CP1270 12V 7Ah(20hr)

Anuncio
CP1270
12V 7Ah(20hr)
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.
Battery Construction
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Copper
Fiberglass
Sulfuric acid
Performance Characteristics
General Features
●
●
●
●
●
●
●
●
Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.
Dimensions and Weight
151 / 5.94
65 / 2.56
93.5 / 3.68
100 / 3.94
2.32 / 5.12
93.5±1
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
Nominal Voltage
12V
Number of cell
6
Design Life
5 years
o
o
Nominal Capacity 77 F(25 C)
20 hour rate (0.35A, 10.5V)
7Ah
10 hour rate (0.68A, 10.5V)
6.8Ah
5 hour rate (1.13A, 10.5V)
5.65Ah
1 hour rate (4.56A, 9.6V)
4.56Ah
Internal Resistance
28mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o
o
105A(5s)
Max. Discharge Current 77 F(25 C)
Short Circuit Current
350A
Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation
77oF(25oC)
14.5-14.9V
2.8A
-30mV/oC
13.6-13.8V
-20mV/oC
Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V
5min 10min 15min 30min
29.1
27.5
26.0
24.4
22.8
18.4
17.5
16.7
15.7
14.8
14.8
14.2
13.6
13.0
12.4
8.30
7.90
7.62
7.24
7.03
1h
3h
5h
10h
20h
4.56
4.40
4.22
4.04
3.84
1.84
1.80
1.74
1.68
1.63
1.26
1.22
1.17
1.13
1.08
0.70
0.69
0.69
0.68
0.66
0.363
0.359
0.355
0.350
0.344
Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V
5min 10min 15min 30min 45min
52.0
49.4
46.9
44.5
41.6
35.1
33.3
31.6
29.8
28.0
27.5
26.5
25.4
24.3
23.3
15.2
14.6
14.0
13.4
12.9
11.50
11.00
10.50
10.10
9.75
1h
2h
3h
5h
8.97
8.59
8.23
7.99
7.62
5.06
4.94
4.80
4.65
4.50
3.59
3.50
3.40
3.30
3.19
2.33
2.29
2.25
2.21
2.15
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
page1 of 2
www.vision-batt.com
13.0
Voltage(v)
12V7Ah
Constant voltage charging
characteristic (0.25CA,25 oC)
(%) (XCA) (V)
140
12.0
120
0.25
100
0.20
11.0
10.0
80
9.0
60
8.0
40
0
Voltage
Discharge characteristic (25 OC)
Current
Charged
Volume
CP1270
0 1
3
2
5
min
20 30
10
60
2 3
5
h
10
0.15
20
0
0
20 30
Charged Volume
14.0
Charge Voltage
13.0
0.10
0.05
15.0
12.0
11.0
Charging Current
0
2
4
6
Discharge time
8
10
12
14
16
18
20
Charging time (hours)
Relationship between
charging voltage and temperature
Self-discharge characteristic
110
100
90
Cycl
15.0
e Us
Capacity(%)
Voltage(V)
15.6
e
14.4
S ta n d
13.8
by Use
80
70
60
o
o
C
o
C
C
50
13.2
40
-10
0
10
20
30
40
o
Ambient temperature( C)
50
0
60
2
4
6
8
10
12
14
16
18
20
Storage time: months
Cycle service life in relation to
depth of discharge
Life characteristics of Standby use
120
120
100
Capacity(%)
Capacity(%)
100
80
60
Testing conditions:floating voltage:2.27 to 2.30V Cell
o
o
ambient temperature: 25 C(77 F)
80
60
40
40
20
20
0
0
1
2
Life(year)
30% Depth of discharge
100% D.O.D. 50% D.O.D.
200
3
400
600
800
1000
1200
1400
Number of cycles(cycles)
Temperature effects on float life
Temperature effects on capacity
10
120
Capacity (%)
Life(years)
100
2.30V Cell
1
C
0 .0 5
0 .1 C
C
2
.
0
80
60
1 .0 C
2 .0 C
40
3 .0 C
20
0.1
10
20
30
40
50
0
-20
60
-10
0
10
20
30
40
o
Temperature( C)
THE INTERNATIONAL CERTIFICATION NETWORK
ISO9001:2000
MH25860
G4M19906-9202-E-16
www.vision-batt.com
Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail: [email protected]
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2003-9)
Page 2 of 2
50( oC)
Descargar