Subido por VICTOR GIOVANY TELLO

Motorpact

Anuncio
IEC 62271-200 defines four categories of Loss of Service Continuity: LSC1, LSC2,
LSC2A, LSC2B.
LSC1 functional unit = Functional unit having one or several high-voltage accessible
compartments, such that, when any of these accessible high-voltage compartments is open,
the busbar and one or several other functional units of the switchgear must be de-energized
LSC2 functional unit = Functional unit having at least an accessible compartment for the
high-voltage connection (called connection compartment), such that, when this compartment is
open the busbar can remain energized. All the other functional units of the switchgear can
continue to be operated normally.
Note: When LSC2 functional units have accessible compartments other than the connection
compartment, further subdivisions into LSC2A and LSC2B are defined.
LSC2A functional unit = Functional unit having several high-voltage accessible
compartments, such that, the busbar can remain energized when any other accessible high
voltage compartment is open. All the other functional units of the switchgear can continue to be
operated normally
LSC2B functional unit = Functional unit having several high-voltage accessible
compartments, such that, the high-voltage connections compartment and the busbar can
remain energized when any other accessible high voltage compartment is open. All the other
functional units of the switchgear can continue to be operated normally.
Unidad funcional LSC2A = Unidad funcional que tiene varios compartimentos accesibles de
alto voltaje, de manera que, la barra colectora puede permanecer energizada cuando
cualquier otro compartimiento de alto voltaje accesible está abierto. Todas las demás unidades
funcionales del equipo de distribución pueden continuar funcionando normalmente
Metal-clad switchgear
Division of the switchgear panel into four compartments (busbar
compartment, switching-device compartment, connection compartment and
low-voltage compartment); partitions between the compartments made of
sheet steel, front plate made of sheet steel or insulating material.
Compartmented switchgear
Division of the switchgear panel same as for metal-clad switchgear, but
with the partitions between the individual compartments made of insulating
material.
Cubicle-type switchgear
All other types of construction that do not meet the above features of the
metal-clad or compartmented designs.
In this context, access to the then common minimum-oil-content circuitbreakers for maintenance work without longer operational interruptions was
of prime importance because of the limited number of operating cycles.
Therefore, with switchgear in metalclad or compartmented design, the
busbar in the busbar compartment and the incoming cable in the
connection compartment could remain in operation. With a cubicletype
design, the incoming cable had to be isolated, but the busbar itself could
remain in operation.
Overview of IEC 62271-200
Siemens HV Switchgear
Although the old IEC 60298 standard was very helpful, in time it was
superseded by the technological progress. Above all, the appearance of
maintenance- free vacuum circuit-breakers, with operating cycles far
exceeding the normal number, made frequent access to this circuit-breaker
no longer of prime importance.
The vacuum arc-quenching principle is technologically so superior to other
arc-quenching principles that the circuit-breaker can be fixed-mounted
again. This resulted in the first-time use of gas insulation with the important
features of climatic independence, compactness and maintenance-free
design. However, both technologies – the vacuum arc-quenching principle
and gas insulation – were not adequately taken into account in the existing
standard. Therefore, at the end of the nineties, the responsible IEC
committees decided on the reformulation of the switchgear standard, which
finally came into effect as IEC 62271-200 in November 2003. At the same
time the old IEC 60298 standard was withdrawn without any transition
period.
Four key features are of special note with the new IEC 62271-200
standard:
1. Changed dielectric requirements
According to IEC 60298, two disruptive discharges were permitted in a
series of 15 voltage impulses for the test with rated lightning impulse
withstand voltage. According to the new standard, the series must be
extended by another fi ve voltage impulses if a disruptive discharge has
occurred during the fi rst 15 impulses. This can lead to a maximum of 25
voltage impulses, whereas the maximum number of permissible disruptive
discharges is still two.
2. Increased demands on the circuit breaker
and earthing switch
In contrast to the previous standard, the switching capacity test of both
switching devices is no longer carried out as a pure device test. Instead, it
is now mandatory to carry out the test in the corresponding switchgear
panel. The switching capacity may get a negative infl uence from the
different arrangement of the switchgear with contact arms, moving
contacts, conductor bars, etc.
For this reason, the test duties T100s and T100a from the IEC 62271-100
standard are stipulated for the test of the circuitbreaker inside the
switchgear panel.
3. New partition classification
The new partition classes PM (partitions metallic = partitions and shutters
made of metal) or PI (partitions nonmetallic = partitions and shutters made
of insulating material) now apply with respect to the protection against
electric shock during access to the individual components.
The assignment is no longer according to the constructional description
(metalclad, compartmented or cubicle-type design), but according to
operator-related criteria.
4. Stricter internal arc classification
Significantly stricter changes have also been implemented here. The
energy flow direction of the arc supply, the maximum number of
permissible panels with the test in the end panel and the dependency of the
ceiling height on the respective panel height have been redefined.
In addition, the five following new criteria must always be completely
fulfilled (no exceptions are permitted):
1. Covers and doors remain closed. Limited deformations are accepted.
2. No fragmentation of the enclosure, no projection of small parts above 60
g weight.
3. No holes in the accessible sides up to a height of 2 meters.
4. Horizontal and vertical indicators do not ignite due to the effect of hot
gases.
5. The enclosure remains connected to its earthing parts.
For the internal arc classifi cation of substations with and without control
aisle, the testing of the substation with installed switchgear is mandatory in
the new IEC 62271-202 standard. The classification of the substation is
only valid in combination with the switchgear used for the test.
The classification cannot be transferred to a combination with another
switchgear type as each switchgear behaves differently in the case of an
internal arc (pressure relief equipment with different cross-sections and
pickup pressures, different arcing conditions because of different conductor
geometries).
PAGE 10
Coast stop is precisely as it sounds - the drive output is de-energized and the motor spins down at
whatever speed the load imparts on it. This is typically the “emergency stop” mode dictated by the
U.S. National Electric Code
Descargar