RECLOSER CONTROLLER for Distribution Automation (Model Name : FTU – R200) JIN KWANG E & CORPORATION 705, Buk-ri, Namsa-myun, Yongin, Kyunggi-do, Korea Tel +82-31-333-3444 Fax +82-31-332-5300, 5301 Website http://www.jinkwang.co.kr E-mail [email protected] ISO 9001 certified Recloser controller FTU- R200 CONTENTS 1. 2. OVERVIEW................................................................................................................................................................................................. 8 1.1. Protection of Distribution Lines ........................................................................................................... 8 1.2. Function of Automatic Circuit Recloser ............................................................................................ 8 1.3. Main Features of FTU-R200 ................................................................................................................... 9 Technical Data ....................................................................................................................................................................................... 12 2.1.1. 2.1.2 Digital Processor .......................................................................................................................................12 Dual Processor Architecture ............................................................................................ 12 2.1.2Analog/Digital Conversion ......................................................................................................... 12 2.1.3. DSP..................................................................................................................................... 13 2.1.4. CPU .................................................................................................................................... 13 2.1.5. Functional Block Diagram ................................................................................................ 14 2.2. Environmental Conditions..................................................................................................................... 14 2.3. Inputs/Outputs .......................................................................................................................................... 15 2.4. Measurement .............................................................................................................................................17 2.4.1. Current ................................................................................................................................ 17 2.4.2. Voltage ............................................................................................................................... 17 2.4.3. Power ................................................................................................................................. 18 2.4.4. Power Factor ..................................................................................................................... 18 2.4.5. Frequency .......................................................................................................................... 18 2.4.6. Energy ................................................................................................................................ 18 2.4.7. Harmonic ........................................................................................................................... 18 www.jinkwang.co.kr 2 / 111 ISO 9001 certified 2.4.8. 2.5. 4. Demand Current and Power............................................................................................ 19 Communication .........................................................................................................................................19 2.5.1. Physical Layer .................................................................................................................... 19 2.5.2. Protocol for scada ............................................................................................................ 19 2.6. 3. Recloser controller FTU- R200 Recording .....................................................................................................................................................20 2.6.1. Event Recorder .................................................................................................................. 20 2.6.2. Waveform Event Recorder ............................................................................................... 21 Construct and External Connection ............................................................................................................................................. 22 3.1. Appearance & Dimension ....................................................................................................................22 3.2. Connector .................................................................................................................................................... 24 Front Panel Operations ..................................................................................................................................................................... 25 4.1. Button & LED Description ....................................................................................................................26 4.1.1. LCD Display ....................................................................................................................... 26 4.1.2. FTU Status ......................................................................................................................... 26 4.1.3. MENU/UP/DOWN/ENTER Buttons .................................................................................. 26 4.1.4. Serial Port .......................................................................................................................... 26 4.1.5. Ethernet/SCADA/Protection Communication Led ......................................................... 26 4.1.6. Battery Test & Lamp Test ................................................................................................ 27 4.1.7. Reset Button...................................................................................................................... 27 4.1.8. Function Led ..................................................................................................................... 27 4.1.9. RECLOSE/PROTECTION/GROUND Enable Buttons and LEDS ...................................... 28 4.1.10. REMOTE/CONTROL LOCK Buttons and LEDS ................................................................ 28 4.1.11. SELECT/OPEN/CLOSE Buttons and LEDS ........................................................................ 28 4.2. LCD Manipulation.....................................................................................................................................29 www.jinkwang.co.kr 3 / 111 ISO 9001 certified 4.2.1. 5. LCD Menu ......................................................................................................................... 30 Protection Functions .......................................................................................................................................................................... 35 5.1. 6 Recloser controller FTU- R200 Fault Detection .......................................................................................................................................... 35 5.1.1 Definite Time Protection ............................................................................................. 36 5.1.2 High Current Trip (HCT) .............................................................................................. 36 5.1.3 Single Shot Operation ................................................................................................. 37 5.1.4 TC Curve .......................................................................................................................... 37 5.1.5 Example of TC Curve Editing ........................................................................................... 39 5.1.6 Auto Reclosing Sequence ........................................................................................... 41 5.1.7 Sequence Coodination ................................................................................................. 43 5.2 Cold Load Pickup .................................................................................................................................44 5.3 Sensitive Earth Fault (SEF) Detection .............................................................................................. 45 5.4 Directional Blocking.................................................................................................................................46 5.5 Inrush Restraints .......................................................................................................................................47 5.6 Open Line Detection (Loss Of Phase)..............................................................................................47 5.7 Phase Sync. Check....................................................................................................................................48 5.8 Under Voltage Protection ..................................................................................................................... 48 5.9 Over Voltage Protection ........................................................................................................................ 49 5.10 Under Frequency Protection ................................................................................................................ 49 5.11 Multiple Protection Groups.................................................................................................................. 50 Configuration Setting......................................................................................................................................................................... 51 6.1 I/O Configuration .....................................................................................................................................51 www.jinkwang.co.kr 4 / 111 ISO 9001 certified 6.1.1 AC Rating .......................................................................................................................... 51 6.1.2 Demand Setting ................................................................................................................ 54 6.1.3 Wave Trigger ..................................................................................................................... 54 6.1.4 Close Interlock .................................................................................................................. 55 6.1.5 FI Reset Select ................................................................................................................... 55 6.1.6 Voltage Display ................................................................................................................. 55 6.2 8 Power Quality Measurement Funcion .............................................................................................55 6.2.1 Voltage & Current Unbalance ......................................................................................... 55 6.2.2 Short-Duration Voltage Variation ................................................................................... 56 6.2.3 Voltage & Current THD Alarm ........................................................................................ 58 6.3 7 Recloser controller FTU- R200 Communication .........................................................................................................................................58 6.3.1 Port Parameters ................................................................................................................ 58 6.3.2 DNP3.0 Parameters........................................................................................................... 60 6.3.3 IEC Parameters .................................................................................................................. 61 Status Monitoring & Control.......................................................................................................................................................... 62 7.1 Switch Control............................................................................................................................................62 7.2 Switch Status Monitoring ...................................................................................................................... 62 7.3 Battey Monitoring ....................................................................................................................................63 Measurements ....................................................................................................................................................................................... 64 8.1 Basic Electric Quantities ......................................................................................................................... 64 8.2 Sequence Components .......................................................................................................................... 64 8.3 Harmonics ....................................................................................................................................................65 8.4 Energy ............................................................................................................................................................65 www.jinkwang.co.kr 5 / 111 ISO 9001 certified 8.5 9 10 11 Recloser controller FTU- R200 Demand currents and power ..............................................................................................................66 Maintenance Software ....................................................................................................................................................................... 67 9.1 Overview .......................................................................................................................................................67 9.2 Operation of FTUMan............................................................................................................................ 68 9.2.1 Menu .................................................................................................................................. 68 9.2.2 Toolbar .............................................................................................................................. 70 9.2.3 Statusbar.............................................................................................................................71 9.2.4 Monitoring bar ................................................................................................................... 71 9.2.5 Function and configuration Setting ................................................................................. 71 9.2.6 Event .................................................................................................................................. 74 9.2.7 Measurement .................................................................................................................... 82 9.2.8 Status ................................................................................................................................. 88 9.2.9 Waveform .......................................................................................................................... 89 I/O Configuration Tool ...................................................................................................................................................................... 91 10.1 Overview .......................................................................................................................................................91 10.2 Operation of IOConfig .......................................................................................................................... 92 10.2.1 Menu .................................................................................................................................. 93 10.2.2 Toolbar .............................................................................................................................. 93 10.2.3 Input................................................................................................................................... 94 10.2.4 Output ............................................................................................................................... 95 DNP3.0 Index Configuration Tool ................................................................................................................................................ 96 11.1 Overview .......................................................................................................................................................96 11.2 Operation of DNPConfig...................................................................................................................... 97 www.jinkwang.co.kr 6 / 111 ISO 9001 certified 12 Recloser controller FTU- R200 11.3.1 Menu .................................................................................................................................. 98 11.3.2 Toolbar .............................................................................................................................. 99 11.3.3 Configuration Tool Box .................................................................................................. 10 0 11.3.4 Binary Input ..................................................................................................................... 10 0 11.3.5 Binary Output .................................................................................................................. 10 2 11.3.6 Analog Input ................................................................................................................... 10 3 11.3.7 Counter ............................................................................................................................ 10 5 Waveform Evaluation Tool............................................................................................................................................................ 107 12.1 Overview .................................................................................................................................................... 107 12.2 Operation of EvalTool ........................................................................................................................ 108 12.2.1 Menu ................................................................................................................................ 10 9 12.2.2 Toolbar .............................................................................................................................110 www.jinkwang.co.kr 7 / 111 ISO 9001 certified 1. Recloser controller FTU- R200 OVER VIEW 1.1. PROTECTION OF DISTRIBUTION LINES Distribution lines have their own equipment outdoors, the types of loads are various, and the configurations of the networks are flexible and complicated. There are many kinds of fault causes such as direct contact of trees or birds, natural phenomenon of lightning or heavy snow, and fault spread-out due to customer’s facilities. Among these faults, most of faults are temporary and the dominant fault type is ground-fault. For rapid fault detection and fault section isolation, blackout area minimization, many protection devices such as Recloser, Sectionalizer, and Line Fuse are adopted. Among these devices, Automatic Circuit Recloser is the most important protection device, whose main functions are fault current trip and auto-reclosing. One distribution line has over 2 Reclosers of serial connections or Recloser – Sectionalizer - Line Fuse of serial connections. This configuration is the concept of Primary Protection and Back-up Protection. In other words, protection coordination is required in the way that a protection device nearer to fault point operates first to eliminate the fault and other devices farther from fault point are configured to operate later with time delays. 1.2. FUNCTION OF AUTOMATIC CIRCUIT RECLOSER When a fault occurs on the load side of Recloser installed location, Recloser detects fault current, trips fault current at high speed, and does reclosing actions after the set time to re-activate the faulted section. In case of temporary fault, the fault can be removed by itself according to highspeed trip and dead time before reclosing actions. But, in case of permanent fault, because fault current is still detected after trip and reclosing actions of pre-set counts, Recloser is locked out finally as opened. Recloser has the time delay element in protection function of its controller and can be freely configured for protection coordination with other protection devices. www.jinkwang.co.kr 8 / 111 ISO 9001 certified 1.3. Recloser controller FTU- R200 MAIN FEATURES OF FTU-R200 Recloser body is connected serially to distribution line to operate open / close of the line, and Recloser Controller is in charge of measurements of currents, voltages, and other electric values, protection, control, status monitoring, recording, and communication. FTU-R200 is a kind of IED’s (Intelligent Electronic Device) for power system automation, which is a fully digitalized and microprocessor-based control device, and through connecting with this control device, Recloser can play a role of automated protection device. Main features of FTU-R200 are as follows, Measurements Magnitude and phase angle of voltages & currents(Fundamental frequency) Sequence components of 3-Phase voltages & currents True RMS, Harmonics and THD of voltages & currents Active, reactive and apparent power for each phase and 3-phase Energy(4-quadrant metering) Displacement Power Factor Frequency PQM, Fault, THD Counter Phase difference between source-side and load-side voltage Control Manual Recloser Open/Close at local or remote(Select Before Operation) Interlocking(Gas low, Handle lock, Operator place, Sync Fail, Live Load) Batter Test External Trip and Close By contact input(Optional) Enable or disable reclosing, protection and Ground function www.jinkwang.co.kr 9 / 111 ISO 9001 certified Recloser controller FTU- R200 Protection 3-stage over current protection Fast and Delayed TC trip elements for phase and earth fault 54 types of built-in TC Curves and 4 Customized TC Curves Definite time over-current element Definite time HCT(High Current Trip) SEF(Sensitive Earth Fault) Detection Auto-Reclosing(up to 4 shots) Cold Load protection(Pickup Adjustment) Magnetizing Inrush Restraints Sequence Coordination Open Line Detection Phase Sync. Fail Detection Over Voltage, Under Voltage Under Frequency Status Monitoring 10 Contact Inputs Open Line Detection Fault Indication Recloser, Protection, Ground Protection, Switch Open/Closed Over Voltage, Under Voltage, Under Frequency Handle Locked Gas Pressure Low External AC Power Loss Battery Discharged Enclosure Door Open Spare (3 Points : Optionally external trip and close command) www.jinkwang.co.kr 10 / 111 ISO 9001 certified Recloser controller FTU- R200 Event Recording Event recording with time-stamp I/O, Functional, System, Fault Current, Demand Current & Daily Max Current & Power Waveform Recording 8 Fault Waveforms 8 PQM Waveforms 1 Manual Trigger Waveform 128 samples/cycle, 20 cycles Saving COMTRADE File Format Counter FTU Restart count Switch Trip Count Fault Detection Count PQM Count THD Count Communication Protocols DNP3.0 DNP3.0 over TCP/IP SCADA Port IEC60870-5-101 IEC60870-5-104 Maintenance Port www.jinkwang.co.kr Modbus-RTU 11 / 111 Power, ISO 9001 certified 2. Recloser controller FTU- R200 TECHNICAL DATA 2.1.1. DIGITAL PROCESSOR 2.1.2 DUAL PROCESSOR ARCHITECTURE 9 32-bit RISC type micro-controller with on-chip flash program memory 9 32-bit floating-point Digital Signal Processor 9 Dual-Port Memory for communication between two processors 9 Data Memoty(SRAM) 9 Non-volatile Memory(1Mbytes) for storing events and parameters 9 Flash Mamory for stroring fault and PQM Waveforms 9 Real Time Clock 2.1.2ANALOG/DIGITAL CONVERSION 9 16-bit A/D Converter 9 Sampling rate : 128 samples/cycle 9 Anti-aliasing analog filter 9 One gain channel for each current input : effective 16-bit resolution for current measurements www.jinkwang.co.kr 12 / 111 ISO 9001 certified 2.1.3. 2.1.4. Recloser controller FTU- R200 DSP 9 Correction of analog input error 9 Fast Fourier Transform : phasor calculation 9 Electric quantities calculation & Fault Decision CPU 9 Status monitoring & Control Command 9 Local Human-Machine Interface 9 Event Recording 9 Remote Communication(DNP3.0, IEC60870-5-101 and IEC60870-5-104) 9 Self Diagnosis www.jinkwang.co.kr 13 / 111 ISO 9001 certified 2.1.5. Recloser controller FTU- R200 FUNCTIONAL BLOCK DIAGRAM Figure 2-1 Functional Block Diagram 2.2. ENVIRONMENTAL CONDITIONS Altitude < 2,000m Wind Speed < 40m/s Ambıent Temporature - 25 ~ +70°C, KSC 0220/1 Storage Temporature - 40 ~ +85°C Humidity < 95%RH www.jinkwang.co.kr 14 / 111 ISO 9001 certified Recloser controller FTU- R200 Dielectric withstand IEC 60255-5, 2kV Impulse voltage IEC 60255-5, 6kV for current input circuit IEC 60255-5, 4kV for voltage, power input & Contacts I/O Insulation resistance IEC 60255-5, >500MΩ (DC500V) High frequency disturbance IEC 61000-4-12 class 3 (2.5kV) Fast transient noise IEC61000-4-4 class 4 (4kV) Radio frequency noise IEC 61000-4-3 10V/m Vibrations IEC 60255-21-1 class 2 Mechanical Shock IEC 60255-21-2 class 2 Enclosure protection IP54 2.3. INPUTS/OUTPUTS Binary Contacts Input : 10 Points DC 24V Baised in the control box Opto-isolation(Viso) : 2,000 Vrms Delay time setting(10~500ms) for each contact input to suppress bouncing Signal Recloser Open Recloser Closed Recloser Locked Gas Pressure Low External AC Power Fail Battery Discharged Control Box Door Open External Trip Command(Optional) External Closer Command(Optional) Spare www.jinkwang.co.kr 15 / 111 ISO 9001 certified Recloser controller FTU- R200 Binary Contacts Output : 6 Points Pulse width of output is variable Signal & Contact rating DC24V Aux. Relay Contact Contact Relay : Switch Open, Close, Battery Test, Spare PhotoMOS Relay : Switch Open, Close for 9 Contact Relay Rating Rated Current 16A Rated Voltage/Max. Breaking Voltage AC 250Vac/440Vac Max. Breaking Capacity AC 4,000VA Make Current (Max. 4s at duty cycle 10%) 30A Dielctring Strength 9 Coil-Contacts 5,000Vrms Open Contact Circuit 1,000Vrms Mechnical Life > 30 x 106 operations Operate Time typical 7ms PhotoMOS Relay Rating Rated Load Current 120mA Rated Load Voltage 350Vac I/O isolation Voltage 1,500Vac Current Input : 4 Channel 12.5A Maximum(external CT Ratio is 1,000:1 normally) Burden : below than 1VA 3-Phase Current and Neutral Currents Isolation by auxiliary CT of RTU(Viso) : 2,000 Vrms Surge Withstand Voltage : 6kV Signal : Ia, Ib, Ic, In www.jinkwang.co.kr 16 / 111 ISO 9001 certified Recloser controller FTU- R200 Voltage Input : 6 Channel 4Vrms at rated Phase Voltages Burden : below than 0.01VA Maximum input range : ~200% Isolation by auxiliary PT of RTU(Viso) : 2,000 Vrms Surge Withstand Voltage : 4kV Signal : Va, Vb, Vc, Vr, Vs, Vt Power Supply Input DC 24V(DC20~DC29V) Power Consumption: Max. 15W 2.4. 2.4.1. MEASUREMENT CURRENT RMS(A) & Phase angle(°) Ia, Ib, Ic, In Sequence Component I1, I2, I0 True RMS Ia, Ib, Ic Reading Range 2~12, 500A(External CT Ratio 1,000 : 1) Accuracy 2~600A ±0.5% or ±1A 600~12,000A ±3% 2.4.2. VOLTAGE RMS(kV) & Phase angle(°) Va, Vb, Vc, Vr, Vs, Vt Sequence Component V1s, V2s, V0S, V1L, V2L, V0LS, True RMS Va, Vb, Vc, Vr, Vs, Vt Phase Angle Difference(°) ∠Va - ∠Vr Reading Range 0.1~26kV Accuracy ±0.5% or ±0.1kV www.jinkwang.co.kr 17 / 111 ISO 9001 certified 2.4.3. Recloser controller FTU- R200 POWER Active Power(kW) A-Phase, B-Phase, C-Phase, 3-Phase Total Reactive Power(kVAR) A-Phase, B-Phase, C-Phase, 3-Phase Total, Apparent Power(kVA) A-Phase, B-Phase, C-Phase, 3-Phase Total Reading Range -32767~32767 Accuracy ±1% 2.4.4. POWER FACTOR A-Phase, B-Phase, C-Phase, 3-Phase Total Lead/Lag Display Reading Range 0~1.0 Accuracy ±2% 2.4.5. FREQUENCY Reading Range 45 ~ 55Hz (System Frequency : 50Hz) 55 ~ 65Hz (System Frequency : 60Hz) Accuracy 2.4.6. ±0.02% ENERGY Positive kWh A-Phase, B-Phase, C-Phase, 3-Phase Total Negative kWh A-Phase, B-Phase, C-Phase, 3-Phase Total Capacitive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Capacitive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Inductive Positive kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Inductive Negative kVARh A-Phase, B-Phase, C-Phase, 3-Phase Total, Reading Range 0~65535(Rollover) Accuracy ±2% 2.4.7. HARMONIC Total Harmonic Distortion (%) 3-Phase Current THD (Ia, Ib, Ic, I3ph) Source side 3-Phase Voltage THD (Va, Vb, Vc, V3ph) 2nd~31st Harmonic RMS(A, kV) www.jinkwang.co.kr Ia, Ib, Ic, Va, Vb, Vc 18 / 111 ISO 9001 certified 2.4.8. Recloser controller FTU- R200 DEMAND CURRENT AND POWER Configurable Demand Interval 5, 10, 15min (Default 15min) 2nd~31st Harmonic RMS(A, kV) Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph Daily Max Current and Power are Stored 2.5. COMMUNICATION 2.5.1. PHYSICAL LAYER 2.5.1.1 RS232C 9-Pin Male Connector DCD(1), Rx(2), Tx(3), DTR(4), GND(5) DSR(6), RTS(7), CTS(8), NC(9) Speed(Baud Rate) 1200, 2400, 4800, 9600, 19200 BPS Suppots Modam Control CTS, DCD Signal Timeout Configurable RTS Off-delay Configurable Optical Isolation ESD, Transient Noise Protection 2.5.1.2 RS232C/RS485C RS232C Mode Rx(2), Tx(3), GND(4), GND(5)CTS(8), RS485C Mode DATA-(3) DATA+(7) Speed(Baud Rate) 1200, 2400, 4800, 9600, 19200 BPS Optical Isolation ESD, Transient Noise Protection 2.5.1.3 TCP/IP Ethernet Port 2.5.2. 10/100 Base-T PROTOCOL FOR SCADA 2.5.2.1 DNP3.0 ① Support DNP3.0 Subset Level 3 ② Class of each point is settable(Using DNP3.0 Index Configuration Tool) www.jinkwang.co.kr 19 / 111 ISO 9001 certified Recloser controller FTU- R200 ③ Supports multi-frame transmission(multi-frame interval is configurable) ④ Enable/Disable unsolicited message class ⑤ Supports file transfer function for uploading fault waveform and local event history ⑥ Non-transmitted events are stored on non-volatile memory during communication fail ⑦ Event buffer size : Binary Input(254), Analog Input(127), Counter(19) ⑧ Supports direct operate or select befor operate(SBO) for control output ⑨ Supports report by exception for analog values ⑩ Protocol frame monitor was built in FTU(Using data terminal on maintenance connector) 2.5.2.2 IEC60870-5-101 IEC 60870-5-101 is primarily used with relatively slow transmission media on the asynchronous V.24 interface. The standard promises baud rates of up to 9600 bit/s, with much higher baud rates (<115200 bit/s) actually being used. X.24/X.27 interfaces with baud rates up to 64000 bit/s, also part of the standard's description, could not establish themselves and are rarely used. 2.5.2.3 IEC60870-5-104 IEC 60870-5-104 (also known as IEC 870-5-104) is an international standard, released in 2000 by the IEC (International Electrotechnical Commission). As can be seen from the standard's full designation 'Network access for IEC 60870-5-101 using standard transport profiles', its application layer is based on IEC 60870-5-101. IEC 60870-5-104 enables communication between control station and substation via a standard TCP/IP network. The TCP protocol is used for connectionoriented secure data transmission. 2.6. 2.6.1. RECORDING EVENT RECORDER This function is used to verify shortly the operated history or log of FTU in normal operation and fault situation. Event recording is triggered by power reset, set value change, operation of www.jinkwang.co.kr 20 / 111 ISO 9001 certified Recloser controller FTU- R200 protection functions, system error or self-diagnosis, etc., and events can be stored including event occurred time, measured values of current/voltage and operation description. And, this recording fuction follows the FIFO (First In First Out) rule. Stored events can be uploaded to and listed on FTU PC S/W (FTUMan) through RS232C port on front panel. Event List Sub Items Max. I/O Events Status change of binary Input/Output 1023 Function Events Operated status of Protection Function 1023 System Events Setting change, Reset, Self Dignosis 255 Fault I Events Latest fault current, phase and time 255 PQM Events Operated status of PQM Function 255 Demand I,P,Q Events Each phase daily average load current, active power 1023 and reactive powe with time Max. I,P,Q Events Each phase daily Peak load current, active power and 1023 reactive powe with time 2.6.2. WAVEFORM EVENT RECORDER Fault & PQM waveforms recording function are used to store the measured instantaneous current/voltage values of pre-fault and post-fault at 128 samples per cycle. Record length, trigger source and trigger position of pre/post-fault in recorded data are adjustable. The record types are 128 samples * 20 cycles, 64 samples * 40 cycles, 32 samples * 80 cycles, 16 samples * 160 cycles. According to the purpose, operators can set the fault recording trigger source and trigger position of pre-fault/post-fault. Trigger position means the percentage position in recorded fault data, and the pre-fault data are recorded before this point and rest of the data are recorded as the post-fault after this point. The recorded fault waveforms are also uploaded to FTU PC S/W, and current/voltage waveforms at fault and protection elements operation can be analyzed with fault evaluation. This waveform recording fuction follows the COMTRADE file format rule. www.jinkwang.co.kr 21 / 111 ISO 9001 certified 3. Recloser controller FTU- R200 CONSTRUCT AND EXTERNAL CONNECTION 3.1. APPEARANCE & DIMENSION Front panel of FTU-R200 has an operational LCD display, a RS232C port for setting and maintenance, indicating LED’s, and push buttons. Figure 3-1 Front Panel Drawing of FTU www.jinkwang.co.kr 22 / 111 ISO 9001 certified Recloser controller FTU- R200 The following is the Top-view of FTU-R200 panel. Figure 3-2 Top View of FTU Panel The next drawing is Side-view of FTU-R200 panel, and there are measurement module connector, control module connector, monitoring module connector, power connectors, and RS232 port for SCADA communication on the right side of FTU panel. Figure 3-3 Side View of FTU Panel www.jinkwang.co.kr 23 / 111 ISO 9001 certified 3.2. Recloser controller FTU- R200 CONNECTOR On the right side of FTU-R200 panel, there are RS232 communication port to SCADA, control source power connector, DI (Status Monitoring) connector, DO (Control) connector, AI (Measurement) connectors for Voltage, Current from top to bottom, TCP/IP connector, CAN connector, and TD connector. RS232C port is DB9 male-type connector. Figure 3-4 Pin Connectors on the Right Side of FTU-R200 www.jinkwang.co.kr 24 / 111 ISO 9001 certified 4. Recloser controller FTU- R200 FRONT PANEL OPERATIONS On the front panel, there are LED’s indicating Recloser’s status, function buttons and LED’s, control buttons and LED’s, LCD & Menu buttons and a RS232C port for maintenance. Figure 4-1 Front Panel Sheet of FTU-R200 www.jinkwang.co.kr 25 / 111 ISO 9001 certified 4.1. 4.1.1. Recloser controller FTU- R200 BUTTON & LED DESCRIPTION LCD DISPLAY 4 lines * 20 characters LCD is used and through MENU/UP/DOWN/ENTER buttons, operators can survey all data and corrent set values. 4.1.2. FTU STATUS These LED’s indicate status of FTU-R200. 4.1.3. CPU Run Normal operation of FTU(CPU OK) System Error Self-diagnosis Error & Switch Status Trouble Ext.Power External AC Power is supplied Battery Fail Battery voltage is low (discharged) MENU/UP/DOWN/ENTER BUTTONS These buttons are used to operate FTU in local position. Refer to LCD Manipulation section for detailed methods. 4.1.4. SERIAL PORT Engineering tool on PC is connected to this port for maintenance and upgrade. RS232C port for maintenance is DB9 femail-type connector. RS232C 4.1.5. Rx(2), Tx(3), GND(5), MODE(9) ETHERNET/SCADA/PROTECTION COMMUNICATION LED These LED’s indicate status of FTU-R200. Ethernet Link Ethernet Linking Ethernet Act Ethernet Active SCADA Rx Communication data are received SCADA Tx Transmitting communication data www.jinkwang.co.kr 26 / 111 ISO 9001 certified Recloser controller FTU- R200 SCADA RTS Data transmission request Protection Rx Communication data are received from another FTU by CAN communication. Protection Tx Transmitting communication data to another FTU by CAN communication. 4.1.6. BATTERY TEST & LAMP TEST To test the battery and charger circuit, push ‘BATTERY TEST’ button. When the test result is fail, we will see turn on Battery Fail LED. To test the LED, push ‘LAMP TEST’ button. When test is OK, all of the LEDs are turn on for a while. 4.1.7. RESET BUTTON This button is used for Annunciator LED Reset (LED turn off). Annunciator LED represents all the LED’s related to Protection, Reclosing and Self-diagnosis Error. 4.1.8. FUNCTION LED LIVE LINE LED’s indicate if the lines to source side and load side are activated or deactivated. LED’s are on, when the line voltage goes up the set ‘Voltage ON Level’ and LED’s are off, when the voltage goes down the set ‘Voltage OFF Level’. Under Voltage LED’s indicate if the voltage reaches under the setting value. Sync.Fail LED is on, when the phase angle difference between source-side voltage (Va) and loadside voltage (Vr) is over the setting value. In this case, Close control command should be inhibited. Fault Indicator LED’s on, when a fault related to each faulted phase occurs. For earth fault of non-gronded networks, SEF LED is on. Reclose Ready LED is on, when the reclosing action is normally operated. This represents the normal stand-by status for reclosing action. www.jinkwang.co.kr 27 / 111 ISO 9001 certified Recloser controller FTU- R200 Reclose Progress LED is indicates the status that reclosing action is normally processed according to the preset tripping and reclosing operation sequences. Reclose Lockout LED is on, when the reclosing action is locked out to open according to the operation sequences or the Recloser is opened by the manual control command. 4.1.9. RECLOSE/PROTECTION/GROUND ENABLE BUTTONS AND LEDS Push the enable buttons and makes the respective LED’s on to fulfill the Reclosing and Protection functions. These buttons are toggled between Enable and Disable. RECLOSE ENABLE button enables or disables the Reclosing Function. In disable mode, the Recloser is locked out right the 1st trip. PROTECTION ENABLE button enables or disables Phase Fault Detection and Earth Fault Detection Functions, simultaneously. GROUND ENABLE button enables or disables Earth Fault Detection Function only. 4.1.10. REMOTE/CONTROL LOCK BUTTONS AND LEDS To decide the control position to Remote, push REMOTE button and make the LED on. This button and LED are also toggled between Remote and Local position. But, the manipulation of this button is possible only in the local for operator’s safety. CONTROL LOCK button enables or disables the Recloser switching operation. If Control Lock LED is on, Recloser switch is not operated. 4.1.11. SELECT/OPEN/CLOSE BUTTONS AND LEDS These buttons are used to locally control (OPEN/CLOSE) the Recloser. Before local control command, check first if the control position is LOCAL. SELECT button is a two-phase safety & confirmation check machanism, and this concept is similar to SBO (Select Before Operate) in communication protocol. To manually and locally control the Recloser, SELECT button shuld be www.jinkwang.co.kr 28 / 111 ISO 9001 certified Recloser controller FTU- R200 pushed down to make the corresponding LED on, and this SELECT function can be expanded to the scheme of Multiple Recloser Control in the future. SELECT → CLOSE 9 Push this button to control the Recloser manually to be closed. After closing, normal fault detection functions are re-performed. In case that Cold Load Pickup function is off or the load current is below the Cold Load Pickup Level, normal Phase & Ground Fault Detection is functined. SELECT→OPEN 9 Manual open control opens the Recloser and makes the switch locked out to open. 4.2. LCD MANIPULATION MENU/UP/DOWN/ENTER buttons are used to manipulate the LCD. The following table explains the common roles of 4 buttons. Button MENU Description 9 To toggle between Main Menu Display from Initial Display 9 To come back to Parent Menu from Child Menu 9 Be careful, because all the set value changes are canceled when this button is pushed down during the change of set values ENTER 9 To select and enter into each menu item 9 To enter the changed set value and configuration 9 After entering the changed set value, this button again goes out from each item to menu tree. (Toggle between menu tree and each menu item) 9 After changing the set values, be sure to save the changed values in the Set Value Change Save Menu. UP 9 To move up the cursor in the menu tree 9 To increment the set values 9 The set values are rolled up and UP button at the highest value goes to the lowest value DOWN 9 To move down the cursor in the menu tree 9 To decrement the set values 9 The set values are rolled down and DOWN button at the lowest value goes to the highest value www.jinkwang.co.kr 29 / 111 ISO 9001 certified 4.2.1. Recloser controller FTU- R200 LCD MENU Figure 4-2 LCD Menu Tree Diagram of FTU-R200 4.2.1.1 INITIAL DISPLAY [Initial Display] shows up the reclosing status. <R / C f o r S e q u e n c e : R / C : S t a t u s [ H O ME DAS > 0 [ HO] C L OS E ] Figure 4-3 Initial Display MENU button at [Initial Display] goes to [Main Menu Display]. MENU button toggles between [Initial Display] and [Main Menu Display]. UP or DOWN button at [Initial Display] goes to [Current / Voltage Measurement Display]. UP / DOWN button toggles between [Initial Display] and [Current / Voltage Measurement Display]. www.jinkwang.co.kr 30 / 111 ISO 9001 certified Recloser controller FTU- R200 I a : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0 I b : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0 I c : 0 0 0 0 0 A 0 0 . 0 / 0 0 . 0 I n : 0 0 0 0 0 A <AB C . R S T > Figure 4-4 Current / Voltage Measurement Display Reclosing Sequence 0, 1, 2, 3 and 4 Total Reclosing Shot 3 Times 0[HO], 1~3[SR], 4[LO] 9 HO Home 9 SR Sequence Running 9 LO Lockout R/C Status CLOSE/OPEN/TROUBLE (No Status Input) Current (Ia,Ib,Ic,In) Each Phase Instantaneous Current Value (unit : A) Voltage (ABC.RST) Source Side Voltage (Va,Vb,Vc) / Load Side Voltage (Vr,Vs,Vt), (unit : kV) Diagnosis Fail If diagnosis failure happens, [FAIL] message will appear in the right side of [HOME] or <ABC.RST> will change into <FAIL>. 4.2.1.2 MAIN MENU DISPLAY [ MA I N ME N U 1 . F u n c t i o n ] S e t t i n g 2 . C o n f i g u r a t i o n 3 . Di s p l a y 4 . E v e n t L i s t Figure 4-5 Main Menu Display [Main Menu Display] shows up 4 main menu items. And UP & DOWN buttons move up and down the main menu trees. ‘>’ symbol indicates the cursor position and ENTER button enters into the selected main menu’s sub items. www.jinkwang.co.kr 31 / 111 ISO 9001 certified Recloser controller FTU- R200 Main Menus Sub Items Function Setting Group1, Group2, Group3, Group4, Group Setting Configuration I/O, Communication, Event, Time Display Measurements, Status, Counter Event List I/O events, Function events, System events, Fault I events, Demand I events, Demand P events, Demand Q events, Max. I events, Max. P events, Max. Q events 4.2.1.3 FUNCTION SETTING [ S e t t i n g Me n u ] 1 . Gr o u p 1 2 . Gr o u p 2 3 . Gr o u p 3 4 . Gr o u p 4 5 . Gr o u p S e t t i n g Figure 4-6 Function Setting In Function Setting, there are 4 different setting groups and the different setting values can be stored individually in 4 different setting groups. After finishing the set value change, when MENU button is pushed to return to [Main Menu Display], [Set Value Change Save Display] shows up to determine Yes or No. If selecting yes and pushing ENTER button, the changed set values are all saved. However, if selecting No and ENTER button or MENU button again, the changed set values are not saved and the existing set values are still applied. 9 CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set values are neither saved nor applied. S a v e C h a n g e d Y e s / S e t ? No Figure 4-7 Set Value Change Save Display www.jinkwang.co.kr 32 / 111 ISO 9001 certified Recloser controller FTU- R200 S e t t i n g S a v i n g ! Figure 4-8 ENTER to Yes [ MA I N ME N U >1 . F u n c t i o n ] S e t t i n g 2 . C o n f i g u r a t i o n 3 . Di s p l a y Figure 4-9 ENTER to No 4.2.1.4 CONFIGURATION [ C ONF I G ME N U ] 1 . I / O 2 . C o mmu n i c a t i o n 3 . E v e n t 4 . T i me Figure 4-10 Configuration Configuration menu has the setting items for communication, I/O, and system configuration. Setting items are I/O, Communication, Event and Time. After finishing the set value change, when MENU button is pushed to return to [Main Menu Display], [Set Value Change Save Display] shows up to determine Yes or No. If selecting yes and pushing ENTER button, the changed set values are all saved. However, if selecting No and ENTER button or MENU button again, the changed set values are not saved and the existing set values are still applied. 9 CAUTION: Be careful not to push down MENU buttons repeatedly! Then, the newly changed set values are neither saved nor applied. www.jinkwang.co.kr 33 / 111 ISO 9001 certified Recloser controller FTU- R200 4.2.1.5 DISPLAY [ DI S P L AY ME N U ] 1 . Me a s u r e m e n t s 2 . S t a t u s 3 . C o u n t e r Figure 4-11 Display In Display menu, measurement values, monitored status, and counter values are displayed. 4.2.1.6 EVENT LIST [ E V E NT 1 . I / O L I S T ] E v e n t s 2 . F u n c t i o n e v e n t s 3 . S y s t e m e v e n t s 4 . F a u l t s e v e n t s 5 . D e ma n d I e v e n t s 6 . D e ma n d P e v e n t s 7 . D e ma n d Q e v e n t s 8 . Ma x . I e v e n t s 9 . Ma x . P e v e n t s 10 . M a x . Q e v e n t s Figure 4-12 Event List In Event List menu, all types of events are displayed with occurred time and event description. Using UP & DOWN buttons, event list can be scrolled up and down in the LCD display. Event List Sub Items Max. I/O Events Status change of binary Input/Output 1023 Function Events Operated status of Protection Function 1023 System Events Setting change, Reset, Self Dignosis 255 Fault I Events Latest fault current, phase and time 255 Demand I,P,Q Events Each phase daily average load current, active power 1023 and reactive powe with time Max. I,P,Q Events Each phase daily Peak load current, active power 1023 and reactive powe with time www.jinkwang.co.kr 34 / 111 ISO 9001 certified 5. Recloser controller FTU- R200 PROTECTION FUNCTIONS 5.1. FAULT DETECTION FTU detects the Phase & Earth Fault and trip the breaker. The fastest operation time is within 45msec including auto-recloser operating time. There are 58 trip curves, which can be selected for fast and delayed operation respectively. The Curve can be edited by using several parameters, i.e. time multiplier, time adder and minimum response time. And high current trip element can be used for instantaneous trip. It is definite time characteristics. During cold-load condition, pickup multiplied by cold-load multiplier. During the cold-load condition, time-delayed curve is applied instead of fast curve. This function can be enabled or disabled by cold-load multiplier. Earth fault detection function can be enabled or disabled by ‘Ground Protection Enable’. Phase Fault Range Earth Fault Def. Range Step Def. Unit Pickup Current 10~900 400 5~900 60 Inrush Block NO/YES YES NO/YES YES 1~58 1-A 1~58 2-B 1 Time Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec RDMT/RIDMT RDMT RDMT/RIDMT RDMT 0.00~100.00 0.00 0.00~100.00 0.00 1 A Fast Operation Time Curve Type Min. Response Time Reset Type Reset Definite Time www.jinkwang.co.kr RDMT(Definite Time) RIDMT(Inverse Time) 0.01 sec 35 / 111 ISO 9001 certified Recloser controller FTU- R200 Phase Fault Earth Fault Step Unit Range Def. Range Def. 1~58 20-1 1~58 21-2 1 Time Multiplier 0.05~2.00 1.00 0.05~2.00 1.00 0.01 sec Time Adder 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec Min. Response 0.00~1.00 0.00 0.00~1.00 0.00 0.01 sec RDMT/RIDMT RDMT RDMT/RIDMT RDMT Delayed Operation Time Curve Type Time Reset Type RDMT(Definite Time) RIDMT(Inverse Time) Reset Definite 0.00~100.00 0.00 0.00~100.00 0.00 0.01 sec Time 5.1.1 Definite Time Protection Definite Time is an alternative to Inverse Time Protection. It works by tripping the recloser at a fixed time after pick-up. Range Def. Step Unit OFF/ON OFF Pickup Current 50~10000 1000 1 A Detection Time 0.00~1.00 0.00 0.01 sec OFF/ON OFF Pickup Current 50~10000 1000 1 A Detection Time 0.00~1.00 0.00 0.01 sec Comment Phase Detection Active Earth Detection Active 5.1.2 High Current Trip (HCT) Very high valued current can cause serious damage to the Recloser and the resultant fault spread-out, therefore HCT element should operate faster than Instantaneous or Time-Delayed TC curve’s operation time and its priority must be higher than the normal auto-reclosing sequence. www.jinkwang.co.kr 36 / 111 ISO 9001 certified Recloser controller FTU- R200 HCT can be configured up to 4 times for phase fault and earth fault, respectively. HCT Count setting value ‘0’ means HCT element disabled. Range Def. Step Unit 0~4 0 1 Pickup Current 50~10000 2000 1 A Detection Time 0.00~1.00 0.00 0.01 sec 0~4 0 1 Pickup Current 50~10000 2000 1 A Detection Time 0.00~1.00 0.00 0.01 sec Comment Phase Detection Operation Count ‘0' means disable. Earth Detection Operation Count 5.1.3 ‘0' means disable. Single Shot Operation In Single Shot Operation is used to provide an appropriate protection curve when non-reclosing operation is required, for example, when closing onto a fault. In Single Shot Operation the controller goes directly to lockout after one trip and will not autoreclosing. Single Shot Time 5.1.4 Range Def. Step Unit 0~180 10 1 sec Comment TC Curve FTU-R200 has 54 types of built-in TC curves including ANSI, IEC Standard curves. And customer can define additional 4 curves as his own curves by using PC Software. Basically, built-in curves have inverse time characteristrics, but can be easily adjusted by three parameters such as multiplier, time adder and minimum response time. In engineering step, the selection and adjustments of TC curves shall be done for the protection coordination with other protection devices in the feeder. The follwing parameters are related to change and editing of TC curve’s characteristics. 9 Time Multiplier www.jinkwang.co.kr 37 / 111 ISO 9001 certified Recloser controller FTU- R200 9 Time Adder 9 Minimum Response Time Time Multiplier is multiplied to the operating time of basic curve (TDM=1.0), then Time Adder is added to the resulting operating time of the curve adjusted by multiplier. Minimum Response Time defines the fastest operating time of the curve. The following tables describe the built-in TC Curve Type and the corresponding numbers in the setting. TC Curve graphs are shown in the appendix. Setting No. 1 2 3 4 5 6 7 8 9 10 Curve A B C D E EI KP L M N Setting No. 11 12 13 14 15 16 17 18 19 20 Curve NI P R T V VI W Y Z 1 Setting No. 21 22 23 24 25 26 27 28 29 30 Curve 2 3 4 5 6 7 8 8* 9 11 Setting No. 31 32 33 34 35 36 37 38 39 40 Curve 13 14 15 16 18 N1 N2 N3 N4 F Setting No. 41 42 43 44 45 46 47 48 49 50 Curve G H J LI 8+ 17 KG A* SI IM Setting No. 51 52 53 54 55 56 57 58 Curve IV IE U8 U2 C1 C2 C3 C4 Curve Type Curve Name Recloser Curves A,A*,B,C,D,E,F,G,H,J,KP,KG,L,M,N,P,R,T,V,W,Y,Z, 1,2,3,4,5,6,7,8,8*,8+,9,11,13,14,15,16,17,18 IEC Standard Curve Standard Inverse(NI),Very Inverse(VI),Extremely Inverse(EI) Long-time Inverse(LI),Short-time Inverse(SI) ANSI/IEEE Standard Moderately Inverse(IM),Very Inverse(IV),Extremely Inverse(IE), Curve Long-time Inverse(U8),Short-time Inverse(U2) KEPCO Standard Curve N1,N2,N3,N4 User Customized Curve C1,C2,C3,C4 www.jinkwang.co.kr 38 / 111 ISO 9001 certified 9 Recloser controller FTU- R200 IEC, ANSI/IEEE, US STANDARD TC CURVE EQUATION T = TDM • {α / (Mβ - 1) +γ} TRESET = TDM • {τ / (Mβ - 1)} T : Operate Time, TDM : Multiplier Setting, TRESET : Reset Time Curve Type Standard Inverse(NI) Standard β γ τ 0.14 0.02 - - Very Inverse(VI) 13.5 1 - - Extremely Inverse(EI) 80.0 2 - - Short-time Inverse(SI) 0.05 0.04 - - Long-time Inverse(LI) 120 1 - - 19.61 2 0.491 21.6 Extremely Inverse(IE) 28.2 2 0.1215 29.1 Moderately Inverse(IM) 0.0515 0.02 0.114 4.85 Very Inverse(IV) IEC α IEEE Short-time Inverse(U2) CO2 0.2394 0.02 0.01694 2.261 Long-time Inverse(U8) CO8 5.95 2 0.18 5.95 5.1.5 EXAMPLE OF TC CURVE EDITING 3-parameters are applied in the follwing order. The values in the parenthesis are examples. 9 Time Multiplier : 1.5 9 Time Adder : 0.03 9 Minimum Response Time : 0.1 In the next figure, for example, the curve A is the basic curve. Assume the operating time of the basic curve (A) at 16 times pickup current is 0.04 sec. When applying Time Multiplier, curve ‘A’ changes its shape, that is, the curve becomes less steep in time axis and operation time becomes longer by a multiplier at the same current value like ‘B’ in the figure. The operating time at 16 times pickup becomes 0.06 sec. Then Time Adder shall be applied. The operating time of the www.jinkwang.co.kr 39 / 111 ISO 9001 certified Recloser controller FTU- R200 resulting curve ‘C’ is 0.09sec. Finally Minimum Response Time cuts the curve part, which is shorter than this time. Then the actual operating time of the example at 16 times becomes 0.1sec. Figure 5-1 TC Curve Editing Example 1 There are two additional definite time over-current elements in the controller. The next figure shows 3-stage over-current protection characteristics. The third stage is prepared for instantaneous protection. Therefore the harmonic restraint is not applied to third stage elements, but the second stage definite time over-current element. Figure 5-2 TC Curve Editing Example 2 www.jinkwang.co.kr 40 / 111 ISO 9001 certified 5.1.6 Recloser controller FTU- R200 Auto Reclosing Sequence The FTU-R200 supports 3-shot reclosing with sequence coordination. For Permanent fault, under the condition of reclosing enabled, no other restraints such as coldload, inrush and no High Current Trip, recloser will be locked out to open the Reclosing Count repeating trip and reclose according to the preset settings. Range Def. Step Unit Operation Count 1~4 4 1 Instantaneous Count 0~4 2 1 Operation Count 1~4 4 1 Instantaneous Count 0~4 2 1 Reclose Interval 1st 0.5~180.0 0.6 0.1 sec Reclose Interval 2nd 1~180 2 1 sec Reclose Interval 3rd 1~180 15 1 sec Reset Time 3~180 30 1 sec 1~4 4 1 Reclose Interval 1st 0.5~180.0 0.6 0.1 sec Reclose Interval 2nd 1~180 2 1 sec Reclose Interval 3rd 1~180 15 1 sec Reset Time 3~180 30 1 sec Comment Phase Earth Phase/ Earth Reclosing SEF Reclosing Operation Count For example in the below figure, the reclosing sequence is organized in 2F2D, which means the Recloser protection function operates as Instantaneous(Fast) element during first 2 reclosing shots and operates as Time-Delayed element during last 2 reclosing shots. This composition also can be configured. www.jinkwang.co.kr 41 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 5-3 Permanent Fault: 3 shot Reclosing & 2F2D For temporary fault, if the fault is removed before the preset Reclosing Count and no fault is detected during the preset Reset Time, then the reclosing sequence is initialized to normal operation standby mode. When a fault is detected again during the Reset Time, the Recloser will be locked out after the remaining reclosing counts excluding the previously operated reclosing counts. Figure 5-4 Temporary Faults: Fault Removal during 1st Reclosing Interval www.jinkwang.co.kr 42 / 111 ISO 9001 certified 5.1.7 Recloser controller FTU- R200 Sequence Coodination In case that there are over 2 Reclosers which operate in serial connections, Sequence Coordination function prevents unnecessary trip of source-side Recloser by instantaneous element due to load-side fault. When this function is set to on and the fault is restored to normal state by load-side Recloser during source-side Recloser’s time-delayed operation, source-side Recloser only increments the reclosing counts without tripping. However, source-side Recloser performs tripping at the last reclosing count. If the Reclosing function is disabled, Sequence Coordination function is no longer carried out. Seq. Coordination Active Range Def. OFF/ON OFF Step Unit Comment For Sequence Coordination, the following setting items should be issued and checked precisely between serially connected Reclosers. 9 Identical Protection Characteristics such as TC Curves, Total Operation Count, Instantaneous Operation Count 9 Identical Reclosing Interval(Dead Time) 9 Source-side TC Curve Time Delay Over 100msec than Load-side 9 Source-side Reset Time longer than Load-side longest Reclosing Interval (to Prevent Source-side Recloser reset during Load-side Reclosing action) Figure 5-5 Operation of Sequence Coordination www.jinkwang.co.kr 43 / 111 ISO 9001 certified 5.2 Recloser controller FTU- R200 Cold Load Pickup Cold Load Pickup is the phenomenon that takes place when a distribution circuit is re-energized following an extended outage of that circuit. Cold load pickup is a composite of two conditions: inrush and loss of load diversity. The magnitude of cold load pickup current is a combination of non-diverse cyclic load current, continuously operating load current, transformer magnetizing current, capacitor inrush current, etc. The combination can result in current levels that are significantly higher than normal peak load levels. Cold load pickup current can be high enough to cause instantaneous overcurrent and/or time overcurrent relays to operate. Cold load pickup is primarily an overcurrent condition. If degraded voltage is also a concern, then the application of voltage sensitive relays should also be considered. Figure 5-6 Cold Load Pickup Current Shape In Cold Load Pickup mode, without changing operational characteristics, pickup level is changed by the times of Cold Load Multiplier (0~10) and the characteristics of time-delayed element operate even if the setting is in the Instantaneous element. If the transient current goes down and retrains below the pickup level within Cold Load Duration, then the normal sequence mode is restored after Cold Load Restore Time. The Cold Load Restore Time is fixed value of 30msec. These setting exist for both phase fault and earth fault separately, and the value ‘0’ of Cold Load Multiplier means Cold Load Pickup Function disabled. Normaly Reclosing Sequence mode is applied. www.jinkwang.co.kr 44 / 111 ISO 9001 certified Recloser controller FTU- R200 Range Def. Step 0~10 2 1 0.00~60.00 3.00 0.01 0~10 2 1 0.00~60.00 3.00 0.01 Unit Comment Phase Detection Pickup Multiplier Duration Time ‘0' means disable. sec Earth Detection Pickup Multiplier Duration Time 5.3 ‘0' means disable. sec SENSITIVE EARTH FAULT (SEF) DETECTION On the non-grounded network, it is hard to detect fault current because ground current of nongrounded network is much low. Therefore, FTU-R200 is designed to measure zero-sequence values from either external core Balanced Current Transformer (or ZCT) or Residual Connection of 3 Phase Current Transformers to detect earth fault in the non-grounded network. This function is generally called SEF detection. In case of earth fault in the non-grounded network, since very small fault current due to line capacitance component flows into the fault point from both sides, SEF detection also considers the fault direction even in the radial network. Maximum Torque Angle is for setting the phase difference between zero-sequence voltage and zero-sequence current, and the protection zone is between -90° and +90° on the basis of Maximum Torque Angle. And it can be used for alarm or Trip. Figure 5-7 Phase Diagram of SEF www.jinkwang.co.kr 45 / 111 ISO 9001 certified Recloser controller FTU- R200 Range Def. Step Unit Pickup Current(3I0) 2~20 5 1 A Pickup Voltage(-3V0) 10~80 30 1 % Comment Rated Phase Voltage Max. Torque Angle 0~345 90 15 Degree Detection Time 0.1~30.0 1.0 0.1 sec Inrush Block NO/YES YES OFF/ALARM/TRIP OFF Function In Use 5.4 Leading DIRECTIONAL BLOCKING Directional Blocking is a protection feature that restricts tripping on faults to a designated side of the recloser. It prevents nuisance tripping if particular network conditions are causing ‘False’ earth faults. In radial systems Directional Blocking prevents nuisance tripping by blocking faults in the reverse direction and only responding to faults in the foward direction. Protect for faults in the forward and reverse direction. A forward fault may use a different timecurrent curve and setting to a reverse fault (i.e. these are individually selectable). Both the forward protection and reverse protection are operating at the same time. This is an additional protection feature. Range Def. Step Unit Trip Direction OFF/FWD/REV/ALL FWD 3V1 Threshold 0~100 20 1 % 3I1 Threshold 0~100 20 1 % 3I1 Max. Torque Angle 0~355 60 5 Degree OFF/FWD/REV/ALL FWD -3V0 Threshold 0~100 20 1 % 3I0 Threshold 0~100 20 1 % 3I0 Max. Torque Angle 0~355 60 5 Degree Comment Phase Detection Earth Detection Trip Direction www.jinkwang.co.kr 46 / 111 ISO 9001 certified 5.5 Recloser controller FTU- R200 INRUSH RESTRAINTS Inrush Restraint works by raising the phase and earth currents for a short period of time to allow the inrush current to subside. Inrush current is an over-current higher than pickup current level, which is mainly caused by transformer’s excitation current at closing action. To distinguish inrush current from load current, 2nd harmonics percentage is adopted as a criterion. When, in the setting, ‘Fault Detection-Inrush Block’ is set to ‘Yes’ and ‘Fault Detection-Inrush Detection-Function In Use’ is set to ‘ON’, inrush current over pickup level is considered as normal load current and reclosing sequence is not processed. This Function can be used to detect magnetizing inrush condition by comparing 2nd harmonic component to fundamental frequency component of current. Range Def. Step Unit 5~50 20 1 % Detection Time 0.02~1.00 0.02 0.01 sec Function In Use OFF/ON ON 2nd Harmonic 5.6 Comment OPEN LINE DETECTION (LOSS OF PHASE) Open Line is detected by Under Voltage characteristics at unbalanced condition. When the voltage on one or two phases drops below the ‘Volt OFF Level’ setting, the ‘Delay Time’ starts running. If the voltage on those phases stays below ‘Volt OFF Level’ setting until the ‘Delay Time’ timer expires, the Loss of Phase will be detected. If the voltage on detected phase rises to the ‘Vol ON Level’ setting, the Loss of Phase is released immediately. Range Def. Step Unit Volt ON Level 50~90 80 5 % Volt OFF Level 35~75 50 5 % Delay Time 0.1~30.0 0.4 0.1 sec Function In Use OFF/ON ON www.jinkwang.co.kr Comment 47 / 111 ISO 9001 certified 5.7 Recloser controller FTU- R200 PHASE SYNC. CHECK Range Def. Step Unit 5~60 30 1 Degree Dalay Time 0.1~30.0 0.1 0.1 sec Function In Use OFF/ON ON Phase Difference 5.8 Comment UNDER VOLTAGE PROTECTION As the supplied voltage to load lowers down, there occur the weakness of illumination intensity and shortening of life span for lighting load, and the damage to motors because of the overcurrent flow. To cope with this situation of damages to equipment, under-voltage protection (UV) is used. UV of FTU supports the delay time element. Furthermore, UV can be used to generate only alarm signal to operator instead of trip signal to Recloser. Figure 5-8 Functional Diagram for Under Voltage Protection Range Def. Step Unit Pickup Level 0.30~0.95 0.80 0.01 PU Delay Time 0.0~180.0 1.0 0.1 sec OFF/ARAMP/TRIP OFF Function In Use www.jinkwang.co.kr Comment 48 / 111 ISO 9001 certified 5.9 Recloser controller FTU- R200 OVER VOLTAGE PROTECTION On the other hand, as the supplied voltage goes up behind the regular load voltage, there occur some problems of equipment deterioration, insulation breakdown, equipment life span shortening, etc. Over Voltage Protection (OV) manages this situation. OV of FTU supports the delay time element. OV also can be used to generate only alarm signal to operator instead of trip signal to Recloser. Figure 5-9 Functional Diagram for Over Voltage Function Range Def. Step Unit Pickup Level 1.05~1.50 1.20 0.01 PU Delay Time 0.0~180.0 1.0 0.1 sec OFF/ARAMP/TRIP OFF Function In Use Comment 5.10 UNDER FREQUENCY PROTECTION Under Frequency protection (UF) element is used into expenditure that detect under frequency and separated load or generator. Under Frequency demands for power increase or occurs in control failure of generator. Under Frequency protection element acts in case of voltage more than ‘Voltage OFF Level’ is approved to Voltage A-Phase. UF of FTU supports the delay time element. Furthermore, UV can be used to generate only alarm signal to operator instead of trip signal to Recloser. www.jinkwang.co.kr 49 / 111 ISO 9001 certified Recloser controller FTU- R200 Range Def. Step Unit Pickup 47.00~59.98 49.80 0.01 Hz Dalay Time 0.03~10.00 0.10 0.01 sec OFF/ARAMP/TRIP OFF Function In Use Comment 5.11 MULTIPLE PROTECTION GROUPS The FTU-R200 supports up to 4 Protection Groups, each of which can be confiqured with completely separate protection characteristics with different inverse time curves and setting currents. The number of protection group avaliable to the operator can be configured. And FTU-R200 support Automatic Protection Group Selection. Automatic Protection Group Selection is used to change the protection group depending on the direction of power flow. This allows the Recloser to be correctly graded with devices downstream regardless of the power flow direction. Default Group ADGS(Automatic Default Group Selection) Function Reverse Group www.jinkwang.co.kr Range Def. Step 1~4 1 1 OFF/ON OFF 1~4 1 1 50 / 111 Unit ISO 9001 certified Recloser controller FTU- R200 6 CONFIGURATION SETTING 6.1 I/O CONFIGURATION 6.1.1 AC RATING Range Def. Step Unit Line Configuration Y-G/DELTA Y-G Systme Frequency 50/60 Rated Voltage (L-L) Reference Voltage (L-N) 50 40 Hz 1000~30000 22900 10 V Phase to Phase 1000~30000 13200 10 V Phase to Earth Reference Phase A/B/C A CB Operating Time 0~35 1 1 ms 1~5000 1000 1 FWD/REV FWD 1.0~5000.0 133.3 NCT Direction FWD/REV FWD Phase Rotation A-B-C/A-C-B A-B-C Sample Record Frequency 16/32/64/128 128 CT Ratio CT Direction NCT Ratio 9 Comment 0.1 SWITCH INSTALLATION The FTU-R200 provides a function to set ‘Reference Phase’ and the ‘CT Direction’ according to the switch installation position and the current flowing direction. Figure 6-1 shows the general and ‘assumed-default’ case of switch installation, in which the distribution lines with current A, B, C are connected to the phase A, B, C terminals of the switch, and the current is flowing A/B/C to R/S/T of the switch. In this case, the ‘Referece Phase’ setting value should ‘A’, which means that the phase of current flowing into the phase A terminal of the switch is ‘A’, In addition, the ‘CT Direction’ setting value should be ‘Foward’, which means that the current is flowing in the direction from the phase A/B/C terminals to the R/S/T terminals of the switch. www.jinkwang.co.kr 51 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 6-1 Switch installation position and the current flowing direction – Case 1 Figure 6-2 shows another case of switch installation, in which the distriburion lines with current A, B, C are connected to the phase A, B, C terminals of the switch, and the current is flowing from R/S/T to A/B/C of the switch. In this case, the ‘Referece Phase’ setting value should ‘A’, which means that the phase of current flowing into the phase A terminal of the switch is ‘A’, In addition, the ‘CT Direction’ setting value should be ‘Reverse’, which means that the current is flowing in the direction from the phase R/S/T terminals to the A/B/C terminals of the switch. Figure 6-2 Switch installation position and the current flowing direction – Case 2 www.jinkwang.co.kr 52 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 6-3 shows another case of switch installation, in which the distriburion lines with current A, B, C are connected to the phase C, B, A terminals of the switch, and the current is flowing from R/S/T to A/B/C of the switch. In this case, the ‘Referece Phase’ setting value should ‘C’, which means that the phase of current flowing into the phase A terminal of the switch is ‘C’, In addition, the ‘CT Direction’ setting value should be ‘Reverse’, which means that the current is flowing in the direction from the phase R/S/T terminals to the A/B/C terminals of the switch. Figure 6-3 Switch installation position and the current flowing direction – Case 3 Figure 6-4 shows another case of switch installation, in which the distriburion lines with current A, B, C are connected to the phase C, B, A terminals of the switch, and the current is flowing from A/B/C to R/S/T of the switch. In this case, the ‘Referece Phase’ setting value should ‘C’, which means that the phase of current flowing into the phase A terminal of the switch is ‘C’, In addition, the ‘CT Direction’ setting value should be ‘Forward’, which means that the current is flowing in the direction from the phase A/B/C terminals to the R/S/T terminals of the switch. www.jinkwang.co.kr 53 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 66-4 Switch installation position and the current flowing direction – Case 4 6.1.2 DEMAND SETTING The FTU calculates and stores average of currents and active, reactive powers during the demand interval, which is configurable as 5, 10 or 15 minutes. The buffer has 1023 demands. Also FTU stores daily peak demand up to 1023. Block Interval Roll Interval 6.1.3 Range Def. 15/30/60 15 1/5/15/30/60 15 Step Unit Comment WAVE TRIGGER Range Def. 16/32/64/128 128 Pre-1st Cycle 1~5 Post-2nd Cycle Pre-2nd Trigger Cycle Sample Record Frequency www.jinkwang.co.kr Step Unit 2 1 Cycle 1~5 2 1 Cycle 1~10 10 1 Cycle Comment 54 / 111 ISO 9001 certified 6.1.4 Recloser controller FTU- R200 CLOSE INTERLOCK Range Def. Live Load NO/YES YES Sync. Fail NO/YES YES Range Def. MANUAL/AUTO MANUAL 6.1.5 Unit Comment Step Unit Comment FI RESET SELECT FI Reset 6.1.6 Step VOLTAGE DISPLAY The controller supports two voltage display of LCD. Voltage Display Range Def. L-N/L-L L-N Step Unit Comment L-N : Phase to Earth L-L : Phase to Phase 6.2 6.2.1 POWER QUALITY MEASUREMENT FUNCION VOLTAGE & CURRENT UNBALANCE Voltage unbalance (or imbalance) is a condition in which the maximum deviation from the average of the three-phase voltages or currents, divided by the average of the three-phase voltage or currents, expressed in percentage. Voltage unbalance can be the result of blown fuses in one phase of a three-phase capacitor bank. Severe voltage unbalance greater than 5% can cause damage to sensitive equipments. www.jinkwang.co.kr 55 / 111 ISO 9001 certified Recloser controller FTU- R200 Range Def. Step Unit Detection Level 0~100 30 1 % Detection Time 0.1~60.0 1.0 0.1 sec Detection Level 0~100 30 1 % Detection Time 0.1~60.0 1.0 0.1 sec Comment Voltage Unbalance Current Unbalance 6.2.2 SHORT-DURATION VOLTAGE VARIATION There are three types of short-duration voltage variations, namely, instantaneous, momentary and temporary, depending on its duration. Short-duration voltage variations are caused by fault conditions, energization of large loads, which require high starting currents or loose connections in power wiring. Depending on the fault location and the system conditions, the fault can generate sags, swells or interruptions. The fault condition can be close to or remote from the point of interest. During the actual fault condition, the effect of the voltage is of short-duration variation until protective devices operate to clear the fault. 6.2.2.1 SAG A sag (also known as dip) is a reduction to between 0.5 and 0.99 pu in RMS voltage or current at the power frequency for a short period of time from 0.5 to 10 cycle. A 10% sag is considered an event during which the RMS voltage decreased by 10% to 0.9 pu. Voltage sags are widely recorgnized as among the most common and inportant aspects of power quality problems affecting industrial and commercial customers. They are particularly troublesome. Since they occur randomly and are difficult to predict. Volatge sags are normally associated with system faults on the distribution system, sudden increase in system loads, lightning strikes or starting of large load like induction motors. It is not possible to eliminate faults on a system. One of the most common causes of faults occuring on high-volatage transmission systems is a lightning strike. When there is a fault caused by a lightning strike, the voltage can sag to 50% of the standard range and can last from four to seven cycles. Most loads will be tripped off when encounter this type of voltage level. Possible effect of voltage www.jinkwang.co.kr 56 / 111 ISO 9001 certified Recloser controller FTU- R200 sags would be system shutdown or reduce effciency and life span of electrical equipment, particularly motors. Equipment sensitivity to voltage sag occurs randomly and has become the most serious power quality problem affecting many industries and commercial customers presently. An industrial monitoring program determined an 87% voltage disturbances could be associate to voltage sags. Most of the fault on the utility transmission and distribution system are single line-to-ground faults (SLGF). Range Def. Step Unit Detection Level 0.50~0.99 0.90 0.01 PU Detection Time 0.5~10.0 2.0 0.5 Cycle Comment 6.2.2.2 SWELL A swell (also known as momentary overvoltage) is an increase in RMS voltage or current at the power frequency to between 1.01 and 1.5 Pu for duration from 0.5 to 10 cycles. Swells are commonly caused by system conditions, switching off a large load or energizing a large capacitor bank. A swell can occur during a single line-to-ground fault (SLGF) with a temporary voltage rise on the unfaulted phases. They are not as common as voltage sags and are characterized also by both the magnitude and duration. During a fault condition, the severity of a voltage swell is very much dependent on the system inpedance, location of the fault and grounding. The effect of this type of disturbance would be hardware failure in the equipment due to overheating. Range Def. Step Unit Detection Level 1.01~1.50 1.20 0.01 PU Detection Time 0.5~10.0 2.0 0.5 Cycle Comment 6.2.2.3 INTERRUPTION An interruption occurs when there is a reduction of the supply voltage or load current to between 0.1 and 0.49 pu for duration from 0.5 to 10 cycle. Possible causes would be circuit breakers responding to overload, lightning and faults. Interruptions are the result of equipment failures, power system faults and control malfunctions. They are characterized by their duration as the voltage magnitude is always less than 10% of the nominal. The duration of an interruption can www.jinkwang.co.kr 57 / 111 ISO 9001 certified Recloser controller FTU- R200 be irregular when due to equipment malfuctions or loose connections. The duration of an interruption due to a fault on the utility system is determined by the utility protective devices operating time. Range Def. Step Unit Detection Level 0.10~0.49 0.10 0.01 PU Detection Time 0.5~10.0 2.0 0.5 Cycle 6.2.3 Comment VOLTAGE & CURRENT THD ALARM The Total Harmonic Distortion, or THD, of a sigmal is a measurement of the harmonic distortion present and is defined as the ratio of the sum of the powers of all harmonic components to the power of the fundamental frequency. Range Def. Step Unit Alarm Level 0.5~100.0 0.0 0.1 % Detection Time 0.2~60.0 0.4 0.2 sec Alarm Level 0.5~100.0 0.0 0.1 % Detection Time 0.2~60.0 0.4 0.2 sec Comment Voltage Current 6.3 COMMUNICATION 6.3.1 PORT PARAMETERS 6.3.1.1 SERIAL PORT Speed Slave Adderss Protocol Port www.jinkwang.co.kr Range Def. 1200/2400/4800/9600/19200 1200 1~65534 1 DNP/IEC101/IEC104 DNP RS232C/RS485 RS232C Step Unit 1 58 / 111 ISO 9001 certified Recloser controller FTU- R200 6.3.1.2 DIAL UP Range Def. Dial-up Mode DISABLE/ENABLE DISABLE Phone Number 20 Digit Auto Hang-up Time Step Unit 1 0~255 5 1 sec Range Def. Step Unit IP Address - 0.0.0.0 Subnet Mask - 255.255.255.0 Gateway - 0.0.0.0 DNP Port 0~65535 20000 1 IEC Port 0~65535 2404 1 Range Def. Step Unit 2-WIRE/4-WIRE 4-WIRE RTS Off Delay 10~500 50 10 ms CTS Timeout 1~255 2 1 sec DCD Timeout 0.1~30.0 5.0 0.1 sec 6.3.1.3 TCP/IP PORT 6.3.1.4 MODEM CONTROL Line www.jinkwang.co.kr 59 / 111 ISO 9001 certified 6.3.2 Recloser controller FTU- R200 DNP3.0 PARAMETERS Range Def. Step 0~2 0 1 D/L Timeout 1~255 30 1 D/L Confirm NO/YES/SOMETIMES SOMETIMES 0~2 1 1 1~255 40 1 sec NO/YES NO Unsolicited Class 1 Delay Time 0~60 5 1 sec Unsolicited Class 2 Delay Time 0~60 5 1 sec Unsolicited Class 3 Delay Time 0~60 5 1 sec Arm Timeout 1~255 15 1 sec Unsolicited Address 0~65534 65534 1 Multi Frame Interval 10~500 100 10 Unsolicited Class 1 DISABLE/ENABLE DISABLE Unsolicited Class 2 DISABLE/ENABLE DISABLE Unsolicited Class 3 DISABLE/ENABLE DISABLE D/L Retries A/L Retries A/L Timeout Initial Unsolicited MSG www.jinkwang.co.kr Unit sec ms 60 / 111 ISO 9001 certified 6.3.3 Recloser controller FTU- R200 IEC PARAMETERS Range Def. Step Unit Cyclic Period 0~60 0 1 sec Arm Timeout 1~255 15 1 sec Single Point Class CLASS1/CLASS2 CLASS1 Double Point Class CLASS1/CLASS2 CLASS1 Measured Point Class CLASS1/CLASS2 CLASS2 Link Address Size 0~2 2 1 Common Address Size 1~2 2 1 Object Address Size 1~3 2 1 COT Address Size 1~2 1 1 NONE/CP24/CP56 CP56 NO/YES YES t0 Off Line Poll Period 1~255 30 1 sec t1 Ack Period 1~255 15 1 sec t2 SFrame Period 1~255 10 1 sec t3 Test Period 1~255 20 1 sec IEC101 PARAMETERS Time Marker Single NACK Control IEC104 PARAMETERS www.jinkwang.co.kr 61 / 111 ISO 9001 certified 7 STATUS MONITORING & CONTROL 7.1 SWITCH CONTROL Recloser controller FTU- R200 Recloser can be controlled from remote or local operator place. Operator place can be changed only at local front panel. ‘REMOTE CONTROL’ push button is to select the operator place. Operator place is toggled between local and remote by pushing button. LED is lit if remote position is selected. FTU-R200 begins with remote position at power-up. Control is allowed only at the position selected. Local switch control requires two-step operation. It’s for security of operation. ‘SELECT’ button should be pushed before ‘CLOSE’ or ‘OPEN’. SELECT LED is lit if SELECT operation is valid. SELECT can be canceled by pushing SELECT button again or automatically after SBO timeout without operation. CLOSE or OPEN operation is valid while this LED is lit. Pushing CLOSE or OPEN button outputs switch control signal with fixed time pulse which is configurable. Switch status change input which is auxiliary contacts of switch stops continuing to output pulse. There are some interlock conditions to inhibit FTU from outputting pulse signal. Gas low, Switch handle lock, same status of switch auxiliary contacts ‘a’, ‘b’ are those. Close or open pulse width shall be set longer than switch operating time. Remote switch control is possible by using SCADA protocol DNP3.0 or IEC60870-5-101, IEC60870-5-104 FTU-R200 supports SBO (Select Before Operate) or Direct operate. If the operator place is set to ‘Local’, remote control commands are refused. Pulse width of remote control command shorter than setting will be overridden by local configuration 7.2 SWITCH STATUS MONITORING FTU monitors switch open/close, gas and lock status through auxiliary contacts. FTU scans these contacts input every 5 milliseconds. Switch open/close status is determined by double binary input, normally open and closed contacts. Changes of all input status are saved as events with time tag in history buffer. For each contact input, on-delay time can be applied. It’s adjustable within 10~500ms by 5ms step. www.jinkwang.co.kr 62 / 111 ISO 9001 certified 7.3 Recloser controller FTU- R200 BATTEY MONITORING FTU monitors external Lead-acid battery through the control unit, which are mounted on inner back-side of control box. Battery voltage is supervised continuously during external AC supply loss. If over-discharge condition occurred, the control unit sends alarm signal to RTU and disconnect battery in order to protect battery cell damage after 1-minute delay. The delay enables RTU to send alarm state to remote station via communication. Also while AC supply is applied, battery test control activates this function with connecting dummy battery load during test pulse, which is configurable. The test control command can be ordered at local or remote. www.jinkwang.co.kr 63 / 111 ISO 9001 certified 8 MEASUREMENTS 8.1 BASIC ELECTRIC QUANTITIES Recloser controller FTU- R200 FTU has 3-phase currents and 6 voltages input. DSP digitizes these signals and calculates various electric quantities. These are basically based on fundamental frequency components. DSP use FFT (Fast Fourier Transform) algorithm to get the components. Also DSP calculates true RMS of 3phase currents and voltages which include system frequency components and 2nd~31th harmonics. Actually harmonic components over than 31th are attenuated by analog filters. Electric quantities calculated are listed in the following. Currents (Ia, Ib, Ic, In) RMS, Phase Angle, True RMS Voltage (Va, Vb, Vc, Vr, Vs, Vt) RMS, Phase Angle, True RMS Apparent Power A-Phase, B-Phase, C-Phase, 3-Phase Total, Active Power A-Phase, B-Phase, C-Phase, 3-Phase Total, Reactive Power A-Phase, B-Phase, C-Phase, 3-Phase Total, Power Factor A-Phase, B-Phase, C-Phase, 3-Phase Total, Va-Vr Phase Angle Difference Current, Voltage Unbalance Frequency, Temporature In the above items listed, active power, reactive power values are signed integer. Sign represents power flow or if loads are inductive or capacitive. Also power factor has lead/lag state value separately. Currents and voltages have phase angles, which are relative phase angles compared to the reference Va. These angles are useful to monitor the phase sequence and imbalance of distribution line. 8.2 SEQUENCE COMPONENTS FTU provides the sequence components of 3-phase currents and voltages. They are positive sequence current (I1) and voltage (V1), negative sequence current (I2) and voltage (V2), and zero sequence voltage (V0) which are calculated by 3-phase phasor quantities. This information can be used to monitor imbalance of distribution line. www.jinkwang.co.kr 64 / 111 ISO 9001 certified 8.3 Recloser controller FTU- R200 HARMONICS FTU extracts harmonic components from 3-phase current and voltage signals by using FFT (Fast Fourier Transform). It provides 2nd to 31st harmonic magnitudes and THDs (Total Harmonic Distortion) for each phase. THD is the total harmonic percentage to the fundamental frequency component. FTU also calculates and provides 3-phase THD. These values may be used to monitor the power quality of distribution line. 8.4 ENERGY FTU provides active energy, reactive energy for each phase or 3-phase total. Also import, export energy are accumulated on separate register. Units of energy are kWh, kVarh, which represent primary distribution line energy flow. The values are represented by 16-bit rollovers kWh, kVarh counters which are available at remote or local. Power calculation for energy is based on the fundamental frequency component. It’s not for billing purpose, but for load management. Proper energy accumulation needs that SCADA read energy counter with reset from FTU and accumulate it on SCADA’s local register by periods shorter than the expected rollover time of the counter. Figure 8-1 Four-quadrant power flow directions www.jinkwang.co.kr 65 / 111 ISO 9001 certified 8.5 Recloser controller FTU- R200 DEMAND CURRENTS AND POWER FTU calculates and stores average of currents and active, reactive powers during the demand interval, which is configurable as 5, 10, or 15 minutes. The buffer has 1023 demands. Also FTU stores daily peak demand up to 1023. www.jinkwang.co.kr 66 / 111 ISO 9001 certified Recloser controller FTU- R200 9 MAINTENANCE SOFTWARE 9.1 OVERVIEW FTU-R200 has a dedicated setting and operation tool, FTUMan. This tool is operated on PC or Notebook, and through RS232C port on front panel of FTU-R200. For this communication, MODBUS protocol is used. It supports the follwing features. 9 Setting & Configuration changes 9 Event & Waveform load 9 Measurement & Status display 9 Waveform File upload and convert 9 SCADA monitors protocol data frame between devices Figure 9-1 Overview of FTUMans www.jinkwang.co.kr 67 / 111 ISO 9001 certified 9.2 9.2.1 Recloser controller FTU- R200 OPERATION OF FTUMAN MENU 9.2.1.1 FILE New Closes the current file and allows the creation of a new file Open Closes the current file and opens a standard window file selection dialog. An existing FTU File (*.f2s) can be selected and opened. Save Saves the current file to the hard drive. If the file is new and this is the first time it has been saved, the Save As dialog will be opened allowing the user to type in a name before saving. Save As Opens a standard Windows Save As dialog box. This allows an existing file to be saved under a new name. Exit Closes the current file and exits the tool. 9.2.1.2 COMM Comm.Config Opens a window for communication configuration dialog. Comm.Connection Starts communication with FTU-R200 Comm.Disconnection Stops connecting with FTU-R200 Figure 9-2 Comm. Configuration Window 9 Port Select a serial Port of Laptop 9 Baud Rate Make to the transmission medium per second of in a digitally signal 9 Retry Set up the count if it failed to connect 9 Timeout www.jinkwang.co.kr Set up the time to connect 68 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.1.3 COMMAND 9 Clock Setting Set RTC Time of FTU-R200 Figure 9-3 Clock Setting Window 9 Device Time Gets the current time per 1 second from FTU-R200. Setting Time The operator can set aside time. Use System Time The operator can use PC’s time. Write Write RTC time to FTU-R200 Close Close this window Factory Reset to factory defaults. Initialization Warning: Restoring FTU-R200 to factory defaults will erase all previous setting, configuration and event. Fiqure 9-4 Factory Initialization Message Window www.jinkwang.co.kr 69 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.1.4 TOOLS Protocol Monitoring Protocol monitoring command activation or deactivation. IO Configuration Run the IOConfig program for I/O setting. The IOConfig is explained in the Section 10. DNP3.0 Run the DNPConfig program for DNP index configuration. Index Configuration The DNPConfig is explained in the Section 11. Waveform Run the EvalTool program for analysis waveform data. Evaluation Tool The EvalTool is explained in the Section 12. 9.2.1.5 VIEW Toolbar Show or hide the toolbar. Status Bar Show or hide the status bar. Monitoring Bar Show or hide the monitoring bar. The monitoring bar shows communication status with FTU-R200. 9.2.1.6 HELP The Help Menu opens a window for FTUMan’s program version and information. 9.2.2 TOOLBAR Below the menu is a toolbar with 9 buttons. Figure 9-5 Toolbar of FTUMan Upload Read input or ouput data from FTU-R200. Download Write input or ouput data to FTU-R200. About Opens a window for FTUMan’s program version and information. www.jinkwang.co.kr 70 / 111 ISO O 9001 certifie ed 9.2..3 R Recloser contrroller FTU- R2 200 STATUS SBAR Fiqu ure 9-6 Statuss Bar 9.2..4 MODEL Model Name F/W mware Version n Firm PORT Seriial Port Numb ber and Speed d MODE Com mmunication Status MONIT ORING BAR R Figure 9-7 Monitorring Bar Som me performancce is finished Read ds data from FTU-R200 Wirttes the setting g value on FT TU-R200 Whe en Factory Initialization occcurs. Erro or of connectio on or operatio on Connect or Disco onnect betwee en PC and FTU U-R200 Whe en the time se et is complete ed 9.2..5 FUNCTIION AND CO ONFIGURAT TION SETTIN NG In n Function an nd Configura ation window w, existing se etting values of FTU-R200 0 can be vie ewed thro ough ‘Upload’ button, or setting values are edited and downloa aded to FTU-R200 by cliccking ‘Dow wnload’ butto on to apply ne ew setting values to FTU-R R200. w www.jinkwang. .co.kr 71 / 111 ISO 9001 certified Recloser controller FTU- R200 In some cases, operators require to save and reuse these edited setting values. To satisfy this request, FTUMan tool has ‘New’, ‘Open’ and ‘Save’ menu items in File Menu. The file extension name is ‘f2s’. If you set up the ADGS (Auto Detection Group Setting) Function ‘ON’, you can check the current direction ‘Forward’ or ‘Reverse’. Function has 5 contents, 4 setting groups and active group setting. Each group has protection setting value for FTU-R200. Configuration has 3 contents for I/O, PQM and communication. Communication seperated 3 contens, for Port, DNP3.0 and IEC protocol parameter to communication for SCADA. In tree view, if you choose some content, icon will be replaced with a red icon from a blue icon. And show setting parameters related content. Figure 9-8 Tree View for Funtion and Coufiguration How to edit the setting value? Click the content in tree view and editing value using double-click or Enter-Key. If you changed value, the text color is changed in red. Figure 9-9 before the Change www.jinkwang.co.kr 72 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 9-10 after the Change And, in event window has a following pop-up menu. In the Tree View, select ‘FUNCTION’or ‘CONFIGURATION’ or all sub contens, and press the right-click pop-up menu is avaliable. If you click ‘Upload’ Button, the setting parameters related selected contents in the tree view reads from FTU-R200. Also, if you click ‘Download’ Button, the setting parameters related selected contents in the tree view writes to FTUR200. Figure 9-11 Pop-up Menu for Event Window Figure 9-12 Input Password Dialog When the Factory Initialization or all of information are changed, Input Password Window will be appeared. Note: Default Password is ‘ftuman’. www.jinkwang.co.kr 73 / 111 ISO 9001 certified 9.2.6 Recloser controller FTU- R200 EVENT In Event window, operators can list up all the event records, which are stored in the memory of FTU-R200 by clicking ‘Upload’ button. Also 8 kinds of events are stored. Each event type of event can be separately uploaded from FTU-R200 and can save to CSV format file. Time Resolution for event recording is 5 msec and scanning interval is 1 msec. And, in event window has a following pop-up menu. In the Tree View, select ‘EVENT’ and press the right-click pop-up menu is avaliable. Figure 9-13 Pop-up Menu for Event Window Upload Reads the selected events in the tree view. Clear All Events Delete all event stored. Clear Fault Events Delete only fault events. Save to CSV File Current event saves to CSV (Comma-Saperated Values file) file format. 9 CSV File A Comma-Seperated Values (CSV) file is used for the digital storage of data structed in a table of lists form, where each associated item (member) in a group is in association with others also seperated by the commas of its set. Each line in the CSV file corresponds to a row in the table. Within a line, fields are seperated by commas, each field belonging to one table column. Since it is a common and simple file format, CSV files are often used for moving tabular data between two different computer programs, for example between a database program and a spreadsheet program. www.jinkwang.co.kr 74 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.1 I/O EVENT Figure 9-14 I/O Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. Description Information of generated binary event. Status Occured contact points and binary status, OFF/ON/AUTO www.jinkwang.co.kr 75 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.2 FUNCTION EVENT Figure 9-15 Function Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. Description Operation of protection functions. Status Occurred function event status, OFF/ON. www.jinkwang.co.kr 76 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.3 SYSTEM EVENT Figure 9-16 System Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. Description Information of generated event like set value changed, triggered by power reset and system error or self-diagnosis. Status Occurred event position and detailed description of system error or selfdiagnosis. www.jinkwang.co.kr 77 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.4 FAULT EVENT Figure 9-17 Fault Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. OC Detecting over-current. SEF Detecting Sensitive Earth Fault. UFR Detecting Under Frequency. DIR Fault current direction. Inrush Detecting inrush restraint. Ia, Ib, Ic, In, V0 Fault current and zero-sequency voltage Group Current setting group www.jinkwang.co.kr 78 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.5 PQM EVENT Figure 9-18 PQM Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. Description The occurance history of power quality function change. Value RMS value of voltage when moment voltage change occurs. Unit: kV Duration Duration time of moment voltage change by msec. Unit: msec www.jinkwang.co.kr 79 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.6 DEMAND CURRENT EVENT Figure 9-19 Demand Current Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. Ia, Ib, Ic, In Demand current of each phase and neutral. www.jinkwang.co.kr 80 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.6.7 DEMAND POWER EVENT Figure 9-20 Demand Power Event Window Index Event sequence number, the recent events that occurred is displayed on top. Date & Time Event occurred time. kWa, kWb, kWc, kW3ph 3-phase total and each phase kW. kVARa, kVARb, 3-phase total and each phase kVAR. kVARc, kVAR3ph 9.2.6.8 DAILY MAXIMUM CURRENT EVENT For more details, similar in section 9.2.5.6. Demand Current Event. 9.2.6.9 DAILY MAXIMUM POWER EVENT For more details, similar in section 9.2.5.7. Demand Power Event. www.jinkwang.co.kr 81 / 111 ISO 9001 certified 9.2.7 Recloser controller FTU- R200 MEASUREMENT Operators can monitor all kinds of measurement values such as current, voltage, sequence value, power and energy, etc. And, FTU-R200 has the function of Harmonic Analysis, therefore up to 31st harmonics RMS value and THD for current and voltage are measured and displayed. Lastly, counter values and accumulation data are displayed. FTUMan has 6 kinds of Mesurement window. The measurement value updates per 1 second. 9.2.7.1 BASIC VALUE Operators can check the basic value like load or source volatage, current including RMS, Phase Angle and True RMS also apparent, active and reactive power. And it shows unbalance frequency, temperature and so on. Figure 9-21 Basic Mesurement Window www.jinkwang.co.kr 82 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.7.2 SEQUENCE VALUE It shows zero, positive and negative sequence of source or load voltage and current. Fiqure 9-22 Sequence Value Window www.jinkwang.co.kr 83 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.7.3 POWER You can check active, reactive and apparent power of each phase or 3-phase. It also shows lag of each phase or lead. Fiqure 9-23 Power Winodw www.jinkwang.co.kr 84 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.7.4 ENERGY FTU-R200 provies imported or exported energy according to conductive, inductive energy of each phase or 3-phase total. Fiqure 9-24 Energy Window www.jinkwang.co.kr 85 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.7.5 HARMONICS It displays THD and each harmonics value of voltage and current. It shows from 2nd to 31st per 1 second. Fiqure 9-25 Harmonics Window www.jinkwang.co.kr 86 / 111 ISO 9001 certified Recloser controller FTU- R200 9.2.7.6 COUNTER It basically shows restart, fault, PQM and THD counter and total interruption time. Fiqure 9-26 Counter Window Restart Show restarts time and its count. Fault Counter Show the total fault count of each, neutral phase and Switch Trip. PQM Counter Show the short-duration voltage variation event count. Total Interruption Time Show the total interruption time. THD Counter Show the each or total phase’s current and voltage THD counts. www.jinkwang.co.kr 87 / 111 ISO 9001 certified 9.2.8 Recloser controller FTU- R200 STATUS In status window, all the status indications and command are displayed. Figure 9-27 Status Window When operator supervises some command in status window, this window generated. Upper box shows device name, bottom box displays command name. If you click the ‘OK’ button, command will be operated and window will be disappeared. Figure 99-28 Commnad Window www.jinkwang.co.kr 88 / 111 ISO 9001 certified 9.2.9 Recloser controller FTU- R200 WAVEFORM In waveform window displays Fault and PQM waveforms list stored in FTU-R200. FTU-R200 can record and store the data for up to 8 faults, up to 6 PQM and 1 waveform by manual triggering. And each waveform has the data of 20 cycles at 128 samples. How to upload waveforms are as follow. First, by using the ‘Upload’ command reads a list of stored waveforms on the FTU-R200. Figure 9-29 Waveform List Uploaded To import the waveform from FTU-R200, select a row and double click, you upload the following message window appears. www.jinkwang.co.kr 89 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 9-30 Message Window If you click the ‘OK’ button, opens standard Windows Save As dialog box and enter the file name, and click the Save button. And then will start uploading waveform. The follwing window shows the progress for uploading. Figure 9-31 Progress Window The file is stored in the COMTRADE file format by converting. The stored file is avalilable the waveform analysis by EvalTool. The EvalTool is explained in the Section 12. And, in waveform window has a following pop-up menu. In the Tree View, select ‘WAVEFORM’ and press the rightclick pop-up menu is avaliable. Fiqure 9-32 Pop-up Menu for Waveform Window Upload Read waveform list from FTU-R200. Manual Trigger Capture current waveform by manual triggerring. Clear Fault Waveforms Delete all fault waveform stored. Clear PQM Waveforms Delete all PQM waveform stored. www.jinkwang.co.kr 90 / 111 ISO 9001 certified 10 Recloser controller FTU- R200 I/O CONFIGURATION TOOL 10.1 OVERVIEW The ‘IO Config’ tool allows FTU users to custom I/O mappings. Figure 10-1 Overview of IOConfig Tool The I/O mapping is created using the tool and saved to an IO File (*.iom). Once a valid file has been created, it is linked to the Recloser device. The IOConfig tool is intended to be used off-line only. Mappings are created, saved and linked to FTUMan while disconnected from the FTU. Once these tasks have been completed the user connects to the device and writes the new mapping into the Recloser. 9 Warning: Make sure the IOConfig Tool is closed after a mapping has been edited. If the Tool is left open while the Automatic Data Retriaval feature is running it may attempt to update a mapping file that is already open in the Tool. This will either cause the read www.jinkwang.co.kr 91 / 111 ISO 9001 certified 9 Recloser controller FTU- R200 operation to fail or result in a situation where the newly read file differs from the file open within the Tool. 10.2 OPERATION OF IOCONFIG To start the IOConfig Tool selects ‘Tools – IO Configration’ from the FTUMan menu. When you run the IOConfig Tool, main screen is displayed as show in following figure. There are two tabbed pages in the IOConfig Tool. Figure 10-2 Main Screen of IOConfig Tool www.jinkwang.co.kr 92 / 111 ISO 9001 certified Recloser controller FTU- R200 10.2.1 MENU The File Menu has the following options. New Closes the current file and allows the creation of a new file Open Closes the current file and opens a standard window file selection dialog. An Save Saves the current file to the hard drive. If the file is new and this is the first time existing IO File (*.iom) can be selected and opened. it has been saved, the Save As dialog will be opened allowing the user to type in a name before saving. Save As Opens a standard Windows Save As dialog box. This allows an existing file to be saved under a new name. Exit Closes the current file and exits the tool. The Comm Menu is explained in the Section 9.2.1.2 Comm. The View Menu is explained in the Section 9.2.1.5 View. The Help Menu opens a window for IOConfig’s program version and information. 10.2.2 TOOLBAR Below the menu is a toolbar with 9 buttons. Figure 10-3 Toolbar of IOConfig Upload Read input or ouput data from FTU-R200. Download Write input or ouput data to FTU-R200. About Opens a window for IOConfig’s program version and information. Once you Press the Upload or Download button, the follwing window appears. This window determines the types of data read or write. www.jinkwang.co.kr 93 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 10-4 Select Widow 10.2.3 INPUT FTU-R200 has 10 inputs. Input is created by filling the fields on the Input tab. Each column is defined as follows. Name Input name is defined. Type of the characters is limited to 11 characters. Note: 0~3 of 4 input points is fixed. Debounce Time The minimum time to retain status change. Like, it prevents making useless information against chattering in the point Invert Specifies whether the point will be inverted. Blk.Open To open blocked Blk.Close To close blocked Ext.Trip To trip using external input Ext. Close To close using external input Figure 10-5 Input Tab www.jinkwang.co.kr 94 / 111 ISO 9001 certified Recloser controller FTU- R200 10.2.4 OUTPUT FTU-R200 has 4 relay outputs and 2 photoMOS relay outs. Output is created by filling the fields on the Output tab. Eash column is defined as follows. Figure 10-6 Output Tab Name Output name is defined. Type characters are limited to 11 characters. Only index number of 3 is changed. Pulse Time Set a pulse command. Control Output Select type of PhotoMOS or Contact Relay for OPEN and CLOSE. www.jinkwang.co.kr 95 / 111 ISO 9001 certified 11 Recloser controller FTU- R200 DNP3.0 INDEX CONFIGURATION TOOL 11.1 OVERVIEW Custom DNP3.0 point index maps can now be created and loaded into FTU directly from DNPConfig. The mappings is created using the tool and saved to a DNP3.0 mapping file (*.d3m). Figure 11-1 Overview of DNPConfig The DNPConfig tool is intended to be used off-line only. Mappings are created, saved and linked to FTUMan while disconnected from the FTU. Once these tasks have been completed the user connects to the device and writes the new mapping into the Recloser. 9 Warning: Make sure the DNPConfig Tool is closed after a mapping has been edited. If the Tool is left open while the Automatic Data Retriaval feature is running it may attempt to update a mapping file that is already open in the Tool. This will either cause the read www.jinkwang.co.kr 96 / 111 ISO 9001 certified Recloser controller FTU- R200 operation to fail or result in a situation where the newly read file differs from the file open within the Tool. 11.2 OPERATION OF DNPCONFIG To start the DNPConfig Tool selects ‘Tools – DNP3.0 Index Configration’ from the FTUMan menu. When you run the DNPConfig Tool, main screen is displayed as show in following figure. There are 4 tabbed pages, Binaty Input, Binary Output, Analog Input and Counter, in the DNPConfig Tool. Figure 11-2 Main Screen of DNPConfig www.jinkwang.co.kr 97 / 111 ISO 9001 certified Recloser controller FTU- R200 The DNPConfig tool allows the user to build custom mapplings to suit their own application. Points are added by selecting a row in PID Columns on one of the tabbed pages then double clicking point from the Configuration Tool Box or entering index number in configuration tool box defined. Points are deleted by selecting a row and pressing ‘Delete’ on the keyboard or entering ‘0’. The PID Number ‘0’ means is not used anymore. You can choose to either shift all the rows below up one, or leave the entire row blank. The DNPConfig tool allows the following. 9 Up to 128 Binary Input 9 Up to 32 Binary Output 9 Up to 512 Analog Input 9 Up to 128 Counter 9 11.3.1 MENU The File Menu has the following options. New Closes the current file and allows the creation of a new file Open Closes the current file and opens a standard window file selection dialog. An existing DNP File (*.d3m) can be selected and opened. Save Saves the current file to the hard drive. If the file is new and this is the first time it has been saved, the Save As dialog will be opened allowing the user to type in a name before saving. Save As Opens a standard Windows Save As dialog box. This allows an existing file to be saved under a new name. Exit Closes the current file and exits the tool. The Comm Menu is explained in the Section 9.2.1.2 Comm. The View Menu is explained in the Section 9.2.1.5 View. The Help Menu opens a window for DNPConfig’s program version and information. www.jinkwang.co.kr 98 / 111 ISO 9001 certified Recloser controller FTU- R200 11.3.2 TOOLBAR Figure 11-3 Toolbar of DNPConfig Tool Shows or hides a window the DNP3.0 Configuration tool box. Upload Read input or ouput data from FTU-R200. Download Write input or ouput data to FTU-R200. About Opens a window for DNPConfig’s program version and information. Pressing Upload or Download button, the follwing window appears. This window determines the types of data read or write. Figure 11-4 Select Widow www.jinkwang.co.kr 99 / 111 ISO 9001 certified Recloser controller FTU- R200 11.3.3 CONFIGURATION TOOL BOX The configutation tool box panel is launched by clicking the Tool button. Figure 11-5 Configuration Tool Box The toolbox contains every available point for FTU-R200. The toolbox displays different points depends on which tab selected. For example, if the Counters tab is selected then only accumulators will be displayed on the list. 11.3.4 BINARY INPUT www.jinkwang.co.kr 100 / 111 ISO 9001 certified Recloser controller FTU- R200 Binary inputs are used to report the status of binary points. Figure 11-6 Binary Input Tab Index Specifies the DNP ID Number of the point Range : 0 to 127 PID www.jinkwang.co.kr Specifies number as defiend in the configuration tool box. 101 / 111 ISO 9001 certified Recloser controller FTU- R200 The PID Number’s ‘0’ meaning is not used anymore. Range : 0 to 59 Name The name of the points as defiend in the configuration tool box. This field can be changed in two ways: 9 Selecting the cell then double clicking a point in the configuration tool box. 9 Class 0~3 Entering PID number as defiend in configuration tool box. The DNP3.0 class of the point. The default class can be modified by checking from the checkbox. COS Select event type, COS(Change of state) or SOE(Sequence of Events) Invert Specifies whether the point will be inverted. If the point is inverted it will be transmitted when the condition is false than true. 9 DNP3.0 Classes There are four classes in DNP3.0. These are defined as follows: 0 Class 0 is not an event class. It is used when reporting current (static) data values and not changes of state events. Note: Setting a point to Class 0 will prevent the controller’s protocol handler from reporting change of state events for that point to the master station. The point still remains accessible through static data polls. 1 Class 1 used to report high priority events. Events in this class take precedence. 2 Class 2 used to report medium priority events. 3 Class 3 used to report low priority events. 11.3.5 BINARY OUTPUT Binary Outputs are used to perform operations on the Recloser device and change setting. www.jinkwang.co.kr 102 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 11-7 Binary Output Tab Index Specifies the DNP ID Number of the point Range : 0 to 31 PID Specifies number as defiend in the configuration tool box. The PID Number ‘0’ means is not used anymore. Range : 0 to 10 Name The name of the points as defiend in the configuration tool box. This field can be changed in two ways: 9 Selecting the cell then double clicking a point in the configuration tool box. 9 Entering PID number as defiend in configuration tool box. 11.3.6 ANALOG INPUT www.jinkwang.co.kr 103 / 111 ISO 9001 certified Recloser controller FTU- R200 Analog Points are used to transmit analog data such as line currents, voltages and contact life. Analog intputs are created by adding points as required, then modifying the parameters from defaults if necessary. Figure 11-8 Analog Input Tab Index Specifies the DNP ID Number of the point Range : 0 to 511 www.jinkwang.co.kr 104 / 111 ISO 9001 certified PID Recloser controller FTU- R200 Specifies number as defiend in the configuration tool box. The PID Number ‘0’ means is not used anymore. Range : 0 to 331 Name The name of the points as defiend in the configuration tool box. This field can be changed in two ways: 9 Selecting the cell then double clicking a point in the configuration tool box. 9 Class 0~3 Entering PID number as defiend in configuration tool box. The DNP3.0 class of the point. The default class can be modified by checking from the checkbox. COS Select event type, COS(Change of state) or SOE(Sequence of Events) Scale The scale is used to multiply the reported analog value by the amount enterd. For example, scaling the Ia RMS value by a multiple of ten will change the reported value from zero decimal points to one decimal point (i.e:9 to 9.0) Default Value: 1, Range: 1,10,100,1000 Deadband Display the deadband value for the point. The analog point value must change by more than the deadband amount before it is reported. 11.3.7 COUNTER Counters are used to count data and events such as Trips, Protection Pickups, Faults and Accumulated kWh. www.jinkwang.co.kr 105 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 11-9 Counter Tab Index Specifies the DNP ID Number of the point Range : 0 to 127 PID Specifies number as defiend in the configuration tool box. The PID Number’s ‘0’ means are not used anymore. www.jinkwang.co.kr 106 / 111 ISO 9001 certified Name Range : 0 to 66 Recloser controller FTU- R200 The name of the points as defiend in the configuration tool box. This field can be changed in two ways: 9 Selecting the cell then double clicking a point in the configuration tool box. 9 Class 0~3 Entering PID number as defiend in configuration tool box. The DNP3.0 class of the point. The default class can be modified by checking from the checkbox. COS 12 Select event type, COS(Change of state) or SOE(Sequence of Events) WAVEFORM EVALUATION TOOL 12.1 OVERVIEW The Waveform data upload from FTU-R200 through the above setting program are analyzed in this evaluation tool. Graphs of currents/voltages and operation of protection elements are displayed, and instantaneous/RMS current and voltage values, phase angles and time information www.jinkwang.co.kr 107 / 111 ISO 9001 certified Recloser controller FTU- R200 at tracker position are presented. If 2 trackter one is moving with left mouse button and the other with right mouse button are used, time difference between two points is presented and it becomes the ruler for correct operation of protection element as setting. And, harmonics up to 31st and THD (Total Harmonic Distortion) also show up. Recorded waveforms can be uploaded to FTUMan in local site. After uploading stored to the COMTRADE file format. These waveform data saved as COMTRADE file format and compatible with other analyzing tool. 9 COMTRADE file Comtrade (COMmon format for Transient Data Exchange for power systems) is a file format for oscilloscops data. It is used by many leading coñpanies for the oscilloscops used in high voltage substations. It has been standardised by the IEEE. Figure 1212-1 Overview of EvalTool 12.2 OPERATION OF EVALTOOL To start the EvalTool selects ‘Tools – Waveform Evaluation Tool’ from the FTUMan menu. The tool has meter view and scroll view for graph. www.jinkwang.co.kr 108 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 12-2 Main Screen of EvalTool 12.2.1 MENU The File Menu has the following options. Open Closes the current file and opens a standard window file selection dialog. An existing Data File (*.dat) can be selected and opened. Exit Closes the current file and exits the tool. The Option Menu has the following options. Graph www.jinkwang.co.kr Opens analog and digital graph select window.. 109 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 12-3 Graph Select Window Harmonic Open a window for voltage and current harmonics. Fiqure 12-4 Haramonic List Window Move Change the position of the screen. Zoom The screen to yellow line center to shrink or enlarge the size. The Help Menu opens a window for EvalTool’s program version and information. 12.2.2 TOOLBAR www.jinkwang.co.kr 110 / 111 ISO 9001 certified Recloser controller FTU- R200 Figure 12-5 Toolbar of EvalTool Graph Show the entire graph Harmonic List Check the harmonic list Move-First Move to the beginning graph Move-Double left Show the prior 2-step Move-Left Show the prior 1-step Move-Right Show the posterior 1-step Move-Double right Show the posterior 2-step Move-End Move to the last graph Zoom In Enlarged image Zoom out Shirink image Zoom All Enlarge all image www.jinkwang.co.kr 111 / 111