Folleto 1377

Anuncio
line discharge class 4
construction design I
Clase de descarga de linea 4 Forma constructiva I
Metal oxide surge arrester
Surge arresters for high voltage systems
Type series SB 6/20.4-I to SB 420/20.4-I
Field of application
Protection of transformers, switch-gears and plants against atmospheric and switching overvoltages
Selection of metal oxide surge arresters
The selection of the rated and the continuous operating voltage of the arresters is depending on the
neutral performance of the networks. Guidelines for selection: see DIN VDE 0675/part 5 and IEC 60099-5
Design
porcelain housing: brown glazed (grey on inquiry),
fittings: Al alloy
connections: clamps, screws, nuts hot dip galv. or stainless steel
Optional accessories
Monitoring spark gap, surge counter, diagnostic appliance
Operating conditions
ambient temperature:
rated frequency:
-60°C to +55°C
48 cps to 62 cps
Technical parameters
Raten voltage Ur :
nominal discharge current :
high current impulse (4/10) :
long duration current impulse:
6 kV to 420 kV
20 kA
100 kA
1200 A /2000 µs
Line discharge class :
rated short circuit current:
specific energy withstand
acc. to IEC 60099-4:
double impulse 3000 µs:
4
40 to 63 kA
9,2 kJ / kVUr
16 kJ / kVUr
Pararrayos de óxido de zinc
Pararrayos para alta tensión
Tipos SB 6/20.4-I a SB 420/20.4-I
Campos de aplicación
Protección de transformadores, equipos e instalaciones eléctricas contra sobretensiones atmosféricas y de
maniobra
Selección del pararrayos
La selección de la tension asignada y la tension de operación continua del pararrayos depende de las
condiciones de puesta a tierra de la red. Criterios de selección: ver DIN VDE 0675/ part 5 y IEC 60099-5.
issue 01/ 05
versión 01/ 05
Diseño
Envolvente de porcelana vidriada color marrón (gris bajo solicitud)
Terminales : aleación de aluminio
Conexiones : abrazaderas, tornillos y tuercas acero galvanizado en caliente o acero inoxidable.
Accesorios opcionales
Entrehierros de control, contador de descargas, unidad de diagnóstico.
Temperatura ambiente:
Frecuencia de la red:
Prospectus no. 1377 en / sp
Folleto N°
1377 en / esp
Condiciones normales de operación
-60°C ... +55°C
48 Hz ... 62 Hz
Datos técnicos
Tensión asignada Ur
Corriente nominal de descarga:
Impulso de corriente de alta
amplitud (4/10):
Impulso de corriente de larga duración
6 kV ... 240 kV
20 kA
100 kA
1200 A / 2000 µs
Clase de descarga de linea:
Corriente de cortocircuito asignada:
Capacidad de absorción de energia
según CEI 60099-4:
con doble impulso de 3000 µs:
4
40 ... 63 kA
9,2 kJ / kVUr
16 kJ / kVUr
Page
1/4
rated continuous
temporary
voltage/ operating
overvoltage
1)
Tensión voltage/
TOV /
asignada Tensión de Sobretensión
operación
1)
temporal
continua
type /
Tipo
SB 6/20.4-I
SB 12/20.4-I
SB 18/20.4-I
SB 30/20.4-I
SB 48/20.4-I
SB 60/20.4-I
SB 72/20.4-I
SB 75/20.4-I
SB 78/20.4-I
SB 81/20.4-I
SB 84/20.4-I
SB 90/20.4-I
SB 96/20.4-I
SB 102/20.4-I
SB 108/20.4-I
SB 114/20.4-I
SB 120/20.4-I
SB 123/20.4-I
SB 132/20.4-I
SB 138/20.4-I
SB 144/20.4-I
SB 150/20.4-I
SB 168/20.4-I
SB 186/20.4-I
SB 192/20.4-I
SB 198/20.4-I
SB 210/20.4-I
SB 214/20.4-I
SB 228/20.4-I
SB 240/20.4-I
SB 264/20.4-I
SB 288/20.4-I
SB 336/20.4-I
SB 342/20.4-I
SB 360/20.4-I
SB 366/20.4-I
SB 372/20.4-I
SB 390/20.4-I
SB 396/20.4-I
SB 420/20.4-I
Ur
Uc
U1s
U10s
kV
kV
kV
kV
6
12
18
30
48
60
72
75
78
81
84
90
96
102
108
114
120
123
132
138
144
150
168
186
192
198
210
214
228
240
264
288
336
342
360
366
372
390
396
420
4,8
9,6
14,4
24,0
38,4
48
58
60
62
65
67
72
77
82
86
91
96
98
106
110
115
123
134
149
154
158
168
171
182
192
211
230
269
274
288
293
298
312
317
336
6,9
13,8
20,7
34,5
55,2
69
83
86
90
93
97
104
110
117
124
131
138
141
152
159
166
173
193
214
221
228
242
246
262
276
304
331
386
393
414
421
428
449
455
483
residual voltage at steep, lightning and switching impulse current /
Tensión residual con impulso de corriente de frente escarpado, impulso de
maniobra e impulso tipo rayo
min.
housing
size /
Tamaño
minimo
de la envolvente
10 kA
5 kA
10 kA
20 kA
40 kA
250 A
500 A
1000 A 2000 A
(1/2 µs) (8/20 µs) (8/20 µs) (8/20 µs) (8/20 µs) (30/70µs) (30/70µs) (30/70µs) (30/70µs)
kV
6,5
15,6
12,9
31,1
19,4
46,7
32,3
77,8
51,6
124,4
65
156
77
187
81
194
84
202
87
210
90
218
97
233
103
248
110
265
116
280
123
296
129
311
132
319
142
342
148
357
155
374
161
400
181
435
200
482
206
498
213
513
226
544
230
555
245
591
258
622
284
685
310
746
361
870
368
887
387
933
393
948
400
964
419
1011
426
1026
452
1089
kV
kV
13,7
14,4
27,4
28,8
41,0
43,2
68,4
72,0
109,4
115,2
137
144
164
173
171
180
178
187
184
194
192
202
205
216
219
230
233
245
246
259
260
274
274
288
280
295
301
317
314
331
329
346
352
370
383
403
424
446
438
461
451
475
479
504
488
514
520
547
547
576
602
634
656
691
766
806
780
821
821
864
834
878
848
893
889
936
903
950
958
1008
kV
kV
15,6
31,1
46,7
77,8
124,4
156
187
194
202
210
218
233
248
265
280
296
311
319
342
357
374
400
435
482
498
513
544
555
591
622
685
746
870
887
933
948
964
1011
1026
1089
17,0
34,0
51,0
85,0
135,9
170
204
212
221
229
238
255
271
289
306
323
340
348
374
391
408
437
476
526
544
561
595
607
645
680
748
815
951
969
1020
1036
1054
1104
1121
1189
kV
kV
kV
kV
11,7
23,3
35,0
58,3
93,3
117
140
146
151
157
164
175
186
198
210
222
233
239
257
268
280
300
326
361
373
385
408
416
443
467
514
560
653
665
700
711
723
758
770
816
11,9
23,8
35,6
59,4
95,0
119
143
149
154
160
167
178
190
202
214
226
238
243
262
273
285
305
332
368
380
392
416
424
451
475
523
570
665
677
713
724
737
772
784
832
12,2
24,5
36,7
61,2
97,9
122
147
153
159
165
172
184
196
208
220
233
245
251
269
281
294
315
343
379
392
404
428
437
465
490
539
587
685
698
734
746
759
796
808
857
12,5
25,1
37,6
62,6
100,2
125
151
157
163
169
176
188
200
213
225
238
251
257
276
288
301
322
351
388
401
413
438
447
476
501
552
601
701
714
752
764
777
814
827
877
1
1
2
3
4
5
6
6
6
6
6
7
7
7
7
8
8
8
8
8
8
8
9
10
10
11
11
11
2x8
2x8
2x9
2x9
2x11
2x11
2x11
2x11
2x11
2x11
2x11
2x11
1) With a prior energy stress of two line discharges of class 4 / Con carga previa de 2 descargas de linea de clase 4
Power frequency voltage versus time characteristic (TOV) (initial temperature +60°C)
Curva característica tensión a.c. - tiempo (TOV) (Temperatura inicial + 60°C)
1,4
1,3
without prestress / sin carga previo
prestressed with two line discharges of class 4/
Con carga previa de 2 descargas de linea de clase 4
U/ Ur
1,2
1,1
1,0
continouos operating voltage /
tensión de operación continua (Uc)
0,9
0,8
0,7
0,1
1
10
100
1000
10000
t [s]
Page
2/4
housing
size /
Tamaño de
la envolvente
height /
Altura
creepage
distance /
Distancia
de fuga
± 5%
h
mm
470
540
610
680
890
1100
1380
1520
1750
1980
2200
2200
2200
3040
3500
4400
1
2
3
4
5
6
7
8
9
10
11
12
13
2x8
2x9
2x11
weight /
Peso
m
kg
32
38
46
54
71
90
115
132
147
168
200
210
221
256
298
415
mm
520
750
980
1210
1950
2630
3550
4000
4700
5450
6250
6800
7595
8000
9400
12500
insulation of arrester housing
Figure/
Figura
(applied to 1000m a.s.l)
Aislamiento exterior de la envolvente
a frecuencia
industrial
a impulso
de rayo
a impulso
de maniobra
PFWL
50 Hz
kV
60
75
90
100
145
190
250
280
285
315
360
360
360
465
535
655
LIWL
1.2/50
kV
140
170
205
240
345
450
585
655
670
730
835
835
835
1085
1245
1530
SIWL
250/2500
kV
105
130
160
185
265
345
450
505
515
560
645
645
645
835
960
1175
1
1
1
1
1
1
1
1
2
2
2
2
2
3
3
4
Ø900
Ø1250
h
h
h
h
Ø700
Ø700
Figure / Figura 1
Figure / Figura 2
Figure / Figura 3
Figure / Figura 4
Mechanical withstand in acc. to IEC 60099-4, Annex N.3 /
Propiedades mecánicas según IEC 60099-4, Anexo 3
Max. permissible dynamic service load
Máxima carga dinámica permisible
MPDSL
Permissible static service load
Carga estática permisible
PSSL
C 120
13380 Nm
5400 Nm
C 130
23000 Nm
9200 Nm
Page
3/4
earth terminals / Terminales de tierra
line terminals / Terminales de linea
type / Tipo X
100
Ø14 M12
max. Ø32mm
110
154
M12
45
60
45
45
80
type / Tipo A
25
147
Ø230
type / Tipo Y
100
50
M12
45
10
Ø14
154
110
45
25
147
Ø230
type / Tipo C
80
type / Tipo B
60
type / Tipo Z
25
88
132
80
110
60
Ø30
Ø13.5
163
Variants of installation and drilling plan / Variantes de instalación y ubicación de orificios
type / Tipo L
type / Tipo M
type / Tipo N
20
20
8
42
M20
34
10
M16
Ø18
Ø270
Ø24
310
Ø270
120°
120°
310
Ø18
How to order / Ejemplo de pedido
address / Dirección:
Metal oxide surge arrester with porcelain housing /
Pararrayos de ZnO con envolvente en porcelana
SB 120/20.4-I
Housing / Envolvente
6
line connection / Terminales de linea
variant of installation / Variante de instalación
earth connection / Terminales de tierra
A
N
X
TRIDELTA
Überspannungsableiter GmbH
Marie-Curie-Str. 3
07629 Hermsdorf
e-mail: [email protected]
Reg.Nr. 3453 - 01
Specifications in this leaflat are subject to change without notice. /
Especificaciones sujetas a modificacion sin previo aviso
Teléfono:
Telefax:
(+49 3 66 01) 6-19 51
(+49 3 66 01) 6-40 48
www.tridelta.de
Page
4/4
Descargar