POWER ON <1>
p0857 … p0862
<2>
Fault
<5>
Motor at standstill
S1: Switching on inhibited
2000.00 µs
with OFF1 – or
OFF3
response
&
...
From all states
ZSWA.06 = 1, ZSWA.11 = 0
ZSWA.00/01/02 = 0
Motor at standstill
"0 = OFF" (STWA.00)
Pulses inhibited
<4> <5>
<4> <5>
&
[2634]
<4> <5>
≥1
<6> [2634]
"Commissioning completed" (p0010 = 0 & p0009 = 0)
"0 = Coast down" (STWA.01)
≥1
r0046.8 EP terminals,
enable missing
Pulse enable
HW [2701.8], [2711.8]
<6>
<6> [2634]
<5>
<5>
"0 = Coast down" (STWA.01)
<4> <5>
<6> [2634]
ZSWA.00 = 1, ZSWA.11 = 0
≥1
"0 = OFF"
Jog 1
Jog 2
p0870
(0)
"0 = OFF"
Jog 1
Jog 2
Infeed ready
p0862
0
p0864
–1
<5>
&
Energize contactor
"0 = Coast down"
(STWA.01)
[2634]
<6>
<5>
r0863.0
S5a: Ramp stop
<5>
ZSWA.00/01 = 1
ZSWA.11 = 1
ZSWA.02/06 = 0
&
≥1
Bring the motor to n <= 0 along
the Ramp-function generator,
then inhibit the pulses
<7>
Bring the motor to n <= 0 along
the Ramp-function generator,
then inhibit the pulses
Controller enable
<5>
S4: Operation
OFF2 (has priority over jogging)
"0 = OFF"
ZSWA.00/01/02 = 1
ZSWA.11 = 1
≥1
&
<1> POWER ON = 24 V electronics supply OFF --> ON or RESET button.
ZSWA.06 = 0
<2> The sequencer is implemented according to the PROFIdrive profile.
<3> Only for SINAMICS S120 and G150:
Pulses enabled
If a DO Infeed (A_INF, B_INF and S_INF) is used, it closes the line contactor
Controller enabled
No
jog
operation:
Setpoints enabled
(refer to [8732], [8832], [8932]) and not the DO SERVO/VECTOR.
OFF3 (has priority over jogging)
<4> These control commands can also be triggered by a fault response.
<5> STWA.xx = control word, sequence control, bit xx (r0898) [2501]; ZSWA.xx = status word, sequence control bit xx (r0899) [2503].
<6> Only if "Safety Integrated" is active.
<7> The parameters p1226, p1227 and p1228 influence this status.
1
2
DO: SERVO, VECTOR
Sequence control - Sequencer
3
4
<7>
ZSWA.00/01 = 1
ZSWA.11 = 1
ZSWA.02/06 = 0
Wait for Enable operation
Closed-loop control operation
&
&
<4> <5>
S5c: Jogging down ramp
ZSWA.00/01 = 1, ZSWA.11 = 0
ZSWA.02/06 = 0
No PU fault
Vdc uploaded
<3>
Debounce time expired (p0868)
Motor at
standstill
S3: Ready
r0863.1
Line contactor is CLOSED
Wait for precharging
Motor at
standstill
&
<7>
Bring the motor to n <= 0 along
the quick stopping ramp or torque
limit, then inhibit the pulses
&
≥1
ZSWA.00/01 = 1, ZSWA.11 = 1
ZSWA.02/06 = 0
&
Main contactor is OPEN
Wait for power up or jog
r0046.8 EP terminals,
enable missing
Close main con
T
S5b: Quick stop
"0 = Quick stop"
(STWA.02)
<4> <5>
S2: Ready for switching on
<4> <5>
&
5
6
fp_2610_54_eng.vsd
20.02.18 V05.02.03
Jog 1
Jog 2
Jog mode
≥1
&
r0899.8
[2503.3]
Missing enable
signals
7
Function diagram
S120/S150/G130/G150
8
- 2610 -