Subido por Manuel Aviles

Werner Water Chiller Manual

Anuncio
Werner Finley
CONTENTS
Description
Chapter
Page No
1, 2
3
4
Chapter 1
Certificates
Design data
Operating limits
Chapter 2
Introduction
General description
Inspection
Handling and lifting
4
4
4
5
Chapter 3
Locating
Foundation & Anti-vibration Mounts
Location
Tips
5
5
5
6
Chapter 4
Liquid Piping
Typical Piping Layout
Immersion Type
Installation Check Report
7
8
9
10
Chapter 5
Start-up & Operation
Preparing the system for start up.
Start up & operation
Emergency Stop
Sequence of Operation
11
12
13
14
Chapter 6
Refrigeration
Refrigeration cycle
standard controls
15
16
17
Chapter 7
Trouble Shooting Chart
19
Maintenance
Safety
System Maintenance
Tips for preventive maintenance
Schedule & warnings
21
23
24
25
Service
System Service
Refrigeration Line Service
26
27
Temperature Controller
Dixell
Subzero
30
31
Technical data
Temperature conversion chart
Pressure, Temperature Chart
32
33
Chapter 8
Chapter 9
Chapter 10
Chapter 11
Werner Finley
Werner Finley Pvt. Ltd.
Industrial Cooling Systems
#9, Cauvery Nagar, Near Swayam Prabha Kalyana Mantapa,
Magadi Main Road, Kamakshipalya, Bangalore 560 079.
Ph. 080-23289889, 23288371 Fax : 91-80-23283191
E-mail: [email protected]
TEST CERTIFICATE
PRODUCT
:
SERIAL NO.
:
CUSTOMER
:
P. O. No.
:
It is certified that the above
Chiller has been inspected for its
specification, material inputs, workmanship capacity and performance. The
results are found to be satisfactory.
For Werner Finley Pvt. Ltd.
1
Werner Finley
Werner Finley Pvt. Ltd.
Industrial Cooling Systems
#9, Cauvery Nagar, Near Swayam Prabha Kalyana Mantapa,
Magadi Main Road, Kamakshipalya, Bangalore 560 079.
Ph. 080-23289889, 23288371 Fax : 91-80-23283191
E-mail: [email protected]
GUARANTEE CERTIFICATE
PRODUCT
:
SERIAL NO.
:
CUSTOMER
:
P.O. No.:
:
We hereby guarantee to replace at free of cost any component found defective
due to bad workmanship or faulty raw materials in the above supply. The defects,
which occured due to transit, bad storage, misuse or mishandling of the
equipment at customer's site or due to normal wear and tear will not be
entertained. This guarantee will be valid for a period of twelve months from the
date of supply.
For Werner Finley Pvt. Ltd.
2
Werner Finley
DESIGN DATA
01.
UNIT SERIAL NO.
-
02.
TYPE OF CHILLER
Kcal/Hr
03.
COOLING CAPACITY
-
04.
POWER SUPPLY
-
1 PH, 230 V, AC, 50 HZ
-
3 PH, 440 V, AC, 50 HZ
05.
POWER / CURRENT
-
06.
APPLICATION
-
07.
LIQUID TYPE & QTY.
-
08
CONDENSER TYPE
-
AIR COOLED
-
WATER COOLED
09.
NO. OF FANS
-
10.
EVAPORATOR TYPE
-
COIL IN TANK
-
SHELL AND TUBE
-
PHE
11.
REFRIGERANT
-
R 134 a / R 407c / R 22 / R 404a
12
PUMP
-
FLOW__________PRESSURE________
13.
TEMP. CONTROLLER -
14.
COLOUR
SEIMENS GREY
-
ADMIRAL GREY
BLUE
OTHERS
3
Werner Finley
OPERATING LIMITS
Standard Air-cooled, reciprocating, liquid chiller packages.
Unit
Description
R22 / R 134a
Min/Max. liquid temperature
Leaving the evaporator
0
Min/Max. liquid temperature
entering the evaporator.
0
12 / 30
0
C
15/ 45
LPM
12 / 20
per TR
C
C
Min/Max. operating ambient temperatures.
Min/Max. flow late of liquid across
Evaporator
7 / 25
Units outside given standard operating limits are also available, for details please
contact our Head Office at Bangalore.
INTRODUCTION
General description
!
Werner Finley liquid chillers are complete, self-contained, automatic refrigeration units
that are ready for installation.
!
These units include the latest engineered components assembled to provide a compact
and efficient Chiller.
!
Each unit is completely factory assembled, wired & pressure tested before charging of
refrigerant. The unit undergoes thorough load test before dispatch.
Inspection
!
Upon receipt of the units at site, ensure the complete shipment against delivery note or
Bill and also inspect the unit for any transit damage.
!
If transit damage is found, report the damage to the transporter and file for insurance
claim.
3
4
Werner Finley
Handling and lifting
!
Always keep the unit in vertical position as per arrow displayed on the wooden box.
!
Dismantle the wooden packing.
!
Lifting hooks / eyebolts are provided at the top of unit. Use them for safe lifting.
!
In some units where lifting hooks are not provided, sling the unit from base to lift
safely.
!
Handling of the unit should be done with the aid of qualified personnel's who are
familiar and experienced with this type of equipment.
Note:
Physical damage to unit after acceptance will not be covered for rework under
warranty
LOCATING
Foundation andAnti Vibration Mounts
!
Werner Finley units have very minimum vibration units and do not require any special
type of mounting.
!
These units can be set directly on the floor or rooftop or any platform with adequate
support system. Shelter to be provided in case of outdoor installations.
!
Anti vibration mounts can be used and can be of Neoprene rubber material.
!
For Immersion type units beading should be provided on the frame where it is to be
mounted, to avoid metal to metal contact.
Location
!
Each side of the unit must be accessible for periodic maintenance and service work.
!
The unit should maintain a good clearance from the surrounding walls for good air
exchange.
!
The area should have good ventilation system or exhaust system.
5
Werner Finley
Location w.r.t. clearances from adjacent walls / obstructions
1m
1m
1 - 1.5m
Note: Upper side clearance should be atleast 2 m from the top of the chiller
Tips on Location Selection
!
In air-cooled units, condenser air inlet and condenser fan air discharge must be free
from any obstructions.
!
Units that are not given enough clearance, will experience coil starvation and hot air
re-circulation and would affect the performance of the chiller.
!
Hence, free air supply and free hot air ventilation is a must at the site of installation
of an air-cooled chiller.
!
The discharge of the condenser is hot and is exhausted out through the cut out
provided (normally top).
!
If required, ducts can be used to vent this hot air out.
!
Aprofessional should take up the ducting work
6
Werner Finley
LIQUID PIPING
In most chillers, the pump is included in the package and only the end connections are to
be made at the site.
!
The pipeline could be of flexible hose or pipe one depending on the pressure and
preferences. Flexible hose should be properly clamped to avoid leakage.
!
Flexible hoses can subjected to pinching if supports are not provided.
!
The inlet/outlet pipeline diameters should not be reduced or increased.
!
Rigid pipeline should be of stainless steel or any non corrossive material pipe to avoid
rusting.
!
Provide isolation valves at inlet / outlet connection to chiller.
!
Providing vibration isolators of the right diameters at the inlet/outlet of the chiller, where
ever the piping its rigid.
!
Providing an air vent in the pipeline is a good practice to vent the trapped air in the pipeline
during startup.
!
It is recommended to use a wire mesh strainer at the inlet to chiller. The size of the strainer
should be at par with the rate of flow of impurity through the pipeline running above the
tank.
!
NRV [Non Return Valve] should be provided in case of lengthy pipelines running above the
tank.
!
In case, where flow consistency cannot be assured, it is highly recommended to install a
flow switch in discharge pipeline and interlock the same with the chiller.
!
As much as possible try giving a positive suction to the pump. If not, use a self priming
pump with a foot valve at the suction. Also provide an opening with a valve in the discharge
line for priming the pump.
!
Please inform our engineering team well before if the pump is subjected to negative suction.
!
Sharp and too many bends will create a back pressure and reduce the liquid flow through the
system.
!
If there is a heavy condensation, insulation to be provided for the liquid lines.
!
Using unions or flanges of correct sizes wherever necessary helps for easy maintenance.
Note:
Werner Finley will not be responsible if chiller or pump fails or malfunctions due
to foreign particle entry, reduction in flow, bad piping, pump starvation, freezing of heat
exchangers, etc.
7
Werner Finley
Typical Piping Layout
5
6
2
3
4
1
7
LABELS
1
2&5
3&6
4
7
8
WATER PRESSURE GAUGE
VALVES
VIBRATION ELIMINATOR
Y-STRAINER
AIR VENT
Werner Finley
Immersion Type Chiller
! Complete coil to be immersed in fluid.
! Electrical float switch is a must.
! Stirrer for larger tank is a must for agitation.
! Lifting arrangement is a must for periodic coil cleaning.
NOTE:
SOFT WATER OR DM WATER CAN BE USED AS THE FLUID.
PEROIDIC CLEANING OF TANK AND REFILLING OF FRESH
WATER ISAMUST.
FLUID CONTAMINATION CAN LEAD TO PUMP FAILURE,
FREEZING OF HEAT EXCHANGERS & EVENTUALLY
COMPRESSOR FAILURE.
FAILURE DUE TO ABOVE REASONS WILL VOID THE
CHILLER WARRANTY.
9
Werner Finley
INSTALLATION CHECK REPORT
Customer
: ....................................................................................
Unit SL. No.
: ....................................................................................
Unit Cap
: ....................................................................................
Sl.
No.
PARTICULARS
01
In case of transit damage, has it be attended completely?
Yes/No.
02
Is there any damage during installations?
Yes/No.
03
Have damages as per list been attended?
Yes/No.
04
Whether unit is mounted as per recommendation?
Yes/No.
05
Is there free space to attend chiller?
Yes/No.
06
Has the piping & insulation been done as per recommendation?
Yes/No.
07
Has sufficient space been left for condenser air entry and
service facility?
Yes/No.
08
Sufficient space to clean evaporator?
Yes/No.
09
Power supply & supply cable as per recommendation?
Yes/No.
10
Sufficient space for attending electrical panel?
Yes/No.
10
Werner Finley
START UP AND OPERATION
NOTE:
DO NOT ATTEMPT TO START THE CHILLER UNTILL THE
FOLLOWING CHECKS HAVE BEEN COMPLETE.
!
With mains disconnected, check all electrical connections in control panel. All though all
connections are tightened at factory, they might have loosened up during shipment, which
may cause system to malfunction.
!
Check the actual line voltage to the unit to make sure it is the same as specified on the chiller
specification plate within _+10% and that the phase voltage imbalance does not exceed
2%. Verify that adequate power supply & capacity is available to meet the required load.
% Of Voltage imbalance
100 x Max. Voltage deviation from average
average voltage
The maximum voltage deviation in the largest difference between a voltage measurement
across two legs and the average across all three legs.
EXAMPLE
a)
Supply voltage is 415V
Voltage across
-
3PH-50 Hz
RY
-
410 V
YB
-
419 V
BR
-
405 V
-
411.33 V
Average
b)
Maximum deviation from average voltage
RY = 1.33V; YB = 7.6V; BR = 6.33 V
Hence Max. deviation is 7.6 V
c)
% voltage imbalance = 100 x
7.67UU
411.33
which is less than the allowable 10% imbalance.
11
= 1.86%
Werner Finley
!
Make sure that all interlock wiring is as per the wiring diagram provided in the control
panel pouch.
!
Check lubrication oil level in the compressor sight glass. The oil level before start up
should be at least 1/3 of the sight glass.
!
Now turn the main switch on, this will energize the crankcase heater. (Crankcase
heater is available on models above 4 TR capacity)
NOTE: Crankcase heaters have to operate at least 12 hrs prior to start up. Crankcase
should be warm.
!
In units that have suction, discharge valve on compressor and liquid line hand shut off
valve, check for them to be in open condition.
!
Check all liquid line valves and keep them open. Now switch on pump and check for
leakage in pump & pipeline.
!
Set the required flow & pressure by using the balancing valves at the discharges, by
pass & return line. Measure the flow using a graduated vessel & ensure it is inline with
the system requirement.
START-UP & OPERATION:
!
Please check whether all the MCB/MPCB are in on condition. Now once the proper
flow is assured by switching on the pump, then turn on the switches for the
compressor & fan simultaneously.
!
The fluid temperature is now sensed & if it is higher than the set point, the comp & fan
will start to operate & the crankcase heater will turn off automatically.
!
Once again check the setting of the OLR, HP, LP & AFT switches for correctness.
12
Werner Finley
!
Now the compressor will work to bring down the fluid temperature to the set point.
Once the fluid temperature reaches set point, the compressor & fan will cut off and
the pump will still be in operation.
!
Again as the fluid gains temperature & raises equivalent to the set differential, the
signal is taken up by the delay timer, after a preset delay of 3 minutes, the
compressor & fan again cuts in to lower the fluid temperature.
!
While unit is fully loaded, check suction pressure, discharge pressure,
comp/fan/pump current and compressor shell temp.
!
Should you face any problem, refer to the chapter on trouble shooting.
EMERGENCY STOP
!
Turn off the rotary switch during such situations
!
Stop on weekend or temporary shut down.
!
Switch off the circuit breakers in the control panel & keep the main switch on during
such shutdowns.
!
Extended shut down:
In larger units where there is a liquid line hand shut off valve, close the valve, run the
system & monitor the suction discharge pressure through gauges. Allow all the gas
to pump down to the condenser side & switch off the unit.
Now close the suction discharge valves in the compressor, close the liquid isolation
valves as well.
!
To start the unit again, follow the steps from START UP.
NOTE: Crankcase heaters have to operate at least for 12 hrs before start up & the crankcase
should be warm. Open all valves before starting
13
Werner Finley
SEQUENCE OF OPERATION FOR LIQUID CHILLERS
ITEMS
Step 1
Initial
checks
ACTIONS
REMARKS
a) Check all electrical connections are tight.
b) Check the supply voltage is within
permissible limits.
c) Check the entire refrigerant & liquid
circuit valves are open.
d) Check oil level in oil sight glass.
e) Check flow across evaporator.
f) Check compressor shell temperature.
b) Shall be within
10%
Step 2
Sequence
of starting
a) Check all safety interlocks
b) Start pump & liquid flow.
c) Start the unit as recommended in unit
startup section
b) Check pressures
at pump discharge
& measure flow.
Step 3
Observation
a) After steady operation at design condition,
see that the refrigerant pressures are stabilized.
b) Take all readings like comp. Suction &
discharge pressures, comp/fan/pump current,
comp shell temp, pump flow & pressure, air
flow across condenser, etc.
c) Periodical oil level check.
d) Abnormal noise & vibration.
e) Vibration of refrigeration and liquid
pipelines.
f) No switch gear components are running hot.
Step 4
Stopping
a) Turn off the circuit switch.
b) Check for oil return in crankcase.
c) Close all valves if required.
14
d) Should be 1/3rd
or 1/2 the sight
glass.
c) Oil level should be
between ½ & 1/3
of sight glass.
e) Arrest all vibrations.
a) It is not advisable
to switch off the
whole unit in one go.
So use the individual
circuit breakers in the
panel & switch off the
comp, fan, and then
pump in the same
order & then turn of
the main switch.
Werner Finley
REFRIGERATION
A liquid whose Saturation temperature at normal atmospheric pressure is below the
temperature that is to be produced by refrigeration is chosen as the working liquid in the
refrigerator and is known as refrigerant. Such a liquid will evaporate at lower temperatures
and will absorb heat as it does so. This heat is extracted from the surroundings. The vapour
formed in this way is compressed in a compressor. After compression the refrigerant may
be in the vapour state or, in the liquid state if its temperature after compression is not
greater than the saturation temperature at that increased pressure. The low temperature
vapor is condensed in a condenser. As a result of condensation in the condenser, it gives off
the heat in the condenser, in doing so it lowers its temperature below the surroundings.
Now the condensed liquid is expanded to a lower pressure and the cycle of refrigeration is
repeated.
VAPOUR COMPRESSION REFRIGERATOR
15
Werner Finley
REFRIGERATION CYCLE
1.
Compressors are used in vapour compression cycles. It is the heart of the system
and it sucks low-pressure refrigerant vapour from the evaporator and compresses it
to a pressure corresponding to the saturation temperature that will be higher than
the air available to condense the refrigerant. The compressor also aids to
continuously re-circulate the refrigerant through the system.
2.
Air-cooled condensers are heat exchangers, which reject heat from the condensing
refrigerant to the atmosphere. The function of condenser in a refrigerated system is
to de-superheat and condense the compressed discharge refrigerant vapour. Highspeed fans are mostly used to speed up the process.
3.
At the exit of the condenser the refrigerant loses temperature but still is in highpressure state. The temperature falls down a little high to the ambient.
4.
Dryers are mainly used to capture the moisture content if any mixed with the
refrigerant. When the refrigerant passes through its thin filter mesh the moisture
gets trapped on the silica gel and clean refrigerant flows through.
5.
Throttle valve (also called as Expansion valve) is also a very important component
of the vapour compression refrigeration system. The function of an expansion
device is to expand the liquid refrigerant from the condensing pressure to the
evaporating pressure. Also it throttles the required flow into the evaporator
depending on the load conditions. Commonly used expansion devices are capillary
tubes, thermostatic expansion valves and constant pressure expansion valves.
6.
Any liquid when evaporates creates a cooling effect. Same applies here, when the
refrigerant exits expansion valve it is partly in vapour state at low temperature and
pressure. It flows through the evaporator and exchanges heat with the
surroundings.
7.
After exiting the evaporator it has gained heat from the surrounding media, thus
lowering the temperature in the freezing compartment. This superheated vapour
passes further and is drawn by the compressor, which compresses it, and delivers to
condenser, thus, completing the refrigeration cycle.
16
Werner Finley
STANDARD CONTROLS
![HP] HIGH PRESSURE
This is a manual reset type pressure controlled electromechanical device used as a
safety cutout against high discharge pressure of the refrigerant.
The reset button is located on the HP/LP switch.
2.
[LP] LOW PRESSURE
This is an automatic reset type pressure controlled electromechanical device used
as safety cutout against low suction pressure. The unit trips & resets automatically
till the pressure completely drops below the desired level.
3.
OILPRESSURE [COMPRESSOR LUBRICATION]
In larger semi hermetic compressors there is an in-built oil pump assistant for the
lubrication of the compressor. There is an oil pressure cutout switch that senses the
discharge pressure of this pump & the suction pressure of the compressor & opens
the compressor motor power circuit in case of a trip. The reset in this cause is done
manually.
4.
THERMISTOR TRIP
In compressors above 5TR, the compressor motor is embeded with temperature
sensor. As the motor winding temperature, exceeds the permissible limits the
thermistor cuts out the power supply to the compressor motor. The reset is
automatic, for which the motor has to cool naturally. As the compressor cuts off,
there is an indication on the panel that remains glowing until the auto reset happens.
5.
[SPP] SINGLE PHASE PREVENTER
This device safeguards the chiller from:
Single phasing, phase reverse & voltage imbalance. Under or over voltage ± 10%.
17
Werner Finley
6.
ANTIFREEZE TRIP
This is a manual reset type thermostat. As the liquid temperature falls below
safety set point, the thermostat trips the compressor & the liquid pump. The reset
button is located on the thermostat itself.
7.
[OLR] OVER LOAD RELAYTRIP
All the motors of the compressor, fan & liquid pump are wired through an over
load relay. As the respective motor draws higher than the set current value, the
OLR trips off the motor & an indication is generated on the panel.
8.
WATER LEVELLOW
In chillers with in-built tank the float switch aids in maintaining an optimum
level in the tank. The whole system comes to a halt as the water level goes low
and an indication on the reset push button is generated on the panel. As the water
level is made up & the reset button is pushed, the chiller resumes its operation.
9.
FLOW SWITCH TRIP
In chillers, where flow switch is installed in the liquid circuit, the whole system
trips as a lack of adequate flow.An indication is generated on the panel and resets
automatically when flow is initiated.
18
Werner Finley
TROUBLE SHOOTING
PROBLEM
Sl.No.
01
02
Unit not switching ON
SPP trip
POSSIBLE CAUSE
ACTION
>
MCB/OLR are kept off when
the unit is dispatched.
Ensure the MCB/OLR of the
unit are in ON condition.
>
Voltage imbalance
Check voltage
>
>
Phase Failure
Incorrect phase sequence
Check voltage.
Interchange the phases.
03
OLR trip
>
>
Pump, Compressor, Fan
Motor taking high current
Contact Vendor
04
Water Level Low
>
>
Low water level in the tank
Leaks in the pipeline
Fill up the water, reset.
Rectify the leaks
05
Antifreeze trip
>
>
>
>
>
No water circulation
Pump Failure
Pump suction valve closed
Low load
Evaporator blocked
Clean the strainer
Contact Vendor
Open the valve
Optimize load
Clean Evaporator coil
06
Flow switch trip
>
>
>
>
No water circulation
Pump Failure
Pump uction valve closed
Dry running of pump
Clean the strainer
Contact Vendor
Open the valve
Prime the pump
07
Oil Pressure trip
> Compressor oil pump failure
> Low compressor oil
Contact vendor
Contact vendor
08
Thermistor trip
> Compressor shell temperature
> very high
> Low refrigerant
Allow the compressor to cool,
automatic restart
Contact vendor
09
Low pressure
>
>
>
>
Low refrigerant
Refrigerant filter choke
Low load
Evaporator blocked
19
Contact vendor
Contact vendor
Optimize load
Clean Evaporator coil
Werner Finley
Sl.No.
PROBLEM
POSSIBLE CAUSE
ACTION
01
High pressure
>
>
>
>
>
>
Clogged filters
Clogged condenser
Condenser fan failure
Hot air re-circulation
Obstruction in air flow
High pressure side choke
Clean filters and condenser
with air pressure
Contact vendor
Provide ventilation
Clear obstruction
Contact vendor
02
Unit ON
but compressor not starting
>
Compressor on timer, initial
time delay 3mins.
Timer not working
Thermostat device open
Wait till the timer elapses.
>
>
>
>
>
05
Compressor starts but
makes humming noise
Compressor starts but trips
immediately
Contact Vendor
Compressor to be replaced.
Contact Vendor
Low Voltage
Start capacitor defective
Compressor windings
defective
High Discharge Pressure
Check the voltage
Change capacitor
Replace the compressor.
Check the voltage
Change the defective
accessories
Contact Vendor
>
Low Voltage
Compressor accessories
defective
Compressor taking high
current
Windings defective
>
>
>
>
>
Compressor not getting on.
Filter clogged with dirt
Compressor taking less current
Compressor over heated
Low refrigerant
Follow instruction No. 2
Clean the filter
Low Refrigerant,
Contact Vendor
Contact Vendor
>
>
>
>
06
Compressor accessories not
working
Overload Protector Tripped
No continuity in compressor
terminals
Contact vendor
Wait till temperature exceeds
set temp by 20c.
Accessories to be changed.
>
>
>
Contact Vendor.
Contact Vendor.
07
High Temperature
09
Low Temperature
>
>
Set temperature altered
Thermostat not working
Check the settings
Replace. Contact Vendor
09
Freezing in Evaporator
>
>
Improper water flow
Pump failure
Check for obstruction
Contact Vendor
20
Werner Finley
MAINTENANCE
SAFETY CONSIDERATIONS
Installation, starting-up and servicing of process chillers can be hazardous due to
system pressures, electrical components and equivalent location viz. roofs, elevated
structures, etc.
Werner Finley make liquid chillers are designed for safe and reliable, when operated
within design limits. When operating this equipment, use judgement and safety
precautions to avoid damage to equipment, property or injury to personnel. Be sure that
you understand and follow the safety precautions.
NOTE:
ONLY TRAINED, QUALIFIED INSTALLERS AND SERVICE
METCHANICS SHOULD INSTALL, START-UP AND SERVICE THIS
EQUIPMENT.
SOME OF THE SAFETY TIPS:
GENERAL:
1.
DO NOT CLIMB over the chiller and DO NOT STEP on refrigerant lines.
Broken lines can release high-pressure refrigerant and cause injury to
personnel.
2.
NEVER SHORT-CIRCUIT any controls in the system.
3.
Care in HANDLING & RIGGING; check weight, use appropriate lifting
equipment, use lifting hooks, or use base frame for lifting equipment.
4.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion,
leaks and damages.
5.
Drain liquid completely before loosening or attending to liquid lines.
21
Werner Finley
PRESSURE TEST
1.
Use only dry Nitrogen. Use a regulating valve with pressure gauge.
2.
DO NOT USE OXYGEN orACETYLENE, both could cause explosion.
3.
HANDLE THE CYLINDERS VERY carefully.
4.
NEVER EXCEED 300 PSI during pressure testing the equipment.
REFRIGERANT
1.
DO NOT VENT refrigerant in closed room as it could displace oxygen and cause
asphyxiation. As per ASHRAE Std 15, refrigerant to be vented out in the open or
through the ventilator in the plant room.
2.
Though R22/R134a/R407c/404a are non-toxic, spillage of liquid refrigerant on
skin & eyes could cause severe damage to the tissue. Use safety goggles and gloves.
In case of refrigerant burn on skin flush with cold water immediately. If liquid
refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water. Consult a
physician immediately.
3.
DO NOT WELD or FLAME CUT any refrigerant line before completing
evacuating the refrigerant from the system. Dry Nitrogen to be used to flush final
traces of Refrigerant and place to be well ventilated. Refrigerant with open flame
produces toxic gases.
4.
CHECK REFRIGERANT TYPE before charging into the system. In case of wrong
charge, the system could get damaged or malfunctioning could occur.
5.
NEVER HEAT refrigerant cylinder with open flame, ONLY use warm water (43) to
heat cylinder.
22
Werner Finley
Electrical:
1.
DO NOT WORK ON HIGH VOLTAGE equipment unless you are a qualified
electrician.
2.
DO NOT WORK ON electrical components, including control panels, switches,
starters or oil heaters unit you are sure ALL POWER IS OFF & NO RESIDUAL
VOLTAGE can leak from capacitors or solid state components.
3.
Lock OPEN & TAG electrical circuits during servicing IF WORK IS
INTERRUPTED, confirm that all circuits are de-energized before resuming work.
SYSTEM MAINTENANCE
A conscientiously administered and maintenance program will enhance the value of the
package chiller by:
!
Increasing the life of the unit.
!
Assuring the proper operation without costly shutdown at critical times.
!
Minimizing the repair cost.
!
Assuring operation of the chiller at maximum efficiency.
!
Under normal conditions, the package chiller will require nothing more than periodic
thorough visual inspection to assure operation at maximum performance. Qualified
personnel shall handle maintenance and inspection only. If the operator has limited
refrigeration and electrical knowledge, he should confine his maintenance of the
equipment to periodic inspection, cleaning of filter and condenser coils only.
23
Werner Finley
TIPS FOR PREVENTIVE MAINTENANCE
To ensure proper unit operation and to avoid damage to unit components, follow periodic
inspection set up.
!
Maintain log book and record essential readings like ambient temperature, liquid
temperature, current, suction / discharge pressure, fluid pressure etc.
!
Maintain history of parts used with date and reason for replacement.
!
Check oil level to be close to 1/3 of the oil sight glass in the compressor.
!
Clean condenser / dust filter often & keep it free for good airflow.
!
Clean filter / Y Strainer in liquid circuit often & keep it free from contamination.
!
In case of coil type evaporator, clean coil with water jet & keep free from scaling
rd
& contamination.
!
In case of shell & tube type evaporator, during break down or other maintenance
schedule, cleaning can be done by circulating de-scaling agents, before restarting
the unit.
!
In case of PHE type evaporator, reverse flush the unit & circulate cleaning agent
& ensure to flush it with water before restarting.
!
Ensure to maintain good liquid quality at all times.
!
Ensure the use of genuine refrigeration parts in the chiller.
!
Never close valves during unit in operation.
!
Tighten the cables & electrical connections every month. Study the wiring
diagram before attending the electrical panel.
!
If liquid back flood occurs in compressor, do not run the compressor. Investigate
& rectify the defects.
CAUTION:
ALWAYS DE-ENERGIZE THE ELECTRICAL PANEL, BEFORE
ATTENDINGTOANY PROBLEM.
24
Werner Finley
RECOMMENDED PREVENTIVE MAINTENANCE SCHEDULE:
Sl.
No.
Type of Operation
Weekly
Monthly
01
Liquid Temperature
*
02
Ambient Temperature
*
03
Current
*
04
Oil level
*
05
Supply Voltage
*
06
Compressor shell temp.
*
07
Setting of safety devices
*
08
Operations of all valves
*
09
Proper operation of controls
*
10
Contacts of motor starters
11
Evaporator Cleaning
12
Condenser Cleaning
13
Connections in Electrical cabin
Quarterly
Yearly
*
*
*
*
WARNINGS
!
The warranty is void if the wiring is not as per WFPL specification.
!
The warranty is void if any setting for protection devices are altered.
!
The warranty is void if any kind of mishandling of the unit is observed.
!
A blown circuit breaker / fuse or tripped protector indicates a short ground or
overload.
!
Before replacing the device or restarting the compressor, the cause must be found
& corrected.
!
Unqualified tampering with the controls can cause serious damage to the
equipment and void the warranty.
!
All safety trips should be immediately attended and ensured that the unit runs only
after rectification.
Do not reset the safety trip unless complete failure cause is detected & repaired.
25
Werner Finley
SERVICE
!
Chiller Cleaning
Remove all the doors [except the electrical cabin] of the chiller. Regularly clean
dust depositions and ensure no contamination of the fabricated body with rust or
water accumulation.
!
Electrical Cabin
Vacuum the cabin dust free. Do not use compressed air, moisture contents can
damage the components. Ensure for loose contacts.
!
Condenser Cleaning
The dust filter and condenser to be kept free from dust to enable good air
movement through the condenser. Use soft nylon brush & cleaning agents that
do not damage the copper tubes & aluminium fins. A gentle jet of compressed
air can also be used for condenser cleaning, ensuring no damage or bending of
fins.
!
Evaporator Cleaning
Coil type evaporator can be cleaned using water jet and nylon brush.
Shell & tube evaporator can be flushed with dilute caustic soda solution &
should be refreshed with water.
!
Strainer Cleaning
The liquid line strainer to be cleaned often to retain optimum flow across the
evaporator.
!
Liquid Quality
The liquid passing through the chiller shall not contain particle impurity, sludge,
etc., purity & filtration level of liquid is very critical.
26
Werner Finley
REFRIGERATION LINE SERVICE
Refrigerant leaks, compressor failures, choked drier/filter are common problems
that occur in refrigeration. Intensive care should be observed while rectifying such kind
of problems.
Refrigerant Leak:
! Release the remaining refrigerant from the system.
! Pressurize the circuit with dry nitrogen up to 300 PSI.
! Use an electronic leak detector or soap solution to detect the leak.
Arresting the Leak:
! If the leak is in flair joints, the joint should be completely replaced.
! Assure no cracks in the copper line, if present replace with new copper pipe of same
diameter.
! Flare the line, apply teflon tape & redo.
! If there is leak in the brazing joints, mark the area & release the nitrogen pressure.
! If elbows or U-bends are cracked, replace with new.
! If weak brazing observed, rework the joint.
! Now once again recharge the system with dry nitrogen.
! Check whether the leak has been positively arrested.
! In doubtful cases, leave the system under 300 PSI of Nitrogen overnight & check
for pressure retention after 12 hours.
! On confirmation release the nitrogen & subject the system for vacuuming.
Vacuuming
! Use a good quality vacuum pump especially designed for refrigeration.
! Run the vacuum pump till the gauge reads 29 PSI below 0 PSI in the vacuum
gauge.
! If the power is interrupted to the vacuum pump while in process, restart again.
! Close the valve of the refrigeration line before switching off the vacuum pump.
27
Werner Finley
Charging the Refrigerant
!
Shut down your equipment/machine while gas charging in progress.
!
Connect the charging tube between the suction service valve & refrigerant cylinder.
!
Remove the trapped air, by purging some refrigerant across the tube.
!
Without switching on the unit, idle charge the system till the pressure equalizes.
!
Before switching on the unit, ensure the fluid is at room temperature.
!
Switch on the unit and consistently observe the current drawn by the compressor.
!
Slowly charge the refrigerant by monitoring discharge / suction pressures &
compressor current.
!
Touch and feel the compressor shell for overheating.
!
Ensure the flow of the fluid through the evaporator.
!
Once the required liquid temperature matches to that of the rated suction/discharge
pressures & compressor current, stop the charging.
!
Close the refrigerant cylinder valve and the service valve.
!
Apply soap water for leak detection on the valves.
!
Observe optimum efficiency of the unit.
Compressor replacement:
!
Evacuate the refrigerant present in the line.
!
Cut the suction / discharge copper line or open the service valves on the compressor.
!
Seal the compressor & the refrigeration lines.
!
Replace the defective compressor, connect the suction/discharge lines & follow the
procedure for leak detection, vacuuming & charging of the refrigerant. Always
replace a new filter/drier along with the new compressor.
Choked Filter/Drier
!
Shut down the system, and close the inlet/outlet valves to the filter.
!
Loosen or cut open the lines & replace new filter/drier.
!
Release the trapped air by purging out the refrigerant across the filter.
!
While replacing the compressor or recharging with refrigerant, it is recommended to
replace a new filter/drier.
28
Werner Finley
NOTE:
!
Disconnect mains while compressor changing & gas charging procedure.
!
Use gas reclamation unit or cylinder dipped in ice bucket to retrieve
refrigerant.
!
Use refrigerant pressure/temperature chart while charging.
!
Use calibrated pressure gauges.
!
Read safety instructions before servicing.
!
Use original spare parts only.
!
Maintain record for each service.
!
Do not over charge / under charge the system.
!
Always take up service by bringing working fluid to room temperature
else moisture will enter the refrigeration system.
!
Check oil quantity & replace during service.
!
Always use dry nitrogen for pressure testing.
!
Use a regulating valve for the nitrogen cylinder.
!
If water has entered the system, thorough nitrogen flushing & extensive
vacuuming is necessary.
!
Leak testing of R22/ R134a, R407c/R404a can be done with refrigerant
charge also, as the standing pressure of the refrigerant is very much above
the atmospheric pressure.
!
Try to retrieve the refrigerant as much as possible.
29
Werner Finley
TEMPERATURE CONTROLLER SETTING
MAIN FUNCTIONS :
HOW TO SEE THE SETPOINT
SET
1.
Push and immediately release the SET key :
the display will show the Set Point value;
HOW TO CHANGE THE SETPOINT
1.
2.
3.
4.
Push the SET key for more than 2 seconds to change the set point value;
The value of the set point will be displayed and the d LED starts blinking;
To change the Set value push the or arrows within 10s.
To memorise the new set point value push the SET key again or wait 10s.
1. Set Point
Function : To set the cutout point of the controller.
Press & hold
set key for 4
seconds and
release.
Display will change to set point 1 and flash.
SZ-7552-P
Set Point 1 / 2
Min. Max. Fac.
0
0
0
0 C 50 C 0 C
R1 will flash along with respective setpoint 1 for compressor.
The setpoint 1 range can now be changed by usingthe UP/DOWN
keys. After achieving the desired range, press the set key and
you will see "- - - -" which confirms that the set point has been
stored in memory.
SZ-7552-P
Set Point 1 / 2
Min. Max.
0
0
-50 C 99 C
Fac.
0
0C
R2 will flash along with respective setpoint 2 for compressor 2.
In the similar manner use UP/DOWN key to set the desired range
and press set key to confirm the settings.
SET
31
Werner Finley
TEMPERATURE CONVERSION CHART
FAHRENHEIT TO CENTIGRADE/CENTIGRADE TO FAHRENHEIT
0
F
-22
-20.2
-18.4
-16.6
-14.8
-13
-11.2
-9.4
-7.6
-5.8
-4
-2.2
-0.4
1.4
3.2
5
6.8
8.6
10.4
12.2
14
15.8
17.6
19.4
21.2
23
24.8
26.6
28.4
30.2
32
33.8
35.6
37.4
39.2
41
42.8
44.6
46.4
48.2
50
51.8
53.6
55.4
57.2
59
60.8
62.6
0
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
-0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
C
-34.4
-33.9
-33.3
-32.8
-32.2
-31.7
-31.1
-30.6
-30
-29.4
-28.9
-28.3
-27.8
-27.2
-26.7
-26.1
-25.6
-25
-24.4
-23.9
-23.3
-22.8
-22.2
-21.7
-21.1
-20.6
-20
-19.4
-18.9
-18.3
-17.8
-17.2
-16.7
-16.1
-15.6
-15
-14.4
-13.9
-13.3
-12.8
-12.2
-11.7
-11.1
-10.6
-10
-9.4
-8.9
-8.3
0
F
64.4
66.2
68
69.8
71.6
73.4
75.2
77
78.8
80.6
82.4
84.2
86
87.8
89.6
91.4
93.2
95
96.8
98.6
100.4
102.2
104
105.8
107.6
109.4
111.2
113
114.8
116.6
118.4
120.2
122
123.8
125.6
127.4
129.2
131
132.8
134.6
136.4
138.2
140
141.8
143.6
145.4
147.2
149
0
18
19
2
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
C
-7.8
-7.2
-6.7
-6.1
-5.6
-5
-4.4
-3.9
-3.3
-2.8
-2.2
-1.7
-1.1
-0.6
0
0.6
1.1
1.7
2.2
2.8
3.3
3.9
4.4
5
5.6
6.1
6.7
7.2
7.8
8.3
8.9
9.4
10
10.6
11.1
11.7
12.2
12.8
13.3
13.9
14.4
15
15.6
16.1
16.7
17.2
17.8
18.3
0
F
150.8
152.6
154.4
156.2
158
159.8
161.6
163.4
165.2
167
168.8
170.6
172.4
174.2
176
177.8
179.6
181.4
183.2
185
186.8
188.8
190.4
192.2
194
195.8
198.6
199.4
201.2
203
204.8
206.6
208.4
210.2
212
213.8
215.6
217.4
219.2
221
222.8
224.6
226.4
228.2
230
231.8
233.6
235.4
0
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
9
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
C
18.9
19.4
20
20.6
21.1
21.7
22.2
22.8
23.3
23.9
24.4
25
25.6
26.1
26.7
27.2
27.8
28.3
28.9
29.4
30
30.6
31.1
31.7
32.2
32.8
33.3
33.9
34.4
35
35.6
36.1
36.7
37.2
37.8
38.3
38.9
39.4
40
40.6
41.1
41.7
42.2
42.8
43.3
43.9
44.4
45
0
F
237.2
239
240.8
242.6
244.4
246.2
248
249.8
251.6
253.4
255.2
257
258.8
260.6
262.4
264.2
266
267.8
269.6
271.4
273.2
275
276.8
278.6
280.4
282.2
284
285.8
287.6
289.4
291.2
293
294.8
296.6
298.4
300.2
302
303.8
3.5.6
307.4
309.2
311
312.8
314.6
316.4
318.2
320
321.8
0
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
C
45.6
46.1
16.7
47.2
47.8
48.3
48.9
49.4
50
50.6
51.1
51.7
52.2
52.8
53.3
53.9
54.4
55
55.6
56.1
56.7
57.2
57.8
58.3
58.9
59.4
60
60.6
61.1
61.7
62.2
62.8
63.3
63.9
64.4
65
65.6
66.1
66.7
67.2
67.8
68.3
68.9
69.4
70
70.6
71.1
71.7
0
F
323.6
325.4
327.2
329
330.8
332.6
334.4
336.2
338
339.8
341.6
343.4
345.2
347
348.8
350.6
352.4
354.2
356
357.8
359.6
361.4
363.2
365
366.8
368.6
370.4
372.2
374
375.8
377.6
379.4
381.2
383
384.8
386.6
388.8
390.2
392
393.8
395.6
397.4
399.2
401
402.8
404.6
406.4
408.2
0
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
C
72.2
72.8
73.3
73.9
74.4
75
75.6
76.1
76.7
77.2
77.8
78.3
78.9
79.4
80
80.6
81.1
81.7
82.2
82.8
83.3
83.9
84.4
85
85.6
86.1
86.7
87.2
87.8
88.3
88.9
89.4
90
90.6
91.1
91.7
92.2
92.8
93.3
93.9
94.4
95
95.6
96.1
96.7
97.2
97.8
98.3
0
F
410
411.8
413.6
415.4
417.4
419
420.8
422.6
424.4
426.2
428
437
446
455
464
473
482
491
500
509
518
527
536
545
554
563
572
581
590
599
608
617
626
635
644
653
662
671
680
689
698
707
716
725
734
743
752
761
0
210
211
212
213
214
215
216
217
218
219
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
360
365
370
375
380
385
390
395
400
405
C
98.9
99.4
100
100.6
101.1
101.7
102.2
102.8
103.3
103.9
104.4
107.2
110
112.8
115.6
118.3
121.1
123.9
126.7
129.4
132.2
135
137.8
140.6
143.3
146.1
148.9
151.7
154.4
157.2
160
162.8
165.6
168.3
171.1
173.9
176.7
179.4
182.2
185
187.8
190.6
193.3
196.1
198.9
201.7
204.4
207.2
0
For example, to fine the Centigrade equivalent of 104 F., locate the figure 104 in the central columns of the table
0
and read off the temperature in degrees Centigrade in the coulumn immediately to the right (headed C,)
0
0
namely, 40 C. Similarly, to fine the Fahrenheit equivalent of 40 C, locate the figure 40 in the central
0
columns and read off the temperature in degrees Fahrenheit in the left-hand column (headed F), namely
32
33
6.0
2.4*
0.7
2.0
5.5
7.8
10.8
13.8
17.1
18.5
20.0
21.5
23.0
24.6
26.3
28.0
29.8
31.6
33.5
34.0*
34.8*
36.0
37.4
38.1
39.4
40.3
41.6
42.5
43.6
44.7
21.6
20.1
18.5
16.7
14.6
12.3
9.7
6.7
3.5
2.3
0.8*
0.4
1.1
1.8
2.6
3.5
4.4
5.3
6.2
6.7
7.2
7.8
8.3
8.8
9.3
9.9
10.5
11.0
11.6
12.2
12.0
9.2
6.1
2.7*
0.5
2.6
4.9
7.4
10.1
11.3
12.5
13.8
15.1
16.5
17.9
19.3
20.8
22.4
24.0
24.8
25.6
26.4
27.3
28.2
29.1
30.0
30.9
31.8
32.8
33.7
19.0
17.3
15.5
13.3
11.0
8.4
5.5
2.3
0.6
1.3
2.0
2.8
3.6
4.5
5.4
6.3
7.2
8.2
9.2
9.7
10.2
10.7
11.2
11.8
12.3
12.9
13.5
14.0
14.6
15.2
-60
-55
-50
-45
-40
-35
-30
-25
-20
-18
-16
-14
-12
-10
-8
-6
-4
-2
0
1
2
3
4
5
6
7
8
9
10
11
12
15.8
16.4
17.1
17.7
18.4
19.0
19.7
20.4
21.0
21.7
22.4
23.2
23.9
24.6
25.4
26.1
26.9
27.7
28.4
29.2
30.1
30.9
31.7
37.6
33.4
34.3
35.2
36.1
37.0
37.9
Temperature
0
F
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
34.7
35.7
36.7
37.7
36.7
39.8
40.8
41.9
43.0
44.1
45.3
46.4
47.6
48.8
49.9
51.2
52.4
53.6
54.9
56.2
57.6
58.8
60.1
61.5
62.8
64.2
65.6
67.1
68.5
70
22
12.8
13.4
14.0
14.1
15.3
16.0
16.7
17.3
18.0
18.7
19.4
20.2
20.9
21.7
22.4
23.2
24.0
24.8
25.6
26.4
27.3
28.1
29.0
29.9
31.29
32.21
33.14
34.08
35.1
36.01
134a
46.0
47.1
48.3
49.5
50.7
52.0
53.1
54.5
55.6
57.1
58.2
59.8
60.9
62.8
63.6
65.5
66.5
68.4
69.4
71.4
72.3
74.6
75.4
77.7
78.5
80.9
81.8
84.3
85.1
87.7
404A
REFRIGERANT
* Figures above this indicate Vacuum Inches of mercury. Other in Rounds for Square Indh (Psig.)
404A
134a
22
12
REFRIGERANT
Temperature
0
F
TEMPERATURE PRESSURE CHART
42
43
44
45
46
47
48
49
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
Temperature
0
F
38.8
39.8
40.7
41.7
42.6
43.6
44.6
45.7
46.7
52.0
57.7
63.8
70.2
77.0
84.2
91.8
99.8
100.2
117.2
126.6
136.4
146.8
157.6
169.1
181.0
193.5
206.6
220.3
234.6
249.5
12
71.4
73.0
74.6
76.0
77.6
79.2
80.8
82.4
84.0
92.6
101.6
111.2
121.4
132.2
143.6
155.7
168.4
181.8
195.9
210.8
226.4
242.7
259.9
277.9
296.8
316.6
337.2
358.9
381.5
405.1
22
37.0
38.0
39.02
40.1
41.1
42.16
43.23
44.33
45.5
51.2
57.4
64.1
71.1
78.7
86.7
95.3
104.3
114.0
129.2
135.0
146.4
158.4
171.2
189.6
198.7
213.6
229.2
245.5
262.9
281.1
134a
88.5
91.2
91.9
94.8
95.5
98.5
99.2
102.3
104.2
114.3
125.0
136.2
148.0
160.7
174.0
188.2
203.0
218.7
235.0
252.6
271.0
290.0
311.1
331.4
354
377.1
402
427.6
454.9
483.7
404A
REFRIGERANT
Werner Finley
Descargar