Centrifugal Upblast & Sidewall Exhaust Models CUBE, CUE, CWB, CW and USGF • General Clean Air • Restaurant Grease • High Wind • Seismic • Smoke Control • Contaminants Performance data now included. November 2018 Models CUE, CUBE, CW, CWB, USGF Centrifugal Exhaust Fans Roof Upblast and Sidewall Table of Contents Vari-Green Options: Model Comparison . . . . . . . . . . . . . . . . . . . . . 3 Vari-Green® Motor . . . . . . . . . . . . . . . . . 10 Standard Construction Features . . . . . . . . . .4-5 Vari-Green® Controls . . . . . . . . . . . . . . . 11 Applications: Vari-Green® Drive . . . . . . . . . . . . . . . . . . 12 General Clean Air . . . . . . . . . . . . . . . . . . . 6 Options and Accessories . . . . . . . . . . . . .13-14 Restaurant Grease . . . . . . . . . . . . . . . . . . 6 Typical Installations . . . . . . . . . . . . . . . . . .15-16 Heavy Grease . . . . . . . . . . . . . . . . . . . . . . 6 Performance and Dimensions: Emergency Smoke Control . . . . . . . . . . . . 7 Model Number Code . . . . . . . . . . . . . . . 17 Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Performance Pages. . . . . . . . . . . . . . .18-49 High Wind & Hurricane . . . . . . . . . . . . . . . 8 Typical Specifications . . . . . . . . . . . . . . . .50-55 Severe Duty Roof Curbs . . . . . . . . . . . . . . 9 Quick Build Program . . . . . . . . . . . . . . . . . . . 56 Our Commitment. . . . . . . . . . . . . . . . . . . . . . 56 Modes CUE, CUBE, CW, CWB, and USGF meet CE (Conformité Européenne). • CUBE, CUE, CWB, and CW models are Listed for Electrical (UL/cUL 705) File no. E40001 • CUBE, CWB, USGF and models CUE and CW sizes 099 and larger are Listed for Grease Removal (UL/cUL 762) File no. MH11745 • CUBE and USGF models are Listed for Emergency Smoke Control Systems (UL/cUL Listed for 500˚F (260˚C) for 4 hours and 1,000˚F (538˚C) for 15 minutes) File no. MH17511 Note: UL/cUL is optional and must be specified Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded from Emergency Smoke Control. Greenheck Fan Corporation certifies that the Model CUBE, CUE, CWB, CW and USGF shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for Model CUBE, CUE, CWB, CW and USGF, are shown on pages 18-49. Enjoy Greenheck’s extraordinary service, before, during and after the sale. Greenheck offers added value to our wide selection of top performing, energy-efficient products by providing several unique Greenheck service programs. • Our Quick Delivery Program ensures shipment of our in-stock products within 24 hours of placing your order. Our Quick Build made-to-order products can be produced in 1-3-5-10-15 or 25-day production cycles, depending upon their complexity. • Greenheck’s free Computer Aided Product Selection program (CAPS), rated by many as the best in the industry, helps you conveniently and efficiently select the right products for the challenge at hand. • Greenheck has been Green for a long time! Our energy-saving products and ongoing corporate commitment to sustainability can help you qualify for LEED credits. • Our 3D service allows you to download, at no charge, easy-to-use AutoDesk® Revit® 3D drawings for many of our ventilation products. Find out more about these special Greenheck services at greenheck.com 2 Models CUE, CUBE, CW, CWB, USGF Centrifugal Exhaust Fans Roof Upblast and Sidewall Model Comparison Maximum Static Pressure (in. wg) Mixed Flow 9 9 9 9 9 Belt 9 9 9 9 9 9 9 9 9 Propeller/Axial Seismic Certification High Temp (above 200°F ) High Wind (150 mph) Smoke Control (UL) Grease (UL 762) Recirculate Reversible 9 9 9 9 9 9 9 9 9 9 9 9 9 99 9 9 9 9 9 9 Performance Maximum Volume (cfm) 9 Supply Wall Hanging Base/Floor Roof Curb 9 9 9 9 9 9 Centrifugal USGF 9 9 9 9 9 9 Impeller Type Direct CWB 9 9 9 9 9 9 Spark Resistant CUBE 9 Contaminated Air CW 9 9 9 9 9 Drive Type Application General/Clean Air CUE Indoor Outdoor Model Airflow Exhaust Mounting Ceiling Mounted Location 14,700 3 6,400 3 30,000 5 12,450 2.75 6,800 3.25 When you buy a Greenheck roof upblast or sidewall exhaust fan, you’ll receive a fan with the industry’s best performance and durability for general clean air, restaurant grease, smoke control, light contaminants, seismic, high wind, and hurricane applications. Both roof upblast and sidewall configurations are specifically designed to discharge air directly away from the mounting surface. • Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory and all models are licensed to bear the AMCA Sound and Air Performance seal. • UL/cUL Listed for Electrical, Grease and Smoke Control. • Greenheck subjects these products to extensive life testing, assuring you the fans will provide many years of reliable performance. LEED information Greenheck became one of the first manufacturers in the Air Movement and Control industry to join the LEED/green movement when they joined the United States Green Building Council (USGBC) in 2005. Greenheck has been actively researching qualification requirements for our products to meet LEED credits and prerequisites. The Vari-Green® motor significantly helps qualification efforts for the Energy and Atmosphere credits and prerequisites; specifically credit one, Optimize Energy Performance and prerequisite two, Minimum Energy Performance. 3 Standard Construction Features Standard Construction Features 1 2 3 9 Wheel An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized to generate high-efficiency and minimal sound. Wheel cones are carefully matched to the venturi for maximum efficiency. Each wheel is statically and dynamically balanced for long life and quiet operation. 9 9 *NonStick, Steel Vibration Isolation True vibration isolators consist of two independent studs separated by a neoprene (rubber) center. Reduces vibration and noise transfer between drive system and fan housing. (No metal to metal contact. Factory-mounted ground wire used to ground system). 9 9 9 NEMA-1 switch is factory-mounted and wiring is provided from the motor as standard (other switches are available). All wiring and electrical components comply with the National Electric Code (NEC) and are either UL/cUL Listed or Recognized. 9 9 Disconnect Switch NEMA-3R switch is factory-mounted and wired as standard. All wiring and electrical components comply with the National Electric Code (NEC) and are either UL/cUL Listed or Recognized. 9 4 Bearings 100% factory tested and designed specifically for air handling applications with a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours). 9 9 9 5 Fan Shaft Precisely sized, ground and polished so the first critical speed is at least 25% over the maximum operating speed. Where the shaft makes contact with bearings, close tolerances result in longer bearing life. 9 9 9 6 Drive Assembly Belts, pulleys and keys are oversized 150% of driven horsepower. Machined cast pulleys are adjustable for final system balancing. Belts are static-free and oil-resistant. 9 9 9 7 Motor Cover Constructed of aluminum. Attached with stainless steel fasteners for easy removal and access to the motor compartment and drive assembly. 9 9 *Steel 8 Stainless Steel Fasteners Allow easy removal and access to the motor compartment and drive assembly. 9 9 9 9 Windband One-piece, heavy-gauge aluminum with a rolled bead for extra strength directs exhaust air away from the mounting surface. 9 9 *Steel 10 Motor Carefully matched to the fan load and is mounted out of the airstream. 9 9 9 11 Motor Cooling Tube Cooling fins located on top of fan wheel draw outside air through a large breather tube directly into the motor compartment. Positive motor cooling with fresh air results in maximum motor life. 9 9 9 12 Internal Supports Heavy-gauge supports provide additional strength to withstand winds of 150 mph and supports motor and drives. 9 9 9 13 Leakproof Construction One-piece windband is continuously welded to the curb cap and drain trough for leakproof protection on models CUE, USGF and CUBE sizes 99 through 300 and all sizes with UL/cUL 762. 9 9 9 14 Curb Cap with Mounting Holes One-piece for a weather-tight fit. Constructed of aluminum with an integral deep spun venturi. Aluminum curb cap has pre-punched mounting holes to ensure correct attachment to the roof. 9 9 *Steel 15 Drain Trough Allows for one-point drainage of water, grease and other residues. 9 16 Galvanized Mounting Plate Allows mounting and sealing to the wall prior to mounting the entire unit. The remainder of the unit is attached to the mounting plate to eliminate positioning and fastening problems associated with mounting a heavy sidewall unit to a wall. 9 17 Galvanized Birdscreen Rigid wire protects the fan discharge from birds and small objects. Standard on all sidewall fan models. 9 18 Nameplate Permanent stamped aluminum nameplate for exact model and serial number identification. 9 9 For easy internal electrical wiring in applications. (Not available on UL 762 rated fans per NFPA 96). 9 9 Not Internal Conduit Shown Chase *Differences from the standard construction feature. 4 CUE CW USGF CUBE CWB 9 9 9 9 9 Standard Construction Features 5 6 7 4 8 3 9 10 2 11 1 12 16 17 13 15 14 Models CW & CWB Models CUBE and CUE Standard Construction Features - Continued 19 Dual Drives CUE CW USGF CUBE CWB 9 Oversized 150%, adjustable, static-free and oil-resistant. Not Hinged Curb Allows maintenance personnel to gain access to wheel and ductwork for regular Shown Base with Cables inspection and cleaning by utilizing the hinged curb base with cables. 20 Clean-Out Port TM 9 Allows the entire centrifugal wheel to be easily cleaned through a 4-inch diameter hole on outside of the fan windband. Meets NFPA 96 standard. 9 9 21 Permatector Coating Typically used for applications that require corrosion resistance in indoor and outdoor environments. 22 Lifting Points Various lifting points located on the drive frame and bearing plate. 9 9 9 19 3 22 20 18 21 Model USGF 5 Applications Restaurant and High Grease Clean Air Applications Models CUE, CUBE, CW and CWB These spun aluminum fans are specifically designed for roof mounted or wall mounted applications. General clean or lightly contaminated exhaust air can be discharged directly upward, away from the roof surface or discharged out and away from building walls. • Most advanced motor cooling of any fan in its class. • One-piece windband, continuously welded to the curb cap, ensures leak-proof construction for the life of the fan. • Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory and all models are licensed to bear the AMCA Sound and Air Performance seal. • Greenheck subjects these products to extensive life testing, assuring you the fans will provide many years of reliable performance. Restaurant and Grease Applications Models CUE, CUBE, CW and CWB When you choose a Greenheck fan, you have selected a fan with the industry’s best performance and durability for restaurant and grease applications. Spun aluminum exhaust fans, models CUBE, CWB and models CUE and CW sizes 099 and larger, are specifically designed for use in restaurant applications to discharge air directly away from the mounting surface. • Most advanced motor cooling of any fan in its class. • One-piece windband, continuously welded to the curb cap, ensures leak-proof construction for the life of the fan. • UL/cUL 762 Listed for exhausting restaurant grease exhaust. Ultimate Steel Grease Fan for Heavy Grease Applications Model USGF Fan model USGF is the industry’s best for performance and durability for heavy grease applications. This spun steel exhaust fan is specifically designed to remove large amounts of grease and/or contaminants associated with solid fuel cooking and discharge the air directly away from the mounting surface. • Only spun steel fan in the industry. • Withstands the most severe cleaning conditions. • Most advanced motor cooling of any grease fan. Capable of continuously handling 400°F (204°C) airstream temperatures. • UL/cUL 762 Listed for restaurant grease exhaust. • Only kitchen-specific exhaust fan to meet Miami-Dade County Test protocols for Large Missile Impact Test. Refer to page 17 for size chart. 6 Applications Emergency Smoke and Seismic Emergency Smoke Control - CUBE, USGF When you buy a Greenheck model CUBE or USGF with the smoke control option, you receive a fan with the industry’s best performance and durability for smoke control applications (as found in emergency smoke control systems). Note: Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded for Emergency Smoke Control. Refer to page 17 for size chart. Seismic - CUE, CUBE, CW and CWB • UL/cUL Listed for 500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes. • Half the weight of traditional smoke control fans, ideal choice for roof load concerns. • Low profile, height is less than half of traditional smoke control fans, maximum of 481⁄8 inches (1334 mm) from curb cap to top of fan. • Multiple applications, capable of exhausting general clean air and satisfying emergency smoke control regulations. With changes in building codes and standards more equipment is being required to be seismically certified in areas of the country not commonly thought of as being in seismically active zones. The International Building Code (IBC) is designed to provide model code regulations that safeguard public health and safety in all U.S. communities. With this code, the standards are intended to improve the performance and design of non-structural systems subject to seismic events. The State of California, one of the most active seismic areas in the United States, has the Office of Statewide Health Planning and Development ((OSHP (OSHPD). OSHPD regulates the design and construction healthcare facilities to ensure they are safe and of h o capable of providing services to the public after c a seismic event. OSHPD developed their own u unique certification process to incorporate the IBC and ASCE testing standards to ensure equipment a rremains operable after a seismic event. Protocols designed for seismic standards: Seismic Testing Criteria All Greenheck seismically certified models have been tested using the most severe seismic event that is found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Because our testing is performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor, it allows Greenheck seismically certified fans to be used anywhere in the United States under any conditions. California OSHPD Test Protocols The California Office of Statewide Health Planning and Development (OSHPD) requires all certified models be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces than they will see during a seismic event. By subjecting Greenheck model CUE, CUBE, CW and CWB fans to this type of testing ensures the fans will operate without problems after a seismic event. OSHPD Certification The OSHPD certification numbers and supporting documents can be viewed on OSHPD’s website and ensures that the fan has been subjected to and passed rigorous testing standards. 7 Applications High Wind and Hurricane High Wind and Hurricane CUE, CUBE, CW, CWB and USGF Greenheck is leading the High Wind Standard for roof top fans and ventilators. Forceful winds are the cause of most hurricane damage. While forceful winds are not the only problem, wind-borne debris can also cause detrimental effects to objects and structures. High winds product extreme forces on buildings and structures. By analyzing calculations, computer simulations, actual testing, and other standards— Greenheck developed the High Wind Standard. Atlantic, Gulf and Pacific history of major hurricane tracks. Protocols designed to protect against wind-borne debris and severe wind loads: Structural Performance Load A static load that is 1.5 times the design load (195 pounds per square foot pressure) is applied both positive and negative to simulate wind force loads in each direction. Structural Performance per Dade County Protocol TAS-202 (ASTM E-330). Large Missile Impact Test Large Missile Impact Testing is required when objects are located 30 feet or less from the ground. The test is per Dade County Protocol TAS-201. The test unit is impacted three times with a piece of lumber (2 in. x 4 in. x 6 ft.) weighing approximately nine pounds and traveling at 34 mph. This simulates wind-borne debris striking the fan. Miami-Dade NOA Numbers The certifications can be viewed on the Miami-Dade County website. Models CUE, CUBE, CW, CWB and USGF are the first upblast aluminum/steel fans in the industry that have received a Miami-Dade NOA for high wind (150 mph) and hurricane zones. Texas Department of Insurance The certifications can be viewed on the Texas Department of Insurance Windstorm website. Certified Independent Third-Party Testing Each of the Greenheck models have been subjected to extensive testing procedures. The CUE, CUBE, CW, CWB and USGF have been certified by an independent third-party to the ASTM E-330 Static Pressure Difference Standard, Florida Building Code Test Protocols TAS-202 Static Pressure Difference and TAS-201 Large Missile Impact. All tests are video taped for documentation of test method and results. Large missile impact test on a model USGF fan. 8 Applications Severe Duty Roof Curbs for High Wind and Hurricane High wind and severe duty roof curbs are available on CUE, CUBE and USGF models with high wind certification. The severe duty roof curb models can ship separately to allow for final finishing of the roof prior to the fan arrival and installation. Available Heights 1 inch (25 mm) Insulation Flashing Flange GPF for flat roofs Curbs are used for high wind/seismic applications. Fully formed on three sides with a single, fully welded seam when dimension (L+Wx2) <118 inches (2,997 mm). Larger sizes are a fully welded assembly. 9 5 inches 8 to 42 (127 mm) (203 to 1067) GPFHL for heavy load applications Curb construction is intended to support compression loads exceeding 1,000 pounds (454 kg). GPFHL is mounted directly to the roof deck structure. The roofing material is brought to the vertical surface and sealed to the flashing flange. Additional standard construction features include 14-gauge galvanized steel and internal vertical support members. 9 5 inches 12 to 24 (127 mm) (305 to 610) Description GPFHD for supporting heavy load equipment For severe duty, high wind and seismic applications. The double thick flashing flange provides an extremely durable surface to secure the curb to the building structure. The roofing material is brought to the vertical surface and sealed to the flashing flange. Additional standard construction features include 12-gauge galvanized steel and internal vertical support members. 9 Inches (mm) Double Thick 12 to 24 5 inches (305 to 610) (127 mm) 9 Vari-Green® Motor Options Models CUE/CW Features Greenheck’s electronically commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energyefficiency into one single low maintenance unit and is the industry’s first fully controllable motor. When combined with Greenheck’s CUE and CW fans, all the CFM and static pressure ranges of a belt drive can be attained with the benefits of a direct drive. 1. Dial on Motor Control - a potentiometer (dial on motor control) is mounted on the motor for easy speed adjustment for system balance. Simply turn the dial. There are no belts and pulleys to adjust. 2. Control Wire Inputs - the motor accepts a 0-10V DC signal from Building Automated Systems or other controls to adjust motor speed. 50/60 HZ Motor Information HP 1/10 1/6 1/4 1/2 1/2 3/4 3/4 1 1 2 RPM 1725 1725 1725 1725 2500 1725 2200 1725 1725 1725 Volts 115 115/230 115/230 115/230 115/230 115/230 115/230 115/230 115/208-230 208-230 Phase Single Single Single Single Single Single Single Single Single Single FLA 1.5 3.1 3.9 6.2 6.5 10.1 11.3 12.4 12.0 / 6.0 12.0 Enclosure TENV TENV ODP ODP ODP ODP ODP ODP TEFC TEFC 1 2 Comparisons: Belt, Direct Drive with PSC and Direct Drive with Vari-Green Motor Turndown Comparison Benefits • The motor can attain up to 85% efficiency and reduce energy consumption. • Watt savings of 30-70% depending on RPM. Note: As motor speed is turned down, efficiency stays high as compared to an AC motor which decreases dramatically. • Operates cooler than a standard AC motor at lower • • • • • RPMs. A cooler motor has longer motor life and reduces energy consumption. 80% usable RPM turndown versus 30%, see Motor Turndown Comparison chart at right. CUE and CW fans with Vari-Green motors can provide all the CFM and static pressure ranges of a comparable belt drive. Maintenance costs are reduced as there are no belts or bearings to replace and no pulleys to adjust. Direct drive fans are often preferred where maintenance access is difficult. Provides a solution for demand-controlled ventilation applications. Vari-Green Advantages • Initial cost is similar to a belt drive 500 INPUT POWER (WATTS) Operates on AC power that’s converted to DC— providing a more efficient motor operation as compared to an AC operation. 50% 75% 100% 600 CUE-121 with PSC 400 Not recommended 300 EEnergy S Savings CUBE-121 Single Phase* 200 CUE-121 with 100 0 0 350 FAN SPEED (RPM) 1750 * CUBE is a belt driven fan The length of each curve indicates the practical turndown range. Data is for 1/2 hp motors with load of 0.35 Bhp at full speed Constant Volume Life Cycle Analysis Three Year Cost Comparison $2,000 1,750 1,500 1,250 1,000 750 500 250 $0 CUBE121 CUE121-A5 CUE121-VG Initial Cost Maintenance cost over three years Operating cost over three years • No maintenance, no belts, pulleys or bearings Analysis is based on operating costs for a period of three years where the fans operate continuously at 1725 rpm, 24/7, with an energy rate of $0.10/kWh. Maintenance on the CUBE-121 is estimated at $65/yr. • Easy RPM adjustment Note: Example is based on a relative cost. Use and installation variables may produce different results. • Lower operating cost 10 Vari-Green® Control Options Vari-Green® Controls Transformer - Provides 24V power from the existing line voltage at the fan to the VariGreen motor and controls. Dual voltage primary (120/240V) transformer provided with the fan. Remote Dial - Allows for remote, manual airflow adjustments. Wall plate with dial may be mounted in a standard 2x4 inch electrical junction box. Two Speed Control with Integral Transformer Control allows motor rpm to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset down to low for energy conservation. Constant Pressure Control – Indoor - Control Vari-Green motor via static (variable volume) or velocity (constant CFM) pressure on the inlet or outlet side of the fan. Optional, one or two, duct or room probes for use in: • Multifamily structures - Apartments, condos, hotels; dryers, residential kitchens and bathrooms. • Institutional facilities - Schools, prisons, multistory office buildings; bathrooms. Contact [email protected] for more information. Daily Operating Comparison: Variable Volume and Constant Volume % of Operation Applications requiring constant pressure or variable volume can utilize CUE or CW fans with Vari-Green motors and Vari-Green Variable Volume controls. Demand Operating Cost Analysis Variable Volume vs. Constant Volume control ventilation $ 2,000 systems reduce the amount of energy used 1,750 by decreasing the 1,500 speed of the fan when 1,250 demand is low. This in 1,000 turn lessens the amount 750 of conditioned air 500 exhausted and further 250 reduces total operating $0 costs associated with Constant Variable Volume air conditioning and Volume heating in multistoried Heating Cost Cooling Cost buildings such as Fan Operating Cost hotels, multifamily complexes, institutional Example of potential savings based on a northeast city in facilities, and high rise the USA using Vari-Green commercial buildings. components for Variable Volume. The Vari-Green constant pressure control is preprogrammed and easy to install for applications that include venting dryers, bathrooms, residential type kitchen space or industrial process exhaust. Hypothetical (Hotel Bathroom) Variable Volume - Load Shape 100 80$$$$$$$$$$$$$$$$$$$$$$$$ 60$$$$$$$$$$$$$$$$$$$$$$$$ 40$$$$$$$$$$$$$$$$$$$$$$$$ 20$$$$$$$$$$$$$$$$$$$$$$$$ 0%$$$$$$$$$$$$$$$$$$$$$$$$ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Series 1 Demand-controlled ventilation offers significant energy savings by exhausting only the necessary amount of air throughout the day. % of Operation Demand Control Ventilation for Multistory Buildings Constant Volume - Load Shape 100 80 60 40 20 0% 1 2 3 4 Series 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Note: A standard VFD compatible motor can also function within a Variable Volume system. Constant Pressure Control – Outdoor - Control a Vari-Green motor via static pressure on the inlet side of the fan. Includes one duct probe and transducer for use in: • Multifamily structures - Apartments, condos, hotels; residential kitchen, dryer facilities and bathrooms. • Institutional facilities - Schools, prisons, multistory. Air Quality – VOC - Control a Vari-Green motor via changes in volatile organic compounds (VOC’s). VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 PPM equivalent. • Institutional facilities – Schools, court houses, hospitals; bathrooms, waiting rooms, cafeterias. • Commercial buildings – Office spaces, conference rooms, bathrooms, break rooms. Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 32 to 120°F and 0 to 100% relative humidity. • Multifamily structures - Apartments, condos, hotels; bathrooms, utility rooms. • Commercial buildings - Office buildings, office space, conference rooms, utility rooms, bathrooms. 11 Vari-Green® Drive Greenheck’s Vari-Green Drive is a factory mounted, wired, and programmed variable frequency drive. Specifically designed for use in air handling applications, the Vari-Green drive expands variable volume operation and simplistic speed adjustment to three phase applications. Features The Vari-Green Drive is available in two models, VGD-100 and VGD-100+. Both of these models are constructed with a NEMA-4X rated enclosure to ensure a long life operating under outdoor environmental conditions. Every Vari-Green Drive is compatible with all Vari-Green controls or any industry control sending a 0-10V signal; model VGD-100+ is also equipped with Modbus/BACnet communications allowing for seamless integration to building management systems. VGD-100 VGD-100+ 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 Features Analog Input (0-10V, 4-20mA) Damper Actuator Output (24VDC) Control Voltage Output (24VDC) LED Indication Lights (3) Relay Output (2) Digital Input - Dry (2) Digital Input - Voltage (2) RS-485 (Modbus/BACnet) Bluetooth/Smart Device Interface On-Board PID Control Optional Pressure Transducer Benefits • Variable volume control from the factory on larger fan sizes where Vari-Green motors are not available. • R3 filtering and short leads mitigates harmonics. • Eliminate compatibility issues as the motor and drive are factory matched. • Induction motors are reliable, efficient and readily available if replacements are needed. • Quick start-up and simplistic commissioning as each drive comes pre-programmed and installed from the factory. Vari-Green® Drive App 6:23 AM The Vari-Green Drive model VGD-100+ features a smart phone companion app available for download from the app store. Manually control and monitor the drive from the app as well as access any advanced programming features. For more information about the companion app and its capabilities, reference the VGD-100+ Quick Start Guide located on greenheck.com and the documentation section of the app. 12 89% 6:23 AM 89% Options and Accessories The following chart shows which options and accessories are available on Greenheck’s roof upblast and sidewall exhaust fans. Options and Accessories Sidewall Mount Roof Curbs Curb Extensions Curb Seal Windband Extension Hinged Curb Cap Hinged Base Tie-Down Points Drain Connection Grease Trap Grease Trap with Absorbent Material Clean-Out Port Birdscreen Non-Stick Wheel Disconnect Switches Dampers Speed Controllers Motor Starters UL 705 UL 762 UL Emergency Smoke Control Systems Coatings CUE CUBE 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 CW std. CWB USGF std. 9 9 std. 9 std. 9 9 9 9 std. std. std. 9 9 9 9 9 9 9 9 9 9 std. 9 9 9 9 std. 9 9 9 9 9 Sidewall Mount — Allows for a horizontal discharge with a square mounting base, models CUE and CUBE. Curb Seal — Foam or high temperature seal between fan and curb to assure proper sealing when attached to a curb. Windband Extension — Aluminum tube raising the fan discharge height. Hinged Curb Cap Kit — The hinged curb cap allows the entire fan to swing open to allow maintenance personnel access to the wheel and ductwork for regular inspection and cleaning. Hinged curb cap kit is an option on all upblast models. Hinged Base — Available on sizes up to 480, allows for easy maintenance. Hinge and restraining cables are factory-mounted to a sub-base attached directly to curb without additional height added. Mounted hinged base with cables standard on all USGF fans. Tie-Down Points — Four brackets located on the windband for securing the fan in heavy wind applications. Drain Connection — Allows for single-point drainage of grease, water or other residues. Roof Curbs — Wide variety of roof curbs are available for mounting the fan to the roof, including: vented, flanged, pitched and soundabsorbing. For more information on severe duty curbs refer to the information on page 9. Grease Trap — Polypropylene trap designed to collect grease residue to avoid drainage onto roof surface. Curb Extensions — Mounts between roof curb Grease Trap with Absorbent Material — Same as above and fan for additional height from roof top. Vented Curb Extensions — Mounts between roof curb and roof mounted fan to meet NFPA requirements of 40-inch (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. with an absorbent material to collect grease residue for easy disposal. 13 Options and Accessories Clean-Out Port — Patented UL/cUL 705 — Models CUE, CUBE, CW and CWB, removable plug allows for easy spray or steam cleaning of wheel through the windband. Available on select models. may be UL Listed for Electrical. CUBE for Smoke Control comes standard with UL 705. UL/cUL 762 — Models CUBE, CWB and CUE and CW sizes 099 and larger, may be Listed for Grease Removal. Model USGF comes standard with UL 762. Birdscreen — Galvanized or aluminum rigid wire to protect the fan discharge from birds or small objects. Galvanized is standard on CW and CWB models. Non-Stick Aluminum Wheel — Patented coating helps prevent wheel imbalance in heavy grease applications and allows buildup on wheel to be easily removed. Disconnect Switches — Assorted NEMA rated switches are available for positive electrical shutoff and safety, including: dust-tight, rainproof and corrosion-resistant. Dampers — Designed to prevent outside air from entering back into the building when fan is off. Includes backdraft and motorized dampers. (Not available with UL/cUL 762 or USGF fans). Speed Controllers — Available for use with shaded pole and permanent split capacitor open motors on direct drive fans. They provide an economical means of system balancing. Motor Starters — The fundamental function of a motor starter is to protect the motor from damage that can occur from overheating. With a Greenheck motor starter you will be provided with the best motor protection available. Specific model components may include: SmartStart™ technology, physical interface, overload protection, disconnect, magnetic contactor, NEMA-1 or NEMA-3R steel enclosures and pre-engineered easy system integration. For complete information on specific Greenheck Motor Starter models refer to greenheck.com, Motor Starters webpage. 14 UL/cUL Emergency Smoke Control — Models CUBE and USGF may be Listed for Emergency Smoke Control. Note: Model sizes CUBE-099, 161XP, 240XP, 300HP & 300XP are excluded from Emergency Smoke Control. Coatings – Wide variety of coatings and colors are available for decorative to protective applications. Primer is applied at the factory to allow PRIMER for final finish in the field. Not available on model USGF. Permatector™ is our standard coating PERMATECTORTM on steel fans and is typically used for applications that require corrosion resistance in indoor and outdoor environments. Hi-Pro Polyester is resistant to salt water, chemical fumes and moisture in more corrosive atmospheres. Typically used for applications that require superior chemical resistance, excellent abrasion and outdoor UV protection. This coating exceeds protective qualities of Air Dried Heresite and Air Dry Phenolic. Customers can choose from seven standard decorative colors or color match any color. Baked Enamel Decorative Coatings are heat cured enamels applied as electrostatic powders. Customers can choose from seven standard decorative colors or color match any color. Note: Colors are subject to change. See Performance Coatings for Commercial & Industrial Fans catalog for more details. Typical Installations by Application General Clean Air/Fume Hood (Non Grease) All CUE, CUBE, CW and CWB exhaust fans are designed for applications ranging from clean air to contaminated air. A typical installation is shown. When roofing materials extend to the top of the curb, roof curbs should be 1½-inches (¾-inch on a side) less than the unit curb cap to allow for roofing and flashing. • For recommended duct size, damper size and roof opening dimensions, refer to the performance data pages. • Installation must include a means for inspecting, cleaning and servicing the exhaust fan. Factory Wired Motor to Junction Box Wall Damper Wiring by Others Damper 8 in. minimum (203 mm) Mounting Bolt Hole Circle Recommended Duct and Damper Size Recommended Wall Opening Roof Deck Recommended Duct and Damper Size Wiring by others Factory Wired Motor to Junction Box Recommended Roof Opening Models CUE and CUBE Models CW and CWB Emergency Smoke Control • Installation must include a means for inspecting, The CUBE with smoke option and the USGF are specifically designed for Emergency Smoke Control applications. These fans are UL/cUL Listed for Electrical and Power Ventilators for Smoke Control Systems for 500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes. • Exhaust fans used in emergency smoke • Due to the varying airstreams encountered in cleaning and servicing the exhaust fan. applications must have external wiring. (Wiring must not be installed in the airstream). Factory Installed Heat Baffle NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube commercial ventilation, system designers must be aware of national, state, and local codes and guidelines governing these installations. Local code authorities should be consulted before proceeding with any ventilation project. • When roofing materials extend to the top of the curb, roof curbs should be 1½-inches (¾-inch on a side) less than the unit curb cap to allow for roofing and flashing. • For recommended duct size, damper size and Liquid Tight Flexible Conduit by Others Minimum 8 in. (203 mm) Roof Deck roof opening dimensions, refer to the performance data pages. Recommended Roof Opening Models CUBE and USGF 15 Typical Installations by Application Commercial Kitchen (Grease) Models CUBE, CWB, USGF and models CUE and CW sizes 099 and larger, are designed to meet restaurant and food service applications. These fans are UL/cUL Listed for Grease Removal and have been tested under high temperature [400°F (204°C)] and abnormal flare-up [600°F (316°C)] conditions. Wall Mounting Bolt Hole Circle Recommended Wall Opening Welded Duct by Others • Due to high temperatures and grease-laden airstreams in commercial kitchen ventilation, system designers must be aware of governing codes and guidelines. The National Fire Protection Association (NFPA) is the primary source which governs many codes for commercial kitchen ventilation. Selected information from NFPA 96 is shown below. Local code authorities should be consulted before proceeding with any kitchen ventilation project. • Exhaust fans used in kitchen ventilation applications must have external wiring. (Wiring must not be installed in the airstream). • Installation must include a means for inspecting, cleaning and servicing the exhaust fan. Greenheck offers a Hinged Curb Cap option for upblast exhaust fans. The Hinged Base is standard on model USGF. • No dampers are to be installed in the system. Note: • The typical installations shown on these two pages are recommendations based on national codes. Local authority may supersede these recommendations. Models CW & CWB • Drawing shows NEMA-1 Standard, NEMA-3R is optional. External Wiring Liquid Tight Flexible Conduit by Others NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube (Optional) Minimum 40 in. (1016 mm) Discharge Height Grease Trap Welded Duct by others. Minimum of 18 in. (457 mm) above roof deck per NFPA NEMA-3R Disconnect factory wired from motor to disconnect through the breather tube (Optional) Minimum 40 in. (1016 mm) Discharge Height Vented Curb Extension 18 in. (457 mm) Minimum Height External Wiring Liquid Tight Flexible Conduit By Others 18 in. (457 mm) Minimum Height Welded Duct by others. Minimum of 18 in. (457 mm) above roof deck per NFPA Grease Trap Roof Deck Roof Deck Recommended Roof Opening Recommended Roof Opening Models CUE & CUBE Vented Installation 16 Models CUE & CUBE Non-Vented Installation External Wiring Liquid Tight Flexible Conduit by Others Model Number Code Performance & Dimensions Quick Reference Motor Cover Curb Caps Material Thickness Windband Page Index 060 18 • 0.051 0.051 0.051 070 19 • (1.3) (1.3) (1.3) 080 20 • 090 21 • 0.051 0.051 0.064 (1.3) (1.3) (1.6) 095 22 • Model CUBE Size CWB CUE CW CUBE Smoke USGF Option The Model number system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model number is determined by the size and performance. CUBE - 240 HP - VG/5/A X Fan Size 099 23 • 101 24 • x 101HP 25 • x 121 26 • x Wheel Pressure Level 131 27 • x HP - High-Pressure XP - Extended High-Pressure 140 28 141 28 • 140HP 29 141HP 29 • 160 30 161 30 • 160HP 31 161HP 31 • 160XP 32 161XP 32 180 180HP 200 x (Belt Drive Only) x 0.040 (1.0) x 0.064 (1.6) x x x x x Configuration CUE - Belt Drive Roof or Wall Mounted CUBE - Direct Drive Roof or Wall Mounted CW - Belt Drive Wall Mounted CW - Direct Drive Wall Mounted USGF - Belt Drive Roof Mounted x 33 • x x 34 x x 35 CUE only 36 x x x x 200HP 36 220 37 x 220HP 38 x 240 39 CUE only 39 40 CUE only 40 240HP 060 through 480 240XP 41 300 42 CUE only 42 300HP 43 CUE only 43 VG = (Direct Drive Only) 0.064 (1.6) USGF 0.051 (1.3) Motor HP 0.040 (1.0) 0.064 (1.6) x x 0.064 0.051 0.064 (1.6) (1.3) (1.6) 0.080 0.051 0.064 44 45 x 360HP 46 x 360XP 47 = = = = 1/4 1/3 1/2 3/4 (Belt Drive Only) 10 = 1 15 = 1½ 20 = 2 30 = 3 50 = 5 75 = 7½ (2.0) (1.3) (1.6) 0.080 0.064 0.080 (2.0) (1.6) (2.0) A = 1725 B = 1140 C = 860 420 48 x 0.080 0.064 0.100 480 49 x (2.0) (1.6) (2.5) (Direct Drive Only) D = 1550 E = 1050 G = 1300 50 HZ Motor RPM CUBE only 360 4 3 5 7 60 HZ Motor RPM x 300XP Vari-Green® (Direct Drive Only) International (See CAPS for performance) K = 950 RPM L = 1290 RPM J = 1425 RPM X = UL 705 F = UL Smoke Control Systems G = UL 762 • Vari-Green option available on direct drive models 17 Roof Upblast/Sidewall Exhaust Size-060: CUE • CW 0.6 195⁄8 Direct Drive RPM (498) RPM (Direct) RPM (Vari-Green) Density 0.075 lb/ft Density 1.2 lb/ft 140 E-1050 RPM 120 40 06 0.3 0.2 CUE CW 0.1 20 0 0- D THE LEFT OF 60 0.4 DO NO TS ELE CT TO 1¾ (44) (432) 80 Static Pressure (in. wg) (289) 100 Static Pressure (Pa) 113⁄8 VG VG-1725 RPM 0- (343) 06 D-1550 RPM *131⁄2 17 THIS SYST EM C URVE 0.5 G-1300 RPM 06 0- G 06 0- E 0.0 0 50 100 150 113⁄4 200 250 (298) 195⁄8 (498) 14 ⁄4 3 0 100 200 300 400 3 (375) Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *131⁄2 (343) Motor HP Direct Fan RPM 0 0.05 0.1 133 0.01 1.7 165 0.01 2.9 197 0.02 4.3 219 0.028 5.4 113 0.01 1.7 148 0.01 2.6 183 0.02 3.9 207 0.028 5 94 0.01 1.7 134 0.01 2.5 169 0.02 3.9 194 0.028 5.1 CUE CW ^Approximate Weight 29 (13) Damper Size 8 x 8 (203 x 203) Roof/Wall Opening 10½ x 10½ (267 x 267) Static Pressure in Inches wg 0.125 0.15 0.2 0.25 26 (12) 8 x 8 (203 x 203) 8½ x 8½ (216 X 216) 0.3 0.35 0.375 107 0.02 4.0 146 0.029 5.3 85 0.02 4.0 137 0.029 5.4 118 0.029 5.5 060 VG1/10 CFM BHP Sones CFM G-1/100 1300 BHP Sones CFM D-1/60 1550 BHP Sones CFM 1725 BHP Sones E-1/200 1050 81 0.01 1.7 126 0.01 2.5 164 0.02 3.9 188 0.028 5.2 65 0.01 1.7 117 0.01 2.5 158 0.02 3.9 183 0.028 5.2 96 0.01 2.5 143 0.02 4.0 172 0.028 5.2 70 0.01 2.5 128 0.02 4.0 159 0.028 5.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 18 300 Volume (cfm) 500 Roof Upblast/Sidewall Exhaust Size-070: CUE • CW 195⁄8 0.6 Direct Drive RPM (498) RPM (Direct) RPM (Vari-Green) Density 0.075 lb/ft Density 1.2 lb/ft 140 E-1050 RPM 120 1¾ (44) (432) 80 60 40 0.4 0.3 0.2 CUE 0.1 CW 20 0 0.0 07 0-V G 07 0-D THE LEFT OF (289) 100 070 -G DO NO TS ELE CT T O VG-1725 RPM Static Pressure (Pa) (343) 113⁄8 Static Pressure (in. wg) D-1550 RPM *131⁄2 17 THIS S YSTEM CURVE 0.5 G-1300 RPM 0 070 -E 100 200 300 400 500 Volume (cfm) 11 ⁄4 3 (298) 195⁄8 0 (498) 143⁄4 200 400 600 800 Volume (m 3/hr) (375) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *131⁄2 (343) Motor HP Direct Fan RPM 0 0.05 0.1 250 0.01 2.7 309 0.01 4.1 369 0.02 5.6 411 0.032 6.8 224 0.01 2.1 288 0.01 3.8 351 0.02 5.4 395 0.032 6.7 193 0.01 1.7 267 0.02 3.4 333 0.03 5.2 379 0.033 6.7 CUE CW ^Approximate Weight 29 (13) Damper Size 8 x 8 (203 x 203) Roof/Wall Opening 10½ x 10½ (267 x 267) Static Pressure in Inches wg 0.125 0.15 0.2 0.25 26 (12) 8 x 8 (203 x 203) 8½ x 8½ (216 X 216) 0.3 0.35 0.375 234 0.03 4.5 305 0.036 6.2 187 0.02 4.1 289 0.035 6.1 160 0.02 3.9 258 0.035 5.9 070 CFM VG- E-1/100 1050 BHP 1/10 Sones G-1/60 D-1/30 CFM BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 1300 171 0.01 1.4 255 0.02 3.3 325 0.03 5.2 371 0.034 6.6 143 0.01 1.1 241 0.02 3.2 316 0.03 5.1 363 0.035 6.6 205 0.02 2.8 293 0.03 4.9 346 0.036 6.5 152 0.01 2.5 269 0.03 4.7 326 0.036 6.4 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 19 Roof Upblast/Sidewall Exhaust Size-080: CUE • CW 220 E-1050 RPM 200 G-1300 RPM 180 D-1550 RPM 1¾ (44) 19 (483) CUE CW 120 100 80 60 0.5 0.4 0.3 0.2 40 20 0 0- VG 08 0- D THE LEFT OF (292) 140 08 08 0- G TO 111⁄2 0.6 NO TS ELE CT VG-1725 RPM 0.7 0.1 08 0- E DO (340) RPM (Direct) RPM (Vari-Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft 0.8 160 Static Pressure (Pa) *133⁄8 0.9 THIS SYST EM C URVE Direct Drive RPM Static Pressure (in. wg) 221⁄4 (565) 0.0 0 100 200 300 15 400 500 600 Volume (cfm) (381) 22 ⁄4 1 (565) 177⁄8 0 100 200 300 400 500 600 3 700 800 900 1000 1100 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 325 0.01 3.8 403 0.02 5.4 480 0.04 7.3 534 0.05 8.4 265 0.01 3.7 356 0.03 5.4 441 0.04 7.3 500 0.06 8.5 247 0.02 3.6 343 0.03 5.4 431 0.04 7.3 491 0.06 8.5 230 0.02 3.7 330 0.03 5.4 421 0.04 7.3 481 0.06 8.5 239 0.03 5.6 352 0.05 7.2 423 0.07 8.6 173 0.03 5.9 314 0.05 7.3 390 0.07 8.5 235 0.05 7.5 333 0.07 8.7 257 0.07 8.7 080 VG1/10 CFM BHP Sones CFM G-1/30 1300 BHP Sones CFM D-1/20 1550 BHP Sones CFM 1725 BHP Sones E-1/40 1050 189 0.02 3.9 302 0.03 5.4 400 0.05 7.3 463 0.06 8.6 133 0.02 4.2 272 0.03 5.5 376 0.05 7.2 444 0.06 8.6 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 20 Roof Upblast/Sidewall Exhaust Size-090: CUE • CW 1.0 221⁄4 Direct Drive RPM RPM (Direct) RPM (Vari-Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft (565) G-1300 RPM 100 0.4 CUE 50 0.2 0 0.0 09 0- VG 09 0- D THE LEFT OF 1¾ (44) 19 (483) 0.6 NO TS ELE CT T O (292) 150 Static Pressure (in. wg) VG-1725 RPM Static Pressure (Pa) *13 ⁄8 111⁄2 0.8 D-1550 RPM 3 (340) 200 THIS S YSTEM CURVE E-1050 RPM 0-G 09 0-E DO CW 09 0 200 400 15 600 800 1000 1200 Volume (cfm) (381) 221⁄4 (565) 17 ⁄8 7 0 500 1000 1500 2000 3 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 549 0.02 4.0 680 0.04 5.4 811 0.06 7.6 903 0.08 8.8 470 0.02 3.9 616 0.04 5.4 757 0.07 7.5 854 0.09 8.8 451 0.02 3.9 600 0.04 5.4 744 0.07 7.5 842 0.09 8.8 429 0.03 4.0 584 0.04 5.4 731 0.07 7.5 830 0.09 8.8 204 0.03 4.5 479 0.05 5.5 651 0.08 7.4 758 0.1 8.7 391 0.05 5.6 604 0.08 7.4 722 0.11 8.7 501 0.09 7.4 652 0.12 8.8 347 0.08 7.9 553 0.12 8.9 090 VG1/10 CFM BHP Sones CFM G-1/30 1300 BHP Sones CFM D-1/20 1550 BHP Sones CFM 1725 BHP Sones E-1/40 1050 381 0.03 4.1 553 0.05 5.4 704 0.07 7.5 806 0.1 8.8 306 0.03 4.2 517 0.05 5.5 677 0.08 7.5 782 0.1 8.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 21 Roof Upblast/Sidewall Exhaust Size-095: CUE • CW 1.0 221⁄4 Direct Drive RPM (565) 0.8 (292) 1¾ (44) (483) 150 100 5- 0.6 0.4 CUE 50 0.2 0 0.0 09 THIS S VG-1725 RPM 111⁄2 09 D 095 -G 095 -E DO CW VG 5- NO TS ELE CT T O TH E LEF T OF (340) Static Pressure (in. wg) *13 ⁄8 Static Pressure (Pa) D-1550 RPM 3 19 200 YSTEM G-1300 RPM RPM (Direct) RPM (Vari-Green) 3 Density 0.075 lb/ft 3 Density 1.2 lb/ft CURVE E-1050 RPM 0 200 400 15 600 800 1000 1200 Volume (cfm) (381) 221⁄4 (565) 17 ⁄8 7 0 500 1000 1500 2000 3 Volume (m /hr) (454) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *133⁄8 (340) Motor HP Direct Fan RPM CUE CW ^Approximate Weight 40 (18) Damper Size 10 x 10 (254 x 254) Roof/Wall Opening 12½ x 12½ (318 x 318) 40 (18) 10 x 10 (254 x 254) 10½ x 10½ (267 X 267) 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 711 0.03 5.4 880 0.06 7.6 1049 0.1 9.6 1167 0.14 11.3 603 0.04 4.5 797 0.07 6.9 983 0.11 9.4 1108 0.15 11.1 570 0.04 4.5 774 0.07 6.7 964 0.11 9.3 1093 0.15 11.0 536 0.04 4.5 750 0.07 6.6 944 0.11 9.2 1077 0.15 11.0 265 0.03 4.6 587 0.07 6.4 816 0.12 8.4 967 0.16 10.2 484 0.07 6.4 747 0.12 8.3 905 0.17 9.9 199 0.05 6.8 616 0.12 8.1 802 0.17 9.8 442 0.11 7.8 680 0.17 9.6 095 VG1/6 CFM BHP Sones CFM G-1/12 1300 BHP Sones CFM D-1/8 1550 BHP Sones CFM 1725 BHP Sones E-1/30 1050 468 0.04 4.4 696 0.07 6.5 905 0.11 8.9 1041 0.16 10.8 381 0.04 4.5 641 0.07 6.4 861 0.12 8.6 1005 0.16 10.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 22 Roof Upblast/Sidewall Exhaust Size-099: CUBE • CUE • CWB • CW 247⁄8 Direct Drive RPM (632) 250 1.0 099-A CUR VE B-1140 RPM 100 SYS TEM 0.6 099-B 0.4 099-C CUBE • CUE 50 86 0.2 0 0.0 0 11 56 8 0 74 4 200 400 167⁄8 600 800 1000 1200 1400 Volume (cfm) (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 40 10 95 DO CWB • CW NO TS EL EC TT OT HE LEF TO FT HIS (483) Static Pressure (in. wg) 19 150 0.8 36 13 1¾ (44) 200 32 15 (441) 25 VG-1725 RPM 17 (718) 173⁄8 Static Pressure (Pa) A-1725 RPM *281⁄4 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP Density 0.075 lb/ft 3 Density 1.2 kg/m 3 HP 1.2 4 1/ 300 C-860 RPM Motor HP Direct Fan RPM 0 0.125 543 0.02 4.5 628 0.03 5.3 700 0.04 6.1 771 0.05 7.1 833 0.06 7.8 904 0.08 8.8 976 0.10 9.9 1047 0.13 10.8 1119 0.15 11.9 1191 0.19 13.0 1260 0.22 14.2 414 0.02 4.0 518 0.03 4.7 603 0.04 5.4 685 0.06 6.2 754 0.07 7.0 832 0.09 8.1 909 0.11 9.4 986 0.13 10.4 1062 0.16 11.4 1137 0.19 12.6 1209 0.23 13.8 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 0.875 1 1.125 099 744 VG1/4 C-1/8 860 958 1056 B-1/6 1140 1238 1/4 1336 1434 1532 1630 A-1/4 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 376 0.03 4.3 490 0.04 4.9 588 0.06 5.7 665 0.07 6.3 752 0.09 7.2 837 0.11 8.5 920 0.14 9.7 1001 0.17 10.9 1080 0.20 12.1 1156 0.23 13.4 MAXIMUM BHP AT A GIVEN RPM = (RPM/3099)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 2.846 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 464 0.06 5.3 565 0.07 5.9 668 0.09 6.7 760 0.12 7.6 848 0.14 8.8 935 0.17 10.0 1020 0.21 11.4 1100 0.24 12.9 408 0.07 5.5 559 0.09 6.4 674 0.12 7.3 776 0.14 8.3 868 0.18 9.4 956 0.21 10.8 1041 0.25 12.3 564 0.11 6.9 687 0.14 8.0 794 0.18 9.1 893 0.21 10.4 981 0.25 11.7 567 0.14 7.6 705 0.17 8.8 818 0.21 10.1 918 0.25 11.5 583 0.16 8.4 730 0.21 9.8 846 0.25 11.2 609 0.20 9.4 759 0.24 10.8 639 0.23 10.6 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 23 Roof Upblast/Sidewall Exhaust Size-101: CUBE • CUE • CWB • CW 247⁄8 1.4 Direct Drive RPM 4 1.2 FT HIS SY STE MC 0.4 CUBE • CUE 50 0.2 0 0.0 NO T 101-C CWB • CW TH EL EF TO 101-B TO 100 0.6 SE LE CT Static Pressure (Pa) (483) 150 0.8 48 14 1¾ (44) 200 11 4 0 86 0 DO 0 200 400 600 167⁄8 800 1000 1200 1400 1600 Volume (cfm) (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 2500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 20 0 25 17 166 17 ⁄8 (441) 1.0 UR VE 250 VG-1725 RPM 18 (718) Static Pressure (in. wg) *28 ⁄4 19 101-A A-1725 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 300 B-1140 RPM 3 H P C-860 RPM 1 3 1/ 1/ (632) Motor HP Direct Fan RPM 0 0.125 0.25 732 0.03 4.6 811 0.041 5.5 890 0.054 6.5 970 0.07 7.2 1066 0.092 8 1149 0.12 8.9 1233 0.14 10.3 1316 0.17 11.8 1413 0.22 12.7 1468 0.24 13.3 1549 0.28 14.3 625 0.035 2.1 717 0.047 4.2 807 0.061 6.2 897 0.078 7 1000 0.1 8 1089 0.13 8.9 1176 0.15 10.2 1264 0.19 11.5 1365 0.23 12.3 1422 0.26 12.9 1505 0.3 13.7 481 0.036 1.3 603 0.05 3.1 707 0.066 5.6 806 0.084 6.5 920 0.11 7.6 1016 0.13 8.6 1112 0.16 9.9 1206 0.2 11.3 1313 0.24 12 1373 0.27 12.5 1459 0.31 13.4 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 0.875 1 1.125 101 C-1/8 VG1/4 860 953 1046 B-1/6 1140 1252 1/4 1350 1448 1546 1660 A-1/4 1725 1/3 1820 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 577 0.065 5.4 707 0.085 6 834 0.11 6.9 940 0.14 8.1 1040 0.17 9.5 1139 0.2 10.9 1251 0.25 11.6 1315 0.28 12 1406 0.32 12.7 MAXIMUM BHP AT A GIVEN RPM = (RPM/3099)3 MAXIMUM RPM = 1820 TIP SPEED (ft/min) = RPM x 2.846 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 411 0.067 5.5 732 0.11 6.5 856 0.14 7.5 966 0.17 9 1072 0.21 10.5 1189 0.26 11.3 1255 0.29 11.7 1350 0.33 12.4 745 0.14 7 886 0.17 8.3 999 0.21 9.8 1125 0.26 10.8 1195 0.29 11.3 1293 0.34 12 763 0.17 8 915 0.21 9.3 1056 0.26 10.2 1129 0.29 10.8 1234 0.35 11.6 793 0.23 8.9 974 0.26 9.6 1062 0.29 10.2 1171 0.35 11.2 861 0.25 9.4 970 0.29 9.7 1106 0.35 10.6 900 0.33 10.1 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 24 Roof Upblast/Sidewall Exhaust Size-101HP: CUBE • CUE • CWB • CW 247⁄8 1/2 Direct Drive RPM (632) 2.5 500 (483) 200 THIS 1.5 1.0 CUBE • CUE 50 20 45 17 80 15 0.5 100 40 13 00 DO CWB • CW 00 22 LEF T OF 300 RPM (Belt) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 25 T HE 1¾ (44) 400 HP TO (441) 1/4 NO TS ELE CT Static Pressure (Pa) 17 ⁄8 3 2.0 HP HP 80 25 (718) Static Pressure (in. wg) *281⁄4 19 1/3 CURV E 600 SYST EM VG-2500 RPM 0 0.0 0 200 400 16 ⁄8 7 600 800 1000 Volume (cfm) (429) 247⁄8 0 (632) 193⁄4 500 1000 1500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Motor HP Belt Direct Fan RPM 0.5 0.625 335 0.067 6 419 0.088 6.8 491 0.11 7.8 560 0.14 8.9 627 0.17 10.3 688 0.2 12.1 761 0.24 13.9 812 0.28 14.1 860 0.32 14.4 977 0.44 15.9 1014 0.48 16.8 182 0.056 6.3 350 0.088 6.6 438 0.11 7.5 512 0.14 8.6 583 0.17 9.9 651 0.21 11.4 729 0.26 13.5 782 0.29 14.1 832 0.33 14.4 954 0.44 15.6 992 0.48 16.4 0.75 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE 58 (26) 53 (24) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 1 1.25 1.5 1.75 2 CWB CW 58 (26) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 2.25 2.5 101HP 1300 VG1/2 1420 1540 1/4 1660 1780 1900 2045 2150 1/3 2250 2500 1/2 2580 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 191 0.073 6.9 371 0.11 7.3 461 0.14 8.4 538 0.17 9.6 610 0.21 11 693 0.26 12.7 752 0.3 13.5 804 0.34 14.2 929 0.45 15.3 969 0.49 16 MAXIMUM BHP AT A GIVEN RPM = (RPM/3195)3 MAXIMUM RPM = 2580 TIP SPEED (ft/min) = RPM x 2.913 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 262 0.12 8.3 430 0.17 9.1 520 0.21 10.5 615 0.26 12.1 678 0.3 12.5 737 0.35 13.2 878 0.48 15 919 0.52 15.7 382 0.19 10.2 522 0.26 11.5 600 0.3 12 665 0.35 12.5 815 0.48 14.4 861 0.53 15.1 346 0.23 11.4 500 0.3 11.5 579 0.35 11.9 750 0.48 13.6 799 0.53 14.4 456 0.32 11.6 677 0.48 12.9 735 0.53 13.7 595 0.48 12.5 655 0.53 13.2 414 0.42 12.2 550 0.49 12.9 323 0.43 12.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 25 Roof Upblast/Sidewall Exhaust Size-121: CUBE • CUE • CWB • CW 247⁄8 1.8 Direct Drive RPM (632) (441) 121-C T CWB • CW 0.4 50 0 0.2 0.0 0 NO 68 400 600 DO 200 10 0 4 800 1000 1200 1400 1600 1800 2000 Volume (cfm) 167⁄8 (429) 247⁄8 0 (632) 19 ⁄4 3 500 1000 1500 2000 2500 3000 3500 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt 00 86 25 17 100 121-B 0.6 45 150 0.8 P 15 CUBE • CUE 200 1.0 H 50 12 40 11 (483) 250 1.2 3 10 14 1¾ (44) 19 300 SE LE CT TO VG-1725 RPM Static Pressure (in. wg) (718) 173⁄8 Static Pressure (Pa) *28 ⁄4 P 1/6 H A-1725 RPM 1 1/ CU RVE 1.4 121-A TH EL EF TO FT HIS SY STE M 350 B-1140 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 1.6 HP 1/4 400 2 1/ C-860 RPM Motor HP Direct Fan RPM 0 0.125 808 0.02 4.4 912 0.04 4.8 1015 0.05 5.3 1181 0.08 6.2 1346 0.11 7.4 1476 0.15 8.8 1665 0.21 11.1 1748 0.25 11.9 1824 0.28 12.8 1931 0.33 14.1 2037 0.39 15.6 669 0.03 4.4 789 0.04 5 905 0.05 5.7 1084 0.08 6.6 1261 0.12 7.9 1397 0.16 9.3 1595 0.22 11.6 1681 0.26 12.4 1760 0.29 13.4 1870 0.34 14.7 1979 0.40 16.1 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 66 (30) 64 (29) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 66 (30) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 1 1.25 1.5 121 684 VG1/2 772 C-1/8 860 1000 1/4 B-1/6 1140 1250 1410 1480 1/3 1545 1635 1/2 A-1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 630 0.043 5.1 781 0.06 5.6 993 0.09 6.8 1180 0.13 8.2 1323 0.17 9.9 1528 0.23 12.2 1617 0.27 13.1 1699 0.30 14 1811 0.36 15.2 1923 0.41 16.7 581 0.06 5.7 870 0.09 6.7 1091 0.13 8.2 1250 0.17 9.9 1463 0.24 12.5 1555 0.28 13.5 1639 0.31 14.5 1755 0.37 15.9 1869 0.43 17.3 MAXIMUM BHP AT A GIVEN RPM = (RPM/2199)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.419 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 691 0.09 6.7 981 0.14 8 1159 0.18 10 1398 0.25 12.6 1493 0.29 13.7 1580 0.32 14.7 1699 0.38 16.2 1816 0.44 17.9 833 0.14 8.1 1053 0.18 9.8 1315 0.26 12.7 1421 0.29 13.8 1518 0.33 14.8 1643 0.39 16.4 1763 0.45 18.2 916 0.18 9.8 1224 0.26 12.7 1338 0.30 13.8 1441 0.34 14.9 1577 0.40 16.6 1710 0.46 18.4 965 0.25 12.3 1132 0.30 13.6 1262 0.34 14.9 1424 0.41 16.7 1571 0.47 18.7 990 0.33 14.6 1226 0.40 16.5 1406 0.48 18.6 1176 0.46 18.4 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 26 Roof Upblast/Sidewall Exhaust Size-131: CUBE • CUE • CWB • CW 1.8 Direct Drive RPM P 2H 1/ 247⁄8 (632) 400 1.6 350 1.4 0.0 TH EL EF TO FT HIS SY STE M SE LE CT TO 0 DO T NO 0 0 0 86 0 65 0 500 1000 167⁄8 1500 2000 2500 Volume (cfm) (429) 247⁄8 0 (632) 193⁄4 500 1000 1500 2000 2500 3000 3500 4000 3 Volume (m /hr) (502) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *281⁄4 (718) Belt HP 0.2 3/4 50 CWB • CW 11 4 10 0 131-C 25 0.4 67 15 100 46 131-B 0.6 16 CUBE • CUE 150 0.8 05 13 (483) 200 1.0 35 14 1¾ (44) 19 250 1.2 17 (441) 300 Static Pressure (in. wg) VG-1725 RPM HP 1/4 (718) 173⁄8 Static Pressure (Pa) A-1725 RPM *28 ⁄4 HP 1/3 B-1140 RPM 1 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 131-A CU RVE C-860 RPM Motor HP Direct Fan RPM 0 0.125 892 0.03 6.2 1036 0.04 7.2 1180 0.06 8.5 1372 0.10 10.7 1564 0.14 12.5 1790 0.22 14.6 1968 0.29 15.7 2041 0.32 16.2 2149 0.37 17.0 2258 0.43 17.9 2366 0.50 18.8 724 0.03 6.0 895 0.05 7.0 1057 0.07 8.3 1267 0.11 10.5 1471 0.15 12.2 1709 0.23 14.3 1895 0.30 15.5 1970 0.33 15.9 2082 0.39 16.8 2194 0.45 17.6 2305 0.51 18.6 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 66 (30) 64 (29) 12 x 12 (305 x 305) 14½ x 14½ (368 x 368) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 CW 66 (30) 53 (24) 12 x 12 (305 x 305) 12½ x 12½ (318 X 318) 1 1.25 1.5 131 650 VG3/4 755 C-1/8 860 1/4 1000 B-1/6 1140 1305 1/3 1435 1488 1567 1/2 1646 A-1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 697 0.05 6.3 914 0.07 7.7 1158 0.11 10.0 1379 0.16 11.8 1629 0.24 13.9 1822 0.31 15.1 1900 0.35 15.7 2015 0.40 16.5 2130 0.46 17.4 2244 0.53 18.4 675 0.07 6.9 1016 0.12 9.2 1280 0.17 11.2 1547 0.25 13.5 1749 0.32 14.8 1829 0.36 15.4 1948 0.41 16.3 2066 0.47 17.2 2183 0.54 18.2 MAXIMUM BHP AT A GIVEN RPM = (RPM/2041)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.420 MAXIMUM MOTOR FRAME SIZE = 56 AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.28 801 0.11 8.3 1144 0.17 10.3 1458 0.26 13.0 1671 0.33 14.3 1756 0.37 15.0 1881 0.43 15.9 2002 0.49 16.9 2122 0.56 18.0 964 0.17 9.7 1340 0.26 12.0 1586 0.34 13.8 1679 0.38 14.5 1808 0.44 15.5 1935 0.50 16.5 2061 0.57 17.6 1201 0.26 11.5 1479 0.35 13.1 1580 0.39 13.9 1728 0.45 15.0 1865 0.51 16.1 1994 0.58 17.2 1198 0.33 11.9 1342 0.38 12.7 1527 0.45 13.8 1686 0.52 15.1 1838 0.60 16.4 1222 0.42 12.6 1458 0.51 14.0 1646 0.60 15.3 1365 0.57 14.1 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 27 Roof Upblast/Sidewall Exhaust Size-140: USGF Size-141: CUBE • CUE • CWB • CW 2.0 Direct Drive RPM 141 -A TH EL EF TO FT HIS SYS TEM CUR VE TO SE LE CT Static Pressure (in. wg) 12 11 40 10 86 0 NO T DO 95 15 100 CWB • CW 90 141-C 13 141-B 0.5 25 17 1.0 95 14 USGF-140 • CUBE • CUE (660) HP (559) 200 4 1/ 1¾ (44) 300 P 3H 1/ 193⁄8 (492) 1.5 Static Pressure (Pa) VG-1725 RPM P (756) 26 400 A-1725 RPM *29 ⁄4 22 2H 1/ B-1140 RPM RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP P 4H 3/ C-860 RPM 3 1 287⁄8 (733) 59 0 0 0.0 0 400 800 1200 1600 2000 2400 2800 3200 Volume (cfm) 193⁄8 (492) 287⁄8 0 (733) 22 ⁄8 1 1000 2000 3000 4000 5000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt Motor HP Direct Fan RPM 0 0.125 1069 0.04 5.0 1313 0.06 5.1 1558 0.11 7.3 2001 0.23 10.9 2065 0.25 11.3 2192 0.30 12.2 2518 0.45 14.9 2708 0.56 17.2 2808 0.63 18.7 2889 0.69 20.0 3124 0.87 26.0 851 0.04 4.5 1151 0.07 5.0 1427 0.12 7.5 1906 0.24 10.8 1973 0.26 11.3 2106 0.31 12.2 2445 0.47 14.7 2640 0.58 16.5 2743 0.64 17.8 2826 0.70 19.0 3066 0.88 23.0 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 84 (38) 90 (41) 125 (57) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 CWB CW 84 (38) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 1.50 1.75 140 / 141 590 VG3/4 or 1 725 1/4 C-1/8 860 1105 B-1/4 1140 1/3 1210 1/2 1390 1495 1550 3/4 1595 VG-1 1 A-1 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 917 0.07 4.4 1264 0.12 7.1 1793 0.25 10.6 1864 0.27 11.0 2006 0.32 11.7 2362 0.48 14.2 2565 0.60 16.3 2671 0.66 17.5 2757 0.72 18.5 3005 0.90 22.0 1034 0.12 6.5 1667 0.26 10.3 1745 0.28 10.7 1896 0.33 11.6 2271 0.50 13.2 2483 0.61 15.6 2594 0.68 17.7 2683 0.74 19.5 2936 0.92 24.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/1726)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1515 0.26 10.0 1605 0.29 10.3 1773 0.34 11.2 2174 0.51 12.9 2396 0.62 13.9 2509 0.69 14.9 2602 0.75 16.1 2865 0.94 24.0 998 0.23 9.6 1167 0.27 10.0 1443 0.34 10.9 1949 0.52 12.1 2202 0.64 12.5 2329 0.71 12.9 2430 0.77 13.3 2711 0.97 15.1 1643 0.51 11.0 1967 0.65 12.2 2110 0.72 12.5 2225 0.79 12.3 2539 0.99 13.4 1617 0.61 10.8 1823 0.70 11.6 1968 0.78 12.6 2339 1.00 14.3 1349 0.62 10.2 1568 0.71 11.6 2085 0.98 13.8 1704 0.91 13.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 28 Roof Upblast/Sidewall Exhaust Size-140HP: USGF Size-141HP: CUBE • CUE • CWB • CW 3.5 4H 3/ Direct Drive RPM 800 3.0 USGF-140HP • CUBE • CUE 141HP-A 1.5 1.0 18 16 05 65 5 5 0.5 895 D 0 0.0 0 200 400 600 800 193⁄8 1000 1200 1400 1600 1800 Volume (cfm) 28 ⁄8 7 (733) 0 500 1000 1500 2000 2500 3000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt 25 108 100 221⁄8 45 17 127 200 CWB • CW (492) 00 10 14 O 26 (660) 300 Static Pressure (in. wg) Static Pressure (Pa) (483) 400 2.0 HP 1¾ (44) 22 500 2 193⁄8 22 21 P 600 HP (756) 2.5 H 1/4 *293⁄4 1/3 700 1/ VG-2200 RPM (492) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P A-1725 RPM NO TS EL EC TT OT HE LEF TO F TH IS S YST EM CUR VE 287⁄8 (733) Motor HP Direct Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 84 (38) 90 (41) 125 (57) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB CW 84 (38) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 2.50 2.75 140HP / 141HP 895 VG3/4 1085 1/4 1275 1465 1/3 1605 A-1/2 1725 1/2 1845 1960 3/4 2035 2110 2200 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 331 0.06 5.7 625 0.11 7.5 833 0.17 11.0 1016 0.24 14.2 1146 0.31 15.3 1256 0.38 16.2 1363 0.46 17.1 1463 0.54 18.1 1528 0.60 19.0 1592 0.67 19.9 1669 0.75 21.0 377 0.10 9.5 700 0.17 10.5 920 0.26 13.5 1063 0.33 14.4 1178 0.40 15.4 1292 0.48 16.6 1399 0.57 17.8 1468 0.63 18.6 1536 0.70 19.4 1617 0.78 21.0 492 0.16 13.9 798 0.26 13.3 965 0.34 14.2 1098 0.42 15.0 1219 0.50 16.1 1330 0.59 17.4 1402 0.66 18.3 1473 0.72 19.2 1557 0.81 20.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/2285)3 MAXIMUM RPM = 2200 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 642 0.26 15.5 846 0.34 14.0 999 0.43 14.9 1137 0.52 16.0 1260 0.61 17.2 1335 0.68 18.1 1409 0.75 19.1 1496 0.84 20.0 704 0.34 15.3 879 0.43 14.7 1042 0.52 15.9 1176 0.62 17.1 1261 0.69 18.0 1341 0.77 19.0 1434 0.86 20.0 747 0.42 15.7 924 0.52 15.7 1086 0.63 17.0 1175 0.70 17.9 1262 0.78 18.8 1364 0.87 20.0 800 0.51 16.2 970 0.62 16.8 1077 0.70 17.7 1178 0.78 18.7 1284 0.88 19.9 854 0.62 17.0 965 0.69 17.5 1073 0.78 18.5 1200 0.89 19.7 826 0.67 17.9 965 0.77 18.3 1097 0.88 19.5 804 0.73 20.0 993 0.87 19.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 29 Roof Upblast/Sidewall Exhaust Size-160: USGF Size-161: CUBE • CUE • CWB • CW 287⁄8 2 Direct Drive RPM (733) 600 17 RV E CU EM ST SY HIS FT TO EF EL TH DO 0.0 TO 96 5 EC 100 0 65 11 86 0 EL CWB • CW 12 40 T Static Pressure (in. wg) Static Pressure (Pa) 0.5 NO 0 T 25 161-C USGF-160 • CUBE • CUE (660) 161-B 1.0 S 90 200 13 26 HP 1/2 (559) 300 1.5 HP 1/3 HP 1/4 1¾ (44) 400 2.0 HP 193⁄8 (492) 500 HP 3/4 VG-1725 RPM 1 A-1725 RPM (756) 22 HP B-1140 RPM *293⁄4 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m /2 11 C-860 RPM HP 161-A 2.5 73 0 1 2 3 4 5 Volume (cfm x 1000) 193⁄8 (492) 287⁄8 0 (733) 22 ⁄8 1 2 4 6 8 3 Volume (m /hr x 1000) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt Motor HP Direct Fan RPM CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 87 (39) 90 (41) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) 0 0.125 0.25 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 2098 0.13 8.1 2314 0.18 9.5 2472 0.22 10.7 2515 0.23 11 2774 0.31 12.4 3191 0.47 15 3277 0.51 15.7 3636 0.70 18.5 3737 0.76 19.1 3996 0.93 21 4959 1.77 30 1905 0.15 8 2143 0.20 9.2 2315 0.24 10.2 2362 0.26 10.6 2637 0.34 12 3072 0.51 14.6 3161 0.55 15.2 3532 0.74 18.1 3636 0.80 18.7 3901 0.97 21 4882 1.83 29 1669 0.15 7.8 1937 0.20 8.9 2126 0.25 9.9 2177 0.26 10.1 2477 0.35 11.5 2941 0.53 14.2 3035 0.57 14.8 3426 0.77 17.6 3534 0.84 18.3 3806 1.01 20 4806 1.88 29 1389 0.15 7.8 1708 0.20 8.8 1918 0.25 9.7 1974 0.26 9.9 2300 0.35 11.2 2796 0.53 13.8 2896 0.57 14.4 3301 0.78 17.2 3413 0.85 17.9 3698 1.03 19.7 4729 1.94 29 1770 0.49 12.5 1983 0.55 13.2 2583 0.78 15.8 2729 0.84 16.5 3078 1.04 18.4 4269 2.00 27 CWB CW 87 (39) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 1 1.5 160 / 161 730 VG3/4 or 1 805 1/4 C-1/4 860 875 1/3 965 1/2 1110 B-1/2 1140 3/4 1265 VG-1 1300 1 1390 VG-2 A-2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1396 0.19 8.7 1680 0.24 9.5 1744 0.26 9.7 2109 0.35 10.8 2641 0.54 13.5 2745 0.58 14.1 3172 0.79 16.8 3290 0.85 17.5 3584 1.04 19.3 4646 1.97 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/1365)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1365 0.24 9.7 1893 0.34 10.6 2475 0.53 13.1 2587 0.58 13.8 3036 0.79 16.5 3157 0.86 17.2 3464 1.04 19 4554 1.97 28 1584 0.33 10.6 2297 0.52 12.9 2421 0.57 13.5 2894 0.79 16.3 3022 0.86 17 3340 1.05 18.8 4463 1.98 27 2163 0.75 15.6 2357 0.82 16.3 2785 1.03 18 4070 2.01 27 2394 1.00 17.9 3855 1.99 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 30 Roof Upblast/Sidewall Exhaust Size-160HP: USGF Size-161HP: CUBE • CUE • CWB • CW 287⁄8 161HP-A Direct Drive RPM (733) B-1140 RPM 600 3/ 4 RV E CU EM ST SY IS TH FT E 1 10 140 65 CT LE DO 0.0 0 55 LE 1.0 0.5 0 13 4 12 OF 161HP-B TO Static Pressure (in. wg) 1.5 100 CWB • CW RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 35 15 Static Pressure (Pa) P USGF-160HP • CUBE • CUE (660) H 200 26 2 1/ (559) 300 HP 1/3 HP 1¾ (44) 400 2.0 1/4 193⁄8 (492) 22 500 HP TH VG-1725 RPM (756) HP 90 25 16 17 A-1725 RPM *293⁄4 1 2.5 0 NO T 82 SE 500 5 1000 1500 2000 2500 3000 Volume (cfm) 19 ⁄8 3 (492) 287⁄8 0 (733) 221⁄8 1000 2000 3000 4000 5000 3 Volume (m /hr) (562) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *293⁄4 (756) Belt Motor HP Direct Fan RPM 0.5 0.625 0.75 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 87 (39) 90 (41) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 0.875 1 1.25 1.5 1.75 CWB CW 87 (39) 90 (41) 15 x 15 (381 x 381) 15½ x 15½ (394 X 394) 2 2.25 160HP / 161HP 1/4 825 VG3/4 or 1 945 1065 B-1/3 1140 1/3 1165 1255 1/2 1340 3/4 1535 1550 1 1690 VG-1 A1 1/2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 889 0.12 6.1 1213 0.18 8.9 1487 0.25 11.1 1645 0.31 12.7 1697 0.32 12.9 1882 0.40 13.1 2053 0.48 14.2 2433 0.70 18.1 2461 0.72 18.3 2722 0.92 21 2787 0.97 22 1062 0.18 8.4 1377 0.26 10.7 1552 0.32 12.5 1608 0.33 12.8 1799 0.41 12.8 1975 0.49 13.8 2368 0.72 17.7 2398 0.74 17.9 2671 0.94 21 2736 0.99 21 1252 0.26 10.3 1444 0.32 12 1504 0.34 12.3 1715 0.42 12.5 1897 0.50 13.3 2301 0.73 17.3 2331 0.75 17.5 2611 0.95 20 2680 1.01 21 1093 0.26 9.7 1322 0.32 11.6 1395 0.34 11.8 1617 0.43 12 1816 0.51 12.9 2233 0.74 16.9 2264 0.76 17.1 2550 0.97 19.8 2620 1.03 21 MAXIMUM BHP AT A GIVEN RPM = (RPM/1660)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 1175 0.32 11 1252 0.34 11.2 1519 0.43 11.5 1724 0.52 12.4 2165 0.76 16.5 2197 0.78 16.7 2488 0.98 19.4 2560 1.04 20 1218 0.42 10.6 1513 0.52 11.3 2015 0.78 15.6 2051 0.80 15.9 2365 1.01 18.7 2439 1.07 19.4 1855 0.79 14.7 1892 0.81 15 2228 1.03 18 2310 1.10 18.7 1638 0.78 13.5 1683 0.81 13.8 2082 1.05 17.3 2167 1.11 18 1352 0.77 14.5 1899 1.05 16.1 2003 1.12 17.1 1664 1.03 15.1 1810 1.11 16 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 31 Roof Upblast/Sidewall Exhaust Size-160XP: USGF Size-161XP: CUBE 3.5 287⁄8 HP *293⁄4 (559) 26 USGF-160XP • CUBE (660) 300 0 URVE 05 F THIS 1.5 1.0 200 100 22 200 THE LEFT O 400 2.0 0.5 25 HP 5 175 0 155 0 DO 1¾ (44) 22 500 NO TS ELE CT T O Static Pressure (Pa) 19 ⁄8 (492) 2.5 Static Pressure (in. wg) 600 (756) RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 25 1 SYSTE MC 1/2 3.0 700 1/ 2 HP 800 3 1 3/4 (733) 0.0 0 400 800 1200 1600 2000 2400 2800 Volume (cfm) 0 500 1000 1500 2000 2500 3000 3500 4000 4500 3 Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 160XP / 161XP CFM 1550 BHP Sones CFM 1648 BHP 1/2 Sones CFM 1750 BHP Sones CFM 1880 BHP Sones CFM 1942 BHP 3/4 Sones CFM 2005 BHP Sones CFM 2138 BHP Sones 1 CFM 2205 BHP Sones CFM 2310 BHP Sones CFM 2432 BHP 11⁄2 Sones CFM 2525 BHP Sones 1 968 0.34 10.0 1157 0.42 11.1 1322 0.52 12.1 1515 0.7 13.7 1599 0.71 14.4 1684 0.77 15.0 1861 0.9 16.6 1946 1.01 17.5 2065 1.17 18.8 2206 1.36 21 2313 1.52 22 1.25 854 0.39 10.1 1116 0.49 11.4 1359 0.6 13.1 1456 0.7 14 1552 0.78 14.8 1743 1.0 16.4 1834 1.03 17.3 1974 1.18 18.7 2132 1.36 20 2241 1.52 22 1.5 726 0.43 10.6 1139 0.6 12.2 1271 0.68 13.2 1392 0.76 14.1 1611 0.9 15.9 1713 1.04 17 1865 1.2 18.5 2031 1.38 20 2155 1.54 22 CUBE ^Approximate Weight Damper Size Roof/Wall Opening USGF 87 (39) 131 (59) 16 x 16 (406 x 406) N/A 18½ x 18½ (470 x 470) Static Pressure in Inches wg 1.75 2 2.25 2.5 2.75 3 3.25 MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3 MAXIMUM RPM = 2525 TIP SPEED (ft/min) = RPM x 3.534 MAXIMUM MOTOR FRAME SIZE = 145T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72 744 0.5 11.8 984 0.63 12.4 1161 0.72 13.4 1451 0.9 15.4 1578 1.01 16.4 1741 1.18 18.1 1926 1.4 20 2056 1.56 22 777 0.63 13.2 1226 0.9 14.8 1395 0.99 15.8 1597 1.16 17.5 1804 1.38 19.6 1946 1.56 21 869 0.8 14.8 1127 0.92 15.5 1415 1.12 17 1660 1.35 19.1 1828 1.53 21 634 0.73 16.4 1134 1.04 16.9 1483 1.31 18.7 1676 1.5 20 644 0.83 18.2 1225 1.23 18.7 1487 1.45 20 826 1.07 19.8 1221 1.35 20 810 1.16 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 32 Roof Upblast/Sidewall Exhaust Size-180: CUBE • CUE • USGF CWB • CW 363⁄4 2.5 Direct Drive RPM 600 (933) HIS SY STE MC UR VE OF T 95 EF T TH EL TO SE LE CT Static Pressure (in. wg) 14 75 94 0 NO T 0 82 0 74 O 5 1 2 25 3 4 5 6 Volume (cfm x 1000) (635) 36 ⁄4 3 (933) 273⁄4 0 2 4 6 8 10 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Belt 60 10 0 13 85 0.0 40 86 D 0 11 11 Static Pressure (Pa) HP 180-C 0.5 CWB • CW P 1H USGF-180 • CUBE • CUE (762) HP 200 1.0 HP 30 180-B 1/4 (762) 1.5 3 1/ 1¾ (44) 400 3/4 (648) HP (727) 251⁄2 30 HP 2.0 1/2 *28 ⁄8 HP 2 1/ B-1140 RPM VG-1000 RPM 5 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 1 C-860 RPM Motor HP Direct Fan RPM 0 0.125 0.25 2815 0.22 9.2 3098 0.30 11.2 3249 0.34 12.3 3551 0.45 13.8 3778 0.54 15.1 4061 0.67 16.5 4307 0.80 17.6 4477 0.90 18.5 4817 1.12 21 5138 1.36 23 5648 1.80 28 2617 0.24 8.6 2916 0.32 10.4 3074 0.37 11.7 3389 0.47 13.5 3625 0.57 14.9 3919 0.70 16.2 4173 0.83 17.1 4348 0.93 17.9 4697 1.15 20 5026 1.39 23 5546 1.84 27 2448 0.26 8.1 2759 0.34 10 2922 0.39 11.1 3243 0.49 13.1 3486 0.59 14.7 3786 0.73 15.8 4045 0.86 16.5 4224 0.96 17.1 4578 1.19 19.5 4913 1.43 22 5443 1.89 27 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 126 (57) 142 (64) 190 (86) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 CWB CW 126 (57) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 1.75 2 180 1/4 VG3/4 or 1 745 820 1/3 C-1/2 860 1/2 940 1000 VG-1 3/4 1075 B-1 1140 1 VG-2 1185 1275 11⁄2 1360 2 1495 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1763 0.25 7.1 2257 0.34 9 2474 0.40 10.2 2879 0.52 12.4 3190 0.63 14.3 3554 0.78 15.5 3822 0.91 16.1 4005 1.01 16.5 4369 1.24 18.7 4710 1.49 21 5254 1.96 26 MAXIMUM BHP AT A GIVEN RPM = (RPM/1167)3 MAXIMUM RPM = 1495 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2363 0.50 11.2 2738 0.62 13.3 3141 0.78 14.7 3470 0.93 15.4 3703 1.04 16 4163 1.30 18.2 4532 1.56 21 5082 2.02 25 2652 0.75 13.3 3072 0.92 14.6 3336 1.04 15.2 3799 1.30 17.5 4232 1.58 20 4921 2.10 25 2477 0.85 13.6 2841 0.99 14.4 3437 1.28 16.7 3912 1.58 19.2 4598 2.10 24 2930 1.22 15.9 3537 1.54 18.3 4313 2.10 23 3023 1.46 17.3 3983 2.06 22 3564 1.99 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 33 Roof Upblast/Sidewall Exhaust Size-180HP: CUBE • CUE • USGF CWB • CW 3.5 2 3.0 700 100 0 SE O T CWB • CW SY FT TO EF EL TH HP 200 0.0 10 65 92 84 5 5 N 0.5 35 15 TO 1.0 13 12 CT Static Pressure (Pa) HP 4 30 3 1/ 15 1/ 1.5 25 17 5 8 16 2.0 HP USGF-180HP • CUBE • CUE HP 30 (762) 300 P 4 (762) 400 H 2 1/ 1¾ (44) 30 500 1 3/ (648) 2.5 LE 600 Static Pressure (in. wg) (727) 251⁄2 HI S *285⁄8 RPM (Belt) RPM (Direct) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m RVE HP 180HP-A 1 1/ 2 HP 800 EM A-1725 RPM CU Direct Drive RPM ST 363⁄4 (933) DO 0 1 2 25 3 4 5 Volume (cfm x 1000) (635) 363⁄4 0 (933) 27 ⁄4 3 1 2 3 4 5 6 7 8 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Belt Direct Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 126 (57) 142 (64) 190 (86) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB CW 126 (57) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 2.5 2.75 180HP 1/4 845 1/3 925 1/2 1065 3/4 1215 1275 1 1335 1430 11⁄2 1530 1610 2 1685 A-2 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1799 0.26 9.6 2104 0.34 10.8 2581 0.50 14.1 3063 0.72 15.4 3253 0.82 17 3441 0.93 19 3735 1.13 22 4035 1.36 24 4273 1.58 26 4495 1.79 28 4613 1.92 29 1688 0.35 9.9 2323 0.52 12.6 2868 0.76 14.8 3066 0.87 16.2 3261 0.98 17.8 3566 1.19 21 3884 1.43 23 4136 1.64 24 4369 1.86 27 4493 1.99 28 1933 0.53 12.5 2626 0.78 14.2 2853 0.89 15.6 3075 1.02 17.3 3401 1.23 20 3728 1.48 22 3986 1.70 24 4226 1.93 26 4353 2.06 27 MAXIMUM BHP AT A GIVEN RPM = (RPM/1315)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2286 0.79 13.5 2566 0.91 15.1 2839 1.04 16.8 3206 1.26 19.6 3574 1.53 21 3840 1.76 23 4085 1.99 26 4215 2.12 29 1854 0.75 12.7 2209 0.89 14.3 2523 1.04 16.3 2964 1.27 19.2 3376 1.55 21 3674 1.79 22 3945 2.04 25 4078 2.18 27 2156 1.01 15.7 2669 1.28 18.8 3135 1.56 20 3485 1.81 22 3768 2.07 23 3917 2.21 25 2320 1.24 18.2 2859 1.57 19.7 3233 1.82 21 3575 2.08 22 3740 2.23 24 2534 1.53 19.1 2965 1.82 20 3325 2.09 22 3509 2.24 23 2656 1.78 19.8 3061 2.08 21 3265 2.25 22 1557 1.38 18.3 2766 2.04 21 2984 2.21 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 34 Roof Upblast/Sidewall Exhaust Size-200: CUBE • CUE • USGF CWB • CW 363⁄4 2.0 Direct Drive RPM (933) *28 ⁄8 TEM SYS HIS 11 FT TO EF 0 96 EL TH 86 TO 0 76 0 CT 0.5 66 LE 100 SE CWB • CW 10 12 40 11 00 P Static Pressure (Pa) HP HP Static Pressure (in. wg) 1 4H 3/ 200-C 4 USGF-200 • CUBE • CUE (762) 1.0 1/ 30 HP (762) 200 1/3 1¾ (44) 300 P (648) H 1/2 (727) 30 CUR VE 200-B 400 1.5 25 ⁄2 HP HP /2 11 B-1140 RPM 5 1 RPM (Belt) RPM (Direct) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 C-860 RPM 5 60 O T 5 DO 0 0.0 0 N 1 2 25 3 4 5 6 7 Volume (cfm x 1000) (635) 36 ⁄4 3 0 (933) 273⁄4 2 4 6 8 10 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Belt Direct Fan RPM CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 142 (64) 170 (77) 213 (97) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) 0 0.125 0.25 Static Pressure in Inches wg 0.375 0.5 0.75 3403 0.25 8.2 3740 0.33 9.6 4275 0.49 12.3 4612 0.61 14.2 4837 0.71 15.8 4922 0.75 16.4 5400 0.98 18.9 5793 1.22 21 6187 1.48 24 6412 1.65 25 6806 1.97 24 3054 0.26 7.6 3422 0.34 9 3994 0.51 11.8 4350 0.63 14.1 4587 0.73 15.7 4676 0.77 16.4 5176 1.01 18.6 5585 1.24 21 5992 1.51 23 6224 1.67 24 6628 2 24 2675 0.26 6.8 3096 0.35 8.3 3718 0.52 11.1 4098 0.65 13.3 4346 0.74 14.9 4439 0.78 15.6 4958 1.03 18 5380 1.26 20 5798 1.53 23 6036 1.7 24 6451 2.03 23 2144 0.25 6.2 2699 0.35 7.5 3413 0.52 10.2 3828 0.65 12.5 4093 0.75 14.4 4192 0.79 15.1 4742 1.04 17.4 5179 1.28 19.7 5610 1.55 22 5855 1.72 23 6279 2.05 23 1 1.25 CWB CW 142 (64) 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 1.5 1.75 200 1/4 605 1/3 665 1/2 760 820 3/4 C-3/4 860 875 1 960 1030 11⁄2 1100 B-2 1140 2 1210 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2073 0.33 7.2 3048 0.51 9.5 3523 0.65 11.5 3815 0.75 13 3922 0.79 13.7 4508 1.04 16.7 4968 1.29 19.2 5421 1.57 22 5674 1.74 22 6108 2.07 23 MAXIMUM BHP AT A GIVEN RPM = (RPM/946)3 MAXIMUM RPM = 1210 TIP SPEED (ft/min) = RPM x 5.595 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2606 0.61 10.9 3084 0.73 12 3240 0.78 12.6 3985 1.04 15.2 4503 1.29 17.8 5006 1.57 21 5283 1.74 22 5748 2.09 22 3169 1.00 14.7 3917 1.27 16.6 4529 1.57 19.7 4837 1.74 21 5350 2.09 21 2972 1.18 17.1 3861 1.53 18.9 4276 1.73 19.6 4892 2.08 20 3445 1.63 20 4289 2.04 20 3365 1.88 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 35 Roof Upblast/Sidewall Exhaust Size-200HP: CUBE • CUE • USGF CWB 363⁄4 1120 4.5 980 4.0 5 (933) 3 3.5 30 (762) 30 USGF-200HP • CUBE • CUE (762) 700 2.5 11 /2 HP 560 2.0 1H P 3/ 4H P 1/ 2H P 420 1.5 280 1.0 CWB 140 0 0.5 0.0 HP TH EL EF TO FT HIS 1¾ (44) 2 DO 0 T NO 1 17 25 16 00 14 00 12 70 11 TO (648) 3.0 EL EC T Static Pressure (Pa) 251⁄2 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP SY TE M (727) CU RV E 840 *285⁄8 HP 10 10 10 S 88 2 3 25 0 4 5 6 7 8 9 Volume (cfm x 1000) (635) 363⁄4 0 (933) 27 ⁄4 3 2 4 6 8 10 12 3 Volume (m /hr x 1000) (705) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *285⁄8 (727) Motor HP Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE USGF 142 (64) 145 (66) 213 (97) 18 x 18 (457 x 457) N/A 20½ x 20½ (521 x 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 CWB 142 (64) 17 x 17 (432 x 432) 17½ x 17½ (445 X 445) 2.5 2.75 200HP 740 1/2 880 945 CUBE • CWB • USGF 3/4 1010 1 1110 1190 11⁄2 1270 1335 2 CUBE USGF 3 1600 CUE 1400 5 1725 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2024 0.31 8.2 2779 0.51 10.7 3094 0.62 12.3 3397 0.75 14.7 3851 0.98 17.1 4207 1.2 19.4 4558 1.44 22 4837 1.67 23 5110 1.91 25 5943 2.81 29 6457 3.50 33 2317 0.52 9.6 2711 0.64 11.7 3067 0.78 14.1 3561 1.02 16.5 3944 1.24 18.5 4312 1.49 21 4606 1.71 23 4898 1.96 24 5775 2.88 27 6302 3.57 30 2092 0.62 10.8 2637 0.79 13.5 3242 1.04 16 3661 1.27 17.9 4055 1.53 21 4369 1.76 22 4674 2.01 24 5581 2.93 28 6135 3.64 30 MAXIMUM BHP AT A w GIVEN RPM = (RPM/1093)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 5.595 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/2.92 2806 1.04 15.8 3321 1.29 17.5 3789 1.56 20 4116 1.79 21 4436 2.05 23 5385 2.99 28 5954 3.69 31 2850 1.26 17.9 3433 1.56 19.3 3826 1.82 21 4195 2.09 22 5182 3.03 28 5772 3.75 32 2944 1.53 20 3482 1.82 21 3880 2.09 23 4971 3.08 26 5582 3.80 32 2946 1.75 22 3515 2.08 23 4760 3.13 26 5386 3.85 30 2982 2.01 24 4476 3.13 28 5190 3.90 28 4189 3.13 30 4948 3.92 31 3760 3.06 31 4682 3.92 35 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 36 Roof Upblast/Sidewall Exhaust Size-220: CUBE CWB 2.0 423⁄4 RV E CU EM ST SY IS TH OF FT LE E TH TO 68 T 5 60 EC Static Pressure (in. wg) 5 EL 0.0 0 NO 1 T 47 S 2 0 52 5 0 3 283⁄8 4 5 6 7 8 Volume (cfm x 1000) 42 ⁄4 3 (1087) 0 311⁄4 2 4 6 8 10 12 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP 5 DO 5 CWB (721) 86 0.5 100 0 95 1.0 75 Static Pressure (Pa) P 4H 3/ CUBE P HP 3 H 1 /4 200 1/ 1¾ (44) (864) 300 HP 281⁄2 (724) 1/2 (860) P H 1.5 *337⁄8 34 P 1H 400 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 HP /2 11 (1086) Fan RPM 0 0.125 0.25 3585 0.19 7.4 3784 0.23 8 4142 0.3 9.3 4779 0.46 12 5138 0.57 13.6 5457 0.68 15 6014 0.91 17.7 6452 1.13 19 6890 1.37 21 7249 1.6 23 7607 1.85 25 3155 0.21 6.8 3377 0.25 7.3 3771 0.32 8.5 4457 0.48 11.1 4838 0.6 12.7 5174 0.71 14.2 5758 0.94 17 6213 1.16 18.5 6667 1.41 20 7036 1.64 22 7405 1.89 25 2624 0.22 6.2 2896 0.26 6.7 3357 0.34 7.7 4124 0.51 10.2 4539 0.63 12 4893 0.74 13.7 5502 0.98 16.6 5975 1.2 17.9 6443 1.45 19.6 6823 1.68 22 7202 1.93 24 ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 0.375 0.5 0.625 CUBE CWB 174 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 174 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) 0.75 1 1.25 1.5 220 450 1/4 475 1/3 520 1/2 600 645 3/4 685 1 755 810 11⁄2 865 910 2 955 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2268 0.25 6.2 2845 0.34 7.2 3736 0.52 9.5 4194 0.64 11.3 4581 0.76 13.2 5239 1.01 16.3 5737 1.24 17.6 6220 1.49 19.2 6612 1.72 21 7000 1.97 24 MAXIMUM BHP AT A GIVEN RPM = (RPM/743)3 MAXIMUM RPM = 955 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 3279 0.52 8.9 3811 0.65 10.6 4234 0.78 12.3 4944 1.03 15.8 5470 1.26 17.2 5987 1.52 18.7 6400 1.76 21 6799 2.02 23 3346 0.64 10 3836 0.78 11.7 4620 1.04 14.9 5185 1.28 16.5 5729 1.54 18.1 6158 1.78 20 6580 2.05 23 3383 0.77 11.2 4258 1.04 14.4 4883 1.29 15.7 5453 1.56 17.4 5909 1.81 19.3 6347 2.07 22 4156 1.27 14.8 4835 1.57 16.5 5365 1.83 18.3 5844 2.11 20 4111 1.53 16.1 4704 1.81 17.4 5261 2.11 19.4 4602 2.07 18.9 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 37 Roof Upblast/Sidewall Exhaust Size-220HP: CUBE CWB 423⁄4 3.0 (1086) 3 700 CUR VE TEM SYS HIS FT TO 98 EF 5 EL 86 0 TH 1.0 78 TO 0 68 CT Static Pressure (in. wg) 40 12 LE 0 SE CWB 85 10 Static Pressure (Pa) HP CUBE 200 1.5 HP (864) 300 HP 34 400 2.0 3/4 1¾ (44) 500 1/2 (724) P (860) 1H *337⁄8 281⁄2 2 HP /2 11 2.5 600 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 0.5 N O T 100 DO 0 0.0 0 1 2 3 283⁄8 (721) 4 5 6 7 8 Volume (cfm x 1000) 423⁄4 (1087) 0 31 ⁄4 1 2 4 6 8 10 12 3 Volume (m /hr x 1000) (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP Fan RPM 0.5 0.75 2909 0.45 8.7 3151 0.51 9.7 3582 0.63 11.9 3902 0.74 13.4 4459 0.96 15 5281 1.39 19.1 5602 1.6 21 5920 1.82 23 6236 2.06 24 6570 2.34 25 6895 2.64 27 1940 0.42 7.7 2405 0.51 8.7 3006 0.65 11 3427 0.78 12.5 4075 1.02 14.3 4988 1.48 17.9 5335 1.69 19.8 5678 1.92 22 6006 2.17 23 6350 2.46 25 6684 2.76 26 1 ^Approximate Weight Damper Size Roof/Wall Opening CUBE CWB 174 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 174 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 2.75 220HP 650 1/2 680 735 CUBE • CWB 3/4 780 1 860 11⁄2 985 1035 2 1085 CUBE 1135 3 1188 1240 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/847)3 MAXIMUM RPM = 1240 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 2716 0.77 12.1 3578 1.05 13.9 4642 1.54 17.4 5033 1.77 18.9 5390 2 20 5743 2.26 22 6111 2.56 24 6469 2.88 26 2863 1.01 13.2 4220 1.57 17.1 4659 1.81 18.7 5061 2.06 20 5456 2.34 22 5848 2.65 24 6217 2.97 25 3674 1.56 16.5 4209 1.82 18.3 4679 2.1 20 5114 2.39 21 5540 2.71 23 5950 3.05 25 2825 1.46 14.9 3630 1.79 17.3 4210 2.09 19.6 4708 2.4 21 5202 2.75 23 5637 3.1 24 3573 2.03 18.1 4215 2.38 21 4792 2.76 22 5283 3.13 24 3518 2.28 19.5 4286 2.72 22 4885 3.13 24 3563 2.59 22 4374 3.08 24 3633 2.92 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 38 Roof Upblast/Sidewall Exhaust Size-240: CUBE • CUE CWB 423⁄4 3.0 (1086) 5 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m H P D 41 OF TH IS S YST EM C 11 40 93 TH EL EF T O NO T 0.5 TO Static Pressure (Pa) 150 CWB HP 3/4 HP P P 3H H 1/ 1/4 CUBE • CUE 1.0 2 (864) 1.5 1/ 34 300 P 1¾ (44) 450 1H (724) 2.0 SE LE CT 28 ⁄2 Static Pressure (in. wg) (860) 1 P 2H HP /2 11 *337⁄8 URV E 2.5 600 0 84 5 73 5 67 0 58 5 51 0 0 0 0.0 0 2 4 6 8 10 12 Volume (cfm x 1000) 283⁄8 (721) 423⁄4 0 (1087) 4 8 12 16 3 Volume (m /hr x 1000) 31 ⁄4 1 (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP Fan RPM 0 0.125 0.25 3717 0.16 6.4 4623 0.31 8.9 5303 0.46 11.5 5693 0.57 12.9 6074 0.69 14.3 6663 0.92 16.6 7162 1.14 18.2 7660 1.39 19.6 7796 1.47 20 8431 1.86 24 10335 3.42 40 3170 0.18 5.8 4243 0.33 8.1 4961 0.49 10.5 5368 0.61 11.9 5763 0.74 13.4 6370 0.97 15.9 6883 1.20 17.5 7400 1.46 19.0 7540 1.54 19.8 8194 1.93 23 10142 3.51 40 2471 0.18 5.3 3717 0.34 7.3 4540 0.51 9.5 5010 0.63 11.1 5461 0.76 12.8 6133 0.99 15.5 6661 1.22 17.2 7184 1.49 18.6 7326 1.57 19.4 7985 1.98 23 9948 3.60 40 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 142 (64) 226 (103) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 175 (79) 20 x 20 (508 x 508) 26½ x 26½ (673 X 673) 1 1.25 1.5 240 1/4 1/3 CUBE • CWB 1/2 3/4 1 CUE CUBE CWB CUBE CUE CWB 11⁄2 2 5 CFM BHP Sones CFM 510 BHP Sones CFM 585 BHP Sones CFM 628 BHP Sones CFM 670 BHP Sones CFM 735 BHP Sones CFM 790 BHP Sones CFM 845 BHP Sones CFM 860 BHP Sones CFM 930 BHP Sones CFM 1140 BHP Sones 410 3134 0.34 6.9 4093 0.52 8.8 4590 0.64 10.4 5052 0.78 12.2 5764 1.01 15.1 6361 1.25 16.8 6947 1.51 18.2 7106 1.59 19.0 7798 2.00 22 9789 3.64 41 3565 0.51 8.4 4141 0.65 9.8 4659 0.79 11.5 5409 1.03 14.6 6011 1.27 16.3 6615 1.54 17.6 6779 1.62 18.4 7536 2.03 22 9637 3.67 40 MAXIMUM BHP AT A GIVEN RPM = (RPM/725)3 MAXIMUM RPM = 1140 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 3600 0.63 9.4 4202 0.78 11.0 5037 1.04 13.9 5693 1.28 15.7 6304 1.56 17.0 6468 1.64 17.8 7233 2.06 21 9484 3.70 39 3524 0.73 10.6 4618 1.03 13.4 5332 1.29 15.0 6002 1.57 16.4 6176 1.66 17.2 6953 2.08 19.9 9240 3.74 37 4453 1.24 14.3 5282 1.56 15.4 5483 1.65 16.2 6375 2.10 18.7 8747 3.81 33 4363 1.52 15.9 5706 2.07 17.8 8306 3.85 30 4324 1.83 17.9 7820 3.87 29 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 39 Roof Upblast/Sidewall Exhaust Size-240HP: CUBE • CUE CWB 3.0 423⁄4 3 P H (1086) TO THE LEF TO F TH IS S YST EM C URV E 5 NO TS EL EC T 5 0.5 77 Static Pressure (Pa) 30 70 0 86 P 2H 1.0 150 67 5 DO CWB 97 1/ CUBE • CUE 300 1.5 HP (864) 3/4 1¾ (44) 34 2.0 10 (724) 450 P 1H (860) Static Pressure (in. wg) *337⁄8 12 P 2H HP /2 1-1 2.5 600 281⁄2 RPM (Belt) HP 3 Density 0.075 lb/ft Density 1.2 kg/m 3 0 0.0 0 2 4 6 8 10 12 Volume (cfm x 1000) 283⁄8 (721) 423⁄4 0 (1087) 4 8 12 16 3 Volume (m /hr x 1000) 31 ⁄4 1 (794) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *337⁄8 (860) Motor HP Fan RPM 0.5 0.625 3046 0.43 8.1 3405 0.51 9.4 3824 0.62 11.3 4233 0.75 13.1 4888 0.99 15.0 5286 1.16 16.4 5737 1.39 18.4 6075 1.59 20 6404 1.80 22 6891 2.16 24 7513 2.68 26 2673 0.43 7.4 3070 0.52 8.8 3547 0.64 10.7 3979 0.77 12.5 4680 1.02 14.5 5094 1.20 15.8 5567 1.43 17.9 5927 1.63 19.6 6272 1.84 22 6766 2.20 24 7395 2.73 25 0.75 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 175 (79) 209 (95) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) Static Pressure in Inches wg 1 1.25 1.5 1.75 175 (79) 20 x 20 (508 x 508) 20½ x 20½ (521 X 521) 2 2.25 2.5 240HP 635 CUBE • CWB 1/2 675 725 3/4 CUBE CUE CWB 775 1 860 913 CUBE • CWB 11⁄2 975 1023 2 CUBE CUE 1070 1140 CUBE 3 1230 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2607 0.51 8.4 3222 0.65 10.3 3704 0.78 12.1 4451 1.05 14.3 4890 1.23 15.4 5387 1.48 17.3 5756 1.68 19.0 6112 1.89 21 6637 2.25 23 7280 2.77 25 MAXIMUM BHP AT A GIVEN RPM = (RPM/837)3 MAXIMUM RPM = 1230 TIP SPEED (ft/min) = RPM x 6.413 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 2940 0.77 11.8 3943 1.07 13.9 4448 1.28 15.2 4988 1.53 16.9 5389 1.75 18.3 5775 1.98 19.7 6329 2.35 22 7016 2.88 25 3185 1.05 13.2 3932 1.29 14.7 4539 1.56 16.6 4995 1.80 18.1 5407 2.04 19.7 5994 2.42 22 6730 2.98 25 4006 1.56 15.9 4533 1.81 17.7 4990 2.07 19.4 5649 2.49 22 6410 3.05 24 3854 1.77 16.4 4550 2.08 18.8 5239 2.50 21 6090 3.13 24 3625 1.95 16.6 4825 2.52 21 5709 3.14 23 4052 2.41 19.8 5326 3.16 23 4722 3.09 25 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 40 Roof Upblast/Sidewall Exhaust Size-240XP: CUBE 3 423⁄4 2 5 HP 1 1200 YSTE H IS S OF T 95 L EF T 17 20 THE 1/2 HP 15 TO 2 18 1 11 95 65 D O NO 200 00 13 CT CUBE 3/ 4H P 3 ELE 400 HP TS 1¾ (44) 34 (864) 600 Static Pressure (in. wg) Static Pressure (Pa) (724) 800 1 65 281⁄2 4 21 (860) M CU HP RVE 2 1/ 1000 *337⁄8 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P H (1086) 0 0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 Volume (cfm) 0 2000 4000 6000 3 Volume (m /hr) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1292 0.40 10.9 1613 0.53 11.6 2079 0.77 13.6 2223 0.86 14.4 2424 1.00 15.9 2743 1.28 18.6 2939 1.48 21 3333 1.94 24 3469 2.13 25 3632 2.37 26 3927 2.85 29 789 0.34 11.9 1321 0.51 12.1 1886 0.78 13.4 2042 0.88 14.2 2256 1.03 15.3 2604 1.31 18.0 2815 1.51 19.8 3222 1.98 23 3361 2.16 24 3529 2.40 25 3830 2.89 28 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 175 (79) 24 x 24 (610 x 610) 26½ x 26½ (673 x 673) 3.5 4 4.5 5 240XP 1100 1/2 1195 3/4 1365 1421 1 1500 1635 11⁄2 1720 2 1895 1956 3 2030 2165 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 792 0.43 13.4 1645 0.77 13.7 1837 0.88 14.2 2079 1.04 15.1 2450 1.33 17.5 2671 1.53 19.2 3109 2.01 22 3252 2.20 23 3423 2.44 25 3733 2.93 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/1478)3 MAXIMUM RPM = 2165 TIP SPEED (ft/min) = RPM x 4.778 MAXIMUM MOTOR FRAME SIZE = 184T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/3.76 1209 0.79 15.3 1630 1.01 15.5 2101 1.34 17.0 2366 1.57 18.4 2847 2.07 21 3006 2.26 22 3197 2.51 24 3535 3.01 27 1631 1.28 17.7 1975 1.53 18.4 2566 2.10 21 2739 2.30 22 2945 2.56 23 3305 3.07 26 1336 1.35 20 2202 2.05 21 2414 2.28 21 2667 2.58 23 3063 3.12 25 1706 1.92 22 2032 2.21 22 2319 2.51 23 2787 3.11 25 1326 1.89 25 1852 2.38 25 2461 3.05 25 2048 2.93 27 1324 2.47 31 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 41 Roof Upblast/Sidewall Exhaust Size-300: CUBE • CUE CWB 50 2.5 (1270) 5 600 UR VE P STE SY H IS FT CT TO EF EL TH TO Static Pressure (in. wg) LE Static Pressure (Pa) SE T NO 53 0 48 0 42 0 36 5 2 4 6 3527⁄32 (910) 5 90 0 5 5 0.0 60 0 5 DO 66 0.5 CWB 76 HP /2 11 CUBE • CUE 1.0 MC P 2H 200 HP P P 3/4 2 H /3 H 1/ 1 (1016) 1.5 1H 1¾ (44) 40 400 P 29 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 3H 2.0 *36 (914) (737) HP 8 10 12 14 16 Volume (cfm x 1000) 50 (1270) 0 38 ⁄8 3 5 10 (975) 15 20 25 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *36 (914) Motor HP Fan RPM 0 0.125 0.25 5777 0.27 6.9 5940 0.29 7.2 6835 0.45 9.0 7811 0.67 11.0 8625 0.90 13.3 9845 1.34 17.0 10822 1.77 20 12449 2.70 24 12937 3.03 26 13995 3.84 30 14727 4.47 32 5132 0.30 6.3 5316 0.33 6.5 6314 0.49 8.2 7377 0.72 10.5 8231 0.95 12.7 9501 1.40 16.4 10508 1.85 19.7 12176 2.78 24 12675 3.12 25 13753 3.93 30 14497 4.57 32 4227 0.31 5.3 4464 0.34 5.7 5660 0.52 7.5 6844 0.76 9.9 7772 1.00 12.2 9127 1.46 15.7 10193 1.92 18.6 11904 2.86 23 12413 3.20 24 13510 4.02 29 14266 4.67 32 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 313 (142) 380 (172) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 313(142) 25 x 25 (635 x 635) 25½ x 25½ (648 x 648) 1.75 2 300 355 1/3 1/2 420 3/4 480 1 530 11⁄2 605 2 665 3 765 CUBE CUBE • CWB 365 CUBE CUBE CUE 795 5 860 905 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/522)3 MAXIMUM RPM = 905 TIP SPEED (ft/min) = RPM x 7.983 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 5440 0.77 8.5 6636 1.05 11.2 8226 1.54 14.8 9411 2.02 17.5 11273 3.00 22 11818 3.35 23 12987 4.19 27 13788 4.85 29 7084 1.55 13.5 8495 2.07 16.7 10554 3.09 21 11145 3.46 22 12392 4.33 26 13223 5.00 28 7271 2.04 15.1 9743 3.15 20 10404 3.53 22 11721 4.41 26 12614 5.11 28 8756 3.14 18.7 9479 3.53 21 11002 4.47 24 11963 5.19 27 7352 2.98 17 8302 3.43 18.5 10124 4.46 23 11191 5.21 26 9007 4.34 21 10357 5.20 24 9178 5.01 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 42 Roof Upblast/Sidewall Exhaust Size-300HP: CUBE • CUE CWB 4.0 980 0 0.0 (910) 0 TH EL EF TO F T HIS SYS TEM 77 TO NO T DO 2 5 1.0 0.5 3527⁄32 P 1.5 CWB 140 H HP 88 Static Pressure (Pa) 2.0 HP /2 1-1 280 2 HP 3/4 HP 2 1/ CUBE • CUE 3 P (1016) 420 2.5 1H 1¾ (44) 560 45 10 (737) Static Pressure (in. wg) 700 0 70 0 SE LE CT (914) 29 40 HP 3.0 0 HP 114 5 *36 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 2 1/ 7- 3.5 840 CUR VE 50 (1270) 61 55 0 5 48 5 4 6 8 10 12 14 16 Volume (cfm x 1000) 50 (1270) 0 383⁄8 3 6 9 12 15 18 3 Volume (m /hr x 1000) (975) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. *36 (914) Motor HP Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening CUE CWB 313 (142) 434 (197) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 313 (142) 25 x 25 (635 x 635) 25½ x 25½ (648 x 648) 2.5 2.75 300HP CFM BHP Sones CFM 485 BHP Sones CFM 555 BHP Sones CFM 610 BHP Sones CFM 700 BHP Sones CFM 770 BHP Sones CFM 860 BHP Sones CFM 885 BHP Sones CFM 991 BHP Sones CFM 1045 BHP Sones CFM 1140 BHP Sones 460 CUBE• CWB 1/2 3/4 1 11⁄2 CUBE 3 5 CUE CUBE CWB CUBE CUE CWB 2 7½ 3125 0.44 7.3 3639 0.52 7.9 4788 0.77 10.4 5549 1.00 12.4 6741 1.47 16.0 7613 1.91 18.6 8712 2.61 22 9014 2.83 23 10275 3.90 30 10909 4.54 35 12016 5.83 46 3651 0.76 9.9 4731 1.03 11.3 6149 1.53 15.2 7107 2.00 18.1 8289 2.72 22 8603 2.94 23 9913 4.03 29 10570 4.68 34 11713 6.00 47 MAXIMUM BHP AT A GIVEN RPM = (RPM/602)3 MAXIMUM RPM = 1140 TIP SPEED (ft/min) = RPM x 7.983 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 5390 1.57 14.0 6535 2.06 17.4 7812 2.80 22 8150 3.03 23 9546 4.16 29 10222 4.82 34 11394 6.14 46 5814 2.09 16.2 7292 2.87 21 7678 3.12 22 9133 4.26 28 9855 4.94 33 11075 6.29 44 4684 1.99 16.0 6647 2.90 20 7062 3.15 21 8711 4.35 28 9455 5.04 32 10733 6.42 42 5834 2.85 19.9 6353 3.14 21 8201 4.41 27 9054 5.13 31 10366 6.52 40 7641 4.44 26 8533 5.17 31 9999 6.63 40 6946 4.39 25 8002 5.21 30 9562 6.70 40 7330 5.15 28 9075 6.74 40 6463 4.99 27 8586 6.77 38 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 43 Roof Upblast/Sidewall Exhaust Size-300XP: CUBE 50 5 (1270) 5 1200 P H 3H SYST THIS T OF 14 LEF 25 THE 12 11 30 ELE CT TO 2 1 0 0 DO NO 200 45 99 90 TS Static Pressure (in. wg) Static Pressure (Pa) P H 400 4 3/ CUBE HP (1016) 600 3 1 1¾ (44) 800 HP /2 11 (737) 90 16 HP (914) 29 40 EM C 2 4 URVE P 1000 *36 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 0 0 0 1 2 3 4 5 6 7 8 9 Volume (cfm x 1000) 0 2 4 6 8 10 12 14 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 313 (142) 30 x 30 (762 x 762) 32½ x 32½ (826 x 826) 3.5 4 4.5 4.75 300XP 790 3/4 900 1 990 1060 1 ⁄2 1 1130 2 1245 1335 3 1425 1493 5 1560 1690 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1776 0.48 9.4 2958 0.79 12.2 3619 1.04 14.6 4073 1.25 16.5 4511 1.48 18.9 5182 1.92 22 5695 2.32 24 6199 2.78 27 6574 3.16 29 6941 3.57 31 7643 4.47 36 2273 0.75 11.3 3167 1.05 13.4 3708 1.28 15.3 4201 1.53 17.8 4930 1.99 21 5465 2.40 24 5983 2.86 26 6369 3.25 28 6746 3.67 30 7464 4.57 35 2538 1.00 12.8 3255 1.28 14.4 3833 1.56 16.8 4648 2.04 20 5220 2.47 23 5768 2.95 25 6164 3.34 28 6549 3.76 30 7284 4.68 34 MAXIMUM BHP AT A GIVEN RPM = (RPM/972)3 MAXIMUM RPM = 1690 TIP SPEED (ft/min) = RPM x 5.825 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/5.50 2773 1.46 15.6 3943 2.08 18.6 4648 2.56 21 5286 3.07 24 5722 3.49 26 6143 3.93 28 6920 4.87 33 2705 1.86 17.9 3905 2.53 19.4 4695 3.14 22 5200 3.58 24 5684 4.05 27 6528 5.04 31 3886 3.03 21 4550 3.57 23 5134 4.12 25 6091 5.16 30 3646 3.37 22 4441 4.02 24 5587 5.24 29 3049 3.50 24 4951 5.14 28 4100 4.88 28 3070 4.32 28 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 44 Roof Upblast/Sidewall Exhaust Size-360: CUBE 585⁄8 2.0 5 HP (1489) 3H RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m P 400 RV E CU EM ST SY IS TH OF FT LE E TH TO Static Pressure (Pa) 5 EC T 36 EL T NO 0 5 32 S 0 0.0 0 69 0 58 0 DO 0 50 46 0.5 100 40 CUBE P HP 1 H 3/4 P 200 2H (1168) 1.0 1/ 1¾ (44) 300 HP /2 11 293⁄8 (746) Static Pressure (in. wg) P (994) 46 2H 1.5 *391⁄8 0 5 10 15 20 Volume (cfm x 1000) 0 10 20 30 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 0.25 8092 0.37 6.9 8631 0.44 7.7 9845 0.66 10.2 10789 0.87 12.7 12408 1.32 16.8 13621 1.74 20 14646 2.17 22 15644 2.64 23 16642 3.18 25 17640 3.78 27 18611 4.44 30 7206 0.42 5.9 7820 0.50 6.8 9142 0.72 9.4 10153 0.94 11.9 11862 1.40 16.5 13125 1.83 20 14184 2.26 22 15212 2.74 23 16236 3.29 25 17257 3.90 27 18248 4.57 29 6023 0.43 5.4 6755 0.52 6.0 8299 0.77 8.5 9426 0.99 11.1 11281 1.48 15.8 12602 1.92 19.8 13705 2.36 21 14769 2.84 23 15826 3.40 25 16873 4.02 27 17884 4.69 28 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 0.375 0.5 0.75 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 1 1.25 1.5 1.75 360 300 1/2 320 3/4 365 1 400 11⁄2 460 2 505 543 3 580 617 5 654 690 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 5256 0.51 6.6 7286 0.78 8.0 8556 1.02 10.3 10587 1.53 15.1 12022 1.99 19.0 13209 2.45 21 14306 2.94 22 15391 3.50 24 16466 4.13 26 17504 4.81 28 5767 0.74 8.3 7575 1.02 9.9 9814 1.55 14.5 11359 2.04 18.6 12606 2.50 20 13783 3.02 22 14942 3.60 24 16056 4.24 26 17115 4.93 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/396)3 MAXIMUM RPM = 690 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 7809 1.52 13.5 9878 2.06 17.9 11302 2.56 19.3 12597 3.10 21 13862 3.71 23 15084 4.39 25 16236 5.11 27 9606 2.52 18.2 11287 3.13 20 12684 3.76 22 14000 4.46 23 15243 5.21 25 9381 3.02 18.4 11227 3.73 21 12831 4.48 22 14187 5.26 24 11217 4.38 21 12985 5.25 23 11290 5.09 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 45 Roof Upblast/Sidewall Exhaust Size-360HP: CUBE 585⁄8 3.0 (1489) 700 E MC STE SY HIS FT TO EF EL TH 55 TO 1.0 CT 5 44 SE 0 NO T 0.5 5 50 LE Static Pressure (in. wg) 5 5 Static Pressure (Pa) 86 75 5 63 200 P CUBE 300 1.5 P 46 (1168) 400 2.0 1H 1¾ (44) 500 P 2H P /2 H 11 (746) 3H (994) 293⁄8 URV P H *391⁄8 HP /2 71 5 2.5 600 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m 100 DO 0 0.0 0 5 10 15 20 Volume (cfm x 1000) 0 5 10 15 20 25 30 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0.5 0.75 1 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 1.25 1.5 1.75 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 2 2.25 2.5 2.75 360HP 420 1 440 11⁄2 505 2 555 595 3 635 695 5 755 781 71⁄2 824 865 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 6407 0.90 9.6 7003 1.03 10.8 8765 1.52 15.3 10029 1.97 17.2 10996 2.40 18.9 11934 2.87 21 13321 3.70 24 14688 4.68 28 15275 5.15 30 16232 6.00 31 17129 6.89 33 7539 1.57 14.3 9046 2.06 16.2 10129 2.50 17.7 11157 3.00 19.5 12662 3.86 23 14086 4.86 27 14693 5.34 29 15689 6.20 29 16631 7.11 32 MAXIMUM BHP AT A GIVEN RPM = (RPM/434)3 MAXIMUM RPM = 865 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 7766 2.08 15.4 9094 2.57 16.8 10276 3.09 18.2 11902 3.98 22 13434 5.01 26 14086 5.51 28 15137 6.40 27 16105 7.32 30 7488 2.49 16.1 9171 3.12 17.8 11053 4.07 20 12734 5.14 25 13410 5.64 27 14511 6.54 28 15544 7.50 29 7329 2.95 17.3 10026 4.09 20 11922 5.23 24 12681 5.75 27 13869 6.69 29 14933 7.64 29 8393 3.92 19.6 10973 5.24 23 11831 5.81 26 13127 6.78 28 14315 7.79 29 9593 5.10 22 10852 5.79 24 12290 6.82 26 13565 7.87 28 9149 5.51 23 11354 6.79 25 12738 7.89 27 9683 6.48 24 11789 7.83 25 10197 7.50 23 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 46 Roof Upblast/Sidewall Exhaust Size-360XP: CUBE 585⁄8 6 (1489) 7 1400 1/ 2 5 HP 3H EM C SYST THIS T OF LEF 10 HE 95 95 OT 2 0 760 EL 1 O NO TS 200 5 87 TT 400 CUBE 13 00 EC Static Pressure (Pa) 600 3 HP (1168) 800 4 1 1¾ (44) 1000 P 2H HP /2 11 (746) 90 14 (994) Static Pressure (in. wg) P *391⁄8 46 URVE 5 1200 293⁄8 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP D 0 0 0 2 4 6 8 10 12 Volume (cfm x 1000) 0 5 10 15 20 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 1 1.25 1.5 2 CUBE ^Approximate Weight Damper Size Roof/Wall Opening Static Pressure in Inches wg 2.5 3 440 (200) 36 x 36 (914 x 914) 38½ x 38½ (978 x 978) 3.5 4 4.5 5 360XP 700 1 760 11⁄2 870 2 955 1025 3 1095 1163 5 1231 1300 1395 71⁄2 1490 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 3210 0.81 10.5 4020 1.05 11.1 5243 1.53 13.6 6081 1.97 15.4 6722 2.38 17.1 7351 2.85 19.2 7945 3.36 21 8528 3.91 23 9113 4.54 26 9910 5.50 29 10699 6.61 33 3225 1.01 11.1 4740 1.57 12.7 5679 2.04 15.4 6396 2.47 16.5 7050 2.95 18.4 7669 3.47 21 8278 4.05 23 8881 4.69 25 9693 5.67 28 10496 6.78 32 4112 1.55 12.3 5216 2.08 14.2 6001 2.54 16.2 6724 3.03 17.8 7386 3.57 19.9 8011 4.15 22 8635 4.82 24 9477 5.83 27 10294 6.96 31 MAXIMUM BHP AT A GIVEN RPM = (RPM/748)3 MAXIMUM RPM = 1490 TIP SPEED (ft/min) = RPM x 7.069 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/7.25 3949 1.98 13.0 5035 2.55 14.5 5930 3.13 16.4 6712 3.73 18.6 7422 4.35 21 8125 5.04 23 9009 6.08 26 9871 7.27 30 3264 2.18 13.4 4905 3.07 15.4 5867 3.75 17.3 6711 4.45 19.4 7502 5.21 22 8490 6.30 25 9429 7.52 29 4700 3.54 16.5 5824 4.40 18.5 6764 5.24 21 7905 6.48 24 8907 7.73 27 4551 4.04 18.0 5867 5.15 20 7193 6.48 23 8340 7.89 26 4286 4.52 20 6348 6.37 23 7673 7.90 26 5143 5.87 23 6881 7.78 26 5830 7.34 27 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 47 Roof Upblast/Sidewall Exhaust Size-420: CUBE 653⁄8 2.0 (1661) 5 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m E URV MC STE SY HIS FT TO EF EL TH TO CT 30 28 5 0 5 SE T 5 0 LE Static Pressure (in. wg) Static Pressure (Pa) 0 60 NO 0 5 52 38 35 24 DO 0.0 0 0.5 100 0 44 HP CUBE 1/2 200 1.0 P 1H P H (1321) 3/4 1¾ (44) 300 P P 2H /2 H 11 351⁄4 (895) HP /2 71 P 1.5 (1137) 52 HP 3H 400 *443⁄4 4 8 12 16 20 24 28 Volume (cfm x 1000) 0 10 20 30 40 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 0.25 9353 0.31 6.5 10416 0.43 7.2 11904 0.64 8.3 12966 0.82 9.4 14879 1.24 11.9 16367 1.65 14.4 17643 2.07 17.2 18706 2.47 17.7 22319 4.19 23 24020 5.23 26 25508 6.26 29 7846 0.37 6.0 9104 0.50 6.7 10785 0.73 7.7 11959 0.94 8.8 14037 1.38 11.2 15629 1.81 13.5 16982 2.24 16.1 18103 2.65 17.1 21817 4.41 22 23553 5.46 25 25069 6.51 29 5075 0.35 5.5 7304 0.53 6.1 9418 0.78 7.1 10781 1.00 8.0 13050 1.46 10.1 14731 1.91 12.4 16148 2.37 14.9 17316 2.81 16.0 21220 4.61 22 23030 5.68 25 24604 6.75 29 CUBE ^Approximate Weight Damper Size Roof/Wall Opening 578 (262) 42 x 42 (1067 x 1067) 44½ x 44½ (1130 x 1130) Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 1.5 1.75 420 220 1/2 245 3/4 280 1 305 11⁄2 350 2 385 415 3 440 5 525 565 71⁄2 600 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 7419 0.77 6.6 9272 1.02 7.3 11925 1.52 9.4 13791 1.99 11.7 15303 2.45 13.8 16532 2.89 14.7 20560 4.78 21 22417 5.88 25 24027 6.96 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/303)3 MAXIMUM RPM = 600 TIP SPEED (ft/min) = RPM x 11.06 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/8.99 10562 1.54 8.6 12701 2.05 10.7 14363 2.53 13.0 15691 2.98 14.6 19904 4.88 20 21806 6.02 24 23451 7.15 28 9246 1.92 8.5 12028 2.56 10.9 13652 3.07 12.8 18497 5.10 19.1 20544 6.25 23 22295 7.38 27 10151 2.82 10.6 16795 5.20 18.1 19112 6.43 21 21023 7.63 25 14802 5.16 17.6 17437 6.50 21 19561 7.75 24 15398 6.38 21 17884 7.77 24 15479 7.47 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 48 Roof Upblast/Sidewall Exhaust Size-480: CUBE 743⁄16 1.8 (1884) 350 1.4 RPM (Belt) HP 3 Density 0.075 lb/ft 3 Density 1.2 kg/m HP 1.6 5 400 RV E CU EM ST SY HIS FT TO EF EL 0 TH TO CT 5 25 22 0 5 0 SE DO 0 5 28 LE Static Pressure (Pa) 36 31 T 0.0 0 0 49 0.2 5 0.4 50 42 Static Pressure (in. wg) P 100 0.6 P CUBE 150 0.8 2H 1/ (1473) 200 1.0 1.2 P 1¾ (44) 58 250 H 3/4 (914) 300 P 2H P /2 H 11 P 1H 36 HP /2 71 3H *481⁄8 (1222) NO 20 5 10 15 20 25 30 Volume (cfm x 1000) 0 5 10 15 20 25 30 35 40 45 50 3 Volume (m /hr x 1000) All dimensions in inches (millimeters), weight in pounds (kilograms). * May be greater depending on motor. ^Weight shown is largest cataloged open drip-proof motor. Specifications and image for each model located at back of catalog. Motor HP Fan RPM 0 0.125 11016 0.33 5.5 12240 0.45 6.3 13770 0.65 7.5 15300 0.89 9.0 17442 1.31 11.1 19278 1.77 12.9 22032 2.64 16.8 24174 3.49 21 26010 4.35 22 28152 5.51 25 29988 6.66 28 8924 0.39 4.9 10490 0.53 5.8 12261 0.73 7.0 13988 0.98 8.5 16332 1.43 10.6 18274 1.90 12.5 21153 2.79 16.5 23373 3.65 20 25266 4.52 21 27464 5.70 24 29342 6.86 27 0.25 CUBE ^Approximate Weight Damper Size Roof/Wall Opening 675 (306) 48 x 48 (1219 x 1219) 50½ x 50½ (1283 x 1283) Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 1.25 1.5 480 180 1/2 200 3/4 225 1 250 11⁄2 285 2 315 3 360 395 5 425 460 71⁄2 490 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 7688 0.52 5.3 10132 0.76 6.6 12248 1.04 8.2 14991 1.52 10.0 17116 2.01 11.8 20222 2.93 16.1 22572 3.81 20 24521 4.69 21 26776 5.89 24 28697 7.06 27 MAXIMUM BHP AT A GIVEN RPM = (RPM/246)3 MAXIMUM RPM = 490 TIP SPEED (ft/min) = RPM x 12.63 MAXIMUM MOTOR FRAME SIZE = 213T AVERAGE DISCHARGE VELOCITY (FPM) = CFM/11.72 9988 1.03 7.9 13240 1.55 9.6 15719 2.08 11.3 19142 3.05 15.3 21605 3.94 19.2 23679 4.85 20 26064 6.07 23 28051 7.26 26 11154 1.52 9.2 14033 2.09 10.4 17848 3.10 14.7 20621 4.07 18.5 22764 4.98 19.4 25219 6.22 22 27291 7.43 25 11996 2.03 10.2 16410 3.12 13.7 19343 4.11 17.6 21766 5.09 18.7 24373 6.37 22 26497 7.59 25 14749 3.08 12.7 18035 4.13 16.6 20556 5.12 17.7 23399 6.46 21 25704 7.75 24 14722 3.97 14.9 17922 5.09 15.6 21163 6.52 18.5 23674 7.85 22 18582 6.42 18.7 21437 7.84 20 18846 7.67 24 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels. 49 Direct Drive Specifications Model CUE Options and Accessories For Direct Drives UL/cUL Listed • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Curb Extensions • Shall be mounted between roof curb and roof mounted fans to meet NFPA requirements of 40-inches (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. Spun aluminum exhaust fans shall be upblast centrifugal direct drive type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be one-piece and 100% continuously welded to the one-piece aluminum curb cap. Grease Containers Motors shall be mounted out of the airstream on vibration isolators. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Easy Clean Options A disconnect switch shall be factory-installed and wired from the fan motor to a junction box within the motor compartment. A conduit chase shall be provided through the curb cap to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. Fans shall be model CUE or CUE-HP as manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. 50 • Drain connection shall be constructed of aluminum and allow for single-point drainage of grease, water or other residues. • Grease trap container shall be constructed from polypropylene. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. • Hinge kit shall be constructed of heavy-gauge aluminum hinges and shall include hold-open mechanism. • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. • Clean-Out Port shall have a hole on the outside of the windband and a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Windband Extension • Shall be constructed from heavy-gauge aluminum tube that raises the fan discharge height. Belt Drive Specifications Model CUBE Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength and shall be joined to the curb cap with a continuously welded seam. Fans shall be model CUBE, CUBE-HP or CUBE-XP as manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. Options and Accessories For Belt Drives UL/cUL Listed Spun aluminum exhaust fans shall be centrifugal belt-driven type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be one-piece and 100% continuously welded to the one-piece aluminum curb cap, including all sizes with UL/cUL 762. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy-gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream where no steel-tosteel contact between rotating components and the base shall occur. Fresh air for motor cooling shall be drawn into the motor compartment through a tensquare-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L50 life of 500,000 hours) at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factoryinstalled and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Curb Extensions • Shall be mounted between roof curb and roof mounted fans to meet NFPA requirements of 40-inches (1016 mm) minimum discharge above the roof when mounted on a minimum 8-inch (203 mm) high roof curb. Grease Containers • Drain connection shall be constructed of aluminum and allow for single-point drainage of grease, water or other residues. • Grease trap container shall be constructed from polypropylene. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. Easy Clean Options • Hinge kit shall be constructed of heavy-gauge aluminum hinges and shall include hold-open mechanism. • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. • Clean-Out Port shall have a hole on the outside of the windband and a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Windband Extension • Shall be constructed from heavy-gauge aluminum tube that raises the fan discharge height. 51 Belt Drive Specifications Model USGF Ultimate Steel Grease Fan Precision ground and polished 1-inch minimum diameter fan shafts shall be mounted in cast pillow block lubricatable ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours) at maximum cataloged operating speed. Dual drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. All fans shall have a dual belt and pulley system. A NEMA-3R disconnect switch shall be factory-installed and wired from the fan motor to a junction box installed outside the motor compartment. Spun steel exhaust fans shall be centrifugal beltdriven type. Fan wheel shall be centrifugal backwardinclined type. The wheel shall be constructed of steel and coated with a non-stick coating similar to Teflon® as manufactured by DuPont™. Wheel shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of 16-gauge steel with a rigid internal support structure and shall be leakproof. The fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength and shall be joined to the curb cap with a continuously welded seam. The fan windband shall have a Clean-Out Port, a 4-inch diameter hole on the outside of the fan’s windband with a grease repellent compression rubber fit, allowing access to entire wheel for cleaning. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavygauge galvanized steel. Motors and drives shall be mounted on heavy-duty true vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment through a tensquare-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. 52 All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 Listed for all electrical components and grease removal. Hinged base shall be constructed of heavy-gauge hinges and shall include hold-open cables for field installation. Grease trap container shall be constructed from polypropylene. The unit shall collect grease and water from the fan and extract the grease from the water for ease of grease disposal. Fans shall be model USGF as manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. Direct Drive Specifications Model CW A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. Fan shall be provided with a mounting plate, which is to be attached and sealed to the wall prior to locating the entire unit. Fans shall be model CW or CW-HP as manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. Options and Accessories For Direct Drives UL/cUL Listed Spun aluminum exhaust fans shall be upblast centrifugal direct drive type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. Motors shall be mounted out of the airstream on vibration isolators. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube, free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. A disconnect switch shall be factory-installed and wired from the fan motor to a junction box within the motor compartment. A conduit chase shall be provided through the curb cap to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Easy Clean Options • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. 53 Belt Drive Specifications Model CWB Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. A conduit chase shall be provided through the base to the motor compartment for ease of electrical wiring. All fans shall bear the AMCA Sound and Air Performance seal. Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number for future identification. Spun aluminum exhaust fans shall be centrifugal belt-driven type. The fan wheel shall be centrifugal backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy-gauge aluminum with a rigid internal support structure. The windband shall be welded to the one-piece curb cap and on all sizes with UL/cUL 762. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. Drive frame assembly shall be constructed of heavy-gauge steel. Motors and drives shall be mounted on vibration isolators, out of the airstream where no steel-to-steel contact between rotating components and the base shall occur. Fresh air for motor cooling shall be drawn into the motor compartment through a ten-square-inch tube free of discharge contaminants. Motors and drives shall be readily accessible for maintenance. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours) at maximum catalogued operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the cast type, keyed and securely attached to the wheel and motor shafts. 54 A leakproof fan housing shall be constructed with a one-piece windband with an integral rolled bead for added strength. Fan shall be provided with a mounting plate, which is attached and sealed to the wall prior to locating the entire unit. Fans shall be model CWB or CWB-HP as manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. Options and Accessories For Belt Drives UL/cUL Listed • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for all electrical components. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 762 for all electrical components and grease removal. Easy Clean Options • Non-stick wheel shall be constructed of aluminum with a non-stick coating similar to Teflon® as manufactured by DuPont™. Severe Duty Specifications Smoke Control Seismic Fan wheel shall be centrifugal backward-inclined, constructed of steel and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Fans shall meet International Building Code (IBC) and the California Office of Statewide Health Planning and Development (OSHPD) requirements for seismic certifications as listed. • Dual drives shall be sized for a minimum of 150% • All Greenheck seismically certified models shall of driven horsepower. • A NEMA-3R disconnect switch shall be factoryinstalled and wired from the fan motor to a junction box installed outside the motor compartment. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for electrical components and UL/ cUL Listed for Emergency Smoke Control Systems [500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes]. be tested to the most severe seismic event on the Spectral Response Map per IBC Figures 1613.5 (1-2). Testing shall be performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor. • Fans shall be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces as experienced during a seismic event. Fans shall be Greenheck model CUE and CUBE specified on pages 50 and 51 and model CW and CWB specified on pages 53 and 54 with seismic rated construction option and manufactured in the USA by Greenheck Fan Corporation headquartered in Schofield, Wisconsin. Fans shall be Greenheck model CUBE and USGF as specified on pages 51 and 52 with smoke control rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. High Wind Fans shall meet all Greenheck wind load standards and shall contain the following third-party certifications: • Miami-Dade Certification • • • • (CUE, CUBE, CW, CWB, USGF) Licensed P.E. calculations shall be available for fan per ASCE 7-05 Minimum Design Loads for Buildings and Other Structures for exposure Class C, 60 foot building height, and a type II building. Fan shall be tested in accordance with ASTM E-330-02 Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference and Florida Building Code Test Protocol TAS-201, 202 and 203 at the ASCE 7-05 calculated design pressure. Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-05 determined design pressure. All calculations and testing shall be done by a state licensed P.E. and a certified test lab. Fans shall be Greenheck model CUE, CUBE, USGF, CW and CWB as specified on pages 50 through 54 with high wind-resistant construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 55 Quick Delivery and Quick Build Programs Greenheck Fan Corporation offers an extensive selection of Quick Delivery (QD) and Quick Build (QB) offerings. The QD program is Greenheck’s stock program and the QB program offers configurable fans in 1, 3, 5, 10, 15 or 25 days. Model Hundreds of in stock ventilation products and accessories are available for shipment to your jobsite in less than 24 hours from our strategically located warehouses throughout the world. The Greenheck Stock and Quick Build catalog is a great resource for specific options and accessories available with QD and QB fans. Size CUE 080 through 121, 141 CW 070 through 095, 101, 121 and 141 CUBE 099 through 121, 141 through 200, 240 & 300 High Pressure CUBE 141HP and 180HP all CUE, CW 060 through 200 CUBE 099, 131, 220, 360 through 480 CWB 099 through 131, 161, 200 through 300 High Pressure CUE, CW 141HP through 180HP High Pressure CUBE 101HP, 161HP, 200HP, 220HP, 300HP & 360HP High Pressure CWB 101HP through 300HP Extended Pressure CUBE 161XP through 360XP Best Available Program In Stock 1 Day Building Value in Air Greenheck delivers value to mechanical engineers by helping them solve virtually any air quality challenges their clients face with a comprehensive selection of top quality, innovative airrelated equipment. We offer extra value to contractors by providing easy-to-install, competitively priced, reliable products that arrive on time. And building owners and occupants value the energy efficiency, low maintenance and quiet dependable operation they experience long after the construction project ends. Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature. P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Prepared to Support Green Building Efforts 00.F&V.1003 R5 11-2018 SP Copyright © 2018 Greenheck Fan Corp.