Subido por Bryan Fernando

ISGTLA17-003

Anuncio
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
Droop Control Based on Fuzzy Logic for Voltage
and Frequency Regulation in Isolated Microgrids
Gerônimo B. Alexandre
João Batista M. dos Santos and Antonio M. N. Lima
Coordination of Control and Industrial Processes
Federal Institute of Pernambuco - IFPE
Garanhuns, Pernambuco, Brazil.
[email protected]
Department of Electrical Engineering
Federal University of Campina Grande - UFCG
Campina Grande, Paraiba, Brazil.
{joaobatista, amnlima}@dee.ufcg.edu.br
Abstract— This paper proposes and validates a control
strategy for simultaneous regulation of voltage and frequency in
isolated microgrid. The proposed technique is based on the
conventional Generalized Droop Control (GDC) structure,
assisted by a fuzzy logic technique, which is used to determine the
line parameters. An optimum tuning method is also proposed to
adjust the controller gains which take into account the actual
microgrid operating conditions and the legal prescriptions
imposed for the voltage and frequency fluctuations of the power
provided for the consumer. Simulation test results obtained for
reference systems (IEEE 3 node and IEEE 14 node) show the
correctness of the design method as well as the feasibility of the
proposed droop controller. With the GDC based on fuzzy logic it
was possible to track the dynamic profile of the load, stabilizing
the voltage and frequency of the microgrid, at different loadswitching scenarios.
Index Terms— GDC, Optimum Tuning, Fuzzy Logic,
Stability and Operation of MG.
A
I. INTRODUCTION
MICROGRID (MG) consists of a low-voltage network
with multiple micro-generators and local loads installed.
Some examples are islands, industries, or remote villages
where the energy is obtained from renewable sources like
photovoltaic systems which require some electronic converter
for power processing. Under normal operating conditions, the
MG is connected to the medium voltage grid. However,
whenever a breakdown occurs, the MG starts to operate on the
isolated operational mode which is inherently autonomous. In
these cases the local loads must be fed only by the microgenerators installed in the MG, and thus the system operation
will be based on a feedback control law which must be
designed to meet the consumer demands.
At the isolated operational mode, the dynamic switching of
loads produces voltage and frequency fluctuations [2]-[5]. In
the case of the traditional Electrical Power System (EPS), this
problem is solved by controlling the excitation of the
synchronous generator. In the case of decentralized EPS, since
there is usually no synchronous generator installed in the MG,
the problem must be solved by controlling individually each
one of the micro-generators. This controller must regulate not
only the voltage and frequency fluctuations, but also the power
splitting between micro-generators [6]-[12].
This paper proposes a control strategy for regulating the
voltage and frequency of a MG when the dynamic load
switching takes place or when the connection to the medium
voltage grid is lost. This control strategy uses the conventional
GDC structure but eliminates the dependency of the line
parameters by using fuzzy logic. The proposed technique also
uses as reference the nominal values of the converter’s
apparent power; the values of the charge’s apparent power; the
estimated line parameters; the control set-points for voltage,
frequency and active/reactive power; and the legal
prescriptions imposed for the voltage and frequency
fluctuations. Simulation test results obtained for reference
systems are used to show the correctness of the design method
as well as the feasibility of the proposed droop controller. One
important feature of this controller is the fast accommodation
of operational conditions on the occasion of an abrupt variation
on the active and reactive power.
The contributions of this paper are: Fuzzy Generalized
Droop controller design for simultaneous regulation of voltage
and frequency; Methodology for tuning the fuzzy GDC
controller, based on MG operating conditions; Use of the fuzzy
logic method to estimate the MG line parameters;
Mathematical formulation of the control region and operational
stability of MG; Determination of minimum conditions for
sample update rates for each microgrid component.
This paper is organized as follows: First, we discuss the
strategy control project in Section II. Then, in Section III, we
present the test scenarios and the case studies that validated the
Droop controller based on fuzzy logic. In this Section, we also
present the results of the simulations and a discussion about the
controller, focusing on the stability and in its physical
implementation in hardware. Finally, in Section IV, we present
the conclusions and the possible developments of this project
in future works.
II. THE ADAPTIVE GENERALIZED DROOP CONTROLER
Fig. 1 shows the equivalent circuit for a micro generator
connected at the common coupling point of the AC bus. The
micro generator is connected to the load dynamic by the line
impedance, . At point S the voltage supplied by DG is
=
°
and at point L the voltage delivered at dynamic load is
°
=
. Where, and are the voltage generated and
the
phase
angle
of
the
voltage
generated
978-1-5386-3312-0/17/$31.00 ©2017 IEEE
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
respectively,
is the voltage at the load and
the line impedance, . Considering = ‖ ‖
is the angle of
= + .
In this scenario the individual Droop control
− can be characterized by [3]:
−
The fundamental active and reactive powers injected to the
grid by the DG (P and Q, respectively) can be expressed as
follows [3] and [7]:
=
(
+
sin + (
−
+
cos ) +
−
−
s
-
Controlled AC
voltage source
Micro generator
S
(1)
cos )
(2)
Variable Load
LINE
+
sin
Measurements
L
O
A
D
P and Q variant
=
−
POWER
CONTROL
Fig. 1. Equivalent circuit of a DG unit connected to the common ac bus. The
micro generator is a controlled power source for which one may dynamically
adjust its amplitude (A) and frequency (f).
sin
In practical applications,
decoupling approximation (
be considered [6], [7]:
=
Δ +
(
−
)
(6)
In the (7) and (8) show that in MGs with inductive
behavior, the active power
must be controlled by the
regulating and is controlled by . Thus, the fundamental
active and reactive powers can be controlled by the phase
angle and magnitude of the DG unit output voltage,
respectively. These strategies are known in the literature as,
respectively,
−
and
− Droop control techniques.
These approximations are valid for shorter transmission lines
(up to 80 km long) represented by an RL circuit, typical of low
voltage distribution systems, which are inserted micro grid.
)
(8)
Δ
−
+
(9)
Δ
+
(10)
Δ and Δ
= −1⁄ ,
= −1⁄ ;
are,
Where:
respectively, the voltage and frequency deviations of the micro
index helps us to identify the
generator. In (9) and (10), the
voltage and frequency simultaneous control. After some
algebraic manipulations from (9) and (10) one may obtain
Δ =
=
Δ
+
Σ
1
−
1
+
−
Δ
−
+
(11)
Δ −
(12)
+
+
-
Σ
+
+
Σ
+
-
Σ
(5)
−
Δ +
is normally small; thus, a /
≈ 1 and
≈ ) can
≈
≈
(4)
(7)
For the general case for
and
(i.e., no approximated
relationship) the instantaneous active and reactive powers
( =
and
=
,
instantaneous
measurements) are represented [3]:
(3)
cos −
≈
and
where,
and
are the nominal values of the MG voltage
and
are the control set-points for active
and frequency;
and reactive power respectively;
and
are the droop
controller coefficients for the GD active and reactive power.
In the (1) and (2) display the dependence of the voltage
and the angle of the inverter output power with the active and
reactive powers. Assuming a mainly inductive electrical
system ( ≈
and
≈ 90°), the fundamental active and
reactive powers can be expressed as [3]:
≈
)
( −
=−
=
FUZZY
GDC
( −
=−
−
+
+
Σ +
-
Σ
+
-
Fig. 2. Generalized Droop Control block diagram.
From (11) it is possible to observe that the
gain directly
ponderation coefficients
alters (has effects on) the Δ and
on the second and third terms, respectively.
Fig. 2 illustrates the block diagram of the Generalized
Droop Controller, implemented by in (11) and (12). So the
Controller has three gains, which must be tuned to adjust realtime fluctuations of voltage and frequency to legal conditions
in response to the request for active and reactive power
requested by the dynamic load. One important feature of this
controller is the fast accommodation of operational conditions
on the occasion of an abrupt variation on the active and
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
reactive power, setting the voltage and frequency fluctuations
at the voltage source inverter (VSI) output.
A. Description of the Control Strategy
The Generalized Droop controller based on fuzzy logic
proposed is illustrated by the block diagram of Fig. 3. It is
worth mentioning that this control structure is installed at each
microsource (DG) unit; if there are microsources present in
the MG, there will be local controllers.
Micro generator
s
+
S
LINE
Variable Load
L
O
A
D
Controller AC
voltage source
The controllers of each micro generators interact with each
other and with the central control located in the operation
center through a low band bidirectional communications
channel. This interaction was implemented through a state
machine, allowing the active power sharing among the several
micro generators installed in the MG.
MF degree
Measurements
Step (D): Usage of the Conventional GDC structure – with
the optimal gains determined in Step (C), the proposed
structure uses the droop strategy of control illustrated in Fig.
2, where the GDC receives the measured and , provides
the amplitude and frequency for the generation of the
sinusoidal signal, used as a modulating signal in the sinusoidal
bipolar PWM (Pulse Width Modulation) strategy.
Figure 2
Droop controller
1
L
0.8
0.6
M
H
MH
0.4
0.2
Sinusoidal signal
0
0
Calculates
P& Q
2
4
6
8
10
12
14
16
18
20
Voltage of variation (V)
Tunning of the controller
1
MF degree
Fuzzy
estimator
ML
−
)
(13)
=
sin(
−
)
(14)
where
and
are the active and reactive
powers measured instantly,
and
are, respectively, the
and
are the angles of
voltage and current modules, and
the voltage and current phases.
Step (B): Calculation of the line parameters – The fuzzy
estimator receives as inputs: the active power error (∆ =
−
), the reactive power error (∆ =
−
) and the voltage and frequency deviations produced
by the Conventional GDC, producing output to the line
impedance seen from the inverter terminals (impedance of the
Thévenin equivalent circuit). In addition to the estimated line
impedance value, the parameter estimator provides the graph
of the estimated current and the estimation error for the
monitoring of the quality of the estimation by the microgrid
operator.
Step (C): Controller tuning - This block sets the optimal
controller gains based on the operational conditions of the
plant (isolated MG) according (19), (20) and (21).
0
2
4
6
8
10
12
14
16
Reactive Power of variation (Var)
MF degree
(a)
1
M
L
0.5
H
0
0
MF degree
cos(
0
5
10
15
20
25
30
Active Power of Variation (W)
35
40
1
M
L
H
0.5
0
0
0.2
0.4
0.6
0.8
1
1.2
Frequency of variation (Hz)
1.4
1.6
1.8
2
(b)
1
MF degree
=
H
MH
0.4
0.2
L
M
ML
0.5
H
MH
0
0
1
MF degree
Step (A) Calculation of the active and reactive power from
the measured data (voltage and current at the output of the
LCL filter), being given as,
M
ML
0.6
Fig. 3. Block diagram for the proposed fuzzy GDC Controller. The fuzzy
logic calculates the line parameters (R and X) from the voltage (∆ =
±20 ) and frequency (∆ = ±2 ) deviations established by law and the
active (∆ ) and reactive power error (∆ ).
The control structure of the GDC based on fuzzy logic
operates in four ordered steps:
L
0.8
1
2
-4
x 10
R (Ohms)
L
M
ML
H
MH
0.5
0
0
0.2
0.4
0.6
0.8
1
X (Ohms)
1.2
1.4
1.6
1.8
2
-3
x 10
(c)
Fig. 4. Membership functions (MF) for the inputs, (a) Voltage deviation and
reactive power; (b) frequency and active power deviation; (c) for the R and
X outputs. L=Low; ML = Medium Low; M = Medium; MH = Medium High;
A = High.
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
B. Calculation of Line Paramenters Using Fuzzy Logic
The operating conditions determine the operational regions
(2D regions) of the
and
distributed generation, as
shown in Fig. 6.
The Fuzzy system implemented to map the input data (∆ ,
∆ , ∆ and ∆ ) in the line parameters (R and X), is a system
with four inputs, two output, 40 rules, Mandani method and
method Of the centroid for Defuzzyfication. The ∆ and ∆
inputs each with five membership functions, the ∆ and ∆
inputs each with three membership functions and the outputs
(R and X) with five membership functions respectively (See
Fig. 4). In the design of the Fuzzy GDC controller were used
the functions of triangular and trapezoidal membership because
they are the most popular for the Mandani method. The the
logic used in the rule base follows the reasoning,
The gains of the controller are defined for the minimum
and maximum conditions of the operation, which define a
region of control in the shape of a parallelepiped, for this case,
with vertices at points.
=(
;
;
),
=
(
;
;
),
=(
;
;
),
=
;
;
),
=(
;
;
),
=
(
(
;
;
),
=(
;
;
) and
=
;
;
). The gains ,
and
that define
(
this region of control are set by in (19), (20) and (21).
IF ∆ =
AND ∆
THEN = E =
From the individual droop control
droop’s definition,
=
AND ∆ =
AND ∆ =
Where: , = 1, 2,3 and , = 1, 2, . . . 5. ∆ , ∆ , ∆ and ∆
are the antecedents; R and X are consequent.
=−
C. The Tuning of the Fuzzy GDC Controller
=−
The adjustment of the gains of the Fuzzy GDC controller is
motivated by the micro generator operating conditions and the
MG restrictions for the voltage and frequency levels imposed
by the legislation ([1]: ∆ = 2
e ∆ = 20 ). The block of
the Fig. 5 was designed to determine the optimal gains of the
Droop Control structure of the Fig. 2.
1
∴
=−
∴
=−
and
1
−
(15)
1
(16)
Substituting (21) and (22) into (6) and (7),
∆ =−
(
−
∆
(
−
=−
Isolating
Equation (19)
Equation (20)
Equation (21a or 21b)
and
)→∆ =
)→∆
1
(
1
=
)
−
(
(17)
)
−
(18)
, it follows as,
=
=
Fig. 5. Generalized Droop Control tuning block diagram.
The block in Fig. 5 receives as input: the reactive and
active powers measured in the electrical network
(instantaneous voltage and frequency measured at the inverter
output); the tolerable minimum and maximum values for the
operational voltage and frequency; the control set-points –
where
is the active power reference,
is the reference of
the reactive power, is the reference of the electric frequency
( =
= 60 ), and
=
= 220 is the
reference of the electrical voltage; and the estimated line
parameters. As to the output, the block provides the
,
controller gains.
and
1
−
(
−
∆
)
(
−
∆
)
(19)
(20)
According to the concept of generalized droop, the
gain is a variable influenced by the line parameters, especially
by the dissipative effect of the line (Joule effect). Applying
(19) and (20) in (11); (19) and (20) in (12), it follows as,
=
=−
Δ (
∆
−
(
(1 − )
)Δ (
−
) +
,
=
‖ ‖
)−(
−
∆
(
(21 )
−
−
)
)
(21 )
gain can be adjusted by
Equation (21) shows that the
the active power, as well as by the reactive power, or that it
can be calculated as an arithmetic mean of the two values, that
is
=
.
To set the 3D control region for the ,
and
gains, it
is necessary to evaluate the extremes of the operational region
(See Fig. 6), setting the minimum and maximum values.
Evaluating minimum and maximum
Fig. 6.
and
operational regions.
values,
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
=
→
(22 )
∆
−
=
=0
→
=
=
→
values,
(23 )
∆
−
=
(23 )
∆
values from the
=0
,
Evaluating minimum and maximum
active and reactive power, when = 0
=−
(1 − )
Δ
(24 )
∆
When the active and reactive powers assume the nominal
is:
values, the gain
=
Δ (
−
( −
∆
)Δ ( −
) +
)−(
∆
(
)
−
)
−
Fig. 7. Micro grid with three micro generators and two banks of loads.
(24 )
The quality of the controller tuning described in this
Section will be robust whenever the estimation of the line
and
gains
parameters is robust. This is the case because
are influenced, respectively, by the active – see in (19) – and
reactive power – see in (20). While the gain
is dependent
on the active power and on the reactive power – see in (21), it
is also influenced by the line parameters.
III. TEST SCENARIOS AND CASE STUDIES
A. 3-Bus Test MG
In order to test and evaluate the effectiveness of the
Generalized Droop control based on Fuzzy Logic, it was
initially evaluated in the 3-bus MG shown in Fig. 7 [3] (IEEE
standard) with loads with a purely inductive behavior
considering: 0.6 kVar initially for load 1, located in bus 1 and
0.2 kVar initially for load 2, located in bus 3. It should be
noted that the nominal apparent power at the inverter output
(control references) of each micro generator considered was of
the S=3+j0.85 kVA, because during load-bank switching,
consumer demand S=1+j0.8 kVA.
315
310
GD1
GD2
GD3
305
300
0.0
0.2
0.4
Time instant (s)
.
.
.
.
.
−
−
−
−
−
.
.
.
.
.
+
) [kVA]
2+
2−
2+
2+
2+
1
1
1
1
1
1
1.2
1.4
1.6
60
59.9
0.0
0.2
0.4
0.6
0.8
Time (s)
Fig. 8. 3-Bus Voltage and frequency profiles.
Impedance (Ω)
0.1 + 1
0.1 − 1
0.1 + 0.5
0.1 + 1
0.1 + 1
Observing Fig. 8, the MG operates within the prescribed
values for voltage and frequency fluctuations, operating
0.8
GD1
GD2
GD3
LOAD MAPPING IN R AND X VALUES.
( =
0.6
60.1
Table I maps the active and reactive power profile
representing the local variable load into resistance and
reactance values (inductive or capacitive).
TABLE I.
and ∆
= ±5
60.15 , ∆ =
(22 )
∆
Evaluating minimum and maximum
between ∆
= ±10 , ∆
= ±6
for tensions and between 59.85
±0.3
for frequency deviations.
Voltage (Vrms)
=
→
Frequency (Hz)
=0
Fig. 9. 14-bus microgrid [3].
1
1.2
1.4
1.6
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
B. 14-Bus Test MG
In order to test and evaluate the effectiveness of the GDC
based on Fuzzy logic, it was initially evaluated in the 14-bus
MG shown in Fig. 9 [3] (IEEE standard / CIGRE). The
dynamic loads are connected to buses 7, 8 and 9 and their
respective switching times are shown in Table III. The fixed
load values connected to these buses are shown in Table II.
The voltage and frequency profiles for this scenario are
illustrated in Fig. 10. The microgrid operates within the
operational range prescribed by law, showing fluctuations of
±10 V for voltage and ±0.02 Hz for frequency.
TABLE II.
FIXED LOADS CONNECTED IN THE 14-BUS MG.
Bus
2+ 1
2.5 + 0.5
5 + 2.5
TABLE III.
5 + 2.5
This research was funded by CNPq and CAPES, Brazil.
VARIABLE LOADS CONNECTED IN THE 14-BUS MG.
REFERENCES
Load 2 in bus 9
[kVA]
Load 3 in bus 7
[kVA]
−
−
−
−
−
−
3
5+ 2
8+ 3
6
4 + 2.5
2+ 2
2
4+ 2
6
2
5
4+ 2
3
3 + 1.5
2.5
1.5
4
5+ 3
.
.
.
.
.
.
GD3
GD4
GD5
GD6
GD7
GD8
GD
GD10
GD11
GD12
GD13
GD14
Upper Limit
320
Voltage (Vpp)
ACKNOWLEDGEMENTS
Load 1 in bus 8
[kVA]
GD2
The proposed solution proved to be efficient when
evaluated not only on several MG’s topologies, but also in
multiple test scenarios of dynamic switching of loads that
operate in closed loop: The Adaptive GDC was able to
preserve both the stability of the MG operation, the
synchronization between micro generators installed in MG and
the generation-consumption balance, while met the legal
prescriptions to voltage and frequency fluctuations.
2+ 1
Time instant
(s)
.
.
.
.
.
IV. CONCLUSIONS
Considering that the proposed control strategy does not
depend on the topology of microgrid under study, this can be
applied to any generic microgrid, since the tuning of controllers
is made in accordance with the operating conditions of the MG.
Load (kVA)
13
strategy is updated at a rate of the 10 seconds, the plant
(MG) is updated at the rate of 10 seconds and the control
strategy is updated at the rate of 10 seconds.
[1]
ABNT NBR 5410:2005, “Electrical installations of low voltage”, 2005.
[2]
H. Bevrani, M. Watanabe, and Y. Mitani, “Micro grid controls,” in Standard
Handbook for Electrical Engineers, H. W. Beatty, Ed., 16 Edition New York:
McGraw Hill, 2012, Section 16.
[3]
H. Bevrani and S. Shokoohi, “An intelligent droop control for simultaneous
voltage and frequency regulation in islanded microgrids,” IEEE Transactions on
Smart Grid. 2013; pp. 1505–13.
[4]
K. De Brabandere, B. Bolsens, J. Van den Keybus, A. Woyte, J. Driesen, and R.
Belmans, “A voltage and frequency droop control method for parallel inverters,”
IEEE Transactions on Power Electronics, vol. 22, pp. 1107–1115, 2007.
[5]
J. M. Guerrero, J. C. Vasquez, J. Matas,. G. de Vicuña and M. Castilla
“Hierarchical control of droop-controlled AC and DC micro grids—A general
approach toward standardization,” IEEE Transactions on Industrial Electronics,
vol. 58, pp. 158–172, 2011.
[6]
J. M. Guerrero, J. Matas, L. G. Vicuña, M. Castilla, J. Miret, “Decentralized
Control for Parallel Operation of Distributed Generation Inverters Using Resistive
Output Impedance,” IEEE Transaction on Industrial Electronics, vol. 54, 2 (2007),
pp. 994-1004.
[7]
H. Morteza, E. Mahmound & S. Reza, “Autonomous Control of Inverter-Interfaced
Distributed Generation Units for Power Quality Enhancement in Islanded
MicroGrids,” International Journal of Mechatronics, Electrical and Computer
Technology, Vol. 4 (10), January, 2014, ISSN: 2305-0543.
[8]
J. A. P Lopes, C. L. Moreira and A. G. Madureira, “Defining control strategies for
Micro Grids islanded operation,” IEEE Transactions on Power Systems, vol. 21, nº
2, pp. 916–924, May 2006.
[9]
Y. Mohamed and E. El-Saadany, “Adaptive decentralized droop controller to
preserve power sharing stability of paralleled inverters in distributed generation
micro grids,” IEEE Transactions Power Electronics, vol. 23, nº 6, pp. 2806–2816,
Nov. 2008.
310
300
290
Lower Limit
280
0
0.2
GD2
GD3
0.4
GD4
GD5
0.6
GD6
0.8
GD7
GD8
1
GD9
GD10
1.2
GD11
1.4
GD12
GD13
GD14
Frequency (Hz)
60.2
60.1
60
59.9
59.8
0
0.2
0.4
0.6
0.8
1
1.2
1.4
Time (s)
Fig.10. 14-Bus Voltage and frequency profiles.
The digital platform chosen to simulate the operation of an
isolated MG was the Simulink Dynamics Systems of
MathWorks MATLAB package, version 7.11 (R2014a) using
variable integration step, ODE3-Bogacki-Shampine Solver
integration method, duration of the 2 seconds. The Fuzzy
estimator is updated at a rate of the 10 seconds, the PWM
[10] N. Pogaku, M. Prodanovic and T. C. Green, “Modeling, analysis and testing of
autonomous operation of an inverter-based micro grid,” IEEE Transactions on
Power Electronics, vol. 22, pp. 613–625, 2007.
[11] J. Vasquez, J. Guerrero, A. Luna, P. Rodriguez and R. Teodorescu, “Adaptive
droop control applied to voltage-source inverters operating in grid-connected and
islanded modes,” IEEE Transactions Industrial Electronics, vol. 56, nº 10, pp.
4088–4096, October 2009.
[12] Q.-C. Zhong, “Robust droop controller for accurate proportional load sharing
among inverters operated in parallel,” IEEE Transactions Industrial Electronics,
vol. 60, nº 4, pp. 1281–1290, April, 2013.
Descargar