Inocencio Solteiro, PPTR/AT 17.05.2012 – Santiago do Chile / Chile Transformers Day Sistema de Monitoreo en Línea Buenas Tardes ¿Quién soy yo ? Nombre, Cargo Actual, Background, Experiencia, etc. Agenda Modelo de Monitoreo Beneficios Económicos Beneficios de Instalar Monitoreo en Línea Sistema de Monitoreo ABB TEC Plataforma Diseño Configuración Sistema CanBus Parámetros de Monitoreo Arquitectura de Instalación Protocolo de Comunicación TEC Demo FRA/Transients PD LTC Hydran M2 Bushing Kelman Minitrans H2O Sensor Gas Sensor Online Sensors Serveron TM3 Kelman Transfix New Data Repositories SCADA Trxf. fingerprint Equations Trxf. 1 Events, alarms Expertise Load Computation Enterprise Top Oil Trxf. 2 Trxf. 3 … Statistics T. amb Trxf. n © ABB Group •| Slide 5 Engineering MTMP Risk of Failure FRA, DFR, Z, etc Routine tests Maintenance actions On going development Off line SOT Static data or information Dynamic data/information Off line DGA Tap pos. Offline Databases Report Recommend Actions Update Risk of Failure ¿Por qué es importante el Monitoreo en Línea? Equipamiento críticos, Alta confiabilidad, Previsión de capacidad de sobrecarga, Extender el periodo de mantenimientos, Reducción de los costos de mantenimientos, Evita salidas de operación fortuitas, Aumento de la vida útil del Transformador , Reducción de los costos de aseguramiento del equipo © ABB Group •| Slide 6 ¿Por que hacer el Monitoreo en Línea? 1. Aumento del tiempo de funcionamiento de los transformadores: Detección temprana de defectos ocultos Asistencia en la operación de una unidad “enferma” hasta su reparación / sustitución 2. Optimizar el mantenimiento: Planificar acciones de mantenimiento Prioridades para las acciones de mantenimiento 3. Carga optimizada: Sobrecarga en condiciones controladas Tasa de envejecimiento, la humedad, la temperatura 4. Plan de inversiones: Reparación Reemplazo © ABB Group •| Slide 7 Beneficios Económicos - CIGRE Beneficios Económicos - CIGRE Pontos Relevantes que Impacta Costos Cargamento eficiente en la red, Duración del periodo de interrupción del servicio, Condición de la vida del Transformador, Optimización del trabajo de mantenimiento, Disponibilidad de piezas de repuesto, Costo del seguro de la flota de Transformadores Sistema de Monitoreo en Línea Transformadores Nuevos Transformadores en Uso Transformadores Non-ABB Sistema de Monitoreo en Línea Puntos de Destaques 100 años de experiencia. 100% Desarrollado y Fabricado por ABB. 04 años en desarrollo 02 años en laboratorio 02 años en campo Concepto Fingerprint. Monitoreo en línea , dados en tiempo real. Monitoreo periódico. © ABB Group April 28, 2012 | Slide 13 Sistema inteligente, con diagnóstico, pronósticos y tendencia de fallas Sistema de Monitoreo en Línea TEC Basic © ABB Group •| Slide 14 TEC Smart Plataforma de Diseño TEC Basic TEC Smart © ABB Group April 28, 2012 | Slide 15 Está basado en un Microprocesador. Un sistema modular y expansivo. No necesita de un PC para almacenamiento de los dados. Comunicación de los datos a través de fibra optica. Fácil de montar y instalar Basado en una tecnología comprobada. Protocolo de Comunicación: IEC 61850 IEC 60870 DNP 3 ModBus Others Sistema Modular y Expansivo TC 110, power supply board Input 85-264 V AC and/or DC TC 122, processor board TEC 2.0 TC 101, back plane TC 150, digital in board (12 inputs) TC130, analogue 4-20 mA board (8 inputs) TC 160, Control and output 3 DO, Warning, Alarm & Trip © ABB 22/07/2009 | Slide 16 TC 140, Pt100 board (4 inputs) TC 170, Display Board Motor Relay Board 6 DO Pruebas de Fabricación © ABB Group April 28, 2012 | Slide 17 Información Técnica Generales TEC Basic © ABB Group •| Slide 18 Gabinete del TEC Basic © ABB Group April 28, 2012 | Slide 19 Información Técnica Generales TEC Smart © ABB Group •| Slide 20 Gabinete del TEC Smart Status lights Power supply board Processor board Space for extra board © ABB Group April 28, 2012 | Slide 21 Display Display button Configuración Padrón - TEC Smart Incluye las siguientes funciones : Carga del Transformador Temperatura del aceite Corriente de HV and LV Calculo de Hot-spot en el bobinado HV and LV Envejecimiento térmico Gases en el aceite Humidad en el papel aislante ABBGroup Group ©©ABB •| Slide April 28, 22 2012 | Slide 22 Opción Configuración © ABB Group •| Slide 23 OLTC ABB OLTC no ABB Controle de resfriamiento Balance térmico del Transformador Capacidad de sobre carga Control de Alarma Monitoreo de Bushing Monitoreo de descarga parciales Monitoreo de gases disueltos en aceite - DGA Sistema Can-bus Rápida instalación en campo! Varios sensores – Uno cable Rápida conexión – Cables padrón Terminación TEC Smart Terminación Transductor de Corriente HydroTEC 1001+ ABBGroup Group ©©ABB •| Slide April 28, 24 2012 | Slide 24 Termómetro de aceite Sistema Can-bus en el Transformador Controle Resfriamiento Velocidad moto ventiladores Posición OLTC Fibra optica H-S Bushings Corriente CAN bus - 24V Kelman Energía Control de los moto ventiladores proporciona bajo sonido Posibilidad de tener sobre velocidad durante la sobre carga © ABB Group April 28, 2012 | Slide 25 Protección Top Bottom Ambiente Ambiente Sombra Sol Aceite Aceite HydroTEC 1001+ Pantalla Principal - Amigable No se necesitan de computadora especial Con doble lenguaje © ABB Group April 28, 2012 | Slide 26 Parámetros Monitoreado Relé Buchholz Temp. Ambiente Capacitancia Bujes Corriente de Carga Temp. del Aceite MotoVentiladores Corriente Motor Bombas Corriente Motor Humedad del Aceite Temp. del Aceite Gases Disueltos: HYDRAN Cambiador bajo Carga Sensores con entrada Analógica de 4-20 mA © ABB Group •| Slide 27 Pocos Sensores Alta funcionalidad Temperatura del aceite - Top • Temperatura Hot-spot • Carga • Edad • Balance térmico • Control resfriamiento Transductores de Corriente • Temperatura Hot-spot • Carga • Edad • Control resfriamiento • Vida de los contactos • Balance térmico Temperatura Ambiente • Sol • Sombra Cambiador bajo carga (OLTC) • Posición • Vida de los contactos • Temperatura • Balance térmico • Humidad OLTC Gases y Humidad • Tendencias • Temperatura © ABB Group •| Slide 28 Temperatura del aceite - bottom • Balance térmico Dados del Diseño – Concepto Fingerprint RI2 losses high voltage winding RI2 losses low voltage winding RI2 losses tertiary winding Eddy losses in high voltage winding Eddy losses in low voltage winding Eddy losses in tertiary winding Calculated values for type test Top oil temperature rise Average oil temperature rise No load loss at test Load losses at test Tap-changer position Current high voltage winding Current low voltage winding Current tertiary voltage winding Hot-spot temperature high volt. wind. Hot-spot temperature low volt. wind. Hot-spot temperature tertiary volt. wind. Temperature gradient high volt. wind. Temperature gradient low volt. wind. Temperature gradient tertiary volt. wind. Mass parameters Cu-Mass of high voltage winding Cu-Mass of low voltage winding Cu-Mass of tertiary winding Free oil Oil in insulation Core steel mass Other steel mass (tank, yoke plate, etc.) Paper mass Type test values Ambient temperature Top oil temperature rise © ABB Group •| Slide 29 kW kW kW kW kW kW °C °C kW A A A °C °C °C °C °C °C kg kg kg kg kg kg kg kg °C °C 89.5 131.0 N/A 8.3 9.55 N/A AF 56.5 41.5 124 764 -2X2.5%(2) 510.5 1600 N/A 74.3 75.3 N/A 17.8 (3) 18.8(3) N/A 32.2 47.2 N/A 3.0 3.4 N/A AN (When applicable) 58 49 124 275 -2X2.5%(2) 306.3 960 N/A 67.5 67.5 N/A 9.5(3) 9.5(3) N/A 4461 kg/limb 3337 kg/limb N/A 99915 4000 89049 67000 438 AF AN (When applicable) Temperaturas del Transformador © ABB Group •| Slide 30 Lectura de los Gases y Humidad © ABB Group •| Slide 31 Lectura de la Vida de los Contacto y Temperatura © ABB Group •| Slide 32 Lectura del Torque del Motor - OLTC © ABB Group •| Slide 33 Lectura de la Temperatura -OLTC © ABB Group •| Slide 34 Predicción del Hot-spot Bajo Condiciones de Sobrecarga © ABB Group •| Slide 35 Pronostico de Carga y Envejecimiento - 24h © ABB Group •| Slide 36 Capacidad de Sobrecarga Visualiza capacidad de sobre cargas Bajeado en dados do transformador, temperatura ambiente e condiciones de cargamento © ABB Group •| Slide 37 Temperatura Hot-spot No precisa termómetro tradicional no bobinado Calculo de la temperatura Hot-spot • Bobinado Alta Tension • Bobinado Baja Tension • Bobinado Terciário © ABB Group •| Slide 38 Control y Monitoreo del Resfriamiento Controla hasta 6 grupos de ventiladores Inicia con top oil, hot-spot o manualmente Todos los grupos son usados durante el mismo tiempo Programación para inicio semanal de los grupos Se muestra el tiempo de servicio de cada grupo Tiempo de retraso entre el inicio de cada unidad Si un grupo falla, el siguiente es automáticamente iniciado. Temperatura mas estable. © ABB Group •| Slide 39 Control de Eventos © ABB Group •| Slide 40 Control de Eventos con Pronostico © ABB Group •| Slide 41 Condicione del Gabinete Temperature and Moisture sensors Processor board - TC 122 © ABB Group •| Slide 42 Descripción General del Sistema TCP/IP Monitoreo Bushing – IDD/Doble Capacitancia Tangente delta Fibra óptica Calisto 9 – Morgan Schaffer Individual 8 gases Humidad ABBGroup Group ©©ABB •| Slide April 28, 43 2012 | Slide 43 Sistema TEC Termal Corrientes Resfriamientos OLTC Conexión del Sistema ABBGroup Group ©©ABB •| Slide April 28, 44 2012 | Slide 44 Servidor Conecta hasta 9 unidades del TEC Relación de carga, Temperatura aceite y Status del los eventos. El aumento de la resolución de los valores almacenados Archive SQL Paginas Web extendidas 24h pronostico Todos señales Pronósticos de eventos Protocolo de comunicación IEC60870-5-101 IEC60870-5-104 IEC 61850 DNP 3.0 MODBUS etc Mantenimiento © ABB 22/07/2009 | Slide 45 Backup de los dados Solución Básica – TEC Smart Solución mínima recomendada para supervisión del Transformador Temperatura ambiente Sombra TEC Smart HydroTEC 1001+ Top Oil Temp. CT Control Cabinet Cables de Cobre / CANBUS Comunicación TCP/IP Conexión Fibra Óptica Transformador Sala de Control / Remoto Red Cliente TCP / IP Station equipment, not part of monitoring scope Ofrecido como una opción … Supervisão Acesso Remoto pelo Centro Serviço ABB TEC Servidor Workstation Nr. 1 Usando link do SCADA IEC 61850, DNP3 o IEC 60870 © ABB Group April 28, 2012 | Slide 46 Workstation Nr. n Solución Básica – TEC Basic Solución mínima recomendada para supervisión del Transformador Temperatura Ambiente. (Sol / Sombra) Contatos auxiliares para sinais de alarmes do sistema SCADA TEC Basic HydroTEC 1001+ Top Oil Temp. CT Control Cabinet OLTC Monitoreo Control Resfriamiento Cables de Cobre / CANBUS Comunicación TCP/IP Conexión Fibra Óptica Transformador Sala de Control / Remoto Red Cliente TCP / IP Station equipment, not part of monitoring scope Ofrecido como una opción … Supervisão Acesso Remoto pelo Centro Serviço ABB TEC Servidor Workstation Nr. 1 Usando link do SCADA IEC 61850, DNP3 o IEC 60870 © ABB Group April 28, 2012 | Slide 47 Workstation Nr. n Solución Alternativa – TEC Basic Temperatura Ambiente. (Sol / Sombra) Monitoreo Bushing IDD or eq. Sistema PD Power Diagnostix or eq. HydroCal 1008 8-gas + Humedad Top Oil CT Temp. Control Cabinet TEC Basic OLTC Monitoreo Control Resfriamiento AContatos auxiliares para sinais de alarmes do sistema SCADA Necesitas la máxima confiabilidad, tomar total control de su transformador Cables de Cobre / CANBUS Comunicación TCP/IP Conexión Fibra Óptica Transformador Sala de Control / Remoto Red Cliente TCP / IP Station equipment, not part of monitoring scope Ofrecido como una opción … Supervisão Acesso Remoto pelo Centro Serviço ABB TEC Servidor Workstation Nr. 1 Usando link do SCADA IEC 61850, DNP3 o IEC 60870 © ABB Group April 28, 2012 | Slide 48 Workstation Nr. n Instalación del Sistema en Transformador en Uso © ABB Group •| Slide 49 Instalación del Sistema en Transformador en Uso Transformador 3 Φ, S/N 60247, ABB Potencia: 300MVA Tensión: 230 / 138 / 13,8 kV © ABB Group •| Slide 50 Instalación del Sistema en Transformador en Uso Recepción de los Materiales © ABB Group •| Slide 51 Instalación de la Fibra óptica Instalación del Sistema en Transformador en Uso Instalación de la Fibra entre el Gabinete TEC y Sala de Control © ABB Group •| Slide 52 Instalación del Sistema en Transformador en Uso Gabinete del Trafo © ABB Group •| Slide 53 Conexión de la Fibra Installation in the Old Transformer Instalación del Gabinete TEC © ABB Group •| Slide 54 Instalación del Sistema en Transformador en Uso Instalación del Sensor de Gases © ABB Group •| Slide 55 Instalación del Sistema en Transformador en Uso Sensor Temperatura Aceite – PT100 Temperatura aceite - Bottom Temperatura aceite - Top © ABB Group •| Slide 56 Instalación del Sistema en Transformador en Uso Instalación Sensor Temperatura Ambiente ( Sol y Sombra) © ABB Group •| Slide 57 Instalación del Sistema en Transformador en Uso Pruebas y Comisionamiento © ABB Group •| Slide 58 Instalación del Sistema en Transformador en Uso © ABB Group •| Slide 59 Sistema listo y Operando © ABB Group •| Slide 60 Ejemplos de Analizador de Gases © ABB Group •| Slide 61 Ejemplos de Sensor de Bujes © ABB Group •| Slide 62 Ejemplos de Monitoreo Descarga Parciales © ABB Group •| Slide 63 Ejemplos de Monitoreo Temperatura directa del Bobinado © ABB Group •| Slide 64 Ejemplos de Monitoreo Temperatura directa del Bobinado © ABB Group •| Slide 65 Ejemplos de Monitoreo Temperatura directa del Bobinado © ABB Group •| Slide 66