USER’S GUIDE PHASES AND ZERO SEQUENCE OVER CURRENT DIGITAL MULTI-FUNCTION RELAY NPI 800 AND NPID 800 ICE - 11, rue Marcel Sembat - 94146 ALFORTVILLE CEDEX - France TEL. : (33) 01 41 79 76 00 - FAX : (33) 01 41 79 76 01 – E-MAIL : [email protected] SITE WEB : www.groupeice.com User’s Guide NPI 800 – NPID 800 Issue : b File : A0333E1E Date : 02/2004 This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization PREFACE This aim of this handbook is to provide to the User information useful for the operation of NPI800 and NPID800 relays with the local MMI. We advise you to read it carefully, in order to take note of the available functionalities and to proceed to connection and power of the product in accordance with the provided recommendations. Locally, setting, commissioning and real time or event readings are accessible from keyboard and displayed on the protection display. To be fully exploited, the available functions must be parameterized and consulted with the setting software PC – Protection, provided with the product. Before any use, we recommend you to read the safety instructions of this User’s guide. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 1 Issue : b CONTENTS 1. SAFETY INSTRUCTIONS ____________________________________________________________ 3 DOCUMENTATION .................................................................................................................................... 3 CONNECTION OF NP800 RELAYS.............................................................................................................. 3 ON LOAD WITHDRAWAL ........................................................................................................................... 3 REMOVAL AND DESTRUCTION .................................................................................................................. 3 2. PROTECTION AND OPERATION FUNCTIONS ________________________________________ 4 2.1 PROTECTION FUNCTIONS NPI800 AND NPID800..................................................................................... 4 2.2 OPERATION FUNCTIONS NPI800 AND NPID800....................................................................................... 4 2.3 PROTECTION AND OPERATION FUNCTIONS SPECIFIC TO NPID800............................................................ 4 2.4 LOCALLY AVAILABLE USER’S FUNCTIONS ............................................................................................... 4 2.5 REMOTELY AVAILABLE USER’S FUNCTIONS............................................................................................. 5 3. FIRST USE__________________________________________________________________________ 6 3.1 DEFAULT SCREEN..................................................................................................................................... 6 3.2 PRESENCE OF A FAULT OR AN ALARM ...................................................................................................... 6 4. GENERAL INFORMATION ON MENUS _______________________________________________ 7 4.1 SETTING MODE (IN / OUT) ........................................................................................................................ 7 4.2 MODIFICATION OF A PARAMETER............................................................................................................. 7 4.3 ACCESS CODE........................................................................................................................................... 8 4.4 ASSIGNMENT OF OUTPUT UNITS ............................................................................................................... 8 5. MENU LIST_________________________________________________________________________ 9 5.1 ACCESS TO MAIN MENUS .......................................................................................................................... 9 5.2 MEASUREMENT MENU.............................................................................................................................10 5.3 OVERCURRENT MENU .............................................................................................................................12 5.4 NEGATIVE SEQUENCE MENU ...................................................................................................................14 5.5 DIRECTIONAL MENU (ONLY NPID800) ...................................................................................................15 5.6 GENERIC FUNCTIONS MENU ....................................................................................................................16 5.7 THERMAL OVERLOAD MENU ...................................................................................................................16 5.8 CLOSING FUNCTION MENU ......................................................................................................................18 5.9 LOGICAL SELECTIVITY MENU ..................................................................................................................19 5.10 REMOTE CONTROL MENU ........................................................................................................................20 5.11 DISTURBANCE RECORDING MENU ...........................................................................................................20 5.12 COUNTERS MENU ....................................................................................................................................21 5.13 OPERATION MENU ...................................................................................................................................22 5.14 MODBUS® COMMUNICATION MENU (OPTIONAL) ....................................................................................23 5.15 CHANGE OF CODE MENU .........................................................................................................................23 5.16 INFORMATION MENU ...............................................................................................................................23 6. CONTENT OF AN EVENT___________________________________________________________ 24 6.1 EVENTS GENERATED ON 51/50/51N/50N/46 THRESHOLDS (NPI800)......................................................24 6.2 EVENTS GENERATED ON 51/50/51N/50N/67/67N/46 THRESHOLDS (NPID800)......................................25 6.3 THERMAL OVERLOAD EVENT ..................................................................................................................25 6.4 CUSTOMIZED INPUTS EVENTS ..................................................................................................................27 6.5 OTHER EVENTS .......................................................................................................................................27 6.6 ACKNOWLEDGEMENT OF EVENTS ...........................................................................................................27 6.7 READING OF THE LAST 250 MEMORIZED EVENTS ....................................................................................27 7. LIST OF FAULTS OR OPERATION MESSAGES_______________________________________ 28 1.1 1.2 1.3 1.4 8. 8.1 8.2 8.3 8.4 8.5 CONNECTION OF NPI800 AND NPID800 PROTECTIONS ______________________________ 29 DESCRIPTION OF THE TERMINAL BLOCKS ................................................................................................29 CONNECTIONS.........................................................................................................................................30 DIAGRAMS ..............................................................................................................................................30 CONNECTION OF THE CURRENT INPUTS ...................................................................................................31 CONNECTION OF THE MODBUS RS485 COMMUNICATION .......................................................................31 This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 2 Issue : b 1. Safety instructions For your safety, we recommend you to read the following information carefully. They have the aim of specifying the precautions essential to the good installation and the correct operation of the relays. 1.1 Documentation Following documentations are available for the products of the range NP800: ♦ General Presentation of the NP800 range ♦ User’s Guide of Setting Software for NP800 range ♦ User’s Guide (for each kind of relay) ♦ First Handling Guide (for each kind of relay) ♦ Diagram of each relay. We advise you to read them before any handling. 1.2 Connection of NP800 relays The terminal blocks of the relays are studied to ensure the safety of the people during the operation of the relays. During installation, commissioning or maintenance, they can however present high voltages and possibly a thermal heating. Consequently, the following precautions must be respected: ♦ Connection of the terminal blocks at installation must be carried out after having ensured of the absence of any voltage ♦ Their access during operation must be carried out through adequate means ensuring as well electric as thermal insulation ♦ The connection of the earth at the back of the relays must imperatively be done with mean of a 2.5 mm² wire. Before powering the relays, it will be necessary to check in particular: ♦ The value of the voltage rating of the auxiliary supply and its polarization ♦ The tightening of the intensity circuits and the good realization of connections ♦ The integrity of the connection to the earth. 1.3 On load withdrawal It is formally misadvised to withdraw the connectors, in particular the current terminal blocks, under voltage or on load. 1.4 Removal and destruction The relays should in no case be opened by the User. During their removal, they must be completely isolated from any external polarity and condensers must be discharged by connecting their external terminals to the earth. Destruction of the relays will have to be carried out in accordance with legislation in force, in particular in compliance with the environment and safety requirements. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 3 Issue : b 2. Protection and operation functions 2.1 Protection functions NPI800 and NPID800 ♦ Three-phase over-current protection, with two ANSI 51 thresholds and one ANSI 50 threshold ♦ Earth fault over current protection, with one ANSI 51N threshold and one ANSI 50N threshold ♦ Inverse over-current protection with one ANSI 46 threshold for the detection of unbalance ♦ Negative phase sequence current ratio protection with one ANSI 46BC threshold for the detection of the broken conductors unbalancer atio = . I .negativese quence I . positivesequencedire ct ♦ ANSI 49 Thermal overload function. Two models, transformer (with inhibition of closing on load) or wire, are available ♦ Logic selectivity function on the phases and earth-fault thresholds ♦ Closing function to avoid spurious trips when closing the circuit breaker ♦ ANSI 50BF circuit breaker failure function by checking of the disappearance of the phases and earth-faults currents (optional function, consult us). 2.2 Operation functions NPI800 and NPID800 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ Two setting groups Assignment of digital inputs Assignment of relay outputs User programmable LEDs Monitoring of trips and reclosings Help in circuit breakers maintenance: number of operations with alarm threshold Storage of the last 250 events Storage of four 52 periods disturbance recordings, according to COMTRADE standard ♦ 8 User configurable generic functions. 2.3 Protection and operation functions specific to NPID800 ♦ ANSI 67 phases and ANSI 67N earth-fault Directional functions, applicable to ANSI 50 and ANSI 51protections ♦ Network frequency Measure ♦ Voltage Measure ♦ Power and energy Counters. 2.4 Locally available User’s functions Locally, the following functions are available: ♦ Choice of language ♦ Setting in or out of order of the functions ♦ Customized identification of protection ♦ Setting of adjustment and primary values for the two tables ♦ Assignment of the inputs / outputs This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 4 Issue : b ♦ ♦ ♦ ♦ ♦ ♦ 2.5 Reading of fault values Reading of each memorized value: measurements and counters Reset of counters Reading of events Configuration of disturbance recording and local trigger Configuration of Modbus® communication. Remotely available User’s functions The following functionalities can be accessed through the RS232 or RS485 links: ♦ Saving of configuration ♦ Commissioning tests: LCD display, adjustment of contrast, LEDs ♦ Commissioning tests: relays, wiring ♦ Reading of real time values: measurement and counters ♦ Reading of disturbance recordings. These functions are however available with the setting software. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 5 Issue : b 3. First use When powering the relay, the displays below can appear. The recommended action allows starting the parameter setting of protection. 3.1 Default screen In absence of a fault, the protection displays the phase 1 current measurement in HV value. CURRENT I1 0.0 A 3.2 Presence of a fault or an alarm If a fault or alarm occurs, a message indicates the type of fault. When threshold is exceeded or when tripping, the following messages appear: INSTANT. PHASE THRESHOLD Followed by > TRIP PHASE THRESHOLD > Note: According to the type of fault, the message of the second line changes. This message disappears at once after acknowledgement of the fault and is replaced by the following message. TRIP PH > A 17/06 14:22:15 E This message remains until the acknowledgement of the fault by the User. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 6 Issue : b 4. General information on menus All parameters can be accessed for reading. On the other hand, parameters are writeprotected by an access code requested on the first modification. 4.1 Setting mode (In / Out) Press any key except CLEAR to enter in setting mode. If no parameter has been modified, exit the mode by pressing the CLEAR key: , MAIN MENU CLEAR ENTER MEASUREMENTS CURRENT I1 0.0 A CURRENT I1 CLEAR 0.0 A If a parameter has been modified, confirm the exit from setting mode: MAIN MENU CLEAR OVER CURRENT QUIT SETTINGS MODE ? ENTER CURRENT I1 0.0 A Without any operation, return to exploitation mode is carried out automatically after 5 minutes. 4.2 Modification of a parameter Use the " parameter " and " " keys to select a menu then press the ENTER key to access the first MAIN MENU MAIN MENU MEASUREMENTS OVER CURRENT Use the " " and " PHASE SETTING ENTER set 1 " keys to access the various parameters in the menu:: I> DELAY TYPE Active tI> DEFINITE Definite tI> 0.60 s Use the and keys to modify the parameter. You must confirm your change using the ENTER key after each parameter modification. After storing the new parameter value, next parameter is displayed: DEFINITE tI> DEFINITE 0,60 s 0,70 s Use the CLEAR and THRESHOLD tI> ENTER THRESHOLD I> 0,5 * In to change menu : I> 0,5 * In CLEAR MAIN MENU MAIN MENU OVER CURRENT NEG.SEQUENCE I2> Leaving any sub menu with the CLEAR key will lead to the above menu. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 7 Issue : b 4.3 Access code On first modification of a parameter, the software requests the access code. The factory-programmed code is " ICE1 ". To enter your own personalised code, use the " CHANGE CODE " menu. The code can be composed up to four alphanumeric characters. The following example shows how to replace code "AA" with " 99 ": MAIN MENU CHANGE CODE ENTER NEW PASSWORD OLD PASSWORD OLD PASSWORD OLD PASSWORD OLD PASSWORD _ A A_ AA NEW PASSWORD _ NEW PASSWORD 9 NEW PASSWORD 9_ MAIN MENU ENTER 99 ENTER CHANGE CODE In case of loss of the code, contact us to obtain an emergency password for your configuration. 4.4 Assignment of output units Relays assigned to a function are displayed with" * ". Key " " allows modifying assignment of the relays. Key allows selection of next relay. Example: assignment of relay B to TRIP U> function. At the beginning, no function was assigned to this relay. REL. TRIP A_ B ENTER C tI> REL. TRIP D A REL. TRIP tI> A B_ C B_ C tI> D REL. TRIP A B tI> C D ENTER REL. TRIP E F G D Next parameter Caution: do not to forget to confirm by ENTER key This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 8 Issue : b tI> 5. Menu list 5.1 Access to main menus The following menus enable setting of the available functions. Each one allows access to the parameters of adjustment and ensures their coherence. CURRENT I1 Press on any key other than CLEAR Press on CLEAR key to to enter the parameter setting mode leave the parameter setting 0.0 A mode ENTER, , , , , CLEAR MAIN MENU Real time measures Use the or keys to select a menu MEASUREMENTS MAIN MENU Parameters of the functions: 50, 50N, 51, 51N OVER CURRENT MAIN MENU Parameters of the function 46. NEG.SEQUENCE I2> MAIN MENU Parameters of the directional (NPID800 only) functions 67, 67N DIRECTIONAL MAIN MENU Parameters of the customized functions GENERIC FUNCTION MAIN MENU Parameters of the thermal overload function THERMAL REPLICA MAIN MENU Parameters of the closing function (reclosing) CLOSING FCT MAIN MENU Parameters of the logic selectivity option LOG. SELECTIVITY MAIN MENU Parameters of the remote control option TELECONTROL MAIN MENU Information about disturbance recording PERTURBOGRAPHY MAIN MENU Information about counters COUNTERS MAIN MENU Operating parameters to be defined at commissioning OPERATION MAIN MENU Configuration of the Modbus RS485 (if option available) communication option MODBUS COMMS MAIN MENU Change of the access code CHANGE CODE MAIN MENU Information about protection INFORMATION MAIN MENU Reading of the event log EVENTS Leaving any sub menu with the CLEAR key will lead to the above menu. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 9 Issue : b 5.2 Measurement menu This menu displays any real time measurement of the protection, as well as the values kept in memory. MAIN MENU MEASUREMENTS ENTER / CLEAR CURRENT I1 0,0 A CURRENT I2 0,0 A CURRENT I3 0,0 A CURRENT Io 0,00 A NEGATIVE SEQ. 0,0 A POSITIVE SEQ. 0,0 A FREQUENCY 50.00 Hz THERMAL STATE I1 0,0 % THERMAL STATE I2 0,0 % THERMAL STATE I3 0,0 % VOLTAGE U21 0V VOLTAGE U32 0V VOLTAGE Vr 0V ACTIVE POWER 0 kW REACTIVE POWER 0 kVAR COS PHI 0,00 INDUCTIVE AVERAGE ACTIVE P 0 kW AVER. REACTIVE P 0 kVAR This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Available real time measures Measure of the phase 1 primary current 0.0 to 64000 A Measure of the phase 2 primary current 0.0 to 64000 A Measure of the phase 3 primary current 0.0 to 64000 A Measure of the earth fault primary current 0.0 to 6400 A Measure of the negative phase sequence current 0.0 to 64000 A Measure of the positive sequence current 0.0 to 64000 A Measure of the network frequency 45 to 55 if Fn = 50 Hz 55 to 65 if Fn = 60 Hz 0.0 to 500 % Measure of the thermal state phase 1 Measure of the thermal state phase 2 Measure of the thermal state phase 3 Measure of the U21 phase to phase primary voltage Measure of the U32 phase to phase primary voltage Measure of the residual primary voltage Measure of instantaneous active power 0.0 to 500 % (if cable thermal overload) 0.0 to 500 % (if cable thermal overload) 0 to 640 000 V (NPID 800 only) 0 to 640 000V (NPID 800 only) 0 to 640 000V (NPID 800 only) (NPID 800 only) Measure of instantaneous reactive power (NPID 800 only) Measure of power-factor and inductive or capacitive information (NPID 800 only) Value of the average active power (NPID 800 only) Value of the average reactive power (NPID 800 only) User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 10 Issue : b AVER. CURRENT I1 0 A AVER. CURRENT I2 0 A AVER. CURRENT I3 0 A AVER. CURRENT I0 0.0 A SETTING set 1 17/06/03 14:53:32 This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Value of the average primary current of phase 1 0 to 64 000 A Value of the average primary current of phase 2 0 to 64 000 A Value of the average primary current of phase 3 0 to 64 000 A Value of the average earth-fault primary current 0 to 64 000 A Display of the active setting Set 1 or Set 2 Day / Month / Year Hour / minute / second User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 11 Issue : b 5.3 Overcurrent menu This menu allows the setting of the phases and earth fault over current functions: setting in and out of order, choice of the types of time delay and curves, adjustment of thresholds, assignment of the output units. This configuration must be carried out successively for each of the two settings groups if they are to be used alternatively. MAIN MENU OVER CURRENT ENTER / CLEAR SETTING set 1 PHASE I> Active DELAY TYPE tI> Mod. Invers.ANSI MOD. INV.ANSI tI> 0,03 s THRESHOLD I> 0,3 *In REL. INST. I> A_ B C D REL. INST. I> E_ F G REL. TRIP tI> A_ B C D REL.TRIP tI> E_ F G PHASE I>> Active DELAY TYPE tI>> Mod. Invers. ANSI MOD. INV.ANS tI>> 0,03 s THRESHOLD I>> 0,3 *In REL. INST. I>> A_ B C D REL. INST. I>> E_ F G REL. TRIP tI>> A_ B C D REL.TRIP tI>> E_ F G This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the ANSI 50, 50N, 51, 51N functions Choose the setting group Set 1 or Set 2 Choose Active to use the phase low threshold ANSI 51-1 function Active or Inactive Select the type of time delay: independent; CEI : Inverse, Very inv, Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv Set the value of the time delay. Independent : 0.04 to 300 s Set the value of the threshold RI Inverse.: 0.1 to 20 s CEI and ANSI : 0.03 to 3 s 0.3 to 24.0 * In Relay to assign to the instantaneous function Relay to assign to the instantaneous function Relay to assign to the trip function Relay to assign to the trip function Choose Active to use the phase high Active or Inactive threshold ANSI 51-2 function Select the type of time delay: independent; CEI : Inverse, Very inv, Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv Set the value of the time delay. Independent : 0.04 to 300 s Set the value of the threshold RI inverse : 0.1 to 20 s CEI and ANSI : 0.03 to 3 s 0.3 to 24.0 * In Relay to assign to the instantaneous function Relay to assign to the instantaneous function Relay to assign to the trip function Relay to assign to the trip function User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 12 Issue : b PHASE I>>> Active DEFINITE tI>>> 0,04 s THRESHOLD I>>> 0,3 *In REL. INST. I>>> A_ B C D REL. INST. I>>> E_ F G REL. TRIP tI>>> A_ B C D REL.TRIP tI>>> E_ F G EARTH LOW Io> Active DELAY TYPE tIo> Mod. Invers. ANSI MOD. INV.ANS tIo> 0,03 s THRESHOLD Io> 0,03 *In REL. INST. Io> A_ B C D REL. INST. Io> E_ F G REL. TRIP tIo> A_ B C D REL.TRIP tIo> E_ F G EARTH HIGH Io>> Active DEFINITE tIo>> 0,04 s THRESHOLD Io>> 0,03 *In REL. INST. Io>> A_ B C D REL. INST. Io>> E_ F G REL. TRIP tIo>> A_ B C D REL.TRIP tIo>> E_ F G This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Choose Active to use the phase very high threshold ANSI 50 Active or Inactive Set the value of the time delay Independent : 0.04 to 300 s Set the value of the threshold 0.3 to 24.0 * In Relay to assign to the instantaneous function Relay to assign to the instantaneous function Relay to assign to the trip function Relay to assign to the trip function Choose Active to use the earth low threshold ANSI 51N function Active or Inactive Select the type of time delay: independent; CEI : Inverse, Very inv, Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv Set the value of the time delay Independent : 0.04 to 300 s Set the value of the threshold RI Inverse : 0.1 to 20 s CEI and ANSI : 0.03 to 3 s 0.03 to 2.40 * In Relay to assign to the instantaneous function Relay to assign to the instantaneous function Relay to assign to the trip function Relay to assign to the trip function Choose Active to use the earth high threshold ANSI 50N function Active or Inactive Set the value of the time delay 0.04 to 300 s Set the value of the 50N function threshold 0.03 to 2.40 * In Relay to assign to the instantaneous function Relay to assign to the instantaneous function Relay to assign to the trip function Relay to assign to the trip function User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 13 Issue : b 5.4 Negative sequence menu MAIN MENU NEG.SEQUENCE I2> ENTER / CLEAR SETTING set 1 FUNCTION I2> Active DELAY TYPE I2> Mod. Invers. ANSI MOD.INV.ANSI I2> 0,10 s THRESHOLD I2> 0,1 *In REL. INST. I2> A_ B C D REL. INST. I2> E_ F G REL. TRIP. I2> A_ B C D REL. TRIP. I2> E_ F G FUNCTION I2/I1> Inactive DEFINITE tI2/I1> 0,04 s THRESHOLD I2/I1> 0,10 REL. INST I2/I1> A_ B C D REL. INST I2/I1> E_ F G REL. TRIP I2/I1> A_ B C D REL. TRIP I2/I1> E_ F G FUNCTION I2/I1>> Inactive DEFINIT. tI2/I1>> 0,04 s THRESHOLD I2/I1>> 0,10 This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the phase unbalance function Choose the setting group Set 1 or Set 2 Choose Active to use the maximum of negative phase sequence function Active or Inactive Select the type of time delay: independent; CEI : Inverse, Very inv, Ext. Inv, RI inv; ANSI : Mod Inverse, Very Inv. Ext. inv Set the value of the time delay. Independent : 0.04 to 300 s Set the value of the threshold RI : 0.1 to 20 s CEI and ANSI: 0.03 to 3 s 0.1 to 24.0 * In Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Choose Active to use the unbalance ratio low threshold Active or Inactive Set the value of the time delay 0.04 to 300.00s Set the value of the threshold 0.10 to 2.50 Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Choose Active to use the unbalance ratio high threshold Active or Inactive Set the value of the time delay 0.04 to 300.00s Set the value of the threshold 0.10 to 2.50 User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 14 Issue : b REL. INST I2/I1>> A_ B C D REL. INST I2/I1>> E_ F G REL. TRIP I2/I1>> A_ B C D REL. TRIP I2/I1>> E_ F G 5.5 Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Relay to assign to the trip function Directional menu (only NPID800) This menu allows the parameter setting of the phase or earth-fault directional functions: setting in and out of order, choice of angles and threshold of polarization. MAIN MENU DIRECTIONAL ENTER / CLEAR SETTING set 1 PHASE DIREC. > Inactive PHASE DIREC. >> Inactive PHASE DIREC. >>> Inactive ANGLE PHASE DIR. 180 ° EARTH LOW DIREC. Inactive EARTH HIGH DIREC. Inactive ANGLE EARTH DIR. 180 ° POLARISATION Vo 3 % Vn INHIB. EARTH DIR. Inactive This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the phase and earth directional functions Choose the setting group Set 1 or Set 2 Choose Active to use the phase low threshold directional function Active or Inactive Choose Active to use the phase high threshold directional function Active or Inactive Choose Active to use the phase very high threshold directional function Active or Inactive Adjustment of the directional angle of -180 ° to 180 ° the phase Choose Active to use the earth low threshold directional function Active or Inactive Choose Active to use the earth high threshold directional function Active or Inactive Adjustment of the directional angle of -180 ° to 180 ° the earth Set the value of the threshold of polarization 3 to 20 % Vn Choose Active to inhibit the earth directional function when Vn < Vo Active or Inactive User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 15 Issue : b 5.6 Generic functions menu This menu allows the parameter setting of 8 customized functions: setting in and out of order, adjustment of the time delays, assignment of the output units, assignment of a logical input. MAIN MENU GENERIC FUNCTION ENTER / CLEAR FCT GENERIC 1 Inactive TEMP GENERIC 1 0,06 s RELAY GENERIC 1 A_ B C D RELAY GENERIC 1 E_ F G DIG.INP.GENER. 1 No input NAME GENERIC 1 GENERIC 1 …………… 5.7 Parameters of the customized functions Choose Active to use function 1 Active or Inactive Set the time delay of function 1 0.04 to 300.00s Relay to assign to function 1 Relay to assign to function 1 Display of input selected for function 1 (configurable with the setting software) Display of label of function 1 (configurable with the setting software) Thermal overload menu This menu authorizes the parameter setting of the thermal overload function: setting in and out of order, type of thermal overload, adjustment of the thermal time-constant, adjustment of the thermal trip and alarm thresholds, assignment of the output units for alarm and trip. MAIN MENU THERMAL REPLICA ENTER / CLEAR SETTING set 1 THERMAL TYPE CABLE THERMAL STATE Active TH. TIME CONST. 4 mn TH.TRIP THRES Ib 1,00 *In TH. TRIP RELAY A_ B C D This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the thermal overload option Choose the setting group Set 1 or Set 2 Choose the type of device to protect Cable or transformer Choose Active to use thermal overload function Active or Inactive Set the value of the thermal overload time-constant 4 to 180 min Set the thermal trip threshold Ib 0.40 to 1.30 * In Select the relays for thermal overload trip User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 16 Issue : b TH. TRIP RELAY E_ F G TH.ALARM THRESH. 80 % TH. ALARM RELAY A_ B C D TH. ALARM RELAY E_ F G See note. HOT START Active HOT START THRESH 40 % START RELAY A_ B C D START RELAY E_ F G Select the relays of thermal overload trip Set the thermal alarm threshold 80 to 100 % Ib Select the relays to be assigned to the thermal alarm function Select the relays to be assigned to the thermal alarm function Choose Active to use Inhibition of hot motor starting Active or Inactive Setting of the threshold of inhibition of hot motor starting 40 to 100 % Set the relays Inhibition of hot motor starting Set the relays Inhibition of hot motor starting Note: For a choice of Transformer thermal overload, an additional sequence of parameter setting is to be intercalated described as follows: TH. ALARM. RELAY Select the relays to be assigned to the thermal alarm function E_ F G former parameter COOLING CONST 1,0 * HEAT CST. START FACTOR 50 % NEG. SEQ. FACTOR 3 Next parameter HOT START Inactive This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Set the cooling constant 1.0 to 6.0 * heating constant Set the coefficient calculation of the thermal overload (starting mode) 50 to 100 % Set the negative sequence factor K (thermal heating) 0 to 9 Choose Active to overload function use User’s Guide NPI 800 and NPID 800 thermal Active or Inactive Date : 01/2004 Print :11/03/2004 Sheet : 17 Issue : b 5.8 Closing function menu This menu authorizes the parameter setting of the closing function: time delay of start, assignment of a logical input. MAIN MENU CLOSING FCT ENTER / CLEAR CLOS. MODE TIME 0,06 s CLOS. MODE RATIO 50 % PHASE I>>> Inactive PHASE I>> Inactive PHASE I> Inactive EARTH HIGH Io>> Inactive EARTH LOW Io> Inactive FUNCTION I2> Inactive FUNCTION I2/I1>> Inactive FUNCTION I2/I1> Inactive CLOS. MODE INPUT No input This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the closing function Set the start time delay 0.04 to 300.00 s Set the start ratio 50 to 200 % Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive Choose Active to modify the threshold during start Active or Inactive ODisplay of the selected logical input User’s Guide NPI 800 and NPID 800 (configurable with the setting software) Date : 01/2004 Print :11/03/2004 Sheet : 18 Issue : b 5.9 Logical selectivity menu This menu authorizes the parameter setting of the logical selectivity function: setting in and out of order, adjustment of the time delays, operating mode. MAIN MENU LOG. SELECTIVITY ENTER / CLEAR SETTING set 1 PHASE S.LOG. I> Inactive PHASE S.LOG. I> 0,06 s PHASE S.LOG. I>> Inactive PHASE S.LOG. I>> 0,06 s PHASE S.LOG. I>>> Inactive PHASE S.LOG. I>>> 0,06 s EARTH LOW S.LOG. Inactive EARTH LOW S.LOG. 0,06 s EARTH HIGH S.LOG Inactive EARTH HIGH S.LOG 0,17 s DIG INPUT S. LOG. No input This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Parameters of the logical selectivity option Choose the setting group Set 1 or Set 2 Choose Active to use the phase low threshold Active or Inactive Set time delay of the phase low threshold function 0.06 to 120.00 s Choose Active to use the phase high threshold Active or Inactive Set time delay of the phase high threshold function 0.06 to 120.00 s Choose Active to use the phase very high threshold Active or Inactive Set time delay of the phase very high threshold function 0.06 to 3.00 s Choose Active to use the earth low threshold Active or Inactive Set time delay of the earth low threshold function 0.06 to 120.00 s Choose Active to use the earth high threshold Active or Inactive Set time delay of the earth high threshold function 0.06 to 3.00 s Display of the logical input selected for the function (configurable with the setting software) User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 19 Issue : b 5.10 Remote control menu This menu authorizes the parameter setting of the remote control function: setting in and out of order, level of load-shedding, adjustment of the time delay of reconnection, assignment of the trip and reclosing relays, pulse of reclosing, assignment of the logical inputs. MAIN MENU Information about remote control option TELECONTROL ENTER / CLEAR TELECONTROL Choose Active to use the remote Active or Inactive control function Inactive LOAD SHED LEVEL Set the level of load-shedding. Level 1 to 6 (pas de 1) 6 inhibits the load-shedding function 6 RE-LOAD DELAY Set the value of time delay before 1.00 to 120.00 s reclosing 1,00 s TRIP RELAY Select the relays to be assigned to the trip A_ B C D TRIP RELAY Select the relays to be assigned to the trip E_ F G RECLOSE RELAY Select the relays to be assigned to the reclosing A_ B C D RECLOSE RELAY E_ F G RECLOSE PULSE 200 ms O/O INPUT Input 1 C/O INPUT Input 2 LOCAL INPUT Input 3 DISTANT INPUT Input 4 Select the relays to be assigned to the reclosing Set the reclosing pulse 100 to 500 ms Display of the logical input assigned to the position of the interlock (configurable with the setting software) Display of the logical input assigned to the position of the interlock (configurable with the setting software) Display of the logical input assigned to the mode of exploitation (configurable with the setting software) Display of the logical input assigned to the mode of exploitation (configurable with the setting software) 5.11 Disturbance recording menu This menu is used to configure the parameters of the disturbance recording. MAIN MENU Parameters of the disturbance recording function PERTURBOGRAPHY ENTER / CLEAR PRE-TIME 35 period(s) PERTURBO. INPUT No input This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Set pre time 1 to 52 Display of input assigned to external trip (configurable with the setting software) User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 20 Issue : b 5.12 Counters menu This menu allows the parameter setting of the counters: display of cut A², number of circuit breaker operations, energies, current maximeters, power maxima, restoring of the counters. MAIN MENU Parameters of the counters function COUNTERS ENTER / CLEAR A2 CUTOFF I1 Display of cut A² of phase 1 0,0 kA2 A2 CUTOFF I2 Display of cut A² of phase 2 0,0 kA2 A2 CUTOFF I3 Display of cut A² of phase 3 0,0 kA2 RESET A2 CUTOFF Reset of cut A² with ENTER key Confirm: ENTER NBER OPERATIONS Display of the number of operations of the circuit breaker 0 RESET NB OPERAT. Reset of the number of operations of the circuit breaker Confirm: ENTER ACTIVE ENERGY + 505368 MWh ACTIVE ENERGY 2365269 MWh REACTIV. ENERGY + 489312 MVARh REACTIV ENERGY 726394 MVARh ENERGY RESET confirm : ENTER MAX. METER I1 1049 A MAX. METER I2 1056 A MAX. METER I3 1048 A MAX. METER I0 68,0 A MAX. METER RESET Confirm: ENTER ACTIVE P MAX -152438 kW REACTIVE P MAX 23556 kVAR RESET P MAX Confirm: ENTER This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Display of positive active energy Display of negative active energy Display of positive reactive energy Display of negative reactive energy Reset of energy with ENTER key Display of the current maximeter on phase 1 Display of the current maximeter on phase 2 Display of the current maximeter on phase 3 Display of the current maximeter on earth Reset of current maximeter with ENTER key Display of the maximum of active power Display of the maximum of reactive power Reset of P power maximeter with ENTER key User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 21 Issue : b 5.13 Operation menu This menu authorizes the parameter setting of the operation function: choice of the language, adjustment of LCD contrast, parameter setting of the values of the phase and earth-fault CTs, parameter setting of the rated primary and secondary voltage of the VTs, display of the input logical corresponding to set 2, trip pulse, maximum of cut A² and number of operations of the circuit breaker, assignment of the relays for circuit breaker failure and discrepancy, average current and power. MAIN MENU OPERATION ENTER / CLEAR LANGUAGE English ADJUST LCD 200 I NOMINAL PRIM. 1000 A Io NOMINAL PRIM. 100 A U NOMINAL PRIM. 1000 V U NOMINAL SECOND 110 V SET 2 INPUT Input 6 CLEAR REL. INPUT Input 5 TRIP PULSE 100 ms MAX A2 CUTOFF 5000000 kA2 MAX NBER OPERAT. 9999 RELAY C.B. FAULT A_ B C D RELAY C.B. FAULT E_ F G RELAY DISC. L/D A_ B C D RELAY DISC. L/D E_ F G I and P AVERAGE in 30 mn This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Operating parameters to be defined at commissioning Choice of the language used locally by protection French or English Adjustment of the angle of vision of the LCD display 70 to 255 Set the value of the phase primary rated current of the CTs 1 to 10000 A Set the value of the earth primary rated current of the CT 1 to 10 000 A Value of the phase to phase rated primary voltage of phase VTs 220 to 250 000 V Value of the phase to phase rated secondary voltage of phase VTs 55 to 120 V Display of input assigned to setting group 2 No input, E1 to E8 Display of input assigned to reset of relays No input, E1 to E8 Setting of minimum duration of trip pulse 100 to 500 ms Adjustment of the maximum of cut A² 1 to 64 000 000 kA² Adjustment of the maximum number of operations of the circuit breaker 1 to 10000 Select the relay assigned to the circuit breaker failure function Select the relay assigned to the circuit breaker failure function Select the relay assigned to the local/distant discrepancy function Select the relay assigned to the local/distant discrepancy function (if remote control option) Adjustment of the time for calculation 5 to 60 min of average values and maximeters User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 22 Issue : b 5.14 Modbus® communication menu (optional) This menu is used to set the parameters of the Modbus® communication function: slave number, size, speed, activity and loop tests. MAIN MENU MODBUS COMMS ENTER / CLEAR SLAVE NUMBER 2 FORMAT 8b+0p+2s ASCII Configuration of the Modbus RS485 communication option SPEED 9600 bauds Speed transmission on RS485 link RECEPT. TIMEOUT 0.10 s ACTIVITY TIMEOUT 0.20 s ACTIVITY TEST Mess.Receiv.com1 Set the time delay of reception timeout Slave number of protection 1 to 255 number of bits + parity + bits of stop + ASCII/Binary format Parity: 1p = pair, 1i = odd, 0p= without p0 = forced to 0, p1 = forced to 1, 300, 600 ,1200 ,1800, 2400, 4800, 9600, 19200 38400, 57 600,115 200 bauds 0.10 to 20 s Set the time delay of activity timeout 0.10 to 20 s Test of the parameter setting and the wiring of Modbus message received / not received: correct activity / communication problem 5.15 Change of code menu This menu allows change of code and is described in chapter Access Code. 5.16 Information menu Information menu specifies the factory set characteristics of the protection, as well as the label assigned by the User. MAIN MENU INFORMATION ENTER / CLEAR NP.ID 800 50 Hz PROC. VER. 1.22a PHASES RAT. 1 A EARTH RAT. 1 A NP 800 ICE This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Information about protection Type of protection Rated frequency Version of the software of protection Display of the phases and earth ratings 32 characters zone programmable with the setting software. User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 23 Issue : b 6. Content of an event Events are different according to information recorded when fault occurs. There are three different types of structures of event. They can be read with the local MMI, the setting software (RS232 link) and the Modbus communication network. 6.1 Events generated on 51/50/51N/50N/46 thresholds (NPI800) Events are recorded as soon as a trip or alarm threshold of the current functions is reached: ♦ INST PH > INST PH >> INST PH >>> ♦ INST Io HIGH INST Io LOW ♦ INST I2 > ♦ INST I2/I1 > ♦ INST I2/I1 >> ♦ TRIP PH > TRIP PH >> TRIP PH >>> ♦ TRIP Io HIGH TRIP Io LOW ♦ TRIP I2 > ♦ TRIP I2/I1 > ♦ TRIP I2/I1 >> Detail of available information can be consulted for each event, in accordance with the list below: MAIN MENU EVENTS ENTER / CLEAR TRIP PH > E 17/06 14:22:00 R 17/06/03 14:22:00.990 SETTING set 1 CURRENT I1 745 A CURRENT I2 743 A CURRENT I3 746 A CURRENT Io 0.1 A This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization List of the last 250 events Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day: Month: Year Hour: Minute: Second. Millisecond Active setting group Set 1 or Set 2 Current of phase 1 measured at disappearance of the trip Current of phase 2 measured at disappearance of the trip Current of phase 3 measured at disappearance of the trip Zero-sequence current measured at disappearance of the trip User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 24 Issue : b 6.2 Events generated on 51/50/51N/50N/67/67N/46 thresholds (NPID800) Events are recorded as soon as a trip or alarm threshold of the current functions is reached: ♦ INST PH > INST PH >> INST PH >>> ♦ INST Io HIGH INST Io LOW ♦ INST I2 > ♦ INST I2/I1 > ♦ INST I2/I1 >> ♦ TRIP PH > TRIP PH >> TRIP PH >>> ♦ TRIP Io HIGH TRIP Io LOW ♦ TRIP I2 > ♦ TRIP I2/I1 > ♦ TRIP I2/I1 >> Detail of available information can be consulted for each event, in accordance with the list below: TRIP PH > 17/06 14:22:00 17/06/03 14:22:00.990 SETTING set 1 CURRENT I1 745 A CURRENT I2 743 A CURRENT I3 746 A CURRENT Io 0.1 A ANGLE Vp/I1 0° ANGLE Vp/I3 0° ANGLE Vp/Io 0° 6.3 E R Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day: Month: Year Hour: Minute: Second. Millisecond Active setting group when tripping Set 1 or Set 2 Phase 1 current measured at disappearance of the trip Phase 2 current measured at disappearance of the trip Phase 3 current measured at disappearance of the trip Earth fault current measured at disappearance of the trip Angle between the polarization voltage and I1, measured at disappearance of the trip Angle between the polarization voltage and I3, measured at disappearance of the trip Angle between the polarization voltage and I0, measured at disappearance of the trip Thermal overload event Events are recorded as soon as a trip or alarm threshold of the voltage or frequency functions is reached: ♦ TRIP THERM REP ♦ ALRM THERM REP Detail of available information can be consulted for each event, in accordance with the list below: This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 25 Issue : b 6.3.1 Thermal alarm ALRM THERM REP S 17/06 13:25:55 R 17/06/03 13:25:55.240 SETTING set 1 CURRENT I1 2484 A CURRENT I2 0A CURRENT I3 0A CURRENT Io 0,0 A THERMAL STATE I1 90,0 % THERMAL STATE I2 0% THERMAL STATE I3 0% Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day: Month: Year Hour: Minute: Second. Millisecond Active setting group when tripping Set 1 or Set 2 Phase 1 current measured at appearance of alarm Phase 2 current measured at appearance of alarm Phase 3 current measured at appearance of alarm Earth fault 1 current measured at appearance of alarm Phase 1 thermal state measured at appearance of alarm Phase 2 thermal state measured at appearance of alarm Phase 3 thermal state measured at appearance of alarm 6.3.2 Thermal trip TRIP THERM REP S 17/06 13:25:59 R 17/06/03 13:26:59.920 SETTING set 1 CURRENT I1 2490 A CURRENT I2 0A CURRENT I3 0A CURRENT Io 0,0 A THERMAL STATE I1 100,0 % THERMAL STATE I2 0% THERMAL STATE I3 0% This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day: Month: Year Hour: Minute: Second. Millisecond Active setting group when tripping Set 1 or Set 2 Phase 1 Current measured at appearance of trip Phase 2 Current measured at appearance of trip Phase 3 Current measured at appearance of trip Earth fault Current measured at appearance of trip Phase 1 thermal state measured at appearance of trip Phase 2 thermal state measured at appearance of trip Phase 3 thermal state measured at appearance of trip User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 26 Issue : b 6.4 Customized inputs events Events are recorded as soon as one of the customized input status changes. ♦ TRIP GENERIC Detail of available information can be consulted for each event, in accordance with the list below: GENERIC 17/06 13:42:23 17/06/03 13:42:23.240 SETTING set 1 6.5 S R Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day / Month / Year Hour: Minute: Second. Millisecond Active setting group Set 1 or Set 2 Other events The contents of the following events can be specified: ♦ ALRM NB OPERAS ♦ ALRM A2 CUTOFF ♦ CB FAIL ♦ DISC LOCA/REMO ♦ MODE REMOTE ♦ UNLISTED EVENT ♦ SETTING SET 2 ♦ TRIP TELECONTR ♦ RECLOSE TELECO Detail of available information can be consulted for each event, in accordance with the list below: ALRM NB OPERAS S 25:6 9:35:45 R 25/6/95 9:35:45.011 SETTING set 1 6.6 Type of fault Start or End of fault Day/Month Hour/Minute/Second - Dated event Relative/Synchronous Day / Month / Year Hour: Minute: Second. Millisecond Active setting group Set 1 or Set 2 Acknowledgement of events The acknowledgement of the last event is carried out while pressing on CLEAR key: TRIP PH > 10/12 16:38.15 6.7 D R CLEAR ACKNOWLEDGE ALL Confirm: ENTER ENTER CURRENT I1 0,0 A Reading of the last 250 memorized events After acknowledgement, the memorized events still may be read. It is necessary to use the local sub-menu EVENTS of the HMI. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 27 Issue : b 7. List of faults or operation messages The following messages are locally displayed in real time on LCD display throughout fault. Messages related to instantaneous type functions: INSTANT. PHASE THRESHOLD>, INSTANT. PHASE THRESHOLD >> INSTANT. PHASE THRESHOLD >>> INSTANT. EARTH HIGH THRESHOLD INSTANT. EARTH LOW THRESHOLD Messages related to trip type functions: TRIP PHASE THRESHOLD >>> TRIP PHASE THRESHOLD >> TRIP PHASE THRESHOLD > TRIP EARTH HIGH THRESHOLD TRIP EARTH LOW THRESHOLD TRIP THERMAL REPLICA TRIP BY TELECONTROL TRIP GENERIC FUNCTION Messages related to alarm type functions: ALARM NUMBER OPERATIONS ALARM A2 CUTOFF CIRCUIT BREAKER FAIL DISCORDANCE : LOCAL / REMOTE ALARM THERMAL REPLICA Various messages: RECLOSE BY TELECONTROL REMOTE MODE UNLISTED EVENT Note: disappearance of cut A² and number of operations alarms is done by resetting the COUNTERS menu. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 28 Issue : b 8. Connection of NPI800 and NPID800 protections 8.1 Description of the terminal blocks Extension board (connectors E, F, G and RS485-2) is optional on the NPI800. + - R S 485-1 E 1 F 7 S1 IA A S2 6 S1 1 IB S2 1 5 B G 5 1 S1 IC C 1 S2 D S1 I0 S2 7 - + - R S 485-2 AU X This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 + Date : 01/2004 Print :11/03/2004 Sheet : 29 Issue : b 8.2 Connections Connections Location Characteristics Modbus® or IEC870-5-103 Communication RS485-1 RS485-2 Connection of the VTs A Screw terminal block. Section of wire 0.6 to 2.5 mm² Logical inputs B Screw terminal block. Section of wire 0.6 to 2.5 mm² Relays C and D Screw terminal block. Section of wire 0.6 to 2.5 mm² Auxiliary supply AUX Screw terminal block. Section of wire 0.6 to 2.5 mm² Relays (optional board) E and F Screw terminal block. Section of wire 0.6 to 2.5 mm² Logical inputs (optional board) G Screw terminal block. Section of wire 0.6 to 2.5 mm² Connection of the CTs IA to IO 4 mm ring type terminal. Section of wire ≤ 6 mm² 8.3 Screw terminal block. Section of wire 0.6 to 2.5 mm² Diagrams Type of relay Observation NPI 800 NPIR 800 S 38018 NPI 800 with recloser NPID 800 NPIDR 800 This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization Reference of diagram S 38023 S 38019 NPID 800 with recloser User’s Guide NPI 800 and NPID 800 S 38020 Date : 01/2004 Print :11/03/2004 Sheet : 30 Issue : b 8.4 Connection of the current inputs Connection is done by 6mm² ring terminals for M4 screw. It is identical for all the variants of inputs: ♦ Phases CT 1A or 5A ♦ Earth-fault CT 1A or 5A or CT Ring. Respect the rotating sense of phases and the direction of the connection of phases. 8.5 Connection of the Modbus RS485 communication 8.5.1 Characteristics of the network cable Recommended characteristics for the cable: • Shielded twisted pairs, maximum length 1000 m. • resistance < 100 ohms/km • capacity between wires < 60 pF/m • capacity between wire and shield < 100 pF/m It is imperatively necessary to tighten the fixing clamp on the shield and not on insulator, in order to ensure continuity of the shield of the cable and its earthing. 8.5.2 Resistance of adaptation Connect a 120 ohms resistance of adaptation to each protection located at each end of the network. It is necessary to connect the Rterm +T/R according to the diagram RS485 * +T/R -T/R 120 Ohms R term If the Master is connected at one end of the network, it is necessary to place a resistance of adaptation on the Master and another on the protection located at the other end of line using the switches of the communication board. This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization User’s Guide NPI 800 and NPID 800 Date : 01/2004 Print :11/03/2004 Sheet : 31 Issue : b