Folleto 1335

Anuncio
Type series SB 6/10.2-0 to SB 240/10.2-0
Field of application
Protection of transformers, switch-gears and plants against atmospheric and switching overvoltages.
Selection of metal oxide surge arresters
The selection of the rated and the continuous operating voltage of the arresters is depending on the
neutral performance of the networks. Guidelines for selection: see DIN VDE 0675/part 5 and IEC 60099-5
Design
porcelain housing: brown glazed (grey on inquiry)
fittings:
Al alloy
connections: clamps, screws, nuts hot dip. galv. or stainless steel
line discharge class 2
construction design 0
Clase de descarga de linea 2 Forma constructiva 0
Metal oxide surge arrester
Surge arresters for high voltage systems
Optional accessories
Monitoring spark gap, surge counter, diagnostic appliance
Operating conditions
ambient temperature:
rated frequency:
-60°C to +55°C
48 cps to 62 cps
Technical parameters
Rated voltage Ur
nominal discharge current:
high current impulse (4/10):
long duration current impulse
6 kV to 240 kV
10 kA
100 kA
500 A / 2000 µs
Line discharge class :
rated short circuit current:
specific energy withstand
acc. to IEC 60099-4:
double impulse 3000 µs:
2
40 ... 50 kA
4,5 kJ / kVUr
8,0 kJ / kVUr
Pararrayos de óxido de zinc
Pararrayos para alta tensión
Tipos SB 6/10.2-0 a SB 240/10.2-0
Campos de aplicación
Protección de transformadores, equipos e instalaciones eléctricas contra sobretensiones atmosféricas y de
maniobra
Selección del pararrayos
La selección de la tension asignada y la tension de operación continua del pararrayos depende de las
condiciones de puesta a tierra de la red. Criterios de selección: ver DIN VDE 0675/ part 5 y IEC 60099-5.
Diseño
Accesorios opcionales
Entrehierros de control, contador de descargas, unidad de diagnóstico.
Condiciones normales de operación
Temperatura ambiente:
Frecuencia de la red:
-60°C ... +55°C
48 Hz ... 62 Hz
Datos técnicos
Tensión asignada Ur
Corriente nominal de descarga:
Impulso de corriente de alta
amplitud (4/10) :
Impulso de corriente de larga duración
6 kV ... 240 kV
10 kA
100 kA
500 A / 2000 µs
Clase de descarga de linea:
Corriente de cortocircuito asignada:
Capacidad de absorción de energia
según CEI 60099-4:
con doble impulso de 3000µs:
2
40 ... 50 kA
4,5 kJ / kVUr
8,0 kJ / kVUr
Page 1 / 4
Prospectus no. 1335 en / esp
Folleto N°
1335 en / esp
issue 01/ 05
versión 01/ 05
Envolvente de porcelana vidriada color marrón (gris bajo solicitud)
Terminales : aleación de aluminio
Conexiones : abrazaderas, tornillos y tuercas acero galvanizado en caliente o acero inoxidable.
type /
Tipo
SB 6/10.2-0
SB 9/10.2-0
SB 12/10.2-0
SB 15/10.2-0
SB 18/10.2-0
SB 21/10.2-0
SB 24/10.2-0
SB 27/10.2-0
SB 30/10.2-0
SB 33/10.2-0
SB 36/10.2-0
SB 39/10.2-0
SB 42/10.2-0
SB 48/10.2-0
SB 51/10.2-0
SB 54/10.2-0
SB 60/10.2-0
SB 63/10.2-0
SB 66/10.2-0
SB 72/10.2-0
SB 75/10.2-0
SB 84/10.2-0
SB 90/10.2-0
SB 96/10.2-0
SB 99/10.2-0
SB 102/10.2-0
SB 108/10.2-0
SB 120/10.2-0
SB 123/10.2-0
SB 132/10.2-0
SB 138/10.2-0
SB 144/10.2-0
SB 150/10.2-0
SB 168/10.2-0
SB 186/10.2-0
SB 192/10.2-0
SB 198/10.2-0
SB 210/10.2-0
SB 214/10.2-0
SB 228/10.2-0
SB 240/10.2-0
rated
voltage /
Tensión
asignada
continuous
temporary
1)
operating overvoltage TOV /
Sobretensión
voltage /
1)
temporal
Tensión de
operación
continua
residual voltage at steep, lightning and switching impulse current /
Tensión residual con impulso de corriente de frente escarpado, de maniobra
y tipo rayo
Ur
Uc
U1s
U10s
10 kA
5 kA
10 kA
20 kA
40 kA
250 A
500 A
1000 A 2000 A
(1/2 µs) (8/20 µs) (8/20 µs) (8/20 µs) (8/20 µs) (30/70µs) (30/70µs) (30/70µs) (30/70µs)
kV
6
9
12
15
18
21
24
27
30
33
36
39
42
48
51
54
60
63
66
72
75
84
90
96
99
102
108
120
123
132
138
144
150
168
186
192
198
210
214
228
240
kV
4,8
7,2
9,6
12,0
14,4
16,8
19,2
21,6
24,0
26,4
28,8
31,2
33,6
38,4
41
43
48
50
53
58
60
67
72
77
79
82
86
96
98
106
110
115
123
134
149
154
158
168
171
182
192
kV
6,9
10,4
13,8
17,3
20,7
24,2
27,6
31,1
34,5
38,0
41,4
44,9
48,3
55,2
59
62
69
72
76
83
86
97
104
110
114
117
124
138
141
152
159
166
173
193
214
221
228
242
246
262
276
kV
6,5
9,8
13,0
16,3
19,6
22,8
26,1
29,4
32,7
35,9
39,2
42,5
45,7
52,3
55
58
65
68
71
78
81
91
98
104
107
111
117
130
134
143
150
156
163
183
202
209
215
228
233
248
261
kV
17,6
26,3
35,1
43,9
52,7
61,5
70,2
79,0
87,8
96,6
105,4
114,2
123,0
140,5
150
158
176
185
194
211
220
245
263
281
289
298
316
351
360
386
404
421
447
492
545
562
580
615
626
667
702
kV
15,0
22,5
30,0
37,5
45,0
52,5
60,0
67,5
75,0
82,5
90,1
97,6
105,1
120,0
128
135
150
158
165
180
188
210
225
240
247
255
270
300
307
330
345
360
382
420
465
480
495
525
535
570
600
kV
16,0
23,9
31,9
39,9
47,9
55,9
63,8
71,8
79,8
87,8
95,8
103,8
111,8
127,7
136
144
160
168
176
192
200
223
239
255
263
271
287
319
327
351
367
383
406
447
495
511
527
559
569
606
638
kV
17,6
26,3
35,1
43,9
52,7
61,5
70,2
79,0
87,8
96,6
105,4
114,2
123,0
140,5
150
158
176
185
194
211
220
245
263
281
289
298
316
351
360
386
404
421
447
492
545
562
580
615
626
667
702
kV
20,2
30,1
40,2
50,3
60,4
70,4
80,4
90,5
100,5
110,6
120,7
130,8
140,9
160,9
171
181
202
212
222
242
252
281
301
321
331
341
362
402
412
442
462
483
512
563
624
644
664
704
717
764
804
kV
12,5
18,7
24,9
31,2
37,4
43,7
49,8
56,1
62,3
68,6
74,8
81,1
87,3
99,7
106
112
125
131
137
150
156
174
187
199
205
212
224
249
255
274
287
299
317
349
387
399
412
437
444
473
498
kV
12,9
19,3
25,8
32,2
38,7
45,2
51,6
58,0
64,5
70,9
77,4
83,9
90,3
103,2
110
116
129
136
142
155
162
180
193
206
213
219
232
258
264
284
297
309
328
361
400
413
426
452
460
490
516
kV
13,5
20,1
26,9
33,6
40,3
47,1
53,7
60,5
67,2
73,9
80,7
87,4
94,1
107,5
115
121
135
141
148
162
168
188
201
215
221
228
242
269
275
296
309
322
342
376
417
430
444
471
479
510
537
kV
14,1
21,1
28,1
35,2
42,2
49,3
56,3
63,3
70,4
77,4
84,5
91,6
98,6
112,6
120
127
141
148
155
169
176
197
211
225
232
239
253
281
288
310
324
338
358
394
437
451
465
493
502
534
563
min.
housing
size /
Tamaño
mínimo
de la envolvente
1
1
1
1
1
2
2
2
2
2
2
3
3
3
4
4
4
4
4
4
5
5
5
5
6
6
6
6
7
7
7
7
7
2x5
2x6
2x6
2x6
2x6
2x6
2x6
2x6
1) With a prior energy stress of two line disharges of class 2 / Con una carga previa de 2 descargas de linea de clase 2
Power frequency voltage versus time characteristic (TOV) (initial temperature +60°C)
Curva característica tensión - tiempo (TOV) (Temperatura inicial + 60°C)
1,4
without prestress / sin carga previa
U / Ur
1,3
prestressed: two line discharges of class 2 /
con carga previa : 2 descargas de linea de clase 2
1,2
1,1
1,0
0,9
continuous operating voltage / tensión de operación continua (Uc)
0,8
0,7
0,1
1
10
100
t(s)
1000
10000
Page 2 / 4
housing size
height
Tamaño la de Altura
envolvente
creepage
distance
Distancia de
fuga
weight
Peso
(applied to 1000m a.s.l.)
figure
Figura
Aislamiento exterior de la envolvente
a frecuencia
industrial
a impulso
de rayo
a impulso
de maniobra
m
PFWL
50 Hz
LIWL
1.2/50
SIWL
250/2500
kV
± 5%
h
insulation of arrester housing
mm
mm
kg
kV
kV
1
415
530
25
55
120
95
1
2
555
990
33
90
190
150
1
3
695
1440
38
125
260
205
1
4
835
1900
46
155
325
255
1
5
1045
2590
59
210
435
340
1
6
1325
3500
72
275
575
450
1
7
1535
4190
88
325
675
530
1
8
1535
4495
93
325
675
530
1
9
1185
3075
63
240
505
395
1
10
1395
3730
76
290
605
475
1
2x5
2090
5180
160
355
735
580
2
2x6
2650
7000
181
455
945
740
2
Figure / Figura 2
h
700
h
Figure / Figura 1
Mechanical withstand in acc. to IEC 60099-4 /
Propiedades mecánicas según IEC 60099-4
C 120
Max. permissible dynamic service load
Máxima carga dinámica permisible
MPDSL
Permissible static service load
Carga estática permisible
PSSL
6500 Nm
2600 Nm
Page 3 / 4
line terminals / Terminales de linea
type / Tipo XÆ 14
M12
max. Æ 32 mm
45
110
154
M12
45
45
80
100
60
type / Tipo A
earth terminals / Terminales de tierra
25
147
230
type / Tipo Y
M12
50
10
25
45
110
154
Æ14
80
100
45
type / Tipo B
147
230
type / Tipo Z
60
25
88
80
132
110
Æ30
60
type / Tipo C
Æ 13.5
163
Variants of installation and drilling plan / Variantes de instalación y ubicación de orificios
type /Tipo T
type / Tipo R
type /Tipo Q
M16
20
20
34
10
34
15
M20
M16
120°
Æ 27
0
Æ24
310
120°
310
Æ27
0
How to order / Ejemplo de pedido
address / Dirección:
Metal oxide surge arrester with porcelain housing /
Pararrayos de ZnO con envolvente en porcelana
SB 120/10.2-0
Housing / Envolvente
6
TRIDELTA
Überspannungsableiter GmbH
Marie-Curie-Str. 3
07629 Hermsdorf
line connection / Terminales de linea
variant of installation / Variante de instalación
earth connection / Terminales de tierra
A
Q
X
Specifications in this leaflat are subject to change without notice. /
Especificaciones sujetas a modificacion sin previo aviso
e-mail: [email protected]
Teléfono:
Telefax:
(+49 3 66 01) 6-19 51
(+49 3 66 01) 6-40 48
Reg.Nr. 3453 - 01
www.tridelta.de
Page 4 / 4
Descargar