Subido por Valeria Diaz Culebro

EVair03 6189655 User.v-11

Anuncio
Compressor
EVair03 Air Compressor
Model OF302-1.5SDA
Technical Reference Manual
Technical manual
IMPORTANT: General directions for use
Note
•
Protect compressor against rain, moisture, frost and dust.
•
OF302 is constructed and approved for a max. pressure of
8 bar/120 psi.
•
Do not operate compressor at ambient temperatures exceeding
40°C/104°F or falling below 0°C/32°F.
•
Technical competence: The procedures described in this Technical
Reference Manual should be performed by trained and authorized
personnel only.
Please note that pictures and figures referred to
may be found on page 5-10.
Maintenance should only be undertaken by competent individuals
who have general knowledge and experience with devices of this
nature.
IMPORTANT - read this first!
No repairs should ever be undertaken or attempted by anyone not
having such qualifications.
Please read the following information and operating instructions included
with this product before use. This information is for your safety and it
is important that you follow these instructions. It will also help prevent
damage to the product. Failure to operate the unit in accordance with
the instructions or using JUN-AIR unauthorized spare parts can cause
damage to the unit and could cause serious injury.
CAUTION: To reduce risk of electric shock
•
Only authorized service agents should carry out service. Removing
parts or attempting repairs can create an electric shock. Refer all
servicing to qualified service agents.
•
Contact JUN-AIR for a list of approved agents.
•
Do not use this unit with electrical voltages other than stated on the
rating plate.
•
Always unplug this unit immediately after use.
•
Store in a dry place.
•
Do not use this product or install in or near liquid or where it can fall
or be pulled into water or other liquids. In which case protection is
required.
•
Do not reach for this product if it has fallen into liquid. Unplug
immediately.
•
This unit is not weatherproof. Never operate outdoors in the rain or in
a wet area.
•
Do not pump any other gases other than atmospheric air.
•
Do not pump combustible liquids or vapours with this product.
•
Do not use this unit near naked flames.
Min. 0°C/32°F • Max. 40°C/104°F
WARNING: To reduce risk of electrocution
Warranty
Provided that the operational instructions have been carried out,
your JUN-AIR compressor is guaranteed against faulty material or
workmanship for 2 years.
The guarantee does not cover damage caused by violence, misuse,
incorrect repairs or use of unoriginal spare parts. Costs of transportation
of parts/equipment are not covered by the guarantee. JUN-AIR’s
Conditions for Sale and Delivery will generally apply. JUN-AIR
International A/S reserves the right to change technical specifications/
constructions.
DANGER: To reduce risk of explosion or fire
Installation
CAUTION: To prevent injury
•
Compressed air can be dangerous; do not direct airflow at your body.
•
Always keep the compressor out of reach of children.
•
Never operate this product if it has a damaged power lead or plug, if
it has been dropped or damaged, or if it has fallen into water. Return
the product to a service centre for examination and repair.
•
Keep the electrical cable away from heat.
•
Never restrict fans. Ensure that all openings are kept free of
restriction.
•
Never insert fingers or any other objects into fans.
•
This unit is thermally protected and will automatically restart when
the overload resets.
•
Wear safety glasses.
•
Use only in well-ventilated areas.
•
Do not use any items not recommended for use with compressed air.
•
The surface of the compressor can get hot. Do not touch compressor
motor during operation.
Your JUN-AIR compressor is very easy to operate. Observe
the following simple instructions and you will get many years’
service from your compressor.
•
Visually inspect unit for shipping damage, contact your
supplier immediately if you think the unit may have been
damaged.
•
If compressor is to be installed in a ventilator cart, follow
manufacturer's installation instructions.
Failure to observe the above safety precautions could result in severe
bodily injury, including death in extreme cases.
2
Technical Reference Manual
6189655 - v.11 - 01.2004
Electrical supply
Weekly
WARNING!
Incorrect electrical connection may result in electric
shock. The electrical connection must be carried out
in accordance with local electrical regulations and by
qualified electrical engineers.
•
For electrical connection, refer to page 8.
•
The EVair03 Air compressor is designed to operate from electrical
mains supply.
•
Verify that your local mains supply voltage matches the rated device
voltage on the serial number plate of the compressor.
•
Connect the power cord to the mains inlet on the rear of the
compressor cabinet.
•
Connect the power cord to the wall outlet.
•
Switch on the mains switch. Verify that the ON-OFF switch on the
front of the compressor unit is lit.
•
Open drain valve on receiver, if water
in receiver, refer to "Fault finding and
repair" point 7.
Check motor, air tubes, hoses and
equipment for leaks.
Clean unit or wipe with a soft, damp
cloth. If necessary, use paraffin on rag
to remove sticky adhesions. Dust and
dirt prevent cooling.
Replace intake filters (P/N 5412400)1
see fig 5a - c.
Check the O-ring in the non-return
valve and replace, if necessary.
(P/N 6243000,6242500)1 see fig 7.
Note! Empty receiver of air before
dismounting.
Operation
•
Monthly Annually
If the temperature of the compressor is extremely low (for instance
after transportation or stocking), allow motor to return to room
temperature before switching on the compressor.
Do not use motor for compression of liquids and dangerous gasses,
such as petrol vapour and solvents.
Check filter and replace filter elements
for optimum efficiency.
(P/N 4071230, 4071240)1 see fig 6a-d.
Check air inlet filter mat for cabinet.
IMPORTANT!
Replace if necessary. (P/N 6985795)1.
The compressor pump is only suitable for
atmospheric air.
1Included in the annual maintenance kit
•
Do not remove protection covers during operation as it may cause
electric shock or risk of other personel injury.
Adjustment of pressure switch (see fig 1a+1b)
•
Ensure that motor is correct for airflow as required.
The pressure switch determines whether the unit runs on primary
or reserve supply. The left scale (Cut in) indicates at which
pressure the unit switches from reserve to primary supply.
WARNING!
If maximum pressure is exceeded, reduced lifetime
may result.
The pressure in the left scale (Cut in) minus the differential
pressure (Diff.) in the right scale indicates when the unit will
switch from primary to reserve supply.
•
All compressors may run at 100% continuous operation.
To adjust the settings, remove the plastic cover. Use the screws
above the scales to adjust the pressure (Cut in)/differential
pressure (Diff.).
•
Do not lubricate the oil-less motor with oil, as this will destroy
important components.
The values for adjusting the pressure switch are:
Cut in:
Diff:
Preventive maintenance
Use the annual maintenance kit to change the parts included in the kit.
Change motor after 8-10,000 hours, order the 10,000-hour
maintenance kit and change the parts included in the kit.
280 kpa / 40.6 psi
30 kpa / 4.35 psi
Cut-in adjustment screw: Turn counterclockwise to increase and
clockwise to decrease the cut-in pressure.
Above this set point the primary supply will have priority.
Diff. adjustment screw: Turn counterclockwise to decrease and
clockwise to increase the differential pressure. The cut-in set
point minus the differential pressure set point indicates the
lower set point. Below the lower set point the reserve supply will
have priority.
Adjustment of relief valve (see fig 2)
The relief valve, see fig. 2, determines the maximum pressure
on the reserve supply system. To adjust the pressure, pull
out the knob. To increase the pressure, turn clockwise and to
decrease the pressure, turn counterclockwise. The non-rising
adjusting knob includes a locking feature, push in knob after
setting, to lock and prevent adjustment.
The value for adjusting the relief valve is 550kpa / 79.8psi.
6189655 - v.11 - 01.2004
Technical Reference Manual
3
Safety valve (see fig 3)
The safety valve, see fig. 3, will prevent pressure buildup. If the
pressure exceeds 1000 kpa/145 psi the valve will open.
Non-return valve (see fig. 4 + 7)
The EVair03 Air compressor has two non-return valves, one for
the primary system and one for the reserve system. The nonreturn valves are used to separate the two systems. Check the
non-return valves annually. Before disassembling the non-return
valve, empty the tank, using the drain valve. The pressure gauge
will not indicate whether there is pressure in the tank. Replace
the O-ring in the non-return valves annually (P/N 6243000).
2. Compressor does not start, makes a buzzing
sound followed by a clicking noise (cannot start
against high pressure):
a) The compressor has not been unloaded and there
is back pressure on the piston. Make sure that the
compressor is unloaded each time it stops. Check
unloader valve and replace, if necessary. See fig. 8.
b) Leaky non-return valve. Remove the flexible pressure
pipe from motor and check for leaking air from the tank.
If so, clean or replace O-ring or non-return valve.
3. Compressor works, but pressure does not
increase:
a) Intake filter clogged. Replace.
b) Leaks in fittings, tubes or pneumatic equipment. Check
with soapy water.
Drain (see fig. 3)
The drain cock will empty the tank for condensate. Normally
there will not be any condensate in the tank due to the
membrane dryer. Occasionally, if the EVair03 Air compressor
has not been used for a long time or if the air from the pipeline
inlet to the compressor is not dry, there may be water in the
tank.
c) Defective valve plate. Replace motor.
d) Failure in non-return valve which is creating a flow
restriction. Replace non-return valve.
e) Check relief valve settings, turn clockwise to increase
pressure.
f)
Intake filter (see fig. 5a + 5b + 5c)
The intake filter prevents dust and other large particles from
getting into the compressor and also reduces the noise level.
Change the filter at least once annually. To loosen the intake
filter, turn counterclockwise, using the JUN-AIR intake filter key
(P/N 4490501).
Unloader valve does not close. Clean or replace
unloader valve.
g) Higher leakage in dryer than normally. Disconnect the
tubes to and from the dryer. Assemble the disconnected
tubes and check if the pressure increases. If the
pressure increases replace the dryer.
4. Loud noise from compressor:
a) Dirt or failure in non-return valve. Clean or replace.
5µm and 0.01µm filters (see fig. 6a + 6b + 6c + 6d)
The EVair03 Air compressor has 3 filters. Two 5µ filters and one
0.01µ filter. A 5µ filter with manual drain is used for the primary
air supply. A 5µ and 0.01µ filter, both with automatic drain, are
used for the reserve supply. For further details, refer to the
pneumatic diagram.
The filters look the same on the outside, however, when
changing the filter elements, it is very important to mount the
bowls in the right place. The small number labels on the upper
part of the filter and on the filter bowl indicate where the bowls
are to be mounted. The numbers of the labels have to match
each other.
5. Motor gets very hot:
a) Leaks. See point 3b.
b) Clogged filter. See point 3a.
c) Too high ambient temperature.
d) Clogged intake filter mat on cabinet. Replace.
6. Compressor does not switch on when primary
pressure is too low or does not switch off when
primary pressure is too high (see User Manual):
a) Check pressure switch for correct adjustment as
described in "Adjustment of pressure switch" on page 3.
b) If this does not work, the pressure switch is defective
and must be replaced.
7. Water in tank (see drain valve fig. 3):
Fault finding and repair
IMPORTANT!
Switch off and isolate from electrical supply before
removing any parts from the pump. Empty air receiver
of air before dismantling parts of compressor unit's
pressure system.
1. Compressor does not start:
a) No power from mains. Check circuit breaker and plug.
b) Breakage or loose joints in electrical connections.
c) Defective capacitor.
d) The thermal protection has switched off the pump due
to overheating. When cooled the pump will automatically
switch on at a suitable operation temperature. Go
through the points in point 5 below.
a) Primary air inlet does not provide dry air. Check the
5µm filter on the primary supply pipeline to the tank.
Press the manual drain valve at the bottom of the filter
bowl. If water comes out of this valve, primary air inlet
does not provide dry air.
The 5µ filter is mounted behind the 5µ and 0.01µ filters,
see fig. 6a.
b) The 5µ and 0.01µ filters used for the reserve supply
may be clogged or there may be dirt in the bowls.
Replace filter elements and clean bowls.
c) Press the test button on the automatic drain for the filter
bowls to make sure that it is working properly. Clean
drain valve and pipes or replace. See fig. 6a + 6b + 6c +
6d.
Timer for automatic drain is to be set to 2 minutes.
d) Defective dryer. Replace dryer.
e) The compressor has seized. Replace motor.
4
Technical Reference Manual
6189655 - v.11 - 01.2004
Pictures/figures
Fig. 2 - Relief valve
Fig. 1b - Pressure switch
Fig. 1a - Pressure switch
Fig. 3 - Safety valve and drain
Fig. - 5a Intake filter
Fig. 4 - Non-return valves
Fig. - 5b Intake filter key
Fig. - 5c Intake filter
Fig. 6a - 5µ and 0.01µ filters for
reserve supply.
The 5µm filter for primary
supply, is mounted behind
these filters.
6189655 - v.11 - 01.2004
Pictures/figures
5
Fig. 7 - Non-return valve
Fig. 6b - 5µ filter with manual
drain for primary supply
Fig. 6c - 5µ filter with
automatic drain for reserve
supply
Fig. 6d - 0.01µ filter with
automatic drain for reserve
supply
Fig. 8 - Unloader valve and part of dryer
6
Pictures/figures
6189655 - v.11 - 01.2004
6189655 - v.11 - 01.2004
Pneumatic drawing
M
Filter drain TEC11
Open 0.3 sec/2min
Heat
exchanger
Intake filter
Pump
Reserve supply
All pipes 6mm
Februar 9, 2004
R1.20
EVair03 Air Compressor
Continuous operating pump
Pneumatic diagram
1l water
drain bottle
Filter 5µ
Pipeline
inlet
Filter
0.01µ
Primary supply
Unloader valve
Membrane
dryer DA
Pressure switch
See spec.
Filter 5µ
1.5 l tank
w/manual
drain
Muffler
Relief valve
See spec.
Non-return
valve
Non-return
valve
Safety valve
See spec.
Pipeline output
Pneumatic drawing
7
8
November 13, 2003
R1.18
Electrical drawing
AC inlet
IEC 320 15A plug
Circuit breaker
230V: 5A
120V: 9A
Pressure switch
EVair03 Air Compressor
Continuous operating pump
Electrical diagram
N
L
Thermal
switch
M
Compressor
Capacitor
AWG16
AWG16
Temperature
switch for fans
Hour meter
M
Fan
Unloader valve
AC outlet for auxiliary equipment
IEC 320 10A socket
M
Fan
Drain valve TEC11
Electrical drawing
6189655 - v.11 - 01.2004
Drawings
6189655 - v.11 - 01.2004
Drawings
9
10
Drawings
6189655 - v.11 - 01.2004
Spare parts
5471001
Filter kit f/OF302-1.5SDA
2 x 4071230 Spare parts kit f/5um filter regulator
3820-21
4071240 Spare parts kit f/0.01um filter 4141-12
2 x 5412400 Intake filter f/OF301 and OF302 motors
6985795 Filter mat f/air intake f/OF302-1.5SDA
5471002
10,000-hour kit 230V/50Hz
2882110 Motor OF302 230V/50Hz vertical
2 x 5414500 Non return valve
4785600 Solenoid valve f/unloader 230V w/plug
4799500 Auto drain 220-240V TEC11
5471003
10,000-hour kit 120V/60Hz
2882210 Motor OF302 120V/60Hz vertical
2 x 5414500 Non return valve
4785650 Solenoid valve f/unloader 120V w/plug
4799600 Auto drain 120V TEC-11
2882110
Motor OF302 230V/50Hz vertical
2882210
Motor OF302 120V/60Hz vertical
3001500
Receiver 1.5l with inspection plug and
internally coated, silver CE
4799500
Auto drain 220-240V TEC11
4799600
Auto drain 120V TEC-11
5095000
Vacuum switch
5150025
Gauge Ø40 built-in
5237007
Capacitor, run complete 20uF/230V AC
f/OF300 (40 cm)
5240608
Capacitor, run complete 60uF/120V AC
f/OF300 (40 cm)
5370055
Handle f/OF302-1.5SDA complete
5414500
Non return valve
5416555
Relief valve V07-200-NNLG
5425500
Safety valve TÜV 10 bar
5447035
Cooler complete
5450155
Fan 120V 4606Z
5451055
Fan 230V 4656Z
6242500
O-ring Ø16.1x1.6 mm
6243000
O-ring Ø7.3x2.4 mm brown f/non-return
valve
6253701
Vibration damper f/OF301/OF302
Ø20x30
6264255
Hose kit f/Datex Ohmeda
6295500
Grommet 170211
6976000
Silencer 1/8"
6984492
Front plate complete f/OF302-1.5SDA
6984508
Cabinet plate f/OF302-1.5SDA 120V
complete
4071000
Filter 5um w/manual drain
4071001
Filter 5um (without manual drain)
4071056
Filter 0.01um (without manual drain)
4082300
Membrane dryer (DA)
4141700
Rapid fitting 1/4" external x Ø6
6984511
4141701
Rapid fitting elbow 1/4" external cyl. x
Ø6
Cabinet plate f/OF302-1.5SDA
230Vcomplete
6984512
Top f/OF302-1.5SDA complete
4141820
Rapid fitting elbow 1/8"internal x Ø6
6984569
Back f/OF302-1.5SDA 230V complete
4142300
Rapid fitting 1/8"xØ4
6984570
Back f/OF302-1.5SDA 120V complete
4142500
Rapid fitting M5x4mm elbow
6985062
ASL Snap lock (complete set)
4146800
Rapid fitting Ø6mmx1/4" elbow
6985562
Mounting plate f/OF302-1.5SDA
4147555
Rapid fitting T-piece Ø6x1/4"
6985795
Filter mat f/air intake f/OF302-1.5SDA
4147556
Rapid fitting T-piece Ø6x1/4" (1/4" side
thread)
7020000
Double nipple 1/8"
7024000
Double nipple 1/4" L= 26 mm
7025000
Double nipple 1/4"x1/8"
7025310
Bushing f/autodrain f/metal cabinet 1/8"
7070000
Connection piece f/non-return valve
7070500
Connection piece f/non-return valve
model 12
4383205
Bracket f/membrane dryer Ø18mm
4490501
Tool for intake filter OF300
4752000
Hour meter 230V
4752200
Hour meter 120V
4781555
Plug type 0712 f/cabinet
4783955
Switch 230V (A32-4-F-050-COAZMO3)
7071500
T-piece 1/4" (3 x internal)
4783956
Switch 120V (A34-4-F-090-COAZMO3)
7074500
Coupling 1/4"
7171855
Distance piece f/motor vertical
4785600
Solenoid valve f/unloader 230V w/plug
7181000
Elbow 1/4" ext./ext.
4785650
Solenoid valve f/unloader 120V w/plug
7568055
Bushing f/OF302-1.5SDA
6189655 - v.11 - 01.2004
Spareparts
11
Phone:
Telefax:
+45 96 32 36 00
+45 96 32 36 01
E-mail:
Internet:
[email protected]
www.jun-air.com
Technical modifications reserved
6189655 - v.10 - 01.2004
JUN-AIR International A/S
Sundsholmen 3-5
Postboks 109
9400 Nørresundby
Denmark
Descargar