Temperature Controller ESM-4420 48x48 DIN 1/16 ESM-4420 48 x 48 DIN 1/16 Temperature Controller with Universal Input - 4 digits process(PV) and 4 digits process set value(SV) display - Universal process input (TC, RTD ) - Configurable ON/OFF, P, PI, PD and PID control forms - Adaptation of PID Coefficients to the system with Self-Tune operation (Step Response Tuning) - Programmable Heating or Cooling Functions for Control Output - Alarm Functions for Alarm Output Instruction Manual. ENG ESM-4420 02 V08 07/13 ABOUT INSTRUCTION MANUAL Instruction manual of ESM-4420 Temperature Controller consists of two main sections. Explanation of these sections are below. Also, there are other sections which include order information and technical specifications of the device. All titles and page numbers in instruction manual are in “CONTENTS” section. User can reach to any title with section number. Installation: In this section, physical dimensions of the device, panel mounting, electrical wiring, physical and electrical installation of the device to the system are explained. Operation and Parameters: In this section user interface of the device, accessing to the parameters, description of the parameters are explained. Also in these sections, there are warnings to prevent serious injury while doing the physical and electrical mounting or using the device. Explanation of the symbols which are used in these sections are given below. c a i This symbol is used for safety warnings. User must pay attention to these warnings. This symbol is used to determine the dangerous situations as a result of an electric shock. User must pay attention to these warnings definitely. This symbol is used to determine the important notes about functions and usage of the device. 2 CONTENTS 1.PREFACE............................................................................................................................................ Page 1.1 GENERAL SPECIFICATIONS 1.2 ORDERING INFORMATION 1.3 WARRANTY 1.4 MAINTENANCE 5 2.INSTALLATION.................................................................................................................................... Page 2.1 GENERAL DESCRIPTION 2.2 DIMENSIONS 2.3 PANEL CUT-OUT 2.4 ENVIRONMENTAL RATINGS 2.5 PANEL MOUNTING 2.6 INSTALLATION FIXING CLAMP 2.7 REMOVING FROM THE PANEL 8 3.ELECTRIAL WIRINGS.........................................................................................................................Page 3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS 3.2 ELECTRICAL WIRING DIAGRAM 3.3 VIEW OF THE DEVICE LABEL 3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE 3.5 PROCESS INPUT CONNECTION 3.5.1 TC (THERMOCOUPLE) CONNECTION 3.5.2 RTD CONNECTION 13 3.6 GALVANIC ISOLATION TEST VALUES OF ESM-4420 TEMPERATURE CONTROLLER 4.OUTPUT CONNECTION FORMS IN ESM-4420 TEMPERATURE CONTROLLER........................... Page 4.1 PROCESS OUTPUT OR ALARM OUTPUT-2 ( RELAY ) CONNECTION 4.2 PROCESS OUTPUT OR ALARM OUTPUT-2 ( SSR DRIVER ) CONNECTION 4.3 ALARM OUTPUT-1 ( RELAY ) CONNECTION 4.4 PROCESS OUTPUT (SSR DRIVER) CONNECTION 19 5.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS.................................................... Page 5.1 FRONT PANEL DEFINITION 5.2 RUN THE DEVICE AND OBSERVATION OF SOFTWARE REVISION ON THE DISPLAYS 5.3 ADJUSTMENT OF PROCESS SET VALUE 5.4 ADJUSTMENT OF ALARM SET VALUE 21 6.PARAMETERS.................................................................................................................................... Page 6.1 PARAMETER LIST 6.2 EASY ACCESS DIAGRAM OF PARAMETERS 6.3 ENTERING TO THE PROGRAMMING SECTION AND PROCESS MENU 6.4 CONTROL MENU 6.5 ALARM MENU 6.6 PROTECTION MENU 24 7.GENERAL INFORMATION.................................................................................................................. Page 7.1 TUNE OPERATION 7.2 ALARM TYPES 39 8.FAILURE MESSAGES IN ESM-4420 TEMPERATURE CONTROLLER............................................ Page 44 9.SPECIFICATIONS................................................................................................................................Page 45 10.OTHER INFORMATION..................................................................................................................... Page 46 3 EU DECLARATION OF CONFORMITY Manufacturer’s Name : EMKO ELEKTRONIK A.S. Manufacturer’s Address : DOSAB, Karanfil Sk., No:6, 16369 Bursa, TURKEY The manufacturer hereby declares that the product: Product Name : Temperature Controller Unit Type Number : ESM-4420 Product Category : Electrical equipment for measurement, control and laboratory use Conforms to the following directives : 2006 / 95 / EC The Low Voltage Directive 2004 / 108 / EC The Electromagnetic Compatibility Directive has been designed and manufactured to the following specifications : EN 61000-6-4:2007 EMC Generic Emission Standard for Industrial Environments EN 61000-6-2:2005 EMC Generic Immunity Standard for Industrial Environments EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and laboratory use When and Where Issued th Authorized Signature 16 October 2009 Name : Serpil YAKIN Bursa-TURKEY Position : Quality Manager 4 1.Preface ESM-4420 series temperature controllers are designed for measuring and controlling a process value. They can be used in many applications with their universal process input, control outputs and selectable alarm functions. Some application fields which they are used are below: Application Fields Application Glass PID Process Control Plastic Petro-Chemistry Textile Automative Machine production industries 1.1 General Specifications ESM-4420 Standard 230 V V (±15%) , 50/60Hz Optional Supply Voltage Input Supply Voltage Input 115 V V (±15%) , 50/60Hz 24 V V (±15%) , 50/60Hz 24 V W (-15%;+10%) , 50/60Hz Process Input Universal Process Input TC, RTD Standard Process Out or Alarm Out Control Output or Alarm Output Heating-Cooling Function ON/OFF, PID Operation Standard Alarm Out Alarm Output Standard Process Out Control Output Heating-Cooling Function ON/OFF, PID Operation 5 1.2 Ordering Information A BC ESM-4420 (48x48 DIN 1/16) D E 0 / FG HI / U V W Z / 01 / 0 0 0 0 02 A Supply Voltage 2 24V W ( -15%;+10% ) 50/60Hz 3 24V V ( ± %15 ) 50/60Hz 4 115V V ( ± %15 ) 50/60Hz 5 230V V ( ± %15 ) 50/60Hz 9 Customer BC Input Type 20 Configurable (Table-1) Scale Table-1 D Serial Communication 0 None All order information of E S M - 4 4 2 0 Te m p e r a t u r e Controller are given on the table at left. User may form appropriate device configuration from information and codes that at the table and convert it to the ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs. Please contact us, if your needs are out of the standards. E Output-1 (Process or Alarm Output) 1 Relay Output (resistive load 5A@250V V , 1 NO + 1NC) 2 SSR Driver Output (maximum 12VZ, max. 24mA) FG Output-2 (Alarm Output) 01 Relay Output (resistive load 5A@250V V , 1 NO) HI Output-3 (Process Output) 02 SSR Driver Output (maximum 12VZ, max. 24mA) Table-1 BC Input Type(TC) 23 J ,Fe CuNi IEC584.1(ITS90) 25 K ,NiCr Ni IEC584.1(ITS90) 27 R ,Pt13%Rh Pt IEC584.1(ITS90) 28 S ,Pt10%Rh Pt IEC584.1(ITS90) 29 T ,Cu CuNi IEC584.1(ITS90) BC Input Type(RTD) 39 PT 100 , IEC751(ITS90) 40 PT 100 , IEC751(ITS90) c Scale(°C) -200°C,900°C -200°C,1300°C 0°C,1700°C 0°C,1700°C -200°C,400°C Scale(°C) Scale(°F) -328°F,1652°F -328°F,2372°F 32°F,3092°F 32°F,3092°F -328°F,752°F Scale(°F) -200°C,650°C -328°F,1202°F -199.9°C,650.0°C -199,9°F,999.9°F V Þ Vac, Z Þ Vdc W Þ Vdc or Vac can be applied 6 1.3 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely. 1.4 Maintenance Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case. 7 2.Installation c Before beginning installation of this product, please read the instruction manual and warnings below carefully. In package , - One piece unit - Two pieces mounting clamp - One piece instruction manual A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product. If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and separate the electrical connection of the device from the system. The unit is normally supplied without a power switch or a fuse. Use power switch and fuse as required. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure. Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented. Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire. Do not use the unit in combustible or explosive gaseous atmospheres. During the equipment is putted in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful. Montage of the product on a system must be done with it’s mounting clamp. Do not do the montage of the device with inappropriate mounting clamp. Be sure that device will not fall while doing the montage. It is your responsibility if this equipment is used in a manner not specified in this instruction manual. 8 2.1 General Description Mounting Clamps Product Label Front Panel Ip65 protection NEMA 4X Panel surface (maximum thickness 5mm / 0.2 inch) 2.2 Dimensions Maximum 5mm / 0.2 inch ESM-4420 °F PS PO AO1 AS1 AO2 AS2 Temperature Controller PSET 48 mm/ 1.89 inch °C ASET P 48 mm/ 1.89 inch 11 ± 1 mm /0.43 inch 84 mm / 3.31 inch 9 2.3 Panel Cut-Out 46 mm / 1.81 inch (min) 65 mm / 2.56 inch (min) 65 mm / 2.56 inch (min) 46 mm / 1.81 inch (min) 10 2.4 Environmental Ratings Operating Conditions Operating Temperature : 0 to 50 °C Max. Operating Humidity : 90% Rh (non-condensing) Altitude c : Up to 2000m. Forbidden Conditions: Corrosive atmosphere Explosive atmosphere Home applications (The unit is only for industrial applications) 2.5 Panel Mounting 1 1-Before mounting the device in your panel, make sure that the cut-out is of the right size. 2-Check front panel gasket position 3-Insert the device through the cut-out. If the mounting clamps are on the unit, put out them before inserting the unit to the panel. 3 2 c During installation into a metal panel, care should be taken to avoid injury from metal burrs which might be present. The equipment can loosen from vibration and become dislodged if installation parts are not properly tightened. These precautions for the safety of the person who does the panel mounting. 11 2.6 Installation Fixing Clamp The unit is designed for panel mounting. 2 1 1-Insert the unit in the panel cut-out from the front side. 2- Insert the mounting clamps to the holes that located top and bottom sides of device and screw up the fixing screws until the unit completely immobile within the panel c Montage of the unit to a system must be done with it’s own fixing clamps. Do not do the montage of the device with inappropriate fixing clamps. Be sure that device will not fall while doing the montage. 2.7 Removing from the Panel c Before starting to remove the unit from panel, power off the unit and the related system. 2 1 1-Loosen the screws. 2-Pull mounting clamps from top and bottom fixing sockets. 3-Pull the unit through the front side of the panel 3 12 3.Electrical Wirings c c c c You must ensure that the device is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. It is your responsibility, as the installer, to ensure that the configuration is correct. Parameters of the device has factory default values. These parameters must be set according to the system’s needs. Only qualified personnel and technicians should work on this equipment. This equipment contains internal circuits with voltage dangerous to human life. There is severe danger for human life in the case of unauthorized intervention. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure. Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented. 3.1 Terminal Layout and Connection Instructions Max. 2.5mm / inch Wire Size: 14AWG/1mm² Solid /Stranded Torque 0.5 Nm a Screw driver 0.8x3mm 13 3.2 Electrical Wiring Diagram c Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’ below to prevent damage to the process being controlled and personnel injury. Universal Temperature Measurement Input (TC, RTD) Pt-100 TC 1 3 2 PROCESS OR ALARM OUT-2 5A@250VV NO C 8 Note-1 9 (-) Process Output or Alarm Output-2 Relay or Optional SSR Output (It must be determined in order.) cY CAT II ALARM OUT-1 5A@250V V NC C NO 6 7 (+) (-) P/N : ESM-4420 a 10 11 12 13 14 (+) N Note-1 Output-3 SSR Output ( Process Output ) L Supply Voltage Input 230V V ( ± 15% ) 50/60Hz - 3VA 115V V ( ± 15% ) 50/60Hz - 3VA 24V V ( ± 15% ) 50/60Hz - 3VA Alarm Output-1 Relay 24V W ( - 15%;+10% ) 50/60Hz - 3VA (It must be determined in order.) Note-1: Max. 12VZ , Max. 24mA for SSR Driver Output i Temperature measurement input is in CAT II class. 14 3.3 View of the Device Label 8 9 NO 10 C 11 NC C 12 13 14 NO N 5A@250VV PROCESS OUT or ALARM OUT-2 ca Y 5A@250VV ALARM OUT-1 P/N : ESM-4420 CAT II SSR DRIVER OUT Max. 24 mA, 12VZ + TC 2 3 4 5 6 _ Pt-100 1 L 230VV ± 15% 50/60 Hz - 3VA 7 15 3.4 Supply Voltage Input Connection of the Device Connection of Supply Voltage Input Y aL 14 Note-1 N 13 External Fuse (1 A V T) Power Supply Switch c Supply Voltage 230 V V (± 15%) 50/60 Hz or 115 V V (± 15%) 50/60 Hz or 24 V V (± 15%) 50/60 Hz 24V W ( - 15%;+10% ) 50/60Hz Note-1: External fuse is recommended. c c c c c Make sure that the power supply voltage is the same indicated on the instrument. Switch on the power supply only after that all the electrical connections have been completed. Supply voltage range must be determined in order. Device is produced different for low and high voltage. While installing the unit, supply voltage range must be controlled and appropriate supply voltage must be applied to the unit. Controlling prevents damages in unit and system and possible accidents as a result of incorrect supply voltage. There is no power supply switch or fuse on the device. So the user must put power supply switch and a fuse to the supply voltage input. In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument. Power supply switch and fuse must be put to a place where user can reach easily. Power supply switch must be two poled for seperating phase and neutral. On/Off condition of power supply switch is very important in electrical connection. On/Off condition of power supply switch must be signed for preventing the wrong connection. External fuse must be on phase connection in Vsupply input. External fuse must be on (+) line connection in Zsupply input. 16 3.5 Process Input Connection 3.5.1 TC (Thermocouple) Connection TC Connect the wires with the polarity as shown in the figure left. 1 2 3 i Always use compensation wire corresponding to the thermocouple used. If present, the shield must be connected to a proper ground. i Input resistance is greater than 10M W. 3.5.2 RTD Connection Pt-100 Pt-100 Note 2 Note 1 1 2 3 3-wire Pt-100 connection (with line compensation) (Max. Line impedance is 10 W) 1 2 3 2-wire Pt-100 connection (without line compensation) Note 1 : In 3-wire system, use always cables of the same diameter (min 1mm²) Always use wires of the same gauge and type whether a 2-wire or 3-wire system. Note 2 : Install a jumper between terminals 2 and 3 when using a 2-wire RTD. Note 3 : If the distance is longer than 10 meters, use 3-wire system i Input resistance is greater than 10M W. 17 3.6 Galvanic Isolation Test Values of ESM-4420 Temperature Controller 2000V V ( For ESM-4420.5..... ) 500V V ( For ESM-4420.3..... ) Supply Voltage 13 Ground 14 2000V V 8 9 10 2000V V 9 10 Process Output or Alarm Output-2 (Relay) Process Output or Alarm Output-2 (SSR Driver) 8 1 2000V V 9 10 9 10 2000V V 2000V V 11 12 Alarm Output-1 (Relay) 11 12 2000V V 6 7 Process Output (SSR Driver) 6 7 2000V V 2 3 Analog Inputs 2 3 18 4. Output Connection Forms in ESM-4420 Temperature Controller 4.1 Process Output or Alarm Output-2 ( Relay ) Connection L N Device 5A V T Fuse C 9 NC 10 Last Control Element (Contactor) NO 8 c Fuse Load c Fuses must be selected according to the application. 4.2 Process Output or Alarm Output-2 ( SSR Driver ) Connection Device 9 L N Last Control Element (SSR) 10 Max. 12 V Z, Max. 24 mA c Fuse c Load Fuses must be selected according to the application. 19 4.3 Alarm Output-1 ( Relay ) Connection L N Device C 5A V T Fuse 11 Last Control Element (Contactor) NO 12 c Fuse Load c Fuses must be selected according to the application. 4.4 Process Output ( SSR Driver ) Connection Device 7 L N Last Control Element (SSR) 6 c Max. 12 V Z, Max. 24 mA c Fuse Load Fuses must be selected according to the application. 20 5. Front Panel Definition and Accessing to the Menus 5.1 Front Panel Definition LED indication of °C:Centigrade Unit LED indication of °F Fahrenheit Unit ESM-4420 Process Output Status Led Displays Process Value (PV) and Parameter °C °F Alarm Output Status Leds PS , Process Set Value LED AS1 , Alarm-1 Set Value LED AS2 , Alarm-2 Set Value LED PO PS AO1 AS1 AO2 AS2 Displays Set Value, Parameter Temperature Controller PSET ASET P Please refer to Section 6.1 for detailed information; Section 6.1 (Process and Alarm Set Parameters) This button is used to access to the process set value. If it is pressed for 5 seconds continuously programming section is entered. Note-1 This button is used to decrase the parameter values, access to the program menus This button is used to access to the alarm set value and use as OK button. Note-1 This button is used to increase the parameter values and access to the program menus Note-1: If increment or decrement button is pressed for 5 seconds continuously, increment and decrement number become 10, if increment or decrement button is pressed for 10 seconds continuously, increment and decrement number become 100. 21 5.2 Run the Device and Observation of Software Version on the Displays When the power is applied to the device all led indicators and display segments are momentarily illuminated for testing. Software revision number of the controller on the bottom display is momentarily illuminated. ESM-4420 °C °F PO PS AO AS Temperature Controller “ rU” Þ Revision Revision number PSET ASET P When power on, display of the indicator is like below: ESM-4420 ESM-4420 ESM-4420 °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS Temperature Controller PSET ASET P Temperature Controller PSET ASET P First segments of top and bottom displays are tested Temperature Controller PSET Second segments of top and bottom displays are tested. ESM-4420 Third segments of top and bottom displays are tested. ESM-4420 ESM-4420 °C °C °C °F °F °F PO AO PS PO AS Temperature Controller PSET ASET P c PS AO1 AS1 AO2 AS2 Temperature Controller PSET ASET P Fourth segments of top and bottom displays are tested. ASET P Revision number is shown. All leds are energised. PO PS AO AS Temperature Controller PSET ASET P Main operation screen is shown If there is an unexpected situation while opening the device, power off the device and inform a qualified personnel. 22 5.3 Adjustment of Process SET Value Operation Screen °C °F Process Set Screen °C °F °C °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P When PSET button is pressed, PS led starts to blink, the information to indicate which set is shown is on top display, process set value is shown on bottom display. Change the process set value with increment and decrement buttons. Press PSET button to exit without saving the process set value. Operation Screen °C °F Operation Screen °F PS PO PS AO AS AO AS ASET Press ASET/OK button for saving process set value. °C PO PSET PSET P ASET P ASET Value, can be adjusted from process set low limit To process set high limit . P 5.4 Adjustment of Alarm SET Value Operation Screen °C °F Alarm Set Screen °C °F °C °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET P PSET When ASET button is pressed, AS led starts to blink, the information to indicate which set is shown is on top display, alarm set value is shown on bottom display. value can be adjusted from alarm set low limit Operation to alarm set high limit . Screen value can be adjusted from alarm set low limit to alarm set high limit . ASET PSET P ASET P Press PSET button to exit without saving the alarm set value. Change alarm set value with increment and decrement buttons. °C °F PO PS AO AS PSET Press ASET/OK button for saving process set value. ASET P 23 6. Parameters 6.1 Parameter List Process menu title Process input type selection ( Default Value = J Type (FE.C.n) ) J type (Fe,Cu,Ni) Thermocouple, -200°C,900°C or -328°F,1652°F K type (Ni,Cr,Ni) Thermocouple , -200°C,1300°C or -328°F,2372°F R type (Pt13%RhPt) Thermocouple , 0°C,1700°C or 32°F,3092°F S type (Pt10%RhPt) Thermocouple, 0°C,1700°C or 32°F,3092°F T type (Cu,Cu,Ni) Thermocouple , -200°C,400°C or -328°F,752°F Pt - 100 , -200°C,650°C or -328°F,1202°F Pt - 100 , -199.9°C,650.0°C or -199.9°F,999.9°F Unit Selection ( Default Value = °C ) Unit is °C Unit is °F Operation scale Low Limit. Minimum Operation scale is defined with this parameter. It changes according to process input type and scale. ( Default Value = -200 ) Operation scale High Limit. Maximum Operation scale is defined with this parameter. It changes according to process input type and scale. ( Default Value = 900 ) Process Set Low Limit. Minimum process set value is defined with this parameter. It changes according to process input type and scale. ( Default Value = -200 ) Process Set High Limit. Maximum process set value is defined with this parameter. It changes according to process input type and scale. ( Default Value = 900 ) Display offset for process value. It can be adjusted from -10% of scale ( PuPL- PLoL ) to 10% of scale( PuPL- PLoL ). It is added to the process display value. ( Default Value = 0 ) Control menu title Process Type selection ( Default Value = Heat ) Process type is heating Process type is cooling Process Control Type selection ( Default Value = on.oF ) Process Control form is ON/OFF Process Control form is PID 24 Tune parameter ( Default Value = no ) This parameter can be observed if CntS parameter is Pýd Proportional Band . It can be adjusted from 1.0% to 100.0%.( Default Value = 10.0 ) If process control type selection CntS = Pýd, then this parameter can be observed. Integral Time. It can be adjusted from 0 to 3600 secs. If process control type selection CntS = Pýd, then this parameter can be observed ( Default Value = 100 ) Derivative Time. It can be adjusted from 0.0 to 999.9 secs. If process control type selection CntS = Pýd, then this parameter can be observed ( Default Value = 25.0 ) Output Control period. It can be adjusted from 1 to 150 seconds. If process control type selection CntS = Pýd, then this parameter can be observed ( Default Value = 10 ) Hysteresis value. If Process Control Type selection CntS = on.oF, then this parameter can be observed. It can be adjusted from 0% of defined scale ( PuPL- PLoL ) to 50% of defined scale ( PuPL- PLoL ).( Default Value = 0 ) Sensor Break output value. It can be adjusted from %0.0 to %100.0 (Default value = 0.0) When sensor breaks, controlling of the process can continue by this %output value. Process Output Selection parameter. This parameter determines, which output will be Proces Control Output. If rLY is chosen, process ouput is relay output(Output-1). If Ssr is chosen, process output is ssr output(Output-3) and Output-1 will be alarm-2 output. (Default = rLY ) Soft Start Set value. It can be adjusted from 0 to 9999. This parameter determines to end point set value of the soft start operation. ( Default value = 0 ) Soft Start Control output. It can be adjusted from %10.0 to %90.0 (Default value = 10.0) This value determines Soft Start control output percentage. Soft Start Control period. It can be adjusted from 0 to 100 sec. This value determines Soft Start control period. ( Default value = 0 ) Alarm menu title Alarm-1 Hysteresis value. It can be adjusted from 0% of defined scale ( AuP1- ALo1 ) to 50% of defined scale ( AuP1- ALo1 ). ( Default Value = 0 ) Alarm-1 Type selection ( Default Value = PHýA (Process High Alarm) ) Alarm-1 Set Value Low Limit. Minimum value of the alarm set value is defined in this parameter. It can be adjusted from operation scale low limit parameter to alarm set high limit parameter. It changes according to process input type and scale( Default Value = 0 ) Alarm-1 Set High Limit. Maximum value of the alarm set value is defined in this parameter. It can be adjusted from alarm set low limit parameter to operation scale high limit parameter.It changes according to process input type and scale( Default Value = 500 ) Alarm-1 on delay time. It can be adjusted from 0 to 9999 seconds. ( Default Value = 0 ) Alarm-1 off delay time. It can be adjusted from 0 to 9998 seconds. When it is higher than 9998, “LtCH” is shown and alarm latching output is selected. To make the alarm latching output passive, decrement button must be pressed in main operation screen. ( Default Value = 0 ) 25 Alarm-2 Hysteresis value. It can be adjusted from 0% of defined scale ( AuP2 - ALo2 ) to 50% of defined scale ( AuP2- ALo2 ). ( Default Value = 0 ) Alarm-2 Type selection ( Default Value = PHýA (Process High Alarm) ) Alarm-2 Set Value Low Limit. Minimum value of the alarm set value is defined in this parameter. It can be adjusted from operation scale low limit parameter to alarm set high limit parameter. It changes according to process input type and scale( Default Value = 0 ) Alarm-2 Set High Limit. Maximum value of the alarm set value is defined in this parameter. It can be adjusted from alarm set low limit parameter to operation scale high limit parameter.It changes according to process input type and scale( Default Value = 500 ) Alarm-2 on delay time. It can be adjusted from 0 to 9999 seconds. ( Default Value = 0 ) Alarm-2 off delay time. It can be adjusted from 0 to 9998 seconds. When it is higher than 9998, “LtCH” is shown and alarm latching output is selected. To make the alarm latching output passive, decrement button must be pressed in main operation screen. ( Default Value = 0 ) Protection menu title Password for accessing to the programming section. It can be adjusted from 0 to 9999. ( Default Value = 0 ) 26 6.2 Easy Access Diagram of Parameters Main Operation Screen Password Entering Screen After 5secs °C °C °C °C °C °F °F °F °F °F PO PS PO PS PO PS PO PS PO PS AO AS AO AS AO AS AO AS AO AS PSET PSET P P For entering to the programming section, press PSET/P button for 5 seconds. Process menu °C °F ASET ASET Password entering screen is shown when ASET/OK Button is pressed. Control menu °C °F Alarm menu °C °F PO PS PO PS PO PS AO AS AO AS AO AS ASET Process Input Type selection °C °F PO PS ASET °F °F PO PS PO PS AO AS AO AS AO AS °F PO PS PO PS AO AS ASET ASET ASET Process Control Type Selection °C °C °C °F °F °F °F PO PS PO PS PO PS PO PS AO AS Operation Scale Low Limit AO AS AO AS ASET ASET ASET Hysteresis Value Tune parameter °C °C °F ASET Alarm Type selection °C AO AS Programming Section Entering Password °F AO AS ASET ASET °C °C AO AS Unit Selection °F PO PS Alarm Hysteresis Value °C Protection Menu °C ASET Process Type Selection °C Press ASET/OK button for entering to the menus. Enter the password with increment or decrement buttons. ASET Alarm Low Limit °F °C °C °F PO PS AO AS PO PS AO AS PO PS °F AO AS PO PS ASET ASET Operation Scale High Limit °C °F Sensor break output °C ASET ASET Proportional Band °F °C °F AO AS PO PS °F AO AS PO PS °C ASET AO AS ASET Proses set value Low Limit Alarm High Limit PO PS PO PS ASET AO AS Process Output Sel. AO AS ASET Integral Time °C °C °F °F PO PS PO PS AO AS AO AS Alarm On Time °C °F PO PS AO AS °C °F ASET ASET PO PS AO AS ASET Proses set value High Limit Soft Start Set value Derivative Time ASET °C °F Alarm Off time °C PO PS °F °C AO AS PO PS °F NOTE : If Process Output Selection Cout is SSr, then Alarm-2 parameters can be observed. °C ASET AO AS °F PO PS AO AS PO PS ASET ASET Process Offset Value Control Period Soft Start output value °C °C °F °F PO PS PO PS AO AS AO AS AO AS °C ASET °F PO PS Soft Start control per. AO AS °C ASET °F PO PS ASET ASET AO AS ASET 27 6.3 Entering to the Programming Section and Process Menu Operation Screen °C °F °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P Press PSET/P button for 5 seconds for entering programming section ASET P When 5secs is expired, programming section entering screen is shown. Programming Section Entering Screen Press ASET/OK button for accessing to the password entering screen. °C °F PO PS AO AS PSET ASET P If password for entering to the programming section is defined, password entering screen is shown. °C °F PO PS AO AS PSET ASET P Enter the password with increment or decrement buttons. Press ASET/OK button for entering to the menus. Protection Menu Process Menu When screen is shown, parameters can be observed by pressing ASET/OK button without entering the password. But no changes can be done with the parameters. Please refer to Section 6.6 (Protection Menu) for detailed information Control Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET P ASET PSET P Former menu can be accessed by pressing left arrow button. ASET PSET ASET P Following menu can be access by pressing right arrow button. Press ASET/OK button for accessing to the Process Menu. 28 Process Input Type Selection Process Input Type can be changed into any of the type which are listed below with increment and decrement buttons. °C °F PO PS AO AS PSET ASET P : J type (Fe,Cu,Ni)Thermocouple, -200°C,900°C or -328°F,1652°F : K type (Ni,Cr,Ni)Thermocouple , -200°C,1300°C or -328°F,2372°F : R type (Pt13%RhPt) Thermocouple, 0°C,1700°C or 32°F,3092°F : S type (Pt10%RhPt) Thermocouple, 0°C,1700°C or 32°F,3092°F : T type (Cu,Cu,Ni)Thermocouple , -200°C,400°C or -328°F,752°F : Pt - 100 , -200°C,650°C or -328°F,1202°F : Pt - 100 , -199.9°C,650.0°C or -199.9°F,999.9°F Press ASET/OK button for saving the changes and accessing to the following parameter. Unit selection °C °F Unit can be selected PO PS AO AS PSET ASET P or by increment and decrement buttons. Press ASET/OK button for saving the changes and accessing to the following parameter. Operation Scale Low Limit °C °F PO PS AO AS Minimum value of the operation scale value can be adjusted with this parameter. It can be adjusted from process input type minimum value to operation scale high limit parameter value. It changes according to the process input type and scale. P Press ASET/OK button for saving the changes and accessing to the following parameter. °C Operation Scale High Limit PSET ASET °F PO PS AO AS PSET P ASET Maximum value of the operation scale value can be adjusted with this parameter. It can be adjusted from operation scale low limit parameter to process input type maximum value. It changes according to the process input type and scale. Press ASET/OK button for saving the changes and accessing to the following parameter. 29 Process Set value Low Limit °C °F PO PS AO AS PSET Minimum value of the process set value can be adjusted with this parameter. It can be adjusted from oparetion scale low limit value to process high limit parameter value. It changes according to the process input type and scale. ASET P Press ASET/OK button for saving the changes and accessing to the following parameter. °C Process Set value High Limit °F PO PS AO AS PSET ASET P Maximum value of the process set value can be adjusted with this parameter. It can be adjusted from process low limit parameter to operation scale high limit value. It changes according to the process input type and scale. Press ASET/OK button for saving the changes and accessing to the following parameter. Process Value Display Offset °C °F PO PS AO AS PSET It can be adjusted -10% of scale( PuPL- PLoL ) to 10% of scale( PuPLPLoL ). Defined value is added to the process display value. ASET P Operation Screen Press ASET/OK button for saving the changes and accessing to the following parameter. Process Menu Control Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET P ASET PSET P Press PSET/P for exiting menu list and turn to operation screen. ASET PSET ASET P Following menu can be accessed by pressing right arrow button. 30 6.4 Control Menu Operation Screen °C °F °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P Press PSET/P button for 5 seconds for entering programming section ASET P When 5secs is expired, programming section entering screen is shown. Programming Section Entering Screen Press ASET/OK button for accessing to the password entering screen. °C °F PO PS AO AS PSET ASET P If password for entering to the programming section is defined, password entering screen is shown. °C °F PO PS AO AS PSET Press ASET/OK button for entering to the menus. Enter the password with increment or decrement buttons. Protection Menu ASET P Process Menu When screen is shown, parameters can be observed by pressing ASET/OK button without entering the password. But no changes can be done with the parameters. Please refer to Section 6.6 (Protection Menu) for detailed information Control Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET P PSET P Former menu can be accessed by pressing left arrow button. ASET PSET ASET P Following menu can be access by pressing right arrow button. Press ASET/OK button for accessing to the Process Menu. 31 Process Type Selection °C °F PO PS AO AS PSET Process Type Selection can be selected decrement buttons. ASET P PO PS AO AS PSET ASET P °C °F PO PS AO AS PSET P °C Process Control Type can be selected or with increment and decrement buttons. °F ASET with increment and Press ASET/OK button for saving the parameter and accessing to the next parameter. Process Control Type Selection °C or °F Press ASET/OK button for saving the parameter and accessing to the next parameter. PO PS AO AS PSET ASET P Hysteresis Value P r o c e s s C o n t r o l Ty p e selection.If = ,then this parameter can be observed.It can be adjusted from 0% of full scale (PuPLPLoL) to 50% of full scale (PuPL-PLoL) with increment and decrement buttons. °C °F PO PS AO AS PSET ASET P Press ASET/OK button for saving the parameter and accessing to the next parameter. °F PO PS AO AS PSET P Tune Parameter Tune operation can be started and stopped with increment and decrement buttons. If Process Control Type is Then this parameter can be observed. Proportional Band °C Proportional band can be adjusted from 1.0% to 100.0% with increment and decrement buttons. If Process Control Type selection = , then this parameter can be observed. For example ; If = 1000°C, = 0°C and = 50.0 Proportional Band = ( )* /100.0 Proportional Band = ( 1000 - 0 ) * 50.0 /100.0 = 500 °C Press ASET/OK button for saving the parameter and accessing to the next parameter. ASET Press ASET/OK button for saving the parameter and accessing to the next parameter. 31 32 Integral Time °C °F PO PS AO AS PSET It can be adjusted from 0 to 3600 seconds with increment and decrement buttons.If Process Control Type selection = , then this parameter can be observed. ASET P Press ASET/OK button to save the value and access to the next parameter. Derivative Time °C °F PO PS AO AS PSET It can be adjusted from 0.0 to 999.9 seconds. If Process Control Type selection = , then this parameter can be observed. ASET P Press ASET/OK button to save the value and access to the next parameter. Output Control Period °C °F PO PS AO AS It can be adjusted from 1 to 150 with increment and decrement buttons. If Process Control Type selection = , then this parameter can be observed. Press ASET/OK button for saving the parameter and accessing to the next parameter. OUTPUT : ON PSET ASET P OUTPUT PERIOD °C OUTPUT PERIOD °C Sensor Break Output °F PO PS AO AS PSET Relay Output : Output period must be short for stable process control. Relay must not be used in short output periods because of limited life of their relay contact (number of open/close events). Relay output must be used as control output in values near to 30 seconds or greater than this value. SSR Output : If short output period is needed in a system (approximately 1-2 seconds) SSR driver output module as last control Process Output Selection °F It can be adjusted from %0 to %100 with increment and decrement buttons. PO PS AO AS PSET ASET Process Output Selection Type can be selected rLY or SSr with increment and decrement buttons. ASET P P °C °C Soft Start Set value °F PO PS AO AS PSET ASET P Soft Start Control Output °F It can be adjusted from 0 to 9999 with increment and decrement buttons. When the device power on, if the Soft start set value different from “0”, and temperature value is lower than soft start value on heating processes, device starts soft start operation, until temperature reaches soft start set value. On soft start device output period is SSCt parameter value and device control output is SSCo parameter value. PO PS AO AS PSET It can be adjusted from %10 to %90 with increment and decrement buttons. ASET P °C Soft Start Control Period °F PO PS AO AS PSET It can be adjusted from 0 to 100 sec with increment and decrement buttons. ASET P Control Menu Process Menu Alarm Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET PSET ASET ASET P P Former menu can be accessed by pressing left-arrow button. PSET ASET P Next menu can be accessed by pressing right-arrow button. Press PSET/P button to exit from menu list and turn to the operation screen. 33 6.5 Alarm Menu Operation Screen °C °F °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P Press PSET/P button for 5 seconds for entering programming section ASET P When 5secs is expired, programming section entering screen is shown. Programming Section Entering Screen Press ASET/OK button for accessing to the password entering screen. °C °F PO PS AO AS PSET ASET P If password for entering to the programming section is defined, password entering screen is shown. °C °F PO PS AO AS PSET Press ASET/OK button for entering to the menus. Enter the password with increment or decrement buttons. Protection Menu ASET P Process Menu When screen is shown, parameters can be observed by pressing ASET/OK button without entering the password. But no changes can be done with the parameters. Please refer to Section 6.6 (Protection Menu) for detailed information Control Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET P PSET P Former menu can be accessed by pressing left arrow button. ASET PSET ASET P Following menu can be access by pressing right arrow button. Press ASET/OK button for accessing to the Process Menu. 34 Alarm Menu °C °F PO PS AO AS PSET ASET P Press ASET/OK button for accessing to the alarm menu. Alarm-1 Hysteresis value °C °F It can be adjusted from 0% of ( AuP1- ALo1 ) to 50% of ( AuP1- ALo1 ). PO PS AO AS P Press ASET/OK button for saving the changes and accessing to the following parameter. °C Alarm-1 Type Selection PSET ASET °F It can be adjusted to the values listed below: PO PS AO AS PSET ASET P : Process High Alarm : Process Low Alarm : Deviation High Alarm : Deviation Low Alarm : Deviation Band Alarm : Deviation Range Alarm : Deviation Range High Alarm Please refer to Section 7.2 Alarm Types for detailed information Press ASET/OK button for saving the changes and accessing to the following parameter. Alarm-1 Set Low Limit Value °C °F PO PS AO AS PSET P Minimum value of the alarm set is defined with this parameter. It changes according to the process type and scale. It can be adjusted from operation scale low limit parameter to alarm set high limit parameter value. ASET Press ASET/OK button for saving the changes and accessing to the following parameter. 35 Alarm-1 Set High Limit Value °C °F PO PS AO AS PSET Maximum value of alarm set is defined with this parameter. It can be adjusted from alarm set low limit parameter to operation scale high limit parameter . It changes according to process input type and scale. ASET P Press ASET/OK button for saving the changes and accessing to the following parameter. °C Alarm-1 On Delay Time °F PO PS AO AS PSET It can be adjusted from 0 to 9999 seconds with increment and decrement buttons. ASET Alarm Status OFF Delay P On Delay Alarm Output Press ASET/OK button for saving the changes and accessing to the following parameter. Alarm-1 OFF Delay Time °C °F PO PS AO AS PSET ASET P It can be adjusted from 0 to 9998 seconds. When it is higher than 9998, is shown and alarm latching output is selected.To make the alarm latching output passive, decrement button must be pressed in main operation screen. Press ASET/OK button for saving the changes and accessing to the following parameter. Control Menu Protection Menu Alarm Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET P Former menu can be accessed by pressing left arrow button. PSET P ASET PSET ASET P Following menu can be access by pressing right arrow button. Press ASET/OK button for Press PSET/P for exiting menu list and turn to operation screen. accessing to the Process Menu. NOTE : If Process Output Selection Cout is SSr, after Alarm-1 parameters, Alarm-2 parameters can be observed. 36 6.6 Protection Menu Operation Screen °C °F °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P Press PSET/P button for 5 seconds for entering programming section ASET P When 5secs is expired, programming section entering screen is shown. Programming Section Entering Screen Press ASET/OK button for accessing to the password entering screen. °C °F PO PS AO AS PSET ASET P If password for entering to the programming section is defined, password entering screen is shown. °C °F PO PS AO AS PSET Press ASET/OK button for entering to the menus. Enter the password with increment or decrement buttons. Protection Menu ASET P Process Menu When screen is shown, parameters can be observed by pressing ASET/OK button without entering the password. But no changes can be done with the parameters. Please refer to Section 6.6 (Protection Menu) for detailed information Control Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET P Press ASET/OK button for accessing to the protection menu. ASET PSET P Former menu can be accessed by pressing left arrow button. ASET PSET ASET P Following menu can be accessed by pressing right arrow button. 37 Programming Section Entering Password °C °F PO PS AO AS PSET It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is 0, programming section is accessed without entering the password. ASET P Press ASET/OK button for saving the parameter and exiting from protection menu parameters. If it is different from 0, in programming section entering password; 1- If user enters the password incorrect: Device turns to main operation screen without being able to see the parameters 2- If user press the ASET/OK button without entering the password for entering to the programming section (observation of the parameters): All menus and parameters except protection menu ( ) can be observed but they can not be changed. (Please refer to Section 8. Failure Messages in ESM-4420 Temperature Controller(4)) Alarm Menu Process Menu Protection Menu °C °C °C °F °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET P PSET ASET PSET P ASET P Following menu can be access by pressing right arrow button. Former menu can be accessed by pressing left arrow button. Press PSET/P for exiting menu list and turn to operation screen. Operation Screen °C °F PO PS AO AS PSET ASET P 38 7. General Information 7.1 Tune Operation Esm-XX20 devices use Self Tune (Step Response Tuning) method to automatically determine PID parameters. Starting the Tune operation by the user ! Enter to the programming section ! Select the parameter in menu, ! Observe that is blinking in set display Operation Screen °C °F and turn to main operation screen. °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET PSET P Press PSET/P button for 5 seconds for entering programming section ASET P When 5secs is expired, programming section entering screen is shown. Programming Section Entering Screen Press ASET/OK button for accessing to the password entering screen. °C °F PO PS AO AS PSET P ASET If password for entering to the programming section is defined, password entering screen is shown. °C °F PO PS AO AS PSET ASET P Press ASET/OK button for entering to the menus. Enter the password with increment or decrement buttons. Control Menu Process Menu Following menu can be accessed by pressing right arrow button. When screen is shown, parameters can be observed by pressing ASET/OK button without entering the password. But parameters can not be changed. Please refer to Section 6.6 (Protection Menu) for detailed information °C °C °F °F PO PS PO PS AO AS AO AS PSET P ASET PSET ASET P Press ASET/OK button for accessing to the Control Menu 39 Process Control Type Selection Process Type Selection °C °F PO PS AO AS PSET ASET °C °C °F °F PO PS PO PS AO AS AO AS PSET P ASET PSET P Press ASET/OK button for saving the parameter and accessing to the next parameter. ASET P Change Process Control Type as with increment button. Press ASET/OK button for saving the parameter and accessing to the next parameter. Proportional Band Tune Parameter °C °F °C °C °F °F PO PS PO PS PO PS AO AS AO AS AO AS PSET ASET PSET P ASET Change Tune Parameter as With increment button. °C °F °F PS PO PS AO AS AO AS ASET PSET Press PSET/P button to exit from the parameters section and turn to main operation screen. Operation Screen PO P ASET P Press ASET/OK button for saving the parameter. °C PSET PSET P “Tune” and PSET value is shown on the main operation screen following one another. ASET P Press PSET/P button to turn to the main operation screen. If Self Tune operation is finished without any problem, device saves new PID parameters to memory and runs. It changes parameter to Canceling Self Tune operation : 1- If sensor breaks ; 2- If Self Tune operation can not be completed in 8 hours ; 3- While Self Tune operation is running, if user changes process set value; Self Tune operation is canceled. Then device continues to run with former PID parameters without changing PID parameters. 40 If power is off while Self Tune operation continues, PID parameters and parameter are not changed. When power is off and then on, device starts to complete the Self Tune operation. If heating function and PID control form is selected for the system; If set value is greater than process value, process output becomes active till to the Temperature+[(Set - Temperature) / 2] value. When process value reaches to this value, process output reduces to 0% and it calculates the PID coefficients. Process Value PID coefficients are determined and system becomes stable Process Set Value ( ) TunE Start Value Start Value + [ ( Set - Start Value) ] 2 Time Process Output % 100 If cooling function and PID control form is selected for the system; If set value is less than process value, process output becomes active till to the Temperature - [( Temperature - Set ) / 2] value. When process value reaches to this value, process output is reduced to 0% and it starts to calculate PID coefficients. Process Value Start Value - [ ( Start Value - Set ) ] 2 TunE Start Value PID coefficient are determined Process Set Value ( ) Time Process Output % 100 i For starting Tune ( Step Response Tuning ) operation : 1- Control form must be P,PI,PD or PID. 2- For heating tune, Process Value must be 5% of full scale lower than process set value For cooling tune, process value must be 5% of full scale higher than process set value. 3- If Process Set Value is changed while Tune operation continues, tune operation is canceled. 41 7.2 Alarm Types Alarm types which are explained in Section 6.5 Alarm Types Selection parameter explained below: are Process High Alarm °C °F PO PS AO AS Alarm Output ON PSET ASET P OFF Process Value Process Low Alarm °C °F PO PS AO AS Alarm Output ON PSET ASET P OFF Process Value Deviation High Alarm °C °F PO PS AO AS PSET Alarm Output ( + ) ON ASET OFF P Process Value °C Deviation Low Alarm °F PO PS AO AS Alarm Output ( - ) ON PSET ASET P OFF Process Value 42 Deviation Band Alarm °C °F PO PS AO AS Alarm Output ( PSET ASET - ) ( + ) ON P OFF Process Value Deviation Range Alarm °C °F PO PS AO AS Alarm Output ( - ) ( + ) ON PSET ASET P OFF Process Value Deviation Range High Alarm °C °F PO PS AO AS Alarm Output ( - ) ON PSET ASET P OFF Process Value Note : If the one of , , , and these alarm types are selected, alarm set value can be decreased to zero with the decrement button even though alarm set low limit is negative value. 43 8. Failure Messages in ESM-4420 Temperature Controller 1- Sensor failure in analog inputs. Sensor connection is wrong or there is no sensor connection. °C °F PO PS AO AS PSET ASET P 2- If value that is read from the analog input is lower than process set low limit parameter , value on the top display starts to blink like on the picture. °C °F PO PS AO AS PSET ASET P For this example in = ; = i °F PS AO AS PSET ASET P °F PS AS PSET and PO PS AO AS PSET ASET P = menu ; = and °C °F PO PS AO AS PSET ASET P Please refer to Section 6.3 for detailed information about the parameter 4- If programming section entering password is different from “0” and user accesses to the parameter by ASET/OK button without entering the password and wants to change a parameter, the warning message is shown on the bottom display as shown on the left. Device does not allow to do any changes without entering the password correctly. °C AO = °F Please refer to Section 6.3 for detailed information about the parameter For this example in = ; = i PO menu ; 3- If value that is read from the analog input is higher than process set high limit parameter value , value on the top display starts to blink like on the picture. °C PO = °C ASET P 5- If user does not do anything for 120 seconds while device is on programming section, device turns to operation screen. °C °F PO PS AO AS PSET ASET P °F PO PS AO AS PSET ASET P 6- In programming section, when Tune operation is selected , if warning which is shown on the left blinks in operation screen for 10 seconds, it means that start conditions is not okay for Tune operation. °C °F PO PS AO AS PSET °C ASET P 44 9. Specifications Device Type Housing&Mounting : Temperature Controller : 48mm x 48mm x 95mm 1/16 DIN 43700 plastic housing for panel mounting. Panel cut-out is 46x46mm. Protection Class : NEMA 4X (IP65 at front, IP20 at rear). Weight : Approximately 0.22 Kg. Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters with none condensing humidity. Storage/Operating Temperature : -40 oC to +85 oC / 0 oC to +50 oC Storage/Operating Humidity : 90 % max. (None condensing) Installation : Fixed installation Overvoltage Category : II Pollution Degree : II, office or workplace, none conductive pollution Operating Conditions : Continuous Supply Voltage and Power : 230 V V (±15%) 50/60 Hz. 3VA 115 V V (±15%) 50/60 Hz. 3VA 24 V V (±15%) 50/60 Hz. 3VA 24 V W (-15%;+10%) 50/60 Hz. 3VA Process Inputs : Universal input TC, RTD Thermocouple input types : Selectable by parameters J ,K ,R ,S ,T (IEC584.1)(ITS90) Thermoresistance input type : PT 100 (IEC751) (ITS90) Accuracy : ± 0,25% of full scale for Thermocouple and Thermoresistance Cold Junction Compensation : Automatically ± 0.1°C/1°C. Line Compensation : Maximum 10 W . Sensor Break Protection : Upscale Sampling Cycle : 3 samples per second Input Filter : 1.0 second Control Forms : Programmable ON / OFF, P, PI, PD or PID. Relay Outputs : 2 pieces. Resistive load 5A@250V V (Programmable control or alarm output) (Electrical Life : 100.000 Operation (Full Load)) SSR Driver Output : Max. 12VZ, Max. 24mA Optional SSR Driver Output : Max. 12VZ, Max. 24mA Process Display : 10.1 mm Red 4 digits LED display Set Display : 8 mm Green 4 dijit LED display LED Indicators : PS ( Process Set Value), AS1 ( Alarm-1 Set Value), AS2 (Alarm-2 Set Value), PO ( Process Output ) , AO1 ( Alarm-1 Output ), AO2 ( Alarm-2 Output ), °C ve °F unit leds Approvals : GOST-R, 45 10. Other Informations Manufacturer Information: Emko Elektronik Sanayi ve Ticaret A.Þ. Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone : +90 224 261 1900 Fax : +90 224 261 1912 Repair and Maintenance Service Information: Emko Elektronik Sanayi ve Ticaret A.Þ. Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone : +90 224 261 1900 Fax : +90 224 261 1912 Thank you very much for your preference to use Emko Elektronik Your Technology Partner Products. www.emkoelektronik.com.tr 46