paper: hicks Strength and ductility of headed stud connectors welded in modern profiled steel sheeting Synopsis Push tests in Australia have suggested that studs welded in modern trapezoidal decks possess lower resistances and slip capacities than expected. This paper presents the results from a comprehensive research programme consisting of full-scale composite beam and companion push tests. The beams exhibited excellent ductility, and the slip capacity at the shear connection far surpassed the levels considered obtainable by current British and European Standards. Comparisons of load–slip performance show that any brittleness exhibited in push tests is as a result of a deficiency in the standard push specimen rather than the shear connection. For single studs, the beam tests demonstrate that the current UK design practice of using the shoulder height of the deck in BS 5950 to be the most appropriate. Conversely, the performance of pairs of studs in the current research appears to be adversely affected by longitudinal connector spacing. Interim design guidance is proposed for studs in this arrangement. equations that are multiplied by the design resistance of studs embedded in solid concrete slabs. The reduction factor formulae in BS 5950-3.1 and Eurocode 4 have been empirically derived from push tests, which have been revised and modified as new deck profiles have been developed. It should also be noted, however, that no advice is given in either of these Standards on how to adapt the standard specimen in Fig 1(a) when decking is present; this has led to a wide variation in specimen geometry for push tests with decking which, in part, may be a reason for the high scatter in results observed in previous calibration studies7,8. The reduction factor formula given by BS 5950-3.1 is as follows: k = 0.85/√nr(b0/hp){(hsc/hp) – 1} ...(1) but k ≤ 1.0 for nr = 1 and k ≤ 0.8 for nr = 2 where nr is the number of studs per rib, b0 is the breadth of the concrete rib (which should be reduced to 2e when the studs are welded in the unfavourable position), hp is the height of the steel deck rib and hsc is the height of the stud (see Fig 2). Introduction Historically, the performance of shear connectors has been established from small-scale specimens of the type shown in Fig 1(a). By applying a load to the top end of the steel-section, the load–slip behaviour of the connectors can be determined. This type of specimen is known as a ‘push test specimen’ in BS 59503.1: 19901 and BS EN 1994-1-1: 20042 (Eurocode 4) and, apart from slight variations in its geometry, has hardly changed since its inception in the early 1930s3. a) b) According to Eurocode 4, if three nominally identical tests are carried out, and the deviation of any individual result from the mean value does not exceed 10%, the characteristic resistance of a shear connector PRk is defined as 0.9 times the minimum failure load per stud (see Fig 1(b)). The ductility of a shear connector is measured by the slip capacity δu, which is defined in Eurocode 4 as the slip value at the point where the characteristic resistance of the connector intersects the falling branch of the load-slip curve (see Fig 1(b)). The characteristic slip capacity δuk is taken as 0.9 times the minimum test value of δu. Alternatively, the characteristic properties of a shear connector can be determined by a statistical evaluation of all of the results according to BS EN 1990: 20024. The rules for partial shear connection given in BS 5950-3.1 and Eurocode 4 are based on extensive numerical analyses, which considered composite beams over a wide range of spans and section types5,6. To enable the designer to assume that all of the studs are equally loaded at the ultimate limit state (i.e., the shear connection is fully plastic), the minimum degree of shear connection in these Standards is based on an assumed ductility limit. In Eurocode 4, a connector may be taken as ductile if the characteristic slip capacity δuk is at least 6mm. When stud connectors are welded within the ribs of profiled steel decking, their resistance is reduced when compared to studs embedded in solid concrete slabs. To account for this reduction, BS 5950-3.1 and Eurocode 4 provide reduction factor 32|The Structural Engineer – 15 May 2007 9 In 1993 the SCI wrote an advisory desk article to clarify the definition of deck height to be used when calculating the reduction factor for modern trapezoidal decks that possess a shallow central stiffening rib on their crests (see Fig 2). The article stated that, for trapezoidal decks of the form shown in Fig 2, only the height to the shoulder hp,n needed to be considered provided that: the stud projects at least 35mm above shoulder height (i.e. hsc – hp,n ≥ 35mm); and the re-entrant portion is not more than 15mm in height (i.e. hp,g – hp,n ≤ 15mm) and 55mm in width. This gave less onerous reduction factors than those based on the overall deck height hp,g. There has been much publicity of push tests in Australia that have suggested considerably lower resistances and slip capacities than expected for stud connectors welded in the troughs of trapezoidal decks10,11. Proprietary solutions, such as special reinforcement, which are now required in certain situations by the Australian Standard12, are proposed to overcome these problems. An obvious question regarding shear connectors in push specimens is whether their behaviour is comparable to that which would occur in a full-scale beam. While many full-scale beam tests have been undertaken in the past, there was insufficient instrumentation to determine the load–slip performance of the shear connectors in situ. As a consequence of this, although the measured end slips were in excess of the required ductility limits, it was impossible to know whether the stud performance was much better in beam specimens or, as implied by Australian push test results, whether the outer studs were on the falling branch of the load–slip curve. Moreover, the degree of shear connection provided in these tests was not low enough to provoke a brittle failure had the studs possessed insufficient slip capacity. In an attempt to answer these questions, full-scale composite beam and companion push specimens were constructed and tested to failure at Cambridge Stephen Hicks BEng(Hons), PhD(Cantab) Manager, Building Engineering, The Steel Construction Institute, Silwood Park, Ascot, Berks Received: 08/06 Modified: 01/07 Accepted: 02/07 Keywords: Beams, Composite construction, Shear connectors, Studs, Decks, BS 5950, Eurocode 4, Testing, Behaviour © Stephen Hicks Your comments on this paper are welcome and will be published online as Correspondence. Please send your contribution to the Editor within 3 months Fig 1. (left) Eurocode 4 (a) standard push test specimen and (b) determination of characteristic resistance and slip capacity from load–slip curve Fig 2. (below) Dimensions of profiled steel decking and studs in the (a) central (b) favourable and (c) unfavourable position paper: hicks strengths fym presented in Table 1 were evaluated. As well as being used in the predictions of moment resistance, the stressstrain behaviour of the material was used in the back-analysis of the strain gauge readings. The target mean compressive cube strength of the concrete was 25N/mm², which was achieved by specifying a normal weight C16/20 mix; this strength was chosen in an attempt to provide the lowest degree of shear connection that is permitted by the current Standards to obtain evidence of slip capacity. A summary of the measured properties on the day of the beam test is presented Table 2. The shear connectors consisted of 19 × 100mm long headed studs (95mm length-as-welded). To determine the mechanical properties of the stud material, three coupons were machined from finished studs. From tensile tests on these coupons, the mean ultimate tensile strength of the stud material was found to be fum = 513.5N/mm² with an elongation of between 15 to 16%. University Engineering Department. The remainder of this paper describes this research and its implications on design. Fig 3. 10m span composite beam specimen Composite beam specimen 1 The composite beam was simply-supported over a span of 10m, and consisted of a 305 × 165 × 46kg/m UB (see Fig 3). To provide the most unfavourable loading to the studs, the beam was propped at third-points at the wet concrete stage so that the full self-weight load was applied to the shear connection once the props were removed. As well as pre-loading the studs, this construction also ensured that the effects of ponding were minimised to enable a constant slab thickness to be assumed in the back-analysis of the test. To gather as much information on the shear connection as possible, two stud arrangements were used in the beam specimen. On the left hand side of the beam in Fig 3, seven pairs of studs were through-deck welded in every other trough in the ‘favourable’ position (see Fig 2(b)); this arrangement was adopted to enable the lowest degree of shear connection to be provided, so as to gain information on the in situ load–slip curves. (N.B. The longitudinal spacing provided was very close to achieving the maximum spacing requirements given in BS 5950-3.1, Clause 5.4.8.1 of the smaller of 600mm or 4 × overall slab depth; however, the spacing was compliant with the requirements given in Eurocode 4, 6.6.5.5(3) of the lesser of 6 × the total slab thickness or 800mm). On the right hand side of the beam in Fig 3, 14 studs were through-deck welded singly in every trough in the ‘favourable’ position. This welding arrangement meant that an equal number of studs were provided in each half of the beam. The steel used in the fabrication of the specimen was grade S355. From coupons cut from the UB, the mean measured yield Table 1: Measured steel properties Top flange Web Bottom flange fym (N/mm²) 368 378 388 Table 2: Measured concrete properties Age (days) fcm,cube (N/mm²) fck,cube (N/mm²) fcm (N/mm²) fck (N/mm²) Ecm (kN/mm²) 42 25.3 16.5‡ 20.4 12.4‡ 26.1† ‡ characteristic value determined from BS EN 1992-1-1: 200413 † modulus of elasticity derived from beam bending stiffness Table 3: Cross-sectional properties for 305×165×46 kg/m UB D (mm) B (mm) t (mm) T (mm) Root radius (mm) Crosssectional area (mm²) 309.8 166.6 7.3 10.9 8.9† 5795 † Nominal value To facilitate the back-analysis, the geometry of the steel section was measured at each of the 16 instrumented cross-sections. The average measured properties of the UB are presented in Table 3. The slab was 140mm thick, and was conventionally reinforced with one layer of A193 square mesh fabric, which was laid directly on the deck (i.e. the top of the studs projected 11mm above the mesh). A total slab width of 2500mm was provided, which corresponds exactly with the effective width requirements given in current Standards of beam span/4. To represent UK practice, a typical 60mm deep trapezoidal deck was fixed perpendicular to the longitudinal axis of the beam (comprising of a Multideck 60-V2 profile); this provided an average concrete rib breadth b0 of 150mm, a ‘shoulder height’ hp,n of 60.9mm and an overall height hp,g of 69.9mm (see Fig 2). Owing to the fact that the rules given in Eurocode 4 reduce the stud resistance for sheet thicknesses less than or equal to 1.0mm, a 0.9mm gauge deck was used to provide the most unfavourable case (thinner gauge decks are not currently in use in the UK). Instrumentation Measured material properties Location Geometric properties To enable the internal forces to be evaluated, the steel beam was instrumented with strain gauges on the top and bottom flange at cross-sections corresponding to the shear connector positions. As well as determining the build-up of axial force, the internal bending moments were evaluated to check the reliability of the strain gauge readings. The slip distribution at the shear connection was established from horizontally mounted transducers, which monitored the relative displacement between bars cast in the concrete behind the shear connector positions and the top flange of the beam (see Fig 4). The internal load–slip curves for the shear connectors were therefore evaluated by plotting the change in axial force at each crosssection against the corresponding slip. Owing to the fact that two stud arrangements were provided, the different load–slip characteristics for the shear connectors meant that there was no position of symmetry. The steel beam was therefore instrumented at 16 cross-sections along its entire length, comprising 48 strain gauges and 30 displacement transducers (see Fig 3). The deflection was monitored by vertical transducers at third-points and at mid-span of the beam. An image of the instrumentation on the side with pairs of studs is shown in Fig 4. In an attempt to closely simulate the bending moment from a uniformly distributed load, four equally spaced point-loads were applied along the centre-line of the beam. The loading was supplied by 60t jacks with a stroke of 300mm, which were located at third points along the beam (see Fig 3). To enable large deflections to be applied to the beam specimen, rollers were provided under the ram of the jacks as well as to the ends of the spreader beams. The bearing plates were plastered directly onto the concrete slab and, to eliminate any question of the shear connection being assisted by horizontal forces taken through the load system, horizontal sliders were 15 May 2007 – The Structural Engineer|33 paper: hicks Fig 4. (left) Instrumentation in the vicinity of the support on the side with pairs of studs Fig 6. (right) Concrete pull-out failure around pairs of studs revealed after separating the slab from the deck provided at the interface between the bearing plate and the rollers to the spreader beam. General behaviour of the beam The props were left in place until the target compressive strength of the concrete was achieved. Once the props were struck, the self-weight loads on the composite cross-section (which amounted to 74.5kN) resulted in a mid-span deflection of 66mm. The end-slips indicated that there was a modest asymmetry in the shear connector behaviour, with measured values of 0.15 and 0.08mm for the side with pairs of studs and single studs respectively. Initially, the beam was subjected to three cycles of load up to approximately 70% of the predicted ultimate load (which was based on BS 5950-3.1, using mean measured material properties, and the shoulder height of the deck hp,n in Eq.(1)); this loading was undertaken to ensure that the beam was elastic in the initial stages and to identify the load level when first yield occurred. The applied moment versus mid-span deflection plot is presented in Fig 5. As can be seen from Fig 5, for load Cycle 4 and 5 up to a midspan deflection of 300mm (equivalent to span/30), the specimen exhibited excellent ductility. Significant slip was recorded on the side with pairs of shear connectors and, at an end-slip of 26.5mm, it was felt that sufficient data had been collected, which resulted in load Cycle 5 being terminated. From test observations, it was clear that significant distress was caused at the shear connector positions with pairs of studs. By a visual inspection of the locations where the deck had delaminated from the concrete slab during load Cycle 4, it appeared that concrete pull-out had occurred, with pyramidal shear cones of concrete clearly visible around the studs. Pullout failure was later confirmed when the concrete slab was removed from the deck to reveal the failure surfaces shown in Fig 6; this failure mode was similar to that experienced in the companion push tests discussed below and reported elsewhere14. In addition to this, there was some evidence of uplift at the unstudded concrete ribs adjacent to the positions where studs were welded in pairs (see Fig 7). In an attempt to gain further information on single studs, an end stop was welded to the left end of the beam in Fig 3 to subject these connectors to greater levels of longitudinal shear force. Fig 7. Slab uplift of unstudded rib adjacent to locations where studs were welded in pairs (Position S7) As can be seen from load Cycle 6 and 7 in Fig 5, the end stop was successful in that, as well as significantly increasing the stiffness, the beam was capable of taking further load. Under this new set-up, load was applied until an end slip of 4.1mm was achieved on the side with single studs welded in each trough. At this point, bearing failure of the concrete in front of the end stop occurred, which resulted in the test being terminated. However, as can be seen from Cycle 6 and 7 in Fig 5, although the test was stopped prematurely, the resistance corresponded almost exactly with the BS 5950-3.1 predictions for the side with single studs. From observations made on the beam, it was clear that the plateau observed in the moment–deflection plot during load Cycle 4 and 5 was caused by a plastic hinge forming in the beam on the side with pairs of studs. A visual inspection of the steel beam confirmed this in that Lüders’ wedges were observed in the web of the UB, adjacent to cross-section S3 on the side with pairs of studs (see Fig 3). Back-analysis of the beam Fig 5. (below) 10m span beam applied moment versus mid-span deflection To enable the internal forces to be evaluated, a special version of the SCI software ‘BFIRE’ was developed. At each instrumented cross-section, the steel beam was sub-divided into a number of rectangular elements. The strain at the centroid of each of these elements was calculated from the strain gauge readings and compared to the stress–strain curves that had been established from coupons cut from the UB. From the distribution of stresses on the cross-section, the internal forces and moments within the steel beam were derived. Load–slip performance of shear connectors The load–slip curves for the pairs of studs closest to the support (7th pair from mid-span) and 646mm from the support (6th pair from mid-span) are presented in Fig 8. As can be seen from this plot, the pairs of studs possessed a high initial stiffness until a peak resistance of approximately 160kN was achieved at slips of about 1mm. As the slip increases, the resistance reduces to approximately 66 and 100kN (i.e., 33 and 50kN per stud); beyond this point, the behaviour is very ductile indeed, and a plateau is maintained up to a slip of 26mm. The load–slip curves for the single studs closest to the support (13th and 14th stud from mid-span) and 646mm from the support (11th and 12th stud from mid-span) are presented in Fig 9. As can be seen from this plot, the single studs possessed 34|The Structural Engineer – 15 May 2007 paper: hicks Fig 8. (above top) Comparison of axial force in beam versus slip for 6th and 7th pair of studs (Load Cycles 1 to 5) loading comprised of two point loads applied to the beam. Owing to the new beam configuration, the left hand side of the beam had seven single studs welded in the unfavourable position (see Fig 2(c)); whereas, the right hand side of the beam had seven single studs welded in the favourable position (see Fig 2(b)). To enable the load–slip curves for single studs to be determined in situ, two extra cross-sections were instrumented at positions N1.5 and N7.5 (see Fig 10). Because it was expected that the unfavourable studs would have a lower resistance than the studs welded in the favourable position, an extra centrally welded stud was provided over the left hand support. A set of concrete cubes had been set aside after the previous beam test, which were crushed on the day of the test to determine the compressive cube strength of the concrete. Although the age of the concrete was 106-days, it was found that the concrete possessed exactly the same properties as those presented in Table 2. General behaviour of the beam Fig 9. Comparison of axial force in beam versus slip for 13th and 14th single studs together with 11th and 12th single studs (Load Cycles 1 to 7) a much higher resistance than the pairs of stud connectors. Assuming that the load was equally distributed between the studs, a maximum resistance of about 113kN was achieved per stud and was maintained with increasing slip. However, owing to the fact that bearing failure of the concrete in front of the end stop occurred, the magnitude of the slips were quite low for the single studs in comparison with studs welded in pairs (4mm cf. 26mm). As a consequence of this, it was impossible to know whether the single studs would have been able to maintain their load for higher levels of slip or, in a similar way as for pairs of studs, their resistance would have reduced. Furthermore, the assumption that the load was equally distributed between the studs may not be entirely correct. The applied moment versus mid-span deflection plot for the 5.0m span beam specimen is presented in Fig 11. During the first two load-cycles, much greater end slips were recorded on the side with unfavourable studs (4.5mm cf. 2.4mm at the maximum moment applied in load Cycle 1). At an end-slip of 12.9mm, the second load cycle was terminated as it was felt that sufficient data had been collected for unfavourable studs. As can be seen from Fig 11, the specimen exhibited excellent ductility up to this point, which corresponded to a mid-span deflection of 85mm (equivalent to span/59). Furthermore, the resistance was 11% higher than the predictions from BS 5950-3.1. Once the load had been removed, an end stop was welded to the left end of the beam in Fig 10, in an attempt to subject the side with single favourable studs to greater levels of longitudinal shear force. As can be seen from load Cycle 3 in Fig 11, under this new set-up further load and deflection was applied to the beam specimen. Once an end slip of 24.6mm was achieved on the side with studs welded in the favourable position, the test was terminated at a mid-span deflection of 174mm (equivalent Composite beam specimen 2 Owing to the fact that there was little evidence of a permanent set within the UB until the plastic hinge position adjacent to cross-section S3 (see Fig 3), it was decided to gather more data on single studs by cutting the specimen in half to form a 5.0m span beam. The tests on this shorter specimen are described below. As can be seen from Fig 10, unlike the previous test, the Fig 10. (below) 5m span composite beam specimen Fig 11. (above) 5m span beam applied moment versus mid-span deflection to span/29) owing to concerns over the stability of the test rig from the large curvatures. In a similar way as the behaviour exhibited in the early stages of the test, the applied moment–deflection plot for load Cycle 3 showed that the specimen possessed excellent ductility. Moreover, the performance of the studs welded in the favourable position was much better than that assumed by current Standards, which resulted in a resistance that was 12% higher than that predicted by BS 5950-3.1. Failure was caused by a plastic hinge forming in the beam adjacent to the load position near instrumented position N3 (see Fig 10), which was confirmed by Lüders wedges being clearly observed in the web of the UB. 15 May 2007 – The Structural Engineer|35 paper: hicks normal force to the face of the slab15,16. Discussion Characteristic properties of stud connectors from beam tests Back-analysis of the beam Load–slip performance of shear connectors The load–slip curves for single studs in the favourable, central and unfavourable position are presented in Fig 12. As can be seen from these plots, much less slip was needed for the stud in the unfavourable position to achieve its peak resistance compared to the favourable and centrally welded studs (2.8mm cf. 7.9mm and 9.6mm respectively). In terms of the slip requirements given by the current Standards, significant ductility was achieved for all of the stud arrangements; in particular, for studs welded in the favourable position (see Fig 2(b)), where a plateau was maintained up to a slip of approximately 25mm. Companion push tests To provide a link between the behaviour of studs in a beam compared to that achieved in a push test, six push specimens were constructed using exactly the same batch of concrete that was used in the beam specimen. These specimens varied slightly from standard test given in Eurocode 4, in that the steel section was split to form two structural ‘tees’ (see Fig 13). The advantage of this set-up was that the casting process was greatly simplified and the same concrete used in the beam specimen could be used for both test slabs (thereby reducing the variation in the results from different concrete mixes). The load–slip curves from the beam tests compared to the push tests are shown in Fig 14 and Fig 15; these curves represent the lowest results obtained from each test type for a particular stud arrangement. As can be seen from these plots, with the exception of initial stiffness, there appears to be no similarity between the performance of studs in these two types of specimen. It might be argued that the peak resistance achieved in the push test is comparable with the plateau exhibited by the studs in the beam specimen. However, the slip measured in the push test is well below the levels achieved in the beam specimen and, if considered in isolation, would suggest that the ductility of the shear connectors was lower than required by the current Standards for partial shear connection design. It is felt that the reason for the poor performance in push tests is due to the absence of a curvature and normal force, which exists in real composite beams from the floor loading. Brittle failures in push tests have also been observed elsewhere, which has led some researchers to modify the standard specimen by applying a 36|The Structural Engineer – 15 May 2007 Fig 12. (above) Comparison of axial force in beam versus slip for single studs in the favourable, central and unfavourable position Fig 13. ( below left) Companion push test specimen Fig 14. ( below) Load–slip curve for single studs in the favourable position – Beam test versus push test Fig 15. (below right) Load–slip curve for pairs of studs in the favourable position – Beam test (7th pair) versus push test Based on the load–slip curves evaluated from the beam tests for studs in the favourable, central and unfavourable position, the characteristic resistances PRk presented in Table 4 have been taken to be 0.9 times the minimum failure load per stud Pe. To examine the performance of the current Standards, predictions based on BS 5950-3.1 and Eurocode 4 (EC 4) are presented for comparison purposes; in these comparisons, predicted stud resistances based on the deck shoulder height, PRk,n and overall deck height, PRk,g are considered. As can be seen from Table 4, the characteristic resistance of 96kN for single centrally welded studs compares well with the predictions for PRk,n using BS 5950-3.1. Moreover, the characteristic slip capacity of the stud in this position out-performs the Eurocode 4 requirements for ductile connectors by almost a factor of two. However, the predictions for PRk,n using Eurocode 4 appear to be overly conservative for single studs. For single studs in the unfavourable position, the predicted resistance given by BS 5950-3.1 is conservative in comparison with that achieved in the beam tests (see Table 4). Furthermore, the Eurocode 4 requirement that studs should be welded alternately on the two sides of the trough throughout the length of the span (when it is not possible to place studs centrally within the trough), seems to be appropriate in that the average of the favourable and unfavourable resistances corresponds almost exactly with the resistance of the centrally welded stud. For pairs of studs, the characteristic resistance is 73kN per stud. Although this resistance is close to the value of PRk,n calculated with BS 5950-3.1, owing to the shape of the load–slip plot (see 7th pair in Fig 12), the corresponding slip capacity is only 0.7mm. This is well below the 6mm requirement given in Eurocode 4 for cases when a connector may be taken as ductile. In order to achieve a slip capacity of 6mm, the characteristic resistance has been down-rated to 49kN per stud in Table 4; this resistance is close to the value of PRk,n calculated according to paper: hicks Table 4: Characteristic properties of studs in the Favourable (F), Central (C) and Unfavourable position (U) evaluated from beam test nr Stud position Pe PRk PRk/PRk,Central δuk (mm) BS 5950 PRk/PRk,n BS 5950 PRk/PRk,g EC 4 PRk/PRk,n EC 4 PRk/PRk,g 1 F 123 111 1.16 9.6 1.27 (87.3) 1.94 (57.2) 2.19 (50.6) 2.88 (38.5) 1 C 107 96 1.00 11.9 1.10 (87.3) 1.68 (57.2) 1.90 (50.6) 2.49 (38.5) 1 U 89 76* 0.79 6.0 1.32 (57.6) 2.36 (32.2) – – 2 F 80 49* 0.51 6.0 0.70 (69.8) 1.21 (40.4) 1.18 (41.7) 1.80 (27.2) †PRk,Central is the characteristic resistance of the centrally welded studs * down-rated to achieve a slip capacity of 6mm ( ) calculated characteristic resistance in kN Table 5: Characteristic resistance of studs welded in the favourable position evaluated from the standard push test nr Stud PRk δuk BS 5950 position (kN) (mm) PRk/PRk,n BS 5950 PRk/PRk,g EC 4 PRk/PRk,n EC 4 PRk/PRk,g 1 F 76.2 2.6 0.87 (87.3) 1.33 (57.2) 1.51 (50.6) 1.98 (38.5) 2 F 46.1 2.4 0.66 (69.8) 1.14 (40.4) 1.11 (41.7) 1.69 (27.2) ( ) calculated characteristic resistance in kN Eurocode 4. Characteristic properties of stud connectors welded in the favourable position from the companion push tests Based on the load–slip plots from the companion push tests (see Fig 14 and Fig 15), the characteristic values presented in Table 5 were calculated according to the requirements given in Annex B of Eurocode 4. By comparing Table 5 with Table 4, the single studs in the beam test out-performed those in the push test both in terms of resistance and ductility (by 46% and 269% respectively). However, when pairs of studs are considered, the characteristic resistance of 46.1kN agrees well with the value given in Table 4. Design resistance of through-deck welded studs Based on BS 5950-3.1, the ratio of the stud reduction factors for pairs of studs to single studs is 0.6/0.85 = 0.71. From the present investigation, the ratio of the characteristic resistance for pairs of studs to single studs is 49/111 = 0.44 for the beam tests, and 46.1/76.2 = 0.60 for the companion push tests. From this comparison it can be concluded that, if results from push tests can be regarded as basically comparative, the resistance of the pairs of studs from the beam test is lower than expected. However, from the observed uplift at the unstudded concrete ribs adjacent to the positions where studs were welded in pairs (see Fig 7), it is believed that performance of the studs in this arrangement was adversely affected by their relatively high longitudinal spacing. Although the effect of stud spacing will be examined in future research, the poor performance of the pairs of studs in the current investigation suggests that the reduction factor given in BS 5950-3.1 is too high. Moreover, the current code assumption that the resistance of pairs of studs is proportional to 1/√nr (where nr is the number of studs per rib), does not appear to be appropriate. As an interim measure, it is suggested that for nr = 2 the factor of 0.85 /√2 = 0.6 in Eq. (1) should be reduced to 0.37 (i.e. 0.85 × 0.44 = 0.37) to give the following reduction factor equation: k = 0.37(b0 /hp){(hsc /hp) – 1} but k ≤ 0.75 for nr = 2 ...(2) where b0 is the breadth of the concrete rib, hp is the depth of the profiled steel sheet (provided that the stud projects at least 35mm above the shoulder of the deck, using the ‘shoulder height’ hp,n as defined in Fig 2) and hsc is the height of the stud. Eq. (2) gives similar resistances to those calculated from Eurocode 4, when the shoulder height of the deck is inserted within the reduction factor formula. From the tests conducted in this investigation, it is also recommended that pairs of studs should not be arranged in line (i.e. in the favourable and unfavourable position within the same trough). A more beneficial arrangement is to have the studs arranged side-by-side, with the maximum transverse spacing that may be practically achieved. Owing to the very good agreement with the characteristic resistance achieved in the beam tests it is recommended that, for single studs through-deck welded in trapezoidal decks (i.e. nr = 1), the current practice of using the deck shoulder height in Eq. (1) should be maintained. Minimum degree of shear connection The minimum degree of shear connection permitted in BS 59503.1 and Eurocode 4 is 40%. However, the definition of the point on the beam where the degree of shear connection should be calculated is unclear in both of these Standards. According to BS 5950-3.1, the critical cross-section that should be considered in positive moment regions is defined by the point of maximum moment. This definition was used in the initial design of the test specimens, in that the critical cross-section was considered to be at mid-span (i.e. the maximum moment comprised of the self weight moment plus the moment applied by the jacks). At maximum moment, the axial forces derived from the strain gauge readings indicated that the critical cross-sections should have corresponded to the point load positions closest to mid-span (i.e. at position N3 and S3 in Fig 3). As a consequence of this, very low levels of shear connection were actually provided. For example, for the 10m span beam specimen with studs provided in pairs, only 24% shear connection was achieved (it is believed that this low level of shear connection is one of the reasons why the moment resistance was below the predictions given by BS 5950-3.1, in that the connectors became fully loaded long before the steel beam was fully yielded). It is therefore recommended that when a beam is subjected to concentrated loads, the critical cross-section that should be considered in design should correspond to the point load positions. Standard push test From comparisons of the load–slip curves it is clear that, for the deck type considered in this investigation, any brittleness exhibited in the push test is as a result of a deficiency in the standard specimen rather than the shear connection. As a consequence of this, some caution should be shown towards any new products that are claimed to increase the ductility of stud connectors since, if these devices were developed using push specimens, the improvements to the performance could be artificial. Although the tests presented in this paper have shown that the performance of studs in typical UK decks are ductile, there remains the problem that, if new floor decks are developed, it is difficult to identify cases when the behaviour could be brittle unless beam tests are undertaken. Furthermore, should the performance of studs in particular decks be better than that suggested by the current Standards (which have been developed from push test results) it is difficult to quantify the improvements in terms of design rules without a standardised specimen that better reflects the conditions that exist in a real beam. In the absence of a new specimen, it is recommended that, when decking is employed, the push test arrangement shown in Fig 16 should be adopted. Although this specimen does not solve the problem of brittleness, this arrangement appears to eliminate an artificial mode of failure caused by the rotation of the last studded rib at the top of the specimen17, which has sometimes been described as ‘back-breaking’. It is also recommended that edge trim from pressed strips of thin galvanised steel, which are normally used to form the floor edge in buildings, should be removed from the push specimens prior to testing to reduce the scatter in results (from earlier comparison tests, it was found that the coefficient of 15 May 2007 – The Structural Engineer|37 paper: hicks variation for specimens with and without edge trim was 9.98 and 4.4% respectively). Conclusions Two full-scale composite beam tests have been undertaken with a trapezoidal deck positioned perpendicular to the longitudinal axis of the beam (i.e. a secondary beam), and through-deck welded shear connectors. Unlike typical UK practice, the specimens were propped during construction to apply the most unfavourable loading to the shear connectors. This form of construction, together with other unfavourable combinations of variables, was adopted to demonstrate the slip capacity that can be achieved in a beam, together with the level of safety that exists in current design Standards. Both specimens exhibited excellent ductility in terms of overall load–deflection performance as well as slip capacity at the shear connection, which far Fig 16. Standard push test with profiled steel decking surpassed the levels of slip assumed in the development of the rules for partial shear connection given in BS 5950-3.1 and Eurocode 4. The performance of the beams with single studs welded in the troughs of trapezoidal decking demonstrated that the current design practice of using the shoulder height of the deck in BS 5950-3.1 should be maintained. However, for pairs of studs in the favourable position, the performance in the beam test was lower than anticipated. Although it is felt that the performance of the studs in this arrangement was adversely affected by their longitudinal spacing, a modified reduction factor formula has been presented as an interim measure. It is believed that research, which is currently underway, will enable this proposed design equation to be relaxed. The definition of the critical cross-section where the degree of shear connection should be calculated is unclear in both BS 5950-3.1 and Eurocode 4. Based on the behaviour of the test specimens it is concluded that, when a beam is subjected to concentrated loads, the critical cross-section that is considered in design should correspond to the point load positions. From comparisons of the load–slip curves from the beam tests with push tests, it is clear that any brittleness exhibited in the push test is as a result of a deficiency in the standard push specimen rather than the shear connection. It is recommended that a standardised specimen, which better reflects the conditions that exist in a real beam, should be developed. In the absence of a new specimen, a standard push test arrangement for slabs that use decking has been presented. Acknowledgments Financial support for this investigation was provided by the Floor/Deck Group of the Metal Cladding and Roofing Manufacturers Association (MCRMA), Corus Construction Services & Development and Corus Strip Products UK. The author wishes to thank the help and assistance of Dr R. E. McConnel, M. R. Touhey and the technical staff of Cambridge University Engineering Department whose expertise ensured the success of the testing programme. Thanks also go to Prof. R. P. Johnson of University of Warwick for his support and advice, together with Dr J. W. Rackham, Dr W. I. Simms and C. King of The Steel Construction Institute. REFERENCES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. BS 5950-3.1: 1990 Structural use of steelwork in buildings: Part 3: Section 3.1: Code of practice for design of simple and continuous composite beams, London, British Standards Institution BS EN 1994-1-1: 2004 Eurocode 4. Design of composite steel and concrete structures. General rules and rules for buildings, London, British Standards Institution Roš, M.: ‘Les constructions acier-beton system Alpha’, L’Ossature Métallique, 3/4, 1934, p 195-208 BS EN 1990: 2002 Eurocode – Basis of structural design, London, British Standards Institution Aribert, J. -M. : ‘Analyse et formulation pratique de l’influence de la nuance de l’acier du profile sur le degree minimum de connexion partielle d’une pouter mixte’, Construction Métallique, 3, 1997, p 39-55 Johnson, R. P. & Molenstra, N.: ‘Partial shear connection in composite beams for buildings’, Proc. Inst Civ. Eng., 91/2, 1991, p 679-704 Roik, K., Hanswille, G. & Cunze-O. Lanna, A.: ‘Harmonisation of the European construction codes – Eurocode 2, 4 and 8/Part 3 – Report on Eurocode 4 Clause 6.3.2 Stud connectors’, Institut für Konstruktiven Ingenieurbau, Ruhr-Universitat-Bochum, Report EC4/8/88, 1989, p 89 Stark, J. W. B. & van Hove, B. W. E. M.: ‘Statistical analysis of push-out tests on stud connectors in composite steel and concrete structures: Part 3: Composite steel and concrete slabs’, TNO report BI-91-163, Delft, 1991 Lawson, R. M.: ‘AD 147: Composite decking with additional re-entrant top stiffeners’, New Steel Construction, 1/6, 1993, p 36 Patrick, M: ‘Composite beam shear connection design and detailing practices for Australian steel decks’, University of Western Sydney, Report CCTRCBSC-001-04, 2004, p 15 Ernst, S., Patrick, M., Bridge, R. and Wheeler, A.: ‘Reinforcement requirements for secondary composite beams incorporating trapezoidal decking’, In: Composite Construction in Steel and Concrete V (eds Leon, R. T. & Lange, J.), New York, Amer. Soc. Civ. Engrs, 2004, p 236-246 AS 2327-1. Australian composite structures standard. Part 1: Simply-supported beams. Standards Association of Australia, 1996 BS EN 1992-1-1: 2004 Eurocode 2. Design of concrete structures. General rules and rules for buildings, London, British Standards Institution Johnson, R. P. and Yuan, H.: ‘Existing rules and new tests for stud shear connectors in troughs of profiled sheeting’. Proc. Instn Civ. Engrs, Structs and Bldgs, 128, 1998, p 244-251 Gibbings, D. R., Easterling, W. S. & Murray, T. M. 1993. Influence of steel deck on composite beam strength. In: Composite Construction in Steel and Concrete II, W. S. Easterling and S. M. Kim Roddis (eds), New York: ASCE, p 758-770 Bradford, M. A., Filonov, A., Hogan, T. J., Ranzi, G. & Uy, B.: ‘Strength and ductility of shear connection in composite T-beams’, 8th Int. Conf. Steel, Space & Composite Structures, Kuala Lumpar, Malaysia, 15-17 May, 2006, p 15-26 Johnson, R. P.: ‘Shear connection in beams that support composite slabs – BS 5950 and EN 1994-1-1’, The Structural Engineer, 83/22, 2005, p 21-24 38|The Structural Engineer – 15 May 2007