Subido por Ed Rdguez

ARc Flash Calculation results

Anuncio
IEEE 1584 2018 Bus + Line + Load Side - Comprehensive Fault
Bus Name
Protective
Bus
Device Name kV
Project: QuebradillasWTP_PV-SYSTEM, Worst Case: Scenario - S0, S1, S2, S3, S4, S5, S6, S7, S8
Bus
Bus
Bolted
Arcing
Fault (kA) Fault (kA)
Prot Dev Prot Dev Trip/
Bolted
Arcing Delay
Fault
Fault
Time
(kA)
(kA)
(sec.)
Breaker
Opening
Time/Tol
(sec.)
Equip
Type
Electrode
Config
Box
Width
(in)
Box
Height
(in)
Box
Depth
(in)
Altitude
(feet)
Gap
(mm)
Arc Flash Working
Boundary Distance
(in)
(in)
Incident
Energy
(cal/cm2)
PPE Level / Notes
(*N)
Label #
BUS-BESS-01
MaxTripTime
@2.0s
0.48
25.82
19.38
8.59
6.45
2
0.0000
PNL
VCB
12
14
10
0
25
155
18
37.4
(*N2) (*N9) (*S8)
# 0001
BUS-BESS-02
MaxTripTime
@2.0s
0.48
25.82
19.38
8.59
6.45
2
0.0000
PNL
VCB
12
14
10
0
25
155
18
37.4
(*N2) (*N9) (*S8)
# 0002
BUS-GD-MSBHA1
MaxTripTime
@2.0s
0.48
26.26
19.67
8.80
6.59
2
0.0000
PNL
VCB
12
14
10
0
25
157
18
38.3
(*N2) (*N9) (*S8)
# 0001
BUS-GD-PVPHA1
MaxTripTime
@2.0s
0.48
25.28
19.02
8.40
6.32
2
0.0000
PNL
VCB
12
14
10
0
25
153
18
36.7
(*N2) (*N9) (*S8)
# 0002
BUS-MINI-POWERZONE
CB-MPZ
0.48
10.45
8.00
10.45
8.00
0.01
0.0000
PNL
VCB
12
14
10
0
25
5
18
0.18
(*S8)
# 0005
BUSS-WTP-MCC
MaxTripTime
@2.0s
0.48
24.05
17.71
7.38
5.44
2
0.0000
SWG
VCB
20
20
20
0
32
140
24
20.1
(*N2) (*N9) (*S8)
# 0003
BUSS-WTP-MSBHA1
MaxTripTime
@2.0s
0.48
37.38
25.45
11.57
7.87
2
0.0000
SWG
VCB
20
20
20
0
32
189
24
32.5
(*N2) (*N9) (*S8)
# 0002
8
PRIMARY (MCB0 LineSide) MaxTripTime
@2.0s
4.16
86.34
86.34
86.17
86.17
2
0.0000
SWG
VCB
30
45
30
0
104
690
36
439.6
(*N2) (*N9) (*N_ka) #
(*S2)
0005-Line
9
SECONDARY
0.48
3.39
2.16
3.39
2.16
2
0.0000
PNL
VCB
12
14
10
0
25
64
18
9.14
(*N3) (*N9) (*S7)
1
2
3
4
5
6
7
10
MCB
For additional information
refer to NFPA 70 E,
Standard for Electrical
Safety in the Workplace.
#Equip
(*N_ka) - Out of
Eval Failed IEEE 1584 kA
=0
Range. Lee
Equation Used.
Consider
NESC/EPRI
method to compare
11
#Bus Equip (*N2) < 80%
Eval Failed Cleared Fault
=0
Threshold
12
#Equip
Failed in
Scenarios
=0
13
14
15
(*N3) - Arcing
Current Low
Tolerances Used
(*N9) - Max Arcing
Duration Reached
IEEE 1584 2018
Bus + Line + Load
Side Comprehensive
Fault80% Cleared
Fault Threshold,
mis-coordination
not checked
Worst Case Bus + Line + Load
Only for:
Side
16
Worst Case:
17
18
(*S0) - SCENARIO
0
(*S1) - Scenario1
19
(*S2) - Scenario2
20
(*S3) - Scenario3
21
(*S4) - Scenario4
22
(*S5) - Scenario5
23
(*S6) - Scenario6
24
(*S7) - Scenario7
Equations used with permission from IEEE 1584, by IEEE. The IEEE disclaims any responsibility or liability resulting from the placement and use in the described manner.
Page 1
# 0009
Cable
Incident
Length From Energy at
Trip Device
Low
(ft)
Marginal
25.00
439.57
Incident Energy at
High Marginal
User Notes
IEEE 1584 2018 Bus + Line + Load Side - Comprehensive Fault
Bus Name
Protective
Bus
Device Name kV
Project: QuebradillasWTP_PV-SYSTEM, Worst Case: Scenario - S0, S1, S2, S3, S4, S5, S6, S7, S8
Bus
Bus
Bolted
Arcing
Fault (kA) Fault (kA)
Prot Dev Prot Dev Trip/
Bolted
Arcing Delay
Fault
Fault
Time
(kA)
(kA)
(sec.)
Breaker
Opening
Time/Tol
(sec.)
Equip
Type
Electrode
Config
Box
Width
(in)
Box
Height
(in)
Box
Depth
(in)
Altitude
(feet)
25
Equations used with permission from IEEE 1584, by IEEE. The IEEE disclaims any responsibility or liability resulting from the placement and use in the described manner.
Page 2
Gap
(mm)
Arc Flash Working
Boundary Distance
(in)
(in)
Incident
Energy
(cal/cm2)
PPE Level / Notes
(*N)
(*S8) - Scenario8
Label #
Cable
Incident
Length From Energy at
Trip Device
Low
(ft)
Marginal
Incident Energy at
High Marginal
User Notes
IEEE 1584 2018 Bus + Line + Load Side - Comprehensive Fault
Bus Name
1
2
3
4
5
6
7
8
9
10
11
12
13
User Notes2
Project: QuebradillasWTP_PV-SYSTEM, Worst Case: Scenario - S0, S1, S2, S3, S4, S5, S6, S7, S8
User Notes3
BUS-BESS-01
BUS-BESS-02
BUS-GD-MSBHA1
BUS-GD-PVPHA1
BUS-MINI-POWERZONE
BUSS-WTP-MCC
BUSS-WTP-MSBHA1
PRIMARY (MCB0 LineSide)
Date:
2024.08.19
13:01:42
-04'00'
SECONDARY
For additional information
refer to NFPA 70 E,
Standard for Electrical
Safety in the Workplace.
DN:
email=erodrigue
[email protected]
m
Date: 2024.08.19
13:02:56 -04'00'
14
15
16
17
18
19
20
21
22
23
24
Equations used with permission from IEEE 1584, by IEEE. The IEEE disclaims any responsibility or liability resulting from the placement and use in the described manner.
Page 3
DN:
[email protected]
m
Date: 2024.08.19 13:03:20 -04'00'
IEEE 1584 2018 Bus + Line + Load Side - Comprehensive Fault
Bus Name
User Notes2
Project: QuebradillasWTP_PV-SYSTEM, Worst Case: Scenario - S0, S1, S2, S3, S4, S5, S6, S7, S8
User Notes3
25
Equations used with permission from IEEE 1584, by IEEE. The IEEE disclaims any responsibility or liability resulting from the placement and use in the described manner.
Page 4