Subido por Kaosar Alam

S 6 Concrete 01 Material Aspects Strength Design WB

Anuncio
REINFORCED CONCRETE
DESIGN IN COMPLIANCE WITH
BNBC-2020 (ACI 318M-08)
Date: 10 Jan 2022
Session 5: Concrete 1 – Material Aspects
Dr. S. K. Ghosh
President, S. K. Ghosh Associates LLC
S-8A SEng PRP
Training Program
1
Standards for Cement, Aggregate, Water,
Admixtures, and Reinforcement
Standards for Cement, Aggregate, Water,
Admixtures, and Reinforcement
ACI 318-08
CHAPTER 3 - MATERIALS
BNBC-2020
VOLUME 1, Part 5 BUILDING MATERIALS,
Chapter 2 BUILDING MATERIALS, Section 2.3
CEMENT AND CONCRETE
VOLUME 2, Part 6 STRUCTURAL DESIGN,
Chapter 5 CONCRETE MATERIAL
3.2 (5.2.1) Cementitious materials
3.2.1 (5.2.1.1) — Cementitious materials shall
conform to the relevant specifications as follows:
(a) Composition, Specification and Conformity Criteria
for Common Cements (BDS EN 197-1:2003)
(b) Portland cement: ASTM C150/C150M;
(c) Blended hydraulic cements: ASTM
C595/C595M[, excluding Type IS (≥70)
which are not intended as principal cementing
constituents of structural concrete];
[Expansive hydraulic cement: ASTM C845]
3.2 (5.2.1) Cementitious materials
3.2.1 (5.2.1.1) — Cementitious materials shall
conform to the relevant specifications as follows:
(d) Hydraulic cement: ASTM C1157;
(5.2.4.6) Fly ash and natural pozzolan: ASTM C618;
(5.2.4.7) Ground-granulated blast-furnace slag: ASTM
C989;
(2.3.3) Sulphate resisting Portland cement: BDS 612;
(2.3.3) Portland cement: BDS 232;
[Silica fume: ASTM C1240]
BDS EN 197-1 – Common Cement
- CEM I
Portland cement
- CEM II Portland-composite cement
- CEM III Blast furnace cement
- CEM IV Pozzolanic cement
- CEM V Composite cement
ASTM C150 – Portland cement
Type I
Normal
Type IA Normal, air-entrained
Type II
Moderate sulfate resistant
Type IIA Moderate sulfate resistant, air-entraining
Type III High early strength
Type IIIA High early strength, air-entraining
Type IV Low heat of hydration
Type V
High sulfate resistance
ASTM C595 – Blended hydraulic cements
Type IS (X)
Portland blast-furnace slag cement
Type IP (X)
Portland-pozzolan cement
Type IS (50)
contains 50% by mass of slag
Type IP:
(A)
air-entraining
(MS)
moderate sulfate resistant
(HS)
high sulfate resistant
(LH)
low heat of hydration
(MH)
moderate heat of hydration
ASTM C1157 – Hydraulic cements
Type GU General use
Type HE High early strength
Type MS Moderate sulfate resistant
Type HS High sulfate resistant
Type MH Moderate heat of hydration
Type LH Low heat of hydration
ASTM C618 – Fly ash for concrete
ASTM C618. Standard Specification for Coal Fly Ash
and Raw or Calcined Natural Pozzolan for Use in
Concrete.
ASTM C989 – Ground granulated blast furnace
slag
ASTM C989. Standard Specification for Slag Cement
for Use in Concrete and Mortars.
3.2 (5.2.1) Cementitious materials
3.2.2 (5.2.1.2) — Cementitious materials used in the
Work shall correspond to those used as the basis for
selecting concrete mixture proportions. See 5.2
(Selection of concrete proportions).
3.3 (5.2.2) Aggregates
3.3.1 (5.2.2.1) — Concrete aggregates shall conform
to one of the following specifications:
Coarse and Fine Aggregates from Natural Source for
Concrete: BDS 243: 1963
(a) Normal-weight: ASTM C33;
(b) (2.3.2) Lightweight: ASTM C330.
(2.3.2.1) Exception: Aggregates that have been shown
by special test or actual service to produce concrete of
adequate strength and durability and approved by the
building official.
3.3 (5.2.2) Aggregates
3.3.1 (5.2.2.1) — Concrete aggregates shall conform
to one of the following specifications:
Aggregates for Radiation-Shielding Concrete: ASTM
C637;
Lightweight Aggregate for Insulating Concrete: ASTM
C332;
Artificial lightweight aggregates for concrete masonry
units: IS 9142.
3.3 (5.2.2) Aggregates
3.3.2 (5.2.2.2) — Nominal maximum size of coarse
aggregate shall be not larger than:
(a) 1/5 the narrowest dimension between sides of
forms, nor
(b) 1/3 the depth of slabs, nor
(c) 3/4 the minimum clear spacing between individual
reinforcing bars or wires, bundles of bars, individual
tendons, bundled tendons, or ducts.
BDS 243 – Aggregates for Concrete
BDS 243:1963. Coarse and Fine Aggregates from
Natural Sources for Concrete.
ASTM C330 – Lightweight aggregates
ASTM C330/330M. Lightweight aggregates. Standard
Specification for Lightweight Aggregates for Structural
Concrete
Mixing water for concrete
[Water used in mixing concrete shall conform to ASTM
C1602M]
3.4.2 (5.2.3.2) — Mixing water for prestressed concrete
or for concrete that will contain aluminum
embedments, including that portion of mixing water
contributed in the form of free moisture on aggregates,
shall not contain deleterious amounts of chloride ion.
See 4.3.1 (5.5.3).
Mixing water for concrete
5.2.3.3 — Non-potable water shall not be used in
concrete except the following conditions:
(a) Selection of concrete proportions shall be based on
concrete mixes using water from the same source.
(b) Non-potable water is permitted only if specified
comparative mortar test cubes made with non-potable
water produce at least 90 percent of the strength
achieved with potable water.
Reinforcement for concrete
Reinforcement for concrete
3.5.2 (5.3.1.3) — Welding of reinforcing bars shall
conform to AWS D1.4. Type and location of welded
splices and other required welding of reinforcing bars
shall be indicated on the design drawings or in the
project specifications. ASTM specifications for bar
reinforcement, except for ASTM A706, shall be
supplemented to require a report of material properties
necessary to conform to the requirements in AWS
D1.4.
Reinforcement for concrete
3.5.3 (5.3.2) — Deformed reinforcement
3.5.3.1 (5.3.2.1) — Deformed reinforcing bars shall
conform to the requirements for deformed bars in one
of the following specifications:
Plain and ribbed bars: BDS ISO 6935-1,
and BDS ISO 6935-2;
Carbon steel: ASTM A615M;
Rail steel and axle steel ASTM A996M. Bars from railsteel shall be Type R.
Reinforcement for concrete
3.5.3 (5.3.2) — Deformed reinforcement
Low alloy steel: ASTM A706M;
Cold worked steel bars: IS 1786 or BS 4461;
Rail-steel bars: ASTM A616M;
Axle-steel bars: ASTM A617M;
Zinc coated (galvanized) steel bars: ASTM A767M
Epoxy-coated reinforcing steel: ASTM A775M
[Stainless steel: ASTM A955M]
Reinforcement for concrete
3.5.3.2 (5.3.2.2) — . . . for bars with fy exceeding 420
MPa, the yield strength shall be taken as the stress
corresponding to a strain of 0.35 percent.
3.5.3.4 (2.3.6a) — Bar mats for concrete reinforcement
shall conform to ASTM A184M. Reinforcing bars used
in bar mats shall conform to ATM A615M or ASTM
A706M.
Yield Strength of Reinforcement
ACI 318-14
ACI 318-11
Reinforcement for concrete
3.5.3.5 (2.3.6a) — Deformed wire for concrete
reinforcement shall conform to ASTM A496M, shall not
be smaller than size D4 (nominal diameter: 5.72 mm),
and for wire with a specified yield strength, fy exceeding
410 MPa, fy shall be the stress corresponding to a
strain of 0.35 percent.
Reinforcement for concrete
Wire Size - Individual wire size designations are based
on the cross-sectional area of a given wire. “M” stands
for metric. "W" represents a plain wire and "D"
represents a deformed wire. The number following the
"W" and the "D" represents the cross-sectional area of
the wire in mm2. A D10 wire would indicate a deformed
wire having a cross-sectional area of 10 mm2.
Reinforcement for concrete
3.5.3.6 (2.3.6b) — Welded plain wire reinforcement shall
conform to ASTM A185M, except that
for wire with fy exceeding 420 (410)
MPa, the yield strength shall be taken
as the stress corresponding to a strain
of 0.35 percent. Welded intersections
shall not be spaced farther apart than
300 mm in direction of calculated stress, except for
welded wire reinforcement used as stirrups.
Reinforcement for concrete
3.5.3.7 (2.3.6a) — Welded deformed wire reinforcement
shall conform to ASTM A497M, except that for wire
with fy exceeding 420 (410) MPa, the yield strength
shall be taken as the stress corresponding to a strain
of 0.35 percent……
Reinforcement for concrete
3.5.3.7 (2.3.6a) (Contd.) — ……Welded intersections
shall not be spaced farther apart than 400 mm in
direction of calculated stress, except for welded
deformed wire reinforcement used as stirrups.
[Deformed wire larger than MD200 is permitted when
used in welded wire reinforcement conforming to
ASTM A497M but shall be treated as plain wire for
development and splice design].
Reinforcement for concrete
3.5.3.8 (5.3.2.3) — Galvanized reinforcing bars shall
comply with ASTM A767M. Epoxy-coated reinforcing
bars shall comply with ASTM A775M or with ASTM
A934M. Bars to be galvanized or epoxy-coated shall
conform to one of the specifications listed in 3.5.3.1
(5.3.2.1).
Reinforcement for concrete
3.5.3.9 — Epoxy-coated wires and welded wire
reinforcement shall conform to ASTM A884M. Wires to
be epoxy-coated shall conform to 3.5.3.4 and welded
wire reinforcement to be epoxy coated shall conform to
3.5.3.5 or 3.5.3.6.
Reinforcement for concrete
3.5.3.10 — Deformed stainless steel wire and deformed
and plain stainless steel welded wire for concrete
reinforcement shall conform to ASTM A1022M, except
deformed wire shall not be smaller than size MD25 or
larger than size MD200, and the yield strength for wire
with fy exceeding 420 MPa shall be taken as the stress
corresponding to a strain of 0.35 percent. Deformed
wire larger than MD200 is permitted where used in
welded wire reinforcement conforming to ASTM
A1022M, but shall be treated as plain wire for
development and splice design.
Reinforcement for concrete
3.5.3.10 (Contd.) — Spacing of welded intersections
shall not exceed 300 mm for plain welded wire and 400
mm for deformed welded wire in direction of calculated
stress, except for welded wire reinforcement used as
stirrups in accordance with 12.13.2.
Reinforcement for concrete
3.5.4 (5.3.3) — Plain reinforcement
5.3.3.1 — Plain bars shall conform to one of the
specifications listed in Section 5.3.2.1(a) (BDS ISO
6935-1 and BDS ISO 6935-2), (b) (ASTM A615M), (c)
or (d) (ASTM A996M)
3.5.4.2 (5.3.3.2) — Plain wire for spiral reinforcement
shall conform to ASTM A82M, except that for wire with
fy exceeding 420 MPa, the yield strength shall be taken
as the stress corresponding to a strain of 0.35 percent.
Reinforcement for concrete
3.5.5 – Headed shear stud reinforcement
3.5.5.1 – Headed studs and headed stud assemblies
shall conform to ASTM A1044M.
Headed shear stud reinforcement
Reinforcement for concrete
3.5.6 (2.3.6d) — Prestressing steel
3.5.6.1 (2.3.6d) — Steel for prestressing shall conform
to one of the following specifications:
(a) Wire: ASTM A421M;
(b) Low-relaxation wire: ASTM A421M including
Supplement “Low Relaxation Wire”;
(c) Strand: ASTM A416M;
(d) High-strength bar: ASTM A722M.
Reinforcement for concrete
3.5.6.2 (2.3.6d) — Wire, strands, and bars not
specifically listed in ASTM A421M, A416M, or A722M
are allowed provided they conform to minimum
requirements of these specifications and do not have
properties that make them less satisfactory than those
listed in ASTM A421M, A416M, or A722M.
Reinforcement for concrete
3.5.7 (5.3.4) — Structural steel, steel pipe, or tubing
3.5.7.1 (5.3.4.1) — Structural steel used with reinforcing
bars in composite compression members meeting
requirements of 10.16.7 (6.3.10.8) or 10.16.8
(6.3.10.9) shall conform to one of the following
specifications:
(a) Carbon steel: ASTM A36M;
(b) High-strength low-alloy steel: ASTM A242M;
(c) High-strength, low-alloy, Structural Manganese
Vanadium Steel: ASTM A572M;
Reinforcement for concrete
3.5.7 (5.3.4) — Structural steel, steel pipe, or tubing
3.5.7.1 (5.3.4.1) (Contd.) —
(d) High-strength, low-alloy, Columbium - Vanadium
steel: ASTM A572M;
(e) High-strength, low-alloy, 345 MPa steel: ASTM
A588M;
[Structural shapes: ASTM A992M]
Reinforcement for concrete
3.5.7.2 (5.3.4.2) — Steel pipe or tubing for composite
compression members composed of a steel encased
concrete core meeting requirements of 10.16.6
(6.3.10.7) shall conform to one of the following
specifications:
(a) Black steel, hot-dipped, zinc-coated: Grade B of
ASTM A53M;
(b) Cold-formed, welded, seamless: ASTM A500M;
(c) Hot-formed, welded, seamless: ASTM A501M.
Reinforcement for concrete
3.5.8 — Steel discontinuous fiber reinforcement for
concrete shall be deformed and conform to ASTM
A820M. Steel fibers shall have a length-to-diameter
ratio not smaller than 50 and not greater than 100.
3.5.9 — Headed deformed bars
shall conform to ASTM A970M, and
obstructions or interruptions of the
bar deformations, if any, shall not
extend more than 2db from the
bearing face of the head.
Admixtures for concrete
3.6.1 (5.2.4.5) — Admixtures for water reduction and
setting time modification shall conform to ASTM
C494M. Admixtures for use in producing flowing
concrete shall conform to ASTM C1017M.
3.6.2 (5.2.4.4) — Air-entraining admixtures shall
conform to ASTM C260M.
3.6.3 — Admixtures to be used in concrete that do not
conform to 3.6.1 and 3.6.2 shall be subject to prior
approval by the licensed design professional.
Admixtures for concrete
2.3.5 — Admixtures to be used in concrete shall be
subject to prior approval by the Building Official and
conform to following standards:
Admixtures for concrete, mortar and grout – Parts 1
and 2: BDS EN 934-1 and BDS EN 934-2
Fly ash or other Pozzolanas: ASTM C618
Ground granulated blast-furnace slag: ASTM C989
Pigment for colored concrete: ASTM C979
Admixtures for concrete
3.6.4 (5.2.4.3) — Calcium chloride or admixtures
containing chloride from sources other than impurities
in admixture ingredients shall not be used in
prestressed concrete, in concrete containing
embedded aluminum, or in concrete cast against stayin-place galvanized steel forms. See 4.3.1 (5.5.1.2)
and 6.3.2 (5.5.2.1).
3.6.5 — Admixtures used in concrete containing
expansive cements conforming to ASTM C845 shall be
compatible with the cement and produce no
deleterious effects.
ASTM C494M
Type A Water-reducing admixtures
Type B Retarding admixtures
Type C Accelerating admixtures
Type D Water-reducing and retarding admixtures
Type E Water-reducing and accelerating admixtures
Type F Water-reducing, high-range admixtures
Type G Water-reducing, high-range, retarding admixtures
Type S Specific performance admixtures
EN 934 - Admixtures for concrete, mortar
and grout
BDS EN 934-1. Admixtures for
Concrete, Mortar and Grout-Part 1:
Common Requirements.
BS EN 934-2. Admixtures for Concrete, Mortar and
Grout-Part 2: Concrete Admixtures Definitions,
Requirements, Conformity, Marking and Labelling.
Storage of materials
3.7.1 (2.1.3) — Cementitious materials and aggregates
shall be stored in such manner as to prevent
deterioration or intrusion of foreign matter.
3.7.2 — Any material that has deteriorated or has been
contaminated shall not be used for concrete.
Durability Requirements for
Concrete
Special exposures
5.5.1.1 — For concrete intended to have low
permeability when exposed to water, the water cement
ratio shall not exceed 0.50.
5.5.1.2 — For corrosion protection of reinforced
concrete exposed to brackish water, sea water or
spray from these sources, the water cement ratio shall
not exceed 0.4.
If minimum concrete cover required by Sec 8.1.8
Chapter 8 is increased by 12 mm, water cement ratio
may be increased to 0.45.
Suggested workability
Table 6.5.1: Suggested Workability of Concrete for
Various Placing Conditions
Placing Conditions
Degree of
Workability
Values of Workability
Concreting of thin sections with
vibration
Very low
20-10 seconds Vee-Bee time, or
0.75-0.80 compacting factor
Concreting of lightly reinforced
sections with vibration
Low
10-5 seconds Vee-Bee time, or
0.80-0.85 compacting factor
Medium
5-2 seconds Vee-Bee time, or
0.85- 0.92 compacting factor, or
25-75 mm slump for 20 mm
aggregate*
High
Above 0.92 compacting factor, or
75-125 mm slump for 20 mm
aggregate*
Concreting of lightly reinforced
sections without vibration or
heavily reinforced section with
vibration
Concreting of heavily reinforced
sections without vibration
* Slump test shall be performed as per ASTM C143. For smaller aggregates, the values will be lower.
Durability requirements
Water Soluble Sulfate
Table 6.5.2: Requirements for normal weight
aggregate concrete exposed to sulphate
containing solutions
Sulphate
Exposure
Water Soluble
Sulphate (SO4)
in Soil, percent
by Weight
Sulphate
(SO4) in
Water, (ppm)
Cement Type1
Maximum
Water Cement
Ratio, by
Weight
Negligible
0.00-0.10
0-150
-
-
Moderate2
0.10-0.20
150-1500
Other than CEM I
and B type
0.50
Severe
0.20-2.00
1500-10,000
Other than CEM I
and B type
0.45
Very
Severe
Over 2.00
Over 10,000
Other than CEM I
and B type
0.45
Notes: Pozzolan that has been determined by test or service record to improve sulphate resistance when
used in concrete containing Type V cement.
1
For types of cement see BDS EN 197:2003 or ASTM C150 and C595
2
Sea water
Durability requirements
Corrosion of Reinforcement
Corrosion of reinforcement
5.5.3.1 — For corrosion protection, maximum watersoluble chloride ion concentrations in hardened
concrete at ages from 28 to 42 days contributed from
the ingredients including water, aggregates,
cementitious materials, and admixtures, shall not
exceed the limits of Table 6.5.3. When testing is
performed to determine water soluble chloride ion
content, test procedure shall conform to AASHTO
T260, "Methods of Sampling and Testing for Total
Chloride Ion in Concrete and Concrete Raw Materials".
Corrosion of reinforcement
5.5.3.2 — When reinforced concrete will be exposed to
brackish water, sea water, or spray from these
sources, requirements of Sections 5.5.1.1 and 5.5.1.2
for water cement ratio, or concrete strength and
minimum cover requirements of Sec 8.1.8 Chapter 8 of
this Part shall be satisfied.
Table 6.5.3: Maximum chloride-ion content
for corrosion protection
Type of Member
Maximum Water-Soluble Chloride
Ion (Cl) in Concrete, Percent by
Weight of Cement
Prestressed concrete
0.06
Reinforced concrete exposed to
chloride in service
0.15
Reinforced concrete that will be dry
or protected from moisture in service
1.00
Other reinforced concrete
construction
0.30
Minimum concrete strength
5.5.4 — Minimum concrete strength for structural use of
reinforced concrete shall be 20 N/mm2. However, for
buildings up to 4 story, the minimum concrete strength
may be relaxed to 17 N/mm2.
Corrosive environments
8.1.7.8 — If a thickness of cover for corrosive
environment or other severe exposure conditions
greater than the concrete covers specified in Sections
8.1.7.1 to 8.1.7.6 is required, such greater thicknesses
shall be specified. For corrosion protection, a specified
concrete cover for reinforcement not less than 50 mm
for walls and slabs and not less than 65 mm for other
members may be used. For precast concrete members
a specified concrete cover not less than 40 mm for
walls and slabs and not less than 50 mm for other
members may be used.
Corrosive environments
8.1.7.8 (contd.) — Minimum compressive strength of
concrete for the corrosive environment or other severe
exposure conditions shall be 25 MPa with minimum
cement of 400 kg per cubic meter. Coarse aggregate
shall be 20 mm down well-graded stone chips and fine
aggregate shall be coarse sand of minimum FM 2.20.
For any non-structural member like drop wall, railing,
fins etc., 12 mm down well graded stone chips may be
used as coarse aggregate.
Corrosive environments
8.1.7.8 (contd.) — Use of brick chips (khoa) as coarse
aggregate is strictly prohibited for the corrosive
environment or other severe exposure conditions.
Water cement ratio shall be between 0.4-0.45. Potable
water shall be used for all concreting.
Concrete Quality, Mixing, and Placing
Concrete quality, mixing,
and placing
5.1.1 (5.12.1.1) — Concrete shall be proportioned to
provide an average compressive strength, fcr' , as
prescribed in 5.3.2 (5.6.2.2) and shall satisfy the
durability criteria of Chapter 4 (Section 5.5).
Concrete shall be produced to minimize the frequency
of strength tests below fc' , as prescribed in 5.6.3.3
(5.12.3.3).
(5.5.4) For concrete designed and constructed in
accordance with the code, fc' shall not be less than 17
MPa.
Concrete quality, mixing,
and placing
5.1.2 (5.12.1.2) — Requirements for fc' shall be based
on tests of cylinders made and tested as prescribed in
5.6.3 (5.12.3).
5.1.3 (5.12.1.3) — Unless otherwise specified, fc' shall
be based on 28-day tests. If other than 28 days, test
age for fc' shall be as indicated in design drawings or
specifications.
Concrete quality, mixing,
and placing
5.1.4 — Where design criteria in 8.6.1, 12.2.4(d), and
22.5.6.1 provide for use of a splitting tensile strength
value of concrete, laboratory tests shall be made in
accordance with ASTM C330 to establish a value of fct'
corresponding to fc' .
5.1.5 (5.12.1.4) — Splitting tensile strength tests shall not
be used as a basis for field acceptance of concrete.
5.1.6 — Steel fiber-reinforced concrete shall conform to
ASTM C1116. The minimum fc′ for steel fiber reinforced
concrete shall conform to 5.1.1.
Concrete quality, mixing,
and placing
5.2.1 (5.6.1.1) — Proportions of materials for concrete
shall be established to:
(a) Provide workability and consistency to permit
concrete to be worked readily into forms and around
reinforcement under conditions of placement to be
employed, without segregation or bleeding;
(b) Meet requirements for applicable exposure
categories of Chapter 4 (Section 5.5);
(c) Conform to strength test requirements of 5.6 (5.12).
Concrete quality, mixing,
and placing
5.2.2 (5.6.1.2) — Where different materials are to be
used for different portions of proposed Work, each
combination shall be evaluated.
5.2.3 (5.6.1.3) — Concrete proportions shall be
established in accordance with 5.3 (5.6.2)
(Proportioning on the basis of field experience or trial
mixtures, or both) or, alternatively, 5.4 (5.6.3)
(Proportioning without field experience or trial
mixtures) and shall meet applicable requirements of
Chapter 4 (Section 5.5).
Proportioning on the basis of field
experience or trial mixtures, or both
5.3 (5.6.2) — Proportioning Concrete Mix on the Basis
of Field Expérience and/or Trial Mixtures
5.4 (5.6.3) — Proportioning by Water Cement Ratio
5.5 (5.6.4) — Average Strength Reduction
Evaluation and acceptance of concrete
5.6.1 (5.12.1) — Concrete shall be tested in accordance
with the requirements of 5.6.2 (5.12.2) through 5.6.5
(5.12.5). … .
5.6.2 (5.12.2) — Frequency of Testing
5.6.3 (5.12.3) — Laboratory Cured Specimens
5.6.4 (5.12.4) — Field Cured Specimens
5.6.5 (5.12.5) — Investigation of Low Strength Test
Results
Steel fiber-reinforced concrete
5.6.6.1 — Acceptance of steel fiber-reinforced concrete
used in beams in accordance with 11.4.6.1(f) shall be
determined by testing in accordance with ASTM
C1609.
In addition, strength testing shall be in accordance with
5.6.1
Steel fiber-reinforced concrete
5.6.6.2 — Steel fiber-reinforced concrete shall be
considered acceptable for shear resistance if
conditions (a), (b), and (c) are satisfied:
a) The weight of deformed steel fibers per cubic meter
of concrete is . . ..
b) The residual strength obtained from flexural testing .
. . at a midspan deflection of . . ..
c) The residual strength obtained from flexural testing .
. . at a midspan deflection of . . ..
Construction aspects
5.7 (5.7) — Preparation of equipment and place of
deposit
5.8 (5.8) — Mixing
5.9 (5.9) — Conveying
5.10 (5.10) — Depositing
5.11 (5.11) — Curing
5.11.3 (5.11.3) — Accelerated curing
5.12 — Cold weather requirements
5.13 — Hot weather requirements
Formwork, Embedments, and
Construction Joints
Formwork, embedments, and construction
joints
6.1 (5.16.1) — Design of formwork
6.2 (5.16.2) — Removal of forms, shores, and reshoring
6.3 (5.16.3) — Embedments in concrete
6.4 (5.16.4) — Construction joints
REINFORCED CONCRETE
DESIGN IN COMPLIANCE WITH
BNBC-2020 (ACI 318M-08)
Date: 10 Jan 2022
Session 5: Concrete 1 – Strength Design Method
Dr. S. K. Ghosh
President, S. K. Ghosh Associates LLC
S-8A SEng PRP
Training Program
Allowable Stress Design and
Strength Design
Two design philosophies have long been prevalent:
• Allowable Stress Design
• Strength Design
Allowable Stress Design and
Strength Design
• Allowable stress design (ASD) was the principal method
used from the early 1900s until the early 1960s.
• ACI 318-56 was the first standard to officially recognize
and permit the use of strength design (SD).
• Starting from the 1963 edition of ACI 318, there was a
rapid transition to strength design, largely because of its
rational approach and provision of better safety and
reliability at the strength limit state.
Allowable Stress Design and
Strength Design
• ACI 318-63 treated both ASD and SD on an equal basis,
but large portions of ASD (e.g., bond, shear and diagonal
tension, combined axial load and bending moment, etc.)
were modified to reflect behavior at nominal strength.
• ACI 318-77 - ASD moved to Appendix B
• ACI 318-02 – ASD deleted from the standard
Strength Design Philosophy
Strength Design: Basics
ACI 318M-08 Section 9.1.1 (6.1.3.3)
The strength design method requires the design
strength of a member at a section to be equal to or
greater than the required strength at that section,
calculated from the code-specified load combinations
as are stipulated in Chapter 2, Loads.
Required Strength (U) ≤ Design Strength
Strength Design: Required Strength
Required Strength = Combination of Service Load
Effects × Respective Load Factors
Service Load = The load specified by the building code,
which a structure is expected to support under normal
usage
Service Load Effects = Internal forces (axial force,
shear force, bending moment, etc.) generated in a
member by the code-specified service loads, and
determined using structural analysis
Load Factor = Factors to account for probable
variations in service load (≥1.0)
Strength Design: Required Strength
Strength-Level Load = The maximum load that any
structure is designed to support
Load factors scale the effects of the service loads on a
structural member up to the effects of strength-level
loads.
Strength Design: Design Strength
Design Strength = φ × Nominal Strength
φ = Strength reduction factor (≤1.0)
Nominal Strength = Strength of a member or a crosssection calculated using the assumptions and strength
design provisions of ACI 318M (BNBC 2020).
Strength Design: Design Strength
Design Strength = φ × Nominal Strength
Both nominal strengths and φ-factors for reinforced
concrete members are to be determined in accordance
with ACI 318M-08 (BNBC 2020)
Strength Design: Notation
Required Strength:
Pu = Factored axial force at section
Vu = Factored shear force at section
Mu = Factored bending moment at section
Tu = Factored torsional moment at section
Strength Design: Notation
Nominal Strength:
Pn = Nominal axial strength at section
Vn = Nominal shear strength at section
Mn = Nominal flexural strength at section
Tn = Nominal torsional moment strength at section
Strength Design: Notation
Design Strength:
φPn = Design axial strength at section
φVn = Design shear strength at section
φMn = Design flexural strength at section
φTn = Design torsional moment strength at section
Strength Design: Load Factors
Account for:
1. Probable variation in specified service loads
because of

Variation in member sizes

Variation in material densities

Structural and nonstructural alterations

Degree of accuracy in load determination
Strength Design: Load Factors
Account for:
2. Uncertainties in calculation of load effects on a
member because of

Assumptions of stiffness, span length, etc.

Other assumptions and simplifications in the
structural model used for analysis
Strength Design:
Strength Reduction Factors
Account for:
1. Probable variation in material strength because of

Quality control

Effect of testing speed

Difference between in-situ strength and specimen
strength

Stresses due to creep and shrinkage
Strength Design:
Strength Reduction Factors
Account for:
2. Probable variation in member sizes because of

Tolerances in formwork

Rolling and fabrication tolerances allowed for
reinforcing bars

Tolerances in reinforcement placement
Strength Design:
Strength Reduction Factors
Account for:
3. Various design assumptions and simplifications that
cause the design behavior of structural members to
deviate from their actual behavior.
4. Consequences of failure.
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
 A modified version of the strength design method
first introduced in ACI 318-95
 Consistent design provisions for reinforced and
prestressed concrete beams and columns
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
Strength Reduction Factor, φ,
Under Flexure and/or Axial Load
Depends on Net Tensile Strain, εt
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
Net tensile strain — The tensile strain at nominal
strength exclusive of strains due to effective prestress,
creep, shrinkage, and temperature effects.
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
Extreme tension steel — The reinforcement
(prestressed or nonprestressed) that is the farthest from
the extreme compression fiber.
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
εt = Net tensile strain
dt = Depth to extreme tension reinforcement
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
Excessive Cracking
Excessive Deflection
Net Tensile Strain
Is a Measure of Both
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
Compression-controlled strain limit — The net
tensile strain at balanced strain conditions.
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
 Compression-controlled section: Sections are
compression-controlled if the net tensile strain, εt, is
equal to or less than the compression-controlled
strain limit. For Grade 420 reinforcement, and for all
prestressed reinforcement, it shall be permitted to set
the compression-controlled strain limit equal to 0.002.
(ACI 318M-08 Section 10.3.3 (6.3.3.3))
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
 Tension-controlled section: Sections are tensioncontrolled if the net tensile strain, εt, is equal to or
greater than 0.005. (ACI 318M-08 Section 10.3.4
(6.3.3.4))
Strength Design:
Strength Reduction Factors
Unified Design Provisions:
 Transition sections: Sections with εt between the
compression-controlled strain limit and 0.005
constitute a transition region between compressioncontrolled and tension-controlled sections. (ACI
318M-08 Section 10.3.4 (6.3.3.4))
Strength Design:
Strength Reduction Factors
Unified Design Provisions
εt ≤ 0.002: compressioncontrolled
εt ≥ 0.005: tensioncontrolled
0.002 < εt < 0.005:
transition region
ACI 318M-08 Fig. R10.3.3 (6.6.3)
Strength Design:
Strength Reduction Factors
9.3.2 (6.2.3.2) — Strength reduction factor shall be as
given in 9.3.2.1 through 9.3.2.7 (Sections 6.2.3.2.1 to
6.2.3.2.6):
9.3.2.1 (6.2.3.2.1) — Tension-controlled sections as
defined in 10.3.4 (6.3.3.4)………………...0.90
9.3.2.2 (6.2.3.2.2) — Compression-controlled sections,
as defined in 10.3.3 (6.3.3.3):
(a) Members with spiral reinforcement conforming
to 10.9.3 (6.3.9.3)………………. 0.75
(b) Other reinforced members…
0.65
Strength Design:
Strength Reduction Factors
9.3.2.2 (6.2.3.2.2) (contd.) — For sections in which
the net tensile strain, εt, is between the limits for
compression-controlled and tension-controlled
sections, φ shall be permitted to be linearly increased
from that for compression-controlled sections to 0.90
as εt increases from the compression-controlled strain
limit to 0.005 (Also see Figure 6.6.1). While
interpolating, it shall be permitted to round φ to second
digit after decimal.
Strength Design:
Strength Reduction Factors
ACI 318M-08 Fig. R9.3.2 (6.6.1)
Strength Design:
Strength Reduction Factors
(6.2.3.2.3) — It shall be permitted for compressioncontrolled sections, as defined in Sec 6.3.3.3, the
following optional, more conservative alternative
values of strength reduction factor φ, where less
controlled construction environment justifies such
selection according to engineering judgment of the
designer:
For members with spiral reinforcement conforming
to Sec 6.3.9.3………………………… 0.70
Other reinforced members………… 0.60
Strength Design:
Strength Reduction Factors
Compression-controlled sections (e.g. columns) are
assigned lower φ-factors than tension-controlled
sections (e.g. beams) because:
 compression-controlled sections generally have
less ductility
 compression-controlled sections are more
sensitive to variation in concrete strength
 Generally, the consequences of a column failure
are more severe than those of a beam failure
Strength Design:
Strength Reduction Factors
Compression-controlled sections in members with spiral
reinforcement are assigned a higher φ-factor than those
in members with tie reinforcement because:
 Members with spiral reinforcement have greater
toughness and ductility, as demonstrated by
performance in the Pentagon (U.S. DoD) building
after it was hit by one of the 9/11 planes
Strength Design:
Strength Reduction Factors
9.3.2.3 (6.2.3.2.4) — Shear and torsion……… 0.75
9.3.2.4 (6.2.3.2.5) — Bearing on concrete (except for
post-tensioned anchorage zones and strut-and-tie
models)………………………………………….. 0.65
9.3.2.5 (9.9.2d) — Post-tensioned anchorage zones
…………………………………………………....
0.85
9.3.2.6 (6.2.3.2.6) — Strut-and-tie models (Appendix
A(I)), and struts, ties, nodal zones, and bearing areas
in such models…………………………………. 0.75
Strength Design:
Strength Reduction Factors
9.3.2.7 (9.9.2f) — Flexural sections in pretensioned
members where strand embedment is less than the
development length as provided in 12.9.1.1:
(a) From the end of the member to the end of the
transfer length……………………… 0.75
(b) From the end of the transfer length to the end
of the development length shall be permitted to
be linearly increased from………
0.75 to 0.9
Where bonding of a strand does not extend to the end of the
member, strand embedment shall be assumed to
begin at the end of the debonded length.
Strength Design:
Strength Reduction Factors
ACI 318M-08 Section 9.3.2.7
Strength Design: Safety Margin
Safety Margin is provided by:
1. Reduction in member strength by φ-factor
2. Increase in the imposed load by load factor
In essence,
Load Factor
*
Safety Margin =
Strength Reduction Factor ( φ )
*Direct calculation like this is not always possible
Strength Design: Safety Margin
Design of a beam for flexural moment from dead
load
Design Eq.: Mu ≤ φMn
From 2009 IBC Eq. 16-1 (2.7.3.1 Eq. 1):
Mu = 1.4 × Bending moment from code specified dead
load
φ = 0.9 for beam flexure (ACI 318M-08 Section 9.3.2
(6.2.3.2))
Safety Margin = 1.4/0.9 = 1.56
Strength Design: Safety Margin
Load factors and strength reduction factors are provided
after considering:

Probability of actual imposed loads exceeding
and member strengths falling short of the
respective design values, AND

Severity of failure if the above does happen
Strength Design: Safety Margin
Various items are considered:

The type of failure, warning of failure, and
existence of alternative load path(s)

Importance of structural element within the
structure

Potential loss of life

Costs to society in lost time, lost revenue, or
indirect loss of life or property due to failure

Cost of replacing the structure
Strength Design: Safety Margin
MacGregor, J.G., “Safety and Limit States Design for
Reinforced Concrete,” Canadian Journal of Civil
Engineering, Vol. 3, No. 4, December 1976.
“The ACI…design requirements…are based on an
underlying assumption that if the probability of understrength members is roughly 1 in 100 and the probability
of overload is roughly 1 in 1000, the probability of
overload on an understrength structure is 1 in 100,000.
Load factors were derived to achieve this probability of
overload. …
Strength Design: Safety Margin
…… Based on values of concrete and steel strength
corresponding to a probability of understrength of 1 in
100, the strengths of a number of typical sections were
computed. The ratio of the strength based on these
values to the strength based on nominal strengths of a
number of typical sections were arbitrarily adjusted to
allow for the consequences of failure and the mode of
failure of a particular type of member, and for a number
of other sources of variation in strength.”
Strength Design: Load Combinations
 A structural member is required to be designed for a
number of combinations of the effects of various
factored loads
 Strength design load combinations are provided in
2009 IBC Section 1605.2 (BNBC 2020 Section 2.7.3)
Codes and standards
2009 IBC
102.4 Referenced codes and standards. The codes
and standards referenced in this code shall be
considered part of the requirements of this code to the
prescribed extent of each such reference. Where
differences occur between provisions of this code and
referenced codes and standards, the provisions of this
code shall apply.
1605.2.1 (2.7.3.1) Strength Design or
LRFD Load Combinations (2009 IBC)
1.
1.4(D + F)
2.
1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or R)
3.
1.2D +1.6(Lr or R) + (L or 0.8W)
4.
1.2D + 1.6W + L + 0.5(Lr or R)
5.
1.2D + 1.0E + 1.0L
6.
0.9D + 1.6W + 1.6H
7.
0.9D + 1.0E + 1.6H
2.7.3 Combinations of Load Effects for
Strength Design Method
Exceptions:
1. The load factor on live load L in combinations (3),
(4), and (5) is permitted to be reduced to 0.5 for all
occupancies in which minimum specified uniformly
distributed live load is less than or equal to 5.0 kN/m2,
with the exception of garages or areas occupied as
places of public assembly (corresponding to f1 = 0.5 in
2009 IBC load combinations)
2.7.3 Combinations of Load Effects for
Strength Design Method
Exceptions:
2. The load factor on H shall be set equal to zero in
combinations (6) and (7) if the structural action due to
H counteracts that due to W or E. Where lateral earth
pressure provides resistance to structural actions from
other forces, it shall not be included in H but shall be
included in the design resistance.
2.7.3 Combinations of Load Effects for
Strength Design Method
Exceptions:
3. For structures designed in accordance with the
provisions of Chapter 6, Part 6 of this Code (reinforced
concrete structures), where wind load W has not been
reduced by a directionality factor, it shall be permitted
to use 1.3W in place of 1.6W in (4) and (6) above.
1605.2.1 (2.1.4) Strength Design or
LRFD Load Combinations (2009 IBC)
D = Dead load effect
F = Fluid load effect
T = Effect of self-straining forces (creep, shrinkage, etc.)
L = Floor live load effect (including live load reduction)
H = Effect of lateral earth pressure, ground water pressure, etc.
Lr = Roof live load effect (including live load reduction)
R = Rain load effect
W = Wind load effect
E = Earthquake load effect
1605.2.1 Strength Design or
LRFD Load Combinations (2009 IBC)
Earthquake loads computed in accordance with the
2009 IBC are already at strength-level.
This is why the load factor on the earthquake load
effect, E, is 1.0.
2.7.3 Combinations of Load Effects for
Strength Design Method
When a structure is located in a flood zone or in tidal
surge zone, the following load combinations shall be
considered:
1. In Coastal Zones vulnerable to tidal surges, 1.6W
shall be replaced by 1.6W+2.0Fa in combinations (4)
and (6).
2. In Non-coastal Zones, 1.6W shall be replaced by
0.8W+1.0Fa in combinations (4) and (6).
Fa = Effect of flood load
1605.2 Strength Design or LRFD Load
Combinations (2009 IBC)
For many members, the only loads considered are
dead, live, wind and earthquake, and F, H, R, S, T
load effects are not required to be included.
Consequently, the load combinations can be
simplified.
1605.2.1 (2.7.3.1) Strength Design or
LRFD Load Combinations (2009 IBC)
1.4D
1.2D + 1.6L + 0.5Lr
1.2D + 1.6Lr + f1L
1.2D +1.6Lr + 0.8W
1.2D + 1.6W + f1L + 0.5Lr
1.2D + 1.0E + f1L
0.9D + 1.6W
0.9D + 1.0E
f1 = 0.5 except in special circumstances
1605.2.1 (2.7.3.1) Strength Design or
LRFD Load Combinations (2009 IBC)
In addition to the possible variability of the specified
loads, values of the load factors are also assigned
based on the probability of simultaneous occurrence of
different load types.
For example: the load factor on dead load (D) alone
(=1.4) is higher than the load factor on dead load
(=1.2) when other loads such as live load (L), wind
load (W) or earthquake load (E) are also present
1605.2.1 (2.7.3.1) Strength Design or
LRFD Load Combinations (2009 IBC)
Load factor values can also be based on other
considerations, such as directionality effect for wind
load (W)
ASCE 7-05
6.5 (2.4.3) Analytical Procedure
 Directionality factor Kd introduced in 1998
• Added to equation for velocity pressure:
• qz = 0.00256 Kz Kzt Kd V2 I
(Eq. 6.2.17)
• Separate out effect of wind load factor
• Requires adjustment to wind load factor ( 1.3 → 1.6 )
(2.7.3 Exception 3)
• Table 6-4 (6.2.12)
Reason: Explicitly identify directionality
effect in future editions.
ASCE 7-05 2.3.2 (2.7.3.1) Strength Design
Load Combinations
Wind load factor:
 Old (1995): LF = 1.3 → included directionality effect
0.85 (directionality) x 1.53 (LF w/o directionality) = 1.3
 Now: Identify directionality effect explicitly in Kd. Round
load factor from 1.53 to 1.6.
Seismic Strength Design Load Combinations (2009
IBC, ASCE 7-05, BNBC 2020)
 1.2D + 1.0E + 1.0L
(Load Combination 5)
 0.9D + 1.0E
(Load Combination 7)
(2.5.13.4)
E = Em = Emh + Ev
(in Load Combination 5)
E = Em = Emh - Ev
(in Load Combination 7)
Seismic Strength Design Load Combinations
(BNBC 2020)
Em = total seismic load effect including overstrength
factor
Emh = effect of horizontal seismic forces as defined in
Sections 2.5.7 or 2.5.9 including structural overstrength
Ev = effect of vertical seismic forces as defined in
Section 2.5.13.2
The horizontal seismic load effect with overstrength
factor, Emh , shall be determined in accordance with the
following equation: Emh = Ω0Eh
Vertical Earthquake Loading
2.5.13.2 The maximum vertical ground acceleration
shall be taken as 50 percent of the expected horizontal
peak ground acceleration (PGA):
Ev = 0.50(ah)D
(Eq. 6.2.56)
ah = expected horizontal peak ground acceleration (in g)
for design = (2/3)ZS
D = effect of dead load, S = site dependent soil factor
(see Table 6.2.16).
Seismic Strength Design Load Combinations (2009
IBC, ASCE 7-05)
Effect of Vertical Earthquake Ground
Motion (2009 IBC, ASCE 7-05)
 Gravity and Earthquake Effects Additive
U = 1.2D + 1.0E + 0.5L
= 1.2D + (ρQE + 0.2SDSD) + 0.5L
= (1.2 + 0.2SDS)D + ρQE + 0.5L
Effect of Vertical Earthquake Ground
Motion (2009 IBC, ASCE 7-05)
 Gravity and Earthquake Effects Counteractive
U = 0.9D - 1.0E
= 0.9D - (ρQE + 0.2SDSD)
= (0.9 - 0.2SDS)D - ρQE
ASCE 7-05 12.4.3.2 Load Combinations with
Overstrength Factor
Basic Combinations for Strength Design with
Overstrength Factor
(1.2 + 0.2SDS)D + Ω0QE + 0.5L
(0.9 − 0.2SDS)D + Ω0QE
Unified Design Provisions
Unified Design Provisions
Unified Design Provisions were first introduced in ACI
318-95 Appendix B
Moved to the main body of ACI 318 in the 2002 edition
Unified Design Provisions
 Unified Design Provisions do not alter the nominal
strength calculations
 The provisions unify the determination of appropriate
strength reduction factors for prestressed and
reinforced concrete beams and columns with
rectangular or nonrectangular sections, and with one
or multiple layers of steel
 The provisions unify the treatment of moment
redistribution in continuous beams of reinforced and
prestressed concrete.
Why Unified Provisions Needed?
1999 CODE
Redistribution of Negative Moments
in Continuous Members
R/C
P/S
8.4
(6.1.6)
18.10.4
(9.10.4)
Limits for Reinforcement of Flexural 10.3.3
Members
(6.3.3.3)
18.8.1
(9.9.1)
8.4 – Redistribution of Negative Moments In Continuous
Nonprestressed Flexural Members (’99)
18.10.4 – Redistribution of Negative Moments in Continuous
Prestressed Flexural Members (’99)
20 1 –
d
ωp –
ω – ω′
dp
0.36β1
percent
10.3.3 – Reinforcement Limit (’99)
 If φ Pn < Smaller of
• 0.10 f’c Ag , or
• φ Pb
Then
18.8.1 – Limits For Reinforcement Of Flexural
Members (’99)
 The following ratios used to compute Mn must not
to exceed 0.36β1
• ωp
• [ωp + (d/dp)(ω - ω’)]
• [ωpw + (d/dp)(ωw - ωw’)]
18.8.1 – Limits For Reinforcement Of
Flexural Members (’99)
 ω is ρfy /fc′
ρ = As/bd
 ω′ is ρ′fy /fc′
ρ' = A's/bd
 ωp is ρpfps /fc′
ρp = Aps /bdp
 ωw is ρwfy /fc′
ρw = As/bwd
 ωw′ is ρw′fy /fc′
ρw' = A's/bwd
 ωpw is ρpwfps /fc′
ρpw = Aps /bwdp
 fps = stress in prestressing steel at nominal flexural
strength
Why Unified Provisions Needed?
R/C
P/S
18.0 – Notation (’99)
Aps = area of prestressed reinforcement in tension zone
dp =
distance from extreme compression fiber to
centroid of prestressed reinforcement
Mn = Apsfps(dp-a/2)
 Aps and dp Not Compatible
Unified Design Provisions
Background Article
Robert F. Mast, “Unified Design Provision for Reinforced
and Prestressed Concrete Flexural and
Compression Members,” ACI Structural Journal,
March-April 1992
Unified Provisions Applicability
 Flexural & compression members
 R/C, P/S, and combinations
 Steel at various depths
 Sections of any shape
 Composite sections
 Tension-controlled columns
8.4 (6.1.5) – Redistribution of Moments in
Continuous Flexural Members (’08)
 Applies equally to both nonprestressed & prestressed
sections
 Based on net tensile strain, εt
 Percent redistribution ∆M = 1000εt
 Minimum εt = 0.0075
 Maximum redistribution = 20%
8.4 (6.1.5) – Redistribution of Moments in
Continuous Flexural Members (’08)
8.4 (6.1.5) – Redistribution of Moments in
Continuous Flexural Members (’08)
8.4 (6.1.5) – Redistribution of Moments in
Continuous Flexural Members (’08)
 Moment redistribution may not be used for slab
systems designed by the Direct Design Method
(see 13.6.1.7 (6.5.6.1.7)).
R8.4 – Moment Redistribution R/C
Net Tensile Strain, εt
R8.4 – Moment Redistribution P/S
Net Tensile Strain, εt
10.3.5 (6.3.3.5) – Maximum Reinforcement for
Nonprestressed Flexural Members
Flexural members or members with
Pu < 0.10fc' Ag
 Net tensile strain ≥ 0.004
 Replaces ρmax ≤ 0.75ρb requirement of ’99 Code
 New limit slightly more restrictive
 For rectangular sections, new limit corresponds to
0.714ρb for Grade 420 MPa steel
18.8.1 (9.9.1) – Reinforcement Limits
 Limits are based on net tensile strain, εt
R18.8.1 (9.9.1) – Reinforcement Limits
 For prestressed concrete sections, net tensile
strain limits for tension-controlled sections may also
be stated in terms of ωp as defined in the 1999 and
earlier editions of the code
The net tensile strain limit of 0.005 corresponds to ωp =
0.32β1 for prestressed rectangular sections
Questions?
Thank you
Descargar