Product Description Full Voltage Starting Electric Fire Pump Controllers Description—Firetrol® FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps where the capacity of the power source permits full voltage starting. Full voltage is applied to the motor as soon as the controller is actuated. The controller monitors, displays and records fire pump system information. Full voltage starting is simple and low cost and is preferred whenever the utility or emergency generator set will permit this type of starting. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage n Fire pump Circuit Breaker n Motor contactor n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition • FTA1000 n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time Option n Weekly Test Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible Low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button and solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1250-20(B) Product Description Part Winding Starting Electric Fire Pump Controllers Description—Firetrol® FTA1250 Part Winding Starting Fire Pump Controllers can be used where the characteristics of the power source do not permit full voltage starting. The controller monitors, displays and records fire pump system information. When the controller is actuated by the pressure switch, START pushbutton, deluge valve contact, etc., the first contactor closes, connecting one of the motor windings to the line. During starting, the motor will draw approximately 65% of its normal locked rotor current and develop approximately 42% of its normal starting torque. After a time delay, the second contactor closes, connecting the second winding in parallel with the first. The motor then draws its normal running current and develops its rated torque. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage • FTA1250 n Fire pump Circuit Breaker n Motor contactor n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible Low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button and solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1250-20(B) Product Description Wye-Delta Open Transition Starting Electric Fire Pump Controllers Description—Firetrol® FTA1300 Wye-Delta, Open Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1300 controllers are of the open circuit transition type in which the motor circuit is opened during the transition from start to run. The controller monitors, displays and records fire pump system information. Actuating the controller by the pressure switch, START pushbutton or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. These controllers are recommended especially for use with generator sets. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage n Fire pump Circuit Breaker n Motor contactor • FTA1300 n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1300-20(B) Product Description Wye-Delta Closed Transition Starting Electric Fire Pump Controllers Description—Firetrol® FTA1350 Wye-Delta, Closed Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1350 controllers are of the closed circuit transition type in which the motor circuit remains closed during the transition from start to run. The controller monitors, displays and records fire pump system information. Actuating the controller by the pressure switch, START pushbutton or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. During this transition, a resistor is connected to each phase, minimizing line disturbances and voltage drop during starting. These controllers are recommended especially for use with generator sets. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage • FTA1350 n Fire pump Circuit Breaker n Motor contactor n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1350-20(B) Product Description Primary Resistance Starting Electric Fire Pump Controllers Description—Firetrol® FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage when starting the pump motor. The controller monitors, displays and records fire pump system information. The circuit to the motor is not opened during the transition from start to run. While starting, the motor will draw 50% of full load starting current and supply 25% of rated torque. This method of starting minimizes line disturbances and voltage drop when starting. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage n Fire pump Circuit Breaker n Motor contactor n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits • FTA1500 n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n Transition Contactor and Power Resistors n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1500-20(C) Product Description Autotransformer Starting Electric Fire Pump Controllers Description—Firetrol® FTA1800 Autotransformer Starting Fire Pump Controllers use an autotransformer to supply reduced voltage when starting the motor. The controller is of the closed circuit type where the motor circuit remains closed during the transition from start to run resulting in minimum line disturbance. The controller monitors, displays and records fire pump system information. The autotransformer has three taps for selection of starting current and torque; 50% tap for 150% current and 25% torque, 65% tap (factory setting) for 250% current and 42% torque and the 80% tap for 384% current and 64% torque. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage n Fire pump Circuit Breaker n Motor contactor • FTA1800 n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n Transition Contactor and Autotransformer n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1800-20(C) Product Description Solid State Starting Electric Fire Pump Controllers Description—Firetrol® FTA1900 Solid State Starting Fire Pump Controllers feature soft start, soft stop and system sensing capabilities that not only provide for reduced voltage starting, but also offer an improved level of hydromechanical performance. The controller monitors, displays and records fire pump system information. When called to run, the motor will accelerate along a ramp beginning at 40% of normal starting current with 15% of full voltage torque. When stopping, the motor will ramp down to a preset level and allow for a restart, limiting stress in the piping system. If no additional starting causes are present, the motor will continue to ramp down to a full stop. This controller helps to reduce water hammer in the system. Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage n Fire pump Circuit Breaker n Motor contactor • FTA1900 n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n Firetrol SS/3 Solid State SCR Starter n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Soft Start Bypass Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Soft Starter Overtemp message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) -AZ CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible low suction pressure alarm with manual reset push-button -CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EG Visible Relief Valve Discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Test push-button with solenoid valve* -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 *Weekly Test Timer Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1900-20(B) Product Description Power Transfer Switches for Electric Fire Pump Controllers Description—Firetrol® Power Transfer Switches are available completely assembled with Firetrol Electric Fire Pump Controllers; full or reduced voltage types. The power transfer switches are built in two versions: FTA900 — For use when the normal power source is a utility and the emergency power source is a generator set. FTA950 — For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals—Firetrol power transfer switches are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment, CSA, Standard for Industrial Control Equipment; and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each transfer switch: n Emergency power source disconnect switch sized for connected motor horsepower and voltage n (FTA950 only) Fire pump circuit breaker • FTA900 FTA950 n (FTA950 only) Mark II monitors for overcurrent tripping (non-thermal) of circuit breaker and alarm indicator for phase failure/phase reversal n 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held n Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails n Transfer Switch Normal LED n Transfer Switch Emergency LED n Emergency Isolating Switch Open LED n Test Selector Switch n Transfer By-pass Switch n Silence Alarm Pushbutton n Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms n Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators n Standard Withstand Rating, emergency side only FTA900 (Generator set equipped with molded case circuit breaker) 100-150A, 22,000A RMS Sym., 200-480V; 10,000A RMS Sym., 550-600V 260-400A, 35,000A RMS Sym ., 200-480 V; 10,000A RMS Sym., 550-600 V 600-800A, 50,000A RMS Sym., 200-480V; 10,000A RMS Sym., 550-600V FTA950—See Options n NEMA Type 2 enclosure (IEC IP11) Note: The withstand rating of the normal power source side of the transfer switch will be the same as the withstand rating of the fire pump controller assembled with the power transfer switch. Options—The following are available as options to FTA950 Power Transfer Switches: Circuit Breaker Option -M Standard withstand rating 200-600V - 100,000 Amps, RMS Sym. -N Intermediate withstand rating 200-600V - 150,000 Amps, RMS Sym. -P High withstand rating 200-600V - 200,000 Amps, RMS Sym. -Q Standard intermediate withstand rating 200-480V - 65,000 Amps RMS Sym. -R Standard low withstand rating 550-600V - 42,000 Amps RMS Sym. Modifications—The following are available as modifications to all transfer switches: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP 56) -G NEMA Type 12 (IEC IP52) Special finish paint—consult factory Special finish color—consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Alarms -EC Extra contacts for remote indication, transfer switch position -BX Contacts for remote indication, second utility source phase failure/phase reversal (FTA950 only) Miscellaneous -ED Load shed circuits -TM Microprocessor type (Group 5) control module -TN As above, with serial communications port -S Tropicalization (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD900-20(A) Product Description Limited Service Controllers Description—Firetrol® FTA750 Limited Service Controllers may be used for the automatic control of small electrically driven fire pumps and booster pumps where they are acceptable to the authority having jurisdiction. Approvals—Firetrol limited service controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Voltage surge protector n Main thermal-magnetic circuit breaker for assigned motor horsepower and voltage n Firetrol FTA436 Phase Failure/Phase Reversal Monitor n Motor contactor • FTA750 n Power Available Pilot Light - indicates 3-phase power available and control power normal n Phase Reversal Pilot Light - illuminates when phases are reversed n Control transformer with 120 volt AC - secondary unfused for controller operating logic circuits, with fuse for possible external auxiliary devices n Circuitry for start by remote deluge valve or other fire protection equipment (requires normally closed, open to start remote contacts) n Remote interlock circuit (requires remote normally open contact which closes to operate) n Built-in Start and Stop pushbuttons to bypass automatic start circuits n Minimum Run Timer for automatic stop n Pressure switch, integrally mounted on a threaded bulkhead fitting with external 1/2 inch connection n Field connection remote alarm terminals (normally open-close to alarm and normally closed-open to alarm) for each of the following: Pump Operating, Pump Power Failure, Phase Reversal n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition—operation of emergency run mechanism results in a full voltage start of the motor n NEMA Type 2 enclosure (IEC IP11) Options—The following are available as options to the controllers: Timer Option -A With running period timer (auto/manual start with auto/manual shutdown, selectable) -B Without running period timer (auto/manual start with manual shutdown only) Circuit Breaker Option -A Standard withstand rating 2-20 HP, 200-240V - 10,000 Amps, RMS Sym. 25-30 HP, 200-240V - 18,000 Amps, RMS Sym. 3-30 HP, 380-600V - 14,000 Amps, RMS Sym. -B Intermediate withstand rating 200-480V - 65,000 Amps, RMS Sym. 550-600V - 18,000 Amps, RMS Sym. NOTE: Standard controllers contain MERCURY filled pressure switches which are readily and visibly labeled “Contains Mercury - do not put in trash. Recycle or dispose as hazardous waste. Keep cover in place.” To avoid the use of Mercury, contact Firetrol or your local representative for alternative devices. Modifications—The following are available as modifications to the controllers: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish—consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Pressure Switches and Recorders -B 0-600 psi (0-42.3 kg/cm2) pressure switch for fresh water service -C 0-300 psi (0-21.1 kg/cm2) pressure switch for sea water/foam service -D 0-600 psi (0-42.3 kg/cm2) pressure switch for sea water/foam service Automatic Power Transfer Switches (Refer to Publication PD975-01) FTA975 - generator set emergency supply FTA976 - second utility emergency supply Alarms -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AM Contacts for remote indication, pump fail to start -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -P Built-in alarm system (includes visible supervisory voltage normal indication and audible phase failure, phase reversal and pump run indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure Miscellaneous -A Sequential start -R Pump operating pilot light -S Tropicalization (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD750-20(A) Product Description Power Transfer Switches for Limited Service Controllers Description—Firetrol® Power Transfer Switches are available completely assembled with Firetrol Limited Service Controllers. The power transfer switches are built in two versions: FTA975 — For use when the normal power source is a utility and the emergency power source is a generator set. FTA976 — For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals—Firetrol power transfer switches are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment, CSA, Standard for Industrial Control Equipment; and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. FTA975 • FTA976 Standard Features—The following are included as standard with each transfer switch: n Emergency power source disconnect switch sized for connected motor horsepower and voltage n (FTA975 only) molded case isolating switch n (FTA976 only) thermal-magnetic circuit breaker n 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held n Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails n Transfer Switch Normal Pilot Light n Transfer Switch Emergency Pilot Light n Emergency Isolating Switch Open Pilot Light n Test Selector Switch n Transfer By-pass Switch n Silence Alarm Pushbutton n Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms n Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators n Standard Withstand Rating, emergency side only FTA975 (Generator set equipped with molded case circuit breaker) 3-30HP, 200-600V, 10,000 Amps, RMS Sym. FTA976 3-20HP, 200-240V, 10,000 Amps, RMS Sym. 25-30HP, 200-240V, 18,000 Amps, RMS Sym. 3-30HP, 380-600V, 14,000 Amps, RMS Sym. n NEMA Type 2 (IEC IP11) enclosure Note: The withstand rating of the normal power source side of the transfer switch will be the same as the withstand rating of the fire pump controller assembled with the power transfer switch. Options—The following are available as options to FTA976 Power Transfer Switches: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (#304 Stainless Steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish - Consult Factory Circuit Breaker Option -B Intermediate withstand rating 200-480V - 65,000 Amps, RMS Sym. 550-600V - 18,000 Amps, RMS Sym. Modifications—The following are available as modifications to all transfer switches: Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Explanation of Catalog Number FTA975-BL100B-ED Type 975 Gen Set 976 Second Utility Start Option -B Automatic Withstand rating -A Standard (FTA976) -B Intermediate (FTA976) -D Standard (FTA975) Modifications Voltage -H 200-208 -A 220-240 -F 380-415 -B 440-480 -C 550-600 Ampere rating 100 Example—FTA975-BD100B-ED FTA975 Power Transfer Switch for generator set emergency power source, 100 Amp, 440-480 Volts, with load shed circuits. Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Alarms -BX Contacts for remote indication, second utility source phase failure/phase reversal (FTA976 only) Miscellaneous -ED Load shed circuits -TM Microprocessor type (Group 5) control module -TN As above, with serial communications port -S Tropicalization (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD975-01(E) Product Description High Voltage Fire Pump Controllers 2300-7200 Volt Description—Firetrol® FTA2000 combined automatic and manual class E2 high voltage controllers are intended for starting of squirrel cage motors driving listed fire pumps. Maximum ratings are as follows: Max. HP 1500 2000 2500 3500 3-Phase Voltage 2200 - 2500 3200 - 3500 4000 - 5000 5000 - 7200 Approvals—Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n Isolating Switch - NEMA Rating, 7200 Volts, 400 Amps with external operating handle with electrical and mechanical interlocks to prevent opening of the high voltage compartment door with the isolating switch or the main contactor closed. Interlocks prevent opening the isolating switch with the main contactor closed. n Vacuum Contactor - NEMA Rating, 7200 Volts, 400 Amps • FTA2000 n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Normal-Off-Test Selector Switch - Internally mounted for functional test of control system only, requires that isolating switch be open and a separate 120 volt AC power source be supplied. n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n Minimum Run Timer / Off Delay Timer n Daylight Savings Time Option n Weekly Test Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) -G NEMA Type 12 (IEC IP52) ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AG Built-in reservoir low alarm -AM Contacts for remote indication, pump fail to start -AW Contacts for remote indication, reservoir low -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -EG Visible Relief Valve Discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK -P -PB -PT -HV -HW -LVA -LW -LY Contacts for remote indication, flow meter on Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) Built-in low system pressure visible alarm with manual reset Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) Audible alarm device Audible and visible pump fail to start alarm (Requires modification -HV) Visible pump on demand alarm Audible and visible pump on demand alarm (requires (-HV)) Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -BAT 220-240 Volt test circuit -EP SIS Wire, sleeve wire markers and ring tongue terminals -GZ 50 Hertz operation -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging *Weekly Test Timer - Standard (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD2000-20(A) Product Description Diesel Engine Fire Pump Controller Description – Firetrol® combined automatic and manual Mark II based diesel engine fire pump controllers are intended for starting and monitoring fire pump diesel engines. They are available for use with 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries. The controller monitors, displays and records fire pump system information. Approvals – Firetrol fire pump controllers are listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cUL), and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard Features – The following are included as standard with each controller: n Two pole AC line circuit breaker n Manual-Off-Auto selector switch n Manual test push-button • FTA1100 n Two manual crank push-buttons n Two 10 Amp battery chargers with 4 stage charging cycle, selectable AC voltage (110 / 220), selectable DC voltage (12 / 24), and selectable battery type (Lead Acid, Ni-Cad 9/18 Cell, NiCad 10/20 Cell) n Door mounted display/interface panel featuring a 80 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n MAIN SWITCH IN AUTO LED n ENGINE FAIL TO START LED n CHARGER MALFUNCTION LED n BATTERY #1 TROUBLE LED n BATTERY #2 TROUBLE LED n SYSTEM PRESSURE LOW LED n ENGINE RUNNING LED n ENGINE COOLANT TEMP HIGH LED n ENGINE OIL PRESSURE LOW LED n ENGINE OVERSPEED LED n LOW FUEL LEVEL LED n Minimum Run Timer / Off Delay Timer n Daylight Savings Time Option n Weekly Test Timer n Engine Run Time Meter n Digital Pressure Display n 3.5” 1.44M Floppy Disk Drive (20,000 events) n Data Log n Event Log (3000 events) n Simultaneous Display of Battery Voltages and Charging Rates n Disk Error Message n Disk Near Full Message n Pressure Error Message n Fail to Start Message n Low Suction Pressure Message n Crank Cycle Status Indication (Displays Cranking Battery, Number of Starting Attempts and Crank/Rest Time Remaining) n 300 psi (20.7 bars) wet parts (pressure transducer, solenoid valve, plumbing) for fresh water applications n High Speed Open Serial Communications Port n NEMA Type 2 enclosure Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP 56) -F NEMA Type 4X (IEC IP56) #304 Stainless Steel -G NEMA Type 12 (IEC IP52) Mounting Legs -N31 Standard 12” Mounting Legs -N32 Base Mounting Legs 6” Anti-Condensation Space Heaters -H 120 Volt Space Heater -J 120 Volt Space Heater with Thermostat -K 120 Volt Space Heater with Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater with Thermostat -N 240 Volt Space Heater with Humidistat Pressure Transducers, Solenoid Valves, Plumbing -B 0-600 psi (0-41.4 bars) wet parts for fresh water applications -C 0-300 psi (0-21.1 bars) wet parts for sea water/foam or copper corrosive applications -D 0-600 psi (0-41.4 bars) wet parts for sea water/foam or copper corrosive applications Alarms -AC Additional contacts for remote indication, engine running - 2 sets provided as standard -AJ Contacts for remote indication, engine overspeed -AK Contacts for remote indication, low oil pressure -AL Contacts for remote indication, high water temperature -AM Contacts for remote indication, engine failed to start -AN Contacts for remote indication, battery / charger failure -AP Contacts for remote indication, main switch in manual -AR Contacts for remote indication, main switch in off -AS Contacts for remote indication, main switch in auto -AT Contacts for remote indication, pump room trouble (common alarm)1 -AV Contacts for remote indication, low pump room temperature1 -AW Contacts for remote indication, reservoir low1 -AY Contacts for remote indication, low suction pressure1 -COM Visible low suction pressure alarm with manual reset push-button1 -CTS Built-in low suction pressure alarm panel (Includes selectable auto/ manual reset, audible, visible and remote alarms and mounted and wired pressure switch) -EE Additional contacts for remote indication, engine trouble (common alarm) 1 set provided as standard -EF Additional contacts for remote indication, main switch mis-set (common alarm) - 1 set provided as standard -EH Contacts for remote indication, relief valve discharge1 -EJ Visible flow meter on alarm1 -EK Contacts for remote indication, flow meter on1 -LC Contacts for remote indication, high fuel level1 -LD Visible fuel spill alarm1 -LE Contacts for remote indication, fuel spill1 -LG Contacts for remote indication, reservoir high1 -PE Contacts for remote indication, low system pressure Miscellaneous -AZ Low pump room temperature switch, mounted and wired -BA 220-240 Volt operation -EL Series pumping, high zone controller -EM Series pumping, mid zone controller -EN Series pumping, low zone controller -S Tropicalization -ZPA Customized, annual service display message (factory programmed) -ZPB High quality impact printer with automatic paper take-up mechanism FTA1100-K1 Low fuel level switch2 FTA1100-K21 380-480 volt operation (transformer)2 Export packaging 1 2 - Initiating switches by others - Shipped loose for installation by the customer (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD1100-20(A) Product Description Alarm Panels Electric Fire Pump Controllers • FTA200-A FTA200-B Type B - Type B panels provide the same alarm indication as the Type A except that SUPERVISORY POWER FAILURE does not have the audible alarm feature. Only a visible alarm indication is provided. Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL), approved by the New York City Bureau of Electrical Control and Board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features—The following are included as standard with each controller: Type A - Type A panels provide audible and visible alarm indication for the following conditions: n Supervisory Voltage Normal n Pump Operating n Pump Phase Failure n Pump Phase Reversal Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Electric Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms. Standard Remote Alarms -AM Pump Fail To Start -BY Pump Overload -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Dimensions and Shipping Weight Explanation of Catalog Number FTA200-A-Y Approx. Shipping Weight 18 lbs (8kg) Alarm Panel Type Modification Code(s) Example - FTA200-A-Y Type A Alarm Panel with Nema Type 1, Flush Mount Enclosure. Information Required With Orders n Catalog number of alarm panel n Catalog number of controller to be used with alarm panel n Modifications if any (give complete description) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-01(B) Product Description Alarm Panels Diesel Engine Fire Pump Controllers • FTA200-F FTA200-G Type G - Type G panels provide alarm indication for the following conditions: n Supervisory Voltage Normal (Visible Only) n Engine Trouble (Audible and Visible n Engine Running (Audible and Visible) n Main Switch Mis-Set (Audible and Visible) n Pump Room Trouble (Audible and Visible) Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 specifications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is under supervision at all times. Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL), approved by the New York City Bureau of Electrical Control and board of Standards and Appeals and Factory Mutual. They are designed to meet or exceed the requirements of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps. Standard Features—The following are included as standard with each controller: Type F - Type F panels provide alarm indication for the following conditions: n Supervisory Voltage Normal (Visible Only) n Engine Trouble (Audible and Visible) n Engine Running (Audible and Visible) n Main Switch Mis-Set (Audible and Visible) Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication, the SILENCE ALARM pushbutton and the PUSH-TO-TEST pushbutton. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM pushbutton has been pressed. Pressing the SILENCE ALARM pushbutton will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM pushbutton or until the abnormal condition has been corrected. The PUSH-TO-TEST pushbutton is supplied for manually testing the pilot lights, audible alarm and output circuits. Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) -Y NEMA Type 1 (IEC IP10) Flush Mount, Painted Steel Consult Factory for other style enclosures. Additional Alarm Functions Each Additional alarm function ordered will include a control relay and pilot light and will provide audible and visible alarm. There is no limit as to the number of additional alarm functions that can be supplied, however, enclosure size and weight may be affected. Consult the Factory for dimensions and shipping weights when ordering more than 2 additional alarms. Standard remote alarms may be ordered by using the Suffix Letters indicated for the corresponding alarm function on the Diesel Engine Fire Pump Controller. Alarm functions must exist in the controller to be ordered as remote alarms. Standard Remote Alarms -AU Low Fuel Level -AV Low Pump Room Temperature -AW Reservoir Low -AY Low Suction Pressure -AJ Engine Overspeed -AK Low Oil Pressure -AL High Water Temperature -AM Engine Failed To Start -AN Battery/Charger Failure -AP Main Switch In Manual -AR Main Switch In Off -AS Main Switch In Auto -LC High Fuel Level -LE Fuel Spill -EG Relief Valve Discharge -EJ Flow Meter On Non-Standard Remote Alarms -BT When ordering, specify the number of alarms required, the function of each and the nameplate marking of each. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on 220-240 Volts -BA Panel is supplied as standard for operation on 110-120 volts. Dimensions and Shipping Weight Approx. Shipping Weight 18 lbs. (8kg) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Explanation of Catalog Number FTA200-G-AU-LE Alarm Panel Type Modification Code(s) Example - FTA200-G-AU-LE Type G Alarm Panel with remote alarms for Low Fuel Level and Fuel Spill. Information Required With Orders n Catalog number of alarm panel n Catalog number of controller to be used with alarm panel n Modifications if any (give complete description) (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-02(B) Product Description Low Suction Pressure Shutdown Alarm Panels Fire Pump Controllers • FTA200-D FTA200-E Mounted on the enclosure door are the pilot lights for visible alarm indication, the audible device for audible alarm indication and the SILENCE ALARM push-button. Each pilot light will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal condition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the pilot light. If another alarm condition occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condition has been corrected. A pressure switch for monitoring the suction pressure is mounted on the side of the enclosure. Description—Firetrol® FTA200 low suction pressure alarm and shutdown panels are designed to be used with electric and diesel engine driven fire pump controllers. They are intended for use where a local authority mandates pump shutdown in the event of low suction pressure. Approvals—These alarm panels have been approved by Factory Mutual. Standard Features—The following are included as standard with each controller: Type D - Type D panels provide audible and visible alarm indication for the following conditions: n Supervisory Voltage Normal n Pump Controller Voltage Failure n Low Suction Pressure (Automatic Reset) Type E - Type E panels provide the same alarm indication as the Type D except that LOW SUCTION PRESSURE shutdown and alarm must be manually RESET when suction pressure is restored. Construction - FTA200 alarm panels make use of printed circuit boards which provide reliable and trouble free service. The enclosures are NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The standard enclosure color is red. APPROVED Modifications—The following are available as modifications to the controllers: Special Enclosures -F NEMA Type 4X, 304 stainless (IEC IP56) Consult Factory for other style enclosures. Substitute Amber for Red Pilot Lights -LA To meet local code requirements. Operation on 220-240 Volts -BA Panel is supplied as standard for operation on 110-120 volts. 50 HZ Operation -GZ Controller is supplied to operate on 50 HZ incoming power. Dimensions and Shipping Weight Explanation of Catalog Number FTA200-D-GZ Alarm Panel Type Modification Code(s) Example - FTA200-D-GZ Type D Alarm Panel with modification to operate on 50 HZ incoming power. Information Required With Orders n Catalog number of shutdown panel n Catalog number of controller to be used with shutdown panel n Modifications if any (give complete description) WARNING- Because NFPA 20 specifically prohibits the installation of any device in the suction piping which will restrict starting or stopping of the fire pump (See NFPA 20, Paragraph 2-9.9), Firetrol assumes no liability when Type D or E Shutdown Panels are used in connection with fire pump control equipment. Approx. Shipping Weight 20 lbs (9 kg) Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD200-03(C) Product Description Jockey Pump Controllers • FTA500 Circuit Breaker Option -A Standard withstand capacity 200-240V - 10,000 Amps, RMS Sym. 380-480V - 14,000 Amps, RMS Sym. 550-600V - 14,000 Amps, RMS Sym. NOTE—Consult factory for high interrupting capacity circuit breakers. Omit Minimum Run Timer -B Controller without minimum run timer Floor Mounting Legs FTA -N2 Specify when ordering Modifications—The following are available as modifications to the controllers: Description—Firetrol® FTA500 Jockey Pump Controllers are intended for use with fire pump systems. They are used for pressure maintenance in fire pump installations to prevent unnecessary cycling of the main fire pump. Approvals—Firetrol jockey pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, and CSA, Standard for Industrial Control Equipment. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest edition NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: n NEMA Type 2 drip-proof enclosure n Horsepower rated fusible disconnect switch with fuseblock and fuses n Horsepower rated motor contactor and overload relay n HAND-OFF-AUTO selector switch n Minimum run timer n 30-300 psi (2.1-20.7 bars) Pressure switch, diaphragm style, snap action type contact and 1040 psi (.7-2.8 bars) adjustable differential, suitable for fresh water applications with 0-300 psi (0-20.7 bars) pressure gauge Options—The following are available as options to the controllers: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish—consult factory Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Pressure Switches and Recorders -ZNY 0-300 psi (0-20.7 bars) pressure switch for fresh water service (Bourdon tube style, Mercury switch type) -B 0-600 psi (0-41.4 bars) pressure switch for fresh water service (Bourdon tube style, Mercury switch type) -C 0-300 psi (0-20.7 bars) pressure switch for sea water/foam service (Bourdon tube style, Mercury switch type) -D 0-600 psi (0-41.4 bars) pressure switch for sea water/foam service (Bourdon tube style, Mercury switch type) -SL 0-300 psi (0-20.7 bars) pressure recorder for fresh water service -SM 0-500 psi (0-34.5 bars) pressure recorder for fresh water service -SN 0-1,000 psi (0-69 bars) pressure recorder for fresh water service -SP 0-300 psi (0-20.7 bars) pressure recorder for sea water/foam service NOTE: Standard Jockey Pump controllers DO NOT CONTAIN MERCURY filled pressure switches. Controllers with optional pressure switches listed above do contain mercury filled switches which are readily and visibly labeled “Contains Mercury - do not put in trash. Recycle or dispose as hazardous waste. Keep cover in place.” -SR 0-500 psi (0-34.5 bars) pressure recorder for sea water/foam service -SS 0-1,000 psi (0-69 bars) pressure recorder for sea water/foam service Alarms -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AM Contacts for remote indication, pump fail to start -BY Contacts for remote indication, pump overload -BW Contacts for remote indication, pump power failure -BX Contacts for remote indication, phase reversal/phase failure Miscellaneous -BJ Power ON pilot light -BZ Elapsed time meter -S Tropicalization -BN Control circuit transformer -R Pump operating pilot light -GZ 50 Hertz operation Dimensions and Shipping Weight Explanation of Catalog Number FTA500-AF05B-B Timer Option -A With running period timer -B Without timer Disconnect -F With Fuseblock and Fuses -A Circuit Breaker Modifications Voltage (3 phase)* -H 200-208 -A 220-240 -F 380-415 -B 440-480 -C 550-600 Horsepower 1/4-50 * For single phase applications (2 HP Max.) use the following voltage codes: -D 110-120 -T 200-208 -E 220-240 -U 380-415 -G 440-480 -S 550-600 Example—FTA500-AF05B-BN FTA500 jockey pump controller, 5 HP, 440-480 Volts, with modification (-BN) control circuit transformer Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA PD500-01(I) Specifications Electric Fire Pump Controllers Main Fire Pump Controller The main fire pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (cULus), approved by Factory Mutual and approved by the City of New York for fire pump service. Starting Method The controller shall be of the combined manual and automatic type designed for: Full Voltage Starting Solid State Soft Starting Wye (Star)-Delta Open Transition Starting Wye (Star)-Delta Closed Transition Starting Part Winding Starting Primary Resistance Reduced Voltage Starting Autotransformer Reduced Voltage Starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall mounted enclosure. Withstand Ratings (Short Circuit Current Ratings) All controller components shall be front mounted, wired and front accessible for maintenance. The minimum withstand rating of the controllers shall not be less than 100,000 Amps RMS Symmetrical at 200600 Volts*. If the available system fault current exceeds these ratings, the controllers shall be supplied with a withstand rating of 150,000 or 200,000 Amps RMS Symmetrical, as required. *Note: 100,000 Amp withstand rating not available in some larger horsepowers. Consult factory for details. Isolation Switch and Circuit Breaker The controller shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch ON first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker OFF first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON • FTA1000 -1900 position without affecting the tripping characteristics of the circuit breaker. The controller door shall have a locking type handle and three point cam and roller vault type hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the full load amps of the connected motor. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. Operator Interface The fire pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 2line, 20-character, vacuum fluorescent, dot matrix type designed to allow easy viewing from all angles and in all light conditions. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The display shall be capable of being programmed for any language. Ammeter/Voltmeter The fire pump controller operator interface shall be capable of displaying true RMS digital motor voltage and current measurements for all three phases simultaneously. Displays requiring pushbutton and selector switches to toggle between phases or current and voltage shall not be accepted. Voltage and current shall be measured by True RMS technology to provide the most accurate measurement for all sine waves, including nonsinusoidal waveforms. Average responding meters will not be accepted. Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of: • Motor On • Sequential Start Time • Minimum Run Time • Local Start / Off Delay Time • Remote Start • Fail to Start • System Battery Low • Under Voltage • Over Voltage • Locked Rotor Trip • Low Suction Pressure • Over Frequency • Emergency Start • Motor Over 320% • Drive Not Installed • Motor Overload • Disk Error • Printer Error • Disk Near Full • Pressure Error The Sequential Start Timer and Minimum Run Timer/ Off Delay Timer shall be displayed as numeric values reflecting the value of the remaining time. LED Visual Indicators LED indicators, visible with the door closed, shall indicate: • Power On • Emerg. Isolating Switch Open • Pump Running • Low System Pressure • Alarm • Transfer Switch Normal • Deluge Open • Transfer Switch Emergency • Phase Failure • Phase Reversal • Interlock On In addition to the standard alarm contacts required by NFPA 20, the digital display module shall have N.O. and N.C. contacts for remote indications of any digitally displayed alarm and N.O. and N.C. contacts for remote indication up to EIGHT, specified, programmable alarm. Data Logging The digital display shall monitor the system and log the following data: • Motor Calls/Starts • Elapsed Motor Run Time • Last Trip Currents • Elapsed Power On Time • Last Breaker Trip • Maximum Run Currents • Minimum Voltages • Minimum Run Currents • Maximum Voltages • Last Motor Run Time • Last Phase Failure • Last Start Currents • Last Phase Reversal • Min/Max Frequency • Min/Max Pressure Event Recording Printer - The controller shall be equipped with a dot matrix, impact printer to record all operational and alarm events. The printer shall use standard 16# bond paper, commercially available at office supply stores. Thermal or electrostatic printers are not acceptable. The printer shall feature a mechanical take-up mechanism to prevent excessive paper buildup in the bottom of the controller during automatic operation. The printer shall automatically record all events and pressure settings. It shall allow the user to select the pressure recording frequency based upon either time or pressure deviation. If set for time based recording, the printer shall record the pressure every 30 minutes during standby and every 15 seconds during operation. Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. Floppy Disk Drive - The controller shall include a floppy disk drive to save all operational and alarm events. The floppy disk drive shall have the ability to store up to 1 year’s worth of data (under normal operating conditions) in individual monthly files. Each event shall be time and date stamped. The controller shall also have the capability to save settings and values to disk through the user interface. Communications - The controller shall feature two independent communications ports to allow connectivity to computers, modems, or building management systems. Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fire pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be field programmable for manual stop automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. The controller shall be fully programmable to allow up to 8 custom alarm messages to be displayed on the user interface. A nonadjustable restart delay timer shall be provided to allow the residual voltage of the motor to decay prior to restarting the motor. At least 2 seconds, but no more than 3 seconds, shall elapse between stopping and restarting the pump motor. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance message for a service inspection. The message text and frequency of occurrence shall be programmable through the user interface. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. The controller shall not start the fire pump motor under a single-phase condition. If the motor is already running when a phase loss occurs, the controller shall continue to run the motor, but still display a Phase Failure alarm. The controller shall be manufactured by Firetrol. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP1000-20(A) Specifications Fire Pump Controller Power Transfer Switches Main Fire Pump Controller with Transfer Switch The main fire pump controller shall be factory assembled and wired with a power transfer switch listed by Underwriters’ Laboratories, Inc. for transfer switch and fire pump service. The power transfer switch shall be approved by Factory Mutual. The power transfer switch and fire pump controller shall be factory assembled, wired and tested as a single unit and shall conform to all requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. Power Transfer Switch for Generator Set Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated disconnect/isolating switch capable of interrupting the motor locked rotor current. The disconnect/isolating switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect/isolating switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety, and shall also be capable of being locked in the ON position. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. A auxiliary contract shall be provided on the transfer switch to prevent starting of the emergency generator set when the transfer switch or the main fire pump controller are being serviced. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer and engine start signals so as to compensate for • FTA900 950 momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the generator set or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF LED’s, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. The power transfer switch shall be furnished with both normally open and normally closed auxiliary contacts for an engine start signal when normal power failure occurs. Auxiliary contacts shall also be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The power transfer switch shall be a Firetrol FTA900 for normal utility power and engine generator set emergency power. Power Transfer Switch for Second Utility Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated combination isolating disconnect switch/circuit breaker, mechanically interlocked and operated with a single, externally mounted handle. When moving the handle from OFF to ON, the interlocking mechanism shall sequence the isolating disconnect switch closed first, and then the circuit breaker. When the handle is moved from ON to OFF, the interlocking mechanism shall sequence the circuit breaker open first, and then the isolating disconnect switch. The isolating disconnect switch/circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The isolating disconnect switch/circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. The circuit breaker trip curve adjustment shall be factory set, tested and sealed for the connected full load amps of the motor. The fire pump controller/power transfer switch shall have data logging capability for historical operation recording and to aid in annual test, service and trouble shooting. The data logging shall be accessible by front mounted interface panel and also by saving the information to supplied 1.44M floppy disk drive. The floppy disk file shall be in text (.txt) format and easily readable by most common text editing or word processing software. The circuit breaker shall be capable of being field tested to verify actual pick up, locked rotor, and instantaneous trip points after field installation without disturbing incoming line and load conductors. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer signal so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the transfer switch or fire pump circuit breakers. The controller shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF LED’s, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. To aid servicing, no indicating lights or switch devices shall be mounted on the enclosure door. Auxiliary contacts shall be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The transfer switch shall be a Firetrol FTA950 for normal utility power and second utility emergency power. Note: FTA900 and FTA950 power transfer switches are designed for use with Firetrol Electric Fire Pump Controllers, models FTA1000, FTA1250, FTA1300, FTA1350, FTA1500, FTA1800 and FTA1900. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP900-20(A) Specifications Limited Service Controllers The main fire pump controller shall be a factory assembled, wired and tested Limited Service Controller conforming to all the requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. The controller shall be manufactured in the United States and be listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment (cUL), approved by Factory Mutual, and approved by the City of New York for fire pump service. The controller shall be of the combined manual and automatic type suitable for full voltage starting of the fire pump motor having the horsepower, voltage, phase and frequency rating shown on the plans and drawings. The controller shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, gasketed, wall mounted steel enclosure. The controller components shall include a thermal magnetic circuit breaker with a minimum withstand rating of not less than: 3-20 H.P. — 200-240 Volts — 10,000 Amps RMS Symmetrical 25-30 H.P. — 200-240 Volts — 18,000 Amps RMS Symmetrical 3-30 H.P. — 380-600 Volts — 14,000 Amps RMS Symmetrical If the available fault current of the system exceeds these ratings, the controllers shall be supplied with a withstand rating as shown below: Horsepower 3-30 3-30 Voltage Withstand Rating Amps RMS Sym. 200-480 65,000 550-600 18,000 The circuit breaker shall have an externally mounted operating handle mechanically interlocked with the enclosure door so that entrance • FTA750 to the controller is not allowed with the handle in the ON position except by a hidden tool operated defeater. The circuit breaker handle shall be capable of being padlocked in the open or OFF position with up to three padlocks for installation and maintenance safety. The circuit breaker handle shall be in full control of the circuit breaker. The controller door shall have a locking type handle. The controller shall have externally mounted, on the enclosure flange, POWER ON and PHASE REVERSAL pilot lights, START and STOP pushbuttons and an EMERGENCY RUN mechanism. The START pushbutton and EMERGENCY RUN mechanism shall be separate units and not combined. The POWER ON pilot light shall be wired through contacts on the phase monitor to give true power on indication. Loss of power in any phase or loss of the control circuit transformer shall cause the light to go out. The PHASE REVERSAL pilot light shall be wired through contacts on the phase monitor to give true indication of incorrect phase angle relationships. The controller shall be supplied with a pressure switch having a range of 0-300 psi (0-21 kg/cm2) and with independent high and low pressure settings. The pressure switch shall be mounted inside the controller to prevent unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a solidly welded bulkhead pipe coupling without any other supporting members and field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The adjustment knobs shall be capable of being sealed after final adjustment. The controller shall have a minimum run period timer set for ten minutes. The minimum run timer shall include an integral timer running pilot light to indicate when the run timer FTA750 Specifications • Limited Service Controllers is in the timing mode. Terminals shall be provided to field convert the controller from automatic to manual shutdown. Terminals shall be provided so that standard duty rated, normally open pushbutton stations can be wired to the controller. Terminals shall be provided so that a remote deluge valve contact may be wired to the controller to start the unit. The controller shall be supplied with interlock and shutdown circuits as standard. Individual PHASE FAILURE, PHASE REVERSAL and PUMP OPERATING alarm contacts shall be wired to terminals. These contacts shall be both normally open and normally closed and be electrically isolated for wiring to either remote alarm panels as supplied by the controller manufacturer, or for use with remote telephone dropout type alarm systems. A factory built in alarm shall be provided in the fire pump controller, requiring only 120 Volt supervisory power. This alarm shall give an audible alarm for PUMP OPERATING, PHASE FAILURE, or PUMP FAILURE and a visual alarm for SUPERVISORY VOLTAGE AVAILABLE. This alarm shall be electrically isolated from the remote alarm contacts so that 24 VDC or separate 120 VAC remote alarms can be utilized. All alarm contacts shall be rated 125 VAC maximum 10 amperes pilot duty. They shall also be suitable for direct switching of low energy alarm circuits — 6 VDC minimum, 10 MA, 0.6 VA minimum. The control circuit transformer shall be of the molded winding construction type with built in molded terminals and shall be fuse protected from external loads. The fuse shall be installed on the transformer. The manufacturer shall test the entire controller assembly prior to shipment. This test shall include, but no be restricted to, each function the controller may be required to perform including remote alarms, remote start, automatic start with manual shutdown, automatic stop, remote deluge valve start, pressure drop start and manual start-stop. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 volts. The controller shall be manufactured by Firetrol, Inc. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP750-01(H) Specifications Fire Pump Controller Power Transfer Switches Main Fire Pump Controller with Transfer Switch The main fire pump controller shall be factory assembled and wired with a power transfer switch listed by Underwriters’ Laboratories, Inc. for transfer switch and fire pump service. The power transfer switch shall be approved by Factory Mutual. The power transfer switch and fire pump controller shall be factory assembled, wired and tested as a single unit and shall conform to all requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. Power Transfer Switch for Generator Set Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated disconnect/isolating switch capable of interrupting the motor locked rotor current. The disconnect/ isolating switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect/isolating switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety, and shall also be capable of being locked in the ON position. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. A auxiliary contact shall be provided on the transfer switch to prevent starting of the emergency generator set when the transfer switch or the main fire pump controller are being serviced. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal • FTA975-976 shall be delayed for one second, delaying the transfer and engine start signals so as to compensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the generator set or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF pilot lights, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. The power transfer switch shall be furnished with both normally open and normally closed auxiliary contacts for an engine start signal when normal power failure occurs. Auxiliary contacts shall also be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The power transfer switch shall be a Firetrol FTA975 for normal utility power and engine generator set emergency power. FTA975-976 Specifications • Fire Pump Controller Power Transfer Switches Power Transfer Switch for Second Utility Emergency Power Source The power transfer switch shall be housed within the fire pump controller enclosure or in a NEMA Type 2 (IEC IP11) drip-proof enclosure attached directly to the fire pump controller. Where the power transfer switch is provided in an attached enclosure, the enclosures shall be fitted so that the assembly constitutes a single unit. The fire pump controller/power transfer switch shall be factory assembled, wired and tested as a unit prior to shipment. The power transfer switch shall include a motor rated circuit breaker, operated with a single, externally mounted handle. The circuit breaker shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The circuit breaker shall be capable of being padlocked in the OFF position for installation and maintenance safety, and shall also be capable of being locked in the ON position without affecting the tripping characteristics of the circuit breaker. The enclosure door shall have a locking type handle and three point cam and roller type vault hardware. The transfer switch circuitry shall be capable of sensing both the normal power source and the emergency power source. The normal power source pickup shall be set at 95% nominal voltage. The emergency power source shall be set to pick up at 90% nominal voltage and 95% nominal frequency. All voltage sensing, frequency sensing, and time delays shall be field adjustable to accommodate individual installation requirements. The transfer signal shall be delayed for one second, delaying the transfer signal so as to com- pensate for momentary, normal power outages. An automatic delay of three seconds shall be provided upon transfer to or from the emergency power source to allow the motor to slow sufficiently, preventing line disturbances that could trip either the transfer switch or fire pump circuit breakers. The transfer switch shall have TRANSFER SWITCH NORMAL, TRANSFER SWITCH EMERGENCY and EMERGENCY ISOLATING SWITCH OFF pilot lights, TEST and TRANSFER BYPASS switches, an audible alarm device and SILENCE ALARM pushbutton mounted on the flange of the enclosure. To aid servicing, no indicating lights or switch devices shall be mounted on the enclosure door. Auxiliary contacts shall be provided and wired to terminals to indicate the transfer switch position. The transfer switch shall be electrically operated and mechanically held, and shall be capable of being operated by a manual transfer mechanism located on the switch. The transfer switch shall be a Firetrol FTA976 for normal utility power and second utility emergency power. Note: FTA975 and FTA976 power transfer switches are designed for use with Firetrol Limited Service Controllers model FTA750. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP975-01(A) Specifications Diesel Engine Fire Pump Controllers Diesel Engine Fire Pump Controller The fire pump controller shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The controller shall be listed by Underwriters Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, and Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment (cULus) and approved by Factory Mutual. The controller shall be: 12 Volt 24 Volt The controller components shall be housed in a NEMA Type 2 (IEC IP11) drip-proof, wall mounted enclosure. Operator Interface The fire pump controller shall feature an operator interface with user keypad. The interface shall monitor and display motor operating conditions, including all alarms, events, and pressure conditions. All alarms, events, and pressure conditions shall be displayed with a time and date stamp. The display shall be a 4line, 20-character, vacuum fluorescent, dot matrix type designed to allow easy viewing from all angles and in all light conditions. The display and interface shall be NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and shall be fully accessible without opening the controller door. The display and user interface shall utilize multiple levels of password protection for system security. A minimum of 3 password levels shall be provided. The display shall be capable of being programmed for any language. Digital Status/Alarm Messages The digital display shall indicate text messages for the status and alarm conditions of: • Engine Run • Sequential Start Time • Minimum Run Time • Crank/Rest Time - Cycle / Off Delay Time • Remote Start • Engine Fail to Start • System Battery Low • Low Suction Pressure • Printer Error • Drive Not Installed • Manual Engine Crank • Disk Error • Disk Near Full • Pressure Error The Sequential Start Timer, Minimum Run Timer/Off Delay Timer and Crank/Rest time shall be displayed as numeric values reflecting the value of the remaining time. LED Visual Indicators LED indicators, visible with the door closed, shall indicate: • Main Switch in Auto • Alarm • Engine Fail to Start • • • • • • • • • FTA1100 Charger Malfunction Battery #1 Trouble Battery #2 Trouble System Pressure Low Engine Running Engine Coolant Temperature High Engine Oil Pressure Low Engine Overspeed In addition to the standard alarm contacts required by NFPA 20, the digital display module shall have N.O. and N.C. contacts for remote indications of any digitally displayed alarm and N.O. and N.C. contacts for remote indication up to EIGHT, specified, programmable alarm. Data Logging The digital display shall monitor the system and log the following data: • Motor Calls/Starts • Total Engine Run Time • Last Engine Run Time • Last Engine Start • Last High Water Temperature • Last Low Oil Pressure • Last Low Fuel Level • Last Battery Charger Failure • Last Battery Trouble • Last Engine Overspeed • Minimum Battery Voltages • Maximum Battery Voltages • Total Unit Run Time • Minimum/Maximum System Pressure Event Recording Printer - The controller shall be equipped with a dot matrix, impact printer to record all operational and alarm events. The printer shall use standard 16# bond paper, commercially available at office supply stores. Thermal or electrostatic printers are not acceptable. The printer shall feature a mechanical take-up mechanism to prevent excessive paper buildup in the bottom of the controller during automatic operation. The printer shall automatically record all events and pressure settings. It shall allow the user to select the pressure recording frequency based upon either time or pressure deviation. If set for time based recording, the printer shall record the pressure every 30 minutes during standby and every 15 seconds during operation. Memory - The controller shall record all operational and alarm events to system memory. All events shall be time and date stamped and include an index number. The system memory shall have the capability of storing 3000 events and allow the user access to the event log via the user interface. The user shall have the ability to scroll through the stored messages in groups of 1, 10, or 100. Floppy Disk Drive - The controller shall include a floppy disk drive to save all operational and alarm events. The floppy disk drive shall have the ability to store up to 1 year’s worth of data (under normal oper- ating conditions) in individual monthly files. Each event shall be time and date stamped. The controller shall also have the capability to save settings and values to disk through the user interface. Communications - The controller shall feature two independent communications ports to allow connectivity to computers, modems, or building management systems. Solid State Pressure Transducer The controller shall be supplied with a solid state pressure transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The solid state pressure switch shall be used for both display of the system pressure and control of the fire pump controller. Systems using analog pressure devices or mercury switches for operational control will not be accepted. The START, STOP and SYSTEM PRESSURE shall be digitally displayed and adjustable through the user interface. The pressure transducer shall be mounted inside the controller to prevent accidental damage. The pressure transducer shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. A Lamp Test feature shall be included. The user interface shall also have the ability to display the status of the system inputs and outputs. Battery Chargers The controller shall include two fully automatic, 200 amp hour, 4 step battery chargers. The chargers shall feature a qualification stage, in which the batteries are examined by the charger to insure that they are not defective and are capable of accepting a charge. The battery charger shall feature: • Selectable AC Power Voltage • Selectable Battery Voltage • Selectable Battery Type • Charge Cycle Reset Push-button The controller shall be a Firetrol brand. Operation A digitally set On Delay (Sequential Start) timer shall be provided as standard. Upon a call to start, the user interface shall display a message indicating the remaining time value of the On Delay timer. The controller shall be field programmable for manual stop or automatic stop. If set for automatic stopping, the controller shall allow the user to select either a Minimum Run Timer or an Off Delay Timer. Both timers shall be programmable through the user interface. The controller shall include an AC Power Loss start timer to start the engine in the event of AC Power failure. The controller shall be fully programmable to allow up to 8 custom alarm messages to be displayed on the user interface. A weekly test timer shall be provided as standard. The controller shall have the ability to program the time, date, and frequency of the weekly test. In addition, the controller shall have the capability to display a preventative maintenance message for a service inspection. The message text and frequency of occurrence shall be programmable through the user interface. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP1100-20 Specifications Alarm Panels The alarm panel shall be a factory assembled, wired and tested unit and shall conform to all the requirements of the latest edition of NFPA 20, Centrifugal Fire Pumps and NFPA 70, National Electrical Code. The alarm panel shall be listed by Underwriters’ Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL), approved by the New York City Bureau of Electrical Control and Board of Standards and Appeals and Factory Mutual. The alarm panel shall be low voltage DC and make use of printed circuit boards which can be easily wired together for future additional alarms. The alarm panel shall have individual pilot lights to indicate its alarm condition which shall remain • FTA200 lighted until the alarm condition has been corrected. The alarm panel shall also have an audible alarm which will sound when the alarm conditions occur and may be silenced by pressing a SILENCE ALARM push-button. Each alarm initiation shall be subsequent to any and all previous alarm conditions so that the silence push-button acknowledgment of any one alarm will not prevent the audible alarm from sounding on successive alarm conditions. The alarm panel shall have a PUSH-TO-TEST push-button for manually testing all pilot lights, audible alarms and output circuits (types A, B, F, G only). All alarm pilot lights and push-buttons shall be plainly marked for identification. The alarm panel shall be NEMA Type 2 (IEC IP11) drip-proof for indoor wall mounting. The alarm panel shall be a Firetrol FTA200 model. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP200-01(E) Specifications Jockey Pump Controllers The auxiliary jockey pump controller, if required and specified on the plans and specifications, shall be factory assembled, wired, and tested and specifically designed for this type of service. This controller shall be UL listed, and shall be of the same manufacturer as the main fire pump controller. The controller shall incorporate a full voltage magnetic starter, main disconnect switch, motor fuse block with fuses, HAND-OFF-AUTOMATIC selector switch and a pressure switch. The pressure switch shall have a range of 30-300 psi (2.1-20.7 bars) and have an adjustable differential range of 10-40 psi (.7-2.8 bars). The pressure switch shall be of the diaphragm type utilizing snapaction type contacts. The pressure switch shall be mounted inside the controller to prevent any unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. A system pressure gauge shall be mounted with the pressure switch to assist in pressure switch adjustments and provide an indication of current system pressure. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The controller shall have a running period timer to prevent too frequent automatic starting of the jockey pump motor. The timer shall be set to keep the motor in operation for at least one minute and interwired with the pressure switch. • FTA500 The disconnect switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety. The minimum enclosure rating shall be NEMA Type 2 (IEC IP11), drip-proof. All pushbuttons, selector switches, pilot lights shall be NEMA Type 12, oiltight. Pilot lights (when specified) shall be transformer type. No pushbuttons or pilot lights shall be mounted on the enclosure door. The control circuit transformer (when specified) shall be of the molded winding construction type with built-in molded terminals and shall be fuse protected. The fuse shall be built into the transformer. The controller manufacturer, prior to shipment, shall hook up and test the jockey pump controller as a completed assembly. This test shall include, but not be restricted to, each function the controller may be required to perform including manual startstop, automatic start-stop and minimum run timing. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 Volts. The controller shall be manufactured by Firetrol, Inc. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP500-01(I) Specifications Jockey Pump Controllers Wye Delta Open Transition with Main Disconnect Switch The auxiliary jockey pump controller, if required and specified on the plans and specifications, shall be factory assembled, wired, and tested and specifically designed for this type of service. This controller shall be UL listed, and shall be of the same manufacturer as the main fire pump controller. The controller shall incorporate a wye delta open transition starting method, control circuit transformer, main disconnect switch, motor fuse block, HAND-OFF-AUTOMATIC selector switch and pressure switch. The pressure switch shall have a range of 30-300 psi (2.1-20.7 bars) and have an adjustable differential range of 10-40 psi (.7-2.8 bars). The pressure switch shall be of the diaphragm type utilizing snapaction type contacts. The pressure switch shall be mounted inside the controller to prevent any unauthorized adjustment and/or accidental damage. The adjustment knobs shall be capable of being sealed after final adjustment. The pressure switch shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. A system pressure gauge shall be mounted with the pressure switch to assist in pressure switch adjustments and provide an indication of current system pressure. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. • FTA516 The controller shall have a running period timer to prevent too frequent automatic starting of the jockey pump motor. The timer shall be set to keep the motor in operation for at least one minute and interwired with the pressure switch. The disconnect switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety. The minimum enclosure rating shall be NEMA Type 2 (IEC IP11), drip-proof. All pushbuttons, selector switches, pilot lights shall be NEMA Type 12, oiltight. Pilot lights (when specified) shall be transformer type. No pushbuttons or pilot lights shall be mounted on the enclosure door. The control circuit transformer shall be of the molded winding construction type with built-in molded terminals and shall be fuse protected. The fuse shall be built into the transformer. The controller manufacturer, prior to shipment, shall hook up and test the jockey pump controller as a completed assembly. This test shall include, but not be restricted to, each function the controller may be required to perform including manual startstop, automatic start-stop and minimum run timing. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 Volts. The controller shall be manufactured by Firetrol, Inc. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP516-01(C) Blank