SLP-275 V/2
Ordering number
A01619
SPD type 2 - Surge Arrester
pluggable module, visual fault signalling, module locking
two-pole varistor surge arrester, installation to LV installations, especially to subdistribution boards in TN-S systems, for protection of the installations and
equipments against impact of induced overvoltages during a lightning strike or
switching overvoltages
Dimension drawing
Basic circuit diagram
Technical specifications
Type of SPD
T2
Nominal voltage
Un
230 V AC
Maximum operating voltage
Uc
275,00 V AC
Maximum operating voltage
Uc
350,00 V DC
Nominal discharge current (8/20 µs)
In
20,00 kA
Maximum discharge current (8/20 µs)
Imax
40,00 kA
Voltage protection level at 5 kA
Up
0,90 kV
Voltage protection level
Up
1,35 kV
Short-circuit current rating
ISCCR
50,0 kA
Maximum overcurrent protection
Response time
160 A gL/gG
ta
25 ns
TOV 5 s L-N
335 V
TOV characteristic (TOV 5 s)
withstand
TOV 120 min L-N
440 V
TOV characteristic (120 min)
safe failure
Cross-section of connected conductors solid (min)
1,00 mm2
Cross-section of connected conductors solid (max)
35,00 mm2
Cross-section of connected conductors stranded (min)
1,00 mm2
Cross-section of connected conductors stranded (max)
25,00 mm2
Fault indication
red indication field
Degree of protection
IP 20
Range of ambient temperatures - min
-40 °C
Range of ambient temperatures - max
80 °C
Mounting
According to standard
DIN rail 35 mm
EN 61643-11:2012, IEC 61643-11:2011
Plug module
ETIM Class
Customs tariff number
EAN
SLP-275 V/0
EC000941
85363030
8595090516194
SALTEK s.r.o., Drážďanská 561/85, 400 07 Ústí nad Labem, CZ | +420 475 655 511 | [email protected] | www.saltek.eu