Subido por Felidor Saez

dlscrib.com-pdf-oimceha0a

Anuncio
CEHA SIDE CHANNEL PUMP
Multicellular, self-priming, low NPSH
Shaft sealing by stuffing
stuff ing box packing with or without cooling
Fig.0.A.1
Operating instructions
Security
Chapter 1
Safety instructions, guarantee
Description and applications
Chapter 2
Operating conditions, pump description, performance data
Planning the Installation
Chapter 3
Piping system, electric connections, accessories
Unpacking, handling, storage
Chapter 4
Checks, storage conditions and safety instructions
Installing the pump
Chapter 5
Installation conditions, piping connections, checks
Commissioning and decommissioning
Chapter 6
Conditions, safety instructions, checks
Maintenance
Chapter 7
Maintenance, disassembly, re-assembly
Help in case of trouble
Chapter 8
Analysis and troubleshooting
troubleshooting of operating defects
Appendices
Chapter 9
Coding, dimensions, cross sectional drawings, data sheet
Caution: This pump or this electric motor/pump
m otor/pump assembly may be installed and put into operation by qualified
and authorized personnel only. These personnel have to observe strictly the operating instructions in this
manual and the laws and regulations in force related to the safety.
If you do not pay attention to these operating instructions,
•
danger may be caused to the various persons working on the equipment and its users,
•
the pump or the electric motor / pump assembly may be damaged
damaged,,
•
the manufacturer is not liable for accidents resulting from such non-observance!
Please be aware of your responsibility for neighbouring personnel when working on the pump or the
electric motor / pump assembly
Document - No.
Revision
: CEH00AE
: 02
1-3 Avenue Georges Politzer-B.P 41-78193 Trappes France
Date
: 02/10/2003
Telephone: +33 (0)1 34 82 39 00 Fax: +33 (0)1 34 82 39 61
SAP Doc.
: 26593/TD/EN/00
Sterling Fluid Systems (France)
Member of the Sterling Fluid Systems Group
Page 1 of 4
Safety
1.0
Safety
Chapter 1
Authorized personnel for the use, maintenance,
maintenance,
This operating manual gives basic instructions
inspection
which are to be observed during installation,
qualifications needed for th
this
is wo
work.
rk.
operation and maintenance of the pump.
responsibility,
It is
and
assembly
skills
and
must
have
the
Scope of
monitoring
of
the
therefore imperative that this manual is read by
personnel must be strictly controlled by the
the fitter, personnel/operator in charge of set-up
purchaser of the equipment.
equipment. If the staff do not
and commissioning,
commissioning, as well as by
by the user. This
have the necessary knowledge, they must be
manual is to be kept always available at the
trained. The manufacturer or the supplier can
installation site of the pump or electric motor-
carry out this
this training. In additio
addition,
n, the purchaser
pump assembly.
is to make sure that the competent personnel
read and fully understood the contents of this
1.1
Meaning of safety symbols used
in this manual
manual.
Safety instructions to be observed to avoid any
danger to persons are shown by the symbol:
1.3
Non-compliance with safety
instructions
Non-compliance with safety instructions may
cause danger to personnel, as well as to the
environment and the machine.
Electrical power risks are shown by the symbol:
The manufacturer is such cases will not be held
responsible.
Non-observance of these safety instructions may
cause in particular:
Instructions where non-observance could cause

damage to the machine, are shown by the word:
Caution
Failure of important functions of the machine
or the installation,

Failure of specified procedures for servicing
and maintenance,
Instructions where non-observance could cause

supplementary risks when the pump is used in
‘’explosible atmosphères’’ are shown by the
symbol:
Exposure of people to electrical, mechanical
and chemical hazards,

Risks of pollution of the environment owing to
hazardous substances being released.
1.4
Accident prevention
The customer undertakes to respect the safety
instructions shown in this manual, the national
Signs affixed directly on the machine, such as the
accident prevention regulations, as well as the
arrow indicating the direction of rotation or the
internal
arrows indicating fluid suction and discharge
conditions, the equipment operation and safety.
regulations
relating
to
the
working
connections must be observed and kept legible.
1.2
Qualification and training of
personnel
Doc.Num.: CL01E
Rev.:01
Rev.:
01
Date: 01/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Page 2 of 4
Safety
1.5
Safety instructions for users
Chapter 1
Pumps and electric motor-pump assemblies,
This pump was designed in compliance with the
which
convey
standard relating to the safety of the pumps.
decontaminated.
hazardous
fluids
must
be
Immediately after completion of work all safety


Parts subject to temperature variations and
and protective facilities must be re-installed and
those where contact with them can be
made operative again.
dangerous must be protected by suitable
After a service or other operation, the instructions
devices.
to re-start the machine given in paragraph 6 are to
Safety devices against accidental contact with
be observed.
moving parts (e.g. coupling guards) must not
be removed from the machine while in
1.7
operation.
Use in Explosible Atmospheres
The pump must never be started without these
coupling guards.
The
instructions
maintenance
The coupling guard is a safety component
designed for its function; in no case, it must never
be used as a step or other support point.

In no case, is this pump to operate without
fluid.
The destruction of the shaft outlet
sealing which could result from such use
would cause fluid leakage endangering the
safety of persons and the environment.
environment.

Ensure that protection is provided against any
hazard
from
electrical
power
(refer
to
regulations in force).
1.6
Safety instructions for
maintenance, disassembly and
assembly
It is the customer’s responsibility to ensure that all
maintenance, inspection and installation work is
performed by qualified and authorized personnel
who have studied this manual.
Any work on the machine shall only be performed
when it is at a standstill. It is imperative that the
procedure
for
shutting
down
the
machine
described in this manual is to be followed.
Doc.Num.: CL01E
Rev.:01
Rev.:
01
Date: 01/04/2003
Manual
for
given
supplied
installation,
throughout
with
the
use
the
pump
and
Owner's
must
be
scrupulously adhered to. This section gives
additional information relevant to equipment use
in explosible atmospheres.
1.7.1 Classification
Classification of the Sterling side channel pumps
as
per
EC
Directive
94/9
"Explosible
atmospheres"
Group
: II
Category
:2
Gas
:G
Build safety
:c
1.7.2 Marking
The nameplate of a Sterling side channel pump
suitable for operation in explosible atmospheres
carries the following indications:
-
Sterling's name and address,
-
the CE approval logo,
-
the serial number,
-
the year of manufacture,
-
the classification, e.g.:
Information subjected to technical
alterations due to engineering development


II 2 G c.
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Page 3 of 4
Safety
1.7.3 Integration
Chapter 1
The pump may only be integrated into an
1.7.5 Risks of Spark Production by
External Shocks
assembly intended for operation in explosible
During
atmospheres, in accordance with EC Directive
operator shall see to it that external shocks on the
94/9 "Explosible atmospheres", if its nameplate
pump or pump set components, which could
includes the information defined in para. 1.7.2
produce sparks, are not likely to occur, otherwise,
(pump marking).
the necessary guards shall be installed.
use
in
explosible
atmospheres, the
If the pump is integrated into a complete system,
with other mechanical or electric components, this
complete system may only be validated if all its
1.7.6 Technical Parameter Monitoring
components comply with EC Directive 94/9
The
"Explosible atmospheres".
atmospheres". Only if this requirement
maintenance
is met will the use of the pump in an explosible
Manual
atmosphere (Group II, category 2) be authorized.
scrupulously adhered to under all circumstances.
NOTE:
However, when the pump has to be used in an
Particular attention shall be paid in checking that
explosive atmosphere, the monitoring of the
these requirements are complied with for every
following parameters has to be reinforced
component item of the complete system.
significantly::
significantly
instructions
for
given
supplied
installation,
throughout
with
the
use
the
and
Owner's
pump
must
be
The use of a single component not meeting the
requirements of EC Directive 94/9 "Explosible

presence
and
correct
operation
of
an
atmospheres" entails that the pump cannot be
used in explosible atmospheres, even though its
emergency shutdown system, provided with
an
interlock
preventing
non-controlled
nameplate includes the adequate symbols:
untimely restarts,


II 2 G c.

conformity of the transmission coupling,

presence and conformity of the coupling
guard,
1.7.4 Conformity of the Pump Set

conformity of the direction of rotation and
impossibility of inadvertent reversal thereof,
Coupling
The transmission coupling shall be provided with

adequate supply during operation,
a system which prevents the two half-couplings to
come into contact in case of abnormal wear of the
sufficient fluid level in the pump at startup and

use of the pump only within the authorized
flexible transmission components.
operating range (flowrate, water head, power,
Coupling guard
speed, NPSH, operation at zero flow without
The
coupling
guard
used
in
compliance
with
it shall be made of a non-sparking material
instructions
(carried
(e.g. bronze, brass, aluminum, etc.),
specific gravity, viscosity, startup intervals),
atmospheres shall meet the following criteria:
cr iteria:


bypass is absolutely prohibited),
explosible
its mechanical design shall be such that it is


conformity
strong enough to resist any distortions likely
temperature
to result in a contact with a rotating part, even
provided),
in case of illegal use of the guard (e.g. use of

the coupling guard as a step).
the
supplier's
fluid,
bearing
(monitoring
and
service
temperature,
operating
lubrication
absence of vibrations and/or overheats due to
poor drive coupling alignment or stresses on
Motor
the pump flanges,
The drive motor shall meet the requirements of

the CE Directive "Explosible atmospheres" it is
subjected to.
Doc.Num.: CL01E
Rev.:01
Rev.:
01
Date: 01/04/2003
of
the
adjustment and control of the acceptable
leaks,

conformity of the shaft seal temperatures,
Sterling Fluid Systems (France)
Information subjected to technical
Member of Group
alterations due to engineering development
Sterling Fluid Systems
Page 4 of 4
Safety
Chapter 1
check of sealing (shaft seal, body, plug,

piping).
1.8
Alter
Alteration
ation of the machi
machine
ne
and of spare parts
No alteration or modification may be undertaken
without prior agreement of the manufacturer.
Genuine spare parts and accessories specified by
the
manufacturer
contribute
to
safety.
The
manufacturer of the machine cannot be held
responsible in the event of accident related to the
use of parts other than genuine parts.
During the guarantee period, any repairs or
modifications can be made only by our fitters or
with our agreement.
1.9
Non-observanc
Non-observance
e of safety
instructions
Safety related to the correct operation of the
machine can be guaranteed only if the
instructions in this manual are respected, as well
as the conditions and operational limits mentioned
in the data sheet attached.
1.10
Warranty / guarantee
The Sterling SIHI guarantee is satisfied only
under the following conditions:

The pump is installed and operated in perfect
compliance with the instructions and under
conditions approved by Sterling SIHI.

All modifications will be submitted for Sterling
SIHI's approval before implementation.
implementation.
Doc.Num.: CL01E
Rev.:01
Rev.:
01
Date: 01/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Description and applications
2.0
Page 1 of 3
Equipment application
Chapter 2
required NPSH, so that this pump can be used
The pump is to be used only for the operating
under very difficult suction conditions.
conditions stated by the purchaser and confirmed
Heating and cooling chambers for the pump hous-
by the supplier.
ing can be inserted in place of hydraulic stages.
The guarantee conditions are
defined as per our general conditions of sale.
It is possible to add a retaining stage at the suc-
The conditions of use are defined in the attached
tion end of the pump.
data sheet.
The shaft outlet sealing can be adapted to suit the
majority of operating conditions.
The construction specifications are defined in
2.1
Safety instructions
chapter 9.
2.4
Performance data
Q(m3/h) – H(m) – P(kW) - NPSH
(See following pages)

You may use the pump only for the application
stated in the data sheet as otherwise accidents
to people and the environment may occur.

Do not exceed the density and viscosity stated
in the data sheet. Otherwise there is danger of
damage to the pump.
2.2
The pump must not operate out of the output
range defined by the minimum and maximum flow
for each size.
Accessories
The accessories delivered with the pump or the
electrical pump unit are indicated in the data
sheet. The corresponding operating and installation instructions can also be found in the appendix.
The installation of additional accessories may be
carried out only after receiving approval from the
manufacturer of the machine.
2.3
Construction and operation
CEHA pumps are side channel, multicellular, selfpriming pumps designed with up to 8 stages, having a horizontal configuration and offering numerous metallurgical variants.
They allow for the simultaneous pumping of gas
and liquid.
The use of a pre-compression turbine at the suction end makes it possible to obtain a very small
Doc.No.: CEH02ABE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Description and applications
Page 2 of 3
Chapter 2
Performance data
CEH-Pumps
n = 1450 rpm
Design tolerances: Output ± 5%
Density = 1kg/l
Delivery height ± 5%
Viscosity = 1mm²/s
Power +10%
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load
Series
Sizes
0.4
(1)
H
[m]
32
57
83
108
133
159
184
209
CEH 1201
CEH 1202
CEH 1203
CEH 1204
CEH 1205
CEH 1206
CEH 1207
CEH 1208
NPSH 1[m]
NPSH 2[m]
P
[kW]
0.42
0.76
1.1
1.44
1.78
2.1
2.45
2.8
1.3
0.11
Q [m³/h]
0.6
H
[m]
30
53
77
100
123
147
170
193
Measuring tolerances: DIN 1944
P
[kW]
0.4
0.72
1.04
1.36
1.68
2
2.3
2.65
1.3
0.11
1.0
H
P
[m]
[kW]
26
0.35
46
0.64
65
0.92
85
1.2
105
1.5
125
1.78
144
2.05
164
2.35
1.35
0.11
1.5
H
[m]
20
36
52
68
83
99
115
130
P
[kW]
0.29
0.53
0.77
1.02
1.26
1.5
1.74
1.98
1.4
0.11
2.5
(2)
H
P
[m]
[kW]
11.5
0.22
19.5
0.38
28
0.53
36
0.69
44
0.84
52
1
60
1.14
68
1.3
1.55
0.48
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
CEH 3101
CEH 3102
CEH 3103
CEH 3104
CEH 3105
CEH 3106
CEH 3107
CEH 3108
NPSH 1[m]
NPSH 2[m]
1.0
48
1.14
87
2.1
126
3.1
165
4.05
204
5
243
6
282
7
321
7.9
1.35
0.17
1.5
44
1.06
79
1.94
114
2.8
149
3.7
184
4.55
219
5.5
254
6.3
289
7.2
1.25
0.17
2.5
34
61
88
115
142
169
196
222
3.5
0.86
1.56
2.25
2.95
3.65
4.35
5.1
5.8
1.1
0.17
25
0.68
44
1.22
63
1.76
82
2.3
101
2.85
120
3.4
139
3.9
159
4.45
0.95
0.17
(2)
4.5
17
0.57
29
0.99
41
1.4
52
1.82
64
2.25
76
2.65
88
3.1
100
3.5
0.95
0.18
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
CEH 3601
CEH 3602
CEH 3603
CEH 3604
CEH 3605
CEH 3606
CEH 3607
CEH 3608
NPSH 1[m]
NPSH 2[m]
3.5 (1)
35
1.2
63
2.2
91
3.15
119
4.15
147
5.1
175
6.1
203
7.1
231
8.1
0.95
0.17
4.5
28
0.99
50
1.82
72
2.65
94
3.45
117
4.25
139
5.1
161
5.9
5 .9
184
6.7
0.95
0.18
6.0
19
33
46
60
74
88
102
115
0.78
0. 78
1.4
2
2.6
3.25
3.85
4.45
5.1
1.1
0.19
7.5 (2)
9.5
0.59
16
1.02
22
1.46
28
1.9
34
2.35
41
2.75
47
3.2
53
3.65
1.4
0.21
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
(2)
: Minimum operating flow
: Maximum operating flow
Doc.No.: CEH02ABE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Description and applications
Page 3 of 3
Chapter 2
Performance data
CEH-Pumps
n = 1450 rpm
Design tolerances: Output ± 5%
Density = 1kg/l
Delivery height ± 5%
Viscosity = 1mm²/s
Power +10%
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load
Measuring tolerances: DIN 1944
Q [m³/h]
Series
Sizes
CEH 4101
CEH 4102
CEH 4103
CEH 4104
CEH 4105
CEH 4106
CEH 4107
CEH 4108
NPSH 1[m]
NPSH 2[m]
6.0 (1)
H
P
[m]
[kW]
37
2.05
67
3.65
98
5.3
128
6.9
159
8.6
189
10.2
220
11.8
250
13.4
0.85
0.22
7.5
H
[m]
31
56
82
107
132
157
182
208
P
[kW]
1.82
3.2
4.6
6.0
7.4
8.8
10.2
11.6
0.9
0.24
9.0
10.5
H
P
[m]
[kW]
26
1.58
45
2.75
65
3.95
84
5.1
104
6.3
123
7.5
143
8.7
8. 7
162
9.8
0.95
0.28
H
P
[m]
[kW]
19.5
1.36
33
2.3
46
3.3
60
4.25
73
5.2
86
6.2
99
7.1
113
8.1
1.05
0.35
12.0 (2)
H
P
[m]
[kW]
13.5
1.2
20
1.98
27
2.75
33
3.55
40
4.3
47
5.1
54
5.9
60
6.7
1.15
0.45
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
CEH 5101
CEH 5102
CEH 5103
CEH 5104
CEH 5105
CEH 5106
CEH 5107
CEH 5108
NPSH 1[m]
NPSH 2[m]
10.5
45
4.2
82
7.9
120
11.6
157
15.4
195
19.2
232
23
270
26.5
307
30.5
0.95
0.35
12.0
42
76
111
145
179
214
248
283
4.1
7.6
11
14.4
17.8
21.5
24.5
28
1.0
0.4
14.0
37
3.75
67
6.8
96
9.9
126
13
156
16
186
19.2
216
22
245
25
1.05
0.45
16.0
32
3.4
56
6.1
81
8.8
106
11.6
130
14.2
155
17
180
19.6
205
22.5
1.15
0.5
18.0
26
3.05
45
5.4
64
7.7
84
10
103
12.4
123
14.8
142
17
161
19.4
1.25
0.55
(2)
20.0
19
2.7
33
4.65
47
6.6
60
8.6
74
10.6
88
12.6
102
14.6
116
16.4
1.35
0.65
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
CEH 6101
CEH 6102
CEH 6103
CEH 6104
CEH 6105
CEH 6106
CEH 6107
CEH 6108
NPSH 1[m]
NPSH 2[m]
16.0
53
8
96
14.8
139
21.5
182
28.5
225
35
268
42
311
49
354
56
1.3
0.35
18.0
50
90
130
170
210
251
291
331
7.6
14.2
20.5
27
33.5
40
46.5
53
1.3
0.4
20.0
46
83
120
157
194
231
268
305
7.3
13.4
19.4
25.5
31.5
38
44
50
1.3
0.4
25.0
36
64
92
120
148
176
204
232
6.2
11.2
16.4
21.5
26.5
31.5
36.5
41.5
1.3
0.55
30.0
25
43
61
79
97
115
133
151
4.9
8.8
12.8
16.6
20.5
24.5
28.5
32.5
1.5
0.65
(2)
35.0
13
4
23
7.1
32
10.2
41
13.3
51
16.4
60
19.5
69
22.6
78
25.7
1.65
0.85
NPSH 1 effective suction of a non gas-free liquid – NPSH 2 pumping under load of a high vapor pressure liquid
(1)
(2)
: Minimum operating flow
: Maximum operating flow
Doc.No.: CEH02ABE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Planning the installation
Page 1 of 4
3.0
Planning of the Installation
3.1
Piping system
Chapter 3
3.1.1 Installation diagram
by-pass
Caution

Respect the direction of flow of the fluid
flow
normalizer
(arrows on the pump flanges).

The diameters of the pipes must not be
smaller
than
the
diameters
of
the
Fig. 3.1
corresponding pump orifices (see data sheet).

Check that cleaning of all pipes has been
carried out prior to installation of the pump.

Adjust the piping positioning to ensure it does
not cause any stress on the pump orifices.

Avoid abrupt changes of piping diameter and
short radius pipe elbows.

In
case
of
change
of
diameter,
use
1 – Gate-valve at the discharge
2 – Qmin-diaphragm or relief valve
3 – Qmax-diaphragm
Qmax-diaphragm
4 – Pressure gauge
5 - Pressure gauge
6 – Gate-valve at the suction end
asymmetrical (eccentric) convergent transition
pieces in order to avoid the formation of air
pockets in the pipes.

Install a flow stabilising length before the
3.1.2 Suction line
In case of effective suction lift operation:
suction branch of the pump; it should have the
same diameter as the pump and a length 10 to
20 times the diameter of the pump.

The flow velocity in the suction line must not
exceed 1m/s.

The pipe holders and anchoring must be
designed in such a way that thermal expansion
in the pipe system does not have any effect on
the pump flanges.

and for filling of pump with liquid.

Fig.3.2
Provide for connections for pressure gauges

must slightly ascend to the pump.
In critical applications, (liquids with impurities)
the system must be protected by a finemeshed strainer.
Doc.No.: CEH03ABE
Rev.: 01
Date: 02/04/2003
The suction line is to be vertical and then

If a foot valve is used, it must be installed at
least 0.50 m below the lowest pumping level.
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Planning the installation
Page 2 of 4
Chapter 3
flow
normalizer
In case of pumping under load:
Fig.3.4
3.1.3 Discharge line
Fig.3.3

The piping must slightly descend to the
pump.

above the axis of the suction line.

Caution
The liquid level must be kept at least 0.50 m
In case of pumping in a vacuum tank, we
recommend the installation of balance piping
of Ø 25 to 50 mm (1" to 2") returning to the
tank.
Adjustment to the operating point of the pump is
to be carried out by the means of a gate valve
installed at the pump discharge line.
If there is a risk of exceeding the working
pressure, a protective device must be installed,
such as a bypass line with diaphragm or a
pressure relief valve.
In both cases of pumping:
working pressure = pressure at pump discharge
with zero flow + suction pressure
Caution
Installing a slow-closing non-return check valve
will

prevent
hammering
in
The gate valve in the suction line must be
installations with long piping.
kept completely open when starting, as well
Use constant diameter piping.
high
pressure
as during the operation of the pump.

The suction line must be protected and
3.1.4 Installing a diaphragm
insulated against heat.

A filter must be installed in the piping in case
of pumping of contaminated
contaminated liquids.
Its
section must have at least three times the
Caution
diameter of the pipe section with a mesh size
equal to 0.1 mm.

Arrange a length of flow stabilising line just
before the pump.
pump.
In case of ch
changes
anges in
diameter, use an asymmetrical convergent
transition piece to avoid the formation of gas
pockets.
- Q-max-diaphragm
In order to avoid exceeding the permitted flow, a
diaphragm
should
be
fitted
into
the
pump
discharge line (see installation diagram).
This will prevent any danger of operating with
cavitation.
- Q-min-diaphragm, relief valve
Doc.No.: CEH03ABE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Planning the installation
-
Page 3 of 4
Chapter 3
The installation of a relief valve or a
These accessories make it possible to check, for
diaphragm in the by-pass piping will ensure
example:
that the required minimum flow for the pump

The
power
load
absorbed
motor.
A
provide for sufficient cooling of the pump and
absorbed by the motor. If this power iis
s too
avoid mechanical overloads.
high, the motor is switched-off.
The
fluid
measures
the
is present (see installation diagram).
diagram). This will

detector
by
the
temperature
power
(PT100).
3.1.5 Pressure checking
The PT100 probe is a resistance thermometer
Pressure checks will be carried out by means of
intended for checking the temperature of
pressure gauges installed on the suction line and
bearings or pumpe
pumped
d liquid
liquid.. A thread
threaded
ed pipe
on the discharge line of the pump (see installation
connection is essential for it to be installed.
diagram).
The switch-off temperature has to be adjusted
10 C higher than the operating temperature.
temperature.
3.1.6 Double envelope of
or reheating casings
cooling
The

level
of
the
pumped
liquid.
To protect the pump from a possible lack of
liquid in the course of operation, it is possible
to use a level detector.
The gradual starting of the motor.

Caution
The cooling or heating piping for the shaft sealing
system will be connected to the ports provided for
that purpose.
3.4
Pumping of liquefied gases and
condensates
For the pump to handle liquefied gases and
condensates it is especially important that the
design
*
and
installation
is
carried
out
by
specialists. Incorrect operations during starting –
15°
15°
causing “dry” operation - lead to damage to pump
parts.
Please follow the instructions below:

Fig.3.5
The loss of pressure must be reduced to a
minimum in the suction line.
*:
Port in the double envelope of the case for

bends, filter, gate-valve or changes in diameter
cooling or heating fluid.

Shut-off valves are to be installed in the inlet and
outlet pipes.
suction flange (see installation diagram).
allow for a safety factor compared to the
The connections and the protection system for the
required NPSH.
electric motor will be made in accordance with the
3.3
Various accessories can be installed to contribute
to the safety of the equipment.
Doc.No.: CEH03ABE
Rev.: 01
Date: 02/04/2003

The by-pass piping is to return to the tank
and not to the pump inlet.

Accessories
The available NPSH (net positive load at the
suction flange) scheduled for the project must
Electrical connections
requirements and regulations
regulations currently in force.
A length of stabilizer pipe must be installed
with a length 10-20 times the diameter of the

3.2
The suction must not be disturbed by
The supply line must be as short as possible.
With longer lines, which may be exposed to
strong sunlight, correct insulation must be
provided.
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Planning the installation

Page 4 of 4
Chapter 3
As liquefied gases may give off oxides,
suitable filters must be provided to prevent
oxides from entering the pump. These must be
cleaned at regular intervals.

Degassing piping must be installed between
the flow stabilizer piping and the gas phase of
the tank at the suction end (see installation
diagram). This piping must be 25 to 50 mm (1’’
to 2’’) in diameter

If the pump is to be used for several tanks
with various mixtures of liquefied gases and
different vapour pressures, high performance
non-return valves must be mounted on the
pump discharge end. This is to prevent the
liquid which is being pumped from returning to
the
suction
end
when
gate-valves
are
actuated.

When draining several tanks with only one
pump, a device allowing for isolation of the
empty tank must be installed, to prevent any

gas from entering the other tanks.
Before each start-up, make sure that the pump
is filled with liquid.
liquid. It is recommended
recommended to fit a
degassing lever valve below the outlet valve.
When filling the pump this valve is kept open
continuously, until the liquid comes out.

In order to check the liquid level, a level detector must be installed to prevent the pump from
dry operation
operation.. A spe
special
cial d
design
esign exists whi
which
ch
makes it possible to add a retention stage directly on the pump (CEH..../7).

Keep the pressure balance line open at the
end which supplies to the tank.

When using the pump in explosion hazard
areas,, make sure
areas
sure that the various
various ancillaries
ancillaries
are in conformity with the current safety
standard.

At pump start-up,
start-up, the outlet gate-valve is to
remain half open. If this valve is fully opened,
there is the danger that the pump will operate
beyond its specification range and this leads to
the formation of vapour in the pump.
Doc.No.: CEH03ABE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Unpacking, handling, storage
4.0
Page 1 of 2
Unpacking, handling, storage
Chapter 4
specific conditions).
conditions). This protection is de
designed
signed
for storage duration of 3 months.
months .
4.1
Safety measures
4.3.1 Short-term storage, less than
three months
If the pump or the electric pump unit is not to be
installed immediately after delivery, the equipment
will have to be stored in a dry location and free

Never stay below the suspended load.
from vibrations, for a duration not exceeding three

Keep a sufficient safety distance during trans-
months. Moreover, it is advised to turn the pump
pump
port of the load.
shaft over manually and periodically to avoid any
Use only appropriate hoisting slings which are
risks of seizing of mobile parts.

in perfect condition.




Adjust the length of the hoisting slings in such
a way that the pump or the electrical pump
4.3.2 Long-term storage
unit is suspended horizontally and stable.
If the storage duration exceeds three months, in
Do not use the eyebolts on the pump compo-
addition to the precautionary measures specified
nents or on the motor for lifting the assembled
in 4.3.1, it is necessary to wash the pump with
pump or the complete
complete unit. They are intended
intended
fresh water and to re-apply the preserving fluid
only for handling spare parts during assembling or dismantling.
every three months. Make sure that the product
used is compatible with the pump materials and
Do not separate the documents attached to
complies with the environmental protection and
the pump.
personnel safety regulations currently in force.
Do not remove the protection caps from the
pump flanges.

Handle the pump or the pump-motor-base
4.3.3 Lengthy installation stoppage
plate assembly with care and avoid impacts.
In the event of installation stopping for more than
3 weeks (this period could be much more shorter
in unfavorable climatic conditions), drain the
pump, wash it with fresh water and spray the cor-
4.2
rosion-resistant agent
agent inside.
inside. Make sure that the
Unpacking
product used is compatible with the pump materiJust after taking delivery of the equipment and
before unpacking, a visual control of the packing
als and complies with the environmental protec-
is recommended.
recommended. If transport damage is visible,
tion and personnel safety regulations currently in
its extent is to be noted on the receipt or on the
force
delivery note.
note. Possible claims are to be lodged
immediately with the carrier.
4.4
Handling
The electric motor-pump assembly weights, as
4.3
Preservation and storage
well as those of the various components, are
After platform testing, every pump is drained and
specified on the drawings in the appendix at-
an internal corrosion-resistant protection is ap-
tached.
plied (except for pumps in stainless material or
Doc.No.: CEH04ABE
Rev.: 00
Date: 03/10/2000
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Unpacking, handling, storage

Page 2 of 2
Chapter 4
During slinging and handling of the pump or
the unit, make sure that the hoisting ropes or
slings cannot escape from the hook.

sling,
When using a single hoisting rope or sling,
it is necessary to cross them in the hook to
prevent them slipping and the load tipping
during handling.
Fig.4.1
Handling the pump
Fig.4.3
Fig.4.2
Handling the pump unit
Doc.No.: CEH04ABE
Rev.: 00
Date: 03/10/2000
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
5.0
Page 1 of 6
Installing the pump
5.4
5.1
Chapter 5
Preconditions
The pump or the electric motor-pump assembly
must have been unpacked and transported in
conformity with the recommendations shown in
chapter 4.
Tools
The assembly and installation of the pump or of the
electrical pump unit does not requir
require
e any speci
special
al
tools,, only regular tools of a mechanical and
tools
electrical workshop are needed.
5.4.1 Environmental conditions
5.2
Personnel qualifications
The work described in this chapter must be carried
out by qualified and authorized personnel only.
5.3
The permissible ambient temperature is between –
20°C and + 60 °C.
°C . The h
humidity
umidity of the air shou
should
ld
be as low as possible in order to avoid corrosion.
5.4.2 Base and foundation
Safety measures
The pump or the electrical pump unit must be
installed always on a horizontal floor or foundation
not subject to external vibration. In case of doubt
use vibration dampening feet.
For the pumps equipped with shaft sealing by
stuffing box, provide a seepage recovery pipe.






Remove the caps from the pump flanges only
when connecting the pipes.
Connect the pipes carefully as to avoid any
leakage when subjected to pressure.
Make sure that the gate-valves at the suction end
and at the discharge end are closed.
Observe
internal
regulations
concerning
conditions of operation.
Wash off the corrosion-resistant substance as
shown in chapter 4 to prevent any contamination
of the plant.
Provide an electric motor control switch and
protection system.
5.4.3 Space required
The space required for installing the pump unit is
shown in the overall dimensions drawing attached.
Make sure there is easy access to the shut-off gates
and valves as well as to the measuring instruments.
5.5
Checks before installation
Caution

Check that all electrical connections are free from
voltage and ensure that the installation cannot be
switched on inadvertently.
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
The following points must be checked before
installing the pump or the electric motor-pump
assembly:
1. Absence of voltage on the electrical connection
and ensure that the installation cannot be
switched on inadvertently.
2. Compatibility of the electric
electric power cable with the
power of the motor concerned.
3. Cleanliness and insulation
insulation of the suction
suction line and
discharge line and of the other related pipes.
4. It should be possible
possible to rotate the pump
pump easily by
hand.
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
Page 2 of 6
Chapter 5
5. Observance of instructions, regulations and
internal precautions to be observed when
carrying out the installation.
5.6
Mounting the electric motor-pump
assembly in the installation
Caution
The couplings are to be assembled on the shafts
taking care to avoid any impact.
They can be
heated to facilitate assembly.
assembly. The shaft ends must
be perfectly aligned, and the distance between the
two Sterling SIHI half-couplings must be 2 to 3 mm.
Caution
straight edge
1. Check that the general instructions given in 3.1
concerning piping are respected.
2. Make the unit perfectly level on its foundation
block by using metal shims; take care that
these shims are as close as possible to the
anchoring points.
3. Carry out an even diagonal tightening of the
unit retaining bolts on its foundation block,
block,
taking care not to cause deformation of the
base.
4. Check and adjust if necessary, the pump/motor
alignment (see 5.7).
5. Remove the protective caps from the pump
flanges, taking care that no foreign body enters
the pump.
6. Check and adjust if necessary, the positioning
of the pipe flanges on the pump flanges; no
stress must be applied to the pump flanges
during positioning and tightening.
tightening. When using
temperature, take care
in conditions of varying temperature,
particularly to avoid the transfer of stresses to
the pump flanges due to piping expansion.
7. Check the
the presence
presence and the correct positioning
positioning
of the seals between the flanges.
Tighten the piping flanges evenly and
diagonally on the pump.
9. Check the pump/motor alignment (see 5.7)
and readjust it, if necessary, by loosening the
flanges and starting again at point 4.
8.
a
b1
a1
2 to 3 mm
a = a1
Coupling
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
b = b1
Fig.5.1
If couplings other than Sterling SIHI couplings are
used, refer to the manufacturer's instructions.

It is essential that the coupling is equipped with a
guard in accordance with current regulations on
the prevention of accidents and the protection of
persons.
5.8
5.7
b
Coupling
in
ATEX
conform
pumpsets
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
Page 3 of 6
The following instructions for couplings need
especially to be followed for pumpsets which are
manufactured in conformity with Directive 94/9/EC
for operations as category II equipment in
hazardous areas.
Limitations
Only the coupling type BDS and HDS is released for
pumpsets in conformity with 94/9/EC.
These couplings are designed to be operated
according the following parameters:
o
Max 25 starts per hour
o
Daily operating cycle up to 24 h
o
Operation within the specified alignment
o
Temperature range -30°C to +80°C in the
immediate vicinity of the coupling
Storage
If coupling parts are stored as spare parts, the
storage area must be dry and free from dust. The
flexible elements must not be stored with chemicals,
solvents, motor fuels, acids, etc.. Furthermore they
should be protected against light, in particular direct
sunlight and
and bright artificial light with high ultraviole
ultraviolett
content.
Chapter 5
Failure to observe these instructions
may result in breakage of the coupling. Danger from
flying fragments! The coupling then becomes an
exlosion hazard.
Mounting the coupling parts
Before beginning installation, the shaft ends and the
coupling parts must be carefully cleaned. Before
cleaning the coupling parts with solvent the flexible
elements must be removed.
If necessary, heating the coupling parts (to max
150°C) will facilitate fittin
fitting.
g. With temperatures over
80°C the flexible elements must be removed from
the coupling part s before heating.
Coupling parts must be fitted with
the aid of suitable equipment to avoid damaging the
shaft bearings through axial joining forces. Always
use a suitable lifting equipment.
The shaft ends must not project from the inner sides
of the hub. Axial securing is effected by means of
the set screw.
The storage area must not contain
any ozone-generating equipment, e.g. fluorescent
light sources, mercury vapour lamps, high voltage
electrical equipment. Damp storage areas are
unsuitable. Ensure that no condensation occurs.
The most favourable atmospheric humidity is below
65%.
Installation
Type B and H couplings shall never be operated
in pumpsets category II.
The flexible elements are delivered in different
materials and are then differently couloured or
marked with stripes in different colours. Only
elements of one type must be used in one
coupling.
When assembling a pumpset with a coupling,
the fits of the bores and shafts must be checked,
see table 5.c1
Table 5.C.1 Tolerances for coupling fit
Fit
Nominal Shaft
Coupling
diameter tolerance bore
tolerance
Shaft
 50 mm k6
H7
tolerance > 50 mm m6
Tightening the set screws to a
tightening torque in accordance with the table 5.C.3.
Failure to observe these instructions
may result in breakage of the coupling. Danger from
flying fragments! The coupling then becomes an
explosion hazard.
After fitting the coupling parts onto the shafts the
flexible elements, if previously removed must be
fitted. Previously heated coupling parts must have
cooled down again to a temperature below +80°C. It
must be
be ensured
ensured that tthe
he fl
flexibl
exible
e element
elements
s are o
off
identical size and colour or have identical marking.
Move together the components to be coupled.
Danger of squeezing!
Alignment
The couplings connect the 2 shaft ends of the driver
and the pump. The alignment of the shaft ends
needs to be adjusted within the following tolerances.
The errors of alignment are differentiated into:
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
o
o
o
Page 4 of 6
Axial misalignment:
misalignment: the allowable
difference between maximum and minimum
axial gap S between the two coupling halfes is
given Table 5.C.2.
Angular misalignment:
misalignment: this can
usefully be measured as the difference in the
gap dimension S = Smax – Smin. The allowable
values are given in Table 5.C.2 depending on
coupling size and speed
Radial misalignment is the radial
offset
between
the
shaft
centers.
The allowable values are the same s values
like for the angular misalignment given in Table
5.C.2..
The method to adjust the alignment is:
first correct the angular misalignment
misalignment
then correct the axial gap
then correct the radial misalignment.
The useful tool are a feeler gauge and a ruler as
shown in figure 5.C.2.
Table 5.C.2 Alignment dimensions
Coupling
type
BDS
Axial
gaps
mm
76
2–4
Angular and radial alignment
S max in mm
at speed
750
1/min
0,25
1000
1/min
0,2
1500
1/min
0,2
2000
1/min
0,15
3000
1/min
0,15
88
2–4
0,25
0,2
0,2
0,15
0,15
103
2–4
0,25
0,25
0,2
0,2
0,15
118
2–4
0,3
0,25
0,2
0,2
0,15
135
2–4
0,3
0,25
0,25
0,2
0,15
152
2–4
0,35
0,3
0,25
0,2
0,2
172
2–6
0,4
0,35
0,3
0,25
0,2
194
2–6
0,4
0,35
0,3
0,25
0,2
218
2–6
0,45
0,4
0,3
0,3
0,2
245
2–6
0,5
0,4
0,35
0,3
0,25
Fixing the coupling on the shaft.
For fixing the coupling parts on the shaft there are
set screws, which need to be locked with the
following torque depending on coupling size:
Table 5.C.3
5.C.3 Torque for
for Set Screws
Screws
Size
Torque Nm
Size
Torque Nm
76
4
172
15
88
4
194
25
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
103
4
218
25
118
4
245
25
135
8
Chapter 5
Operation:
If any irregularities are registered
during operation (vibrations or noise) the pumpset is
to be switched off immediately. Determine the cause
of the fault
fault usin
using
g the fault
fault list in Ch
Chapte
apterr 8. This list
list
contains possible faults, their reasons and
succested actions.
If the analysis is not possible then contact the
Sterling Service.
Maintenance:
regular control of the torsional
backlash is necessary to prevent breakdown.
The torsional backlash is to be measured in the
following way: One coupling part is rotated against
the other with no torque to a stop. Then this position
of the two coupling halfes is marked as shown in the
left had picture of figure 5.C.3. Then the coupling
parts are rotated into the other direction as far as
possible without torque. The distance between the
two marks is the backlash measure delta sb. The
maximum values for this measure are given in table
5.C.4 by coupling size. If this measure is exceeded,
then the flexible elements need to be exchanged.
the flexible elements must be
replaced in sets (all elements of one coupling at
once, independent of the individual wear) Only
identically marked flexible elements must be used.
Only spareparts from the original equipment
manufacturer is allowed for replacement.
Table 5.C.4 Torsional Backla
Backlash
sh measure
Size
Delta
mm
Size
delts
76
7,0
88
5,0
103
7,0
194
8,0
218
7,0
245
6,5
118
9,0
135
10,5
152
11,5
172
9,0
152
8
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
Page 5 of 6
Chapter 5
Figures:
Figure 5.C.1
Measures for checking alignment
Smax
Smax
•S
Smin
Smin
•S = Smax - Smin
Figure 5.C.2
Checking of alignment
Ruler
S
Figure 5.C.3
Measurement
Measurement of Torsional Backlash
•Sb
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Installing the pump
5.9
Page 6 of 6
Pump mounting for operation at
high temperatur
temperature
e
5.12
Chapter 5
Hydrostat
Hydrostatic
ic pressure test
When subjecting the piping system to a
hydrostatic pressure test, exclude the pump from
this test. Otherwise make that no foreign bodies
can enter the pump.
Caution


If this pump is intended to convey a hot fluid,
(with cooled shaft sealing), the retaining
screws at the pump drive end are to be locked.
The nuts and spring washers at the opposite
end must allow for pump dilation in the
longitudinall direction.
longitudina
The hydrostatic test pressure for the pump must
not exceed 1.
1.3
3 ttim
imes
es the no
nomi
mina
nall pum
pump
p
pressure.. (See the data sheet in the appendix).
pressure
After mounting the two spring washers in the
opposing position shown, position the flat washer
and screw the self-locking nut into contact (the
washers must be able to be moved by hand).
Then tighten the two self-locking nuts half a turn.
pump foot
retaining
stud
self-locking nut
flat washer
base
spring
washers
Fig.5.2
5.10
Monitoring and regulation
The monitoring / regulation accessories and
instruments must be set up in accordance with
their individual instructions (see appendix).
5.11
Final checks
The following final checks must be carried out:
Check all tightening that has been carried out
during the mounting of the pump in the
installation, particularly the tightening of the
connecting flanges.
Check that the pump can be rotated easily by
hand (turn the motor fan for this).
Check the alignment.
Verify the presence and check the fastening of




the coupling guard.
Doc.No.: CEH05ABE
Rev.: 02
Date: 02/10/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Commissioning and
decommissioning
Page 1 of 3
6.0
Commissioning and
decommissioning
6.1
Preconditions

Chapter 6
As soon as the rated speed is attained, the
The pump or the electrical pump unit must have
flow adjustment will be done by means of the
been installed according to the directions and
gate-valve placed at the discharge
discharge end of
of the
instructions in chapter 5.
pump. The gate-valve at the suction end must
always be open during operation to prevent
cavitation, both during effective suction and
6.2
Personnel qualification
under load.
The work described in this chapter must be
carried out by qualified and authorized personnel
only.
6.4
6.3
Filling the pump
Safety measures
Caution
To preserve the installation from pollution by the
anti-corrosion

All electrical connections are to be carried out
according to the rules of the trade, in
accordance
with
current
product
and
to
avoid
any
compatibility problem with the pumped substance,
the pump must be rinsed out. The anti-corrosio
anti-corrosion
n
product is water-soluble.
relevant
requirements, laws and regulations.

Only authorized and qualified personnel may
Before the first start, the pump and the suction
carry out this work.
line, must be completely filled with the pumping
liquid to prevent the pump running dry and to
avoid the formation of air pockets and thermal
shock.


Fill the pump correctly in order to avoid any
damage due to dry operation (the shaft sealing
or sleeve bearings could be destroyed and
6.5
moving parts could seize).
circuit diagram
diagram in the termin
terminal
al box. (See safety
safety
Check the direction of rotation only after filling
measures in 6.3).
the
pump
and
at
the
precise
Electrical connection
The motor has to be connected according to the
moment
described in 6.7.


Fill the pump very slowly if hot pumping liquid
6.6
is used in order to avoid distortions or thermal
The
shock.
accessories must be carried out in accordance
When
pumping
explosive,
harmful,
hot,
crystalline or corrosive products, ensure that
persons
and
the
environment
are
Accessories
installation
and
connections
of
the
with their attached commissioning instruction
manuals. (See appendix).
not
endangered.
Doc.No.: CEH06ABE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Commissioning and
decommissioning
6.7
Page 2 of 3
Checking before switching-on
Chapter 6
If the pumping pressure does not constantly
rise with increasing speed, stop the motor
again and bleed the pump carefully again.
5. After reaching operating speed, adjust the
Caution
operating point of the pump by means of the
regulating gate-valve in the discharge line.
Before switching-on the pump unit, ensure that
nobody can be endangered by starting the pump
unit.
It is mandatory to check the following points:
Caution
1. The pipelines are all
all connected and the unions
are leak proof.
Operating with the gate-valve closed at the
2. The pump and pipes
pipes are correctly filled and air
air
has been bled.
discharge end, even for short durations, is
possible only if the installation is equipped with a
3. The cooling system supply (if applicable) is
open and its system has been bled.
by-pass providing for circulation of the minimum
flow necessary for the correct operation of the
4. If the installation is protected by
by a relief valve
pump. If not, operating with the gate
gate-valve
-valve closed
make sure that its adjustment is correct,
at the discharge end quickly causes destruction of
particularly in accordance with the pressure
the sealing and seizing of the moving parts.
rating of the pump housing.
5. The regulating gate-valve
at the
the discharge
discharge
end is fully opened.
6.9
6. The gate-valve at
at the suction end
end is completely
open.
Frequency of switching on/off
The CEHA pump may be switched on up to 15
times per hour.
7. The coupling alignment has been checked and
is correct (see chapter 5).
8. The coupling
coupling guard is in place
place..
6.10
Checks during operation
9. The motor is ready for operation.
10.At this point check the direction of rotation
of the motor (short pressure on the switch), the
Caution
rotation of the CEHA pump is anti-clockwise
when facing at the end of the pump drive shaft.
During operation, the following points must be
checked:
6.8

Commissioning
discharge end.
For commissioning proceed as follows:
1. Open the gate-valve
gate-valve at the suction
suction end fully.
fully.
2. Open
the
discharge
regulating
end
fully.
gate-valve
When
at

pumping

Check the liquid level in the tank at the suction
end.

3.4).
The pump runs regularly, smoothly, and
without vibration.
the
condensates, only half-open this valve (see
Check the temperature of the pump bearing
(maximum temperature 80 °C or 50 °C above
3. Switch on the motor.
motor.
the ambient temperature).
4. Check the pressure on the
the pressure gauge at
the discharge end.
Constant rotation speed and pressure at the

Check the temperature of the shaft sealing
coolant.
Doc.No.: CEH06ABE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Commissioning and
decommissioning


Page 3 of 3
Chapter 6
If shaft sealing is provided by a stuffing box, 10
6.11 Decommissioning
to 20 drops per minute leakage is necessary
When decommissioning the unit, proceed as
and normal to avoid overheating of the sealing
follows:
system.
1. Shut-off the motor po
power
wer supply.
If shaft sealing is provided by a rotating
2. Close
mechanical seal, a slight leak is possible at the
the
regulating
gate-valve
at
the
discharge end.
first startup; if the conditions allow it, let it run
3. Close the g
gate-valve
ate-valve at the
the suction end.
end.
for 30 minutes so that the components take up
4. Close the sh
shaft
aft sealing coolant inle
inlet.
t.
their positions.
positions. If the leak persists, dismantle.
dismantle.
Drain the pump if there is a risk of freezing.
Caution
In the event of significant leakage, stop the pump
as soon as possible, and check the shaft sealing.
If draining the pump produces explosive, harmful,
or crystalline
measures
to
products, take
protect
the
persons
necessary
and
the
environment.
If the pump has to be dispatched elsewhere, it
must be free of any dangerous product.
In the event of prolonged stoppag
stoppage
e of the pump, it
must be rinsed and then protected internally with
a suitable anti-corrosion product.
Doc.No.: CEH06ABE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Maintenance, disassembly,
assembly
7.0
Page 1 of 5
Maintenance, disassembly,
assembly
Chapter 7
After 8 000 service hours, or at the latest 2 years
after commissioning, check the inner sleeve bearing for wear. Replace it, if necessary.
7.1
Preconditions
Shaft sealing
The pump or the electric motor / pump assembly
After prolonged use and frequent re-tightening,
must be put out of operation in accordance with
the stuffing-box packing rings can lose their origi-
the instructions in chapter 6.
nal elasticity, and must be renewed.
After 2500 hours of operation, we advise you to
7.2
Personnel qualification
check the packing rings; if settling of the rings is
The work described in this chapter must be car-
equal to 20% or has a value of a half ring, they
ried out by qualified and authorized personnel
must be changed.
only.
Rings replacement: see 7.7.4
Any work on electrical connections must be carried out by authorized skilled staff only.
7.5
7.3
7.5.1 Preparation for disassembly
Safety measures
Disassembly
Proceed as follows:
1. Make sure that the pow
power
er supply is switchedoff and cannot be switched-on inadvertently
during the operation.
operation.
2. Disconnect the motor in the
the terminal b
box.
ox.

If the pump has conveyed explosive, hot, toxic,
crystalline, etc. products, the necessary measures must be taken so that persons and the
environment are not endangered.

In the event of the pump being dispatched
elsewhere, it must be free from any trace of
pumped product.

Since the pump could still contain pumped
product, it must be rinsed out carefully prior to
disassembly.
7.4
3. Shut off the isola
isolation
tion gate-valves at the suction
and discharge ends, and carefully drain this
part of the installation.
4. If necessary, disconnect and dismantle the
measuring and checking instruments.
5. Disassemble the pum
pump
p flanges and disassemdisassemble the pump from the base plate.
6. Drain the pump
pump,, and then rin
rinse
se it again, if n
nececessary.
7.5.2 Spare parts
Maintenance and inspection
When ordering spare parts, note the information
given on the pump identification plate, that is to
say:
1. The exact type of pump.
2. The complete pump identification number.
Caution
Use the attached cross-sectional drawing to note
the identification references of the items required.
r equired.
After commissioning this kind of pump requires
The spare parts must meet the manufacturer’s
only little maintenance.
maintenance.
technical requirements, and the guarantee is only
For checks during operation refer to 6.10.
valid when genuine original parts are used.
Bearings
Sterling SIHI will not admit liability in the event of
The ball bearing is lifetime lubricated and does
failure or accident related to the use of parts other
not require any maintenance.
Doc.No.: CEH07AE
Rev.: 01
Date: 02/04/2003
than genuine parts.
Sterling Fluid Systems (France)
Information subjected to technical
Member of Group
alterations due to engineering development
Sterling Fluid Systems
Maintenance, disassembly,
assembly
Page 2 of 5
7.5.3 Disassembly of the pump
Chapter 7
7. Disassemble the screws 9011 and the cap
See the sectional drawing attached.
3600, then remove the circle 9320, and the
The working surface must be clean, free from dirt,
spacer 5051.
8. Separate the bearing casing 3500 from the
filings etc. and be perfectly clear.
1. To facilitate later assembly
assembly make marks along
discharge flange 1070 and from the stuffing
the whole length of the pump body and num-
box casing 4510 by removing the screws
ber the parts.
9012.
2. Disassembly starts at the suction end.
3. Remove the nuts
nuts 9201,
9201, the flat washers
washers 5500,
the cup springs 9512 (only for model 501 with
cooling casing), the tie bolts 9050 and extract
the suction flange 1060.
9. Use a hub puller to extract the bea
bearing
ring casing
3500 with the ball bearing 3210 and the spacer
5050.
10.Remove the hexagonal nuts 9200; extract the
gland 4520, slide the stuffing box casing 4510
along the shaft. Extract the stuffing box packing rings 4610, the stuffing box intensive cooling ring 4420 with its gaskets 4120 (only for
model with cooling casing).
The pump may still contain residues of pumped
fluid or of rinsing
rinsing product.
product.
Take precautions
precautions to
7.6
Work after the disassembly
contain any leakage.
7.6.1 Cleaning instructions
4. Release the lock washer 9310 and loosen the
hexagonal nut 9220 while holding the shaft
with a strap wrench or gripping it in a soft jaw
vice.
The use of some solvents requires special precautions. Refer to the supplier's recommendations
CAUTION
and to current regulations.
The hexagonal nut 9220 has a left-hand thread
Clean all parts using an appropriate solvent.
5. Disassemble successively the impellor 2310,
A scraper can be used to remove the residue of
the key 9402, the centrifugal body 1080 and
adhesive on the mating faces of the bodies; take
the shaft sleeve 5240 (only sizes 4100 –
care not to damage the surface finish during this
6100).
operation.
6. Then, disassemble the inlet body 1090, the
vane impeller 2350, the key 9411 (9401) and
the discharge body 1140. Repeat this procedure as many times as there are stages, (the
last discharge body bears the number 1141).
Doc.No.: CEH07AE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Maintenance, disassembly,
assembly
Page 3 of 5
Chapter 7
7.6.2 Repair instructions
Caution
The following parts must be checked carefully:
1. Ball bearing 3210
Since the bearing is lubricated for life, it does not
35°
require any maintenance.
maintenance. Check it for wear
and change it if necessary.
2. Lip sealing ring 4210
Fig 7.1: drive end view
If the shaft is marked at the corresponding location, change the lip sealing ring; pay attention
to the correct mounting position to prevent the
grease from escaping and to prevent dirt entering.
3. Stuffing b
box
ox packing rings 4610
4610
Change the rings in accordance with the directions given in 7.7.4.
4. Shaft 2100
Any pronounced mark on the shaft, at the stuffing
box rings, at the lip sealing ring or bearing
bush positions requires it to be changed.
5. Shell bearing 0241
In the event of severe wear on the shell bearing
0241 (play >0.2mm), carry out its replacement
as follows:

Extract the worn shell bearing.

Degrease the bore of the body 1080 using a
solvent. Spread adhesive
adhesive on the parts accordaccording to the instructions of the adhesive manu-
facturer (Loctite 640 or equivalent).
Cold-press the bearing bush 0241 into the body
1080; ensure that the lubrication groove is correctly orientated (Fig 7.1).
6. Body 1090, 1140, 1141
Body surfaces in contact with the wheel may be
re-machined to a max. of 0.5 mm with a plane
plane
parallelism defect of 10 µm in relation to the
mating surfaces. The max. admissible roughness height of the re-worked surface will be Rt
= 6 µm. The mating surface of the body 1090
has to be re-machined also, in such a way that
the depth is greater by min. 0.10 mm to max.
0.13 mm (sizes 1200/3100/3600) and by min.
0.15
mm
to
max.
0.20
mm
(sizes
4100/5100/6100) in relation to the thickness of
the vane impellor.
Since hydraulic perform-
ance is linked to the depth of the bodies, do
not re-machine more than necessary.
N.B.: For multi-stage pumps and for a complete
overhaul, it is preferable to mix new stages
and old re-machined stages to avoid out-ofline keying, losses of efficiency or out-of-line
pump mounting brackets in relation to the base
plate mounting holes.
7. Vane impeller 2350
Re-machining the wheel produces uncontrolled
changes in specifications and interchangeability is no longer guaranteed.
8. Body she
shellll bearings
bearings 0242
0242
(Sizes 4100 to 6100 only)
In the event of severe wear, they must be
changed. These shell bearings have to be
cold-pressed and glued with a product like
Loctite 640 or equivalent.
Doc.No.: CEH07AE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Maintenance, disassembly,
assembly
Page 4 of 5
Chapter 7
cooling casing) and the stuffing box packing
9. Shaft sleeve 5240
rings 4610.
(Sizes 4100 to 6100 only)
2. Position the gland 4520 and screw in the two
In the event of severe wear, they must be
nuts 9200 slightly.
changed.
3. Assemble the bearing casing 3500, after
7.7 Assembly
checking that the radial shaft seal ring 4210 is
present, then fasten the assembly on the discharge flange 1070 using screws 9012.
7.7.1 Instructions before assembly


4. Pass the shaft 2100 through the assembly;
Make sure that all the parts have been
mount the spacer 5050 and the ball bearing
checked and are perfectly clean (mating
3210 and
and the spacer
spacer 5051. Secure the shaft
planes, faces of the bodies).
by the circlip 9320, then fasten the cap 3600
Coat all sliding surfaces with molybdenum
using the screws 9011.
disulfide paste, except for carbon surfaces.

Sealing of the mating surfaces on the hydrau-
(drive shaft end downwards), wedge it or
lic part bodies is done by:
clamp the shaft end in an opening in the
- Adhesive EPPLE 33 or equivalent for cast
bench.
6. Assemble the discharge b
body
ody 1141 (1140 for
iron pumps.


5. Position the assembly vertically on the b
bench
ench
- Soft Teflon cord for stainless steel pumps (Ø
the following stages), the key 9411 (9401), the
0.75 mm for sizes 1200, 3100, 3600 / Ø 1 mm
for sizes 4100, 5100, 6100).
vane impeller 2350 and the inlet body 1090.
Repeat this procedure as many times as there
It is mandatory to ensure that the bodies are
are stages, until all stages are mounted; en-
correctly orientated
orientated to ensure
ensure correct operaopera-
sure that bodies are correctly orientated in ac-
tion of the pump (use the bodies assembly dia-
cordance with the location drawing attached.
gram attached). The reference marks traced
Then reassemble the shaft sleeve 5240 (only
before disassembly simplify this aspect.
sizes 4100 to 6100), the centrifugal body 1080
For pumps which require adhesive, immedi-
(do not forget the positioning of the soft Teflon
ately coat the mating faces of the bodies 1140,
cord sealing for pumps which require it), the
1141, 1080, and 1090 so as to allow the adhe-
key 9402 and the vane impeller 2310.
sive to cure slightly before assembly.
7. Position the lock washer 9310. Tighten the
wheel nut 9220 and secure it by bending the
lock washer.
7.7.2 Tightening torque
Nuts and bolts must be tightened using a torque
CAUTION
wrench. The following tightening torques
torques must be
applied:
The hexagonal nut 9220 has a left-hand thread
Rated Ø
M5
M6
M8 M
M10
10 M1
M12
2 M16
M16 M20
M20
Torque Nm
4.5
8.5
12
25
40
90
175
7.7.3 Assembling the pump
1. Mount the stuffing box casing 4510 on the
discharge casing 1070, then place the stuffing
box cooling ring 4420 with its O-rings 4120 on
the stuffing box casing (only for models with
Information subjected to technical
Doc.No.: CEH07AE
alterations due to engineering development
Rev.: 01
Date: 02/04/2003
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Maintenance, disassembly,
assembly
Page 5 of 5
Chapter 7
Skew cut
Staggered cuts
8. Mount the suction flange 1060, the tie bolts
9050 with the spring washers 9512 (models
with cooling casing) and the flat washers 5500.
Tighten the nuts 9201 slightly. Grease the tie
bolt ends, the washers and nuts for better
Fig. 7.3
tightening torque distribution.
Positioning the preformed rings
9512
9201
Caution
When running, the stuffing box should not exceed
a temperature which is bearable to the touch and
should leak in small drops.
5500
9050
Fig.7.2
Location of spring washers at the suction end
7.8
Checking after assembly
9. Place the pump on a surface plate
plate straighten
the retaining lugs and gradually tighten the tie
Caution
bolt nuts 9210
9210 diagonally,
diagonally, observing the tightening torques specified in 7.7.2.
10.Insert the key 9400 and the half-sleeve of the
coupling, without hitting it; heat it if necessary.
1. Check that th
the
e pump rotates freely by
by hand.
2. Check and if necessary correct th
the
e tightening
torque on the tie bolt nuts. Leave th
the
e pump
several hours before operating it (to allow the
7.7.4 Changing the stuffing box packing rings
sealing compound to dry).
3. Perform a hydrostatic test under maximum
pressure equal to 1.3 times the rated pressure
Changing the stuffing box rings can be done with-
(see the data sheet for the definition of the
out disassembling the pump entirely.
rated pressure). Choose a test liquid which is
compatible with the pumped product.
1. Loosen the gland and move it out of the way.
2. Extract the worn rings, taking care not
not to dam-
4. After the test, check the tightening torque of
the tie-bolts, correct it if necessary.
age the surface finish of the shaft.
3. The rings are preformed and precut; position
the rings with their gaps staggered.
4. The rings must be pushed back using the stuffing box gland.
7.9
Installing in the plant
When installing in the plant, follow the notes
shown in chapter 5.
5. Tighten the gland nuts until you feel a slight
friction when turning the pump shaft by hand.
6. Loosen the gland again
again and tighten it slightly.
Doc.No.: CEH07AE
Rev.: 01
Date: 02/04/2003
Information subjected to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Help in case of trouble
Page 1 of 1
8.0
Troubleshooting
8.1
Personnel qualifications
Chapter 8
Troubleshooting
Troubleshoo
ting must be carried out by qualified, authorized personnel only.
Problem
Poor performance
Cause
- Counter pressure too high.
- Pump or pipe not full or not completely
free of gas.
- Suction lift too high or positive suction
head too low.
- Clearances too large due to wear.
- Wrong direction of rotation.
- Foreign body in pump.
- Stuffing box too loose.
- Air leakage between bodies or at flanges
on the suction line.
- Bodies, shaft sealing, foot valve or
suction line leaking.
Pump runs irregular or noisy
- Suction lift too high or positive suction
head too low.
- Stresses on the pump or on the electric
motor /-pump assembly.
- Foreign body in the pump.
- Leak between the bodies due to loose tiebolts.
Pump leaking
- Leak at mechanical seal.
- Leak at stuffing box too large.
- Pump or pipe not completely filled.
High pump temperature
- Suction lift too high or positive suction
head too low.
Motor protective circuit breaker
opens
- The pump operates with the discharge
gate closed without by-pass or the
minimum rated output is not respected.
- Stresses on the pump or on the electric
motor / pump assembly.
- The specified operating point is not
correct.
- Absorbed current higher than the
specified max. limit value of the thermal
relay.
- Stuffing box too tight.
- Foreign body in the pump.
Doc.No.: CL08E
Rev.: 00
Date: 03/10/2000
Solution
Check and readjust the operating point.
Clean the pipes.
Bleed and fill the pump and the suction
line.
Check the level of liquid in the tank; open
the gate-valve at the suction end.
Clean the filter at the suction end.
Replace worn pump parts.
Reverse two phase wires on the motor.
Open and clean pump.
Re-tighten the gland.
Re-machine the bodies sealings.
Replace the flange seals.
Check the body seals.
Check the shaft sealing.
Check the flange mating.
Check the liquid level in the tank; open the
gate at the suction end.
Clean the filter at the suction end.
Check the mounting of the pump, the
coupling alignment and the pipe coupling.
Open and clean the pump.
Check the tightening torque of the tie bolts
nuts, if the leakage remains re-work the
intermediate pieces sealing.
Check the friction surfaces, replace the
sealings if necessary.
Adjust the stuffing box.
Change the stuffing box packing rings.
Bleed and fill the pump and the suction
line.
Check the liquid level in the tank; open the
gate-valve at the suction end.
Clean the filter at the suction end.
Open the discharge gate-valve or install a
by-pass, check the minimum output.
Check the mounting of the pump, the
coupling alignment and the pipe coupling.
Check and adjust the operating point (see
data sheet).
Check the motor protective circuit breaker
and the electrical connections.
Adjust the stuffing box.
Check the pump for free rotation, dismantle
and clean the pump.
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
Page 1 of 11
Chapter 9
9.0
Appendices
9.1
Cross sectional drawing - CEHA pump – shaft sealing by stuffing box
*only for sizes 4100 to 6100 as from 5-stage models - **only for sizes 4100 to 6100.
***flat key (9401) for sizes 5100 and 6100.
Fig.9.1.a
0
0
1
2
0
0
4
9
1
1
0
9
0
6
3
1
5
0
5
9
0
1
2
3
0
5
0
5
0
0
2
9
0
2
0
9
0
0
5
3
2
1
0
9
0
1
2
4
0
1
6
4
0
2
5
4
0
1
5
4
1
1
4
9
*
*
*
1
0
4
9
*
2
4
2
0
0
4
1
1
*
*
0
4
2
5
0
5
0
9
0
1
6
5
0
3
0
9
1
4
1
1
0
7
0
1
0
2
3
0
9
0
1
0
5
3
2
1
4
2
0
8
0
1
2
0
4
9
0
0
1
3
2
0
0
5
5
0
1
3
9
1
0
2
9
0
2
2
9
0
6
0
1
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
Page 2 of 11
Chapter 9
9.2
Cross sectional drawing - CEHA pump – shaft sealing by cooled stuffing box
*only for sizes 4100 to 6100 as from 5 stage models - ** only for sizes 4100 to 6100
*** flat key (9401) for sizes 5100 and 6100
Fig.9.2.a
0
0
4
9
1
1
0
9
0
0
6
3
0
2
3
9
0
1
2
3
1
5
0
5
0
0
2
9
0
5
0
5
0
2
0
9
0
0
5
3
2
1
0
9
0
1
6
4
0
1
5
4
0
1
2
4
0
4
0
9
0
1
3
7
0
3
0
9
1
4
1
1
0
7
0
1
1
1
4
9
0
2
1
4
*
*
*
1
0
4
9
0
5
3
2
*
2
4
2
0
0
4
1
1
2
5
0
5
0
9
0
9
0
1
0
6
0
1
1
4
2
0
0
8
0
1
2
0
4
9
0
1
3
2
2
1
5
9
0
0
5
5
0
2
5
4
0
1
6
5
0
2
4
4
*
*
0
4
0
0
1
2
0
1
3
9
0
2
2
9
1
0
2
9
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.3
Page 3 of 11
Chapter 9
Appendix – Parts list
CEHA pump – shaft sealing by stuffing box and cooled stuffing box
0241
0241
Bear
Bearin
ing
g bush
bush for
for iint
nter
erme
medi
diat
ate
e piec
piece
e 1080
1080
02
0242*
42*
Bearin
Bearing
g bush
bush for
for interm
intermedi
ediate
ate piece
piece 1140
1140 (si
(sizes
zes 410
4100
0 to 6
610
100
0 from
from 5 stages
stages))
1060
Suction casing
1070
Discharge casing
1080
Intermediate piece
1090
1140
Intermediate piece
Intermediate piece
11
1141
41
Inte
Interm
rmed
edia
iate
te pi
piec
ece
e (l
(las
astt inte
interm
rmed
edia
iate
te be
befo
fore
re d
dis
isch
char
arge
ge casi
casing
ng))
2100
Shaft
2310
Impeller
2350
Vane wheel impeller
3210
Ball bearing
3500
Bearing housing
3600
Bearing cover
4120
Seal for cooling insert 4420
4210
Sealing ring for ball bearing 3210
4420
Cooling insert
4510
4520
Stuffing box housing
Gland
4610
Stuffing box packing ring (preformed "tefloned" rings)
5050
Spacer
5051
Spacer
52
5240*
40***
Bearin
Bearing
g bush
bush (inter
(interme
media
diate
te casin
casing
g 108
1080),
0), for
for sizes
sizes 4100
4100 to 6100
6100
5500
Flat washer (tie bolt)
56
5610
10
Spline
Splined
d guid
guide
e pin
pin (disch
(discharg
arge
e fflan
lange
ge/st
/stuff
uffing
ing bo
box
x casin
casing/b
g/bear
earing
ing hou
housin
sing)
g)
9011
9011
Hexa
Hexago
gona
nall s
scr
crew
ew (b
(bea
eari
ring
ng co
cove
verr rret
etai
aini
ning
ng))
90
9012
12
Hexag
Hexagona
onall screw
screw (disc
(discha
harge
rge fla
flange
nge/st
/stuff
uffing
ing box cas
casing
ing/be
/beari
aring
ng c
casi
asing
ng rreta
etaini
ining)
ng)
9020
Dowel p
piin (stuffing b
bo
ox)
9030
Plug
Plug (di
(disc
scha
harg
rge
e fla
flan
nge dra
rain
in hole)
le)
90
9040
40
9050
Plug
Pluggi
ging
ng scr
screw
ew (di
(disc
scha
harg
rge
e flan
flange
ge for
for coo
coole
led
d stuf
stuffi
fing
ng box
box ver
versi
sion
on))
Tie bolt
9200
Hexagonal nu
nut ((s
stuffing b
bo
ox)
9201
Hexagonal n
nu
ut ((ttie b
bo
olt)
9220
9220
Hexa
Hexago
gon
n nut
nut ((sh
shaf
aft,
t, le
left
ft-h
-han
ande
ded
d thre
thread
ad))
9310
Lock washer fo
for shaft nut
9320
Circlip ((b
bearing)
9400
Flat key (motor drive)
9401***
940
1***
Flat key (vane
(vane wheel
wheel impeller
impeller drive,
drive, size
sizes
s 5100
5100 a
and
nd 6100)
6100)
9402
Flat ke
key (i
(impellor 23
2310 d
drrive)
94
9411
11
Disk
Disk key
key ((va
vane
ne whee
wheell iimp
mpel
elle
lerr d
driv
rive,
e, size
sizes
s1
120
200
0 tto
o 410
4100)
0)
95
9512
12
Spri
Spring
ng wash
washer
er (p
(pum
ump
p eq
equi
uipp
pped
ed with
with cool
coolin
ing
g casi
casing
ng))
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.4
Page 4 of 11
Chapter 9
Appendix – Dimension drawing – CEHA pump
f
a
uk
Ød2
ØD Øk
l
dk6
DNA
w
u
uk
15°
ØkE
t
DNE
c
h
h
ue
Ød2
e1
e2
s
b
q1
m2
n2
n1
m1
ue: draining hole - uk: Connection to the sealing cooled casing
Dime
Di
mens
nsio
ions
ns:: G1
G1/4
/4”” for
for si
size
zes
s 120
1200
0 to 51
5100
00 - G3
G3/8
/8”” for
for si
siz
ze 61
6100
00
Fig.9.3
Sizes
DNA
DN
b
C
e1
e2
f
h1
h2
n1
n2
Q1
s
d
l
t
u
w
E
1200
20
40
35
10
44
41
171
100
100
100
105
113
13
14
25
16.1
5
176
31/3600
32
65
35
12
50
42
201
112
132
112
135
134
13
19
40
21.5
6
214
4100
40
80
40
15
52
43
195
132
140
132
155
140
13
24
45
26.9
8
238
5100
50
100
45
18
60
66
237
160
165
160
170
159
15
28
50
30.9
8
276
6100
65
100
50
20
64
63
262
180
180
180
195
172
15
32
65
35.3
10
300
(in models with stage cooling chamber or retaining stage, the latter take the place of a hydraulic stage)
1 stage
2 stages
3 stages
4 stages
Sizes
a
m1
m2
a
m1
m2
a
m1
m2
a
m1
m2
12..
195
238
204
229
272
238
263
306
272
297
340
306
31/36..
213
261
227
253
301
267
293
341
307
333
381
347
41..
268
294
260
323
349
315
378
404
370
433
459
425
51..
305
353
315
380
428
390
455
503
465
530
578
540
61..
338
391
353
428
481
443
518
571
533
608
661
623
5 stages
6 stages
7 stages
8 stages
Sizes
a
m1
m2
a
m1
m2
a
m1
m2
a
m1
m2
12..
331
374
340
365
408
374
399
442
408
433
476
442
31/36..
373
421
387
413
461
427
453
501
467
493
541
507
41..
488
514
480
543
569
535
598
624
590
653
679
645
51..
605
653
615
680
728
690
755
803
765
830
878
840
61..
698
751
713
788
841
803
878
931
893
968
1021
983
Flanges connection as per DIN 2501 PN40
DNA/E
20
32
40
50
65
80
100
Øk
75
100
110
125
145
160
190
ØD
115
140
150
165
185
200
235
Ød2 x n
14 x4
18 x4
18 x 4
18 x 4
18 x 8
18 x 8
22 x 8
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.5
Page 5 of 11
Chapter 9
Appendix – CEHA pump - Forces and permissible moments on the flanges
MxA
A
y
F
FxA
FxE
E
y
F
FzA
FzE
E
x
M
Fig.9.4
If several individual forces are developed,
developed, the components of the resultants of these forces should
not exceed the acceptable values in each direction.
The pump brackets must be fixed on a plane base plate with uniform tightening.
If these conditions are not met, it is no longer possible to guarantee either the sealing or the general
mechanical behaviour of the pump.
Suction flange 1060
Discharge flange 1070
N
N
Nm
Sizes
FxE
F
Fy
yE
Fz
FzE
Fx
FxA
FyA
FzA
MxE
MxA
1200
2500
4000
3000
2000
4000
2000
220
75
3100
3000
4500
3500
2500
4500
2200
320
120
3600
3000
4500
3500
2500
4500
2200
320
120
4100
3500
5000
4000
3000
5000
2400
400
160
5100
4000
6000
4500
3500
6000
2600
570
210
6100
4500
7000
4500
4000
7000
3000
660
290
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.6
Page 6 of 11
Chapter 9
Appendix – CEHA pump – Identification coding
Position
1-3
4
5-8
Characteristic
Code
Type
CEH
Construction
Sizes
9-10
11
12
Hydraulic
Bearing
A
1201-6108
Definition
Self-priming,, multi-cellular, side channel pump, with low NPSH.
Self-priming
Early production stage.
Size and number of stages.
…/5
Pump for LPG.
…/7
Pump for LPG with retaining stage
A
A
First hydraulic stage.
One grooved ball bearing to DIN 625 and one liquid surrounded
sleeve bearing
1313-15
Shaf
haft sea
sealing
001
Stuffing box flushed from internal source
501
Stuffing box with intensive cooling.
AAE
Unbalanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: FN - Mat.: EBPGG.
AA1
Unbalanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: FN – Mat.: GBVGG.
AF3
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AEGG.
AF8
Balanced standard mechanical seal, flushed from internal source
AF4
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BEGG.
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1EGG.
AFU
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AVGG.
AFJ
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BVGG.
AFS
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1VGG.
AFV
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1AM1GG.
AFK
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1BM1GG.
AFT
Balanced standard mechanical seal, flushed from internal source
Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1M1GG.
AS3
Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1AEGG.
ASJ
Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1BV1GG
AST
Cooled, balanced standard mechanical seal, flushed from internal
source. Brand: SFS – Type: Sterling GNZ – Mat.:Q1Q1M1GG
BF3
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1AEGG
BFJ
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1BVGG
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
13 - 15
Shaft sealing
Page 7 of 11
BFT
Chapter 9
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: M7N – Mat.:Q1Q1TGG
BG3
Balanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: H7N – Mat.:Q1AEGG
BGJ
Balanced standard mechanical seal, flushed from internal source.
Brand: Burgmann – Type: H7N – Mat.:Q1BVGG
BGT
Balanced standard mechanical seal, flushed from internal source.
CAK
Brand: Burgmann – Type: H7N – Mat.:Q1Q1M1GG
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Crane – Type: CR59B – Mat.:BQ1TGG
CBK
Balanced standard mechanical seal, flushed from internal source.
Brand: Crane – Type: CR59B – Mat.:BQ1TGG
DAJ
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA600 – Mat.:Q1BVGG
DBJ
Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:Q1BVGG
DAK
Unbalanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA600 – Mat.:Q1BTGG
DBK
Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:Q1BTGG
DBG
Balanced standard mechanical seal, flushed from internal source.
Brand: Pacific – Type: PA610 – Mat.:SAVGG
16-17
18
Material
Casing seal
0A
Main parts in GG, impeller in brass
0B
Main parts in GG, impeller in stainless steel
0F
Main parts in GG, impeller in PAEK
1A
Main parts in GGG, impeller in brass
1B
Main parts in GGG, impeller in stainless steel
1F
Main parts in GGG, impeller in PAEK
4B
Main parts in CrNiMo-steel or cast
4F
Main parts in CrNiMo-steel or cast, impeller in PAEK
0
Liquid sealing compound
4
Soft Teflon cord.
19
20
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.7
9.7
Page 8 of 11
Chapter 9
Ap
Appe
pend
ndix
ix – CE
CEHA
HA pu
pump
mp – As
Asse
semb
mbli
ling
ng bo
bodi
dies
es
Mark (exte
(external
rnal side
side))
Groove
Suction body 1090
Discharge body 1140 / 1141
Fig.9.5
The suction bodies 1090, and discharge bodies 1140 and 1141, together with a vane impellor, form a stage.
The foundry marks I, II, III, IV, are visible on the external sides of the bodies.
bodies. Assembly is carried out by
juxtaposing the marks with the upper generating
generating line as indicated on the assem
assembly
bly drawing; for this purpose,
use the foundry groove visible
visible outside the bodie
bodies.
s. The foundry groove in body 1080 is always located
located
opposite the foundry groove in body 1090 which precedes it.
CAUTION
If the specified angular position of the stages, as defined, is not respected, pump performance will be
adversely affected.
CEHA pumps can comprise up to 8 stages in regular models.
In models with a cooling chamber or a retaining stage, the latter take the place of a hydraulic stage, so the
pump will be able to take only 6 or 7 hydraulic stages (depending on the case concerned); this fact must be
taken into account when evaluating the desired specifications.
Discharge
flange
Discharge
flange
1141
1090
1080
1141
1090
1140
1090
Discharge
flange
1080
Suction
flange
1141
1090
1140
1090
1140
1090
1080
Suction
flange
Suction
flange
1-sta e um
2-stag
2-s
tage
e pum
pump
p
3-sta e um
Fig.9.6
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
Page 9 of 11
Chapter 9
9.7.1 Appendix – CEHA pump – Assembling bodies
sc arge
flange
sc arge
flange
1141
1090
1140
1090
1140
1090
1140
1090
1141
1090
1140
1090
1140
1090
1140
1090
1080
1140
1090
1080
Suction
flange
4-stage pump
Suction
flange
5-stage pump
Fig.9.7
Discharge
flange
1141
1090
1140
1090
Discharge
flange
1140
1090
1140
1090
1141
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1080
1080
Suction
flange
6-stage pump
7-stage pump
Suction
flange
Fig.9.8
Discharge
flange
1141
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1140
1090
1080
8-sta e um
Suction
flange
Fig.9.9
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
9.8
Page 10 of 11
Chapter 9
Appendix – Technical data summary
When using CEHA pumps, the following technical data must be taken into account.
Self-priming pump
Direction of rotation: anti-clockwise facing the end of the pump drive shaft
RP: 40 bars
Max. admissible P*: 40 bars at 120°C / 32 bars at 180°C
Test Pressure: 52 bars (1.3 times the rated
r ated pressure)
Max. admissible viscosity*: 300 mm²/s
Max. n*: 1800 rpm
*These limits are not valid for
for all products or all types of construction.
construction. For use in conformity
conformity and complete
safety, take into account the existing requirements
requirements (standards) concerning the type of sealing and cooling.
Number of stages: 1 to 8 stages maximum (if a retaining stage is used, it takes the place of a hydraulic
stage).
Connecting flanges: as per DIN 2501, PN 40, (positions and dimensions: see dimension drawing).
Bearings: plain bearing at the pump end, ball bearing at the drive end
Bearing
Sizes
according to
DIN 625
1200
6302
3100
6304
3600
6304
4100
6305
5100
6306
6100
6307
Lubrication: 1 plain bearing at the pump end lubricated by the pumped product, 1 ball bearing at the drive
end lubricated for life.
Weight of the pump:
Approximate weight in kg
Sizes
1-stage pump weight
Cast iron
Stainless steel
Add per additional stage
Cast iron
Stainless steel
1200
18
19
2.0
2.2
3100
31
33
3.5
4.0
3600
31
33
3.5
4.0
4100
41
43
6.0
6.5
5100
60
63
10.0
10.0
11.0
6100
79
83
12.5
12.5
13.5
Minimum / maximum output:
Refer to Chapter 2
Temperature limits
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
Annexes
Page 11 of 11
Minimum temperature
temperatur e of pumped liquid =
- 40 °C *
Maximum temperature
temperatur e of pumped liquid =
120 °C *
Chapter 9
180°C for high temperature execution *
**These limits are not valid for all products
products or all types of construction. For use in conformity
conformity and complete
safety, take into account the existing requirements
requirements (standards) concerning the type of sealing and cooling.
Maximum permissible temperature of pumping liquid
The highest temperatures usually occur on the pump casing surface, on the bearing housing in the area of
the anti-friction bearings and on the casing cover near the mechanical seal. A dry running must be prevent.
The temperature occurring on the pump casing is almost the same as that of the liquid handled
A maximum temperature
temperature of 80°C,
80°C, if grease lubricated,
lubricated, can be expe
expected
cted in the area of the anti-friction
bearings, provided the requirements for appropriate pump operation are met and regular
maintenance on the bearings is provided. Insulation of the bearing housing is not permissible.
If the pump is adequately
adequately filled with liquid, the temperature of the liquid handled in the shaft seal area
should not increase by more than 15°C for dead end operation with a single acting mechanical seal.
Thus, the following theoretical maximum temperature of the liquid handled as a function of the temperature
class according to EN 13463-1 is obtained. The maximum operating temperature
temperature of the pump as well as the
operating limits of the mechanical seal must be observed (if there is any doubt, please contact Sterling SIHI
or the mechanical seal manufacturer).
Temperature class
Max. temperature of
acc. EN 13463-1
pumping liquid
T5
85 °C
T4
120 °C
T3
185 °C
T2
285 °C
T1
350 °C
Doc.No.: CEH09AE
Rev.: 01
Date: 02/04/2003
Information subject to technical
alterations due to engineering development
Sterling Fluid Systems (France)
Member of Group
Sterling Fluid Systems
S.A. Sterling Fluid Systems France)
Zone Industrielle de Trappes-Elancourt
1-3, Avenue Georges Politzer B.P.41 - 78193 Trappes Cedex, France
Téléphone: +33 (0)1 34 82 39 00 Télécopie: +33 (0)1 34 82 39 61
Declaration of Conformity
for bare shaft pump
In the sense of the EU Directive 98/37/EC, Appendix II B
Herewith we declare that the pump type:
CEH
In the version supplied by us complies with the following relevant regulations:
EU Machine Directive 98/37/EC, Appendix I No. 1
EU Directive 94/9/EC, Group II, category 2
And that is destined for installation in a machine / assembly with other machines to fform
orm
a single machine and that it may not be commissioned until it has been determined that
the machine in which this pump is to be installed or with which this pump is to be
assembled complies with the clauses of the EU Machine Directive in the version of
98/37/EC and 94/9/EC.
Harmonised standards used, in particular:
EN 809
EN 292 part 1
EN 292 part 2
EN 13463 - 1
prEN 13463 - 5
In the actual version.
National technical standards and specifications used, in particular:
Unauthorised alterations of the pump unit and any use not in accordance with valid
regulations and / or intended use result in a loss of validity of this declaration.
Notification of Pump:
Operation Manager
II 2 G c T1-T5
Business Unit Manager
Dr R. EHL
O. LOESER
Membres du groupe Sterling Fluid S
Systems
ystems
Descargar