warning / attention / aviso

Anuncio
WARNING / ATTENTION / AVISO
Suction Entrapment Hazard: Suction in suction outlets and/or suction outlet
covers which are damaged, broken, cracked, missing, or unsecured can cause
severe injury and/or death due to the following entrapment hazards:
Hair Entrapment- Hair can become entangled in suction outlet cover.
Limb Entrapment- A limb inserted into an opening of a suction outlet sump or
suction outlet cover that is damaged, broken, cracked, missing or not securely
attached can result in a mechanical bind or swelling of the limb.
Body Suction Entrapment- A negative pressure applied to a large portion of the body or limbs
can result in an entrapment.
Evisceration/ Disembowelment Entrapment- A negative pressure applied directly to the intestines
through an unprotected suction outlet sump or suction outlet cover which is damaged, broken, cracked,
missing, or unsecured can result in evisceration/disembowelment entrapment.
Mechanical Entrapment- There is a potential for jewelry, swimsuits, hair decorations, finger, toe or
knuckle to be caught in an opening of a suction outlet cover resulting in mechanical entrapment.
READ
FIRST
NGE R
DA
AR
D
DRO
W
NI
Z
STOP!
Read and Follow All Instructions. Failure to Follow Instructions can cause Severe Injury or Death.
NG HA
To Reduce the Risk of Entrapment Hazards:
A minimum of two functioning suction outlets per pump must be installed. Suction Outlets in the same
?
plane (i.e. Floor or wall), must be installed a minimum of three feet [1 meter] apart, from near point to
near point.
Dual suction fittings shall be placed in such locations and distances to avoid “dual blockage” by a user.
?
Dual suction fittings shall not be located on seating areas or on the backrests for such seating areas.
?
The maximum system flow rate shall not exceed the rating of any listed (per ASME/ANSI A112.19.8M?
1987, ASME A112.19.8M-2007) suction outlet cover installed.
Never use Pool or Spa if any suction outlet component is damaged, broken, cracked, missing or not
?
securely attached.
Replace damaged, broken, cracked, missing, or not securely attached suction outlet components
?
immediately.
In addition to two or more suction outlets per pump installed in accordance with the latest APSP
?
standards and CPSC guidelines, follow all National, State, and Local codes applicable.
CAUTION - Do not exceed maximum flow rate stated on suction fitting.
?
When replacing pump, use pump with similar flow curve and horsepower.
Doc #3000 Suction Hazard Warning Label-Jan-09-2
WARNING / ATTENTION / AVISO
STOP!
REPLACEMENT
READ
FIRST
Instruction for Installation of Frame and Grate.
Model # MLD-FGD-1212
SUBMERGED SUCTION OUTLETS
MAXIMUM RATED FLOW RATES –ACCEPTABLE PIPE SIZE
FLOOR: 365 GPM – 6 INCH
WALL: 340 GPM – 6 INCH
Read instructions before installing. This cover must be properly installed using supplied stainless-steel screws. When using other than
the supplied frame and fasteners, the design professional certifying the sump must also approve the type and installation of frame and
fasteners used. Close pool immediately if cover breaks or becomes loose and replace with a new cover. Failure to maintain cover can
result in severe injury or death.
When installing the grate without using the supplied frame, the grate must be anchored into a sturdy existing frame using the hardware
supplied.
Use one of the retrofit options for anchoring listed below, depending on the type of existing frame.
EXISTING FRAMES WITH SAME FASTENER LOCATIONS
Use newly supplied #10 self tapping screws into existing #8 fastening holes.
/OR/
Drill out existing fastening holes with 7/32" drill bit and install supplied brass
inserts by lightly tapping with hammer. Use newly supplied #8-32 bolts to fasten grate.
NGE R
DA
Use #2 Square head screw driver and tighten to 60 in/lbs torque.
EXISTING FRAME REPLACEMENT
Grout
(Concrete Mixture)
D
AR
NI
Z
W
Use the fasteners provided to insure a minimum of 3 complete turns
into the receiving material or inserts. Ensure screw heads are flush.
DRO
If the existing frame is not compatible with the grate, or is damaged during retrofit
attempt, remove existing frame and install supplied frame using instructions included
for new construction. Secure grate using supplied 1/4"x20x3/4" screws using #2
square head screw driver and tighten to 60 in/lbs torque.
NG HA
VGB-2008
1/4"x20x3/4" Screw
(Modelo# BOLT-01-SS)
Frame
Domed Grate
Brass Insert
(Modelo# BRASS-TI)
CAUTION:
Floor or Wall Concrete
Total head loss at maximum flow rate is less than 0.1 PSI.
The suction fitting fasteners must be
observed for damage or tampering before
each use of this facility and or at least annually.
Link to general certification of conformity to VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Call 1.800.897.6160
for inquiries or assistance
The Wizards of Aquatic Technology
Doc. # 2005 Replacement Domed Grate 1212 Rev. 03-09-1
Visit us at: www.lawsonaquatics.com
STOP!
READ
FIRST
WARNING / ATTENTION / AVISO
REPLACEMENT
Instruction for Installation into Existing Concrete Ledge or Frame.
Model # MLD-FGD-1818
SUBMERGED SUCTION OUTLETS
MAXIMUM RATED FLOW RATES –ACCEPTABLE PIPE SIZE
FLOOR: 816 GPM; WALL: 712 GPM – 8 INCH
Read instructions before installing. This cover must be properly installed using supplied brass screws. When using other than the
supplied frame and fasteners, the design professional certifying the sump must also approve the type and installation of frame and
fasteners used. Close pool immediately if cover breaks or becomes loose and replace with a new cover. Failure to maintain cover
can result in severe injury or death.
When installing the grate without using the supplied frame, the
grate must be anchored into a solid concrete base using the
fasteners provided.
NGE R
DA
Use grate to locate and mark the 4 anchoring positions.
Using a 5/16" concrete bit; drill the 4 holes to a depth of 1".
Use caution. Do not over drill.
MLD-FGD-1818 - (4) 1/4"X20X1-1/4" (Mo# BOLT-03BS)
Use the fasteners provided to insure a minimum of 3 complete turns into concrete anchor.
Ensure screws heads are flush.
AR
NI
Z
W
Using a #2 square head screwdriver, install the grate and tighten
the brass screws supplied to 60 in/lbs torque:
D
DRO
Install the 4 drop-in stainless-steel anchors
supplied and set with the proper tool. (Not provided)
NG HA
VGB-2008
Total head loss at maximum flow rate is less than 0.3 PSI.
1/4" x 20 Screw
Domed Grate
1/4" Drop-In Anchor
(Mo# ANCR-SSD)
CAUTION:
The suction fitting fasteners must be
observed for damage or tampering before
each use of this facility and or at least annually.
Concrete Ledge
Link to general certification of conformity to VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Call 1.800.897.6160
for inquiries or assistance
The Wizards of Aquatic Technology
Doc. # 2010 Replacement Domed Grate 1818 Rev. 03-09-1
Visit us at: www.lawsonaquatics.com
STOP!
WARNING / ATTENTION / AVISO
NEW CONSTRUCTION
READ
FIRST
Instruction for Installment for Frame & Grate.
SUBMERGED SUCTION OUTLETS
MAXIMUM RATED FLOW RATES –ACCEPTABLE PIPE SIZE
MLD-SG-1818 (18 X 18) - FLOOR: 816 GPM; WALL: 712GPM – 8 INCH
MLD-SG-1212 (12 X 12) - FLOOR: 365 GPM; WALL: 340GPM – 6 INCH
Read instructions before installing. This cover must be properly installed using only supplied stainless- steel screws. Close
pool immediately if cover breaks or becomes loose and replace with a new cover. Failure to maintain cover can result in severe
injury or death.
During concrete placement, block-out for installation of PVC frame
Minimum block-out:
MLD-FGD-1212 - 15"x15"x1-1/2"
MLD-FGD-1818 - 21"x21"x1-3/4"
NGE R
DA
W
Using a #2 square head screwdriver, install the grate and tighten
the screws supplied to 60 in/lbs torque.
AR
NI
Z
Use care to keep threaded brass inserts clean.
D
DRO
When setting frame, use proper concrete mixture to insure
frame can only be removed by demolition.
NG HA
Use only stainless-steel fasteners provided.
MLD-FGD-1212 - (4) 1/4"x20x5/8" (Mo# BOLT-01-SS)
MLD-FGD-1818 - (4) 1/4"x20x15/16" (Mo# BOLT-02-SS)
No other means of fasteners will be approved.
Total head loss at maximum flow rate is less than 0.1 PSI for MLD-FGD-1212
and 0.3 PSI for MLD-FGD-1818.
VGB-2008
1/4" x 20 Screw
Grout
(Concrete Mixture)
Frame
Domed Grate
Brass Insert
(Model# BRASS-TI)
CAUTION:
Floor or Wall Concrete
The suction fitting fasteners must be
observed for damage or tampering before
each use of this facility and or at least annually.
Link to general certification of conformity to VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Call 1.800.897.6160
for inquiries or assistance
The Wizards of Aquatic Technology
Doc. # 2020 Domed Grate - New Construction Rev. 02-09-2
Visit us at: www.lawsonaquatics.com
STOP!
READ
FIRST
WARNING / ATTENTION / AVISO
GENERAL SAFETY GUIDELINES
MAIN DRAIN FRAME & GRATE – SUMP & GRATE
SUBMERGED SUCTIONS OUTLETS
FOR THE FOLLOWING SIZES AND RATINGS
MAXIMUM RATED FLOW RATES –ACCEPTABLE PIPE SIZE
FI-SG-1836 (18 X 36) - FLOOR: 2,080 GPM; WALL: 1,496 GPM – 10 INCH
MLD-SG-1818 (18 X 18) - FLOOR: 816 GPM; WALL: 712 GPM – 8 INCH
MLD-SG-1212 (12 X 12) - FLOOR: 365 GPM; WALL: 340 GPM – 6 INCH
If there are any doubts about the use, installation and function of this
product, always consult a Registered Design Professional.
NGE R
DA
3 Do not locate suction outlets on seating areas or on the backrests for such
D
AR
When two or more suction fittings are used on a common suction line they shall
be separated by a minimum of 3 feet, or if any are located closer they shall be
located on two different planes (on the bottom and vertical wall) or 2 separate
vertical walls.
NI
Z
2
W
This product is for use as a Submerged Suction Outlet for multiple drain use
only (FI-SG-1836 is unblockable and can be used for single use).
DRO
1
NG HA
seating areas.
4
In the event that one suction outlet is completely blocked, the remaining suction
outlets serving the system shall have a flow rating capable of the full flow of the
pump(s) for the specific suction system.
5
This sumps are fitted with the appropriate side pipe fitting. The main suction
pipe diameter may possibly need to be increased if the collector tank distance is
more than 30 feet. Refer to a Registered Design Professional.
6
If a field built sump is to be used, refer to the enclosed AMSE 112.19.8-2007
guidelines for correct sizing and formation of them. These are then to be
certified by a Registered Design Professional within the State of installation.
7
For use as in floor or wall mounting positions only.
8
This grate / cover, part # MLD-GO-1818(flat), MLD-GOD-1818(domed), and
MLD-GOD-1212(domed) is to be replaced after 10 installed years.
9
Many codes differ from ASME/ANSI A 112.19.8 2007 recommendations. It is the
responsibility of the installer to choose the proper suction fitting for the
application.
VGB-2008
CAUTION:
The suction fitting fasteners must be
observed for damage or tampering before
each use of this facility and or at least annually.
Link to general certification of conformity to VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Call 1.800.897.6160
for inquiries or assistance
The Wizards of Aquatic Technology
Doc. # 2050 Main Drain Install-Safety Guidelines Rev. 03-09-1
Visit us at: www.lawsonaquatics.com
STOP!
READ
FIRST
WARNING / ATTENTION / AVISO
MAIN DRAIN INSTALLATION INSTRUCTIONS
FOR FIELD BUILT SUMPS FOR ALL SIZES OF
FRAMES & GRATES FOR SUBMERGED SUCTION OUTLETS
Flow rates are NOT NSF certified for field-fabricated sumps, and must
be approved as a complete system by registered design professional.
3
Place the frame over the concrete formed pit. Drill hole for receipt of
protruding inserts when supplied
W
Insert and tighten the stainless steel square head screw in place to secure
grate to the frame. Use only the fasteners supplied. Refer to Document
#2020 for installation instructions.
4
5
It is suggested to place a board over the opening until the pool has been
surfaced and ready to receive the grate.
6
MAXIMUM FLOW RATES AS TESTED ON MANUFACTURER'S SUMPS.
Maximum rated flow rates
Acceptable pipe size
Tested pipe depth
18X36 - Floor: 2,080GPM; Wall: 1,496GPM 10" or larger
1 to 1 ratio
18x18 - Floor: 816 GPM; Wall: 712 GPM
8" or larger
1 to 1 ratio
12x12 - Floor: 365 GPM; Wall: 340 GPM
6" or larger
1 to 1 ratio
7
D
Frame have inserts for insertion of fasteners.
AR
2
NGE R
DA
NI
Z
Read all general, safety and installation literature first and then keep
them for future reference.If there are any questions or further information
needed call 1-800-897-6160 for assistance.
DRO
1
NG HA
VGB-2008
Flow rates were tested on a sump with a distance from the underside of the grate to the top
of the pipe equal to the inside diameter of the pipe. The acceptable pipe sizes shown above
are the minimum size to be used. For smaller size piping, the sump must be built to the
minimum dimensions shown in the diagram below.
IMPORTANT NOTICE
The diagram below represents the ASME-2007 standards for minimum sump dimensions.
A
D Min
NOTE
B
D Min
1.5 D Min
1.5 D Min
D
1
D = Inside diameter of pipe.
2
All dimensions shown are
minimums.
3
A broken line indicates
suggested sump
configuration.
D
D Min
C
D Min
D
D Min
D Min
D Min
1.5 D Min
D
1.5 D Min
D
CAUTION: The suction
fitting fasteners must be
observed for damage or
tampering before each
use of this facility and/or
at least annually.
Link to general certification of conformity to VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Call 1.800.897.6160
for inquiries or assistance
The Wizards of Aquatic Technology
Doc. # 2100 Field Built Sump-Grate Install Rev. 03-09
Visit us at: www.lawsonaquatics.com
WARNING / ATTENTION / AVISO
STOP!
LEA
REEMPLAZO
PRIMERO
Instrucciones para la instalación de marcos existentes
Modelo # MLD-FGD-1212
ENCHUFE SUMERGIDO DE LA SUCCIÓN
TAMAÑOS Y GRADOS DE FLUJOS CLASIFICADOS (AL MAXIMO)
TAMAÑOS ACEPTABLES; SUELO: 365 GPM; MURAR: 340GPM – 6 PULGADAS
Lea las instrucciones antes de instalar. Cubierta se debe instalar correctamente usando tornillos inoxidables (suplidos). Al usar con
excepción del marco y de los sujetadores proveídos, el profesional del diseño que certifica el colector debe también aprobar el tipo y la
instalación del bastidor y de los sujetadores usados. Si la cubierta se rompe o se afloja – cierre la piscina inmediatamente y reemplace
con una cubierta nueva. Falta de mantenimiento resultara en lesión severa o muerte.
Al instalar la rejilla se debe anclar a un marco existente usando las piezas suplidas.
Utilice una de las siguientes opciones (Retrofit) para anclar, dependiendo del tipo de soporte existente.
MARCOS EXISTENTES CON LAS MISMAS LOCALIZACIONES DEL SUJETADOR
Utilice los tornillos suministrados #10 en los agujeros existentes de la cerradura #8.
/O/
Taladre los agujeros existentes con 7/32" e instale partes de cobre suministrados ligeramente
golpeando con el martillo. Utilice los pernos suministrados #8-32 (bolts) para sujetar la rejilla.
Utilice el destornillador principal cuadrado #2 y apriete al esfuerzo de torsión de 60 in/lbs.
REEMPLAZO EXISTENTE DEL MARCO
Si el marco existente no es compatible con la rejilla, o se daña durante la modificación
desentierre el marco hacia fuera e instale el marco usando las instrucciones incluidas
para la nueva construcción. Asegure la rejilla usando 1/4" - 20 (bolts).
Utilice los sujetadores proporcionados dándole un mínimo de 3 vueltas completas.
Asegúrese que las cabezas de tornillo sea rasante.
1/4"x20x3/4" Screw
(Modelo# BOLT-01-SS)
Grout
(Concreto Mixture)
VGB-2008
Frame
Domed Grate
Brass Insert
(Modelo# BRASS-TI)
Floor or Wall Concreto
PRECAUCIÓN:
La pérdida total de la cabeza en la tarifa del caudal
máximo es menos de 0.1 PSI.
Los sujetadores apropriados deben ser
revisados antes de cada uso or anualmente.
Ligúese a la certificación general
de la conformidad a VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Llame al 1.800.897.6160
para obtener asistencia
The Wizards of Aquatic Technology
Doc. # 2005 del reemplazo abombado reja 1212 Rev. 03-09-1
Visítenos en: www.lawsonaquatics.com
STOP!
LEA
WARNING / ATTENTION / AVISO
REEMPLAZO
PRIMERO
Instrucciones para la instalación al marco existente.
Modelo # MLD-FGD-1818
ENCHUFE SUMERGIDO DE LA SUCCIÓN
TAMAÑOS Y GRADOS DE FLUJOS CLASIFICADOS (AL MAXIMO)
TAMAÑOS ACEPTABLES
SUELO: 816 GPM; MURAR: 712 GPM – 8 PULGADAS
Lea las instrucciones antes de instalar. Cubierta se debe instalar correctamente usando tornillos inoxidables (suplidos). Al usar
con excepción del marco y de los sujetadores proveídos, el profesional del diseño que certifica el colector debe también aprobar
el tipo y la instalación del bastidor y de los sujetadores usados. Si la cubierta se rompe o se afloja – cierre la piscina
inmediatamente y reemplace con una cubierta nueva. Falta de mantenimiento resultara en lesión severa o muerte.
El método aprobado para instalar la rejilla es de sujetar
a una base sólida y fija, especialmente si el marco
proveído no se usara.
Utilice la rejilla para localizar y marcar las 4 posiciones del anclaje.
Usando un tornillo para concreto 5/16“; perfore los 8 agujeros a una profundidad de 1 ".
Utilice precaución. No exceda al taladrar.
Usando cautela, perfore 4 agujeros de 1" con un taladro. Instale las
4 anclas inoxidables con la herramienta apropiada. (No proveída).
Con un destornillador principal cuadrado #2, instale la rejilla y apriete
los tornillos de cobre amarillo proveídos al esfuerzo de torsión de 60 in/lbs:
MLD-FGD-1818 - (4) 1/4"X20X1-1/4"
Utilice los sujetadores para asegurar un mínimo de 3 vueltas
completas. Asegúrese que las cabezas de tornillos estén niveladas.
La pérdida total de la cabeza en la tarifa del caudal máximo es menos de 0.3 PSI.
VGB-2008
1/4" x 20 Screw
Domed Grate
1/4" Drop-In Anchor
(Mo# ANCR-SSD)
PRECAUCIÓN:
Concrete Ledge
Los sujetadores apropriados deben ser
revisados antes de cada uso or anualmente.
Ligúese a la certificación general
de la conformidad a VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Llame al 1.800.897.6160
para obtener asistencia
The Wizards of Aquatic Technology
Doc. # 2010 del reemplazo abombado reja 1818 Rev. 03-09-1
Visítenos en: www.lawsonaquatics.com
STOP!
LEA
WARNING / ATTENTION / AVISO
REEMPLAZO
PRIMERO
Instrucciones para la instalación al marco existente.
ENCHUFE SUMERGIDO DE LA SUCCIÓN
TAMAÑOS Y GRADOS DE FLUJOS CLASIFICADOS (AL MAXIMO)
TAMAÑOS ACEPTABLES
MLD-SG-1818 (18 X 18) - SUELO: 816 GPM; MURAR: 712 GPM – 8 PULGADAS
MLD-SG-1212 (12 X 12) - SUELO: 365 GPM; MURAR: 340 GPM – 6 PULGADAS
Lea las instrucciones antes de instalar. Cubierta se debe instalar correctamente usando solamente tornillos inoxidables
(suplidos). Si la cubierta se rompe o se afloja – cierre la piscina inmediatamente y reemplace con una cubierta nueva. Falta de
mantenimiento resultara en lesión severa o muerte.
Al colocar, bloquee parar la instalacion del tubo de PVC:
Medidas (al mínimo): MLD-FGD-1212 - 15"x15"x1-1/2"
MLD-FGD-1818 - 21"x21"x1-3/4"
Al fijar el marco, utilice la mezcla de concreto apropiada
para asegurar que el marco quede fijo y solamente removible
por demolición. Use cautela y mantenga roscas limpias.
Con un destornillador principal cuadrado #2, instale la rejilla
y apriete los tornillos proveídos al esfuerzo de torsión de 60 in/lbs.
Utilice sujetadores proporcionados y aprobados.
MLD-FGD-1212 - (4) 1/4"x20x5/8" (Mo# BOLT-01-SS)
MLD-FGD-1818 - (4) 1/4"x20x15/16" (Mo# BOLT-02-SS)
La pérdida total de la cabeza en la tarifa del caudal máximo es menos
de 0.1 PSI (MLD-FGD-1212) y 0.3 PSI (MLD-FGD-1818).
1/4" x 20 Screw
Grout
(Concrete Mixture)
VGB-2008
Frame
Domed Grate
Brass Insert
(Modeol# BRASS-TI)
Floor or Wall Concrete
PRECAUCIÓN:
Los sujetadores apropriados deben ser
revisados antes de cada uso or anualmente.
Ligúese a la certificación general
de la conformidad a VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Llame al 1.800.897.6160
para obtener asistencia
The Wizards of Aquatic Technology
Doc. # 2020 rejilla cúpula de nueva construcción Rev. 02-09-2
Visítenos en: www.lawsonaquatics.com
STOP!
LEA
PRIMERO
WARNING / ATTENTION / AVISO
GIA GENERAL Y DE SEGURIDAD
MARCO Y REJILLA PRINCIPAL - COLECTOR (SUMP)
ENCHUFES DE SUCCIONES SUBMERJIDOS
TAMAÑOS Y GRADOS DE FLUJOS CLASIFICADOS (AL MAXIMO)
TAMAÑOS ACEPTABLES
FI-SG-1836 (18 X 36) - SUELO: 2,080 GPM; MURAR: 1,496 GPM – 10 PULGADAS
MLD-SG-1818 (18 X 18) - SUELO: 816 GPM; MURAR: 712GPM – 8 PULGADAS
MLD-SG-1212 (12 X 12) - SUELO: 365 GPM; MURAR: 340GPM – 6 PULGADAS
Consulte con un profesional del diseño si tiene preguntas o dudas sobre
el uso, la instalación o la función de este producto.
1
Este producto es solamente para uso con enchufes de succión para el dren
(múltiple). (FI-SG-1836 es inblockable y se puede utilizar para un solo uso).
2
Cuando dos o más guarniciones se utilizan en una línea de succión común
estas deben ser separadas por un mínimo de 3 pies, o si se están más
cerca, entonces deben ser situadas en dos diversos planos (en la parte
inferior y la paredes) o dos paredes verticales separadas.
3 No localice los enchufes de la succión en zonas para sentarse o en los
respaldos para tales zonas para sentarse.
4
En caso de que uno de los enchufes estén totalmente bloqueado los
enchufes restantes tendrán que tener flujo completo para el sistema de
succión especificado.
5
Los colectores deben ser ajustados a la tubería apropiada. El diámetro
principal tendrá que ser aumentada si la distancia del tanque son más de
30 pies. Consulte con un profesional del diseño registrado.
6
Si usa un colector construido por otro proveedor, repase las pautas
incluidas de AMSE 112.19.8-2007 para detalles. Éstos deben ser
certificados por un profesional del diseño registrado dentro del estado de la
instalación.
7
Para uso solamente en instalaciones de piso o de pared.
8
Esta rejilla/cubierta #MLD-GOD-1818, y MLD-GOD-1212 debe ser
reemplazada después de 10 años de instalación.
9
Muchos códigos y recomendaciones diferencian a ASME/ANSI A 112. Es la
responsabilidad del instalador elegir la guarnición apropiada.
VGB-2008
PRECAUCIÓN:
Los sujetadores apropriados deben ser
revisados antes de cada uso or anualmente.
Ligúese a la certificación general
de la conformidad a VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Llame al 1.800.897.6160
para obtener asistencia
The Wizards of Aquatic Technology
Doc. # 2050 Main Drain Install-Safety Guidelines Rev. 03-09-1
Visítenos en: www.lawsonaquatics.com
STOP!
LEA
PRIMERO
WARNING / ATTENTION / AVISO
INSTRUCCIONES DE INSTALACION
DEL COLECTOR (FIELD BUILT SUMP)
COLECTORES DE CAMPO PARA TODOS LOS TAMAÑOS DE MARCOS
Y REJILLAS PARA LOS ENCHUFES SUMERGIDOS DE LA SUCCIÓN
Los índices de corriente NO son NSF certificado para los colectores campo-fabricados, y
deben ser aprobado como un sistema completo por el profesional del diseño registrado.
1
Lea la literatura y guarde para referencia futura. Para obtener información
o preguntas llame al 1-800-897-6160.
2
Los marcos tienen partes movibles para la inserción de sujetadores.
3
Ponga el marco sobre el hoyo formado de concreto. Taladre un hueco
en preparación para las partes movibles.
4
Inserte y apriete el tornillo de acero inoxidable para asegurar la rejilla al marco.
Utilice solamente los sujetadores suministrados. Refiérase al documento
# 2020 para la instrucción de instalación.
5
Se sugiere poner un tablero sobre la abertura durante la preparación de la rejilla.
6
TAMAÑOS Y GRADOS DE FLUJOS CLASIFICADOS (AL MAXIMO) - TAMAÑOS
ACEPTABLES - PROFUNDIDAD DE LA TUBERÍA PROBADA
18X36 - SUELO: 2,080GPM; MURAR: 1,496GPM – 10 pulgadas o más grandes – cociente 1 a 1
18X18 - SUELO: 816 GPM; MURAR: 712GPM – 8 pulgadas o más grandes – cociente 1 a 1
12X12 - SUELO: 365 GPM; MURAR: 340GPM – 6 pulgadas o más grandes – cociente 1 a 1
VGB-2008
7 Los índices de corriente fueron probados en un colector con una distancia de la
superficie inferior de la rejilla a la tapa de la tubería igual al diámetro interior de
la tubería. Los tamaños aceptables de la tubería demostrados arriba son el tamaño
mínimo que se utilizará. Para una tubería más pequeña de tamaño, el colector se
debe construir a las dimensiones mínimas demostradas en el diagrama abajo.
AVISO IMPORTANTE
El diagrama abajo representa los estándares de ASME 2007 para las dimensiones mínimas del colector.
A
D Min
B
D Min
1.5 D Min
1.5 D Min
NOTA
1 D = diámetro al interior de
D
la tubería.
D
2 Dimensiones demostradas
son basadas en mínimas
D Min
C
D Min
D
3 Líneas (puntos abiertos)
indican configuración para
sump
D Min
D Min
D Min
1.5 D Min
D
1.5 D Min
D
PRECAUCIÓN:
Los sujetadores
apropriados deben
ser revisados antes
de cada uso or
anualmente.
Ligúese a la certificación general
de la conformidad a VGB 2008
http://www.lawsonaquatics.com/certification.htm
TM
Llame al 1.800.897.6160
para obtener asistencia
The Wizards of Aquatic Technology
Doc. # 2100 Instrucciones de instalacion del colector de aciete (FIELD BUILT SUMP) Rev. 03-09