user`s guide phases and zero sequence over current digital multi

Anuncio
USER’S GUIDE
PHASES AND ZERO SEQUENCE
OVER CURRENT
DIGITAL MULTI-FUNCTION RELAY
NPI 800 AND NPID 800
ICE - 11, rue Marcel Sembat - 94146 ALFORTVILLE CEDEX - France
TEL. : (33) 01 41 79 76 00 - FAX : (33) 01 41 79 76 01 – E-MAIL : [email protected]
SITE WEB : www.groupeice.com
User’s Guide
NPI 800 – NPID 800
Issue : b
File : A0333E1E
Date : 02/2004
This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization
PREFACE
This aim of this handbook is to provide to the User information useful for the operation of
NPI800 and NPID800 relays with the local MMI.
We advise you to read it carefully, in order to take note of the available functionalities and to
proceed to connection and power of the product in accordance with the provided
recommendations.
Locally, setting, commissioning and real time or event readings are accessible from keyboard
and displayed on the protection display.
To be fully exploited, the available functions must be parameterized and consulted with the
setting software PC – Protection, provided with the product.
Before any use, we recommend you to read the safety instructions of this User’s guide.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 1
Issue : b
CONTENTS
1.
SAFETY INSTRUCTIONS ____________________________________________________________ 3
DOCUMENTATION .................................................................................................................................... 3
CONNECTION OF NP800 RELAYS.............................................................................................................. 3
ON LOAD WITHDRAWAL ........................................................................................................................... 3
REMOVAL AND DESTRUCTION .................................................................................................................. 3
2.
PROTECTION AND OPERATION FUNCTIONS ________________________________________ 4
2.1
PROTECTION FUNCTIONS NPI800 AND NPID800..................................................................................... 4
2.2
OPERATION FUNCTIONS NPI800 AND NPID800....................................................................................... 4
2.3
PROTECTION AND OPERATION FUNCTIONS SPECIFIC TO NPID800............................................................ 4
2.4
LOCALLY AVAILABLE USER’S FUNCTIONS ............................................................................................... 4
2.5
REMOTELY AVAILABLE USER’S FUNCTIONS............................................................................................. 5
3.
FIRST USE__________________________________________________________________________ 6
3.1
DEFAULT SCREEN..................................................................................................................................... 6
3.2
PRESENCE OF A FAULT OR AN ALARM ...................................................................................................... 6
4.
GENERAL INFORMATION ON MENUS _______________________________________________ 7
4.1
SETTING MODE (IN / OUT) ........................................................................................................................ 7
4.2
MODIFICATION OF A PARAMETER............................................................................................................. 7
4.3
ACCESS CODE........................................................................................................................................... 8
4.4
ASSIGNMENT OF OUTPUT UNITS ............................................................................................................... 8
5.
MENU LIST_________________________________________________________________________ 9
5.1
ACCESS TO MAIN MENUS .......................................................................................................................... 9
5.2
MEASUREMENT MENU.............................................................................................................................10
5.3
OVERCURRENT MENU .............................................................................................................................12
5.4
NEGATIVE SEQUENCE MENU ...................................................................................................................14
5.5
DIRECTIONAL MENU (ONLY NPID800) ...................................................................................................15
5.6
GENERIC FUNCTIONS MENU ....................................................................................................................16
5.7
THERMAL OVERLOAD MENU ...................................................................................................................16
5.8
CLOSING FUNCTION MENU ......................................................................................................................18
5.9
LOGICAL SELECTIVITY MENU ..................................................................................................................19
5.10 REMOTE CONTROL MENU ........................................................................................................................20
5.11 DISTURBANCE RECORDING MENU ...........................................................................................................20
5.12 COUNTERS MENU ....................................................................................................................................21
5.13 OPERATION MENU ...................................................................................................................................22
5.14 MODBUS® COMMUNICATION MENU (OPTIONAL) ....................................................................................23
5.15 CHANGE OF CODE MENU .........................................................................................................................23
5.16 INFORMATION MENU ...............................................................................................................................23
6.
CONTENT OF AN EVENT___________________________________________________________ 24
6.1
EVENTS GENERATED ON 51/50/51N/50N/46 THRESHOLDS (NPI800)......................................................24
6.2
EVENTS GENERATED ON 51/50/51N/50N/67/67N/46 THRESHOLDS (NPID800)......................................25
6.3
THERMAL OVERLOAD EVENT ..................................................................................................................25
6.4
CUSTOMIZED INPUTS EVENTS ..................................................................................................................27
6.5
OTHER EVENTS .......................................................................................................................................27
6.6
ACKNOWLEDGEMENT OF EVENTS ...........................................................................................................27
6.7
READING OF THE LAST 250 MEMORIZED EVENTS ....................................................................................27
7.
LIST OF FAULTS OR OPERATION MESSAGES_______________________________________ 28
1.1
1.2
1.3
1.4
8.
8.1
8.2
8.3
8.4
8.5
CONNECTION OF NPI800 AND NPID800 PROTECTIONS ______________________________ 29
DESCRIPTION OF THE TERMINAL BLOCKS ................................................................................................29
CONNECTIONS.........................................................................................................................................30
DIAGRAMS ..............................................................................................................................................30
CONNECTION OF THE CURRENT INPUTS ...................................................................................................31
CONNECTION OF THE MODBUS RS485 COMMUNICATION .......................................................................31
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 2
Issue : b
1.
Safety instructions
For your safety, we recommend you to read the following information carefully. They have
the aim of specifying the precautions essential to the good installation and the correct
operation of the relays.
1.1 Documentation
Following documentations are available for the products of the range NP800:
♦ General Presentation of the NP800 range
♦ User’s Guide of Setting Software for NP800 range
♦ User’s Guide (for each kind of relay)
♦ First Handling Guide (for each kind of relay)
♦ Diagram of each relay.
We advise you to read them before any handling.
1.2 Connection of NP800 relays
The terminal blocks of the relays are studied to ensure the safety of the people during the
operation of the relays.
During installation, commissioning or maintenance, they can however present high voltages
and possibly a thermal heating. Consequently, the following precautions must be respected:
♦ Connection of the terminal blocks at installation must be carried out after having
ensured of the absence of any voltage
♦ Their access during operation must be carried out through adequate means ensuring
as well electric as thermal insulation
♦ The connection of the earth at the back of the relays must imperatively be done with
mean of a 2.5 mm² wire.
Before powering the relays, it will be necessary to check in particular:
♦ The value of the voltage rating of the auxiliary supply and its polarization
♦ The tightening of the intensity circuits and the good realization of connections
♦ The integrity of the connection to the earth.
1.3
On load withdrawal
It is formally misadvised to withdraw the connectors, in particular the current terminal blocks,
under voltage or on load.
1.4 Removal and destruction
The relays should in no case be opened by the User. During their removal, they must be
completely isolated from any external polarity and condensers must be discharged by
connecting their external terminals to the earth.
Destruction of the relays will have to be carried out in accordance with legislation in force, in
particular in compliance with the environment and safety requirements.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 3
Issue : b
2.
Protection and operation functions
2.1
Protection functions NPI800 and NPID800
♦ Three-phase over-current protection, with two ANSI 51 thresholds and one ANSI 50
threshold
♦ Earth fault over current protection, with one ANSI 51N threshold and one ANSI 50N
threshold
♦ Inverse over-current protection with one ANSI 46 threshold for the detection of
unbalance
♦ Negative phase sequence current ratio protection with one ANSI 46BC threshold for
the detection of the broken conductors
unbalancer atio =
.
I .negativese quence
I . positivesequencedire ct
♦ ANSI 49 Thermal overload function. Two models, transformer (with inhibition of
closing on load) or wire, are available
♦ Logic selectivity function on the phases and earth-fault thresholds
♦ Closing function to avoid spurious trips when closing the circuit breaker
♦ ANSI 50BF circuit breaker failure function by checking of the disappearance of the
phases and earth-faults currents (optional function, consult us).
2.2
Operation functions NPI800 and NPID800
♦
♦
♦
♦
♦
♦
♦
♦
Two setting groups
Assignment of digital inputs
Assignment of relay outputs
User programmable LEDs
Monitoring of trips and reclosings
Help in circuit breakers maintenance: number of operations with alarm threshold
Storage of the last 250 events
Storage of four 52 periods disturbance recordings, according to COMTRADE
standard
♦ 8 User configurable generic functions.
2.3
Protection and operation functions specific to NPID800
♦ ANSI 67 phases and ANSI 67N earth-fault Directional functions, applicable to ANSI
50 and ANSI 51protections
♦ Network frequency Measure
♦ Voltage Measure
♦ Power and energy Counters.
2.4
Locally available User’s functions
Locally, the following functions are available:
♦ Choice of language
♦ Setting in or out of order of the functions
♦ Customized identification of protection
♦ Setting of adjustment and primary values for the two tables
♦ Assignment of the inputs / outputs
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 4
Issue : b
♦
♦
♦
♦
♦
♦
2.5
Reading of fault values
Reading of each memorized value: measurements and counters
Reset of counters
Reading of events
Configuration of disturbance recording and local trigger
Configuration of Modbus® communication.
Remotely available User’s functions
The following functionalities can be accessed through the RS232 or RS485 links:
♦ Saving of configuration
♦ Commissioning tests: LCD display, adjustment of contrast, LEDs
♦ Commissioning tests: relays, wiring
♦ Reading of real time values: measurement and counters
♦ Reading of disturbance recordings.
These functions are however available with the setting software.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 5
Issue : b
3.
First use
When powering the relay, the displays below can appear. The recommended action allows
starting the parameter setting of protection.
3.1
Default screen
In absence of a fault, the protection displays the phase 1 current measurement in HV value.
CURRENT I1
0.0 A
3.2
Presence of a fault or an alarm
If a fault or alarm occurs, a message indicates the type of fault.
When threshold is exceeded or when tripping, the following messages appear:
INSTANT. PHASE
THRESHOLD
Followed
by
>
TRIP PHASE
THRESHOLD >
Note: According to the type of fault, the message of the second line changes.
This message disappears at once after acknowledgement of the fault and is replaced by the
following message.
TRIP PH >
A
17/06 14:22:15
E
This message remains until the acknowledgement of the fault by the User.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 6
Issue : b
4.
General information on menus
All parameters can be accessed for reading. On the other hand, parameters are writeprotected by an access code requested on the first modification.
4.1
Setting mode (In / Out)
Press any key except CLEAR to enter in setting mode.
If no parameter has been modified, exit the mode by pressing the CLEAR key:
, MAIN MENU
CLEAR
ENTER MEASUREMENTS
CURRENT I1
0.0 A
CURRENT I1
CLEAR
0.0 A
If a parameter has been modified, confirm the exit from setting mode:
MAIN MENU
CLEAR
OVER CURRENT
QUIT SETTINGS
MODE ?
ENTER
CURRENT I1
0.0 A
Without any operation, return to exploitation mode is carried out automatically after 5
minutes.
4.2
Modification of a parameter
Use the "
parameter
" and "
" keys to select a menu then press the ENTER key to access the first
MAIN MENU
MAIN MENU
MEASUREMENTS
OVER CURRENT
Use the "
" and "
PHASE
SETTING
ENTER
set 1
" keys to access the various parameters in the menu::
I>
DELAY TYPE
Active
tI>
DEFINITE
Definite
tI>
0.60 s
Use the and keys to modify the parameter.
You must confirm your change using the ENTER key after each parameter modification.
After storing the new parameter value, next parameter is displayed:
DEFINITE
tI>
DEFINITE
0,60 s
0,70 s
Use the CLEAR and
THRESHOLD
tI>
ENTER
THRESHOLD
I>
0,5 * In
to change menu :
I>
0,5 * In
CLEAR
MAIN MENU
MAIN MENU
OVER CURRENT
NEG.SEQUENCE I2>
Leaving any sub menu with the CLEAR key will lead to the above menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 7
Issue : b
4.3
Access code
On first modification of a parameter, the software requests the access code.
The factory-programmed code is " ICE1 ".
To enter your own personalised code, use the " CHANGE CODE " menu. The code can be
composed up to four alphanumeric characters.
The following example shows how to replace code "AA" with " 99 ":
MAIN MENU
CHANGE CODE
ENTER
NEW PASSWORD
OLD PASSWORD
OLD PASSWORD
OLD PASSWORD
OLD PASSWORD
_
A
A_
AA
NEW PASSWORD
_
NEW PASSWORD
9
NEW PASSWORD
9_
MAIN MENU
ENTER
99
ENTER
CHANGE CODE
In case of loss of the code, contact us to obtain an emergency password for your
configuration.
4.4
Assignment of output units
Relays assigned to a function are displayed with" * ".
Key " " allows modifying assignment of the relays.
Key
allows selection of next relay.
Example: assignment of relay B to TRIP U> function. At the beginning, no function was
assigned to this relay.
REL. TRIP
A_
B
ENTER
C
tI>
REL. TRIP
D
A
REL. TRIP
tI>
A
B_
C
B_
C
tI>
D
REL. TRIP
A
B
tI>
C
D
ENTER
REL. TRIP
E
F
G
D
Next parameter
Caution: do not to forget to confirm by ENTER key
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 8
Issue : b
tI>
5.
Menu list
5.1
Access to main menus
The following menus enable setting of the available functions. Each one allows access to the
parameters of adjustment and ensures their coherence.
CURRENT I1
Press on any key other than CLEAR Press on CLEAR key to
to enter the parameter setting mode leave the parameter setting
0.0 A
mode
ENTER, , , , ,
CLEAR
MAIN MENU
Real time measures
Use the or
keys to
select
a
menu
MEASUREMENTS
MAIN MENU
Parameters of the functions:
50, 50N, 51, 51N
OVER CURRENT
MAIN MENU
Parameters of the function 46.
NEG.SEQUENCE I2>
MAIN MENU
Parameters of the directional
(NPID800 only)
functions 67, 67N
DIRECTIONAL
MAIN MENU
Parameters of the customized
functions
GENERIC FUNCTION
MAIN MENU
Parameters of the thermal overload
function
THERMAL REPLICA
MAIN MENU
Parameters of the closing function
(reclosing)
CLOSING FCT
MAIN MENU
Parameters of the logic selectivity
option
LOG. SELECTIVITY
MAIN MENU
Parameters of the remote control
option
TELECONTROL
MAIN MENU
Information about disturbance
recording
PERTURBOGRAPHY
MAIN MENU
Information about counters
COUNTERS
MAIN MENU
Operating parameters to be defined
at commissioning
OPERATION
MAIN MENU
Configuration of the Modbus RS485 (if option available)
communication option
MODBUS COMMS
MAIN MENU
Change of the access code
CHANGE CODE
MAIN MENU
Information about protection
INFORMATION
MAIN MENU
Reading of the event log
EVENTS
Leaving any sub menu with the CLEAR key will lead to the above menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 9
Issue : b
5.2
Measurement menu
This menu displays any real time measurement of the protection, as well as the values kept
in memory.
MAIN MENU
MEASUREMENTS
ENTER / CLEAR
CURRENT I1
0,0 A
CURRENT I2
0,0 A
CURRENT I3
0,0 A
CURRENT Io
0,00 A
NEGATIVE SEQ.
0,0 A
POSITIVE SEQ.
0,0 A
FREQUENCY
50.00 Hz
THERMAL STATE I1
0,0 %
THERMAL STATE I2
0,0 %
THERMAL STATE I3
0,0 %
VOLTAGE U21
0V
VOLTAGE U32
0V
VOLTAGE Vr
0V
ACTIVE POWER
0 kW
REACTIVE POWER
0 kVAR
COS PHI
0,00 INDUCTIVE
AVERAGE ACTIVE P
0 kW
AVER. REACTIVE P
0 kVAR
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Available real time measures
Measure of the phase 1 primary
current
0.0 to 64000 A
Measure of the phase 2 primary
current
0.0 to 64000 A
Measure of the phase 3 primary
current
0.0 to 64000 A
Measure of the earth fault primary
current
0.0 to 6400 A
Measure of the negative phase
sequence current
0.0 to 64000 A
Measure of the positive sequence
current
0.0 to 64000 A
Measure of the network frequency
45 to 55 if Fn = 50 Hz
55 to 65 if Fn = 60 Hz
0.0 to 500 %
Measure of the thermal state phase
1
Measure of the thermal state phase
2
Measure of the thermal state phase
3
Measure of the U21 phase to
phase primary voltage
Measure of the U32 phase to
phase primary voltage
Measure of the residual primary
voltage
Measure of instantaneous active
power
0.0 to 500 %
(if cable thermal overload)
0.0 to 500 %
(if cable thermal overload)
0 to 640 000 V
(NPID 800 only)
0 to 640 000V
(NPID 800 only)
0 to 640 000V
(NPID 800 only)
(NPID 800 only)
Measure of instantaneous reactive
power
(NPID 800 only)
Measure of power-factor and
inductive or capacitive information
(NPID 800 only)
Value of the average active power
(NPID 800 only)
Value of the average reactive
power
(NPID 800 only)
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 10
Issue : b
AVER. CURRENT I1
0 A
AVER. CURRENT I2
0 A
AVER. CURRENT I3
0 A
AVER. CURRENT I0
0.0 A
SETTING
set 1
17/06/03
14:53:32
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Value of the average primary
current of phase 1
0 to 64 000 A
Value of the average primary
current of phase 2
0 to 64 000 A
Value of the average primary
current of phase 3
0 to 64 000 A
Value of the average earth-fault
primary current
0 to 64 000 A
Display of the active setting
Set 1 or Set 2
Day / Month / Year
Hour / minute / second
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 11
Issue : b
5.3
Overcurrent menu
This menu allows the setting of the phases and earth fault over current functions: setting in
and out of order, choice of the types of time delay and curves, adjustment of thresholds,
assignment of the output units.
This configuration must be carried out successively for each of the two settings groups if they
are to be used alternatively.
MAIN MENU
OVER CURRENT
ENTER / CLEAR
SETTING
set 1
PHASE
I>
Active
DELAY TYPE
tI>
Mod. Invers.ANSI
MOD. INV.ANSI tI>
0,03 s
THRESHOLD
I>
0,3 *In
REL. INST.
I>
A_ B
C D
REL. INST.
I>
E_ F
G
REL. TRIP
tI>
A_ B
C D
REL.TRIP
tI>
E_ F
G
PHASE
I>>
Active
DELAY TYPE
tI>>
Mod. Invers. ANSI
MOD. INV.ANS tI>>
0,03 s
THRESHOLD
I>>
0,3 *In
REL. INST.
I>>
A_ B
C D
REL. INST.
I>>
E_ F
G
REL. TRIP
tI>>
A_ B
C D
REL.TRIP
tI>>
E_ F
G
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the ANSI 50, 50N, 51,
51N functions
Choose the setting group
Set 1 or Set 2
Choose Active to use the phase low
threshold ANSI 51-1 function
Active or Inactive
Select the type of time delay: independent; CEI : Inverse, Very inv,
Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv
Set the value of the time delay.
Independent : 0.04 to 300 s
Set the value of the threshold
RI Inverse.: 0.1 to 20 s
CEI and ANSI : 0.03 to 3 s
0.3 to 24.0 * In
Relay to assign to the instantaneous
function
Relay to assign to the instantaneous
function
Relay to assign to the trip function
Relay to assign to the trip function
Choose Active to use the phase high Active or Inactive
threshold ANSI 51-2 function
Select the type of time delay: independent; CEI : Inverse, Very inv,
Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv
Set the value of the time delay.
Independent : 0.04 to 300 s
Set the value of the threshold
RI inverse : 0.1 to 20 s
CEI and ANSI : 0.03 to 3 s
0.3 to 24.0 * In
Relay to assign to the instantaneous
function
Relay to assign to the instantaneous
function
Relay to assign to the trip function
Relay to assign to the trip function
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 12
Issue : b
PHASE
I>>>
Active
DEFINITE tI>>>
0,04 s
THRESHOLD I>>>
0,3 *In
REL. INST.
I>>>
A_ B
C D
REL. INST.
I>>>
E_ F
G
REL. TRIP tI>>>
A_ B
C D
REL.TRIP
tI>>>
E_ F
G
EARTH LOW
Io>
Active
DELAY TYPE tIo>
Mod. Invers. ANSI
MOD. INV.ANS tIo>
0,03 s
THRESHOLD
Io>
0,03 *In
REL. INST.
Io>
A_ B
C D
REL. INST.
Io>
E_ F
G
REL. TRIP
tIo>
A_ B
C D
REL.TRIP
tIo>
E_ F
G
EARTH HIGH Io>>
Active
DEFINITE tIo>>
0,04 s
THRESHOLD Io>>
0,03 *In
REL. INST.
Io>>
A_ B
C D
REL. INST.
Io>>
E_ F
G
REL. TRIP tIo>>
A_ B
C D
REL.TRIP
tIo>>
E_ F
G
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Choose Active to use the phase very
high threshold ANSI 50
Active or Inactive
Set the value of the time delay
Independent : 0.04 to 300 s
Set the value of the threshold
0.3 to 24.0 * In
Relay to assign to the instantaneous
function
Relay to assign to the instantaneous
function
Relay to assign to the trip function
Relay to assign to the trip function
Choose Active to use the earth low
threshold ANSI 51N function
Active or Inactive
Select the type of time delay: independent; CEI : Inverse, Very inv,
Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv
Set the value of the time delay
Independent : 0.04 to 300 s
Set the value of the threshold
RI Inverse : 0.1 to 20 s
CEI and ANSI : 0.03 to 3 s
0.03 to 2.40 * In
Relay to assign to the instantaneous
function
Relay to assign to the instantaneous
function
Relay to assign to the trip function
Relay to assign to the trip function
Choose Active to use the earth high
threshold ANSI 50N function
Active or Inactive
Set the value of the time delay
0.04 to 300 s
Set the value of the 50N function
threshold
0.03 to 2.40 * In
Relay to assign to the instantaneous
function
Relay to assign to the instantaneous
function
Relay to assign to the trip function
Relay to assign to the trip function
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 13
Issue : b
5.4
Negative sequence menu
MAIN MENU
NEG.SEQUENCE I2>
ENTER / CLEAR
SETTING
set 1
FUNCTION
I2>
Active
DELAY TYPE
I2>
Mod. Invers. ANSI
MOD.INV.ANSI I2>
0,10 s
THRESHOLD
I2>
0,1 *In
REL. INST.
I2>
A_ B
C
D
REL. INST.
I2>
E_ F
G
REL. TRIP.
I2>
A_ B
C D
REL. TRIP.
I2>
E_ F
G
FUNCTION
I2/I1>
Inactive
DEFINITE tI2/I1>
0,04 s
THRESHOLD I2/I1>
0,10
REL. INST
I2/I1>
A_ B
C
D
REL. INST
I2/I1>
E_ F
G
REL. TRIP I2/I1>
A_ B
C D
REL. TRIP I2/I1>
E_ F
G
FUNCTION I2/I1>>
Inactive
DEFINIT. tI2/I1>>
0,04 s
THRESHOLD I2/I1>>
0,10
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the phase unbalance
function
Choose the setting group
Set 1 or Set 2
Choose Active to use the maximum
of negative phase sequence function
Active or Inactive
Select the type of time delay: independent; CEI : Inverse, Very inv,
Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv
Set the value of the time delay.
Independent : 0.04 to 300 s
Set the value of the threshold
RI : 0.1 to 20 s
CEI and ANSI: 0.03 to 3 s
0.1 to 24.0 * In
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Choose Active to use the unbalance
ratio low threshold
Active or Inactive
Set the value of the time delay
0.04 to 300.00s
Set the value of the threshold
0.10 to 2.50
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Choose Active to use the unbalance
ratio high threshold
Active or Inactive
Set the value of the time delay
0.04 to 300.00s
Set the value of the threshold
0.10 to 2.50
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 14
Issue : b
REL. INST I2/I1>>
A_ B
C
D
REL. INST I2/I1>>
E_ F
G
REL. TRIP I2/I1>>
A_ B
C D
REL. TRIP I2/I1>>
E_ F
G
5.5
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Relay to assign to the trip function
Directional menu (only NPID800)
This menu allows the parameter setting of the phase or earth-fault directional functions:
setting in and out of order, choice of angles and threshold of polarization.
MAIN MENU
DIRECTIONAL
ENTER / CLEAR
SETTING
set 1
PHASE DIREC.
>
Inactive
PHASE DIREC. >>
Inactive
PHASE DIREC. >>>
Inactive
ANGLE PHASE DIR.
180 °
EARTH LOW DIREC.
Inactive
EARTH HIGH DIREC.
Inactive
ANGLE EARTH DIR.
180 °
POLARISATION Vo
3 % Vn
INHIB. EARTH DIR.
Inactive
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the phase and earth
directional functions
Choose the setting group
Set 1 or Set 2
Choose Active to use the phase low
threshold directional function
Active or Inactive
Choose Active to use the phase high
threshold directional function
Active or Inactive
Choose Active to use the phase very
high threshold directional function
Active or Inactive
Adjustment of the directional angle of -180 ° to 180 °
the phase
Choose Active to use the earth low
threshold directional function
Active or Inactive
Choose Active to use the earth high
threshold directional function
Active or Inactive
Adjustment of the directional angle of -180 ° to 180 °
the earth
Set the value of the threshold of
polarization
3 to 20 % Vn
Choose Active to inhibit the earth
directional function when Vn < Vo
Active or Inactive
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 15
Issue : b
5.6
Generic functions menu
This menu allows the parameter setting of 8 customized functions: setting in and out of order,
adjustment of the time delays, assignment of the output units, assignment of a logical input.
MAIN MENU
GENERIC FUNCTION
ENTER / CLEAR
FCT GENERIC 1
Inactive
TEMP GENERIC 1
0,06 s
RELAY GENERIC 1
A_ B
C
D
RELAY GENERIC 1
E_ F
G
DIG.INP.GENER. 1
No input
NAME GENERIC 1
GENERIC 1
……………
5.7
Parameters of the customized
functions
Choose Active to use function 1
Active or Inactive
Set the time delay of function 1
0.04 to 300.00s
Relay to assign to function 1
Relay to assign to function 1
Display of input selected for function 1
(configurable with the
setting software)
Display of label of function 1
(configurable with the
setting software)
Thermal overload menu
This menu authorizes the parameter setting of the thermal overload function: setting in and
out of order, type of thermal overload, adjustment of the thermal time-constant, adjustment of
the thermal trip and alarm thresholds, assignment of the output units for alarm and trip.
MAIN MENU
THERMAL REPLICA
ENTER / CLEAR
SETTING
set 1
THERMAL TYPE
CABLE
THERMAL STATE
Active
TH. TIME CONST.
4 mn
TH.TRIP THRES Ib
1,00 *In
TH. TRIP RELAY
A_ B
C
D
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the thermal overload
option
Choose the setting group
Set 1 or Set 2
Choose the type of device to protect
Cable or transformer
Choose Active to use thermal
overload function
Active or Inactive
Set the value of the thermal overload
time-constant
4 to 180 min
Set the thermal trip threshold Ib
0.40 to 1.30 * In
Select the relays for thermal
overload trip
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 16
Issue : b
TH. TRIP RELAY
E_ F
G
TH.ALARM THRESH.
80 %
TH. ALARM RELAY
A_ B
C
D
TH. ALARM RELAY
E_ F
G
See note.
HOT START
Active
HOT START THRESH
40 %
START RELAY
A_ B
C
D
START RELAY
E_ F
G
Select the relays of thermal overload
trip
Set the thermal alarm threshold
80 to 100 % Ib
Select the relays to be assigned to
the thermal alarm function
Select the relays to be assigned to
the thermal alarm function
Choose Active to use Inhibition of
hot motor starting
Active or Inactive
Setting of the threshold of inhibition
of hot motor starting
40 to 100 %
Set the relays Inhibition of hot motor
starting
Set the relays Inhibition of hot motor
starting
Note: For a choice of Transformer thermal overload, an additional sequence of parameter
setting is to be intercalated described as follows:
TH. ALARM. RELAY
Select the relays to be assigned to
the thermal alarm function
E_ F
G
former parameter
COOLING CONST
1,0 * HEAT CST.
START FACTOR
50 %
NEG. SEQ. FACTOR
3
Next parameter
HOT START
Inactive
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Set the cooling constant
1.0 to 6.0 * heating constant
Set the coefficient calculation of the
thermal overload (starting mode)
50 to 100 %
Set the negative sequence factor K
(thermal heating)
0 to 9
Choose Active to
overload function
use
User’s Guide
NPI 800 and NPID 800
thermal Active or Inactive
Date : 01/2004
Print :11/03/2004
Sheet : 17
Issue : b
5.8
Closing function menu
This menu authorizes the parameter setting of the closing function: time delay of start,
assignment of a logical input.
MAIN MENU
CLOSING FCT
ENTER / CLEAR
CLOS. MODE TIME
0,06 s
CLOS. MODE RATIO
50 %
PHASE
I>>>
Inactive
PHASE
I>>
Inactive
PHASE
I>
Inactive
EARTH HIGH Io>>
Inactive
EARTH LOW
Io>
Inactive
FUNCTION
I2>
Inactive
FUNCTION
I2/I1>>
Inactive
FUNCTION
I2/I1>
Inactive
CLOS. MODE INPUT
No input
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the closing function
Set the start time delay
0.04 to 300.00 s
Set the start ratio
50 to 200 %
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
Choose Active to modify the
threshold during start
Active or Inactive
ODisplay of the selected logical input
User’s Guide
NPI 800 and NPID 800
(configurable with the
setting software)
Date : 01/2004
Print :11/03/2004
Sheet : 18
Issue : b
5.9
Logical selectivity menu
This menu authorizes the parameter setting of the logical selectivity function: setting in and
out of order, adjustment of the time delays, operating mode.
MAIN MENU
LOG. SELECTIVITY
ENTER / CLEAR
SETTING
set 1
PHASE S.LOG.
I>
Inactive
PHASE S.LOG.
I>
0,06 s
PHASE S.LOG. I>>
Inactive
PHASE S.LOG. I>>
0,06 s
PHASE S.LOG. I>>>
Inactive
PHASE S.LOG. I>>>
0,06 s
EARTH LOW S.LOG.
Inactive
EARTH LOW S.LOG.
0,06 s
EARTH HIGH S.LOG
Inactive
EARTH HIGH S.LOG
0,17 s
DIG INPUT S. LOG.
No input
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Parameters of the logical selectivity
option
Choose the setting group
Set 1 or Set 2
Choose Active to use the phase low
threshold
Active or Inactive
Set time delay of the phase low
threshold function
0.06 to 120.00 s
Choose Active to use the phase high
threshold
Active or Inactive
Set time delay of the phase high
threshold function
0.06 to 120.00 s
Choose Active to use the phase very
high threshold
Active or Inactive
Set time delay of the phase very high
threshold function
0.06 to 3.00 s
Choose Active to use the earth low
threshold
Active or Inactive
Set time delay of the earth low
threshold function
0.06 to 120.00 s
Choose Active to use the earth high
threshold
Active or Inactive
Set time delay of the earth high
threshold function
0.06 to 3.00 s
Display of the logical input selected
for the function
(configurable with the
setting software)
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 19
Issue : b
5.10 Remote control menu
This menu authorizes the parameter setting of the remote control function: setting in and out
of order, level of load-shedding, adjustment of the time delay of reconnection, assignment of
the trip and reclosing relays, pulse of reclosing, assignment of the logical inputs.
MAIN MENU
Information about remote control
option
TELECONTROL
ENTER / CLEAR
TELECONTROL
Choose Active to use the remote
Active or Inactive
control
function
Inactive
LOAD SHED LEVEL
Set the level of load-shedding. Level 1 to 6 (pas de 1)
6 inhibits the load-shedding function
6
RE-LOAD DELAY
Set the value of time delay before
1.00 to 120.00 s
reclosing
1,00 s
TRIP RELAY
Select the relays to be assigned to
the
trip
A_ B
C
D
TRIP RELAY
Select the relays to be assigned to
the
trip
E_ F
G
RECLOSE RELAY
Select the relays to be assigned to
the reclosing
A_ B
C
D
RECLOSE RELAY
E_ F
G
RECLOSE PULSE
200 ms
O/O INPUT
Input 1
C/O INPUT
Input 2
LOCAL INPUT
Input 3
DISTANT INPUT
Input 4
Select the relays to be assigned to
the reclosing
Set the reclosing pulse
100 to 500 ms
Display of the logical input assigned
to the position of the interlock
(configurable with the setting
software)
Display of the logical input assigned
to the position of the interlock
(configurable with the setting
software)
Display of the logical input assigned
to the mode of exploitation
(configurable with the setting
software)
Display of the logical input assigned
to the mode of exploitation
(configurable with the setting
software)
5.11 Disturbance recording menu
This menu is used to configure the parameters of the disturbance recording.
MAIN MENU
Parameters of the disturbance
recording function
PERTURBOGRAPHY
ENTER / CLEAR
PRE-TIME
35 period(s)
PERTURBO. INPUT
No input
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Set pre time
1 to 52
Display of input assigned to external
trip
(configurable with the
setting software)
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 20
Issue : b
5.12 Counters menu
This menu allows the parameter setting of the counters: display of cut A², number of circuit
breaker operations, energies, current maximeters, power maxima, restoring of the counters.
MAIN MENU
Parameters of the counters function
COUNTERS
ENTER / CLEAR
A2 CUTOFF I1
Display of cut A² of phase 1
0,0 kA2
A2 CUTOFF I2
Display of cut A² of phase 2
0,0 kA2
A2 CUTOFF I3
Display of cut A² of phase 3
0,0 kA2
RESET A2 CUTOFF
Reset of cut A² with ENTER key
Confirm: ENTER
NBER OPERATIONS
Display of the number of operations
of the circuit breaker
0
RESET NB OPERAT.
Reset of the number of operations of
the circuit breaker
Confirm: ENTER
ACTIVE ENERGY +
505368 MWh
ACTIVE ENERGY 2365269 MWh
REACTIV. ENERGY +
489312 MVARh
REACTIV ENERGY 726394 MVARh
ENERGY RESET
confirm : ENTER
MAX. METER I1
1049 A
MAX. METER I2
1056 A
MAX. METER I3
1048 A
MAX. METER I0
68,0 A
MAX. METER RESET
Confirm: ENTER
ACTIVE P MAX
-152438 kW
REACTIVE P MAX
23556 kVAR
RESET P MAX
Confirm: ENTER
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Display of positive active energy
Display of negative active energy
Display of positive reactive energy
Display of negative reactive energy
Reset of energy with ENTER key
Display of the current maximeter on
phase 1
Display of the current maximeter on
phase 2
Display of the current maximeter on
phase 3
Display of the current maximeter on
earth
Reset of current maximeter with
ENTER key
Display of the maximum of active
power
Display of the maximum of reactive
power
Reset of P power maximeter with
ENTER key
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 21
Issue : b
5.13 Operation menu
This menu authorizes the parameter setting of the operation function: choice of the language,
adjustment of LCD contrast, parameter setting of the values of the phase and earth-fault
CTs, parameter setting of the rated primary and secondary voltage of the VTs, display of the
input logical corresponding to set 2, trip pulse, maximum of cut A² and number of operations
of the circuit breaker, assignment of the relays for circuit breaker failure and discrepancy,
average current and power.
MAIN MENU
OPERATION
ENTER / CLEAR
LANGUAGE
English
ADJUST LCD
200
I NOMINAL PRIM.
1000 A
Io NOMINAL PRIM.
100 A
U NOMINAL PRIM.
1000 V
U NOMINAL SECOND
110 V
SET 2 INPUT
Input 6
CLEAR REL. INPUT
Input 5
TRIP PULSE
100 ms
MAX A2 CUTOFF
5000000 kA2
MAX NBER OPERAT.
9999
RELAY C.B. FAULT
A_ B
C
D
RELAY C.B. FAULT
E_ F
G
RELAY DISC. L/D
A_ B
C
D
RELAY DISC. L/D
E_ F
G
I and P AVERAGE
in 30 mn
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Operating parameters to be defined
at commissioning
Choice of the language used locally
by protection
French or English
Adjustment of the angle of vision of
the LCD display
70 to 255
Set the value of the phase primary
rated current of the CTs
1 to 10000 A
Set the value of the earth primary
rated current of the CT
1 to 10 000 A
Value of the phase to phase rated
primary voltage of phase VTs
220 to 250 000 V
Value of the phase to phase rated
secondary voltage of phase VTs
55 to 120 V
Display of input assigned to setting
group 2
No input, E1 to E8
Display of input assigned to reset of
relays
No input, E1 to E8
Setting of minimum duration of trip
pulse
100 to 500 ms
Adjustment of the maximum of cut A²
1 to 64 000 000 kA²
Adjustment of the maximum number
of operations of the circuit breaker
1 to 10000
Select the relay assigned to the
circuit breaker failure function
Select the relay assigned to the
circuit breaker failure function
Select the relay assigned to the
local/distant discrepancy function
Select the relay assigned to the
local/distant discrepancy function
(if remote control option)
Adjustment of the time for calculation 5 to 60 min
of average values and maximeters
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 22
Issue : b
5.14 Modbus® communication menu (optional)
This menu is used to set the parameters of the Modbus® communication function: slave
number, size, speed, activity and loop tests.
MAIN MENU
MODBUS COMMS
ENTER / CLEAR
SLAVE NUMBER
2
FORMAT
8b+0p+2s ASCII
Configuration of the Modbus
RS485 communication option
SPEED
9600 bauds
Speed transmission on RS485 link
RECEPT. TIMEOUT
0.10 s
ACTIVITY TIMEOUT
0.20 s
ACTIVITY TEST
Mess.Receiv.com1
Set the time delay of reception
timeout
Slave number of protection
1 to 255
number of bits + parity + bits of
stop + ASCII/Binary format
Parity: 1p = pair, 1i = odd,
0p= without
p0 = forced to 0, p1 =
forced to 1,
300, 600 ,1200 ,1800,
2400, 4800, 9600, 19200
38400, 57 600,115 200
bauds
0.10 to 20 s
Set the time delay of activity
timeout
0.10 to 20 s
Test of the parameter setting and
the wiring of Modbus
message received / not
received: correct activity /
communication problem
5.15 Change of code menu
This menu allows change of code and is described in chapter Access Code.
5.16 Information menu
Information menu specifies the factory set characteristics of the protection, as well as the
label assigned by the User.
MAIN MENU
INFORMATION
ENTER / CLEAR
NP.ID 800
50 Hz
PROC. VER. 1.22a
PHASES RAT. 1 A
EARTH RAT. 1 A
NP 800
ICE
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Information about protection
Type of protection
Rated frequency
Version of the software of
protection
Display of the phases and earth
ratings
32 characters zone programmable with the setting software.
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 23
Issue : b
6.
Content of an event
Events are different according to information recorded when fault occurs. There are three
different types of structures of event.
They can be read with the local MMI, the setting software (RS232 link) and the Modbus
communication network.
6.1
Events generated on 51/50/51N/50N/46 thresholds (NPI800)
Events are recorded as soon as a trip or alarm threshold of the current functions is reached:
♦ INST PH >
INST PH >>
INST PH >>>
♦ INST Io HIGH
INST Io LOW
♦ INST I2 >
♦ INST I2/I1 >
♦ INST I2/I1 >>
♦ TRIP PH >
TRIP PH >>
TRIP PH >>>
♦ TRIP Io HIGH
TRIP Io LOW
♦ TRIP I2 >
♦ TRIP I2/I1 >
♦ TRIP I2/I1 >>
Detail of available information can be consulted for each event, in accordance with the list
below:
MAIN MENU
EVENTS
ENTER / CLEAR
TRIP PH >
E
17/06 14:22:00
R
17/06/03
14:22:00.990
SETTING
set 1
CURRENT I1
745 A
CURRENT I2
743 A
CURRENT I3
746 A
CURRENT Io
0.1 A
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
List of the last 250 events
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group
Set 1 or
Set 2
Current of phase 1 measured at disappearance of the trip
Current of phase 2 measured at disappearance of the trip
Current of phase 3 measured at disappearance of the trip
Zero-sequence current measured at disappearance of the
trip
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 24
Issue : b
6.2
Events generated on 51/50/51N/50N/67/67N/46 thresholds (NPID800)
Events are recorded as soon as a trip or alarm threshold of the current functions is reached:
♦ INST PH >
INST PH >>
INST PH >>>
♦ INST Io HIGH
INST Io LOW
♦ INST I2 >
♦ INST I2/I1 >
♦ INST I2/I1 >>
♦ TRIP PH >
TRIP PH >>
TRIP PH >>>
♦ TRIP Io HIGH
TRIP Io LOW
♦ TRIP I2 >
♦ TRIP I2/I1 >
♦ TRIP I2/I1 >>
Detail of available information can be consulted for each event, in accordance with the list
below:
TRIP PH >
17/06 14:22:00
17/06/03
14:22:00.990
SETTING
set 1
CURRENT I1
745 A
CURRENT I2
743 A
CURRENT I3
746 A
CURRENT Io
0.1 A
ANGLE Vp/I1
0°
ANGLE Vp/I3
0°
ANGLE Vp/Io
0°
6.3
E
R
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group when tripping
Set 1 or
Set 2
Phase 1 current measured at disappearance of the trip
Phase 2 current measured at disappearance of the trip
Phase 3 current measured at disappearance of the trip
Earth fault current measured at disappearance of the trip
Angle between the polarization voltage and I1, measured
at disappearance of the trip
Angle between the polarization voltage and I3, measured
at disappearance of the trip
Angle between the polarization voltage and I0, measured
at disappearance of the trip
Thermal overload event
Events are recorded as soon as a trip or alarm threshold of the voltage or frequency
functions is reached:
♦ TRIP THERM REP
♦ ALRM THERM REP
Detail of available information can be consulted for each event, in accordance with the list
below:
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 25
Issue : b
6.3.1 Thermal alarm
ALRM THERM REP S
17/06 13:25:55
R
17/06/03
13:25:55.240
SETTING
set 1
CURRENT I1
2484 A
CURRENT I2
0A
CURRENT I3
0A
CURRENT Io
0,0 A
THERMAL STATE I1
90,0 %
THERMAL STATE I2
0%
THERMAL STATE I3
0%
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group when tripping
Set 1 or
Set 2
Phase 1 current measured at appearance of alarm
Phase 2 current measured at appearance of alarm
Phase 3 current measured at appearance of alarm
Earth fault 1 current measured at appearance of alarm
Phase 1 thermal state measured at appearance of alarm
Phase 2 thermal state measured at appearance of alarm
Phase 3 thermal state measured at appearance of alarm
6.3.2 Thermal trip
TRIP THERM REP S
17/06 13:25:59
R
17/06/03
13:26:59.920
SETTING
set 1
CURRENT I1
2490 A
CURRENT I2
0A
CURRENT I3
0A
CURRENT Io
0,0 A
THERMAL STATE I1
100,0 %
THERMAL STATE I2
0%
THERMAL STATE I3
0%
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group when tripping
Set 1 or
Set 2
Phase 1 Current measured at appearance of trip
Phase 2 Current measured at appearance of trip
Phase 3 Current measured at appearance of trip
Earth fault Current measured at appearance of trip
Phase 1 thermal state measured at appearance of trip
Phase 2 thermal state measured at appearance of trip
Phase 3 thermal state measured at appearance of trip
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 26
Issue : b
6.4
Customized inputs events
Events are recorded as soon as one of the customized input status changes.
♦ TRIP GENERIC
Detail of available information can be consulted for each event, in accordance with the list
below:
GENERIC
17/06 13:42:23
17/06/03
13:42:23.240
SETTING
set 1
6.5
S
R
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day / Month / Year
Hour: Minute: Second. Millisecond
Active setting group
Set 1 or
Set 2
Other events
The contents of the following events can be specified:
♦ ALRM NB OPERAS
♦ ALRM A2 CUTOFF
♦ CB FAIL
♦ DISC LOCA/REMO
♦ MODE REMOTE
♦ UNLISTED EVENT
♦ SETTING SET 2
♦ TRIP TELECONTR
♦ RECLOSE TELECO
Detail of available information can be consulted for each event, in accordance with the list
below:
ALRM NB OPERAS S
25:6 9:35:45 R
25/6/95
9:35:45.011
SETTING
set 1
6.6
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day / Month / Year
Hour: Minute: Second. Millisecond
Active setting group
Set 1 or
Set 2
Acknowledgement of events
The acknowledgement of the last event is carried out while pressing on CLEAR key:
TRIP PH >
10/12 16:38.15
6.7
D
R
CLEAR
ACKNOWLEDGE ALL
Confirm: ENTER
ENTER
CURRENT I1
0,0 A
Reading of the last 250 memorized events
After acknowledgement, the memorized events still may be read. It is necessary to use the
local sub-menu EVENTS of the HMI.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 27
Issue : b
7.
List of faults or operation messages
The following messages are locally displayed in real time on LCD display throughout fault.
Messages related to instantaneous type functions:
INSTANT. PHASE THRESHOLD>,
INSTANT. PHASE THRESHOLD >>
INSTANT. PHASE THRESHOLD >>>
INSTANT. EARTH HIGH THRESHOLD
INSTANT. EARTH LOW THRESHOLD
Messages related to trip type functions:
TRIP PHASE THRESHOLD >>>
TRIP PHASE THRESHOLD >>
TRIP PHASE THRESHOLD >
TRIP EARTH HIGH THRESHOLD
TRIP EARTH LOW THRESHOLD
TRIP THERMAL REPLICA
TRIP BY TELECONTROL
TRIP GENERIC FUNCTION
Messages related to alarm type functions:
ALARM NUMBER OPERATIONS
ALARM A2 CUTOFF
CIRCUIT BREAKER FAIL
DISCORDANCE : LOCAL / REMOTE
ALARM THERMAL REPLICA
Various messages:
RECLOSE BY TELECONTROL
REMOTE MODE
UNLISTED EVENT
Note: disappearance of cut A² and number of operations alarms is done by resetting the
COUNTERS menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 28
Issue : b
8.
Connection of NPI800 and NPID800 protections
8.1
Description of the terminal blocks
Extension board (connectors E, F, G and RS485-2) is optional on the NPI800.
+
-
R S 485-1
E
1
F
7
S1
IA
A
S2
6
S1
1
IB
S2
1
5
B
G
5
1
S1
IC
C
1
S2
D
S1
I0
S2
7
-
+
-
R S 485-2
AU X
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
+
Date : 01/2004
Print :11/03/2004
Sheet : 29
Issue : b
8.2
Connections
Connections
Location Characteristics
Modbus® or IEC870-5-103
Communication
RS485-1
RS485-2
Connection of the VTs
A
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Logical inputs
B
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
C and D
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Auxiliary supply
AUX
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
(optional board)
E and F
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Logical inputs
(optional board)
G
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Connection of the CTs
IA to IO
4 mm ring type terminal. Section of wire ≤ 6 mm²
8.3
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Diagrams
Type of relay
Observation
NPI 800
NPIR 800
S 38018
NPI 800 with recloser
NPID 800
NPIDR 800
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Reference of diagram
S 38023
S 38019
NPID 800 with recloser
User’s Guide
NPI 800 and NPID 800
S 38020
Date : 01/2004
Print :11/03/2004
Sheet : 30
Issue : b
8.4
Connection of the current inputs
Connection is done by 6mm² ring terminals for M4 screw. It is identical for all the variants of
inputs:
♦ Phases CT 1A or 5A
♦ Earth-fault CT 1A or 5A or CT Ring.
Respect the rotating sense of phases and the direction of the connection of phases.
8.5
Connection of the Modbus RS485 communication
8.5.1 Characteristics of the network cable
Recommended characteristics for the cable:
• Shielded twisted pairs, maximum length 1000 m.
• resistance < 100 ohms/km
• capacity between wires < 60 pF/m
• capacity between wire and shield < 100 pF/m
It is imperatively necessary to tighten the fixing clamp on the shield and not on insulator, in
order to ensure continuity of the shield of the cable and its earthing.
8.5.2 Resistance of adaptation
Connect a 120 ohms resistance of adaptation to each protection located at each end of the
network.
It is necessary to connect the Rterm +T/R according to the diagram
RS485
*
+T/R
-T/R
120
Ohms
R term
If the Master is connected at one end of the network, it is necessary to place a resistance of
adaptation on the Master and another on the protection located at the other end of line using
the switches of the communication board.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPI 800 and NPID 800
Date : 01/2004
Print :11/03/2004
Sheet : 31
Issue : b