XML-F Telemecanique Electronic sensor for pressure control Détecteur électronique pour contrôle de pression Elektronischer sensor für Drucküberwachung Detectores electrónicos para control de presión Bar Psi Menu Enter Output 1 Bar Output 1 Bar Psi Output 2 Psi Menu Menu Enter Enter Output 1 Bar Psi Menu Enter Instruction sheet Instruction de service Gebrauchsanleitung Manual de instrucciones 04/2000 Nautilus XML-F Information reserved for local legislation Informations réservées à certaines législations locales Information reserviert für locale Gezetzgebungen Informaciones reservadas a ciertas legislaciones locales ! DANGER HAZARDOUS VOLTAGE. Disconnect all power before working on equipment. Electric shock will result in death or serious injury. ! WARNING HIGH PRESSURE AIR OR FLUID. • Reduce pressure to zero before disconnecting device from pressure source. • To avoid damage or seal leakage, do not use this pressure switch where system or surge pressure exceeds pressure switch rating. Failure to follow this instruction can result in death, serious injury or equipment damage. 3 XML-F Nautilus Range Gamme Ausführungen Gama Bar Bar Psi Psi Menu Menu Enter Enter Enter 2 3 XML-F ••• D2 01 • XML-F ••• D2 11 • 24 V ( Analogue pressure sensor - 1 analogue output 0...10 V with shunt calibration Capteur analogique - 1 sortie 0...10 V avec shunt calibration Beschreibung Analog Drucksensor - 1 Analogausgang 4…20 mA mit Kalibriershunt Analog Drucksensor - 1 Analogausgang 0…10 V mit Kalibriershunt Descripción Captador analógico Captador analógico - 1 salida 4 ... 20 mA con - 1 salida 0 ... 10 V con shunt calibración shunt calibración Description 4 XML-F •••D2 02 • 17 ... 33 V ) Analogue pressure sensor - 1 analogue output 4...20 mA with shunt calibration Capteur analogique - 1 sortie 4...20 mA avec shunt calibration Description Bar Psi Menu 1 Power supply Alimentation Versorgung Alimentación Output 1 Universal sensor - 1 analogue output 4...20 mA - 1 digital output 200 mA Détecteur universel - 1 sortie analogique 4...20 mA - 1 sortie T.O.R. 200 mA Universellen Drucksensor - 1 Analogausgang 4…20 mA - 1 Schaltausgang 200 mA Detector universal - 1 salida analógica 4 ... 20 mA - 1 salida TON 200 mA Nautilus XML-F Range Gamme Ausführungen Gama Output 1 Bar Output 1 Bar Psi Output 2 Psi Menu Menu Enter Enter Enter Description Description Beschreibung Descripción 5 XML-F ••• D2 12 • XML-F ••• D2 03 • ( 24 V 17 ... 33 V ) Universal sensor - 1 analogue output 0...10 V - 1 digital output 200 mA Détecteur universel - 1 sortie analogique 0...10 V - 1 sortie T.O.R. 200 mA Universellen Drucksensor - 1 Analogausgang 0…10 V - 1 Schaltausgang 200 mA Detector universal - 1 salida analógica 0 ... 10 V - 1 salida TON 200 mA Bar Psi Menu 4 Power supply Alimentation Versorgung Alimentación Output 1 6 XML-F ••• E2 04 • 120 V AC (102 ... 132 V AC) Dual stage electronic pressure switch - 2 digital outputs 200 mA Pressostat électronique - 2 sorties T.O.R. 200 mA Electronic pressure switch for AC - 1 Relay output 2.5 A Elektronischer Druckschalter - 2 Schaltausgänge 200 mA Elektronischer Druckschalter - 1 Schaltausgang 2,5 A Presostato electrónico - 2 salidas TON 200 mA Presostato electrónico - 1 salida relé 2,5 A Préssostat électronique - 1 sortie relais 2,5 A 5 Nautilus 113/4.45 1 2 5 142/5.59 1 2 5 88/3.46 164/6.46 6 100 N.m (886 lb.in) Maximum tightening torque Couple de serrage max. Maximalen Anzugsmoment Par de apriete máx. 15/ 0.59 129/5.08 mm / in 58/2.28 119/4.69 6 Dimensions Encombrements Abmessungen Dimensiones 10/0.39 1 2 5 16/0.63 6 XML-F 46/1.81 138/5.43 XML-F •••• 2 ••• 5 1/4” Gaz female 1/4” Gaz femelle G1/4 innen 1/4" Gas hembra XML-F •••• 2 ••• 6 1/4” NPT female 1/4” NPT femelle 1/4 NPT innen 1/4" NPT hembra XML-F •••• 2 ••• 9 SAE 7/16-20UNF SAE 7/16-20UNF SAE 7/16 20UNF SAE 7/16-20 female femelle innen UNF hembra Cabling Câblage Kabelanschlus Cableado 4 1 3 3 2 XML-F ••• D2 •••• Product No Produit N° Produktnummer Producto N° (p. 4 / 5) + - 2 5 1 XML-F ••• E204 •• 1 2 Digital output 4...20 mA Digital output 0...10 V T.O.R. T.O.R. Schaltausgang Schaltausgang TON TON GND Shunt calibrat Relay 1 2 1 3 2 - - - 4 - 3 4 1 3 2 4 - - - - 5 1 3 - 4 2 - - - 1 2 - - - 3 - 4/5 6 6 U 4 Nautilus XML-F Pressure size list Liste des calibres Liste der Druckberreiche Lista de los calibres Analogue output curve Courbe de la sortie analogique Kurve des Analogausganges Curva de la salida analógica bar -1 2,5 psi 75 20 mA - 10 V 125 % -14,5 36,25 10 145 16 232 25 362,5 40 580 70 1015 100 1450 160 2320 12 mA - 5 V 4 mA - 0 V 0 3625 400 5800 600 8700 100 Pressure switches operating curve Courbes de fonctionnement des pressostats Grafik des Einstellberreiches der Druckschalter Curvas de funcionamiento de los presostatos Rising pressure Steigenden Druck Pression ascendante Presión ascendente 250 50 100 % 1 1 Maximum differential Ecarts maximaux Max. Schaltdifferenz Intervalos máximos 2 Minimum differential Ecarts minimaux Minimale Schaltdifferenz Intervalos mínimos 2 50 8 0 5 50 Falling pressure Pression descendante 97 % Fallenden Druck Presión descendente 7 XML-F Nautilus Product configuration Configuration du produit Produkteinstellung Configuración producto Page Seite Pagina • General menus 14 • Display symbol list (Alphanumeric list) 10 • Output modes 13 • - Analogue pressure sensors 4-20 mA or 0-10 V + shunt calibration "PROG" menu, complete configuration of the product "USER" menu, diagnostic "READ" menu, read the configuration of the product only 1 16 2 18 • - Universal pressure sensors (4-20 mA or 0-10 V) + digital output "PROG" menu, complete configuration of the product "USER" menu, threshold adjustment and diagnostic "READ" menu, read the configuration of the product only 3 20 4 22 • - Dual stages electronic pressure switches "PROG" menu, complete configuration of the product "USER" menu, threshold adjustment and diagnostic "READ" menu, read the configuration of the product only 5 26 • - A.C. electronic pressure switches "PROG" menu, complete configuration of the product "USER" menu, threshold adjustment and diagnostic "READ" menu, read the configuration of the product only 6 30 16 20 24 24 28 28 • Menus généraux 14 • Légende des termes de l’afficheur (ordre alphanumérique) 10 • Modes de sortie 13 • - Capteurs de pression analogiques 4-20 mA ou 0-10 V avec shunt de calibration "PROG" menu de configuration initiale "USER" menu de diagnostique "READ" menu de lecture des paramètres configurés et réglés 1 16 2 18 • - Détecteurs de pression universels (4-20 mA ou 0-10 V) + T.O.R. "PROG" menu de configuration initiale "USER" menu de réglage et de diagnostique "READ" menu de lecture des paramètres configurés et réglés 3 20 4 22 • - Pessostats électroniques à deux étages "PROG" menu de configuration initiale "USER" menu de réglage et de diagnostique "READ" menu de lecture des paramètres configurés et réglés 5 26 • - Pessostats électroniques pour courant alternatif "PROG" menu de configuration initiale "USER" menu de réglage et de diagnostique "READ" menu de lecture des paramètres configurés et réglés 6 30 8 16 20 24 24 28 28 Nautilus XML-F Page Seite Pagina • Hauptmenüs 14 • Erläuterung der Begriffe des Displays (in alphanumerischer Reihenfolge) 10 • Ausgangsmodi 13 • - Analog Drucksensoren 4-20 mA oder 0-10V +, Shuntkalibrierung "PROG" Menü, komplete Einstellung des Gerätes "USER" Menü, Diagnose "READ" Menü, nur ablesen der Produkteinstellung 1 16 2 18 • - Universellen Drucksensoren (4-20 mA oder 0-10V) + Schaltausgang "PROG" Menü, komplete Einstellung des Gerätes "USER" Menü, Schaltpunkteinstellung und Diagnose "READ" Menü, nur ablesen der Produkteinstellung 3 20 4 22 • - Elektronische Druckschaltern mit 2 Schaltausgänge "PROG" Menü, komplete Einstellung des Gerätes "USER" Menü, Schaltpunkteinstellung und Diagnose "READ" Menü, nur ablesen der Produkteinstellung 5 26 • - AC Version, elektronische Druckschaltern "PROG" Menü, komplete Einstellung des Gerätes "USER" Menü, Schaltpunkteinstellung und Diagnose "READ" Menü, nur ablesen der Produkteinstellung 6 30 16 20 24 24 28 28 • Menús generales 14 • Leyenda de los términos del display (orden alfanumérico) 10 • Modos de salidal 13 • - Captadores de presión analógica 4-20 mA o 0-10 V con shunt de calibración "PROG" menú de configuración inicial "USER" menú de diagnóstico "READ" menú de lectura de los parámetros configurados y ajustados 1 16 2 18 • - Detectores de presión universal (4-20 mA o 0-10 V) + TON "PROG" menú de configuración inicial "USER" menú de ajuste y de diagnóstico "READ" menú de lectura de los parámetros configurados y ajustados 3 20 4 22 • - Presostatos electrónicos de dos etapas "PROG" menú de configuración inicial "USER" menú de ajuste y de diagnóstico "READ" menú de lectura de los parámetros configurados y ajustados 5 26 • - Presostatos electrónicos para corriente alterna "PROG" menú de configuración inicial "USER" menú de ajuste y de diagnóstico "READ" menú de lectura de los parámetros configurados y ajustados 6 30 16 20 24 24 28 28 9 XML-F Nautilus Display symbol list (Alphanumeric list) Légende des termes de l’afficheur (ordre alphanumérique) Erläuterung der Begriffe des Displays (in alphanumerischer Reihenfolge) Leyenda de los términos del display (orden alfanumérico) 4-20 AnLG Analogue output active Analogue function Sortie analogique activé Fonction analogique Analoger Ausgang aktiv Analogfunktion Salida analógica activada Función analógica bAr bar bar bar bar CAL Manual shunt calibration Shunt de calibration manuel ShuntHandkalibrieren Shunt de calibración manual CLrA Return to factory configuration Retour à la configuration usine Zurück zur Werkseinstellung dA-1 Response time output 1 Temps de réponse sortie 1 Ansprechzeit Ausgang 1 Retorno a la configuración predefinida Tiempo de respuesta salida 1 dA-2 Response time output 2 Response time analogue output Display reaction time Ansprechzeit Ausgang 2 Ansprechzeit Analogausgang Anzeigenfilter Anzeige diAG Diagnostic Temps de réponse sortie 2 Temps de réponse de la sortie analogique Sensibilité de l’afficheur Diagnostique diSP Display Affichage Safety request : Do you really want to return to factory configuration ? Return to factory configuration Attention : Voulez Sicherheitsfrage : vous revenir à la Wollen Sie wirklich configuration usine ? zur Werkseinstellung zurück ? Retour à la Zurück zur configuration usine Werkseinstellung Reset time delay output 1 Reset time delay output 2 Switching time delay output 1 Switching time delay output 2 Output 1 functions Temporisation du point bas sortie 1 Temporisation du point bas sortie 2 Temporisation du point haut sortie 1 Temporisation du point haut sortie 2 Configuration de la sortie 1 Configuration de la sortie 2 dA-A dA-d doCL donE drP1 drP2 dSP1 dSP2 Fct1 Fct2 10 Output 2 functions Diagnose OFF-Verzögerung Ausgang 1 OFF-Verzögerung Ausgang 2 ON-Verzögerung Ausgang 1 ON-Verzögerung Ausgang 2 Funktionen Ausgang 1 Funktionen Ausgang 2 Tiempo de respuesta salida 2 Tiempo de respuesta de la salida analógica Sensibilidad del display Diagnóstico Visualización Atención: ¿Quiere volver a la configuración predefinida? Retorno a la configuración predefinida Temporización del punto bajo salida 1 Temporización del punto bajo salida 2 Temporización del punto alto salida 1 Temporización del punto alto salida 2 Configuración de la salida 1 Configuración de la salida 2 Nautilus Fnc1 Window mode, NC output signal 1 Fnc2 Window mode, NC output signal 2 Fno1 Fno2 FS-A FSt XML-F Signal de sortie 1 NC, DEL en mode “ window ” Signal de sortie 2 NC, DEL en mode “ window ” Signal de sortie 1 NO, DEL en mode “ window ” Signal de sortie 2 NO, DEL en mode “ window ” Fenstermodus Ausgang 1 Öffner Señal de salida 1 NC, DEL en modo "window" Señal de salida 2 NC DEL en modo "window" Window mode, NO Fenstermodus Señal de salida 1 NO output signal 1 Ausgang 1 Schliesser DEL en modo "window" Window mode, NO Fenstermodus Señal de salida 2 NO output signal 2 Ausgang 2 Schliesser DEL en modo "window" Analogue output Plage de réglage de Endwerteinstellung Gama de ajuste de la range limit values la sortie analogique vom Analogausgang salida analógica Direct display of value Affichage rapide sans Direkte Visualización rápida w/o time filter filtrage Messwertanzeige sin filtrado ohne Filte Hnc1 Hysteresis mode, N.C. output signal 1 Hnc2 Hysteresis mode, N.C. output signal 2 Hno1 Hysteresis mode, N.O. output signal 1 Hno2 Hysteresis mode, N.O. output signal 2 Fenstermodus Ausgang 2 Öffner non1 Output 1 non active Signal de sortie 1 NC, DEL en mode “ Hysteresis ” Signal de sortie 2 NC, DEL en mode “ Hysteresis ” Signal de sortie 1 NO, DEL en mode “ Hysteresis ” Signal de sortie 2 NO, DEL en mode “ Hysteresis ” Sortie 1 non active Augang 1 nicht aktiv Salida 1 no activa non2 Output 2 non active Sortie 2 non active Augang 2 nicht aktiv Salida 2 no activa nonA Analogue output non active Direct display of value with filtering at 0.5 % Sortie analogique non active Affichage moyen avec filtrage à 0,5% du calibre Sortie 1 active en NPN Sortie 2 active en NPN Sortie T.O.R. 1 Analogausgang nicht Salida analógica no aktiv activa nor nPn1 nPn2 out1 Output 1 active on NPN Output 2 active on NPN Digital output 1 Hysterese-Modus Öffner Ausgang 1 Señal de salida 1 NC DEL en modo "Histéresis" Hysterese-Modus Señal de salida 2 NC Öffner Ausgang 2 DEL en modo "Histéresis" Hysterese-Modus Señal de salida 1 NO Schliesser Ausgang 1 en modo "Histéresis" Hysterese-Modus Señal de salida 2 NO Schliesser Ausgang 2 en modo "Histéresis" Direkte Messwertanzeige mit Filter 0,5% Ausgang 1 als NPN aktiv Ausgang 2 als NPN aktiv Schaltausgang 1 Visualización media con filtrado a 0,5% del calibre Salida 1 activa en NPN Salida 2 activa en NPN Salida TON 1 out2 Digital output 2 Sortie T.O.R. 2 Schaltausgang 2 Salida TON 2 outA Analogue output Sortie analogique Analogausgang Salida analógica PCLr Clear maximum peaks Remise à 0 des peaks Druckspitzemessung Puesta a 0 de los löschen tipos 11 XML-F PnP1 PnP2 PrHi ProG Psi rEAd rP1 rP2 SHUn SLo SP01 SP02 SP1 SP2 unit uSEr 12 Nautilus Output 1 active on PNP Output 2 active on PNP Peaks reading Sortie 1 active en PNP Sortie 2 active en PNP Lecture des peaks Ausgang 1 als PNP aktiv Augang 2 als PNP aktiv Druckspitzenanzeige Salida 1 activa en PNP Salida 2 activa en PNP Lectura de los picos Programming menu Programmiermenü psi Menu de configuration psi Menú de configuración psi Read the existing configuration Menu de lecture de la Lese die bestehende Menú de lectura de la configuration Einstellung configuración In rEAd mode, when trying to change the parameters by pressing an arrow, the display show "rEAd" without giving access to the parameter itself. Dans le menu rEAd, quand vous essayer de changer un paramètre en appuyant sur une touche, l’afficheur indique “ rEAd ” sans donner accés à ce paramètre Reset point Réglage du point de decreasing pressure consigne bas (1st stage) (1er étage) Reset point Réglage du point de decreasing pressure consigne bas (2nd stage) (2eme étage) Shunt calibration Shunt de calibration actived actif Direct display of value Affichage lent avec with filtering at 1 % filtrage à 1% du calibre Setting digital Configuration de la output 1 sortie 1 Setting digital Configuration de la output 2 sortie 2 Switching point Réglage du point de increasing pressure consigne haut (1st stage) (1er étage) Switching point Réglage du point de increasing pressure consigne haut (2nd stage) (2eme étage) Measurement unit Unité de mesure User menu Menu de diagnostique psi Wenn im Readmodus die Pfleilentasten betätigt werden zeigt das Gerät “ read ” an, und gibt kein Zugang zu der Parametereinstellung En el menú rEAd cuando usted trate de cambiar un parámetro pulsando una tecla, el display indica "rEAd" sin dar acceso a este parámetro. Rückschaltpunkt : fallenden Druck Ajuste del punto de consigna bajo (1ra etapa) Rückschaltpunkt : fallenden Druck Ajuste del punto de consigna bajo (2da etapa) Kalibriershunt aktiviert Shunt de calibración activo Direkte Messwertanzeige mit 1% Filter Schaltausgang 1 Visualización lenta con filtrado a 1% del calibre Configuración de la salida 1 Configuración de la salida 2 Schaltausgang 2 Einschaltpunkt bei steigendem Druck Ajuste del punto de consigna alto (1ra etapa) Einschaltpunkt bei steigendem Druck Ajuste del punto de consigna alto (2da etapa) Messeinheit Unidad de medida Benutzermenü Menú de diagnóstico Nautilus XML-F Output modes Modes de sortie Ausgangsmodi Modos de salidal Hysteresis mode N.C. LED on Contact off LED off Contact on Window (field) mode N.C. LED on Contact off LED off Contact on Hysteresis mode N.O. LED on Contact on LED off Contact off Window (field) mode N.O. LED on Contact on LED off Contact off 13 XML-F Nautilus XML-F Nautilus Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display General menus Menus généraux Hauptmenüs Menús generales page 16 page 20 1 3 page 10 Seite 10 Página 10 page 24 page 28 5 6 diAG diAG Menu Enter + + ProG Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder Zur Entriegelung gleichzeitig 5 Sekunden drücken Pulsar simultáneamente durante 5 segundos para acceder Enter This menu gives access to the complete programming of all the features of the refered switch, including those involved in the uSEr menu. Menu Output 1 2 diAG Ce menu donne accés à la configuration complète de tous les paramètres du produit sélectionné, il inclue les réglages du menu uSEr. 4 diAG Dieses Menü gibt Zugang zu allen Einstellungen des Gerätes inklusiv die vom Usermenü. page 16 page 20 1 3 2 Este menú da acceso a la configuración completa de todos los parámetros del producto seleccionado; incluye los ajustes del menú uSEr. page 24 page 28 5 6 diAG diAG 4 Bar Psi or rEAd Enter diAG diAG Menu Enter Press for 5 secs one arrow to unlock Appuyer sur une flèche pendant 5 sec. pour y accéder Zur Entriegelung einen Pfeil 5 Sekunden drücken Pulsar sobre una flecha durante 5 segundos para acceder This menu gives only access to read the complete configuration of the device that has been programmed with the "uSEr" or "ProG" menus. In a new device this menu gives access to read the factory configuration. Ce menu donne seulement accés à la lecture des paramètres configurés dans les menus uSEr et ProG. Sur un produit non configuré, ce menu permet de lire la configuration d'usine. Dieses Menü gibt nur Zugang zum Ablesen der Einstellungen die mit "uSEr" oder "ProG" festgelegt wurden. Bei einem neuen Gerät zeigt dieses Menü die Werkseinstellungen. page 18 page 22 1 3 Este menú da solamente acceso a la lectura de los parámetros configurados en los menús uSEr y ProG. En un producto no configurado, este menú permite leer la configuración predefinida. page 26 page 30 5 6 SP01 SP01 Menu + Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder Zur Entriegelung gleichzeitig 5 Sekunden drücken Pulsar simultáneamente durante 5 segundos para acceder uSEr Enter 2 diAG 4 SP01 This menu gives access to : • Setting points on increasing and decreasing pressure of the first stage (when available), Ce menu donne accés à : • Points de consigne du point haut et du point bas du 1er étage (si disponible), Dieses Menü gibt Zugang zu : • den Schaltpunkten bei steigendem und fallenden Druck des Ausgangs 1 (wenn vorhanden), Este menú da acceso a: • Puntos de consigna del punto alto y del punto bajo de la primera etapa (si está disponible,) • Setting points on increasing and decreasing pressure of the second stage (when available), • Points de consigne du point haut et du point bas du 2ème étage (si disponible), • den Schaltpunkten bei steigendem und fallenden Druck des Ausgangs 2 (wenn vorhanden), • Puntos de consigna del punto alto y del punto bajo de la segunda etapa (si está disponible), • Peaks reading and reset, • Lecture et remise à zéro des pics de pression, • Lesen und Zurücksetzen Spitzenwertanzeige, • Lectura y puesta a cero de los picos de presión, • Shunt de calibration manuelle. • Shunt-Kalibrierung von Hand. der • Manual shunt calibration. 14 • Shunt de calibración manual. 15 XML-F Nautilus Analogue pressure sensors 4-20 mA or 0-10 V + shunt calibration "READ" menu, read the configuration of the product only and "PROG"menu, complete Menu Enter Menu XML-F Nautilus configuration of the product Enter Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Cancel key ProG diAG Enter diagnostic Enter CAL Manual shunt calibration PrHi Peaks reading rEAd PCLr Clear maximum peaks diSP + Display unit Measurement unit dA-d Display reaction time or + Enter Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Press for 5 secs one arrow to unlock Appuyer sur une flèche pendant 5 sec. pour y accéder Zur Entriegelung einen Pfeil 5 Sekunden drücken Pulsar sobre una flecha durante 5 segundos para acceder ONLY Err Shunt calibration actived donE 0.0 Menu Menu ( ProG ) Return key (to enable value) SHUn page 10 Seite 10 Página 10 0000 3 seconds PrHi bAr Psi psi FSt nor SLo Direct display of value w/o time filter Direct display of value with filtering at 0.5% Direct display of value with filtering at 1% Menu bar In ( rEAd ) mode, Menu when trying to change the parameters by pressing an arrow, the display show "rEAd" without giving access to the parameter itself. AnLG Analogue output outA Analogue output or Bar nonA 4-20 Analogue output non active Analogue output active dA-A Response time analogue output XXX 5 ... 500 ms FS-A Analogue output range limit values XXX 75% ... 125% Psi 5 500 75% 125% Menu Enter 1 16 2 ONLY ( ProG ) CLrA Return to factory configuration? doCL Safety request : Do you really want to return to factory configuration ? donE Return to factory configuration? 17 XML-F Nautilus XML-F Analogue pressure sensors 4-20 mA or 0-10 V + shunt calibration "USER" menu, diagnostic Menu Enter Nautilus Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Menu page 10 Seite 10 Página 10 Menu Enter Cancel key Return key (to enable value) ERR uSEr Enter diAG Diagnostic CAL Manual shunt calibration SHUn Shunt calibration actived donE Menu PrHi Peaks reading PCLr Clear maximum peaks 0.0 Peak + 3 seconds 0000 Activation Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Bar Psi Menu Enter 1 18 2 19 XML-F Nautilus Universal pressure sensors (4-20 mA or 0-10 V) + digital output "READ" menu, read the configuration of the product only and "PROG"menu, complete Menu Enter Menu XML-F Nautilus configuration of the product Enter Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Cancel key ProG diAG Enter diagnostic Enter CAL Manual shunt calibration PrHi Peaks reading PCLr Clear maximum peaks ( ProG ) Return key (to enable value) SHUn page 10 Seite 10 Página 10 Shunt calibration actived ONLY Err donE 0.0 0000 3 seconds PrHi Menu Menu Menu rEAd diSP Display + dA-d Display reaction time FSt nor SLo Direct display of value w/o time filter Direct display of value with filtering at 0.5% Direct display of value with filtering at 1% outA Analogue output nonA 4-20 Analogue output non active dA-A Response time analogue output FS-A Analogue output range limit values or + Enter Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder AnLG Press for 5 secs one arrow to unlock Appuyer sur une flèche pendant 5 sec. pour y accéder Zur Entriegelung einen Pfeil 5 Sekunden drücken Pulsar sobre una flecha durante 5 segundos para acceder SP01 Analogue function Setting digital output 1 or Output 1 bAr Psi bar Measurement unit unit Bar out1 Digital output 1 psi Analogue output active XXX 5 ... 500 ms XXX 75% ... 125% non1 nPn1 PnP1 Output 1 non active Hysteresis mode, NC output signal 1 Hysteresis mode, NO output signal 1 Window mode, NC output signal 1 Window mode, NO output signal 1 Output 1 functions SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range Psi Menu Enter 3 20 4 ONLY ( ProG ) CLrA Return to factory configuration? drP1 Reset time delay output 1 dA-1 Response time output 1 doCL Safety request : Do you really want to return to factory configuration ? XX 0 ... 50 s XX 0 ... 50 s XXX donE 75% 125% In ( rEAd ) mode, Menu Output 1 active on PNP Fct1 Switching time delay output 1 500 Output 1 active on NPN Hnc1 Hno1 Fnc1 Fno1 dSP1 5 when trying to change the parameters by pressing an arrow, the display show "rEAd" without giving access to the parameter itself. 8% 100% 5% 97% 0 50 5 500 5 ... 500 ms Return to factory configuration 21 XML-F Nautilus XML-F Universal pressure sensors (4-20 mA or 0-10 V) + digital output "USER" menu, threshold adjustment and diagnostic Menu Enter Nautilus Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Menu Enter Cancel key uSEr Enter SP01 Setting digital output 1 page 10 Seite 10 Página 10 Return key (to enable value) SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range 8% 100% 5% 97% Menu + Menu Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Output 1 ERR diAG Diagnostic CAL Manual shunt calibration SHUn Shunt calibration actived donE PrHi Peaks reading PCLr Clear maximum peaks 0.0 Peak Bar 3 seconds Psi Menu 0000 Activation Enter 3 22 4 23 XML-F Nautilus Dual stages electronic pressure switches "READ" menu, read the configuration of the product only and "PROG"menu, complete Menu Enter Menu XML-F Nautilus configuration of the product Enter Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Cancel key ProG diAG Enter diagnostic Enter CAL Manual shunt calibration PrHi Peaks reading PCLr Clear maximum peaks ( ProG ) Return key (to enable value) SHUn page 10 Seite 10 Página 10 Shunt calibration actived ONLY Err donE 0.0 0000 3 seconds PrHi Menu Menu Menu rEAd diSP bAr Psi bar Measurement unit dA-d Display reaction time FSt nor SLo Direct display of value w/o time filter Direct display of value with filtering at 0.5% Direct display of value with filtering at 1% Digital output 1 non1 nPn1 PnP1 Output 1 non active out1 Hysteresis mode, NC output signal 1 Hysteresis mode, NO output signal 1 Window mode, NC output signal 1 Window mode, NO output signal 1 unit Display + or + Enter SP01 Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Setting digital output 1 Press for 5 secs one arrow to unlock Appuyer sur une flèche pendant 5 sec. pour y accéder Zur Entriegelung einen Pfeil 5 Sekunden drücken Pulsar sobre una flecha durante 5 segundos para acceder Output 1 Bar Output 2 Psi As SP01 or SP02 Menu 5 24 ONLY ( ProG ) CLrA Output 1 functions SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range Switching time delay output 1 drP1 Reset time delay output 1 dA-1 Response time output 1 out2 (dual stage only) Fct2 Return to factory configuration? doCL Digital output 2 Safety request : Do you really want to return to factory configuration ? XX 0 ... 50 s XX 0 ... 50 s XXX Menu Output 1 active on PNP Fct1 dSP1 In ( rEAd ) mode, Output 1 active on NPN Hnc1 Hno1 Fnc1 Fno1 Setting digital output 2 Enter psi when trying to change the parameters by pressing an arrow, the display show "rEAd" without giving access to the parameter itself. 8% 100% 5% 97% 0 50 5 500 5 ... 500 ms non2 nPn2 PnP2 Output 2 non active donE Return to factory configuration? Output 2 active on NPN Output 2 active on PNP 25 XML-F Nautilus XML-F Dual stages electronic pressure switches "USER" menu, threshold adjustment and diagnostic Menu Nautilus Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Enter Menu Enter Menu Enter Cancel key uSEr Enter SP01 Setting digital output 1 Menu + SP02 Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder page 10 Seite 10 Página 10 Return key (to enable value) SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range Setting digital output 2 SP2 Switching point increasing pressure (2nd Stage) XXXX 8 ... 100% range (dual stage only) rP2 Reset point decreasing pressure (2nd Stage) XXXX 5 ... 97% range 8% 100% 5% 97% 8% 100% 5% 97% Menu ERR diAG Diagnostic CAL Manual shunt calibration SHUn Shunt calibration actived donE Output 1 Bar Output 2 Psi PrHi Peaks reading PCLr Clear maximum peaks 0.0 Peak Menu Enter 3 seconds 5 26 0000 Activation 27 XML-F Nautilus A.C. electronic pressure switches "READ" menu, read the configuration of the product only and "PROG"menu, complete Menu Enter Menu XML-F Nautilus configuration of the product Enter Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Cancel key ProG diAG Enter diagnostic Enter CAL Manual shunt calibration PrHi Peaks reading PCLr Clear maximum peaks ( ProG ) Return key (to enable value) SHUn page 10 Seite 10 Página 10 Shunt calibration actived ONLY Err donE 0.0 0000 3 seconds PrHi Menu Menu Menu rEAd diSP Display unit dA-d + bAr Psi bar Measurement unit Display reaction time FSt nor SLo Direct display of value w/o time filter Direct display of value with filtering at 0.5% Direct display of value with filtering at 1% Hnc1 Hno1 Fnc1 Fno1 Hysteresis mode, NC output signal 1 Hysteresis mode, NO output signal 1 Window mode, NC output signal 1 Window mode, NO output signal 1 or + Enter Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Press for 5 secs one arrow to unlock Appuyer sur une flèche pendant 5 sec. pour y accéder Zur Entriegelung einen Pfeil 5 Sekunden drücken Pulsar sobre una flecha durante 5 segundos para acceder SP01 Setting digital output 1 or Output 1 Bar Output 2 Psi Fct1 Output 1 functions psi SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range dSP1 Switching time delay output 1 drP1 Reset time delay output 1 dA-1 Response time output 1 XX 0 ... 50 s XX 0 ... 50 s XXX In ( rEAd ) mode, Menu when trying to change the parameters by pressing an arrow, the display show "rEAd" without giving access to the parameter itself. 8% 100% 5% 97% 0 50 5 500 5 ... 500 ms Menu Enter 6 28 ONLY ( ProG ) CLrA Return to factory configuration? doCL Safety request : Do you really want to return to factory configuration ? donE Return to factory configuration? 29 XML-F Nautilus XML-F A.C. electronic pressure switches "USER" menu, threshold adjustment and diagnostic Menu Enter Nautilus Français : voir Légende des termes de l’afficheur Deutsch : Siehe Anzeigeabkürzungsliste Español : ver leyenda de los términos del display Menu Enter Menu Enter Cancel key uSEr Enter SP01 Setting digital output 1 page 10 Seite 10 Página 10 Return key (to enable value) SP1 Switching point increasing pressure (1st Stage) XXXX 8 ... 100% range rP1 Reset point decreasing pressure (1st Stage) XXXX 5 ... 97% range 8% 100% 5% 97% Menu + Menu Press for 5 secs at the same time to unlock Appuyer simultanément pendant 5 sec. pour y accéder 5 Sek. lang gleichzeitig drücken Pulsar simultáneamente durante 5 segundos para acceder Output 1 ERR diAG Diagnostic CAL Manual shunt calibration SHUn Shunt calibration actived donE PrHi Peaks reading PCLr Clear maximum peaks 0.0 Peak Bar 3 seconds Psi Menu 0000 Activation Enter 6 30 31 W916340040111 A02 04-2000