18/4/2018
Setting up Logix5000 - FACTORY I/O
Setting up a Logix5000 PLC

Requirements
Allen-Bradley Edition or Ultimate Edition
Compatible [../../../manual/drivers/ab-logix5000/] Logix5000 PLC with Ethernet connection
RSLogix 5000

Sample Project
Assembling with a CompactLogix [../sample-logix5000/]
This tutorial gives you a step-by-step instructions on how to use a CompactLogix to control FACTORY I/O. Although
this guide exempli es with a CompactLogix, the same steps apply to a ControlLogix PLC.
Setting up communication between PC and PLC
1. Connect the PLC to the network.
2. Assign an IP address to the PLC.

To complete this step you should refer to the CompactLogix Controllers User Manual 1769-UM011
[http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1769-um011_-en-p.pdf#page=29],
which describes methods to assign an IP address to the controller.
3. Start RSLinx and open the driver con guration dialog by selecting Communications > Con gure Drivers from
the menu.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
1/7
18/4/2018
Setting up Logix5000 - FACTORY I/O
4. Add an EtherNet/IP driver.
5. You should now be able to nd the controller under the newly added driver.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
2/7
18/4/2018
Setting up Logix5000 - FACTORY I/O
Connecting FACTORY I/O to the PLC
1. In FACTORY I/O click on FILE > Driver Con guration to open the Driver Window.
2. Select Allen-Bradley Logix5000 from the driver drop-down list.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
3/7
18/4/2018
Setting up Logix5000 - FACTORY I/O
3. Open the driver Con guration Panel by clicking on CONFIGURATION.
4. Insert the controller's IP address into the Host eld. On this panel, you can also de ne how many I/O Points to
use, as well as the controller's tags they reference.

Each I/O point name (e.g. BOOL_IN_0) represents an existent PLC tag. It is de ned by setting a Pre x (1) and an Offset
(2) index which will be added to the pre x for each point created (e.g. BOOL_IN_3). Count de nes the number of I/O
points to use for each data type. You may choose any pre x you wish, as long as each I/O point has a matching tag
de ned on the PLC.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
4/7
18/4/2018
Setting up Logix5000 - FACTORY I/O
See Logix5000 Con guration [../../../manual/drivers/ab-logix5000/#con guration].
5. Press Esc to return to the Driver Window. Now, click on CONNECT to connect to the PLC. A successful
connection is indicated by a green icon next to the selected driver, as well as next to the driver name displayed
on the status bar.
When connected to a PLC, non-existent tags or tags with an error are grayed out. Hover the mouse cursor over
a grayed out point to get relevant information about the error.
Creating Tags in RSLogix 5000
1. Open a project in RSLogix 5000.
2. Right-click on Controller Tags and select Edit Tags.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
5/7
18/4/2018
Setting up Logix5000 - FACTORY I/O
3. Add a new tag with BOOL_IN_0 as name, and BOOL as a data type. Continue adding tags until each one has a
matching input I/O point in FACTORY I/O.
A fast way to complete this step is to copy and paste the previously added tag. RSLogix will automatically
increment the index.
4. Now repeat the same process and add BOOL_OUT_0 up to BOOL_OUT_15. These will match the output I/O
points of FACTORY I/O.
5. Select Communications > Download to send the new program to the PLC.
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
6/7
18/4/2018
https://factoryio.com/docs/tutorials/allen-bradley/setting-up-logix5000/
Setting up Logix5000 - FACTORY I/O
7/7