD GUN) Flash Shield Loosen Adjustment Screws On each side Stick-Out Gauge 2mm 1. 2. 3. Loosen the adjustment screws and collar screws as needed. Adjust flash shield as needed to achieve stud stickout per drawing above. Tighten all screws and recheck with gauge. 24 CLEAR RAM PROCEDURE IMPORTANT: Write down all of the “Outlet Programming” and “Weld Programming” values as these values will be lost after performing this procedure. 1. Turn off main power switch to DCE Control. Wait 30 seconds. Open the door of DCE Control. 2. Locate the DCE ZCPU Board on right wall inside the DCE Control. 3. Locate the Dip Switches on the DCE ZCPU Board. SEE PICTURE ON THE FOLLOWING PAGE. 4. Turn Dip Switch 2 “on”. Dip Switches on the DCE ZCPU Board are looked at ONLY during “power up” of the DCE Control. 5. Close door to cabinet and power up the DCE Control. The RAM should now be cleared. You must now reprogram the “Outlet Programming” and “Weld Programming” under the “Main Menu” “Programming”. IMPORTANT: After reprogramming the DCE Control, it is STRONGLY recommended that you turn the DCE Control off, wait 30 seconds, then open the door of the DCE Control and turn Dip Switch 2 “off”. Normal position for all Dip Switches is “off”. If this is not done, the next time you cycle power on the DCE Control with Dip Switch 2 still “on”, you will again clear the RAM. SEE NEXT PAGE FOR PICTURE OF DCE ZCPU BOARD 25 DCE ZCPU Board OFF ON 8 1 DIP SWITCHES NOTE: DIP SWITCHES ARE “OFF” FOR NORMAL OPERATION. ALL DIP SWITCH POSITIONS ARE REGISTERED ONLY AT DCE CONTROL POWER-UP 26 PK560 HANDGUN SET-UP (3 STEPS) 1. SETTING LIFT Flash Shield .045” lift gauge BACK direction Loosen Flash Shield setscrew -Loosen Flash Shield setscrew, pull flash shield fully back (this may require force). -Push on stud with .045” tooth of lift gauge as far back as it will go; hold gauge at that position. -Carefully pull Flash Shield forward to gauge. Hold Flash Shield at that position and tighten Flash Shield set screw. -With stud in collet, push down on gun until flash shield sits squarely on a flat surface. Hold at this position for the remainder of Angularity adjustment. 2. SETTING ANGULARITY -Turn 1.5mm allen wrench clockwise until “” LED turns off, then turn counter-clockwise until the “” LED just barely turns on. -This is perfect Angularity. Adjust more counter-clockwise for less Angularity sensitivity. Flash Shield PKE BOX CONTINUED NEXT PAGE 27 PK560 HANDGUN SET-UP (continued) At the DCE Keypad, press “ESC” key until “Main Menu” is displayed at the top of the screen. 1. Use the <> arrow key to select the line “System Configuration”; press “Enter” key. 2. Use the <> arrow key to select the line “System Parameters”; press “Enter” key. 3. Use the <> arrow key to select the line “Outlet 1…PKE”; press “Enter” key. You should now see the following screen: Outlet 1 Configuration PKE --------------------------------------Program Select Switch.........no Program Select Sensor.........no Mechanical Angularity Switch..yes Mechanical Counter............no Slide Rail Valves.............Intern Stud Arrival Sensor...........no Air Pressure Monitor..........no Gas Pressure Monitor..........no Color Mark....................no Airblow.......................no Page 2.<> --------------------------------------Help Message Area 4. Use the <> arrow key to select the line “Mechanical Angularity Switch”. Use the <+> or <-> keys to ensure that this line reads “yes”; press “Enter” key. 3. SETTING DROP DOWN TIME FOR PK560 HANDGUN At the DCE Keypad, press “ESC” key until “Main Menu” is displayed at the top of the screen. 1. Use the <> arrow key to select the line “Service Functions”; press “Enter” key. 2. Use the <> arrow key to select the line “Cycle Functions”; press “Enter” key. You should now see the following screen: Cycle Functions ---------------------------------------| 1 | 2 | 3 | 4 | 5 ----------+-----+-----+-----+-----+----Cycle |..?..|..?..|..?..|..?..|..?.. SKK ext. |..?..|..?..|..?..|..?..|..?.. SKK ret. |..?..|..?..|..?..|..?..|..?.. Start feed|..?..|..?..|..?..|..?..|..?.. Lift |..?..|..?..|..?..|..?..|..?.. Set WC |..?..|..?..|..?..|..?..|..?.. Color mark|..?..|..?..|..?..|..?..|..?.. Reference output: 1 SKK ext. . 0 ms Drop time...11,5 ms SKK ret. . 0 ms Lift dist. . 0,0 mm ---------------------------------------Help Message Area 3. Loosen (slightly unscrew) the black cap on the back of the PK560 handgun. 4. With a stud in the collet, hold the PK560 handgun firmly onto a grounded piece of metal. Ensure that the Flash Shield is completely seated on the metal. (CONTINUED ON NEXT PAGE) 28 PK560 HANDGUN SET-UP (continued) 5. Pull the Trigger on the PK560 handgun. The stud will lift and drop without welding. On the lower right side of the keypad, read the “Drop Time” in ms- mille seconds. a. The desired “Drop Time” time reading is between 11.0ms and 11.5ms. b. To adjust this time proceed to step 6. 6. Using a flat standard screwdriver, adjust the Plunge Spring tension by turning the adjustment screw just inside the center of black cap that you loosened earlier. NOTE: After each adjustment of the Plunge Spring tension, repeat a. Turn adjustment clockwise to decrease “Drop Time”. b. Turn adjustment counter-clockwise to increase “Drop Time”. Repeat Steps 4 through 6 until the “Drop Time” reads between 11.0ms and 11.5ms. 7. Once you have adjusted the “Drop Time” to a value between 11.0ms and 11.5ms, carefully tighten the black cap on the back of the PK560 without moving the adjustment screw. It might be helpful to keep the screwdriver in place while tightening the black cap. 29 PISTON LUBRICATION PROCEDURE 1. You’re Weld Head, Piston and Front end Components will differ depending on the style and fastener being welded. 2. This procedure applies to all Weld Guns also. Boots not shown were removed for clarity. Remove front end components to gain access to the piston assembly. 30 Remove Piston Assembly Clean Piston Head and O-Ring 31 Clean the inside of the Load Tube thoroughly with a clean cloth. Carefully remove the O-Ring and clean the groove. Clean and inspect the O-Ring for wear and replace if necessary. 32 Place the O-Ring in the groove. With your finger spread the O Lube that was expelled by the O-Ring, around the O-Ring. 33 Apply the remaining Parker O Lube on your finger inside the Load Tube, and spread evenly Insert the piston and move it back and forth a few times to help spread the O Lube. The piston should move freely. 34 Wipe excess Parker O Lube off the face of the Load Tube with a clean rag. Reassemble the front end of the weld tool. Install new boots if they are missing or damaged. (not shown) 35 PISTON TIP AIR FLOW PROCEDURE FOR NUT WELD HEADS STEP 1 Feeder Input Air Regulator First check the air regulator settings on the feeder. These regulators provide air to the piston air flow –control. (the flow-control itself is mounted on the side of the weld head) Head Forward Air Regulator STEP 2 Feeder Input Air Regulator Adjust Feeder Input Air Regulator to the standard setting for your production plant. NOTE: No less than 80psi. 90psi is preferable. WARNING: All subsequent adjustments in this procedure flow from this setting. Changing this adjustment during normal operation will affect the piston air flow. 36 STEP 3 Head Forward Air Regulator Adjust Head Forward Air Regulator to 40psi. WARNING: Changing this adjustment during normal operation will affect the piston air flow. NOTE: You will only have a reading on this dial when the weld head extends pneumatically to the forward position. (See steps 5 through 9 if you want to manually extend the head to make this adjustment). STEP 4 Ensure accessibility to the front of the weld head. Remove Nut from the collet. 37 STEP 5 At Control Keypad, select “Service Functions” from the “Main Menu”. Press the “Enter” key. STEP 6 At Control Keypad, select “Cycle Functions” from the “Service Functions” menu. Press the “Enter” key. STEP 7 38 STEP 8 Select the line “SKK F-pos.” under the appropriate column number for the specific head you are adjusting. See next page. 39 STEP 9 While holding down the “F6” key, press the “Enter” key. The weld head should pneumatically extend to the forward position. STEP 10 With the head extended forward, you should now hear and feel air coming out the end of the collet. Insert the tube of the Flow Meter into the empty collet. Ensure that the tube covers the tip of the Piston. SEE NEXT PAGE 40 Flow Meter tube Piston tip This is what should be happening when you insert the Flow Meter tube into the empty collet. Piston tip should be inserted in the Flow Meter Tube. Collet shown removed here for clarification. STEP 11 Adjust the piston Flow Control mounted on the side of the Nut Weld Head so that the registered flow on the Flow Meter reads 40 l/min. SEE NEXT PAGE. 41 Top of the ball hits the 40 l/min. mark. STEP 12 Select the line “SKK R-pos.” under the column number for the specific head you are adjusting. See next page. 42 STEP 13 While holding down the “F6” key, press the “Enter” key. The weld head should pneumatically move to the rear position. Now hit the “Esc” key repeatedly until you exit the “Cycle Functions” mode. Return to normal operation. 43 PROPER ETF20 FEEDER SETUP PROCEDURE The following settings are required for proper operation of the ETF20 Feeder: Go to main menu on Emhart key pad. Scroll down to “Programming” press “Enter”. “Outlet Programming” press “Enter”. 44 Input the outlet # to which ETF 20 feeder is connected to: “#” press “Enter”. (Note: There are 3 pages of parameters for this step) Scroll down to next page. The following are the required settings for this feeder: Set these parameters on this page: Container Up time …… 2200 ms Container Down time …. 1200 ms 45 Scroll down to next page and set these parameters Maximum hopper steps……………………………………. 30 Bowl Delay………………………………………………… 0 studs Press Enter after you have completed with your settings to save them. 46 Important Feeder Hardware Adjustments Feeder / Hopper door opening for 27mm and 25.5mm Large Flange studs Emhart Number 29933 and 29646 needs to be set at 43mm (Easiest way to set this adjustment is by using some type of a space (gauge) block ). Feeder / Hopper door opening for T5 x 14mm long Xmas tree stud Emhart number SWB 236 or 29631 needs to be set at 33mm. Feeder / Hopper door opening for Grounding stud-nut assembly needs to be set at 30mm. Air flow controls on the lift mechanism need to be set in such a way that the stud lifting mechanism moves up and down freely and with-in set time. Air flow controls also need to be adjusted so that the air cylinder creates no impact at the top or the bottom position. o This can be accomplished by setting its air flow controls to the following settings. Set the air flow control at the top (upper) of the air cylinder 6 and 1/4 turns from fully closed. Set the air flow control at the bottom (lower) of the cylinder to 6 turns from fully closed. Upper air flow control Lower air flow control 47 Air flow control on the kicker cylinder needs to be set in such a way that it does not start moving toward its extended position (forward) until the lifting mechanism is at least one half way down to its down (retracted) position. Kicker cylinder needs to be adjusted so that when it is in its extended position its tip rides right on top of the fully lowered lift mechanism stud channel. Air flow control Kicker cylinder Lower air flow valve 48 Connecting rod between air cylinder and lift channel needs to be connected to the bolt hole on the back of the lift channel. Rear mounting hole Connecting rod 49