Subido por claudio sappa

diferencial 87t

Anuncio
(AP) 6 Application Notes
Application of Individual Protection Functions
2.1.8.2
Example 2: Autotransformer (P645) - Load Tap Changer
Figure 24 shows the application of a P645 to protect an autotransformer. The power
transformer data has been given: 175/175/30 MVA Autotransformer, YNyn0d1,
230/115/13.8 kV. The current transformer ratios are as follows: HV CT ratio - 800/5, LV
CT ratio - 1200/5 and TV CT ratio 2000/5.
Since the transformer has an on load tap changer on the HV side, the nominal voltage of
the HV winding must be set to the mid tap voltage level. According to the nameplate data,
the mid tap voltage is 218.5 kV. The mid tap voltage can also be calculated as follows:
100
Mid tap position
(5 15 )
2
230
100
218 .5kV
175/ 175/ 30 MVA
230/ 115/13. 8 kV
230kV
+5%/-15%
19 taps
a
b
c
YNynd1
A
a
B
b
C
c
Grounding transformer
inside the protection
zone
a
a
a
B
b
b
b
B
c
c
a
a
b
b
c
c
B
B
c
B
B
Yd 11 software interposing CT
Ydy0 software interposing CT
a
a
a
b
b
b
c
c
c
B
B
B
D
D
D
Ydy0 software interposing CT
P645
P4304ENb
Figure 24 - P645 used to protect an autotransformer with load tap changer
P64x/EN AP/A62
Page (AP) 6-41
(AP) 6 Application Notes
Application of Individual Protection Functions
Ratio correction:
The relay calculates the ratio correction factors as follows:
K amp ,T1CT
Inom ,T1CT
800
S ref
175 10 6
3 Vnom ,HV
K amp ,T5CT
K amp ,T3CT
1.730
218.5 103
3
Inom ,T5CT
1200
S ref
175 10 6
1.366
3 Vnom ,LV
3 115 103
Inom ,T 3CT
2000
S ref
175 10 6
3 Vnom ,TV
0.273
3 13.8 10 3
To check that the differential protection does not misoperate due to errors introduced by
the on load tap changer, the user may perform the following calculations.
Transformer nominal rating
Calculate HV full load current at both tap extremities and LV and TV full load current.
175 106
3 241500
HV full load current on tap 1 (5%)
418.37
160
HV full load current on tap 1 (5%)
418.37 A primary
2.615 A secondary
HV corrected current on tap 1 1.730 2.615 4.524 A secondary
HV full load current on tap 19 (-15%)
HV full load current on tap 19 (-15%)
175 10 6
3 195 .510 3
516.810
160
HV corrected current on tap 19 1.730 3.230
LV full load current
LV full load current
TV full load current
TV full load current
145 10 6
3 115 10 3
727 .963
240
3.230 A secondary
5.588 A secondary
727 .963 A primary
3.033 A secondary
30 10 6
3 13.8 10 3
1255 .109
400
516 .810 A primary
1255 .109 A primary
3.138 A secondary
Determine Idiff at both tap extremities (with mid tap correction).
LV correctedcurrent 1.366 3.033
Page (AP) 6-42
4.143
P64x/EN AP/A62
(AP) 6 Application Notes
Application of Individual Protection Functions
TV correctedcurrent 0.273 3.138
0.857
Idiff at tap 1
0.476 A
Idiff at tap 19
4.524 4.143 0.857
5.588 4.143 0.857
0.588 A
0.476
5
0.588
5
0.095 pu
0.118 pu
Determine Ibias at both tap extremities (with mid tap correction). The currents used in the
Ibias calculation are the currents after ratio and vector correction.
Ibias at tap 1
Ibias at tap 19
4.524 4.143 0.857
2
4.762 A
5.588 4.143 0.857
2
5.294 A
4.762
5
5.294
5
0.9524 pu
1.059 pu
Determine relay differential current.
Iop = Is1, (Ibias
Is1/K1)
Iop = K1 Ibias, (Is1/K1
Iop = K1
Is2 + K2
Ibias
Is2)
(Ibias - Is2), (Ibias
Is2)
Ibias at tap 1 is less than 5 A (1 pu) and greater than 3.33 A (0.667 pu); since Is2 is
set to the rated current (5 A), Iop is calculated as follows:
Iop = 0.3
4.762 = 1.429 A
Ibias at tap 19 is greater than 5 A; since Is2 is set to the rated current (5 A), Iop is
calculated as follows:
Is2 = 1 pu = 1
Iop = 0.3
5=5A
5 + 0.8
(5.294 - 5) = 1.735 A
Check Idiff < Iop by a 10% margin for each tap extremity and adjust Is1 and/or K1 as
necessary.
Tap 1: Since Idiff = 0.476A and 0.9Iop at tap 1 = 0.9 x 1.429 = 1.286 A
Therefore there is sufficient safety margin with K1 = 30% and Is1 = 0.2 pu.
Tap 19: Since Idiff = 0.588A and 0.9Iop at tap 19 = 0.9 x 1.735 = 1.562 A
Therefore there is sufficient safety margin with K1 = 30% and Is1 = 0.2 pu.
66.7% of transformer nominal rating
Calculate HV, LV and TV load current at 66.7% of the nominal MVA rating. The 66.7% is
the interception between Is1 and K1. It is determined as Is1/K1 100% = (0.2/0.3) 100
= 66.7%.
HV full load current on tap 1(5%) 0.667
HV full load current on tap 1(5%)
P64x/EN AP/A62
279 .05
160
175 10 6
3 241500
279.05 A primary
1.744 A secondary
Page (AP) 6-43
(AP) 6 Application Notes
Application of Individual Protection Functions
HV corrected current on tap 1 1.730 1.744
3.017 A sec ondary
175 10 6
HV full load current on tap 19 (-15%) 0.667
3 195 .510 3
344.71
160
HV full load current on tap 19 (-15%)
2.154 A secondary
HV corrected current on tap 19 1.730 2.154
LV full load current 0.667
LV full load current
485 .551
240
TV full load current 0.667
837.158
400
TV full load current
145 10 6
3 115 10 3
344 .71A primary
3.727 A sec ondary
485 .551A primary
2.023 A secondary
30 10 6
3 13.8 10 3
837.158 A primary
2.093 A secondary
Determine Idiff at both tap extremities (with mid tap correction).
LV corrected current 1.366 2.023
2.763 A
TV corrected current 0.273 2.093
0.571A
Idiff at tap 1
3.017 2.763 0.571
Idiff at tap 19
0.317 A
3.727 2.763 0.571
0.393 A
0.317
5
0.393
5
0.063 pu
0.0786 pu
Determine Ibias at both tap extremities (with mid tap correction). The currents used in
Ibias calculation are the currents after ratio and vector correction.
Ibias at tap 1
3.017 2.763 0.571
2
Ibias at tap 19
3.727 2.763 0.571
2
3.176 A
3.531A
3.176
5
3.531
5
0.635 pu
0.706 pu
Determine relay differential current.
Iop = Is1, (Is1/K1
Ibias)
Iop = K1 Ibias, (Is1/K1
Iop = K1
Is2 + K2
Ibias
Is2)
(Ibias - Is2), (Ibias
Is2)
Ibias at tap 1 is less than 3.33 A (0.667 pu); then Iop = 0.2 pu = 1 A
Ibias at tap 1 is less than 5 A (1 pu) and greater than 3.33 A (0.667 pu); since Is2 is
set to the rated current (5 A), Iop is calculated as follows:
Page (AP) 6-44
P64x/EN AP/A62
(AP) 6 Application Notes
Application of Individual Protection Functions
Iop = 0.3
3.531 = 1.059 A
Check Idiff < Iop by a 10% margin for each tap extremity and adjust Is1 and/or K1 as
necessary:
Tap 1: Since Idiff = 0.317 A and 0.9Iop at tap 1 = 0.9 x 1 = 0.9 A
Therefore there is sufficient safety margin with K1 = 30% and Is1 = 0.2 pu.
Tap 19: Since Idiff = 0.393 A and 0.9Iop at tap 19 = 0.9 x 1.059 = 0.953 A
Therefore there is sufficient safety margin with K1 = 30% Is1 = 0.2 pu.
Figure 25 shows the bias characteristic, the CT and tap changer errors (assumed
as 20%), and the bias, differential coordinates corresponding to full load current
and 66.7% of full load current. It can also be seen that it is necessary to check the
safety margin at the two knee-points of the bias characteristic.
2.5
Bias characteristic
CT and tap changer errors
2
nominal MVA, tap 1
nominal MVA, tap 17
66.7% of nominal MVA, tap 1
66.7% of nominal MVA, tap 17
1.5
1
0.5
0
0
0.5
1
1.5
2
Ibias/Inom
2.5
3
3.5
4
P4305ENa
Figure 25 - Safety margin at the two knee-points of the bias characteristic
Vector correction and zero sequence filtering
Vector correction is done by setting LV Vector Group in SYSTEM CONFIG to 0
and TV Vector Group in SYSTEM CONFIG to 1. The zero sequence filtering is
done by setting HV Grounding, LV Grounding and TV Grounding in SYSTEM
CONFIG to Grounded. The TV winding is grounded using a grounding transformer
inside the protected zone.
The system configuration and differential protection settings are shown in Figure
26:
P64x/EN AP/A62
Page (AP) 6-45
Descargar