A relay is defined as an electrically controlled device that opens and closes
electrical contacts, or activates and deactivates operation of other devices in the
same or another electrical circuit. Two types of relay technology are available,
mechanical and solid state. A mechanical relay is essentially a combination of
an inductor and a switch, where the electromagnetic force of the inductor causes
a switch to change position. A solid state relay accomplishes the same function
with semiconductor devices changing impedance to effectively activate or
deactivate a circuit open or closed. This document is intended to be a general
guide to aid the designer in the appropriate selection of a relay for the intended
application. Detailed information on the selection and use of relays can be found
in MIL-STD-1346.
Table 1. Military Relay Specifications
Military Specification
MIL-R-5757
MIL-R-6106
MIL-R-28776
MIL-R-39016
MIL-R-28750
MIL-R-83726
Description
Relays for Electrical,
for Electronic and
Communication Type
Equipment
Electromagnetic
Relays
Relays for Electrical
for Electronic and
Communication type
Equipment, Hybrid
Relay,
Electromagnetic,
Established
Reliability
Solid State Relay
Time Delay, Hybrid
and Solid State
Relays
Packaging
Relays are available in a variety of unique package styles. The size and mass of
the package are dependent on the electrical characteristics, power dissipation
and environmental requirements. Relays are generally the larger size
components of a system, where increased attention must be paid to clearances
and mounting, especially in high vibration level environments. Many package
styles initially developed for unique applications have since gained wide
acceptance.
Failure Mechanisms and Anomalies
FAILURE MODES
Table 2. Normalized Failure Mode
Distributions for Relays
Table 2 shows the relative
Failure Mode
Relative Probability
probability of the three principal
Failure
to
Trip
55%
failure modes for relays. Relays
Spurious Trip
26%
most commonly fail in the "stuck
Short
19%
open" position where the
mechanical switching element fails
to close and the relay fails to carry a
current. Relays are less likely to unintentionally close or remain closed after the
switching current is released. For this reason, the reliability of relay circuits can
be improved by using parallel redundancy.
Unlike most of the other electrical parts, relays (with the exception of
solid state relays) contain a switching element that physically moves to make
electrical contact. This makes them less likely to follow a constant failure rate or
traditional "bathtub curve” profile. Instead, they are more prone to follow the
failure rate curve for a mechanical part, with an increasing failure rate with age.
Except for special high voltage and high temperature applications, solid-state
relays are inherently more reliable and predictable for long life applications.
Failure Mechanisms
The two most common failure mechanisms of relays are contamination and
mechanical wear of the internal switching elements discussed as follows:
a. Contamination is a major cause of early life failures. Sources of
contamination are numerous, but they are often from the various
chemicals used in the manufacturing operation (e.g., soldering
fluxes and cleaning agents). Types of contamination can be
divided into two categories: metallic and non-metallic. Metallic
contamination causes shorted conditions or blocks the physical
movement of mechanical elements. Non-metallic or gaseous
contamination creates open circuits when it periodically deposits
itself on contacts.
b. A second major cause of early life failures in relays is
mechanical wear of internal switching elements. In fact, the life of a
relay is essentially determined by the life of its contacts.
Degradation of contacts is caused from high in-rush currents, highsustained currents, and from high voltage spikes. The source of
high currents and voltages, in turn, are determined by the type of
load. Inductive loads create the highest voltage and current spikes
because they have lowest starting resistance compared to
operating resistance. This is especially true for lamp filaments and
motors, which is why derating is more severe for these types of
loads. The life of a contact can be further degraded if
contamination or pitting is present on the contact. Physical wear
can also occur to other elements within the relay. Some relays
contain springs to provide a mechanical resistance against
electrical contact when a switching current is not applied. Springs
will loose resiliency with time. Relays can also fail due to poor
contact alignment and open coils.
Reliability
Selection of the proper relay type for a given application is the most significant
factor affecting relay reliability. Many poor design practices are used when
designing them into circuits. This is because relays are a relatively uncommon
circuit element and often receive little attention during the design process.
Whereas most designs will use hundreds each of microcircuits, resistors, etc.;
relays typically number in the single digits. Therefore, designers are often less
familiar with the intricacies of selecting the proper relay type and rating for a
particular application. Some of the more common poor design practices are
listed as follows:
a. Paralleling contacting is where two relays are placed in parallel
to handle the current that one of them cannot handle alone. The
problem with this type of design is that mechanical switching occurs
at relatively slow switching speeds. Therefore, for a brief instant,
only one relay needs to carry the full current load. Further,
switching speeds tend to slow with age, amplifying the affect over
time. The preferred method is to use a single relay of sufficient
current handling capability. If dual relays are used in parallel in
increase reliability, each relay should be capable of handling the full
current load.
b. Transient surge currents are often difficult to measure and
predict, especially when switching inductive loads. It is not
uncommon for surge current to reach ten times steady state
current. Protective devices should be used to limit surge current.
The simplest solution is to use a relay with a substantially higher
rated surge current than anticipated.
c. A cold filament lamp draws between 3 and 10 times the steadystate current until warmed up. Relay contacts used for switching
lamps should be able to withstand such current surges without the
possibility of welded contacts.
d. Relays are sometimes used in applications where they switch a
redundant circuit element or an additional power supply current into
a circuit. High surges occur in ac applications when the redundant
current is not in synchronization with the original current.
e. A typical misapplication is the use of small multipole relays in
112/200 volt 3-phase ac applications. Phase-to-phase shorting at
rated loads is a strong possibility, with potentially catastrophic
results.
f. Caution must be applied when using relays to reverse motors,
particularly where the motor can be reversed while running
(commonly called "plugging"). This results in a condition where
both voltage and current can greatly exceed nominal. Only power
relays rated for "plugging" and reversing service should be utilized
in these applications.
g. A relay race condition occurs when one relay must operate prior
to another from a separate drive circuit, but fails to do so. The
problem usually occurs after the equipment ages or temperatures
rise. Potential race circuits should be avoided. Where they must
be used, extra consideration must be given to wear considerations,
coil suppression circuitry, ambient temperature, drive power, and
operate and release times.
h. A slowly rising triggering current has an increased likelihood of
causing chattering conditions. A problem occurs because back
electromotive forces (EMFs) are produced when the armature
closes to the pole face. This voltage is opposite in polarity to the
driving voltage and can cause the relay to release immediately after
initial contact. This process repeats and causes a chatter condition
until a sufficient amount of drive current is available to overcome
the back EMF.
Derating
Continuous Current
Derating of continuous current is dependent upon the load type and is shown in
Table 3. Derating is more severe for inductive and filament loads, due to high
current demands upon initial startup and increased propensity of voltage spikes.
If a relay is used to switch a combination of loads, the most dominant load should
be used for derating purposes.
Some relay specifications will contain individual current limitations for capacitive,
inductive, motor, and filament loads. For such specifications, limit current to
either the current derived through Table 1 or the maximum current rating for the
particular load type given in the specification, whichever is less.
Coil Energizing Voltage
The voltage to energize or trigger the relay should be at least 110% of the
minimum rated energizing voltage. Coil energizing voltage is not derated in the
traditional sense of the term because operation of a relay at less than nominal
ratings can result in switching failures or increased switching times. The latter
condition introduces contact damage and can reduce relay reliability.
Coil Dropout Voltage
The voltage to dropout or un-trigger a relay should be less than 90% of the
maximum rated coil dropout voltage.
Temperature
Limit ambient temperature to maximum rated ambient temperature as shown in
Table 3.
Note: Relay ratings may be given under the assumption that the relay case will
be grounded. If such relays are used in applications where the case is not
grounded, additional derating should be considered because the relay may lack
arc barriers and contain smaller internal spacings.
Table 3. Derating Requirements for Relays
Part
Type
Relay
Derating
Parameter
Continuous
Current
Coil Energize
Voltage
Coil Dropout
Voltage
Ambient
Temperature
% of Resistive Load Rated Value in Environment
Category 1
Category 2
Category 3
Protected
Normal
Severe
50 -- Resistive
60 -- Resistive
70 -- Resistive
Load
Load
Load
50 -- Capacitive
60 -- Capacitive
70 -- Capacitive
Load
Load
Load
30 -- Inductive
40 -- Inductive
50 -- Inductive
Load
Load
Load
20 -- Motor
20 -- Motor
30 -- Motor
10 -- Filament
10 -- Filament
20 -- Filament
(Lamp)
(Lamp)
(Lamp)
110, Maximum
110, Maximum
110, Maximum
90, Minimum
90, Minimum
90, Minimum
10oC of Max
Rated
20oC of Max
Rated
30oC of Max
Rated
Design and Material
The construction methods and materials of each type of relay differ.
Considerable differences exist between the materials and processes The
construction methods and materials of each type of relay differ. Considerable
differences exist between the materials and processes used to manufacture
relays. A relay, in its most basic form, is a combination of a switch and an
inductive element. In solid state relays, the inductor is replaced by a
semiconductor element. The military specifications and standards are listed in
Table 1, and other information can be found in MIL-STD-1346. The following
lists the major categories available:
a. A reed relay is operated by an electromagnetic coil or solenoid
which, when energized, causes two flat magnetic strips to move
laterally to each other. The magnetic reeds serve both as magnetic
circuit paths and as contacts. Because of the critical spacing and
the frailty of the arrangement, the reeds are usually sealed in a
glass tube.
b. A solid state relay incorporates semiconductor or passive circuit
devices. As the name implies, it contains no moving parts, and
therefore has low switching noise and essentially no bounce or
chatter. Solid state relays also have long life and fast response
times. Their main disadvantage is a limited number of applications
for which they can be used.
c. A latching or magnetic latching relay is a bistable polarized relay
having contacts that latch in either position. A signal of the correct
polarity and magnitude will reset or transfer the contacts from one
position to the other.
Note: In addition to the categories listed above, mercury, bimetal (thermal), and
contractor relay technologies are also available.
Facility Assessment and Quality
Quality and reliability levels of relays may be expressed as the number of switch
cycles before wear-out rather than the more traditional failure rate. Vendors
consider rated number of switch cycles to be the guaranteed minimum number of
cycles the relay can withstand under normal operating conditions before failure
(intermittent or constant). Relays manufactured to the military standards have a
failure rate level designator as shown
in Table 4 (levels established at 90%
Table 4: Failure Rate Level Designators
confidence level for qualification and
for Relays
60% confidence level for
maintenance of qualification).
Failure Rate Letter Failure Rate Level
Quality is further dependent on the
Designator
(%failures per
ruggedness of the package and how
10,000 Operations)
well the internal switching elements
L
3.0
are sealed against influences of the
M
1.0
outside environment. Commercial
P
0.1
grade relays and relays found in
R
0.01
COTS equipment are not routinely
S
0.001
acceptable for use in Military
environments.
Sampling
The trend in Military procurements is to specify end item performance
requirements rather than specifying specific sampling plans. Sampling plans
differ between vendors, and the particular part vendor must be consulted if test
and inspection sampling rates are needed.
Process Controls
If process controls or SPC requirements are needed for a particular application,
consult the individual vendor detailed information.
Part Assessment
Relays typically do not require additional screening or testing by the user at the
piece part level.
Handling and Storage Precautions
No special handling precautions are necessary for relays. Mechanical relays are
not considered ESD sensitive, and solid state relays are normally rated at Class
3 ESD sensitive. Care should be exercised when handling hermetically sealed
relays to retain the hermetic seal.
Closing Comments
Solid stage relays are generally preferred over electromechanical relays due to
decreased chatter noise, increased reliability, and more consistent performance
with age. Exceptions are relays used in high temperature environments.
Special mounting consideration are necessary for mechanical relays in high or
vibration environments because relays are typically high mass parts and can
switch unintentionally when subjected to shock. Particular care is needed in
airborne applications. Relays should not unintentionally switch even during
absolute worse case operating conditions. In addition, the designer should take
into account the wear of springs in long life applications.
Arc suppression techniques should be used to protect relay contacts of
intermediate and power level devices to increase long term reliability. Arc
suppression usually consists of external circuitry (e.g., diodes) to limit current
surge.
To increase reliability, relays can be designed into circuits with parallel
redundancy. The relative probably of a relay failing in the open position is
substantially higher than failure in a closed position (see Table 2), thereby
improving reliability in parallel redundant configurations. However, parallel
redundancy should only be used to increase reliability, not to increase the current
handling capabilities of a relay circuit.
For relays used over a wide temperature rate, account for increased switching
current demand at higher temperatures. As a general rule of thumb, coil
resistance increases with temperature at a rate of 0.004 Ω/Ω/oC.
If a relay is rated under grounded case conditions, the relay should only be used
in applications where the case will be grounded. Use in an ungrounded
application may cause a personnel hazard.
When using relays to reverse motor loads while running, use only relays
specifically rated to reverse switch motor loads.