Energía de baterías BAE Secura OGi BLOCK Technical Specification for Stationary VLA-Block Batteries 1. Application BAE Secura OGi BLOCK batteries are robust and for high discharge-performances optimised lead-acid batteries. They are particularly suitable for autonomy times of a few minutes to one hour. BAE OGi batteries are used for uninterrupted power supplies (UPS), to start diesel engines and for emergency power supplies in switch stations of utilities, in signal systems of railway applications or in other stations. 2. Types, capacities, dimensions, weights Type C10 h C3 h 20 °C 20 °C Ah Ah C1 h C30 min C10 min 20 °C 20 °C 20 °C Ah Ah Ah C5 min 20 °C Ah C8 h 25 °C Ah 1.80 1.75 1.70 1.65 1.65 1.65 1.75 12 V 1 OGi 25 12 V 2 OGi 50 12 V 3 OGi 75 12 V 4 OGi 100 12 V 5 OGi 125 12 V 6 OGi 150 30 60 91 112 151 166 23 47 71 90 118 133 18 36 54 69 90 103 15 30 45 58 75 86 10 20 31 40 50 59 7 14 20 27 33 39 6 V 7 OGi 175 6 V 8 OGi 200 6 V 9 OGi 225 6 V 10 OGi 250 6 V 11 OGi 275 6 V 12 OGi 300 206 234 262 289 317 344 163 185 207 230 252 274 124 141 159 176 193 210 103 118 132 147 162 176 69 78 86 95 103 111 555 690 822 425 528 631 355 442 529 234 286 335 Ue V/cell 2 V 24 OGi 600 703 2 V 30 OGi 750 869 2 V 36 OGi 900 1,030 Ri 1) mV Ik 2) kA Length Width (L) (W) mm mm Height Weight Weight (H) dry filled mm kg kg 30 61 91 113 152 167 16.78 9.11 6.39 5.00 4.19 3.60 0.74 1.37 1.95 2.50 2.99 3.47 272 272 272 272 380 380 205 205 205 205 205 205 385 385 385 385 385 385 22.0 30.0 37.2 44.5 54.5 60.7 35.0 42.0 47.5 54.2 71.5 74.7 44 50 55 60 65 69 208 236 264 292 320 348 1.61 1.44 1.33 1.23 1.15 1.09 3.89 4.32 4.68 5.05 5.40 5.73 272 272 380 380 380 380 205 205 205 205 205 205 385 385 385 385 385 385 34.8 40.0 46.0 50.0 54.0 57.6 48.0 51.0 63.3 67.0 71.0 72.5 150 182 211 708 872 1,040 0.16 0.13 0.12 12.95 15.29 17.38 205 205 205 272 380 380 385 385 385 40.0 50.0 57.6 51.0 67.0 72.5 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-11 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. BAE Secura OGi blocks are also available as dry pre-charged version. They are titled with additional “TG”, e.g. 12 V 6 OGi 150 TG. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 3. Terminal positions 12 V 1 OGi 25 to 12 V 6 OGi 150 6 V 7 OGi 175 to 6 V 12 OGi 300 2 V 24 OGi 600 to 2 V 36 OGi 900 Technical Specification for BAE Secura OGi BLOCK Blocks with blind cells Plugs Pole-bushing Kind of pole Connectors Connector screw Kind of protection 5. Charging IU-characteristic Float current Boost charge Charging time up to 90 % 6. Discharge characteristics Reference temperature Initial capacity Depth of discharge (DOD) Deep discharges 7. Maintenance Every 6 months Every 12 months 8. Operational data Service life Water-refilling-interval IEC 60896-11 cycles Self-discharge Battery temperature Standard Tests according to Safety standard, ventilation Transport BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany grid-plate with circular bars in a corrosion-resistant low antimony alloy grid-plate in low antimony alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l high impact, transparent SAN (Styrol-Acrylic-Nitrile), UL-94 rating: HB high impact SAN in grey colour (colour may vary slightly from given image), UL-94 rating: HB 4 V, 6 V, 8 V, 10 V labyrinth plugs for arresting aerosols, optional ceramic plugs or ceramic funnel plugs according to DIN 40740 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2, as option: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to VBG 4 Imax without limitation U = 2.23 V/cell ± 1 %, between 10 °C and 30 °C (50 °F and 86 °F) in the monthly average otherwise DU/DT = -0.003 V/cell per K approx. 20 mA/100 Ah C10, increasing to approx. 60 mA/100 Ah C10 at the end of service life U = 2.33 to 2.40 V/cell, time limited 6 h with 1.5 x I10 initial current, 2.23 V/cell, 50 % C10 discharged 20 °C (68 °F) according to IEC 60896-11: 95 % at the 1st cycle, 100 % at the 5th cycle normally up to 80 % more than 80 % DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided check battery voltage, pilot block voltages, temperatures record battery and block voltages and temperatures 16 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) >3 years, float at 20 °C to 25 °C (68 °F to 77 °F) >1,000 approx. 3 % per month at 20 °C (68 °F) -20 °C to 55 °C (-4 °F to 131 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) dimensions according to DIN 40737-3 IEC 60896-11 EN 50272-2 Batteries are not subject to ADR (road transport), if the conditions of Special Provision 598 (Chapter 3.3) are observed. These cells/batteries are dangerous goods on sea transport. Declaration and packaging must comply with the requirements of IMDG-Codes. Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 12/2012 4804036 Technical details may be subject to alterations. 4. Design Positive electrode Negative electrode Separation Electrolyte Container Lid BAE Secura OGi Technical Specification for Stationary VLA-Cells Similar to the illustration 1. Application BAE Secura OGi cells are designed for reliable operation, long service life, high discharge currents during short discharge times and capacitive loads over longer discharge times. They are used as stand-by source in power supply stations, transforming stations, UPS-stations and emergency light equipment. Due to the used grid plate design with high mass of lead and circular bars a long operational life and a very good high-current-performance can be assured. The slick-walled containers and the vertical arranged plates offer a high power density related to a small foot-print. The transparent container allows an easy visual access and simplifies service and maintenance significantly. 2. Types, capacities, dimensions, weights Type Ue V/cell C10 h C5 h 20 °C 20 °C Ah Ah 1.80 1.80 C3 h 20 °C Ah 1.79 C1 h 20 °C Ah 1.75 C30 min C10 min C8 h 20 °C 20 °C 25 °C Ah Ah Ah 1.72 1.65 1.75 Ri 1) mV Ik 2) kA Length Width (L) (W) mm mm Height Weight Weight (H) dry filled mm kg kg 8 OGi 200 10 OGi 250 12 OGi 300 14 OGi 350 16 OGi 400 18 OGi 450 234 289 345 397 455 510 206 255 304 350 402 451 183 226 270 312 357 402 140 173 207 239 276 310 115 143 170 197 229 257 79 97 115 132 158 177 236 292 348 400 459 515 0.45 0.38 0.33 0.29 0.23 0.20 4.58 5.47 6.28 7.02 9.25 10.21 103 124 145 145 187 187 206 206 206 206 206 206 420 420 420 420 420 420 14.4 17.2 19.9 22.4 25.3 27.8 18.8 22.6 26.5 28.7 34.0 36.2 5 OGi 400 6 OGi 480 7 OGi 560 8 OGi 640 9 OGi 720 422 506 590 675 710 352 423 493 560 595 306 366 429 489 525 222 266 310 353 385 172 205 239 271 299 100 119 138 156 173 415 498 581 664 701 0.44 0.37 0.32 0.29 0.26 4.71 5.53 6.34 7.08 7.84 145 145 145 145 145 206 206 206 206 206 700 700 700 700 700 27.5 31.3 34.9 38.6 42.3 41.0 44.6 47.8 51.3 54.6 10 OGi 800 11 OGi 880 12 OGi 960 843 910 942 705 760 795 612 666 699 444 483 515 343 374 402 199 218 235 824 896 928 0.22 0.20 0.19 9.23 10.07 10.88 210 210 210 191 191 191 700 700 700 50.9 54.6 58.2 67.7 71.2 74.5 13 OGi 1040 14 OGi 1120 15 OGi 1200 1,090 1,140 1,170 910 960 990 792 837 870 568 608 635 431 467 488 243 267 278 1,080 1,128 1,160 0.19 0.17 0.17 10.66 12.00 12.28 210 210 210 233 233 233 700 700 700 62.7 66.6 70.2 83.5 87.2 90.5 16 OGi 1280 17 OGi 1360 18 OGi 1440 1,340 1,115 1,370 1,155 1,410 1,190 972 1,011 1,047 695 734 768 526 563 596 295 321 344 1,320 1,360 1,392 0.16 0.14 0.13 12.83 14.31 15.59 210 210 210 275 275 275 700 700 700 75.1 78.8 82.4 100.0 103.5 106.8 19 OGi 1520 20 OGi 1600 21 OGi 1680 22 OGi 1760 23 OGi 1840 24 OGi 1920 1,590 1,670 1,750 1,800 1,820 1,860 1,330 1,400 1,470 1,510 1,540 1,575 1,164 846 1,224 889 1,284 932 1,323 966 1,353 996 1,389 1,028 659 691 725 753 780 807 387 406 425 442 460 476 1,568 1,648 1,728 1,768 1,792 1,832 0.11 0.10 0.10 0.10 0.09 0.09 18.45 19.19 20.08 20.82 21.69 22.35 210 210 210 210 210 210 360 360 360 360 360 360 675 675 675 675 675 675 88.7 92.3 95.9 99.7 103.5 106.9 122.0 125.2 128.6 132.0 135.3 138.7 25 OGi 2000 26 OGi 2080 27 OGi 2160 28 OGi 2240 29 OGi 2320 30 OGi 2400 2,080 2,160 2,230 2,260 2,290 2,320 1,745 1,810 1,870 1,900 1,935 1,965 1,521 1,581 1,632 1,665 1,701 1,731 855 886 918 944 972 996 497 514 533 548 567 580 2,048 2,128 2,192 2,224 2,264 2,296 0.09 0.08 0.08 0.08 0.08 0.07 23.05 23.67 24.58 25.20 26.10 26.61 210 210 210 210 210 210 440 440 440 440 440 440 675 675 675 675 675 675 112.8 116.5 120.2 123.9 127.6 131.3 154.1 157.5 160.8 164.1 167.6 170.9 1,104 1,146 1,186 1,216 1,248 1,277 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-11 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values published in the table correspond to 100 % discharge of current depending capacity without voltage drop of connectors. 3. Terminal positions 8 OGi 200 to 9 OGi 720 10 OGi 800 to 18 OGi 1440 19 OGi 1520 to 30 OGi 2400 Technical Specification for BAE Secura OGi 4. Design Positive electrode Negative electrode Separation Electrolyte Container Lid Plugs Pole-bushing Kind of pole Connectors Connector screw Kind of protection grid-plate with circular bars in a corrosion-resistant low antimony alloy grid-plate in low antimony alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l high impact, transparent SAN (Styrol-Acrylic-Nitrile), UL-94 rating: HB high impact SAN in grey colour, UL-94 rating: HB, on request also in ABS (Acrylonitrile-Butadiene-Styrene), UL-94 rating: V-0 labyrinth plugs for arresting aerosols, recommended BAE ceramic funnel plugs according to DIN 40740 or BAE ceramic plugs 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 copper insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2; on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to BGV A3 BAE Secura OGi cells are also available as dry, pre-charged version. They are specifically marked with “TG”, e.g. 30 OGi 2400 TG. 5. Charging IU-characteristic Boost charge 6. Discharge characteristics Reference temperature Initial capacity 7. Operational data Service life Water-refilling-interval IEC 60896-11 cycles Self-discharge Battery temperature 20 °C (68 °F) according to IEC 60896-11: 95 % at the 1st cycle, 100 % at the 5th cycle 20 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) >3 years, float at 20 °C to 25 °C (68 °F to 77 °F) >1,200 approx. 3 % per month at 20 °C (68 °F) -20 °C to 55 °C (-4 °F to 131 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) dimensions according to DIN 40736-1 IEC 60896-11 EN 50272-2 03/2015 4805604 Technical details may be subject to alterations. Standard Tests according to Safety standard, ventilation Imax without limitation U = 2.23 V/cell ± 1 %, between 10 °C and 30 °C (50 °F and 86 °F) in the monthly average, otherwise DU/DT = -0.003 V/cell per K U = 2.33 to 2.40 V/cell, time limited BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de BAE Secura OPzS BLOCK Technical Specification for Stationary VLA-Block Batteries 1. Application BAE Secura OPzS Block batteries belong to the most enduring lead-acid batteries. They are suitable for stand-by operations as well as for capacitive loads. They perfectly meet requirements for autonomy times between 30 min and more than 10 h. Fields: Telecommunications Emergency lighting Microwave radio systems Power generation plants 2. Types, capacities, dimensions, weights Type C10 h 20 °C Ah C5 h 20 °C Ah C3 h 20 °C Ah C1 h 20 °C Ah C8 h 25 °C Ah 1.80 1.77 1.75 1.67 1.75 12 V 1 OPzS 50 12 V 2 OPzS 100 12 V 3 OPzS 150 56 109 167 48 95 145 42 84 129 31 63 95 6 V 4 OPzS 200 6 V 5 OPzS 250 6 V 6 OPzS 300 223 279 334 194 242 290 171 214 257 127 159 191 Ue V/cell Ri 1) mV Ik 2) kA Length Width Height Weight Weight (L) (W) (H) dry filled mm mm mm kg kg 55 108 165 16.62 8.91 6.27 0.75 1.40 1.99 272 272 380 205 205 205 385 385 385 29.5 38.0 51.0 41.0 47.6 69.4 220 276 332 2.47 2.09 1.82 2.52 2.98 3.42 272 380 380 205 205 205 385 385 385 33.0 41.7 48.5 46.5 60.4 66.5 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-11 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. BAE Secura OPzS blocks are also available as dry pre-charged version. They are titled with additional “TG”, e.g. 12 V 3 OPzS 150 TG. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 3. Terminal positions 12 V 1 OPzS 50 to 12 V 3 OPzS 150 6 V 4 OPzS 200 to 6 V 6 OPzS 300 Technical Specification for BAE Secura OPzS BLOCK Negative electrode Separation Electrolyte Container Lid Blocks with blind cells Plugs Pole-bushing Kind of pole Connectors Connector screw Kind of protection 5. Charging IU-characteristic Float current Boost charge Charging time up to 90 % 6. Discharge characteristics Reference temperature Initial capacity Depth of discharge (DOD) Deep discharges 7. Maintenance Every 6 months Every 12 months 8. Operational data Service life Water-refilling-interval IEC 60896-11 cycles Self-discharge Battery temperature Standard Tests according to Safety standard, ventilation Transport BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany tubular-plate with woven polyester gauntlet and solid grids in a corrosion-resistant PbSbSnSe-low antimony alloy grid-plate in low antimony alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l high impact, transparent SAN (Styrol-Acrylic-Nitrile), UL-94 rating: HB high impact SAN in grey colour (colour may vary slightly from given image), UL-94 rating: HB 4 V, 6 V, 8 V, 10 V labyrinth plugs for arresting aerosols, optional ceramic plugs or ceramic funnel plugs according to DIN 40740 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2; on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point P 25 regarding EN 60529, touch protected according to VBG 4 Imax without limitation U = 2.23 V/cell ± 1 %, between 10 °C and 30 °C (50 °F and 86 °F) in the monthly average, otherwise DU/DT = -0.003 V/cell per K approx. 15 mA/100 Ah C10, increasing to approx. 30 mA/100 Ah C10 at the end of service life U = 2.33 to 2.40 V/cell, time limited 6 h with 1.5 x I10 initial current, 2.23 V/cell, 50 % C10 discharged 20 °C (68 °F) according to IEC 60896-11: 95 % at the 1st cycle, 100 % at the 5th cycle normally up to 80 % more than 80 % DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided check battery voltage, pilot block voltages, temperatures record battery and block voltages and temperatures 18 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) >3 years, float at 20 °C to 25 °C (68 °F to 77 °F) >1,200 approx. 3 % per month at 20 °C (68 °F) -20 °C to 55 °C (-4 °F to 131 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) DIN 40737-3 IEC 60896-11 EN 50272-2 Batteries are not subject to ADR (road transport), if the conditions of Special Provision 598 (Chapter 3.3) are observed. These cells/batteries are dangerous goods on sea transport. Declaration and packaging must comply with the requirements of IMDG-Codes. Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 12/2012 4804034 Technical details may be subject to alterations. 4. Design Positive electrode BAE Secura OPzS Technical Specification for Stationary VLA-Cells Similar to the illustration 1. Application BAE Secura OPzS batteries belong to the most enduring lead-acid batteries. They are suitable for stand-by operations as well as for capacitive loads. They perfectly meet requirements for autonomy times between 1 h and more than 10 h. Fields: Telecommunications Emergency lighting Microwave radio systems Power generation plants 2. Types, capacities, dimensions, weights Type C10 h 20 °C Ah C5 h 20 °C Ah C3 h 20 °C Ah C1 h 20 °C Ah C8 h 25 °C Ah 1.80 1.77 1.75 1.67 1.75 2 OPzS 100 3 OPzS 150 4 OPzS 200 5 OPzS 250 6 OPzS 300 111 167 223 279 334 97 145 193 242 290 86 129 171 214 257 63 95 127 159 191 5 OPzS 350 6 OPzS 420 7 OPzS 490 389 467 544 346 414 483 306 366 429 6 OPzS 600 7 OPzS 700* 8 OPzS 800 9 OPzS 900* 10 OPzS 1000 11 OPzS 1100* 12 OPzS 1200 665 777 886 992 1,100 1,210 1,320 580 675 770 860 960 1,050 1,150 11 OPzS 1375* 12 OPzS 1500 13 OPzS 1625* 14 OPzS 1750 15 OPzS 1875* 16 OPzS 2000 17 OPzS 2125* 18 OPzS 2250 19 OPzS 2375* 20 OPzS 2500 22 OPzS 2750 24 OPzS 3000 26 OPzS 3250 1,470 1,600 1,740 1,880 2,010 2,140 2,290 2,420 2,560 2,690 2,950 3,220 3,480 1,295 1,415 1,550 1,665 1,780 1,900 2,030 2,150 2,265 2,380 2,615 2,845 3,080 Ue V/cell Ri 1) mV Ik 2) kA Length Width Height Weight Weight (L) (W) (H) dry filled mm mm mm kg kg 110 165 220 276 332 1.52 1.06 0.84 0.70 0.60 1.37 1.96 2.46 2.98 3.47 105 105 105 126 147 208 208 208 208 208 420 420 420 420 420 9.1 11.2 12.8 15.3 18.1 14.5 16.4 18.0 21.7 25.7 223 267 310 392 470 548 0.57 0.49 0.44 3.61 4.18 4.69 126 147 168 208 208 208 535 535 535 20.0 23.5 26.8 28.8 34.0 39.1 504 594 675 753 840 918 1,005 352 415 473 522 585 635 698 670 781 888 1,000 1,112 1,216 1,328 0.47 0.36 0.32 0.33 0.28 0.28 0.24 4.41 5.66 6.36 6.20 7.25 7.36 8.41 147 215 215 215 215 215 215 208 193 193 235 235 277 277 710 710 710 710 710 710 710 33.0 42.1 46.6 51.4 56.0 61.0 65.4 47.4 61.5 65.4 75.4 79.4 89.6 93.4 1,137 1,245 1,371 1,473 1,578 1,680 1,797 1,899 2,004 2,106 2,307 2,514 2,715 790 869 978 1,051 1,123 1,195 1,280 1,352 1,425 1,496 1,635 1,777 1,917 1,496 1,632 1,768 1,904 2,032 2,168 2,320 2,456 2,592 2,728 2,992 3,264 3,536 0.24 0.22 0.16 0.15 0.14 0.13 0.12 0.11 0.11 0.11 0.10 0.09 0.09 8.38 9.48 13.03 13.82 14.43 15.20 16.91 17.55 18.36 18.92 19.92 21.26 22.49 215 215 215 215 215 215 215 215 215 215 215 215 215 277 277 400 400 400 400 490 490 490 490 580 580 580 855 855 815 815 815 815 815 815 815 815 815 815 815 72.7 77.4 90.8 95.3 100.2 105.4 117.7 121.9 126.8 132.0 145.4 155.2 165.0 105.9 110.4 137.8 142.4 146.9 151.6 175.1 179.1 183.6 188.3 213.9 223.0 232.0 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-11 * Special type based on DIN 40736-1 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values published in the table correspond to 100 % discharge of current depending capacity without voltage drop of connectors. 3. Terminal positions 2 OPzS 100 to 6 OPzS 600 7 OPzS 700 to 12 OPzS 1500 13 OPzS 1625 to 16 OPzS 2000 17 OPzS 2125 to 26 OPzS 3250 Technical Specification for BAE Secura OPzS 4. Design Positive electrode Negative electrode Separation Electrolyte Container Lid Plugs Pole-bushing Kind of pole Connectors Connector screw Kind of protection tubular-plate with woven polyester gauntlet and solid grids in a corrosion-resistant PbSbSnSe-low antimony alloy grid-plate in low antimony alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l (20 °C / 68 °F) high impact, transparent SAN (styrene-acrylonitrile resin), UL-94 rating: HB high impact plastic lid in grey colour, UL-94 rating: HB, on request also in ABS (Acrylonitrile-Butadiene-Styrene), UL-94 rating: V-0 labyrinth plugs for arresting aerosols, recommended BAE ceramic funnel plugs according to DIN 40740 or BAE ceramic plugs 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2; on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to BGV A3 BAE Secura OPzS cells are also available as dry, pre-charged version. They are specifically marked with „TG“, e.g. 12 OPzS 1500 TG. Boost charge 6. Discharge characteristics Reference temperature Initial capacity 7. Operational data Service life Water-refilling-interval IEC 60896-11 cycles Self-discharge Battery temperature Standard Tests according to Safety standard, ventilation BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany Imax without limitation U = 2.23 V/cell ± 1 %, between 10 °C and 30 °C (50 °F and 86 °F) in the monthly average, otherwise DU/DT = -0.003 V/K U = 2.33 to 2.40 V/cell, time limited 20 °C (68 °F) according to IEC 60896-11: 95 % at the 1st cycle, 100 % at the 5th cycle 20+ years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) >3 years, float at 20 °C to 25 °C (68 °F to 77 °F) >1,500 approx. 3 % per month at 20 °C (68 °F) -20 °C to 55 °C (-4 °F to 131 °F), recommended 10 °C to 30 °C (50 °F to 86 °F) DIN 40736-1 (except * marked cells) IEC 60896-11 EN 50272-2 Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 03/2015 4805603 Technical details may be subject to alterations. 5. Charging IU-characteristic BAE Secura OPzV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries 1. Application BAE Secura OPzV Block batteries belong to the highest EUROBAT classification for maintenance-free lead-acid batteries: >12 years long life. In applications with high requirements of operational safety and autonomy times of 1 h to more than 10 h, the BAE Secura OPzV Blocks are the right choice. They are used as stand-by power sources in telecommunications, in microwave radio systems, emergency lighting and other equipments. 2. Types, capacities, dimensions, weights Type C10 h 20 °C Ah C5 h 20 °C Ah C3 h 20 °C Ah C1 h 20 °C Ah C8 h 25 °C Ah 1.80 1.77 1.75 1.67 1.75 12 V 1 OPzV 50 12 V 2 OPzV 100 12 V 3 OPzV 150 60 110 167 53 99 149 48 89 135 35 68 103 6 V 4 OPzV 200 6 V 5 OPzV 250 6 V 6 OPzV 300 224 281 337 200 251 301 181 227 273 2 V 12 OPzV 600 2 V 15 OPzV 750 2 V 18 OPzV 900 674 844 1,010 600 750 905 543 681 819 Ue V/cell Ri 1) mV Ik 2) kA Length (L) mm Width (W) mm Height Weight (H) mm kg 60 109 166 17.47 9.55 6.74 0.73 1.34 1.91 272 272 380 205 205 205 385 385 385 43.0 52.0 74.2 137 172 207 222 279 335 2.66 2.24 1.94 2.42 2.87 3.31 272 380 380 205 205 205 385 385 385 51.0 65.0 73.8 413 517 622 668 832 1,000 0.29 0.24 0.21 7.33 8.81 10.18 205 205 205 272 380 380 385 385 385 51.0 65.0 73.8 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-21 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 3. Terminal positions 12 V 1 OPzV 50 to 12 V 3 OPzV 150 6 V 4 OPzV 200 to 6 V 6 OPzV 300 2 V 12 OPzV 600 to 2 V 18 OPzV 900 Technical Specification for BAE Secura OPzV BLOCK Negative electrode Separation Electrolyte Container and lid Blocks with blind cells Valve Pole-bushing Kind of pole Connectors Connector screw Kind of protection Horizontal operation 5. Charging IU-characteristic Float current Boost charge Charging time up to 92 % 6. Discharge characteristics Reference temperature Initial capacity Depth of discharge (DOD) Deep discharges 7. Maintenance Every 6 months Every 12 months 8. Operational data Classification according to EUROBAT Service life Maintenance-free IEC 60896-21 cycles Self-discharge Battery temperature Deep discharge recovery Standard Tests according to Safety standard, ventilation Transport BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany tubular-plate with woven polyester gauntlet and solid grids in a corrosion-resistant PbCaSn-alloy grid-plate in PbCaSn-alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l, fixed as GEL by fumed silica high impact SAN (Styrol-Acrylic-Nitrile), grey coloured (colour may vary slightly from given image), UL-94 rating: HB on request also in ABS (Acrylonitrile-Butadiene-Styrene), UL-94 rating: V-0 4 V, 6 V, 8 V, 10 V one valve per cell with flame arrestor, opening pressure approx. 120 mbar 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm², on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm² M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to VBG 4 Please use BAE special type OPzV “horizontal”. The construction and production of this type is adapted to the horizontal operation. Imax without limitation U = 2.25 V/cell ± 1 %, between 10 °C and 45 °C (50 °F and 113 °F) in the monthly average, DU/DT = -0.003 V/cell per K below 10 °C (50 °F) 20 - 30 mA/100 Ah C10 U = 2.33 to 2.40 V/cell, time limited 6 h with 1.5 x I10 initial current, 2.25 V/cell, 50 % C10 discharged 20 °C (68 °F) according to IEC 60896-21: 95 % at the 1st cycle, 100 % at the 5th cycle normally up to 80 % more than 80 % DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided check battery voltage, pilot block voltages, temperatures record battery and block voltages and temperatures 12 years and longer - long life 18 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) no topping up during life >1,500 approx. 2 % per month at 20 °C (68 °F) -20 °C to 45 °C (-4 °F to 113 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) short time 45 °C to 55 °C (113 °F to 131 °F) very good DIN 40744 IEC 60896-21, -22 EN 50272-2, Ventilation requirements are reduced to 20 % compared to those for vented batteries of the same capacity. Batteries are not subject to ADR (road transport), if the conditions of Special Provisions 598 and 238 (Chapter 3.3) are observed. BAE cells/batteries are conform to the IMDG-Code, therefore these products are no dangerous goods on sea transport. Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 12/2012 4804035 Technical details may be subject to alterations. 4. Design Positive electrode BAE Secura OPzV Technical Specification for Stationary VRLA-GEL-Cells (DIN 40742) 1. Application BAE OPzV batteries belong to the highest EUROBAT classification for maintenance-free lead-acid batteries: >12 years long life. In applications with high requirements of operational safety and autonomy times of 1 h to more than 10 h, the BAE OPzV batteries are the right choice. They are used as stand-by power sources in telecommunications, in microwave radio systems, emergency lighting, power generation plants and other equipments. 2. Types, capacities, dimensions, weights Type C10 h 20 °C Ah C5 h 20 °C Ah C3 h 20 °C Ah C1 h 20 °C Ah C8 h 25 °C Ah 1.80 1.77 1.75 1.67 1.75 2 OPzV 100* 3 OPzV 150* 4 OPzV 200 5 OPzV 250 6 OPzV 300 121 182 243 304 364 107 161 214 268 322 96 144 192 240 288 71 107 143 179 215 5 OPzV 350 6 OPzV 420 7 OPzV 490 447 529 610 388 459 530 342 405 468 6 OPzV 600 7 OPzV 700* 8 OPzV 800 9 OPzV 900* 10 OPzV 1000 11 OPzV 1100* 12 OPzV 1200 729 858 970 1,090 1,200 1,320 1,440 630 740 840 945 1,045 1,145 1,245 11 OPzV 1375* 12 OPzV 1500 13 OPzV 1625* 14 OPzV 1750* 15 OPzV 1875* 16 OPzV 2000 17 OPzV 2125* 18 OPzV 2250* 19 OPzV 2375* 20 OPzV 2500 22 OPzV 2750* 24 OPzV 3000 26 OPzV 3250* 1,570 1,710 1,890 2,070 2,170 2,300 2,480 2,610 2,740 2,870 3,210 3,470 3,650 1,375 1,495 1,660 1,810 1,900 2,015 2,170 2,290 2,405 2,520 2,805 3,035 3,210 Ue V/cell Ri 1) mV Ik 2) kA Length (L) mm Width (W) mm Height (H) mm Weight filled kg 120 180 240 300 360 1.65 1.15 0.89 0.73 0.63 1.30 1.86 2.40 2.91 3.39 105 105 105 126 147 208 208 208 208 208 420 420 420 420 420 12.4 17.1 19.4 23.3 27.4 254 302 350 440 521 601 0.68 0.58 0.52 3.14 3.64 4.12 126 147 168 208 208 208 535 535 535 31.4 36.9 42.4 564 663 750 840 933 1,020 1,113 417 492 559 616 691 748 822 718 840 952 1,072 1,192 1,304 1,416 0.46 0.36 0.32 0.34 0.28 0.28 0.24 4.63 5.81 6.54 6.29 7.50 7.56 8.63 147 215 215 215 215 215 215 208 193 193 235 235 277 277 710 710 710 710 710 710 710 51.0 61.9 68.8 77.0 83.9 92.2 99.2 1,209 1,317 1,461 1,590 1,677 1,779 1,911 2,016 2,121 2,223 2,466 2,670 2,832 839 927 1,040 1,125 1,191 1,265 1,358 1,433 1,507 1,581 1,740 1,887 2,014 1,576 1,704 1,880 2,056 2,160 2,288 2,464 2,600 2,728 2,864 3,192 3,456 3,640 0.27 0.23 0.18 0.17 0.16 0.15 0.14 0.13 0.12 0.12 0.11 0.10 0.10 7.86 9.18 11.91 12.63 13.25 13.94 15.32 16.03 16.70 17.37 18.43 19.76 21.02 215 215 215 215 215 215 215 215 215 215 215 215 215 277 277 400 400 400 400 490 490 490 490 580 580 580 855 855 815 815 815 815 815 815 815 815 815 815 815 108.2 116.5 131.4 141.2 147.9 156.2 173.6 181.4 189.6 197.8 205.7 222.0 235.1 1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-21 * Special type based on DIN 40742 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 3. Terminal positions 2 OPzV 100 to 6 OPzV 600 7 OPzV 700 to 12 OPzV 1500 13 OPzV 1625 to 16 OPzV 2000 17 OPzV 2125 to 26 OPzV 3250 Technical Specification for BAE Secura OPzV Negative electrode Separation Electrolyte Container and lid Valve Pole-bushing Kind of pole Connectors Connector screw Kind of protection Horizontal operation 5. Charging IU-characteristic Float current Boost charge Charging time up to 92 % 6. Discharge characteristics Reference temperature Initial capacity Depth of discharge (DOD) Deep discharges 7. Maintenance Every 6 months Every 12 months 8. Operational data Classification acc. to EUROBAT Service life Maintenance-free IEC 60896-21 cycles Self-discharge Battery temperature Deep discharge recovery Standard Tests according to Safety standard, ventilation Transport BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany tubular-plate with woven polyester gauntlet and solid grids in a corrosion-resistant PbCaSn-alloy grid-plate in PbCaSn-alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l, fixed as GEL by fumed silica high impact ABS (Acrylonitrile-Butadiene-Styrene), grey coloured (colour may vary slightly from given image), UL-94 rating: HB; on request also in UL-94 rating: V-0 valve with flame arrestor, opening pressure approx. 120 mbar 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2; on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to VBG 4 Please use BAE special type OPzV “horizontal”. The construction and production of this type is adapted to the horizontal operation. Imax without limitation U = 2.25 V/cell ± 1 %, between 10 °C and 45 °C (50 °F and 113 °F) in the monthly average, DU/DT = -0.003 V/cell per K below 10 °C (50 °F) 20 - 30 mA/100 Ah C10 U = 2.33 to 2.40 V/cell, time limited 6 h with 1.5 x I10 initial current, 2.25 V/cell, 50 % C10 discharged 20 °C (68 °F) according to IEC 60896-21: 95 % at the 1st cycle, 100 % at the 5th cycle normally up to 80 % more than 80 % DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided check battery voltage, pilot cell voltages, temperatures record battery and cell voltages and temperatures 12 years and longer - long life 20 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) no topping up during life >1,500 approx. 2 % per month at 20 °C (68 °F) -20 °C to 45 °C (-4 °F to 113 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) short time 45 °C to 55 °C (113 °F to 131 °F) very good DIN 40742 (except * marked cells) IEC 60896-21, -22 EN 50272-2, Ventilation requirements are reduced to 20 % compared to those for vented batteries of the same capacity. Batteries are not subject to ADR (road transport), if the conditions of Special Provisions 598 and 238 (Chapter 3.3) are observed. BAE cells/batteries are conform to the IMDG-Code, therefore these products are no dangerous goods on sea transport. Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 12/2012 4804068 Technical details may be subject to alterations. 4. Design Positive electrode BAE Secura OGiV BLOCK Technical Specification for Stationary VRLA-GEL-Block Batteries 1. Application BAE Secura OGiV BLOCK batteries belong to the highest EUROBAT classification for maintenance-free lead-acid batteries: >12 years long life. In applications with high requirements of operational safety and autonomy times of 15 min to several hours, BAE Secura OGiV Blocks are the right choice. They are used as reserve power in telecommunications, radio relay systems, switching stations of utilities, emergency light equipment and uninterrupted power supplies. 2. Types, capacities, dimensions, weights Type C10 h 20 °C Ah C5 h 20 °C Ah C3 h C1 h C30 min C10 min 20 °C 20 °C 20 °C 20 °C Ah Ah Ah Ah C8 h 25 °C Ah 1.80 1.79 1.78 1.74 1.70 1.60 1.75 12 V 1 OGiV 25 12 V 2 OGiV 50 12 V 3 OGiV 75 12 V 4 OGiV 100 12 V 5 OGiV 125 12 V 6 OGiV 150 26 52 78 105 131 157 24 48 72 96 121 145 22 45 67 90 112 135 18 36 55 73 92 110 15 31 47 62 78 94 11 22 34 45 57 68 6 V 7 OGiV 175 6 V 8 OGiV 200 6 V 9 OGiV 225 6 V 10 OGiV 250 6 V 11 OGiV 275 6 V 12 OGiV 300 183 210 236 262 288 315 169 193 217 242 266 290 157 180 202 225 247 269 128 147 165 184 203 221 110 125 141 156 172 187 2 V 24 OGiV 600 2 V 30 OGiV 750 2 V 36 OGiV 900 630 787 945 580 725 870 540 675 807 442 553 664 376 470 563 Ue V/cell Ri 1) mV Ik 2) kA Length (L) mm Width Height Weight (W) (H) mm mm kg 26 52 79 104 131 157 17.96 9.70 6.77 5.27 4.38 3.75 0.71 1.32 1.90 2.44 2.93 3.43 272 272 272 272 380 380 205 205 205 205 205 205 385 385 385 385 385 385 35.0 44.0 53.0 62.0 84.0 93.0 79 89 100 110 121 131 184 210 236 263 289 316 1.66 1.49 1.37 1.26 1.18 1.10 3.86 4.31 4.69 5.08 5.46 5.82 272 272 380 380 380 380 205 205 205 205 205 205 385 385 385 385 385 385 53.0 57.0 73.0 78.0 81.0 85.0 269 333 395 632 790 944 0.16 0.13 0.12 12.91 15.39 17.63 205 205 205 272 380 380 385 385 385 57.0 78.0 85.0 1, 2) Internal resistance Ri and short circuit current Ik from IEC 60896-21 Height (H) is the maximum height between container bottom and top of the bolts in assembled condition. All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 6. 3. Terminal positions 12 V 1 OGiV 25 to 12 V 6 OGiV 150 6 V 7 OGiV 175 to 6 V 12 OGiV 300 2 V 24 OGiV 600 to 2 V 36 OGiV 900 Technical Specification for BAE Secura OGiV BLOCK Blocks with blind cells Valve Pole-bushing Kind of pole Connectors Connector screw Kind of protection Horizontal operation 5. Charging IU-characteristic Float current Boost charge Charging time up to 92 % 6. Discharge characteristics Reference temperature Initial capacity Depth of discharge (DOD) Deep discharges 7. Maintenance Every 6 months Every 12 months 8. Operational data Classification according to EUROBAT Service life Maintenance-free IEC 60896-21 cycles Self-discharge Battery temperature Standard Tests according to Safety standard, ventilation Transport BAE Batterien GmbH Wilhelminenhofstraße 69/70 12459 Berlin Germany grid-plate with circular bars in a corrosion-resistant PbCaSn-alloy grid-plate in PbCaSn-alloy with long-life expander material microporous separator sulphuric acid with a density of 1.24 kg/l, fixed as GEL by fumed silica high impact SAN (Styrol-Acrylic-Nitrile), grey coloured (colour may vary slightly from given image), UL-94 rating: HB on request also in ABS (Acrylonitrile-Butadiene-Styrene), UL-94 rating: V-0 4 V, 6 V, 8 V, 10 V one valve per cell with flame arrestor, opening pressure approx. 120 mbar 100 % gas- and electrolyte-tight, sliding, plastic coated “Panzerpol” M10 brass insertion flexible insulated copper cables with cross-section of 25, 35, 50, 70, 95 or 120 mm2, on request: insulated solid copper connectors with cross-section 90, 150 or 300 mm2 M10, steel, insulated, with measuring point IP 25 regarding EN 60529, touch protected according to VBG 4 Please use BAE special type OGiV “horizontal”. The construction and production of this type is adapted to the horizontal operation. Imax without limitation U = 2.25 V/cell ± 1 %, between 10 °C and 45 °C (50 °F and 113 °F) in the monthly average, DU/DT = -0.003 V/cell per K below 10 °C (50 °F) 20 - 30 mA/100 Ah C10 U = 2.33 to 2.40 V/cell, time limited 6 h with 1.5 x I10 initial current, 2.25 V/cell, 50 % C10 discharged 20 °C (68 °F) according to IEC 60896-21: 95 % at the 1st cycle, 100 % at the 5th cycle normally up to 80 % more than 80 % DOD or discharges beyond final discharge voltages (dependent on discharge current) have to be avoided check battery voltage, pilot block voltages, temperatures record battery and block voltages and temperatures 12 years and longer - long life 15 years in stand-by operation, float at 20 °C to 25 °C (68 °F to 77 °F) no topping-up during life >800 approx. 2 % per month at 20 °C (68 °F) -20 °C to 45 °C (-4 °F to 113 °F) recommended 10 °C to 30 °C (50 °F to 86 °F) short time 45 °C to 55 °C (113 °F to 131 °F) dimensions according to DIN 40737-3 IEC 60896-21, -22 EN 50272-2, Ventilation requirements are reduced to 20 % compared to those for vented batteries of the same capacity. Batteries are not subject to ADR (road transport), if the conditions of Special Provisions 598 and 238 (Chapter 3.3) are observed. BAE cells/batteries are conform to the IMDG-Code, therefore these products are no dangerous goods on sea transport. Tel.: +49 (0)30 53001-661 Fax: +49 (0)30 53001-667 E-Mail: [email protected] www.bae-berlin.de 12/2012 4804037 Technical details may be subject to alterations. 4. Design Positive electrode Negative electrode Separation Electrolyte Container and lid