ZEECO PILOT TESTING
®
Pilot Testing Per API 537
Flare systems operate as a critical safety device within facilities to protect nearby personnel and equipment.
A stable, reliable, and robust pilot is the most critical component in a flare system because the pilot initiates and
ensures combustion. Zeeco is proud to offer pilots tested and proven to meet and exceed American Petroleum
Institute (API) 537 standards.
Given the criticality of flare pilots, industry
leaders and international experts came together to
set API criteria for evaluating acceptable flare pilot
performance. Using pilots that are tested and proven
to meet the criteria assures equipment operators and
the public that a flare pilot will perform reliably. API is
responsible for determining and updating nearly 700
globally accepted industry standards designed to set
the expectations for real world performance.
Zeeco has installed an API-recommended
test stand to test and prove the suitability of our
pilot designs, and to develop and test future pilot
technologies. The ZEECO® HSLF-Z pilot has been
tested and proven to far exceed the minimum
standards of API 537.
While API 537 requires that a pilot stays lit when
subjected to 140 km/h (85 mph) wind speeds and
5 cm/h (2 in/h) of rainfall, the HSLF-Z pilot has been
proven to stay lit under punishing hurricane force
274 km/h (170 mph) winds in the face of 131 cm/h
(51 in/h) of rainfall. To ensure your flare equipment
meets safety expectations and API 537 requirements,
choose a ZEECO flare pilot.
HSLF Flare Pilot
(Still image from live pilot test video.)
To view the HSLF hurricane test video, visit www.zeeco.com/pilots
®
BURNERS
FLARES
INCINERATORS
PARTS & SERVICE
Pilot Testing Per API 537
(LEFT) API 537 testing requires that testing
be performed for 3 different configurations,
to test performance when the wind is
moving across the pilot flame in an upwind,
downwind, or crosswind condition.
(BELOW) ZEECO® HEI and FFG pilot types
sustained ignition in all three positions under
wind conditions of 274 km/h (170 mph) at
rainfall rates of 130 cm/h (51 in/h).
Ignition Source
Position
HEI
(High Energy Ignition)
FFG
(Flame Front Generator)
Tested Conditions
Wind Velocity km/h (mph)
“Rainfall” Rate cm/h (in/h)
274 (170)
131 (51)
1
2
3
1
2
3
Ignition confirmed
and sustained
Ignition confirmed
and sustained
Ignition confirmed
and sustained
Ignition confirmed
and sustained
ZEECO® combustion and environmental solutions are designed and manufactured to
comply with applicable local and international standards as defined by our customers.
ZEECO GERMANY
ZEECO CANADA
ZEECO POLAND
ZEECO LOUISVILLE
ZEECO EUROPE
REGISTERED
ISO 9001: 2008
CERTIFICATION APPLIES TO ZEECO HEADQUARTERS ONLY.
Zeeco Corporate Headquarters
22151 East 91st Street
ZEECO WINFIELD
ZEECO CORPORATE HEADQUARTERS
ZEECO FRANCE
ZEECO CONNECTICUT
ZEECO HOUSTON
ZEECO MEXICO
Broken Arrow, Oklahoma 74014 USA
ZEECO RUSSIA
ZEECO ASIA
ZEECO CHINA
ZEECO ITALY
ZEECO UAE
ZEECO MIDDLE EAST
Phone: +1 918 258 8551
ZEECO JAPAN/APPLICOT
ZEECO INDIA
ZEECO SE ASIA
Fax: +1 918 251 5519
E-mail: [email protected]
Zeeco.com
ZEECO is a registered trademark of Zeeco, Inc. in the U.S.
ZEECO office, affiliate, sales, representative, or third party representative/licensee offices.
© COPYRIGHT 2018 - ZEECO, INC. ALL RIGHTS RESERVED
®
ZEECO BRAZIL
ZEECO AUSTRALIA
18- API rev 3
Descargar