TITLE Modbus register for standard Easy2/Easy3 DOC. Ner Revision 0 1 2 KJA00091G Date 10/01/2000 21/11/14 07/03/19 Name Description Issue Changed Piovan Logo Changed Piovan Logo I.M. A.C. A.C. Code and firmware requirements table Serial card code FW main card code FW 2.15 HMI card Code Absolute addressing table USER VERSION KJA00091G _Easy2_Easy3_User_Version_R2 FW Register N° (dec) Description HMI-Ref. Type Mode Dec. Points Min Max Eng. Units Note WF Ready Bios >=FW Modbus Supported function CODE: Function code &H03 &H04 &H06 &H16 Description Read Holding registers Read Input registers Write single register Write multiple registers KJA00091G _Easy2_Easy3_User_Version_R2 Note Same effect as &H03 function code Compliance device Easy2/Easy3 Plant General Parameters table: Register N° (dec) 0 1 2 3 4 5 6 7 8 Description HMIRef. Keypad firmware version(secondary keypad) OR Alarms (1÷15) (secondary keypad) OR Alarms(16÷31) ( secondary keypad) Local/Remote control ( secondary keypad) Local Control Remote Control Horn reset ( secondary keypad) Alarms reset ( secondary keypad) Stand-by Units ( secondary keypad) b0: Plant 1 b1: Plant 2 b2: Plant 3 b3: Plant 4 b4: Plant 5 b5: Plant 6 b6: Plant 7 b7: Plant 8 b8: Reserved b9: Reserved b10: Reserved b11: Reserved b12: Reserved b13: Reserved b14: Reserved b15: Reserved Type Mode Dec. Points Min Max INT R 2 0 99.99 &Hex &Hex INT INT INT INT INT &Hex R R R/W W W W W R/W 0 0 0 0 0 0 0 0 0 FFFF 0 0 0 0 0 1 1 1 1 1 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Eng. Units Note WF Ready Bios >=FW (*19) (*19) (*20) (*21) (*22) (*23) (*24) (*25) (*25) (*25) (*25) (*25) (*25) (*25) (*25) Note: (*19) 0 = No active alarms >=1 active alarms Two Word used as Long Word: bit ‘n’ set to 1 means presence of alarms on element with address ‘n’ (compability with extended keypad old version). (*20) 0 = LOCAL 1 = REMOTE ( In the old protocol the register was only READ) (*21) 1 = LOCAL (OBSOLETE :kept only for compability) (*22) 1 = REMOTE (OBSOLETE :kept only for compability) (*23) Horn reset (*24) Alarm reset (*25) 0 = Plant bit ‘n’ running ; 1 = Plant bit ‘n’ in Stand-by KJA00091G _Easy2_Easy3_User_Version_R2 Compliance device Easy2/Easy3 Plant General Parameters table(cont.): Register N° (dec) Description 9 Generic Alarms (secondary keypad) b0: At least one Plant OFF( stand-by) b1: Too slaves detected b2: Reserved b3: Reserved b4: Reserved b5: Reserved b6: Reserved b7: Reserved b8: Reserved b9: Reserved b10: Reserved b11: Reserved b12: Reserved b13: Reserved b14: Reserved b15: Reserved Number of attempts before going OFFLINE ( secondary keypad) 10 HMIRef. Type Mode Dec. Points &Hex R 0 INT R/W 0 KJA00091G _Easy2_Easy3_User_Version_R2 Min Max 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 0101 0F0F Eng. Units Note WF Ready Bios >=FW Compliance device Easy2/Easy3 Plant General Parameters table(cont.): Register N° (dec) 901..948 Description HMIRef. Inputs status(secondary keypad) Type Mode Dec. Points &Hex R 0 bit0: INI1 ( digital output 1 status) bit1: INI2 ( digital output 2 status) bit2: INI3( digital output 3 status) bit3: Not used bit4: Station included bit5: Alarm check bit6: Station enable bit7: Blower(servo) Valid status only for single Station or Plant &Hex R &Hex R Max 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Eng. Units Note (*27) (*28) 0 bit8: Status output 4 bit9: Status output 4 bit10: Status output 3 bit11: Status output 3 bit12 Status output 2 bit13: Status output 2 bit14: Status output 1 bit15: Status output 1 Valid status only for Blower(servo) Min (*29) 0 bit8: Red Led Status bit9: Green LED Status bit10: Status output 4 bit11: Status output 3 bit12 Status output 2 bit13: Status output 1 bit14: Flash bit15: not significative Note: (*27) Check Alarm (NB: If Bit5 == 1 Bit4 == 0) (*28) Station enable(local button: se Bit6 == 0 locally excluded) (*29) 00=OFF ; 01=Swinging; 10==ON(active) ; 11=OFF (*30) Red and Green Leds blink KJA00091G _Easy2_Easy3_User_Version_R2 (*30) WF Ready Bios >=FW Compliance device Easy2/Easy3 Plant General Parameters table(cont.): Register N° (dec) 950…999 Description HMIRef. Alarm History ( secondary keypad) Type Mode Dec. Points Min Max INT R 0 0 FFFF Note (*31) 950 : Generic Alarms 951…..974 : Alarms Elements (MSB: station 2, LSB : station 1) … 975…..976 : Alarms CSA ID 50 977…..978 : Alarms CSA ID 51 979…..980 : Alarms CSA ID 52 981…..982 : Alarms CSA ID 53 983 : Alarms MGS ID 54 984 : Alarms MGS ID 55 985 : Alarms MGS ID 56 986 : Alarms MGS ID 57 987 : Alarms MGS ID 58 988 : Alarms MGS ID 59 989 : Alarms MGS ID 60 990 : Alarms MGS ID 61 991….999: Alarms CSM (concentrators A0..A7, duplicated) KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units Note (*31) WF Ready Bios >=FW Compliance device Esay2/Easy3 Plant Parameters table : see note (*32) Register N° (dec) Description +1 +2 +3 +4 Set time Stand-by blower Cycles number before filter cleaning Filter cleaning time Unit Alarms b0: Charge failure b1: Blower Thermal switch and/or vacuum breaker failure b2: Pressure switch b3: b4: b5: b6: b7: b8: Offline servo b9: OR Alarms Units element b10: b11: b12: b13: b14: b15: Blower status ( secondary keypad) Number of stations waiting for charging +5 +6 HMI-Ref. Type Mode Dec. Point s Min Max Eng. Units INT INT INT &Hex R/W R/W R/W R 0 0 0 0 0 0 0 999 99 999 s n s 0(off) 0(off) 1(on) 1(on) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0 0 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1 48 INT INT R R 0 0 Note: (*32) The absolute address of each Plant is computable in the following way: Ofs = N° Plant[1..8] * 1000 (*33) Excluded Silos and Manifolds (*34) 1= Blower running KJA00091G _Easy2_Easy3_User_Version_R2 Note (*33) (*34) WF Ready Bios >=FW Compliance device Esay2/Easy3 Plant Parameters table (cont.): Register N° (dec) Description +7 +8 Charging station (secondary keypad) Level Current sequence (secondary keypad) Stand –by Plant +9 HMI-Ref. Type Mode Dec. Points Min Max Eng. Units Note INT INT R R 0 0 0 0 48 200 n n (*35) (*36) INT R/W 0 0 1 n (*37 Note: (*35) 0= No station is charging (*36) 0÷100 = current sequence step (on loading station of the plant ) with flag ‘BUSY’ active 100÷200 = current sequence step (on loading station of the plant) without flag ‘BUSY’. (*37) 0 = Plant running ; 1 = Plant in Stand-by KJA00091G _Easy2_Easy3_User_Version_R2 WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table: ID 49(CSM) see note(*38) Register N° (dec) Description HMI-Ref. Type Mode +0 Module firmware version INT R +1 Receiver 1 Material code in use INT R +2 Receiver 2 Material code in use INT R +3 Receiver 3 Material code in use INT R 4 Receiver 4 Material code in use INT R +5 Receiver 5 Material code in use INT R +6 Receiver 6 Material code in use INT R +7 Receiver 7 Material code in use INT R +8 Receiver 8 Material code in use INT R +9 Receiver 9 Material code in use INT R +10 Receiver 10 Material code in use INT R +11 Receiver 11 Material code in use INT R +12 Receiver 12 Material code in use INT R +13 Receiver 13 Material code in use INT R +14 Receiver 14 Material code in use INT R +15 Receiver 15 Material code in use INT R +16 Receiver 16 Material code in use INT R +17 Receiver 17 Material code in use INT R +18 Receiver 18 Material code in use INT R +19 Receiver 19 Material code in use INT R +20 Receiver 20 Material code in use INT R +21 Receiver 21 Material code in use INT R +22 Receiver 22 Material code in use INT R +23 Receiver 23 Material code in use INT R +24 Receiver 24 Material code in use INT R +25 Receiver 25 Material code in use INT R +26 Receiver 26 Material code in use INT R +27 Receiver 27 Material code in use INT R +28 Receiver 28 Material code in use INT R +29 Receiver 29 Material code in use INT R Notes: (*38) ID 49 (CSM): Ofs = +9200 (*39) The value of this register returns the material code associated IMPORTANT: stations 1 to 48 are detected through CSM hardware connection Dec. Points Min Max 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 99.99 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units Note (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.): ID 49(CSM) Register N° (dec) Description HMI-Ref. +30 +31 +32 +33 +34 +35 +36 +37 +38 +39 +40 +41 +42 +43 +44 +45 +46 +47 +48 +49 +50 +51 +52 +53 +54 +55 +56 Receiver 30 Material code in use Receiver 31 Material code in use Receiver 32 Material code in use Receiver 33 Material code in use Receiver 34 Material code in use Receiver 35 Material code in use Receiver 36 Material code in use Receiver 37 Material code in use Receiver 38 Material code in use Receiver 39 Material code in use Receiver 40 Material code in use Receiver 41 Material code in use Receiver 42 Material code in use Receiver 43 Material code in use Receiver 44 Material code in use Receiver 45 Material code in use Receiver 46 Material code in use Receiver 47 Material code in use Receiver 48 Material code in use Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Alarms on Concentrator and Detector Type Mode Dec. Points Min Max INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT INT R R R R R R R R R R R R R R R R R R R R R R R R R R R 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF Note: (*40) These 8 registers indicates , concentrator (0÷7), alarms presence. bit0 = failure/offline detector 1 bit1 = failure/offline detector 2 ……. bit14 = failure/offline detector 15 KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units Note (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*39) (*40) (*40) (*40) (*40) (*40) (*40) (*40) (*40) WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.): ID 49(CSM) Register N° (dec) +57 Description HMIRef. CSM Alarms b0: not used b1: not used b2: not used b3:not used b4: not used b5: not used b6: not used b7: Manifold offline b8: Concentrator address 0 duplicated b9: Concentrator address 1 duplicated b10: Concentrator address 2 duplicated b11: Concentrator address 3 duplicated b12: Concentrator address 4 duplicated b13: Concentrator address 5 duplicated b14: Concentrator address 6 duplicated b15: Concentrator address 7 duplicated Type Mode Dec. Points &Hex R 0 KJA00091G _Easy2_Easy3_User_Version_R2 Min Max 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Eng. Units Note WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table: ID 50,51,52,53(CSA) see Note (*41) Register N° (dec) +0 +1 +2 Description HMIRef. Module firmware version Position Working status b0: CSA in position/ searching position b1: CSA Ready/Set-up b2: CSA / CSY b3:not used b4: not used b5: not used b6: not used b7: b8: CSA Positions number b9: CSA Positions number b10: CSA Positions number b11: CSA Positions number b12: CSA Positions number b13: CSA Positions number b14: CSA Positions number b15: CSA Positions number b15: CSA Positions number Type Mode Dec. Points Min Max INT INT INT R R R 2 0 0 0 0 0 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 99.99 99 FFFF 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Note: (*41) Ofs = +9300 (ID 50) ; Ofs = +9400 (ID 51) ; Ofs = +9500 (ID 52) ; Ofs = +9600 (ID 53) (*42) The values returns the current position of the CSA. (*43) 0 =Searching for position( when cleaning pipe time is over, flag is set to 0) ; 1= CSA position OK (*44) 0= Set-Up in progress( This means that the CSA is busy in other internal operations, waiting); 1=CSA READY (*45) 0= CSA; 1= CSY( deviation valves) (*46) CSA number of positions KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units (*42) (*43) (*44) (*45) (*46) (*46) (*46) (*46) (*46) (*46) (*46) (*46) (*46) (*46) Note WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.):ID 50,51,52,53(CSA) Register N° (dec) Description HMIRef. +3 ALARMS 1 b0: Hardware Error, N° wrong positions b1: Hardware error, EEPROM loss data b2: Hardware Error, Input time limit b3: Hardware Error, Release time limit b4: HW Error, Reference 1 missing b5: HW Error, edge reference missing b6: HW Error, Position time limit b7: HW Error, Encoder fault b8: HW Error, Counting reference missing b9: HW Error, Motor fault b10: Requested position not available b11: Maintenance time b12: HW Error, CSA blocked b13: Not used b14: Error, unusual keypad behaviour b15: HW Error, CSA OFFLINE Type Mode Dec. Points &Hex R 0 Note (*47) wrong number positions( only after automatic set-up) (*48) EEPROM loss data (request to execute set-up) (*49) Requested position not available( wrong position set) (*50) CSA blocked ( after 2nd attempt) KJA00091G _Easy2_Easy3_User_Version_R2 Min Max 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Eng. Units Note (*47) (*48) (*49) (*50) WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.): ID 50,51,52,53(CSA) Register N° (dec) +4 Description ALARMS 2 ( deviation valve) st b0: 1 valve wrong position b1: 1B valve wrong position nd b2: 2 valve wrong position b3: 2B valve wrong position rd b4 3 valve wrong position b5: 3B valve wrong position th b6: 4 valve wrong position b7: 4B valve wrong position th b8: 5 valve wrong position b9: 5B valve wrong position th b10 : 6 valve wrong position b11: 6B valve wrong position th b12: 7 valve wrong position b13: 7B valve wrong position th b14: 8 valve wrong position b15: 8B valve wrong position HMIRef. Type Mode Dec. Points &Hex R 0 KJA00091G _Easy2_Easy3_User_Version_R2 Min Max 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Eng. Units Note WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table: ID 54,55,57,58,59,60,61 (MSG) see note (*51) Register N° (dec) +0 +1 +2 +3 +4 Description HMIRef. Module firmware version Digital inputs status ( secondary keypad) Digital outputs status Silos/Hopper level ( secondary keypad) Alarm 1 (secondary keypad) b0: 1= Max level b1: 1= Medium level b2: 1= Minimum level b3: 1= Waiting for valve to be ON b4: 1= Waiting for valve to be OFF b5: 1= Analog sensor level fault b6: 1= Empty b7: b8: 1= Pressure switch b9: 1= Manual priority b10: b11: b12: b13: b14: valve wrong positioning b15: OFFLINE Type Mode Dec. Points Min Max INT INT INT INT &Hex R R R R R 2 0 0 2 0 0 0 0 0 99.99 FFFF FF 99.99 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 0(off) 0(off) 1(on) 1(on) 0(off) 0(off) 1(on) 1(on) Eng. Units Note WF Ready Bios >=FW (*52) Note: (*51) Ofs = +9700 (ID 54); Ofs = +9730 (ID 55); Ofs = +9760 (ID 56); Ofs = +9790 (ID 57); Ofs = +9820 (ID 58); Ofs = +9850 (ID 59); Ofs = +9880 (ID 60) Ofs = +9910 (ID 61) (*52) The register indicates the percentage of the silos material level value . If no continuous level is installed the value will have this format: “--.—“ KJA00091G _Easy2_Easy3_User_Version_R2 Compliance device Easy2/Easy3 Special Modules table(cont.): ID 54,55,57,58,59,60,61 (MSG) Register N° (dec) +5 +6 +7 +8 +9 +10 Description HMIRef. Hardware configuration register b0: b1: b2: b3: Analogue level b4: Deviation valve b5: Silo/Hopper b6: b7: b8: b9: b10: b11: b12: b13: b14: b15: b12: b13: b14: b15: Material ( secondary keypad) Type Mode Dec. Points &Hex R 0 INT R/W 0 Note: (*53) 0= Silos 1= Hopper (*54) Set the material number associated to the silos. KJA00091G _Easy2_Easy3_User_Version_R2 Min Max Eng. Units Note 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) (*53) 0 FF (*54) WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.): ID 54,55,57,58,59,60,61 (MSG) Register N° (dec) +11 +12 +13 +14 +15 +16 +17 Description HMIRef. Type Mode Dec. Points Min Max Mode ( secondary keypad) Valve configuration register b0: b1: b3: b4: b5: b6: b7: b8: b9: b10: b11: b12: b13: b14: b15: b12: b13: b14: b15: Priority(Manual) (secondary keypad) Set alarm minimum level (secondary keypad) Set alarm reorder level INT &Hex RW R/W 0 0 0 2 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Set linearization minimum( secondary keypad) Eng. Units Note (*55) (*56) INT INT R/W R/W 0 2 0 00.00 1 99.99 (*57) (*58) INT R/W 2 00.00 99.99 (*59) INT R/W 2 00.00 99.99 (*60) Note: (*55) 0= selection; 1= sequential; 2= alternate (*56) Bit [0..7] see table map (with YV-OFF = YV-ON negate) (*57) 0= normal; 1= priority Silos( within the group the Silos belongs to) (*58) 0= alarm excluded; 1= Set threshold ( respect to analogue value) to activate minimum level (*59) 0= alarm excluded; 1= Set threshold ( respect to analogue value) to activate reorder level (*60) See linearization function (ADC) KJA00091G _Easy2_Easy3_User_Version_R2 WF Ready Bios >=FW Compliance device Easy2/Easy3 Special Modules table( cont.): ID 54,55,57,58,59,60,61 (MSG) Regi ster N° (dec) Description +18 +19 Set linearization maximum(secondary keypad) Reading frequency Vegalot sensor (secondary keypad) Command HL-00 ( secondary keypad) Command YV-00 ( secondary keypad) +20 +21 HMIRef. Type Mode Dec. Points Min Max INT INT R/W R/W 0 0 0 0 9999 9999 (*61) (*62) INT INT R/W R/W 0 0 0 0 2 1 (*63) (*64) Note: (*61) See linearization function (Vegalot) (*62) waiting time between two readings of the Vegalot sensor (*63) 0= output HL-00 disable; 1= output HL-00 active continuous mode; 2= output HL-00 active blinking mode (*64) 0= output YV-00 disable; 1= output YV-00 enable KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units Note WF Ready Bios >=FW Compliance device Easy2/Easy3 Station Settings table: see note (*1) Register N° (dec) Description +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 HMIRef. Type Mode Dec. Points Min Max Eng. Units Max suction time ( secondary keypad) ON/OFF Receiver ( secondary keypad) Suction time ( timer 1), (secondary keypad) INT INT INT R/W R/W R/W 0 0 0 0 0 0 999 2 Ofs +0 s n s Pipe cleaning Time (timer 2) (secondary keypad) Cycles of proportional valve( secondary keypad) Regrind percentage ( secondary keypad) Material discharge time( timer 4) ( secondary keypad) Slide gate activation time (Timer 3)( secondary keypad) Blower stand –by time ( timer 6) ( secondary keypad) Filter cleaning time ( timer 5) ( secondary keypad) INT R/W 0 0 999 s INT R/W 0 0 9 n INT INT R/W R/W 0 0 0 0 99 999 s INT R/W 0 0 999 s (*5) INT R/W 0 0 999 s (*6) INT R/W 0 0 999 s (*7) Note: (*1)The absolute address of each station, is computable in the following way: Ofs = N°Stations[1..44] * 20 (for stations 1..44) Ofs = N°Stations ([45..48]-44) * 20 +9000 (for stations 45..48) (*2) 0= OFF (charge excluded) ; 1= ON (Charge enable) ; 2= ON + ALARM (Charge enable with alarm check) (*3) Important only if proportional valve is installed (*4) Important only if proportional valve is installed (*5) Important only if slide gate is installed (*6) Important only if stand–by valve is installed (*7) Important only if filter and/or cleaning equipment is installed KJA00091G _Easy2_Easy3_User_Version_R2 Note (*2) (*3) (*4) WF Ready Bios >=FW Compliance device Easy2/Easy3 Station Settings table (cont.): Register N° (dec) Description +10 +11 +12 +13 +14 +15 Alarms station Time (Timer 7) ( secondary keypad) Time (Timer 8) ( secondary keypad) Time (Timer 9) (secondary keypad) Material selected (CVC- Ofs +12) Analogue threshold ( CVC – Ofs +14) (secondary keypad) Program code ( secondary keypad) Analogue level (1) (secondary keypad) +16 +17 Note: (*8) Msb Lsb 0000 0000 0000 0001 0000 0010 0000 0100 0000 1000 0001 0000 0010 0000 0100 0000 1000 0000 = = = = = = = = = HMI-Ref. Type Mode Dec. Points Min Max Eng. Units &Hex INT INT INT INT INT R R/W R/W R/W R/W R/W 0 0 0 0 0 0 0 0 0 0 0 Ofs+0 999 999 255 1023 s s s n % INT INT R R 0 0 0 0 FFFF 1023 n No alarms Charge Failure Motor Overload /(servo) or vacuum breaker (single/plant) Obstructed suction line Wrong material connection Waiting for cycling( loading interrupted) Plant blocked due to loading interrupted Element OFFLINE Minimum Level (*9) Future use (*10) Material level threshold, range value set: 2V ÷ 10V 0= Sensor level excluded (0%) (*11) Program code stored into CVC( From CVC-Ofs 0 ex CRC_ID) (*12) Material level into hopper( Important only if sensor level is installed). Analogue level 1 always available KJA00091G _Easy2_Easy3_User_Version_R2 1023=100% Note (*8) (*9) (*9) (*9) (*10) (*11) (*12) WF Ready Bios >=FW Compliance device Easy2/Easy3 Station Settings table (cont.): Register N° (dec) +18 Description Inputs/Outputs status Status valid for digital Inputs b0: INI 1 ( status digital input 1) b1: INI 2 ( status digital input 2) b2: INI 3 (status digital input 3) b3: Not used b4: Station included b5: Alarm check b6: Station enabled b7: Blower(servo) HMI-Ref. Type Mode Dec. Points ID &Hex R 0 Min Max 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 0(off) 1(on) Eng. Units Note (*13) (*14) 0(off) 1(on) Status valid only for single station or plant b8: output 4 status b9: output 4 status b10: output 3 status b11: output 3 status b12: output 2 status b13: output 2 status b14: output 1 status b15: output 1 status 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Status valid only for Blower (servo) b8: Red Led Status b9: Green Led status b10: output 4 status b11: output 3 status b12: output 2 status b13: output 1 status b14: output FLASH b15: not significative 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 0(off) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) 1(on) Note: (*13) (NB: if Bit5 == 1 Bit4 == 0) (*14) local button: if Bit6 == 0 locally escluded (*15) 00= OFF; 01=Swinging; 10=ON(active) ; 11 = OFF (*16) Red and Green light blink KJA00091G _Easy2_Easy3_User_Version_R2 (*15) (*15) (*15) (*15) (*15) (*15) (*15) (*15) (*16) WF Ready Bios >=FW Compliance device Easy2/Easy3 Station Settings table (cont.): Description Register N° (dec) +19 IN3 counter ( secondary keypad) Note: (*17) Counter of UPs-- HMI-Ref. Type Mode Dec. Points Min Max INT R 0 0 FFFF DOWNs transitions on IN3 of the receiver. Not resettable. KJA00091G _Easy2_Easy3_User_Version_R2 Eng. Units Note (*17) WF Ready Bios >=FW Compliance device